Loading...
HomeMy WebLinkAbout047-070-105VINCI & ASSOCIATES 61ruclural Cnyineers September 16, 2014 Alternative Energy Systems P.O. Box 9231 Chico, CA 95927 Subject: Review of minimum footing requirements Project: (168) Module Photovoltaic Groundmount Installation (1 Array) Burch Creek - County Line Highway 99 E, Chico, CA 95973 V&A Project No. 12-3457 The purpose of this report is to provide a site specific analysis of the minimum footing requirements for the photovoltaic array groundtrac installation at Highway 99 E in Chico, CA 95973. Based upon our review of the 1 Photovoltaic Array, installed 4 modules high and 42 modules wide. The PV Array shall have a transverse spacing of approximately 8.42 feet on center and a longitudinal spacing of 8.00 feet maximum. Based upon a wind speed of 100 mph, Exposure C, it was determined that the Krinner KSF PV M24/PV T 76x1600 ground screw is sufficient for the applicable horizontal and vertical wind loading. Refer to attached calculations and details for additional information. Our professional services have been performed using the degree of care and skill ordinarily L exercised under similar circumstances by reputable engineers practicing in this locality. No other warranty, expressed or i ied, is made as to the professional options included in this report. We hope this prov' es ou with the information you need at this time. Please call us if you have any queen �earding this report. Sincerely, o Qsw Ess VINCI IATES No. 5441,1 Exp. 12/31/�1�5 ciJa n, S.E. of CAY " � � P Z �1 � 2 ce se No. S-4411 VV - -- REVIEWED FOR CO E COMPLIANCE DATE ( BY 175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360 p805.496-2100 'f805.496-2442 • e vinci@vincise.com oAtE: 9/16/2014 VINCI & ASSOCIATES SHEET: Al PROJECT: Burch Creek - County Line 61ruclural Cngineers JOB No.: 12-3457 Highway 99 E 175 E. WILBUR ROAD, STE 103 - THOUSAND OAKS, CA 91360 ENGR.: JRV Chico, CA 95973 p805.496.2100 • f805.496.2442 • evinci@VinciSE.com CLIENT: Alternative Energy Systems DESIGN DATA: WIND DESIGN CRITERIA: BASIC WIND SPEED = 100 mph WIND EXPOSURE = C GROUND SNOW LOAD = 0 psf SOLAR MODULE ARRAY DATA Sloped Dimension of Array = 170.68 in Angle of Array = 20 degrees Slope of Array: _. 4.10 :12 No. of Modules in Transverse Direction = 4 No. of Modules in Longitudinal Direction 42 Total No. of Modules in Project = 168 Transverse Post Spacing = 8.42 ft Longitudinal Post Spacing = 8.00 ft Number of supports - Transverse Direction = 2 Diameter of Pier Footing = 3 in Number of Arrays = 1 Array Uniform Load = 2.8 psf SOIL DESIGN CRITERIA (Based upon Chapter 18 of CBC) Allowable Soil Bearing Pressure = 1500 psf Allowable Soil Lateral Bearing = 200 pcf Allowable Shaft Skin Friction = 200 pcf V'INCI s ASSOCIATES WIND TO BOTTOM, 7 = 0' WIND TO TOP, 7 = 180' couw�a a,a .o. PROJECT: Buch Creek - y Count Line PAGE: A2 C CLIENT: Highway 99 E, Chico, CA 95973 - DESIGN BY: JRV �...:,._,:.. JOB NO.: 11-3457 _ r DATE : 09/16/14 REVIEW BY: Wi d'Analysts,for 0aen Stru'c"ture'(Sol'a'rzPd"nels)�Bised.o ASCE17w057,IBCi2009',/ CBCf2OI0 / ASCE 7-10 / CBC 2013 ............. INPUT DATA WIND TO BOTTOM, 7 = 0' WIND TO TOP, 7 = 180' CLEAR FLOW OBSTRUCTED CLEAR FLOW OBSTRUCTED Exposure category (B, c or o) = A C -1.46 \ Importance factor, pg 73, (0.87, 1.0 or 1.15) 1 = 1.70 1.00 Category II Basic wind speed (3 sec. gust wind) V = -22.88 100 mph 23.69 Topographic factor (Sec.6.5.7.2, pg 26 & 45) KA = -16.48 1.00• Flat Height of mean roof h = -1.33 8 ft 0.38 -0.87 Roof slope B -2.16 4.10 : 12 -0.76 f,,,2Jse'd) Roof length L = -0.14 10 ft -33.94 -2.44 Roof horizontal projected width B = 31.55 10 ft -2.28 Effective area of component / cladding A = -0.13 10 ft 2 a roe DESIGN SUMMARY 1. Main Wind -Force Resisting System Max horizontal force / base shear from roof Max vertical download force Max vertical uplift force Max moment at centroid of base from roof 2. Component and Cladding Elements Max inward pressure Max net outward pressure ANALYSIS Velocity pressure 0.86 kips + 0.09 kips (eave & columns increasing) E 0.95 kips = 2.52 kips 2.33 kips = 9.54 ft -kips + 0.95 ft -kips (eave & columns increasing) £ 10.50 ft -kips = 63 psf = 67 psf qh = 0.00256 Kh K:t Kd V21 = 18.50 psf where: qh = velocity pressure at mean roof Leight, h. (Eq. 6-15, page 27) Kh = velocity pressure exposure coefficient evaluated at height, h, (Tab. 6-3, Case 1,pg 79) = 0.85 Kd = wind directionality factor. (Tab. 6-4, for building, page 80) = 0.85 h = height of mean roof = 8.00 ft Main Wind -Force Resistinq System (Sec. 6.5.13.2) p=ghGCN F=PAf where: G = gust effect factor. (Sec. 6.5.8, page 26). = 0.85 0 = roof angle = 18.88 degree < 45 deg. [Satisfactory] Ar = roof actual area. = 52.8 ft2, windward 52.8 ft2, leeward CN = net force coefficients. (Fig. 6-18A, page 66) Check Fig. 6-18A limitation h / B = 0.80 within [0.25 , 1.0] [Satisfactory] 0 WIND TO BOTTOM, 7 = 0' WIND TO TOP, 7 = 180' CLEAR FLOW OBSTRUCTED CLEAR FLOW OBSTRUCTED CASE CNw Cnn CNw Crn CNw Crn CNw CNS A -1.21 -1.46 -1.31 -1.60 1.51 1.70 0.45 -1.05 p (psf) -19.03 -22.88 -20.55 -25.21 23.69 26.78 7.10 -16.48 18.88 F (kips) -1.01 -1.21 -1.09 -1.33 1.25 1.42 0.38 -0.87 B -2.16 -0.16 -2.20 -0.76 2.01 0.65 1.25 -0.14 p (psf) -33.94 -2.44 -34.64 -11.87 31.55 10.25 19.68 -2.28 F (kips) -1.79 -0.13 -1.83 1 -0.63 1 1.67 1 0.54 1.04 1 -0.12 DATE: 9/16/2014 / VINCI S ASSOCIATES SHEET: A3 PROJECT: Burch Creek - County Line cif chiral Cn9ineers JOB NO.: 09-3457 Highway 99 E 175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360 ENGR.: JRV Chico, CA 95973 p805.496.2100 • f805.496.2442 • evinci@VinciSE.com CLIENT: Alternative Energy Systems FOOTING DESIGN - Skylight Diagonal Dimension: 170.68 in TYPICAL ARRAY Skylight Angle: 20 degrees Post Spacing: 8.00 ft No. of Supports: 2 Footing Diameter (d): 3 in MAXIMUM VERTICAL FORCE: 2.52 k / (10.0 x 10.0 ) = 25.24 psf MAXIMUM UPLIFT FORCE: 2.33 k / (10.0 x 10.0 ) = 23.26 psf GROUNDTRAC SYSTEM CAST INTO EARTH Maximum Vertical Load: P = 25.24 psf + 2.8 psf DL + 0 psf Snow = 28.04 psf P = 28.037 psf x ( 160 " /12"/ft) x ( 96.0 " /12"/ft) = 2998 lbs for 2 Supports P = 1499 lbs/footing KRINNER SOLAR GROUND SCREW 1498.9 lbs << 7875 lbs Therefore O.K. Maximum Uplift Load: P = 23.26 psf - 2.8 psf DL = 20.46 psf P = 20.458 psf x ( 160 " /12"/ft) x ( 96.0 " /12"/ft) = 2188 lbs for 2 Supports P = 1094 lbs/footing KRINNER SOLAR GROUND SCREW 1093.8 lbs << 4838 lbs Therefore O.K. DATE: 9/16/2014 VINCI & ASSOCIATES SHEET: A4 PROJECT: Burch Creek - County Line cSlruclura/ Cnyineers JOB NO.: 09-3457 Highway 99 E 175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360 ENGR.: SRU Chico, CA 95973 p 805.496.2100 • f 805.496.2442 • e vinci@VinciSE.com CLIENT: Alternative Energy Systems DESIGN OF PIER FOOTING & POST CHECK I WIND Post Spacing: 8.00 ft Number of Columns: 2 Horizontal Load: 9.5 psf Exposed wind surface 4 ft -DESIGN BASED UPON NON -CONSTRAINED CBC FORMULA: (CBC Section 1805.7.2.1) d = (A/2) (1 + ( 1 + (4.36h/A) )^.5)) D DESIGN COLUMN h d A = (2.34*P)/(S1 *b) P = 152 lbs h = 5.5 ft = 9.5 psf x 8.0 ft x 4 ft / 2 columns (Average Height) M.I = Ph = 836 ft -lbs < 3246 ft -lbs (Krinner Ground ScrE Scol = Mcol / Fb = 0.30 in3 Fb = 0.66 x 50,000 psi »»> USE: 1-1/2" Schedule 40 Pipe S = 0.31 in with KSF PV M24/PV T 76x1600 Ground Screw 100% j 95% 90% 85% 80% 75% SUNPOWER OFFERS THE BEST COMBINED POWER AND PRODUCT WARRANTY POWER WARRANfiY.,-- PRODUCT WARRANTY 5• DF-VEL.0P-1A rNT SERVICES , FOR t sm P civ r9 0 5 10 15 20 25 Years More guaranteed power: 95% for first 5 years, -0.4x,6/yr. to year 25.8 ELECTRICAL DATA Max load E20 -327 -COM E19 -310 -COM Nominal Power" (Pnom) 327 W 310 W Power Tolerance +5/-3% +5/-3% Avg. Panel EfficienCy13 20.A% 19.3% Rated Voltage (Vmpp) 54.7 V 54.7 V Rated Current (Impp) 5.98 A 5.67 A Open -Circuit Voltage (Voc) 64.9 V 64.4 V Short -Circuit Current (ISC) 6.46 A 6.05 A Maximum System Voltage 1000 V UL; 1000 V IEC Maximum Series Fuse 20A Power Temp Coef. (Pmpp) —0.38% / aC Voltage Temp Coef. (Voc) —176.6 mV / aC Current Temp Coef. (Isc) 3.5 mA / aC REFERENCES: 1 Al comparisons are SPR -E20-327 vs. a representative conventional panel: 240W, approx. 1.6 m7, 15% efficiency. 2 PVEvolution Labs "SunPower Shading Study," Feb 2013. 3 Typically 7-9% more energy per watt, BEW/DNV Engineering "SunPower Yield Report," Jan 2013. ' 4 SunPower 0.255/o/yr degradation vs. 1.0a/o/yr cony: panel. Campeau, Z. et al. "SunPower Module Degradation Rate," SunPower white paper, Feb 2013; Jordan, Dirk "SunPower Test Report, • NREL, Oct 2012. 5 "SunPower Module 40 -Year Useful Life" SunPower white paper, Feb 2013. Useful life is 99 out of 100 panels operating at more than 70% of rated power. 6 Out of all 2600 panels listed in Photon International, Feb 2012. 7 8% more energy than the average of the top 10 panel companies tested in 2012 (151 panels, 102 companies), Photon International, March 2013. 8 Compared with the top 15 manufacturers. SunPower Warranty Review, Feb 2013. 9 Some exclusions apply. See warranty for details. 10 5 of top 8 panel manufacturers were tested by Fraunhofer ISE, "FV Module Durability Initiative Public Report, • Feb 2013. 11 Compared with the non -stress -tested control panel. Atlas 25+ Durability test report, Feb 2013. 12 Standard Test Conditions (1000 W/m' irradiance, AM 1.5, 25" C). 13 Based on average of measured power values during production. Traditional I I i 0 5 10 15 20 25 Years Combined Power and Product Defect 25 year coverage that includes panel replacement costs. s OPERATING CONDITION AND MECHANICAL DATA Temperature — 40aF to +185aF (— 40aC to +85aC) Max load Wind: 50 psf, 2400 Pa, 245 kg /M2 front & back Snow: 112 psf, 5400 Pa, 550kg/m2 front Impact resistance 1 inch (25 mm) diameter hail at 52 mph (23 m/s) Appearance Class B Solar Cells 96 Monocrystalline Maxeon Gen 11 Cells Tempered Glass High Transmission Tempered Anti -Reflective Junction Box IP -65 Rated Connectors MC4 Compatible Frame Class 2 silver anodized Weight Al lbs (18.6 kg) —r 1046mm 7[41.2in] 46mm [1.81in]�r1559mm [61.4in] See htto://www.sunpowercorp.com/facts for more reference information. For further details, see extended datasheet: www.sunoowercorp.com/datasheets Read safety and installation instructions before using this product. Designed in California t ® March 2013 SunPower Corporation. All rights reserved. SUNPOWER, the SUNPOWER logo, MA%EON, MORE ENERGY. FOR LIFE., and SIGNATURE are trademarks or registered trademarks of su n powereorp. com Sump— Corporation. Specifications included in this datasheet are subject to change without notice. Document H 505701 Rem A /LTR_EN TESTS AND CERTIFICATIONS Standard tests UL 1703, IEC 61215, IEC 61730 Quality tests ISO 9001:2008, ISO 14001:2004 EHS Compliance ROHS, OHSAS 18001:2007, lead-free Ammonia test IEC 62716 Salt Spray test IEC 61701 (passed maximum severity) PID test Potential -Induced Degradation free: l OOOV 10 Available listings CEC, JET, KEMCO, MCS, FSEC, CSA, UL, TUV —r 1046mm 7[41.2in] 46mm [1.81in]�r1559mm [61.4in] See htto://www.sunpowercorp.com/facts for more reference information. For further details, see extended datasheet: www.sunoowercorp.com/datasheets Read safety and installation instructions before using this product. Designed in California t ® March 2013 SunPower Corporation. All rights reserved. SUNPOWER, the SUNPOWER logo, MA%EON, MORE ENERGY. FOR LIFE., and SIGNATURE are trademarks or registered trademarks of su n powereorp. com Sump— Corporation. Specifications included in this datasheet are subject to change without notice. Document H 505701 Rem A /LTR_EN Absolute Maximum Open Circuit Voltage 600 VDC 1000 VDC i Operating Voltage Range 180-580 VDC 260-580 VDC 300.900 VDC fAPPT Input Voltage Range 300.540 VDC 300.550 VDC 480-800 VDC 500.800 VDC MPPTrackers 2 with 4 -fused inputs per tracker Maximum Operating Input Current 2x 25A 2x 35A 2x 27 A 2x 32 A Strike Voltage 300V 330 V Nominal Output Voltage 208 VAC, 3 -Ph 480 VAC, 3 -Ph AC Voltage Range (Standard) -12%/.10% Continuous Output Power (VAC) 14 kW 20 kW 23 kW 28 kW Continuous Output Current (VAC) 39A 27.3 A 32A 39A Maximum Backfeed Current 0 A Nominal Output Frequency 60 Hz Output Frequency Range 57.63 Hz 59.3.60.5 Hz 57.63 Hz Power Factor Unity, >0.99 Total Harmonic Distortion (THD) (3% Peak Efficiency 96.9% 97.4% 98.4% CEC Efficiency 96.0% 97.0% 98.0% Tare Loss c 4 W c 2 W 8 Fused Positions (4 positions per MPPT) 15 A (fuse by-pass available) Ambient Temperature Range -130F to +140°F (-25°C to +60°C) -13°F to +140°F (-25°C to +60°C) Derating occurs over +50°C Derating occurs over +45°C Storage Temperature Range -22°F to +158°F (-30°C to +70°C) Relative Humidity (non -condensing) 0-95% Optional SolrenView Web -based Monitoring Integrated Optional Revenue Grade Monitoring External ) External Communication Interface RS485 Modbus RTU Safety Listings & Certifications UL 1741/IEEE 1547, IEEE 1547.1, CSA C22.2#107.1, FCC part 15 B Testing Agency i ETL CSA Standard 10 year Optional 15, 20 year; extended service agreement AC/DC Disconnect Standard, fully -integrated 41.6x21.4x8.5in. 39.4 x 23.6 x 9.1 in. Dimensions (H x W x D) (1057 x 543 x 216 mm) (1000 x 600 x 230 mm) Weight 141 lbs (64 kg) 132 lbs (60 kg) 122 lbs (55 kg) Enclosure Rating Type 4 Enclosure Finish Polyester powder coated aluminum SOLECTRIA RE N EWA B LES www.solectria.com I inverters@solectria.com 1 978.683.9700 ffl INNER The Ground Screw Technical Data Sheet G Series Basic Info Nominal length (mm) 2100 1600 1300 Tube diameter (mm) 76.10 76.10 76.10 Weight (kg) 14.00 10.50 8.50 Item number 25456 25455 25454 Construction • Nut: DIN EN ISO 4032 - 8 • Continuous welded helix • Coating: Hot -dip galvanized according to DIN EN ISO 1461 PERMIT # ho( y �� BUTTE COUNTY DEVEI..OPb1EPiT -F ERViCES R` ,VIEWE - DATE t �S7 Z�- 'r3Y i KSF G 76x 1300-3xM16 Subject to technical change! efficient • no concrete • durable Krinner Schraubfundamente GmbH I Passauer Strane 55 1 D-94342 Strankirchen Phone: +49 9424 9401-80 1 E -Mail: service@krinner.com I www.krinner.com J!;J KR I N N ER The Ground Screw Technical Data a Length (mm) (±25 mm) 208_0 1580 12_80 b _ _ _ Shaft outer diameter (mm)� _ _ + 7_6.10 76.10 ! 76.10 c inner diameter (mm) 68.90 68.90 68.90 `d Diameter setting (mm) 60 60. 60 e Depth setting (mm) (_25 mm) 1815 1315 1020 If Thread 3xM16 �3xM16 ^� 3xM16 f b a Online Service Webkey G2545611D a .II II G25455110 G2545411D R1 a o, a a � a PERMIT# BUTTE COUNrr DEVELOPMENT SERVICES IEWED FOR �, . Subject to technical change! ;ODE CPLIANCE Krinner Schraubfundamente GmbH I Passauer Strane 55 1 D-94342 Strankirchen DATE_ 3� �%v BY C-.,, Phone: +49 9424 9401-80 1 E -Mail: service@krinner.com I www.krinner.com Customer Name: Burch CreekCounty Line Panel Specifications Customer Address: Highway 99 E, Chico , CA 95973 Manufacturer: Sunpower Model: SPR -E20=327 -COM Service Panel Bus Bar Rating: 200 A PV Pmax: 327 W Length: 61.4 inches Service Panel AC paramters: 480 V Vmpp: 54.7 V Width: 41.2 inches Total Solar AC System Size: 53200 W Voc: 64.9 V Weight: 41 lbs Min Service Panel CB Size: 100 A f11, n7 Impp: 5.98 A Voc %Temp: 0.0027 V Area Lowest Temp: -11 °C Isc: 6.46 A Voc Temp: 0.1766 V Inverter I Manufacturer Solecria Inverter I Manufacturer Solecria h "A" ' Inverter Model PVI-23TL 480V "B" Inverter Model PVI-23TL 480V Inverter Output Power 26600 W Inverter Output Power 26600 W Inverter Imax 32.0 A Min CB Sizer -7490A Inverter Imax 32.0 A Min CB Size _40 A f3 6f Strings of 14 Actual CB Sizel 401A Strings of F-141 Actual CB Size 461A Voltage 480 VAC Voltagel 480 VAC Array String Array String DC Operating Voltage 1 765.80J 765.80 VDC DC Operating Voltage 765.80 765.80 VDC P DC Max Voltage 1000.08 1000.08 VDC DC Max Voltage 1000.08 1000.08 VDC f8 DC Operating Current 35.88J 5.98 A DC Operating Current 35.88 5.98 A f9 DC Short Circuit Current 38.76 6.46 A DC Short Circuit Current 38.76 6.46 A flo PERMIT 9 Y /1/- u `S� QL+TTL ,OUNTV DEVELQP viEiJT SERVICES REVIEWED FOR CODE COMPLIANCE DATE /_2 Y Notes Formulas n , NEC, Annex C, Annex C Table C rf sc x x of series panes in series x vmpp n2, Conduit fill, NEC Table 310.15(B)(2)(a) f2, Isc x 1.25/Conduit fill x (Ambient Temp - Sunlight Exposure Correction f8,k of series panels x ((26C + Record Low Celcius x panel Voc temp Coef n3, Temp correction, NEC Table 310.16 Factor) + Voc)) n4, DC Resistance, NEC Chapter 9 Table 8 f3, Inverter Imax x 1.25 f9,tt of strings x Impp - n5, AC resistance, NEC Chapter 9 Table 9 f4, Inverter Imax x 1.25/Conduit fill x (Ambient Temp - Sunlight Exposure f10,# of strings xlsc n6, NEC Article 310.15 Correction Factor) f11,Bus Bar or conductor rating x 1.2 - Sum of all Input Breakers <or= Bus n7, NEC Article 690.8(B)(1) f5, Tolerance % x V/D x I x.2 bar or conductor rating x 1.2 n8, Sunlight Exposure,NEC Table, 310.15(B)(2)(c) f6, .2 x D x I x R/V DC Circuit Ampacity Calcalator Wire Note: F 1 Descripition: Module to INVERTER 10 Minimum Wire and Conduit Size based on Voltage drop and Amacity: 6.461A Isc/A Number of Strings 6.46 A Circuit Amps 17.40 A Ampacity After Derat 10 Wire Size based on Ampacity 30 A 0.4454. % of V drop 10 Wire Size based on Voltage Drop 30 A 17.40 A Minimum Conductor Ampacity Based on Conditions of Use A Minimum Conductor Ampacity Based on 1.56 Rule Conditions of Use 0.464 Derate Total �70 "C Temp Coef (ambient+Sunlight) 70 T Ambient Temp none Sunlight Exposure 4 Number of Current Carrying Conductors Voltage Drop. Allowable Tolerance I% 158 F 0.58 Derate 158 F 32 F 0 °C Temp adder 0.8 Derate applied to Temp Coeficient 54.7 V Vmp/Volts 14 Panels in Series 5.98 A Imp/Amps 765.8 V Circuit Voltage 5.98 A Circuit Amps 230 ft One way distance 101 Wire Size 1.24 Resistance 0.4454 % of loss Conduit Size 171 Conduit Type 0.2661000 VoltConduit Size 0.864 Conduit Internal Diameter AC Circuit Ampacity Calcalator Job Name: BURCH CREEK FARMS COUNTY LINE Meter #: 1004538571 Location: kN/A Wire Note: JAC- I _ Descripition: Inverter to DISTRIBUTION PANEL 26.592 kWatts 480 VAC Delta Voltage Configuration 8 Minimum Wire Size based on Voltage drop and Amacity: 39.98033• A Minimum Circuit Breaker/Fuse Size 39.98033 A Min Ampacity 8 Wire Size based on Ampacity 55 A 0.103949 % of Drop 8 Wire Size based on Voltage Drop 55 A 31.98427 A Circuit Ampacity 1.732 Factor Phases 0.82 Conditons of Use Derate Factor 39.00521A Minimum Conductor Ampacity Based on Conditions of Use 39.980331A Minimum Conductor Ampacity Based on 1.25 Rule Conditions of Use 50 "C Ambient Temp 122 F 0.82 Derate Total none Sunlight Exposure 32 F Adder 0 °C 3 or less Number of CCC Factor 1 Derate applied to Temp Coef 50 'C Temp Coeficient (ambient+Sunlight) 0,82 Voltage Drop: Allowable Tolerance (Solar Generation I %/ Distribution3%) A ft One way distance �8Wire Size 0.78 Resistance 0.103949 % of lossV Circuit Voltage L� 31.9842667 A Circuit Amps Conduit Size EATT Conduit Type 0.255 600 Volt 11.82% 1 Conduit Size .0.86J Conduit Internal Diameter AC Circuit Ampacity Calcalator Job Name: BURCH CREEK FARMS COUNTY LINE Meter #: 1004538571 Location: N/A Wire Note: AC -1 Descripition: Inverter to DISTRIBUTION PANEL 53.184 kWatts 480 VAC Delta Voltage Configuration 4 Minimum Wire Size based on Voltage drop and Amacity: 79.96067 A Minimum Circuit Breaker/Fuse Size 79.96067 A Min Ampacity 4 Wire Size based on Ampacity 95 A 0.082626 % of Drop 4 Wire Size based on Voltage Drop 95 A 63.96853 A Circuit Ampacity 1.732 Factor 31 Phases 0.82 Conditons of Use Derate Factor 78.01041 A Minimum Conductor Ampacity Based on Conditions of Use M960671A Minimum Conductor Ampacity Based on 1.25 Rule Conditions of Use 50 T Ambient Temp 122 F 0.82 Derate Total none Sunlight Exposure 32 F Adder 0 °C 3 or less Number of CCC Factor 1 Derate applied to Temp Coef gp °C Temp Coeficient (ambient+Sunlight) .0,82 Voltage Drop. Allowable Tolerance (Solar Generation 1 %/ Distribution3%) 10 ft One way distance 41 Wire Size 0.31 Resistance 0.082626 % of loss 480 V Circuit Voltage �J 63.9685333 A Circuit Amps Conduit Size 1:71 ConduitType 0.335' 600 VoltConduit Size 1.237 Conduit Internal Diameter ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH THE 2011 NATIONAL ELECTRIC CODE (NEC), OR LOCAL MUNICIPAL CODE, AND FIRE DISTRICT REGULATIONS. 1. ALL EQUIPMENT SHALL BE LISTED AND LABELED PER RECOGNIZED ELECTRICAL TESTING LABORATORY AN INSTALLED PER THE LISTING REQUIREMENTS AND THE MANUFACTURER'S INSTRUCTIONS. 2. ALL INVERTERS SHALL BE IEEE 929 COMPLIANT AND SHALL BE INSPECTED BY LOCAL UTILITY BEFORE COMMISSIONING, TESTING, AND OPERATION OF THE SYSTEM. 3. ALL OUTDOOR EQUIPMENT SHALL BE MINIMUM NEMA 3R, INCLUDING OUTDOOR MOUNTED TRANSITION BOXES, COMBINER BOXES, AND SWITCHES. 4. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED PER THE REQUIREMENTS OF NEC ART.250,690. 19.INSTALLATION OF PV PANEL ARRAYS SHOULD RESIST SLIDING AND POP-UP RESULTING FROM SEISMIC EVENTS AND SHOULD COMPLY WITH CBC SECTION 1613A AND ASCE STANDARD 7-05, CHAPTER 13. 20.PV SYSTEM INSTALLER WILL BE RESPONSIBLE FOR FURNISHING AND INSTALLATION OF ALL RELATED EQUIPMENT, CABLES, ADDITIONAL CONDUITS, BOXES WIREWAYS AND OTHER ACCESSORIES NECESSARY FOR COMPLETE AND OPERATIONAL PHOTOVOLTAIC SYSTEMS. 21.PV SYSTEM CONTRACTOR SHALL COORDINATE ALL THE WORK WITH THE ENGINEER, THE CONSTRUCTION MANAGER AND ALL OTHER CONTRACTORS TO ENSURE THAT PV SYSTEM IS INSTALLED AS SPECIFIED IN THESE DRAWINGS. 22.DRAWING IN GENERAL OR DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF THE EQUIPMENT AND WORK INCLUDED. THE INTENTION OF THE DRAWING IS TO INDICATE SIZE, CAPACITY, APPROXIMATE LOCATION AND GENERAL RELATIONSHIP, BUT NOT EXACT DETAIL OR PHYSICAL PLACEMENT. 5. NEC. ART. 690.9(A). ALL CIRCUITS CONNECTED TO MORE THAN ONE SOURCE SHALL HAVE OVERCURRENT DEVICES LOCATED SO AS TO PROVIDE 23.FIELD VERIFIES EXACT AIC RATING REQUIRED OF THE MAIN SWITCHBOARD OVERCURRENT PROTECTION FROM ALL SOURCES. FROM LOCAL UTILITY. 6. NEC ART. 690.18. DUE TO THE FACT THAT PV MODULES ARE ENERGIZED 24.A PV SYSTEM WITH MULTIPLE INVERTERS, WHERE INVERTERS ARE WHENEVER THEY ARE EXPOSED TO LIGHT, PV CONTRACTOR SHALL DISABLE REMOTELY LOCATED FROM EACH OTHER, WILL HAVE A DIRECTORY THE ARRAY DURING INSTALLATION AND SERVICE BY SHORT CIRCUITING, CREATED FOR EACH LOCATION. AS PER 2011 NEC 690.5(H) AND IN OPEN CIRCUITING, OR COVERING THE ARRAY WITH AN OPAQUE ACCORDANCE WITH 2011 NEC 705.10. COVERING. 7. PHOTOVOLTAIC SYSTEM SHALL BACKFEED THE DISTRIBUTION SYSTEM ON SITE PER THE REQUIREMENTS OF NEC ART.690.64(B). ALL BACKFEED BREAKERS SHALL BE IDENTIFIED AS SUCH AND SHALL BE SECURED IN PLACE BY ADDITIONAL FASTENER PER THE REQUIREMENTS OF NEC 408.16(F) (408.36 IN 2011 NEC. 8. FALL ARREST PROTECTION PER OSHA REQUIREMENTS SHALL BE PROVIDED FOR ALL ROOF WORK. 9. ALL CONDUCTORS AND TERMINATIONS SHALL BE RATED FOR 75° C MINIMUM. 10.NEC ART. 690.14. - SEE SHEET RE -4.3 FOR LABEL DIAGRAM 11.NEC ART. 690.53. - SEE SHEET RE -4.3 FOR LABEL DIAGRAM 12.NEC ART. 690.17. EACH AC DISCONNECT SHALL ALSO BE LABELED WITH: "WARNING! -ELECTRICAL SHOCK HAZARD - DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND LOAD SIZE MAY BE ENERGIZED IN THE OPEN POSITION". 13.DC DISCONNECT ATTHE INVERTER WILL BE READILY ACCESSIBLE AFTER THE INSTALLATION IS COMPLETE PER 2011 NEC ART. 690.17 WHERE TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN POSITION. PROVIDE A WARNING SIGN OF THE HAZARDS PER 2011 NEC ART.690.17 14.CONTRACTOR TO PROVIDE GROUND FAULT PROTECTION FOR ROOF MOUNTED PHOTOVOLTAIC ARRAYS LOCATED ON DWELLINGS PER 2011 NEC ART.690.17. 15. WHERE MORE THAN ONE NOMINAL VOLTAGE SYSTEM EXIST, THE DIFFERENT SYSTEMS SHALL BE IDENTIFIED BY PHASE AND SYSTEM PER 2011 NEC ART.210.41D 16.PROVIDE AN ACCESSIBLE DISCONNECT DEVICE THAT IS LOCKABLE IN OPEN POSITION AND IS LOCATED WITHIN 10'-0" OF THE METER PER LOCAL ELECTRICAL UTILITY REGULATIONS. 17.PHOTOVOLTAIC SOURCE CURRENTS MUST BE RATED AT BOTH 125% OF THE PARALLEL MODULE AND AT A CONTINUOUS LOAD OF ANOTHER 125% FOR ATOTAL OF 156%OFTHE LOAD. I PROJECT OWNER: PAGE # CONTENT BURCH CREEK - COUNTY LINE I HIGHWAY 99 E PV -1.0 SCOPE CHICO, CA 95973 PV -2.0 SITE PLAN APN#:047.070.105.000 PV -2.1 UNDERGROUND SITE PLAN PV -3.0 ARRAY LAYOUT CONTRACTOR: PV -4.0 ELECTRICAL DIAGRAM PV -4.1 MONITORING DIAGRAM PV -4.2 LABEL DIAGRAM I ALTERNATIVE ENERGY SYSTEMS INC. PV -5.0 RACKING DETAILS MAIL TO: PO BOX 9231 ATTACHMENT MODULE SPECS CHICO, CA 95927 INVERTER SPECS PHYSICAL: 13620 HWY 99 WIRE CALCS CHICO, CA 95973 CSLB 853351 C-10, C-46 I SCOPE: BUILDING JURISDICTION: INSTALL GROUND MOUNTED BUTTE COUNTY PHOTOVOLTAIC SOLAR SYSTEM AND DEPT. OF DEVELOPMENT SERVICES UPDATE ELECTRICAL EQUIPMENT AS NEEDED IN ACCORDANCE WITH ALL 7 COUNTY CENTER DRIVE APPLICABLE BUILDING CODES OROVILLE, CA 95965 SPECIFICALLY REFERENCING THE 2013 OFFICE#: (530) 538-7601 CALIFORNIA ELECTRICAL CODE/ 2011 FAX#: (530) 538-2140 BUTTE NEC USING THE FOLLOWING SPECIFIC INSPECTION LINE: (530) 538-4365 REQUESTS PHONED IN BY 2PM WILL BE INgQY EQUIPMENT: THE NEXT BUSINESS DAY SEP 17 2014 I MODULES: SUNPOWER I (168) SPR -E20 -327 -COM PERMIT # DEVELOPMENT I 54.94kW SYSTEM BUTS -E COON i Y _Q�VPI..Oi,MSNT SERVICES SERVICES I 3, 025 SQFT COVER I INVERTER(S): SOLECTRIA CODE q_ xll'wcc, " �0R ` 1 0 1 LIANCE B �l 1 _ `'I 1 (2) PVI-23TL 480V DATE I 5 a jO11 BY � P-ROJ-ECT INFORMATION 18.PROVIDE PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION I (i OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC I I SYSTEM DISCONNECT MEANS IF THEY ARE NOT IN THE SAME LOCATION I I t PER 2011 NEC ART.690.56. REVISION o= DoCh 0 nLD mN LA in Q1 R N G1 � m c m Q' oNi v N Q Om DO f0 rn v v o 0 CO a Ln O=r 0 CL U d LL .0 W _ Z J } H z O o U mo LL a) o tll LuCnQlO Q O UQU� =�O0 U=U:m 2 a m2UQ SCALE NTS DRW By AW DATE 09/12/2014 SHEET GENERAL NOTES 3 I LOCATION MAP N2 SITE MAP Z PV -1.0 NITSINTS SCOPE r-1 LE!§i7 <��--ry REVISION E 0 Y w O DO 0 n l0 tD m N EA m 01 C N N Ln mrn c N 01N cn v (V Q Om DO N 01 V L O mo u aLn@J 0 = 0 X 0 auCi- Ei c LLJ Z J F— Z Z) O OU m o W al O IJ1 T --I LTJ 07 Ol O } Q O UQU� =�60 U=Vii m2Ua SCALE NTS ORw BY AW DATE 09/12/2014 SHEET PV -2.0 SITE FLAN p Z 's ., - \_ HIGH WAY 99 E J PhonCHICe(530) 345 6980 01 C " a z •N CH ICO CA 95973 148Boom Fax(530) 892, CA 95927 2360 a APN#:047.070.105.000 Alternative Energy Systems Inc. info@solarenergyforlife.com 4 iv -IF AF ir a i` a e 4OF FIRST RAIL--- m m O 0. — — — — x - r•S& REVISION A E n 0 41 W 00 Q Q I 2'.7j- kq N u1 m 16. '"I m m ^4 ami N Q m OO iO Z, o, U Eno 0 co Li c Ln@) t C 40F DOST o a° ., n m e v ,n n m m a • „ ':: .. m. .. .. $ .. ,. .. $ n n a a U LL V � � C O N 1 ` ai ® >- %A A No. 44 1 cl a, P. 1 /31/ w` w e� � a 8. 5,14 STRUC U L ONLY VINCI & SII 0 C I A T E S C31rucfu #yineers 175 E. WILBUR ROAD, SUITE 103 - I OUSAND OAKS, CA 91360 P - 805.496.2100 f- 805.49ciSE.com J } Z 0 p U Mo W0)O--------------------------------------------------------- - --- ---- Y r- i U.J cy) STRING LAYOUT } Q o UQU� PERMIT #U = U BUTTE COU-iTY DEVSLOPMZN T SERVICES REVIEWED FOR CC) z u a DATE 4-0 "— y NTS DRW 0 AW '6ATI7— 09/12/2014 SHEET PV -3.0 ARRAY LAYOUT ARRAY LAYOUT MATERIALS MID CLAMPS END CLAMPS RAILS U -BOLTS SQUARE FOOTAGE RAIL UNION 252 168 (84) 174" 168 3,025 SQ. FT. 0 FTGS & T'S HORIZ. PIPE VERT. PIPE SHORT VERT. PIPE LONG PIPE UNION ENDCAPS 56 (18)24' (28) 5' (28) 8' 16 4 e� � a 8. 5,14 STRUC U L ONLY VINCI & SII 0 C I A T E S C31rucfu #yineers 175 E. WILBUR ROAD, SUITE 103 - I OUSAND OAKS, CA 91360 P - 805.496.2100 f- 805.49ciSE.com J } Z 0 p U Mo W0)O--------------------------------------------------------- - --- ---- Y r- i U.J cy) STRING LAYOUT } Q o UQU� PERMIT #U = U BUTTE COU-iTY DEVSLOPMZN T SERVICES REVIEWED FOR CC) z u a DATE 4-0 "— y NTS DRW 0 AW '6ATI7— 09/12/2014 SHEET PV -3.0 ARRAY LAYOUT ARRAY LAYOUT (84) PV MODULES �1 I SUINPOWER:SPR-E20-327-COM (6) STRINGS OF (14) I I 600VOC I 1 I I 6 I I 1a I I I I I I DC -1 (3) 1" EMT w/ (4) #10 PV -WIRE CU. & -----------"—(1) #10 THWN-2 CU. GRD. WIRE RUN: 230' IMP: 17A r— (84) PV MODULES �11 SUINPOWER: SPR -E20327 -COM (6) STRINGS OF (14) I I I 6 I 14 1 I I I I I I DC -1 (3) 1" EMT w/ (4) #10 PV -WIRE CU. & --'----------(1) #10 THWN-2 CU. GRD. WIRE RUN: 230' IMP: 17A INVERTER "A" 26.59kW GRIDTIED INVERTER 32A/ 3P/ 480V SOLECTRIA: PVI-23TL 480V W/ INTEGRATED DC DISC. - INVERTER INVERTER "B" 26.59kW GRID TIED INVERTER 32A/ 3P/ 48OV SOLECTRIA: PVI-23TL 480V w/ INTEGRATED DC DISC. -_ INVERTER 3 L AC -C- 1 (2) 1" EMT EACH w/ ' (4) #8 THWN-2 CU. & (1) #8 THWN-2 CU. GRD. WIRE RUN: 10' IMAX: 40A AC DISTRIBUTION PANEL 300A/3P/480V _Ll _1-2 -L3 i AC -2 (1) 11/4" PVC w/ '(3) #4 TH W N-2 CU. & (2) #8 THWN-2 CU. GRD./NEU WIRE RUN: 100' IMAX: SOA 100A� I 10OA/3P/600V SQUARE D: D323NRB NEW GREENFIELD METER (GENERATION ONLY) 100A/3P/480V METER AC -3 (1) 1" EMT w/ (4) #3 THWN-2 CU. & (1) #8 THWN-2 CU. GRD. WIRE RUN: 100' IMAX: SOA UTILITY CONNECTION POINT AT SEALABLE 1 -BOX ABOVE NEW METER (E) AC SERVICE PANEL 200A/3P/480V. METER #1004538571 200 A 480 VAC 3 PHASE L2 L3 REVISION E O L3 w o = 00 `O ON r1O`�° m ONY RN N Ln m �In in N Q 00 m Ol U to O O °O c Ln m @! 0 =L � c n U a m . c O � a Y d W A N W C W 42 m S. (COMPLY WITH 2013 CALIFORNIA ELECTRICAL j CODE.- ARTICLE 890.70 (E), 408.38(D) find 705.1200 I Lit REQUIREMENTS FOR IN&Y-GitelVonnected . Z E/ectdc Power.Production,syvtems J Z o O o U m o UJ 0)Iji C)o LI w�a)o PERMIT # oC�Qo Q U�U� - euTr1 couN r r;tv�,l_0p14E,IrSERI/IGEs 2 0 OU �t��IC btco I g- R u = CODE,0;!5alo m 2 U Q DATE �2�/� 13Y. -J SCALE NTS DRW BY AW DATE 09/12/2014 SHEET PV -4.0 ELECTRICAL SINGLE LINE DIAGRAM ELECTRICAL SINGLE LINE 120 VAC 120 VAC DECK MONITORING BROADBAND ROUTER GATEWAY DECK ALL -IN -ONE -BOX COMMUNICATION CARD A INVERTER A COMMUNICATION CARD B INVERTER B SOURCE INTERNET COMMUNICATION CARD C INVERTER C PERMIT # bbl -Wo BUTTE COUNTY DEVE"LOPAAIENT SERVICES a ?—'a �Yn e""'c REVISION v 0 0o m 02 N LA M tko� Ln N W LA M C M 010 `1 N Q m W N M x LA i O ED u c Ln 0 = L x 0 CL V d LL .0 Li J C L N wIA A W d w a W Z J Z ° mo Iwo w�0,o }ao U a U =�po U=Uit Inn 2 U Q CODE ap�l L—�r i5t.. ,it ��Ljj,,,,jj''�u I-�,j1 l SCALE NTS ' 4d"WDE 0.% Y'.GO LIANCE ORW BY AW DATE _ jo fa�T BY v DATE 09/12/2014 SHEET PV -4.1 MONITORING SINGLE LINE DIAGRAM NTS MONITORINGSINGLELINE ARRAY COMBINER INVERTER I CAUTION:SOLAR Installed on all DC conduit every 10' and on both sides of any penetration. O SUB PANEL NEC 690.54, Interactive Point of Interconnection AC DISC. MAIN SERVICE 0 WARNING Dual Power'Supply Photovoltaic NEC 705.10, Point of Connection, Located On Main Service Panel. REVISION - .R 'NN EL ONLY! . Installed at all Electrical 1\ PHOTOVOLTAIC SYSTEM Installed on all DC Junction boxes Distribution Panel covers that DISCONNECT provide a path from PV to Utility z _. NEC 690.14, Disconnection Means, _j_ PHOTOVOLTAICUSCONNECTAt - -• CUUlt RRENT the single AC Disconnect or Main 7 SHORT - ENT A Breaker. o o o ELECTRIC SHOCK - .L • - - • • • - : • m w ^ gyri A GROUND FAULT IS INDICATED, MAX SYSTEM VOLTAGE 600 VDC -i NORMALLYIF -. . . CONDUCTORS MAY BE UNGROUNDED . . WARNING SHOCK-. .. not touch terminalsTerminals of both line and-_ _ SOLARU��o W a) Q1 0 . Q r: Per 690.5(C), Warning Shock_ ... side .. .. .. Relocate �t p o Hazard. Included on all PV NEC 690.14, Solar Disconnect Solar Breaker Label @ Any breaker ovc (Dz disconnects. on the front of all PV DC passing Bi -Directional Power m = u a Disconnects. Filled out in # PERMIT ruTTE GOUrJiY t,�VELCPPA^eNT SERVICES SCALE accordance with NEC 690.55 rt�,�pj�IEWED FOR NT DPW BY C0 Lr.) T,./9,MPLIANCE DATE AW r , DATE J '�+ BY c/ 09/12/2014 SHEET ` PV -4.2 LABEL DIAGRAM -- LABEL DIAGRAM I . F S/ �oqv_ �Z 0.411 F 1 / 1/15 'req l TUR �Q V OF CA t ^ 1.. 3" STRUCT L ONLY • 11,ABLETRAY", `' 1 V N y p I 1 ' ii A S CA T EIS i SOLAR MODULE ( .61ruchiLra/ 11 IL2 S s p STRUT PER PLAN _ 175 E. WILBUR ROAD, SUITE 103 - THOUSAND AKS, CA 91360 ALL WIRES TO BE RUN - P- 805.496.2100 f- 805.496.2442 e - Vinci@VinciSE.com - - INSIDE RACK AND CABLE TRAY I TO AVOID EASY ACCESS POST * . ' CONSTRUCTION TYPICAL HORIZONTAL MEMBER: oo� 1 1/2" HOLLAENDER "T', TYP. T CABLE TRAY TOP AND BOTTOM CABLE TRAY DETAIL 4 • NTS GM1 GM4 J END CAP- _ 11' 0 SCHED.40 - P. PIPE \ GALV- PIPE UNION STRUT PER PLAN * 1}"O SCHED.40 / GALV- PIPE 30" INBED MIN, TYP. UNO 1 J_ 2 \ TY CALU-BOLTASSENIBLY 1/2" HOLLAENDER T A . TYPICAL PROSOLAR GROUND MOUNT RAIL TO PIPE DETAIL 3 NT ti GM3 I RACKS & MODULES PER PLAN 8"X8"X6" NEI ENCLOSURE REVISION 11'0 SCHED. 40 GALV. PIPE, TYP. U.O.N. 1" METALLIC FLEX 8"X8"X6" NEI ENCLOSURE ' A 3/8 -16 x1 STAINLESS HEX WASHER HD TYPE F SELF TAPPING E PRE W/ 5/16" �, TYP. 1 Z" 0 SCHED. 40 a E GALV. PIPE, TYP. U.O.N. 0000 am o w GROUNDING ELECTRIC ry I m m CONDUCTOR cn m m N w m m a rn v I "[II`- !l l I - -- I l ll- Il1-1f 1T1 iT` IIF Tti=1 T11=11=1 l f' I[f=1TL l (yil ii1�17= Nam °° 0 W1=:; 11=LLI 1 1=1 m u cu 0 0 _ TSI I I I a o @� 1: i -iTC= m u o X a I I l= T- I CI I - I I C� I= -I a -T I U- I I� ` =11 I- I I 11=1 I CI I- I I d v a i -jjT - I I I F�If-1 1 �llll 1111I'I r 11= - I I I I-1 I -I' I I I I 11= i I --J -I I —i�i TYPICAL J BOX. AT BACK OF ARRAY E y • NT SOLAR MODULE STRUT PER PLAN i SEE SECTION 4 FOR ADI INI 170.6$r� l-1/2" HOLLAENDER "T; TYP. f � a» TYPICAL HORIZONTAL MEMBER: 11}"OSCHED. 40 ki " _GALV. PIPE, TYP. LINO t 'CABLE TRAY TOP AND BOTTOM Lu • . 4 �� � TYPICAL POSTS: Z 1 20° 1},.O SCHED 40 GALV. PIPE, TYP. UNO. = O O M O & 16f A w w, y j TYPICAL FOOTING: KRINNER I W^ 0 try�Aq - t. fj� SOLAR GROUND SCREW Y O W 11 111 Ill 11 El: LY } Q O 1 LI `4 UQ U� Is � vI0cfz °C=Uz < MIT # ��l Z _ BUTTE OUNTY DEVELOPMENT SERVICES _ REVIEWED FOR °o = U Q CODE COMPLIANCE SCAB NTS BY Ram AW LDATE v 1.8'-5" 09/12/2014 S E CTI O N SHEET 17 NT PV -5.0 RAKING DETAIL RACgNG DETAIL