HomeMy WebLinkAbout047-070-105VINCI & ASSOCIATES
61ruclural Cnyineers
September 16, 2014
Alternative Energy Systems
P.O. Box 9231
Chico, CA 95927
Subject: Review of minimum footing requirements
Project: (168) Module Photovoltaic Groundmount Installation (1 Array)
Burch Creek - County Line
Highway 99 E, Chico, CA 95973
V&A Project No. 12-3457
The purpose of this report is to provide a site specific analysis of the minimum footing
requirements for the photovoltaic array groundtrac installation at Highway 99 E
in Chico, CA 95973.
Based upon our review of the 1 Photovoltaic Array, installed 4 modules high and 42
modules wide. The PV Array shall have a transverse spacing of approximately 8.42 feet
on center and a longitudinal spacing of 8.00 feet maximum. Based upon a wind speed
of 100 mph, Exposure C, it was determined that the Krinner KSF PV M24/PV T 76x1600
ground screw is sufficient for the applicable horizontal and vertical wind loading.
Refer to attached calculations and details for additional information.
Our professional services have been performed using the degree of care and skill ordinarily
L
exercised under similar circumstances by reputable engineers practicing in this locality. No
other warranty, expressed or i ied, is made as to the professional options included in this
report. We hope this prov' es ou with the information you need at this time. Please call us
if you have any queen �earding this report.
Sincerely, o Qsw Ess
VINCI IATES No. 5441,1
Exp. 12/31/�1�5
ciJa n, S.E. of CAY
"
�
�
P Z
�1
� 2
ce se No. S-4411
VV - -- REVIEWED FOR
CO E COMPLIANCE
DATE ( BY
175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360
p805.496-2100 'f805.496-2442 • e vinci@vincise.com
oAtE: 9/16/2014 VINCI & ASSOCIATES SHEET: Al
PROJECT: Burch Creek - County Line 61ruclural Cngineers JOB No.: 12-3457
Highway 99 E 175 E. WILBUR ROAD, STE 103 - THOUSAND OAKS, CA 91360 ENGR.: JRV
Chico, CA 95973 p805.496.2100 • f805.496.2442 • evinci@VinciSE.com
CLIENT: Alternative Energy Systems
DESIGN DATA:
WIND DESIGN CRITERIA:
BASIC WIND SPEED =
100
mph
WIND EXPOSURE =
C
GROUND SNOW LOAD =
0
psf
SOLAR MODULE ARRAY DATA
Sloped Dimension of Array =
170.68
in
Angle of Array =
20
degrees
Slope of Array: _.
4.10
:12
No. of Modules in Transverse Direction =
4
No. of Modules in Longitudinal Direction
42
Total No. of Modules in Project =
168
Transverse Post Spacing =
8.42
ft
Longitudinal Post Spacing =
8.00
ft
Number of supports - Transverse Direction =
2
Diameter of Pier Footing =
3
in
Number of Arrays =
1
Array Uniform Load =
2.8
psf
SOIL DESIGN CRITERIA (Based upon Chapter 18 of CBC)
Allowable Soil Bearing Pressure =
1500
psf
Allowable Soil Lateral Bearing =
200
pcf
Allowable Shaft Skin Friction =
200
pcf
V'INCI s ASSOCIATES
WIND TO BOTTOM, 7 = 0'
WIND TO TOP, 7 = 180'
couw�a a,a .o.
PROJECT:
Buch Creek - y Count Line
PAGE: A2
C
CLIENT:
Highway 99 E, Chico, CA 95973
-
DESIGN BY: JRV
�...:,._,:..
JOB NO.:
11-3457 _ r DATE : 09/16/14
REVIEW BY:
Wi d'Analysts,for 0aen Stru'c"ture'(Sol'a'rzPd"nels)�Bised.o ASCE17w057,IBCi2009',/ CBCf2OI0
/ ASCE 7-10 / CBC 2013 .............
INPUT DATA
WIND TO BOTTOM, 7 = 0'
WIND TO TOP, 7 = 180'
CLEAR FLOW OBSTRUCTED CLEAR FLOW OBSTRUCTED
Exposure category (B, c or o)
=
A
C
-1.46
\
Importance factor, pg 73, (0.87, 1.0 or 1.15)
1 =
1.70
1.00
Category II
Basic wind speed (3 sec. gust wind)
V =
-22.88
100
mph
23.69
Topographic factor (Sec.6.5.7.2, pg 26 & 45)
KA =
-16.48
1.00•
Flat
Height of mean roof
h =
-1.33
8
ft
0.38
-0.87
Roof slope
B
-2.16
4.10
: 12
-0.76
f,,,2Jse'd)
Roof length
L =
-0.14
10
ft
-33.94
-2.44
Roof horizontal projected width
B =
31.55
10
ft
-2.28
Effective area of component / cladding
A =
-0.13
10
ft 2
a roe
DESIGN SUMMARY
1. Main Wind -Force Resisting System
Max horizontal force / base shear from roof
Max vertical download force
Max vertical uplift force
Max moment at centroid of base from roof
2. Component and Cladding Elements
Max inward pressure
Max net outward pressure
ANALYSIS
Velocity pressure
0.86 kips
+ 0.09 kips (eave & columns increasing)
E 0.95 kips
= 2.52 kips
2.33 kips
= 9.54 ft -kips
+ 0.95 ft -kips (eave & columns increasing)
£ 10.50 ft -kips
= 63 psf
= 67 psf
qh = 0.00256 Kh K:t Kd V21 = 18.50 psf
where: qh = velocity pressure at mean roof Leight, h. (Eq. 6-15, page 27)
Kh = velocity pressure exposure coefficient evaluated at height, h, (Tab. 6-3, Case 1,pg 79) = 0.85
Kd = wind directionality factor. (Tab. 6-4, for building, page 80) = 0.85
h = height of mean roof = 8.00 ft
Main Wind -Force Resistinq System (Sec. 6.5.13.2)
p=ghGCN
F=PAf
where: G = gust effect factor. (Sec. 6.5.8, page 26). = 0.85
0 = roof angle = 18.88 degree
< 45 deg. [Satisfactory]
Ar = roof actual area. = 52.8 ft2, windward
52.8 ft2, leeward
CN = net force coefficients. (Fig. 6-18A, page 66)
Check Fig. 6-18A limitation h / B = 0.80 within [0.25 , 1.0] [Satisfactory]
0
WIND TO BOTTOM, 7 = 0'
WIND TO TOP, 7 = 180'
CLEAR FLOW OBSTRUCTED CLEAR FLOW OBSTRUCTED
CASE CNw Cnn CNw Crn CNw Crn CNw CNS
A
-1.21
-1.46
-1.31
-1.60
1.51
1.70
0.45
-1.05
p (psf)
-19.03
-22.88
-20.55
-25.21
23.69
26.78
7.10
-16.48
18.88
F (kips)
-1.01
-1.21
-1.09
-1.33
1.25
1.42
0.38
-0.87
B
-2.16
-0.16
-2.20
-0.76
2.01
0.65
1.25
-0.14
p (psf)
-33.94
-2.44
-34.64
-11.87
31.55
10.25
19.68
-2.28
F (kips)
-1.79
-0.13
-1.83
1 -0.63 1
1.67
1 0.54
1.04 1
-0.12
DATE: 9/16/2014 / VINCI S
ASSOCIATES SHEET: A3
PROJECT: Burch Creek - County Line cif chiral Cn9ineers JOB NO.: 09-3457
Highway 99 E 175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360 ENGR.: JRV
Chico, CA 95973 p805.496.2100 • f805.496.2442
• evinci@VinciSE.com
CLIENT: Alternative Energy Systems
FOOTING DESIGN - Skylight Diagonal Dimension:
170.68 in TYPICAL ARRAY
Skylight Angle:
20 degrees
Post Spacing:
8.00 ft
No. of Supports:
2
Footing Diameter (d):
3 in
MAXIMUM VERTICAL FORCE: 2.52 k
/ (10.0 x 10.0 ) = 25.24 psf
MAXIMUM UPLIFT FORCE: 2.33 k
/ (10.0 x 10.0 ) = 23.26 psf
GROUNDTRAC SYSTEM CAST INTO EARTH
Maximum Vertical Load:
P = 25.24 psf + 2.8 psf DL + 0
psf Snow = 28.04 psf
P = 28.037 psf x ( 160 " /12"/ft) x ( 96.0 "
/12"/ft) = 2998 lbs for 2 Supports
P = 1499 lbs/footing
KRINNER SOLAR GROUND SCREW
1498.9 lbs << 7875 lbs
Therefore O.K.
Maximum Uplift Load:
P = 23.26 psf - 2.8 psf DL = 20.46 psf
P = 20.458 psf x ( 160 " /12"/ft) x ( 96.0 " /12"/ft) = 2188 lbs for 2 Supports
P = 1094 lbs/footing
KRINNER SOLAR GROUND SCREW
1093.8 lbs << 4838 lbs
Therefore O.K.
DATE: 9/16/2014 VINCI & ASSOCIATES SHEET: A4
PROJECT: Burch Creek - County Line cSlruclura/ Cnyineers JOB NO.: 09-3457
Highway 99 E 175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360 ENGR.: SRU
Chico, CA 95973 p 805.496.2100 • f 805.496.2442 • e vinci@VinciSE.com
CLIENT: Alternative Energy Systems
DESIGN OF PIER FOOTING & POST CHECK I WIND
Post Spacing: 8.00 ft
Number of Columns: 2
Horizontal Load: 9.5 psf
Exposed wind surface 4 ft
-DESIGN BASED UPON NON -CONSTRAINED CBC FORMULA:
(CBC Section 1805.7.2.1)
d = (A/2) (1 + ( 1 + (4.36h/A) )^.5))
D
DESIGN COLUMN
h
d
A = (2.34*P)/(S1 *b)
P = 152 lbs
h = 5.5 ft
= 9.5 psf x 8.0 ft x 4 ft / 2 columns
(Average Height)
M.I = Ph = 836 ft -lbs < 3246 ft -lbs (Krinner Ground ScrE
Scol = Mcol / Fb = 0.30 in3 Fb = 0.66 x 50,000 psi
»»> USE: 1-1/2" Schedule 40 Pipe S = 0.31 in
with KSF PV M24/PV T 76x1600 Ground Screw
100% j
95%
90%
85%
80%
75%
SUNPOWER OFFERS THE BEST COMBINED POWER AND PRODUCT WARRANTY
POWER WARRANfiY.,-- PRODUCT WARRANTY
5• DF-VEL.0P-1A rNT SERVICES
, FOR t
sm P
civ r9
0 5 10 15 20 25
Years
More guaranteed power: 95% for first 5 years, -0.4x,6/yr. to year 25.8
ELECTRICAL DATA
Max load
E20 -327 -COM E19 -310 -COM
Nominal Power" (Pnom)
327 W 310 W
Power Tolerance
+5/-3% +5/-3%
Avg. Panel EfficienCy13
20.A% 19.3%
Rated Voltage (Vmpp)
54.7 V 54.7 V
Rated Current (Impp)
5.98 A 5.67 A
Open -Circuit Voltage (Voc)
64.9 V 64.4 V
Short -Circuit Current (ISC)
6.46 A 6.05 A
Maximum System Voltage
1000 V UL; 1000 V IEC
Maximum Series Fuse
20A
Power Temp Coef. (Pmpp)
—0.38% / aC
Voltage Temp Coef. (Voc)
—176.6 mV / aC
Current Temp Coef. (Isc)
3.5 mA / aC
REFERENCES:
1 Al comparisons are SPR -E20-327 vs. a representative conventional panel: 240W,
approx. 1.6 m7, 15% efficiency.
2 PVEvolution Labs "SunPower Shading Study," Feb 2013.
3 Typically 7-9% more energy per watt, BEW/DNV Engineering "SunPower Yield Report,"
Jan 2013. '
4 SunPower 0.255/o/yr degradation vs. 1.0a/o/yr cony: panel. Campeau, Z. et al.
"SunPower Module Degradation Rate," SunPower white paper, Feb 2013; Jordan, Dirk
"SunPower Test Report, • NREL, Oct 2012.
5 "SunPower Module 40 -Year Useful Life" SunPower white paper, Feb 2013. Useful life
is 99 out of 100 panels operating at more than 70% of rated power.
6 Out of all 2600 panels listed in Photon International, Feb 2012.
7 8% more energy than the average of the top 10 panel companies tested in 2012 (151
panels, 102 companies), Photon International, March 2013.
8 Compared with the top 15 manufacturers. SunPower Warranty Review, Feb 2013.
9 Some exclusions apply. See warranty for details.
10 5 of top 8 panel manufacturers were tested by Fraunhofer ISE, "FV Module Durability
Initiative Public Report, • Feb 2013.
11 Compared with the non -stress -tested control panel. Atlas 25+ Durability test report,
Feb 2013.
12 Standard Test Conditions (1000 W/m' irradiance, AM 1.5, 25" C).
13 Based on average of measured power values during production.
Traditional
I I i
0 5 10 15 20 25
Years
Combined Power and Product Defect 25 year coverage
that includes panel replacement costs. s
OPERATING CONDITION AND MECHANICAL DATA
Temperature — 40aF to +185aF (— 40aC to +85aC)
Max load
Wind: 50 psf, 2400 Pa, 245 kg /M2 front & back
Snow: 112 psf, 5400 Pa, 550kg/m2 front
Impact
resistance
1 inch (25 mm) diameter hail at 52 mph (23 m/s)
Appearance
Class B
Solar Cells
96 Monocrystalline Maxeon Gen 11 Cells
Tempered Glass
High Transmission Tempered Anti -Reflective
Junction Box
IP -65 Rated
Connectors
MC4 Compatible
Frame
Class 2 silver anodized
Weight
Al lbs (18.6 kg)
—r
1046mm
7[41.2in]
46mm
[1.81in]�r1559mm
[61.4in]
See htto://www.sunpowercorp.com/facts for more reference information.
For further details, see extended datasheet: www.sunoowercorp.com/datasheets Read safety and installation instructions before using this product. Designed in California
t ® March 2013 SunPower Corporation. All rights reserved. SUNPOWER, the SUNPOWER logo, MA%EON, MORE ENERGY. FOR LIFE., and SIGNATURE are trademarks or registered trademarks of su n powereorp. com
Sump— Corporation. Specifications included in this datasheet are subject to change without notice.
Document H 505701 Rem A /LTR_EN
TESTS AND CERTIFICATIONS
Standard tests
UL 1703, IEC 61215, IEC 61730
Quality tests
ISO 9001:2008, ISO 14001:2004
EHS Compliance
ROHS, OHSAS 18001:2007, lead-free
Ammonia test
IEC 62716
Salt Spray test
IEC 61701 (passed maximum severity)
PID test
Potential -Induced Degradation free: l OOOV 10
Available listings
CEC, JET, KEMCO, MCS, FSEC, CSA, UL, TUV
—r
1046mm
7[41.2in]
46mm
[1.81in]�r1559mm
[61.4in]
See htto://www.sunpowercorp.com/facts for more reference information.
For further details, see extended datasheet: www.sunoowercorp.com/datasheets Read safety and installation instructions before using this product. Designed in California
t ® March 2013 SunPower Corporation. All rights reserved. SUNPOWER, the SUNPOWER logo, MA%EON, MORE ENERGY. FOR LIFE., and SIGNATURE are trademarks or registered trademarks of su n powereorp. com
Sump— Corporation. Specifications included in this datasheet are subject to change without notice.
Document H 505701 Rem A /LTR_EN
Absolute Maximum Open Circuit Voltage
600 VDC 1000 VDC i
Operating Voltage Range
180-580 VDC
260-580 VDC 300.900 VDC
fAPPT Input Voltage Range
300.540 VDC
300.550 VDC 480-800 VDC 500.800 VDC
MPPTrackers
2 with 4 -fused inputs per tracker
Maximum Operating Input Current
2x 25A
2x 35A 2x 27 A 2x 32 A
Strike Voltage
300V 330 V
Nominal Output Voltage
208 VAC, 3 -Ph
480 VAC, 3 -Ph
AC Voltage Range (Standard)
-12%/.10%
Continuous Output Power (VAC)
14 kW
20 kW 23 kW 28 kW
Continuous Output Current (VAC)
39A
27.3 A 32A 39A
Maximum Backfeed Current
0 A
Nominal Output Frequency
60 Hz
Output Frequency Range
57.63 Hz
59.3.60.5 Hz 57.63 Hz
Power Factor
Unity, >0.99
Total Harmonic Distortion (THD)
(3%
Peak Efficiency
96.9%
97.4% 98.4%
CEC Efficiency
96.0%
97.0% 98.0%
Tare Loss
c 4 W
c 2 W
8 Fused Positions (4 positions per MPPT)
15 A (fuse by-pass available)
Ambient Temperature Range
-130F to +140°F (-25°C to +60°C) -13°F to +140°F (-25°C to +60°C)
Derating occurs over +50°C Derating occurs over +45°C
Storage Temperature Range
-22°F to +158°F (-30°C to +70°C)
Relative Humidity (non -condensing)
0-95%
Optional SolrenView Web -based Monitoring
Integrated
Optional Revenue Grade Monitoring
External )
External Communication Interface
RS485 Modbus RTU
Safety Listings & Certifications
UL 1741/IEEE 1547, IEEE 1547.1, CSA C22.2#107.1, FCC part 15 B
Testing Agency
i
ETL CSA
Standard
10 year
Optional
15, 20 year; extended service agreement
AC/DC Disconnect
Standard, fully -integrated
41.6x21.4x8.5in. 39.4 x 23.6 x 9.1 in.
Dimensions (H x W x D) (1057 x 543 x 216 mm) (1000 x 600 x 230 mm)
Weight 141 lbs (64 kg) 132 lbs (60 kg) 122 lbs (55 kg)
Enclosure Rating Type 4
Enclosure Finish Polyester powder coated aluminum
SOLECTRIA
RE N EWA B LES www.solectria.com I inverters@solectria.com 1 978.683.9700
ffl INNER
The Ground Screw
Technical Data Sheet G Series
Basic Info
Nominal length (mm)
2100
1600
1300
Tube diameter (mm)
76.10
76.10
76.10
Weight (kg)
14.00
10.50
8.50
Item number
25456
25455
25454
Construction
• Nut: DIN EN ISO 4032 - 8
• Continuous welded helix
• Coating: Hot -dip galvanized according to DIN EN ISO 1461
PERMIT # ho(
y ��
BUTTE COUNTY DEVEI..OPb1EPiT -F ERViCES
R` ,VIEWE -
DATE t �S7 Z�- 'r3Y
i
KSF G 76x
1300-3xM16
Subject to technical change! efficient • no concrete • durable
Krinner Schraubfundamente GmbH I Passauer Strane 55 1 D-94342 Strankirchen
Phone: +49 9424 9401-80 1 E -Mail: service@krinner.com I www.krinner.com
J!;J KR I N N ER
The Ground Screw
Technical Data
a
Length (mm) (±25 mm)
208_0 1580
12_80
b
_ _ _
Shaft outer diameter (mm)�
_ _
+
7_6.10 76.10
!
76.10
c
inner diameter (mm)
68.90 68.90
68.90
`d
Diameter setting (mm)
60 60.
60
e
Depth setting (mm) (_25 mm)
1815 1315
1020
If
Thread
3xM16 �3xM16
^� 3xM16
f
b
a
Online Service
Webkey
G2545611D
a
.II II
G25455110 G2545411D
R1 a o, a
a � a
PERMIT#
BUTTE COUNrr DEVELOPMENT SERVICES
IEWED FOR
�, .
Subject to technical change! ;ODE CPLIANCE
Krinner Schraubfundamente GmbH I Passauer Strane 55 1 D-94342 Strankirchen DATE_ 3� �%v BY C-.,,
Phone: +49 9424 9401-80 1 E -Mail: service@krinner.com I www.krinner.com
Customer Name: Burch CreekCounty Line Panel Specifications
Customer Address: Highway 99 E, Chico , CA 95973 Manufacturer: Sunpower Model: SPR -E20=327 -COM
Service Panel Bus Bar Rating: 200 A PV Pmax: 327 W Length: 61.4 inches
Service Panel AC paramters: 480 V Vmpp: 54.7 V Width: 41.2 inches
Total Solar AC System Size: 53200 W Voc: 64.9 V Weight: 41 lbs
Min Service Panel CB Size: 100 A f11, n7 Impp: 5.98 A Voc %Temp: 0.0027 V
Area Lowest Temp: -11 °C Isc: 6.46 A Voc Temp: 0.1766 V
Inverter I Manufacturer Solecria Inverter I Manufacturer Solecria
h "A" ' Inverter Model PVI-23TL 480V "B" Inverter Model PVI-23TL 480V
Inverter Output Power 26600 W Inverter Output Power 26600 W
Inverter Imax 32.0 A Min CB Sizer -7490A Inverter Imax 32.0 A Min CB Size _40 A f3
6f Strings of 14 Actual CB Sizel 401A Strings of F-141 Actual CB Size 461A
Voltage 480 VAC Voltagel 480 VAC
Array String Array String
DC Operating Voltage 1 765.80J 765.80 VDC DC Operating Voltage 765.80 765.80 VDC P
DC Max Voltage 1000.08 1000.08 VDC DC Max Voltage 1000.08 1000.08 VDC f8
DC Operating Current 35.88J 5.98 A DC Operating Current 35.88 5.98 A f9
DC Short Circuit Current 38.76 6.46 A DC Short Circuit Current 38.76 6.46 A flo
PERMIT 9 Y /1/- u `S�
QL+TTL ,OUNTV DEVELQP viEiJT SERVICES
REVIEWED FOR
CODE COMPLIANCE
DATE /_2 Y
Notes
Formulas
n , NEC, Annex C, Annex C Table C
rf sc x x
of series panes in series x vmpp
n2, Conduit fill, NEC Table 310.15(B)(2)(a)
f2, Isc x 1.25/Conduit fill x (Ambient Temp - Sunlight Exposure Correction f8,k of series panels x ((26C + Record Low Celcius x panel Voc temp Coef
n3, Temp correction, NEC Table 310.16
Factor)
+ Voc))
n4, DC Resistance, NEC Chapter 9 Table 8
f3, Inverter Imax x 1.25
f9,tt of strings x Impp -
n5, AC resistance, NEC Chapter 9 Table 9
f4, Inverter Imax x 1.25/Conduit fill x (Ambient Temp - Sunlight Exposure f10,# of strings xlsc
n6, NEC Article 310.15
Correction Factor)
f11,Bus Bar or conductor rating x 1.2 - Sum of all Input Breakers <or= Bus
n7, NEC Article 690.8(B)(1)
f5, Tolerance % x V/D x I x.2
bar or conductor rating x 1.2
n8, Sunlight Exposure,NEC Table, 310.15(B)(2)(c)
f6, .2 x D x I x R/V
DC Circuit Ampacity Calcalator
Wire Note: F
1 Descripition: Module to INVERTER
10 Minimum Wire and Conduit Size based on Voltage drop and Amacity:
6.461A Isc/A Number of Strings
6.46 A Circuit Amps
17.40 A Ampacity After Derat 10 Wire Size based on Ampacity 30 A
0.4454. % of V drop 10 Wire Size based on Voltage Drop 30 A
17.40 A Minimum Conductor Ampacity Based on Conditions of Use
A Minimum Conductor Ampacity Based on 1.56 Rule
Conditions of Use
0.464 Derate Total
�70 "C Temp Coef (ambient+Sunlight)
70 T Ambient Temp
none Sunlight Exposure
4 Number of Current Carrying Conductors
Voltage Drop. Allowable Tolerance I%
158 F 0.58 Derate
158 F
32 F 0 °C Temp adder
0.8 Derate applied to Temp Coeficient
54.7
V
Vmp/Volts 14 Panels in Series
5.98
A
Imp/Amps
765.8
V
Circuit Voltage
5.98
A
Circuit Amps
230
ft
One way distance 101 Wire Size
1.24
Resistance
0.4454 % of loss
Conduit Size
171
Conduit Type 0.2661000 VoltConduit Size 0.864 Conduit Internal Diameter
AC Circuit Ampacity Calcalator
Job Name: BURCH CREEK FARMS COUNTY LINE Meter #: 1004538571
Location: kN/A
Wire Note: JAC- I _ Descripition: Inverter to DISTRIBUTION PANEL
26.592 kWatts 480 VAC Delta Voltage Configuration
8 Minimum Wire Size based on Voltage drop and Amacity:
39.98033• A Minimum Circuit Breaker/Fuse Size
39.98033 A Min Ampacity 8 Wire Size based on Ampacity 55 A
0.103949 % of Drop 8 Wire Size based on Voltage Drop 55 A
31.98427 A Circuit Ampacity 1.732 Factor Phases
0.82 Conditons of Use Derate Factor
39.00521A Minimum Conductor Ampacity Based on Conditions of Use
39.980331A Minimum Conductor Ampacity Based on 1.25 Rule
Conditions of Use
50 "C Ambient Temp 122 F 0.82 Derate Total
none Sunlight Exposure 32 F Adder 0 °C
3 or less Number of CCC Factor 1 Derate applied to Temp Coef
50 'C Temp Coeficient (ambient+Sunlight) 0,82
Voltage Drop: Allowable Tolerance (Solar Generation I %/ Distribution3%)
A
ft One way distance �8Wire Size 0.78 Resistance 0.103949 % of lossV Circuit Voltage L� 31.9842667 A Circuit Amps
Conduit Size
EATT Conduit Type 0.255 600 Volt 11.82%
1 Conduit Size .0.86J Conduit Internal Diameter
AC Circuit Ampacity Calcalator
Job Name: BURCH CREEK FARMS COUNTY LINE Meter #: 1004538571
Location: N/A
Wire Note: AC -1 Descripition: Inverter to DISTRIBUTION PANEL
53.184 kWatts 480 VAC Delta Voltage Configuration
4 Minimum Wire Size based on Voltage drop and Amacity:
79.96067 A Minimum Circuit Breaker/Fuse Size
79.96067 A Min Ampacity 4 Wire Size based on Ampacity 95 A
0.082626 % of Drop 4 Wire Size based on Voltage Drop 95 A
63.96853 A Circuit Ampacity 1.732 Factor 31 Phases
0.82 Conditons of Use Derate Factor
78.01041 A Minimum Conductor Ampacity Based on Conditions of Use
M960671A Minimum Conductor Ampacity Based on 1.25 Rule
Conditions of Use
50 T Ambient Temp 122 F 0.82 Derate Total
none Sunlight Exposure 32 F Adder 0 °C
3 or less Number of CCC Factor 1 Derate applied to Temp Coef
gp °C Temp Coeficient (ambient+Sunlight) .0,82
Voltage Drop. Allowable Tolerance (Solar Generation 1 %/ Distribution3%)
10 ft One way distance 41 Wire Size 0.31 Resistance 0.082626 % of loss
480 V Circuit Voltage �J 63.9685333 A Circuit Amps
Conduit Size
1:71
ConduitType 0.335' 600 VoltConduit Size 1.237 Conduit Internal Diameter
ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH THE 2011 NATIONAL
ELECTRIC CODE (NEC), OR LOCAL MUNICIPAL CODE, AND FIRE DISTRICT
REGULATIONS.
1. ALL EQUIPMENT SHALL BE LISTED AND LABELED PER RECOGNIZED
ELECTRICAL TESTING LABORATORY AN INSTALLED PER THE LISTING
REQUIREMENTS AND THE MANUFACTURER'S INSTRUCTIONS.
2. ALL INVERTERS SHALL BE IEEE 929 COMPLIANT AND SHALL BE INSPECTED
BY LOCAL UTILITY BEFORE COMMISSIONING, TESTING, AND OPERATION OF
THE SYSTEM.
3. ALL OUTDOOR EQUIPMENT SHALL BE MINIMUM NEMA 3R, INCLUDING
OUTDOOR MOUNTED TRANSITION BOXES, COMBINER BOXES, AND
SWITCHES.
4. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED PER THE REQUIREMENTS
OF NEC ART.250,690.
19.INSTALLATION OF PV PANEL ARRAYS SHOULD RESIST SLIDING AND POP-UP
RESULTING FROM SEISMIC EVENTS AND SHOULD COMPLY WITH CBC
SECTION 1613A AND ASCE STANDARD 7-05, CHAPTER 13.
20.PV SYSTEM INSTALLER WILL BE RESPONSIBLE FOR FURNISHING AND
INSTALLATION OF ALL RELATED EQUIPMENT, CABLES, ADDITIONAL
CONDUITS, BOXES WIREWAYS AND OTHER ACCESSORIES NECESSARY FOR
COMPLETE AND OPERATIONAL PHOTOVOLTAIC SYSTEMS.
21.PV SYSTEM CONTRACTOR SHALL COORDINATE ALL THE WORK WITH THE
ENGINEER, THE CONSTRUCTION MANAGER AND ALL OTHER
CONTRACTORS TO ENSURE THAT PV SYSTEM IS INSTALLED AS SPECIFIED IN
THESE DRAWINGS.
22.DRAWING IN GENERAL OR DIAGRAMMATIC AND INDICATE GENERAL
ARRANGEMENT OF THE EQUIPMENT AND WORK INCLUDED. THE
INTENTION OF THE DRAWING IS TO INDICATE SIZE, CAPACITY,
APPROXIMATE LOCATION AND GENERAL RELATIONSHIP, BUT NOT EXACT
DETAIL OR PHYSICAL PLACEMENT.
5. NEC. ART. 690.9(A). ALL CIRCUITS CONNECTED TO MORE THAN ONE
SOURCE SHALL HAVE OVERCURRENT DEVICES LOCATED SO AS TO PROVIDE 23.FIELD VERIFIES EXACT AIC RATING REQUIRED OF THE MAIN SWITCHBOARD
OVERCURRENT PROTECTION FROM ALL SOURCES. FROM LOCAL UTILITY.
6. NEC ART. 690.18. DUE TO THE FACT THAT PV MODULES ARE ENERGIZED 24.A PV SYSTEM WITH MULTIPLE INVERTERS, WHERE INVERTERS ARE
WHENEVER THEY ARE EXPOSED TO LIGHT, PV CONTRACTOR SHALL DISABLE REMOTELY LOCATED FROM EACH OTHER, WILL HAVE A DIRECTORY
THE ARRAY DURING INSTALLATION AND SERVICE BY SHORT CIRCUITING, CREATED FOR EACH LOCATION. AS PER 2011 NEC 690.5(H) AND IN
OPEN CIRCUITING, OR COVERING THE ARRAY WITH AN OPAQUE ACCORDANCE WITH 2011 NEC 705.10.
COVERING.
7. PHOTOVOLTAIC SYSTEM SHALL BACKFEED THE DISTRIBUTION SYSTEM ON
SITE PER THE REQUIREMENTS OF NEC ART.690.64(B). ALL BACKFEED
BREAKERS SHALL BE IDENTIFIED AS SUCH AND SHALL BE SECURED IN PLACE
BY ADDITIONAL FASTENER PER THE REQUIREMENTS OF NEC 408.16(F)
(408.36 IN 2011 NEC.
8. FALL ARREST PROTECTION PER OSHA REQUIREMENTS SHALL BE PROVIDED
FOR ALL ROOF WORK.
9. ALL CONDUCTORS AND TERMINATIONS SHALL BE RATED FOR 75° C
MINIMUM.
10.NEC ART. 690.14. - SEE SHEET RE -4.3 FOR LABEL DIAGRAM
11.NEC ART. 690.53. - SEE SHEET RE -4.3 FOR LABEL DIAGRAM
12.NEC ART. 690.17. EACH AC DISCONNECT SHALL ALSO BE LABELED WITH:
"WARNING! -ELECTRICAL SHOCK HAZARD - DO NOT TOUCH TERMINALS.
TERMINALS ON BOTH LINE AND LOAD SIZE MAY BE ENERGIZED IN THE
OPEN POSITION".
13.DC DISCONNECT ATTHE INVERTER WILL BE READILY ACCESSIBLE AFTER
THE INSTALLATION IS COMPLETE PER 2011 NEC ART. 690.17 WHERE
TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN THE
OPEN POSITION. PROVIDE A WARNING SIGN OF THE HAZARDS PER 2011
NEC ART.690.17
14.CONTRACTOR TO PROVIDE GROUND FAULT PROTECTION FOR ROOF
MOUNTED PHOTOVOLTAIC ARRAYS LOCATED ON DWELLINGS PER 2011
NEC ART.690.17.
15. WHERE MORE THAN ONE NOMINAL VOLTAGE SYSTEM EXIST, THE
DIFFERENT SYSTEMS SHALL BE IDENTIFIED BY PHASE AND SYSTEM PER
2011 NEC ART.210.41D
16.PROVIDE AN ACCESSIBLE DISCONNECT DEVICE THAT IS LOCKABLE IN OPEN
POSITION AND IS LOCATED WITHIN 10'-0" OF THE METER PER LOCAL
ELECTRICAL UTILITY REGULATIONS.
17.PHOTOVOLTAIC SOURCE CURRENTS MUST BE RATED AT BOTH 125% OF
THE PARALLEL MODULE AND AT A CONTINUOUS LOAD OF ANOTHER 125%
FOR ATOTAL OF 156%OFTHE LOAD.
I
PROJECT OWNER:
PAGE # CONTENT
BURCH CREEK - COUNTY LINE
I HIGHWAY 99 E
PV -1.0 SCOPE
CHICO, CA 95973
PV -2.0 SITE PLAN
APN#:047.070.105.000
PV -2.1 UNDERGROUND SITE PLAN
PV -3.0 ARRAY LAYOUT
CONTRACTOR:
PV -4.0 ELECTRICAL DIAGRAM
PV -4.1 MONITORING DIAGRAM
PV -4.2 LABEL DIAGRAM
I ALTERNATIVE ENERGY SYSTEMS INC.
PV -5.0 RACKING DETAILS
MAIL TO: PO BOX 9231
ATTACHMENT MODULE SPECS
CHICO, CA 95927
INVERTER SPECS
PHYSICAL: 13620 HWY 99
WIRE CALCS
CHICO, CA 95973
CSLB 853351 C-10, C-46
I
SCOPE:
BUILDING JURISDICTION:
INSTALL GROUND MOUNTED
BUTTE COUNTY
PHOTOVOLTAIC SOLAR SYSTEM AND
DEPT. OF DEVELOPMENT SERVICES
UPDATE ELECTRICAL EQUIPMENT AS
NEEDED IN ACCORDANCE WITH ALL
7 COUNTY CENTER DRIVE
APPLICABLE BUILDING CODES
OROVILLE, CA 95965
SPECIFICALLY REFERENCING THE 2013
OFFICE#: (530) 538-7601
CALIFORNIA ELECTRICAL CODE/ 2011
FAX#: (530) 538-2140
BUTTE
NEC USING THE FOLLOWING SPECIFIC
INSPECTION LINE: (530) 538-4365
REQUESTS PHONED IN BY 2PM WILL BE INgQY
EQUIPMENT:
THE NEXT BUSINESS DAY SEP 17 2014
I MODULES: SUNPOWER
I (168) SPR -E20 -327 -COM PERMIT #
DEVELOPMENT
I 54.94kW SYSTEM BUTS
-E COON i Y _Q�VPI..Oi,MSNT SERVICES SERVICES
I 3, 025 SQFT COVER
I INVERTER(S): SOLECTRIA CODE
q_ xll'wcc, " �0R ` 1
0 1 LIANCE B �l 1 _ `'I
1 (2) PVI-23TL 480V DATE
I
5 a jO11 BY � P-ROJ-ECT INFORMATION
18.PROVIDE PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION I (i
OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC I I
SYSTEM DISCONNECT MEANS IF THEY ARE NOT IN THE SAME LOCATION I I t
PER 2011 NEC ART.690.56.
REVISION
o=
DoCh
0
nLD mN LA in
Q1 R N G1
� m c
m Q' oNi v
N Q Om DO f0
rn v v o 0
CO a Ln
O=r 0
CL U d LL .0
W
_ Z
J
}
H
z
O o
U mo
LL a) o
tll
LuCnQlO
Q O
UQU�
=�O0
U=U:m
2 a
m2UQ
SCALE
NTS
DRW By
AW
DATE
09/12/2014
SHEET
GENERAL NOTES 3 I LOCATION MAP N2 SITE MAP Z PV -1.0
NITSINTS
SCOPE
r-1 LE!§i7 <��--ry
REVISION
E
0
Y
w
O
DO 0
n l0 tD m
N EA m
01 C N N
Ln mrn c
N 01N cn v
(V Q Om DO N
01 V L O
mo u aLn@J
0 = 0 X 0
auCi- Ei c
LLJ
Z
J
F—
Z
Z)
O
OU m o
W al O
IJ1
T --I
LTJ 07 Ol O
} Q O
UQU�
=�60
U=Vii
m2Ua
SCALE NTS
ORw BY AW
DATE
09/12/2014
SHEET
PV -2.0
SITE FLAN
p
Z
's
., - \_ HIGH WAY 99 E J PhonCHICe(530) 345 6980
01
C " a z •N CH ICO CA 95973 148Boom Fax(530) 892, CA 95927
2360
a APN#:047.070.105.000 Alternative Energy Systems Inc. info@solarenergyforlife.com
4
iv -IF AF ir
a i` a e
4OF FIRST RAIL--- m m O
0. — — — —
x -
r•S&
REVISION
A E
n
0
41
W
00 Q
Q
I
2'.7j- kq
N u1 m
16. '"I m m ^4 ami
N Q m OO iO
Z, o, U Eno 0
co Li c Ln@)
t C
40F DOST o a° ., n m e v ,n n m m a • „ ':: .. m. .. .. $ .. ,. .. $ n n a a
U LL
V
� � C
O N
1 ` ai ® >-
%A A
No. 44 1 cl
a,
P. 1 /31/ w`
w
e�
� a
8. 5,14
STRUC U L ONLY
VINCI & SII 0 C I A T E S
C31rucfu #yineers
175 E. WILBUR ROAD, SUITE 103 - I OUSAND OAKS, CA 91360
P - 805.496.2100 f- 805.49ciSE.com
J
}
Z
0 p
U Mo
W0)O--------------------------------------------------------- - --- ---- Y r- i
U.J
cy)
STRING LAYOUT } Q o
UQU�
PERMIT #U = U
BUTTE COU-iTY DEVSLOPMZN T SERVICES
REVIEWED FOR CC) z u a
DATE 4-0
"— y NTS
DRW 0
AW
'6ATI7—
09/12/2014
SHEET
PV -3.0
ARRAY LAYOUT ARRAY LAYOUT
MATERIALS
MID CLAMPS
END CLAMPS
RAILS U -BOLTS
SQUARE FOOTAGE
RAIL UNION
252
168
(84) 174" 168
3,025 SQ. FT.
0
FTGS & T'S
HORIZ. PIPE
VERT. PIPE SHORT VERT. PIPE LONG
PIPE UNION
ENDCAPS
56
(18)24'
(28) 5' (28) 8'
16
4
e�
� a
8. 5,14
STRUC U L ONLY
VINCI & SII 0 C I A T E S
C31rucfu #yineers
175 E. WILBUR ROAD, SUITE 103 - I OUSAND OAKS, CA 91360
P - 805.496.2100 f- 805.49ciSE.com
J
}
Z
0 p
U Mo
W0)O--------------------------------------------------------- - --- ---- Y r- i
U.J
cy)
STRING LAYOUT } Q o
UQU�
PERMIT #U = U
BUTTE COU-iTY DEVSLOPMZN T SERVICES
REVIEWED FOR CC) z u a
DATE 4-0
"— y NTS
DRW 0
AW
'6ATI7—
09/12/2014
SHEET
PV -3.0
ARRAY LAYOUT ARRAY LAYOUT
(84) PV MODULES �1
I SUINPOWER:SPR-E20-327-COM
(6) STRINGS OF (14) I
I 600VOC I
1 I
I 6
I
I 1a
I I
I I
I I DC -1
(3) 1" EMT w/
(4) #10 PV -WIRE CU. &
-----------"—(1) #10 THWN-2 CU. GRD.
WIRE RUN: 230'
IMP: 17A
r— (84) PV MODULES �11
SUINPOWER: SPR -E20327 -COM
(6) STRINGS OF (14) I
I I
6
I 14
1
I I
I I
I I DC -1
(3) 1" EMT w/
(4) #10 PV -WIRE CU. &
--'----------(1) #10 THWN-2 CU. GRD.
WIRE RUN: 230'
IMP: 17A
INVERTER "A"
26.59kW GRIDTIED INVERTER
32A/ 3P/ 480V
SOLECTRIA: PVI-23TL 480V
W/ INTEGRATED DC DISC.
- INVERTER
INVERTER "B"
26.59kW GRID TIED INVERTER
32A/ 3P/ 48OV
SOLECTRIA: PVI-23TL 480V
w/ INTEGRATED DC DISC.
-_ INVERTER
3
L
AC -C- 1
(2) 1" EMT EACH w/ '
(4) #8 THWN-2 CU. &
(1) #8 THWN-2 CU. GRD.
WIRE RUN: 10'
IMAX: 40A
AC DISTRIBUTION PANEL
300A/3P/480V
_Ll _1-2 -L3
i
AC -2
(1) 11/4" PVC w/
'(3) #4 TH W N-2 CU. &
(2) #8 THWN-2 CU. GRD./NEU
WIRE RUN: 100'
IMAX: SOA
100A�
I
10OA/3P/600V
SQUARE D: D323NRB
NEW GREENFIELD METER
(GENERATION ONLY)
100A/3P/480V
METER
AC -3
(1) 1" EMT w/
(4) #3 THWN-2 CU. &
(1) #8 THWN-2 CU. GRD.
WIRE RUN: 100'
IMAX: SOA
UTILITY CONNECTION
POINT AT SEALABLE
1 -BOX ABOVE NEW
METER
(E) AC SERVICE PANEL
200A/3P/480V.
METER
#1004538571
200 A
480 VAC
3 PHASE
L2 L3
REVISION
E
O
L3
w
o =
00 `O
ON
r1O`�° m
ONY RN N
Ln m
�In in
N Q 00 m
Ol U to O O
°O c Ln
m @!
0 =L � c
n U a m .
c
O �
a Y
d W A N
W
C
W
42
m
S.
(COMPLY WITH 2013 CALIFORNIA ELECTRICAL j
CODE.- ARTICLE 890.70 (E), 408.38(D) find
705.1200 I
Lit
REQUIREMENTS FOR IN&Y-GitelVonnected .
Z
E/ectdc Power.Production,syvtems
J
Z
o
O o
U m o
UJ 0)Iji
C)o
LI
w�a)o
PERMIT #
oC�Qo
Q
U�U�
-
euTr1 couN r r;tv�,l_0p14E,IrSERI/IGEs
2 0
OU
�t��IC btco I g- R
u =
CODE,0;!5alo
m 2 U Q
DATE �2�/� 13Y. -J
SCALE
NTS
DRW BY
AW
DATE
09/12/2014
SHEET
PV -4.0
ELECTRICAL SINGLE LINE DIAGRAM
ELECTRICAL SINGLE LINE
120
VAC
120
VAC
DECK MONITORING
BROADBAND ROUTER
GATEWAY
DECK ALL -IN -ONE -BOX
COMMUNICATION
CARD
A
INVERTER
A
COMMUNICATION
CARD
B
INVERTER
B
SOURCE
INTERNET
COMMUNICATION
CARD
C
INVERTER
C
PERMIT #
bbl -Wo
BUTTE COUNTY DEVE"LOPAAIENT SERVICES
a
?—'a �Yn e""'c
REVISION
v
0
0o
m 02
N LA M tko�
Ln N W
LA M C
M 010 `1
N Q m W N
M
x LA i O
ED u c Ln
0 = L x 0
CL V d LL .0
Li
J C
L N
wIA
A
W
d
w
a
W
Z
J
Z
° mo
Iwo
w�0,o
}ao
U a U
=�po
U=Uit
Inn 2 U Q
CODE
ap�l L—�r i5t.. ,it ��Ljj,,,,jj''�u I-�,j1 l SCALE NTS
' 4d"WDE 0.% Y'.GO LIANCE ORW BY
AW
DATE _ jo fa�T BY v
DATE
09/12/2014
SHEET
PV -4.1
MONITORING SINGLE LINE DIAGRAM
NTS MONITORINGSINGLELINE
ARRAY COMBINER INVERTER
I
CAUTION:SOLAR
Installed on all DC conduit every 10'
and on both sides of any
penetration.
O
SUB PANEL
NEC 690.54, Interactive Point of
Interconnection
AC DISC.
MAIN SERVICE
0
WARNING
Dual Power'Supply
Photovoltaic
NEC 705.10, Point of Connection,
Located On Main Service Panel.
REVISION
- .R 'NN EL ONLY! .
Installed at all Electrical
1\ PHOTOVOLTAIC SYSTEM
Installed on all DC Junction boxes
Distribution Panel covers that
DISCONNECT
provide a path from PV to Utility
z
_.
NEC 690.14, Disconnection Means,
_j_
PHOTOVOLTAICUSCONNECTAt
- -• CUUlt RRENT
the single AC Disconnect or Main
7
SHORT - ENT A
Breaker.
o
o o
ELECTRIC SHOCK - .L
• - - • • • - : •
m
w ^ gyri
A GROUND FAULT IS INDICATED,
MAX SYSTEM VOLTAGE 600 VDC
-i
NORMALLYIF
-. . . CONDUCTORS
MAY BE UNGROUNDED . .
WARNING SHOCK-.
.. not touch terminalsTerminals of both line and-_
_ SOLARU��o
W a) Q1 0
.
Q r:
Per 690.5(C), Warning Shock_
... side .. ..
.. Relocate
�t
p o
Hazard. Included on all PV
NEC 690.14, Solar Disconnect
Solar Breaker Label @ Any breaker
ovc (Dz
disconnects.
on the front of all PV DC
passing Bi -Directional Power
m = u a
Disconnects. Filled out in
#
PERMIT ruTTE GOUrJiY t,�VELCPPA^eNT SERVICES
SCALE
accordance with NEC 690.55
rt�,�pj�IEWED FOR
NT
DPW BY
C0 Lr.) T,./9,MPLIANCE
DATE AW
r ,
DATE J '�+ BY c/
09/12/2014
SHEET
`
PV -4.2
LABEL DIAGRAM
--
LABEL DIAGRAM
I
.
F S/
�oqv_ �Z
0.411
F 1 / 1/15
'req l TUR �Q
V OF CA
t ^
1.. 3"
STRUCT L ONLY •
11,ABLETRAY",
`' 1 V N y p I
1 '
ii A S CA T EIS
i
SOLAR MODULE
(
.61ruchiLra/ 11 IL2 S
s
p
STRUT PER PLAN
_ 175 E. WILBUR ROAD, SUITE 103 - THOUSAND AKS, CA 91360
ALL WIRES TO BE RUN
- P- 805.496.2100 f- 805.496.2442 e - Vinci@VinciSE.com - -
INSIDE RACK AND CABLE TRAY
I
TO AVOID EASY ACCESS POST * .
'
CONSTRUCTION
TYPICAL HORIZONTAL MEMBER:
oo�
1 1/2" HOLLAENDER "T', TYP.
T
CABLE TRAY TOP AND BOTTOM
CABLE TRAY DETAIL 4
•
NTS GM1
GM4
J
END CAP- _ 11' 0 SCHED.40 -
P. PIPE \ GALV- PIPE
UNION
STRUT PER PLAN
*
1}"O SCHED.40
/
GALV- PIPE
30" INBED MIN, TYP. UNO
1
J_
2
\
TY CALU-BOLTASSENIBLY
1/2" HOLLAENDER T
A
.
TYPICAL PROSOLAR GROUND MOUNT RAIL TO PIPE DETAIL 3
NT
ti GM3
I RACKS &
MODULES PER PLAN
8"X8"X6" NEI
ENCLOSURE
REVISION
11'0 SCHED. 40
GALV. PIPE, TYP. U.O.N.
1" METALLIC FLEX
8"X8"X6" NEI
ENCLOSURE
' A
3/8 -16 x1 STAINLESS HEX
WASHER HD TYPE F
SELF TAPPING E
PRE W/ 5/16" �, TYP. 1 Z" 0 SCHED. 40 a
E
GALV. PIPE, TYP. U.O.N.
0000
am o w
GROUNDING ELECTRIC ry I m m
CONDUCTOR cn m m N w
m m a rn v
I "[II`- !l l I - -- I l ll- Il1-1f 1T1 iT` IIF Tti=1 T11=11=1 l f' I[f=1TL l (yil ii1�17= Nam °° 0
W1=:;
11=LLI 1 1=1 m u cu 0 0
_ TSI I I I a o @�
1: i -iTC= m u o X a
I I l= T- I CI I - I I C� I= -I a -T I U- I I� ` =11 I- I I 11=1 I CI I- I I d v a i
-jjT - I I I F�If-1
1 �llll 1111I'I
r
11= - I I I I-1 I -I' I I I I 11= i I --J -I I
—i�i
TYPICAL J BOX. AT BACK OF ARRAY E
y
• NT
SOLAR MODULE
STRUT PER PLAN
i SEE SECTION 4 FOR
ADI INI
170.6$r� l-1/2" HOLLAENDER "T; TYP.
f �
a» TYPICAL HORIZONTAL MEMBER:
11}"OSCHED. 40
ki " _GALV. PIPE, TYP. LINO
t
'CABLE TRAY TOP AND BOTTOM Lu
• . 4
�� �
TYPICAL POSTS: Z
1 20° 1},.O SCHED 40
GALV. PIPE, TYP. UNO. = O
O M O
& 16f A w w, y j TYPICAL FOOTING: KRINNER I W^ 0
try�Aq - t. fj� SOLAR GROUND SCREW Y O
W
11 111 Ill 11 El:
LY } Q O
1 LI `4 UQ U�
Is �
vI0cfz °C=Uz
< MIT # ��l Z _
BUTTE OUNTY DEVELOPMENT SERVICES _
REVIEWED FOR °o = U Q
CODE COMPLIANCE SCAB
NTS
BY Ram
AW
LDATE
v 1.8'-5" 09/12/2014
S E CTI O N SHEET
17 NT PV -5.0
RAKING DETAIL
RACgNG DETAIL