August 7, 2017
Butte County Fire - CALFIRE
Administrative Office
176 Nelson Avenue
Oroville, CA 95965
To Whom to May Concern;
Enclosed is a copy of the Title 19 5 -year Fire Sprinkler Inspection Report for Berberian Nut located at
6100 Wilson Landing Rd. in Chico CA that was recently preform by Rick Zimmerman of Foothill Fire
Protection. This property did not pass the inspection so we have given them a quote for corrections.
After we have performed these corrections we will send you an updated inspection report.
Please keep this copy for your records. If you have any questions or would like to speak to Rick
regarding this report and its findings, please feel free to call our office at (530) 826-3013.
Thank you
Darci Peck
Administrative Assistant
dpeck@ffprotection.com
Name:
Address:
City:
ZIP:
Contact:
Telephone:
Inspection, Testing, and Maintenance Cover Sheet
NFPA25 as amended by CCR, Title 19
Berberian Nut Company
6100 Wilson Landing
95927
Occupancy/Use:
Construction Type:
No. Stories:
Year Constructed:
Office/Processing Plant
Steel
Taylor Bean
(530) 343-5365
:rxr
Name:
Address:
City:
State:
Telephone:
CA License#:
Job #:
Performed by:
Foothill Fire Protection, Inc.
170 Erma Ct
Copy sent to:
Owner Date: 07/31/17
J Fire AHJ
❑ Contractor
(530) 826-3013
783132
6100WIL
Rick Zimmerman
Date: 07/31/17
NOTES:
1) For specific inspection, testing, and maintenance
requirements and information, see NFPA 25, 2011
edition as amended by California Code of Regulations,
Title 19, §901 to §906.
2) Inspection items may be performed by the owner in
accordance with California Code of Regulations, Title 19,
§904.1(a)
fOr
Yal Ala /4
Forms Included with this Report
• Automatic Sprinkler System
O Standpipe and Hose System
O Private Water Supply System
O Fire Pump
O Water Storage Tank
O Water Spray System
O Foam Water Sprinkler System
O Water Mist System
NFPA 25
Chapter
5
6
7
8
9
10
11
12
arof7
Number of Forms N/A
4
0
0
0
0
0
0
0
Fail" Pass
❑
❑✓
0 Concerns that are Not Deficiencies (i.e. Non-Sprinklered Areas)
ien
and Comment"`'ct
E
❑ Yes
AES 1
September 3, 2013
Wet Pipe
Fire Sprinkler System
California Code of Regulations - Title 19
Inspection, Testing, and Maintenance
Property Information
Building Name
Berberian Nut Company
Address
6100 Wilson Landing
City
Chico
Contact Person
Taylor Bean
5 -Year
Report
1 of 3
Contractor or Licensed Owner Information
Name
Foothill Fire Protection, Inc.
License # 783132
❑ SFM
❑✓ CSLB C-16
Address
170 Erma Ct
City
Chico
St. CA
Zip 95928
Phone
Job #
(530) 826-3013
6100WIL
Misc.
NNUAL
Left
Left Middle
3 2
4 2
109
113
8
45
2
Right Middle
6
2
113
25
45
4
Right
6
2
120
30
45
P
P
LI This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached:
-Ye TTESTING
A 1 d Annual
,:,. , ��d//G/ /l%,r ,. i„✓,,._., n , Gig , � ,i�,.
G AN
inspecttons, rests,
,. r,a„ .
AINTENANCE
and Maintenance f
,,, ��,,., ,,, ...
P = Pass F = Fail N/A = Not Applicable
= Inspection T = Test M = Maintenance
4!'
Description
NFPA 25CA
ed.
Reference��,
1 /f
�� � Date
i',
07/21/17
r O k ,
� 6i#Yi z
\
m
r, N/A
,„u,...
P
1.1 I
Control Valves — Identification Sign
13.3.1
1.2 I
Control Valves — Inspection
13.3.2
5.2.5
07/21/17
07/21/17
P
P
1.3 1
WaterflowAlarm Devices
1.4 1
Supervisory Devices
5.2.5
07/21/17
P
1.5 1
Gauges (Wet Pipe Systems)
5.2.4.1
07/21/17
P
1.6 I
Hydraulic Design Information Sign
(For Hydraulically Designed Systems)
5.2.6
07/21/17
P
1.7 '`:. 1
Enter Water Supply Pressure Below Riser Check
5.2.4.1
07/21/17
psi
P
Enter Water Supply Pressure Above Riser Check
5.2.4.1
07/21/17
psi
P
1.9
Pressure Readings Acceptable
5.2.4.1
07/21/17
P
1.10
General Information Sign
(Not Required for System Prior to 2007 Edition NFPA 13)
5.2.8
07/21/17
NA
1.11
Heat Tape
5.2.7
07/21/17
NA
1.12
Spare Sprinklers
5.2.1.4
07/21/17
P
1.13
Fire Department Connections
13.7
07/21/17
P
1.14
Alarm Valves — Exterior Inspection
13.4.1
07/21/17
P
1.15 1
Pressure Reducing Valves
13.5.1.1
07/21/17
NA
1.16 '` 1
Backflow Preventers
13.6.1
07/21/17
P
Form AES 2.2
Sept. 3, 2013
-
p
California Wet Pipe
ire Sprinkler System
Code5 Year
Regulations itle � - 2 of3�
Inspection, Testing and Maintenance -,—'
Property Information
Building Name Berberian Nut Company
Address
6100 Wilson Landing
City
Chico
Contractor or Licensed Owner Information
Name
Foothill Fire Protection, Inc.
Job #
6100WIL
= Inspection
T = TesM = Maintenance
P = Pass F = Fail N/A ~ Not Applicable
1.17
/
SmonHose conn0000no'Hose vo*o
—'— 3.5.27/21/2017
13.5.51
N/A
1.18
|
PRV — Fire Sprinkler Systems
13.5.1.1
7/31/2017
N/A
1.19
|
Buildings (Freeze Protection)
4.1.1.1
7/21/2017
Owner's Responsibility
p
1.20
1
Sprinklers
5.2.1
7/21/2017
F
1.21
1
Sprinklers Accessible Concealed Space
5.2.1.1.6
7/21/2017
N/A
1.22
|
Pipe and Fittings
5.2.2
7/21/2017
P
1.23
|
Pipe and Fittings - Accessible Concealed Space
5.2.2.3
7/21/2017
N/A
1.24
|
Hangers
5.2.3
7/21/2017
F
1.25
|
Hangers -Accessible Concealed Space
5.2.3.3
7/21/2017
N/A
1.26
|
Seismic Braces
5.2.3
7/31/3017
P
1.27
|
Seismic Braces - Accessible Concealed Space
5.2.3.3
7/31/2017
N/A
1.28
1
Unsprinklered Arao
CFC 901.4
7/21/2017
aYoo
NI No
2.1
T
Field Service Test Required
Send Repo*mF��Code O�o�/
5.3.1
7/21/2017
nnsOu|nsosnt'p'u|
mounso,orem'm*Uo,from until
Lob
N/A
2.2
T
Recalled Sprinklers
If not present = Pass; Ifpresent =Fail
Title 19
904.1(o)
7/21/3017
P
2.3
T
Water FIow Alarm Devices
yusecs ma� Enter time
533
13.2.6
7/21/2017
1) 37sec o)eaec,o)4aoevsec.
F
2.4
T
Main Drain Test
(Enterdata on Page 1 orthis form)
� �
132 5
13.3.3.4
7/21/2017
P
2.5
T
Control Valve - Position
13.3.3.2
7/21/2017
P
2.6
T
Cuntm|Va|vo—Oporuuon
13.3.3.1
7/21/2017
P
2.7
T
Supervisory Devices
13.3.3.5
7/21/2017
F
2.8
T
Backflow ProvontorAssemblies
13.6.2
7/21/2017
P
2.9
T
Small Hose Connections*
w/PRV Hose Valves —Pa�io| Flow Test
13523
13.5.3.3
7/21/2017
N/A
2.10
T
Pmv—Fire Sprinkler Systems
13.5.1.3
7/21/2017
N/A
2.11
T
Pressure Gauges - Calibration
5.3.2
7/21/2017
New Gauges on risers 1, 2, &3
P
2.12
T
Small Hose Connections*
13.5.6.2.2
7/21/2017
N/A
* Small hose connections are hose valves and optional hose supplied by the fire sprinkler system.They do not include Class 1, 11, or 111
standpipe systems.
Form AES 2.2
Sept. 3, 2013
et Pipe
`ire SprtrxKKter System
California Code ofRegulations r Title 19
Inspections Testing, and Maintenance
5 Year
Report
Property Information
Building Name Berberian Nut Company
6100 Wilson Landing
Chico
I = Inspection
M = Maintenance
Contractor or Licensed Owner Information
Name
Job #
Description
PA 25 CA e+
Reference.
Foothill Fire Protection, Inc.
6100WIL
P = Pass F = Fail N/A = Not Applicable
3.1
3.2
M
M
Check Valves - Internal inspection
Control Valves
13.4.2
13.3.4
07/21/17
07/21/17
P
P
tAj
3.3
3.4
3.5
M
M
M
FDC - Backflush
Internal Pipe Inspection - See Deficiencies and
Comments Section for Results.
Obstruction Investigation Required. If "Yes", See
Deficiencies and Comments Section for Results
14.3.2.3
14.3.2.4
14.2
14.3
07/21/17
07/21/17
07/21/17
Yes
No
P
N/A
N/A
3.6
M
System Returned to Service
4.5.3
07/21/17
Yes
ri No
P
D = Deficiency C = Comment (Indicate type )
It t '
ji et
Riser
D
X
De �r ltd Comments
indiic pp ttr tlot rt placed
Owner maintains system, item 3.4 & 3.5 excluded.
X
Performed Five year Inspection in Accordance with CA NFPA 25
2.3
7-21-2017
4
X
No alarm coverage on riser 4. System is not currently monitored. No alarm will sound/notify during the event of a fire
2.7
7-21-2017
4
X
Control valve is not monitored. No signal will be received/reported of system valve is shut off
1.20
7-21-2017
1
X
Sprinklers in break room bathrooms are corroded (x6). 1 sprinkler between bathroom entries corroded
1 sprinkler in bathroom in new office area painted
1.24
7-21-2017
2
X
Two hangers on the 3" floater main have been disconnected from structure and are hanging from pipe
Check here if additional Deficiencies and Comments are listed on Form AES 9. Number attached:
E See Correction Form AES 10 for corrected deficiencies. Number attached:
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by
the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable
except as noted in the "Deficiencies and Comments" section of this form.
Print Name
Signature
Rick Zimmerman
Tie, ?inzm., //o/r
Date 07/31/17
Form AES 2.2
Sept. 3, 2013