Loading...
HomeMy WebLinkAboutCALFIRE OVERHEAD SPRINKLER HYDRO TEST 8 7 2017'1?- IZo-o7-3 P6annizt FIRER MARIS it =CUR= DESIGN • INSTALLATION • INSPECTION • REPAIR • EXTINGUISHERS Rocklin Office: 4000 Alvis Ct., Rocklin, CA 95677 • Phone: (916) 663-3582 Chico Office: 170 Erma Ct, Chico, CA 95928 • Phone: (530) 826-3013 Greater Bay Area Office: 2280 Bates Ave, Ste_ A, Concord, CA 94520 • (925) 209-6164 Redding Office: 3092 Crossroads Dr_ Ste. 1, Redding, CA 96003 • Phone: (530) 223-2492 C.L. C16 *783132 & C10? 998I29 August 7, 2017 Butte County Fire - CALFIRE Administrative Office 176 Nelson Avenue Oroville, CA 95965 To Whom to May Concern; Enclosed is a copy of the Title 19 5 -year Fire Sprinkler Inspection Report for Berberian Nut located at 6100 Wilson Landing Rd. in Chico CA that was recently preform by Rick Zimmerman of Foothill Fire Protection. This property did not pass the inspection so we have given them a quote for corrections. After we have performed these corrections we will send you an updated inspection report. Please keep this copy for your records. If you have any questions or would like to speak to Rick regarding this report and its findings, please feel free to call our office at (530) 826-3013. Thank you Darci Peck Administrative Assistant dpeck@ffprotection.com Name: Address: City: ZIP: Contact: Telephone: Inspection, Testing, and Maintenance Cover Sheet NFPA25 as amended by CCR, Title 19 Berberian Nut Company 6100 Wilson Landing 95927 Occupancy/Use: Construction Type: No. Stories: Year Constructed: Office/Processing Plant Steel Taylor Bean (530) 343-5365 :rxr Name: Address: City: State: Telephone: CA License#: Job #: Performed by: Foothill Fire Protection, Inc. 170 Erma Ct Copy sent to: Owner Date: 07/31/17 J Fire AHJ ❑ Contractor (530) 826-3013 783132 6100WIL Rick Zimmerman Date: 07/31/17 NOTES: 1) For specific inspection, testing, and maintenance requirements and information, see NFPA 25, 2011 edition as amended by California Code of Regulations, Title 19, §901 to §906. 2) Inspection items may be performed by the owner in accordance with California Code of Regulations, Title 19, §904.1(a) fOr Yal Ala /4 Forms Included with this Report • Automatic Sprinkler System O Standpipe and Hose System O Private Water Supply System O Fire Pump O Water Storage Tank O Water Spray System O Foam Water Sprinkler System O Water Mist System NFPA 25 Chapter 5 6 7 8 9 10 11 12 arof7 Number of Forms N/A 4 0 0 0 0 0 0 0 Fail" Pass ❑ ❑✓ 0 Concerns that are Not Deficiencies (i.e. Non-Sprinklered Areas) ien and Comment"`'ct E ❑ Yes AES 1 September 3, 2013 Wet Pipe Fire Sprinkler System California Code of Regulations - Title 19 Inspection, Testing, and Maintenance Property Information Building Name Berberian Nut Company Address 6100 Wilson Landing City Chico Contact Person Taylor Bean 5 -Year Report 1 of 3 Contractor or Licensed Owner Information Name Foothill Fire Protection, Inc. License # 783132 ❑ SFM ❑✓ CSLB C-16 Address 170 Erma Ct City Chico St. CA Zip 95928 Phone Job # (530) 826-3013 6100WIL Misc. NNUAL Left Left Middle 3 2 4 2 109 113 8 45 2 Right Middle 6 2 113 25 45 4 Right 6 2 120 30 45 P P LI This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached: -Ye TTESTING A 1 d Annual ,:,. , ��d//G/ /l%,r ,. i„✓,,._., n , Gig , � ,i�,. G AN inspecttons, rests, ,. r,a„ . AINTENANCE and Maintenance f ,,, ��,,., ,,, ... P = Pass F = Fail N/A = Not Applicable = Inspection T = Test M = Maintenance 4!' Description NFPA 25CA ed. Reference��, 1 /f �� � Date i', 07/21/17 r O k , � 6i#Yi z \ m r, N/A ,„u,... P 1.1 I Control Valves — Identification Sign 13.3.1 1.2 I Control Valves — Inspection 13.3.2 5.2.5 07/21/17 07/21/17 P P 1.3 1 WaterflowAlarm Devices 1.4 1 Supervisory Devices 5.2.5 07/21/17 P 1.5 1 Gauges (Wet Pipe Systems) 5.2.4.1 07/21/17 P 1.6 I Hydraulic Design Information Sign (For Hydraulically Designed Systems) 5.2.6 07/21/17 P 1.7 '`:. 1 Enter Water Supply Pressure Below Riser Check 5.2.4.1 07/21/17 psi P Enter Water Supply Pressure Above Riser Check 5.2.4.1 07/21/17 psi P 1.9 Pressure Readings Acceptable 5.2.4.1 07/21/17 P 1.10 General Information Sign (Not Required for System Prior to 2007 Edition NFPA 13) 5.2.8 07/21/17 NA 1.11 Heat Tape 5.2.7 07/21/17 NA 1.12 Spare Sprinklers 5.2.1.4 07/21/17 P 1.13 Fire Department Connections 13.7 07/21/17 P 1.14 Alarm Valves — Exterior Inspection 13.4.1 07/21/17 P 1.15 1 Pressure Reducing Valves 13.5.1.1 07/21/17 NA 1.16 '` 1 Backflow Preventers 13.6.1 07/21/17 P Form AES 2.2 Sept. 3, 2013 - p California Wet Pipe ire Sprinkler System Code5 Year Regulations itle � - 2 of3� Inspection, Testing and Maintenance -,—' Property Information Building Name Berberian Nut Company Address 6100 Wilson Landing City Chico Contractor or Licensed Owner Information Name Foothill Fire Protection, Inc. Job # 6100WIL = Inspection T = TesM = Maintenance P = Pass F = Fail N/A ~ Not Applicable 1.17 / SmonHose conn0000no'Hose vo*o —'— 3.5.27/21/2017 13.5.51 N/A 1.18 | PRV — Fire Sprinkler Systems 13.5.1.1 7/31/2017 N/A 1.19 | Buildings (Freeze Protection) 4.1.1.1 7/21/2017 Owner's Responsibility p 1.20 1 Sprinklers 5.2.1 7/21/2017 F 1.21 1 Sprinklers Accessible Concealed Space 5.2.1.1.6 7/21/2017 N/A 1.22 | Pipe and Fittings 5.2.2 7/21/2017 P 1.23 | Pipe and Fittings - Accessible Concealed Space 5.2.2.3 7/21/2017 N/A 1.24 | Hangers 5.2.3 7/21/2017 F 1.25 | Hangers -Accessible Concealed Space 5.2.3.3 7/21/2017 N/A 1.26 | Seismic Braces 5.2.3 7/31/3017 P 1.27 | Seismic Braces - Accessible Concealed Space 5.2.3.3 7/31/2017 N/A 1.28 1 Unsprinklered Arao CFC 901.4 7/21/2017 aYoo NI No 2.1 T Field Service Test Required Send Repo*mF��Code O�o�/ 5.3.1 7/21/2017 nnsOu|nsosnt'p'u| mounso,orem'm*Uo,from until Lob N/A 2.2 T Recalled Sprinklers If not present = Pass; Ifpresent =Fail Title 19 904.1(o) 7/21/3017 P 2.3 T Water FIow Alarm Devices yusecs ma� Enter time 533 13.2.6 7/21/2017 1) 37sec o)eaec,o)4aoevsec. F 2.4 T Main Drain Test (Enterdata on Page 1 orthis form) � � 132 5 13.3.3.4 7/21/2017 P 2.5 T Control Valve - Position 13.3.3.2 7/21/2017 P 2.6 T Cuntm|Va|vo—Oporuuon 13.3.3.1 7/21/2017 P 2.7 T Supervisory Devices 13.3.3.5 7/21/2017 F 2.8 T Backflow ProvontorAssemblies 13.6.2 7/21/2017 P 2.9 T Small Hose Connections* w/PRV Hose Valves —Pa�io| Flow Test 13523 13.5.3.3 7/21/2017 N/A 2.10 T Pmv—Fire Sprinkler Systems 13.5.1.3 7/21/2017 N/A 2.11 T Pressure Gauges - Calibration 5.3.2 7/21/2017 New Gauges on risers 1, 2, &3 P 2.12 T Small Hose Connections* 13.5.6.2.2 7/21/2017 N/A * Small hose connections are hose valves and optional hose supplied by the fire sprinkler system.They do not include Class 1, 11, or 111 standpipe systems. Form AES 2.2 Sept. 3, 2013 et Pipe `ire SprtrxKKter System California Code ofRegulations r Title 19 Inspections Testing, and Maintenance 5 Year Report Property Information Building Name Berberian Nut Company 6100 Wilson Landing Chico I = Inspection M = Maintenance Contractor or Licensed Owner Information Name Job # Description PA 25 CA e+ Reference. Foothill Fire Protection, Inc. 6100WIL P = Pass F = Fail N/A = Not Applicable 3.1 3.2 M M Check Valves - Internal inspection Control Valves 13.4.2 13.3.4 07/21/17 07/21/17 P P tAj 3.3 3.4 3.5 M M M FDC - Backflush Internal Pipe Inspection - See Deficiencies and Comments Section for Results. Obstruction Investigation Required. If "Yes", See Deficiencies and Comments Section for Results 14.3.2.3 14.3.2.4 14.2 14.3 07/21/17 07/21/17 07/21/17 Yes No P N/A N/A 3.6 M System Returned to Service 4.5.3 07/21/17 Yes ri No P D = Deficiency C = Comment (Indicate type ) It t ' ji et Riser D X De �r ltd Comments indiic pp ttr tlot rt placed Owner maintains system, item 3.4 & 3.5 excluded. X Performed Five year Inspection in Accordance with CA NFPA 25 2.3 7-21-2017 4 X No alarm coverage on riser 4. System is not currently monitored. No alarm will sound/notify during the event of a fire 2.7 7-21-2017 4 X Control valve is not monitored. No signal will be received/reported of system valve is shut off 1.20 7-21-2017 1 X Sprinklers in break room bathrooms are corroded (x6). 1 sprinkler between bathroom entries corroded 1 sprinkler in bathroom in new office area painted 1.24 7-21-2017 2 X Two hangers on the 3" floater main have been disconnected from structure and are hanging from pipe Check here if additional Deficiencies and Comments are listed on Form AES 9. Number attached: E See Correction Form AES 10 for corrected deficiencies. Number attached: I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable except as noted in the "Deficiencies and Comments" section of this form. Print Name Signature Rick Zimmerman Tie, ?inzm., //o/r Date 07/31/17 Form AES 2.2 Sept. 3, 2013