HomeMy WebLinkAboutUP06-11T
�7_
Memorandum
TO: f EPIC Wireless/ Verizon Wireless
Attn: Regina
381 South Lexington Dr.
Folsom, CA, 95630
FROM:Tim Snellings, Director
Department of Development Services
SUBJECT: Use Permit Applications for Addition of Diesel Generators to Existing
. Verizon Wireless Communications Facilities, Deemed Minor Changes.
DATE: March 10, 2006 ,
Department of Development Services
Planning Division
Summary:
Based on analysis 'and recommendations from the staff of the Development Services
Department we have deemed the proposed additions of diesel generators, equipment
cabinets, and backup batteries to be "minor changes" to existing use permits. This
memorandum grants approval of these minor changes to the five use permit applications
referenced below. The approved minor changes consist of addition, of one backup
emergency diesel generator to each existing wireless communications facility, and the
addition of four equipment cabinets and back-up batteries within the existing approved
footprint of each facility. In each case the wireless facility was allowed by an approved
Use Permit or Minor Use Permit, as required by the zoning of each site.
Date
Project #
APN
Location
Zoning
Facility Use
Received
Permit
12-7-05
MUP 06-02
047-100-191
Hamilton Nord
A-40
MUP 00-10
Hwy.
12-22-05
MUP 06-03
040-520-045
Media Way off
FR -20
MUP 00-07
Skyway, one mile
SW of Paradise
12-01-05
UP 06-05
025-330-006
Hwy. 70, north of
U
UP 00-12
Cox Lane
12-22-05
UP 06-06
006-400-056
Esplanade, one
C-2
MUP 00-15
mile south'of Hwy.
99/ Esplanade
1-20-06
UP 06-11
041-220-064
Table"Mountain
U
UP 98-05
Blvd., Oroville
EPIC -Verizon Wireless Use Permit/Minor Use Permit
Minor Changes Approval Memo, March 10, 2006
1
P
Description of Requested Minor Modification:
Each of the five use permit applications above is to add a 25-30 KW/3-liter diesel=
powered emergency electrical generator and four equipment cabinets to an existing
wireless communications facility. These additions would be contained within the original
footprint of the approved facility. Each, of the above facilities is essentially identical
interims of layout and composition of equipment on the site. The proposed additional
equipment cabinets include batteries to backup the electronic communications equipment,
bridging the time gap between grid -power outage and generator startup. Mr. Kortick of
Verizon explained that the backup generators are started remotely as a test each Thursday
morning, and run for about 15 minutes, and remotely monitored as to electrical output.
Each facility is serviced once per month, at which time the generators would also receive
any required service.
Each of the use permit approvals that granted the original wireless facility contained the
following standard special condition of approval #3:
Minor changes may be approved administratively by the Directors of Development
Services, Environmental Health, or Public Works upon receipt of a substantiated
written request by the applicant, or their respective designee. Prior to such approval,
verification shall be made by each Department or Division that the modification is
consistent with the application, fees paid, and environmental determination as
conditionally approved. Changes deemed to be major or significant in nature shall
require a formal application for amendment. . -
Staff assessed the following potential impacts ofthe proposed changes:
• Noise impacts from generator/hours of operation.
• Air quality impacts from generator operations.
• Hazards/toxics issues with storage of diesel fuel on the site.
• Hazards/toxics issues with backup batteries on the site.
DETERMINATIONS: The Development Services Department has made the following
determinations:
1) The applications for use permit listed above, are deemed to be requests for "minor
changes" to the approved use permit/minor use permit on each site.
2) The proposed changes are consistent with the environmental determination for the
originally -approved use' permit or minor use permit.
3) The proposed changes are consistent with the County Code 24-262 Wireless
Communications Facilities purpose, intent, applicability, exemptions, permit
requirements, application requirements, development criteria, and general
standards for the zones in which each is respectively located.
4) As no fee structure exists as yet for minor changes to use permits, the original fees
paid will be refunded to the applicant minus the cost of the actual staff time spent
in processing these minor changes.
EPIC -Verizon Wireless Use Permit/Minor Use Permit
Minor Changes Approval Memo, March 10, 2006
Environmental. Health Department (EHD) Fee:
Program Manager. Mike Huerta has determined that the Environmental Health
Department will assess a $90 fee for the processing of each of these applications, to cover
the required staff time. The applicant will need to complete a separate Request for
Service Environmental Health Department application for each project.
Planning Department Fee:
The Planning Department has expended approximately 3.5 hours to process each of these
applications. At the standard weighted planning staff rate of $137 per hour (3.5 X $137 =
$4.79.50), it is reasonable to conclude that a $480 fee will be deducted from the Use
Permit fees already paid for processing each of the five applications. The balance of fees
already paid will then be refunded to the applicant.
REQUIREMENTS REGARDING THE APPROVED MINOR CHANGES:
Planning Division:
1. All previous conditions for Use Permits or Minor Use Permit still apply.
2. The project site shall be developed in accordance with the approved project site plan
and the conditions for each Use Permits/Minor Use Permit. All new equipment
additions must be installed within the original footprint of the approved facility.
Said site plan is ori file in the Planning Division. .
3. The minor changes are limited to addition of one 25-30 KW/3-liter diesel -
powered emergency electrical generator, four equipment cabinets, and° backup
batteries. All new facilities shall be painted and/or screened from view with
adequate landscaping appropriate to the surrounding environment. All aesthetic
treatments, including landscaping shall be maintained as approved for the life of
the facility.
4. Minor change approval includes a requirement that the weekly generator tests
take place only between the hours of 8:00 a.m. 5:00 p.m., Monday through
Friday.
5. As noise impacts are anticipated to be infrequent and short-term, prior to issuance
of building permit, the applicant is required to provide technical documentation
certifying that the noise levels from generator operation will be less than 70 dB at
the perimeter of the facility, per GeneralPlan Noise Element Chart No. 4,
conditionally -acceptable level for residential low-density housing. (see attached
GENERAC specification sheet of 5/22/03 and comment 'by Verizon Wireless
Engineers of 11/10/05). The applicant is required to install the Series 2000 Sound
Attenuated Enclosure for which noise attenuation data was provided.
EPIC -Verizon Wireless Use Permit/Minor Use Permit
Minor Changes Approval Memo, March 10, 2006
3
i
t
0
•
Building Division:
6. Prior to installation of the new equipment, obtain all necessary building permits.
Environmental Health Division:
7. Prior to issuance of a building permit, provide written verification that the Butte
County Environmental Health Division has received and approved a Hazardous
Materials Release Response Plan iegarding the requested additions.- '-
Butte County Fire Department/CDF:
8. Construction, installation or development of structures or facilities on the parcel
shall comply with the latest California Fire Safe Regulations (Public Resources
Code 4290) and all other applicable State and County codes, ordinances and
regulations in effect at the time of application for'improvement permits.
9. 'Building identification and/or addresses shall be installed in conformance with
Public Resources Code 4290 and shall be posted at the beginning of building
.construction and maintained continuously thereafter.
10. Provide plans and specifications to the Butte County Fire' Marshal to determine
compliance with fire and life safety standards of Titles 19 and 24, California Code
of Regulations.
11. Comply with NFPA Standard 1-10 Emergency Standby Power Systems.
Butte County Air Quality Management District:
12. Prior to issuance of a building permit, provide written verification that the Butte
County Air Quality Management District has determined that the proposed diesel
generator(s) fall below the State -mandated threshold (37 JCW) at which the
licensing of such diesel engine installations is required (see attached letter of
January 19, 2006).
}
DEVELOPMENT SERVICES APRIOVAL:-
I hereby approve the above requested changes to the five approved use permits/minor use
permits as listed above/4p the�Determinations and Requirements listed above.
Tim Snellings, Director of Development Services. Date: March 10, 2006
Applicant Acknowledgement and Acceptance: The applicant here acknowledges
agreement with and acceptance of the determinations and requirements detailed herein
related to minor changes to the five use permit applications referenced above.
Date:
EPIC-Vizon Wireless Use Permit/Minor Use Permit 4
Minor Changes Approval Memo, March 10, 2006
CC: Doug Fogel, Program, Environmental Health Department
Mike Huerta.'Program Director, Environmental Health Department
Leslie Roberts, Environmental Health Department -Chico
Darren Read, Fire Captain, CDF
Scott Rutherford,, Building Chief
Building Permit Files
EPIC -Verizon Wireless Use Permit/Minor Use Permit 1
Minor Changes Approval.Memo, March 10, 2006
2525 Dominic Drive, Suite J
Chico, CA 95928
(530)891-2882
(530) 891-2878 Fax
January 19, 2006
Steve Troester, Butte County Development
Services Department, Planning Division
7 County Center Drive
Oroville, CA 95965
W. James Wagoner
Air Pollution Control Offer
Robert McLaughlin
Asst Air Pollution Control Offi"_er
BuTrE
COUNTY
JANE 4006
jEVELOYiPv ENT
SERVICES
RE: Use Permit Applications for Addition of Diesel Generators to Existing Verizon Wireless
Communications Facilities
Dear Mr. Troester:
The District has reviewed the information submitted regarding use permit applications for diesel
generators at Verizon Wireless Communications Facilities. The District recommends that Butte
County Planning Division consider the following information regarding diesel generators.
Stationary internal combustion engines rated at less than 50 horsepower do not currently require
written approval or other authorization from the Air Pollution Control Officer prior to installation
and/or operation in Butte County. However, the installation of several power generation units
(each rated at less than 50 HP) that collectively power one communications system at a location
in an effort to circumvent permitting requirements will be considered a violation of District rules,
regulations, and policies.
District Rule 400, Section 4.13 exempts other sources of minor significance as specified by the
APCO. In District Policy 6.6.1., the District has specified that stationary internal combustion
engines rated at 50 horsepower or below are exempt from District permitting requirements and
do not require an application or request for exemption prior to installation or operation.
Thank you for the opportunity to comment on the proposed project. If you have any questions,
please contact the District at 891-2882.
Sincerely,
r
f
Gail Williams
Air Quality Planner
File No 3452
FILE NO.:
PROJECT TYPE:
APN:
APPLICANT:
ADDRESS:
PHONE:
OWNER:
ADDRESS:
REPRESENTATIVE
ADDRESS:
PROJECT SUMMARY SHEET
UP 06-11
Use Permit
041-220-064
Epic Wireless - Brad Korticle
381 South Lexington Street, Folsom, CA 95630
Earl & Eva Gardner
5700 Eve's Lane, Chico, CA 95928
EPIC Wireless/Verizon Wireless
381 S. Lexington Drive, Folsom, CA 95630
0
PROJECT DESCRIPTION: add an "emergency only" generator to the existing wireless facilities
LOCATED: on Table Mountain Blvd., about a mile northwest of the Table Mountain Blvd. - Garden Drive intersection
PROPERTY ZONED: U (Unclassified)
GENERAL PLAN DESIGNATION: GOL (Grazing & Open Land)
TOWN/AREA: Oroville
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18
19
20
21
22
Application accepted: 1/20/2006 Amount: $ 3752.5 Receipt #: 443574
Assigned To: Steve Troester
Comments sent to: Public Works Director, Environmental Health, Assessor, LAFCo, Agricultural Commissioner,
CDF, Building Manager, County Counsel
Sent to Inter -Departmental Review Committee (IDR):
Status Letter sent to applicant:
Date scheduled for IDR: 12:00:00 AM
Comments received from:
Rezone Petition Signatures Checked:
Mailing List/Lead-in Sheet:
Environmental Determination:
State Clearinghouse No. Categorical Exemption-CEQA#
Negative Declaration
Mitigation Negative Declaration
Subject to Fish & Game: Environmental Impact Report
Gen. Rule Ex. — CEQA #
Other
Staff Report
Project Video:
Clearinghouse circulation required: Yes
No Date Sent to SCH:
Publication Notice Written:
Display Ad Prepared:
Notices Mailed:
Number of Notices:
NewspaperTublication Date:
O C P G B
Planning Commission Hearing(s):
Action taken:
Board of Supervisors' Hearing(s):
Action taken:
Board Resolution No.:
Ordinance No: Adopted:
Type Use Permit,
Send for signature:
N.O.E. / N.O.D. / APPENDIX G:
Fish & Game Fees Paid: Yes No
Send validated Use Permit:
Assessor's Memo:
Copy of Use Permit to GIS:
DEPARTMPiT OF DEVELOPMENIFSERVICES
BUTTE COUNTY UNIFORM APPLICATION
APPLICANT: Agent information to be provided is on page 2
APPLICANT'S NAME: (If application is different fromr an affidavit is requ}re .)
gPJL kv? e�� �neb )�vx� /z 4A
ASSESSOR'S PARCEL NUMBER:
o - o�
A1)1)RFSS: STREET, CITY, TATE, & ZIP CODE
3e2 S. � ;Z--� lam¢ 9J-'Q0
FILE NUMBER: (FOR OFFICE USE)
f any)�ovG� /^ _
NAME 01= PROPOS P�20J21A�lal-j
- 1 e)- i'!-�
TELEPHONE: -
LOCATION OF PROJECT (Major cross streets and Address, if any)
/� D
G NERAL INFORMATION REQUIRED
O\'\/NI--'R'S NAME:
Dk 4�1 v� `fes
TELEPHONE:
(ZZi% 2-24111"
ADDRESS: LCITY, STATE, & ZIP CODE:
I I
/ZO--NNE�/,�
GL-NERAL PLAN
7ING LAND USE
SITE IZE (in Square Feet or Acres)
E\IS FIN(; S I'ItUC"I'IJItIS (i Square Feet)
PROPOSED STRUCTURES (in Square Feet)
(Check One) N 14—
❑ PROPERTY IS OR PROPOSED TO BE SEWERED
❑ PROPERTY IS OR PROPOSED TO BE ON SEPTIC
(Check One)
❑ PROPERTY ISVRfROPOSED TO BE ON PUBLIC WATER
❑ PROPERTY IS OR PROPOSED TO BE ON WELL WATER
APPLICATION REQUESTED
❑ GENERAL PLAN AMENDMENT ❑ TENTATIVE SUBDIVISION MAP
" �1= ❑ TENTATIVE PARCEL MAP
❑ZEFERMIT
❑ WAIVER OF PARCEL MAP
❑ MINOR USE PERMIT ❑ BOUNDARY LINE MODIFICATION
❑ VARIANCE ❑ LEGAL LOT DETERMINATION
❑ MINOR VARIANCE ❑ CERTIFICATE OF MERGER
❑ ADMINISTRATIVE PERMIT ❑ MINING AND RECLAMATION PLAN
❑ UI:V I:LOI'IVI ENT AGREEMENT ❑ OTHER
PROJECT DESCRIPTION
FULL DESCRIPTION OF PROPOSED PROJECT (Attach necessary sheets. If this application is for a land division, describe the number and size
of parcels.)
OWNER CERTIFICATION
I L'LR 1"1171• fi IAT I AM PRESENTLY THE LEGAL OWNER OR THE AUTHORIZED AGENT OF THE OWNER OF THE ABOVE DESCRIBED PROPERTY.
FURTI IFR. I ACKNO\VI_I:DGE THE FILING OF THIS APPLICATION AND CERTIFY THAT ALL OF THE ABOVE INFORMATION IS TRUE AND
ACCURATL. (If an agent is to be authorized, execute an affidavit of authorization and include the affidavit with this application.)
DATE: 1-2-LI3 Or SIGNATURE:
I_K.\FORMS\UNI FORM APPLICATION
• Page I of 2
AGENT AUTHORIZATION
T0: Butte County, Department of Development Services:
�/ /G /jt/t ✓ e �✓ G' f'i'/ Phone Number (11-16)
Print Name
161. S Xiiv �/'� v� ��'�% 07�
�.
k,IailinL Address
i; hereby authorized to process the application for 1 .�V/`F2Z�h4 �'y� � �`•��
on my property, identified as Butte County Assessor Parcel Number: ����-�►G�
APN# 04/ - J a / - 06.
This 'uthorization allows representation for all applications, hearings, appeals, etc. and to sign all documents
necess,lry for said processing, but not including document(s) relating to record title interest.
Owner(s) of Record: (sign and print name)
�Gl v'� Ciail�ll" SNP!/
Print N, 31,11
Si,nauirr
Architect and/or Engineer:
L U0- & n,_—
Print
/Print Name
Signature
/P— �O7yt ivk Phone Numbercr`l�
Print Name of Architect/Engineer
,rf \ /iJ / /c7 (� /Gt d.J C J-6 0 ('0
Mailing Address
FOR OFFICE USE ONLY
\�ellfv. r'Q
Daic Received: Total Amount Received:
❑ AP Numbers)
❑ Legal'Description �r
❑ Owners Authorization ❑ Zoning Requirements
❑ Project Description ❑ Copies of plot plan ` JO
Taken by: Receipt No.
Plan E. H. CDF NOD
Payment
Fee
Payment of the currently required Application Fee and/or Deposit (Any unused portion of a deposit) will be returned upon
final action.
Current fee for this application is as of
Make check payable to "Butte County Treasurer".
K:\FURMS'dINIFORM APPLICATION
Page 2 of 2
p ..
USE PERMIT and MINOR USE PERMIT
COMMUNICATIONS FACILITY
APPLICATION PACKET CHECKLIST
This checklist is'designed to assist applicants in making sure all necessaryinformation is included in their
application. packet for a communications facility. Please include this checklist along with your submittal.
Applicant Planner
1. 1 -1/ ❑ A completed, signed, Uniform Application and Environmental Information form. If the
application is signed by an agent for the property owner, an agent authorization form must
be submitted along with the Uniform. Application. The application shall not be accepted
unless signed by the owner or authorized agent.
2. ❑ Payment of the currently required Application Fee and/or Deposit (any unused portion of
the deposit will be returned upon final action, if any remains.) (Planner advises applicant)
3. ❑ Thirty-five (35) copies of plans which shall include a detailed site plan drawn to scale. All
plans shall be drawn on uniform size sheets no greater than 24" x 36". The finished plans
shall be folded to 8'/2" x 11 ". The detailed site plan must include:
a. ❑ Name and address of Applicant, Engineer and/or person who prepared the plan.
b. ❑ Property lines and lot dimensions.
C. dLJ ❑ Assessor Parcel Number(s) and the street address.
�❑ ed use and/or uses of theproperty.
d. Propos
e. ❑ Proposed landscaping plan, if applicable.
f. 0 ❑ Dimensioned locations of existing and proposed improvements on the property
(including, but not limited to, buildings, driveways, parking areas, wells, septic tanks
and leach fields).
IF rNSUFFICIENT INFORMATION IS SUBMITTED, THE APPLICATION WILL BE DEEMED INCOMPLETE.
IF INSUFFICIENT INFORIMATION IS SUBMITTED, THE APPLICATION WILL BE DEEMED INCOMPLETE.
2
g. ❑
Distances from any significant natural and constructed features of the property, such
as streets, access roads,. streams, rock outcroppings, major tree stands, storm drains,
bodies of water, railroads, to the property lines.
h: 12IX❑
Location of all slope banks and
p , ponds, creeks, buttes, sloughs, rock outcroppings, natural
drainage courses,'irrigation canals and existing vegetation worthy of consideration for
preservation, such as oak trees.
i. � ❑
Any existing faults or fractures and geologic hazards.
j. ❑
North arrow and scale of drawing. Alllans shall be drawn to an engineering scale
p g g
with the preferred scale"of 1" = 20', with a north arrow preferably oriented to -the ton
of sheet.
k. ❑
Building setbacks from the ultimate road -
Building o right-of-way (front, rear, sides).
1. ❑
Proposed and existing on-site driveways and/or roads.
�❑
M.
Location, height, and materials of walls and fences (sections may be required).
n. Er�❑
All driveways, drawn to scale on ad'acent and across the street properties y , � prop rhes within
100 feet of the subject site.
o.❑
Existing curbs, gutters, sidewalks and existing paving widths on-site or within 100
feet of the site, on adjacent and across the street properties.
�❑
P
Nearest cross streets on both sides with plus or minus distances
p s is es from subject site.
q. I ❑
Approximate location of all buildings within 1,000 feet, on adjacent properties.
r. ❑'Existing
and nearest fire hydrants,
S. ❑
e
Access, both pedestrian and vehicular, showing service areas and points of ingress and
egress.
�❑
t.
Elevation contours at a minimumer USGS maps.
P.
IF INSUFFICIENT INFORIMATION IS SUBMITTED, THE APPLICATION WILL BE DEEMED INCOMPLETE.
2
4. ❑ ❑ Conceptual Grading Plan
Items to be shown include:
a. ❑
b. ❑
c. ' ❑
❑* Natural areas to be preserved.
❑ Proposed cut and fill areas in contrasting colors of zipatone pattern.
❑ Existing and proposed contours within 100 feet of project boundaries.
d. `❑ ❑ Proposed drainage and flood control facilities.
e. ❑ . ❑ Erosion control measures (e.g. - slope landscaping).
f. ❑ ❑ Natural drainage
g. ❑ ❑ Elevations and finished contours.
h. ❑ ❑ Location of retaining Walls, drainage channels and existing structures.
i. ❑ ❑ Location, elevation and size of proposed building pads.
j. ❑ ❑ All plans must be clear and legible.
5. ❑ �� One copy of 8 %z" x 11" transparency reduction of the detailed site plan.
6. XJ • ❑ A vicinity map showing closest major cross streets, zoning and existing land use.
The following additional items are required per Butte County Code Section 24-262.E.
7. CrEl Statement of Justification:
a. ❑ein
Includes a description of the proposed Facility, including the type of facility being
requested.
IF INSUFFICIENT INFORMATION IS SUBMITTED, THE APPLICATION WILL BE DEEMED INCOMPLETE.
3
b. ❑ Height from natural grade to the top of proposed Facility.
C. ❑ Support equipment proposed.
d. Zr
❑ RFR/EMF and wattage output.data including the number of channels.
e. Horizontal and vertical location coordinates.
8. ❑ Proposed elevations of the structure and any accessory buildings, including building
height and other physical dimensions, drawn to graphic scale.
9. ❑ Visual impact assessment, photo montages, mock-ups as determined by the Director of
N Development Services or Planning Commission. The assessment shall identify any
proposed trimming of vegetation that will be required for the normal operation of the
Facility. Stealth technology is encouraged.
10. ❑ )k❑ Mock-ups required (may be required at any time during the processing of the permit).
11. ❑ ❑ A discussion of and supporting information regarding the alternative site selection of at least
W' a minimum of three to four other sites, if available, including colocation opportunities, and
a statement as to why these alternative sites and/or colocation opportunities were rejected.
12. ❑ ❑ A complete service area map showing the entire wireless communications network of the
provider's twenty (20) miles in all directions from the proposed site for the time period from
the filing of the application to twelve (12) months from the filing of the application, for the
purpose of visually aiding cumulative environmental analysis, with and without the
proposed Facility or Facilities, showing all hand-off sites within the above specified area.
13. ❑1I ElA graphic depiction of the search ring and all other technical criteria used in determining
FJ the proposed Facility location.
14. ❑ Documentation which identifies failure characteristics of,the Facility structure or tower and
6 Gd" demonstrates that the site and setbacks are of adequate size to contain falling debris.
15. ❑ ❑ Written evidence demonstrating that the selected Facility structure or tower design is as
visually unobtrusive as possible, given technical and engineering considerations, which
D " indicate what type of Facility is required to provide reasonably effective service and also the
best technology and/or construction available to maximally achieve visual unobtrusiveness.
IF rNSUFFICIENT rNFORIMATION IS SUBMITTED, THE APPLICATION WILL BE DEEMED INCOMPLETE.
4
The use of best available -technology and/or construction to maximally achieve visual
unobtrusiveness is mandatory.
16. ❑ Applicants which operate common carrier facilities (specifically, but.not limited to cellular,
PCS, SMR and paging service licensees of the FCC) shall provide written evidence that the
applicant has provided notice to all FCC licensed wireless communication service carriers
operating within the County of Butte. of the plans to develop the site.
17. ❑ l Evidence of a valid, current operating license or construction permit from the FCC or, if the
applicant is not a wireless communications service provider, a user operating agreement for
each and every such provider to which the applicant intends to rent space on the proposed
Facility.
18. ❑ A report, signed by a qualified radio frequency engineer licensed by the FCC, prepared
pursuant to FCC OET 65, . stating whether the maximum radio frequency
radiation/electromagnetic radiation (RF/EMF) to be emitted by the proposed Facility, taking
into account all other Facilities, both existing and known future Facilities, at the proposed
site and adjacent properties, conforms to safety standards adopted by the FCC, if applicable.
The reports prepared for Facilities shall conform to the reporting requirements set by the
County and FCC OET 65 human exposure standards. The report shall also analyze the
evidence provided in support of the proposed Facility location, height, and radiated power,
frequency, the number of channels, and all other related data and present alternatives for the
location, height and radiated power, pursuant to the requirements of this section. If the
proposed Facility exceeds FCC OET 65 human exposure standards, applicant shall also
provide additional comprehensive technical and planning information regarding how the
applicant shall protect all persons from such excessive exposure consistent with all Federal
and State requirements, and any additional County requirements.
19. �/4 ❑ Landscaping and painting plans for the completed project.
20. -E ❑ Projects in Agc Rural Zones (A-5 through A-160) shall, Prior to submitting an application
for a proposed Facility, submit a site plan of the proposed Facility to the Butte County
Agricultural Commissioner for comment and send a notification letter to all aerial
agricultural applicators registered in the County informing them of the proposed site
location and tower height. No hearing on an application for a proposed facility in any
agricultural zone will be scheduled, nor shall any Administrative Permit for any such facility
be issued without proof that the Butte County Agricultural Commissioner and all aerial
agricultural applicators registered in the County have been notified, as specified herein.
IF rNSUFFICIENT INFORMATION IS SUBMITTED, THE APPLICATION WILL BE DEEMED INCOMPLETE.
5
Ll
21. ❑ ❑ All applications for Facilities that are proposed to be located within the boundaries of any
Comprehensive Airport Land Use Plan or Airport Area of Influence, as adopted or
designated from time to time by the Butte County Airport Land Use Commission, shall be
submitted to the Department of Development Services, Planning Division, and a copy
submitted to the Butte County Airport Land Use Commission for review regarding
consistency with adopted Comprehensive Airport Land Use Plans and for recommendations
addressing potential impacts -to air navigation within the Airport Area of Influence.
The County may in its sole discretion retain an independent consultant to review either' individual
elements of or the entire application and advise the County at the applicant's sole expense.
Additional information may be required in order to clarify; amplify, correct or otherwise supplement the- above
submittal information or to complete any required environmental review documents, as deemed necessary by the
Department of Development Services, Public Works, Environmental Health Division, Butte County Fire
Department, or Agriculture Commissioner.
Signature: G%�//l/L
Applicant/Representative
Signature:
Planner Receiving Application
K FOFtNIT-SUBMITAL'.CHECKLIS CELLUP WPD
Date -/ Z//l—
Date:
IF INSUFFICIENT INFORMATION IS SUBMITTED, THE APPLICATION WILL BE DEEMED INCOMPLETE.
6
COUNTY OF BUTTE
ENVIRONMENTAL INFORMATION FORM
(To be completed By Project Applicant)
Date Filed
GENERAL INFORMATION:
1 . Name and address of owner, and/or developer, and/or project sponsor:
00 A-0 xtdW4
2.. Address of project:
Assessor's Parcel Number: D
3. Name, address, and telephone number of person to be contacted concerning this project: /
! Gr✓ l�anr,,4,-C' ; 38 Z s. x�.v
d4r^G w i.eX-e sr �iYr j
4. List and describe any other related permas and other public approvals required for this project,
including those required by city, regional, state and federal agencies:
5. Existing general plan designation:�Ag-,� ,e
6. Existing zoning district:
7. How is land currently used?
8. Proposed use of site (Project -for which this form is filed):
.4 e r _ -
Project Description:
9. Site size: (Acres/Sq. Feet)
10. Off-street parking spaces: Full size: /V Compact:
Total:
11. Plans attached: Yes //No
12. Proposed development schedule ��� / y
13. Associated projects %2 ~
�?a . _
14. Anticipated incremental or phased development
0 Butte County Department of Development Services 0 Planning Division 0
Q
Attach description of project containing the following information:
eo
15. If residential, include the number of units, schedule of unit sizes, range of sale prices or rents, and
type of household size expected.
16. If commercial, indicate the type, whether neighborhood, city or regionally oriented, square footage
of sales area and loading .facilities'.
17. If industrial, indicate type, estimated employment per shift, and loading facilities.
18. If institutional, indicate the major function, estimated employment per shift, estimated occupancy,
loading facilities, and community benefits to be derived from the project.
19. If the project involves a minor variance, conditional use, rezoning application, or any development
permits, state this and indicate clearly why the application is required. If permits have already been
issued, please attach as Exhibit
Are the following items applicable to the project or its effects?
checked yes (attach additional sheets as necessary).
20
21.
22
23
24
25
26.
27.
28.
29.
30.
31.
YES
Change in existing features of any hills, buttes, canyons
or substantial alteration of ground contours.
Change in scenic views or vistas from existing residential
areas or public lands or roads.
Change in pattern or character of general area of project.
Significant amounts of solid waste or litter.
Change in dust, ash, smoke, fumes or odors in vicinity.
Change in bay, lake, river, stream or ground water quality
or quantity, or alteration of existing drainage patterns.
Substantial change in existing noise or vibration levels
in the vicinity.
Site on filled land or on slopes of 10 percent or more.
Use of, or disposal of potentially hazardous materials,
such as toxic substances, flammable or explosives.
Substantial change in demand for municipal services
(police, fire, water, sewage, etc. including special districts).
Substantially increase fossil fuel consumption
(electricity, oil, natural gas, etc.).
Relationship to a larger project or_series of projects.
Discuss below all items
NO
❑ Butte County Department of Development Services ❑ Planning Division ❑
y
y
•
Environmental Setting: (Attach brief description)
32." " Describe the project site as it exists before the project, including ,information on topography, soil
stability, plants and animals, and any cultural, historical, or scenic :aspects. Describe any' existing
structures on the site and the use of the structures. Attach photographs of the site. Snapshots or
Polaroid photos will be accepted.
33. Describe the surrounding properties, including information on plants and animals and any cultural,
historical, or scenic aspects. Indicate the type of land use (residential, commercial, etc.), intensity
of land use (one -family, apartment houses, shops, department' stores, etc.), and scale of
development (height, frontage, set -back, rear yard, etc.). Attach photographs of the vicinity.
Snapshots or Polaroid photos will be accepted. -
Certification
I hereby certify that the statements furnished above and in the attached exhibits present the data and
information required for this initial evaluation to the best of my ability, and that the facts, statements, and
information presented. are true and correct to the best of my knowledge and belief.
Date Signature
K:\Planning\FORMS\Submittal\ENV-INFO.FRM
0 Butte County Department of Development Services 0 Planning Division 0
APPLICATION CHECKLIST
[ _] Application Typed
10
Check Amount
[ ]Notice Material
[ ] Drawings: Number: Size:
[ ]. Letter of Authorization
[ ] Pre-application Meeting
[ ] Title Report
[ ] Power Density Material
[ ] Project _Description
[ ] Photo Simulation
[ ] Site Photos
[]
[]
COUNTY OF BUTTE
AUDITOR'S CERTIFICATE AND TREASURER'S RECEIPT
OROVILLE, CA
ATR NO
RECEIVED FROM PLANNING
RAG - 316 DATE 113012006
FUND FUND DEPT ACCT CASH
DESCRIPTION TITLE COTE CODE CODE CODE AMOUNT
DEPOSIT DATE: 1130
FOR 1927
RECEIPTS: 443574- 443ffiO
PLANNING APPL FEES GE:NL
0010
440MI
42109 101001
3,616.77 �
Project Number
Amount of Fee _
PPR! 041-220-084;'EPIC. WIRELESS; UP 06-11
2,970.00 ✓
APN 031-281-14 SERENAV�IEBB; AAUP G&W
91:77''
APN 027-120-01.4, 015; RON GRAVES; LLA 0611%
$
655.00
LAND DEVELOPMENT GEHL
0310
440 4
4611700 101001
524.00
Project Number.
Amount of Fee
APP -1.441-220-064; EPIC.WRIELESS: UP 0&11
$
165.00
APN 0227-920-014, 015; RON GRAVES; LLA. 00-10
$
359.00
ENVIRONMENTAL FILTH GEHL
00143
540=1
4614901 901001
416.00
' Project Number.
Amount of Fee
APN 44V-220-084: EPICWR.ELESS; UP 06-.11 .: --
-
$
202.00
APN 027-1211.014,.015i,RON GRAVES; LLA 06-A%
'$
214.00
FIRE PLNG APPL 4E , FIRE PROTECT
0100.
4617240 101001
401:00
Project Number
Amount of Fee _
_
APN 041-220••064: EPIC WIRELESS, UP 06-11 ^
$
347.00
APN 027120-014,1115; RON GRAVES, LLA 06 j`b
$
54.00'
NODINOE: CLERKS FILING FE GENS.
0010
47 'I
4612399 101001
72.00
.($w)--R)Tjeck_Number
Amount of Fee
APN 671i-220-064; EPIC'vMRELPSS; i!P 06-14
$
36.00
AGRICULTURE -AG FEE 0010 4 1 461,2200 101001 65 Dti
Project Number ,Amount of Fee
,APN 041-220-034; EPIC WRELESS; UP 06-11 $ 32.50
APN 027-120-0'14, 015: RON-GRAVES; LLA 0-M $ 32.60
b--7;L'380.c�j �enrY�LL�e-'� TTL. �,0 .��
o5
APPROVED BY: RECEIVED BY:
AUDITOR -CONTROLLER TREASURER
BY:
white=4r•easurer pink--aud.gor canary�:depositor•
golden rod--fale
Z S�
Friday, January 27, 2006
Development Services
PLANNING DIVISION
Counter
.
I ,
Person
.Gwyn
Payment Date
;01/27/2006
i
$165.00
443574 .
Receipt Number
Environmental Health
Received From
!Epic Wireless
;same
Applicant
CDF (Fire Department)
j
lApplication Number
UP 06-11
or ImReference To
$36.00
Parcel Number
1041-220-064
Aunt Minnie
;5398/5459
Check Number / Cash"
Planning Review / EIR
Total Received
$3,752.50
Total Fees
$3,752.50
Ver. 1.0 '
DDS Planning
$0.00
$2,970.00
(General Fund)
j
Public Works
$0.00
$165.00
(Land Development)
Environmental Health
$202.00
CDF (Fire Department)
j
$347.00
1
$36.00
NOD / NOE
(Recording Fee)
Aunt Minnie
$0.00
$1, 500 or $2,000
Planning Review / EIR
$0.00
Fish/Game
$0.00
ALUC
(Airport Land
$0..00
$0.00
Non Sufficient
Funds ($25.00 Fee)
1Cell Tower
($2500.00)
$0.00
Public Sales /Copies $0.00
Other: ( $32.50
r'i
(
~ �
2
COUNTY OF BUTTEle. .
OFFICIAL RECEIPT 443114
OFFICE OR DEPARTMENT ISSUING RECEIPT 20 <54
Received from 1-/, 77
�
i By—
CASH �l 'nu°
. --
^
.'
By
'
nm�oaoawsooponwo.aamr�*o` Form 84702
�
EPIC WIRELESS GROUP, INC. (Mbank. .5398.
1 800 US BANKS
381 SOUTH LEXINGTON DR., STE. 103
FOLSOM, CA 95630 90-2267/1211
(916) 984-5921 8/30/2005
PAY
TO THE Butte County
Three Thousand Five Hundred Fifty and
DOLLARS
Butte County
Oroville, CA 95965
MEMO
(Mbank. 54E9
EPIC WIRELESS GROUP, INC. 1-800 US BANKS
381 SOUTH LEXINGTON DR., STE. 103
FOLSOM, CA 95630 90-2267/1211 9/15/2005
(916) 984-5921
PAY
TO THE Butte County $ **202.00
ORDER OF
Two Hundred Two and
DOLLARS
Butte County
7 County Center Road
Oroville, CA 95965
MEMO AUMORIZED SIGNATURE
N --Esplanade- GE092005
COUNTY OF BUTTE
AUDITOR'S CERTIFICATE AND TREASURER'S RECEIPT
OROVILLE, CA a
DECEIVED FROM PLANNING
BAG: 316
ATR NO
91995
DATE 113012006
FUND FUND DEPT ACCT CASH
DESCRIPTION TITLE CODE' CODE CODE CODE AMOUNT
DEPOSIT DATE: 9/30
FOR 1127
RECEIPTS: 443674- 443660
PLANNING APPL FEES GENL 080.10 A417M1 4210900 101001 3,616.77
Prosect Number Amqunt_caf Fee
APN 031-299-120; SERENA VZMD; MUP 06-01
$ 99.77
APN 027-120-094, 015; RON GRAVES- LLA 06-17
_ $ 555.00
LAND DEVELOPMENT GENL
0010
440M 4611700 101001
Project. Number
Amount of Fee
•F •
APRI G41-220-064; EPIC 4MRELESS: UP O6 -i 1
$ 185. 0
APN 027-120-094, 015; ROS! GRAVES; LLA W-17
$ 359.00
ENVIRONMENTAL HLTI•I CSES+lL
OI810
040 3 4614901 101009
_ .Project Number .
Amount of Fee _
APN 044-22&084; EPICWRELESS; UP 06-.19
202.00 _
APN 027-12M14..095 ,RON GRAVES; LLA 05.17
$ 2.94.00
FIRE PLNG APPL 4E: FIRE PROTECT
0100 :.
4691240 101001
Project Number
Amount of Fee
APN 041-220••064; EPIC WIRELESS, UP 06-11 -
` .
$ 347.00
APN 027-120-Oi4, 096; RON GRAVES; LLA 06-17
$ 6.4.00
NODINOE CLERK'S FILING FIE GENL.
0090 ,
470001 . 46123`19 101001
($36) Project Number �--
Amount of Fee
APN f.W-229.064; EPIC WIRELESS: UP 00A I
$ 36.07
_ 8; LLA iJ6-17
$ 36.00
AGMCULTURE AG FEE-
0010
4 1 46122W 101001
Project Number
Amount of Fee
- AFN GM -22G-004; EPIC VARELESS; UP 06-11
s$ X2.50
APiV 027-920-014 015• RON GRAVES; LLA (16-V
$ 32.50
624.00
416.OfD
409:00
72.00
65.0`13
- —0,�2• ��so. o� , -„�a� , -D��r a�-v� TOTAL.$ 5,0"77
APPROVED Bel: DECEIVED BY:
AUDITOR -CONTROLLER TREASURER
L.
v-aate=4reasurer gran -auditor a anargr-depositor golden rod --file
a
K-0
OF SUPERVISOR
MAR 2 2 2006
,.: i E, CALIFORNIA
March 15, 2006
David Rowland -
Consumer Protection and Safety Division
California Public Utilities Commission
505 Van Ness Avenue,
San Francisco, CA 94102
per....„<
I�e"—Zpnmreless
One Verizon Place
MC: GA3B 1 REG
Alpharetta, GA 30004
(678) 339=4269
wBUTTE
-°� ' COUNTY
MAR 2 f 20
DE+ j!E'A,021YAhN
SERNM TS
Re: Notification Letter for NORTH ESPLANADE of Sacramento Valley Limited
Partnership (U -3004-C), of Chico, CA MSA
This is to provide the Commission with notice according to the provisions of General Order No
159. A of the Public Utilities Commission of the State of California ("CPUC") for the project
described in Attachment A.
A copy of this notification letter is also being provided to the appropriate local government
agency for its information. Should there be any questions regarding this project, or if you
disagree with any of the information contained herein, please,. contact, Veleta Wilson of Verizon
Wireless at (678) 339-4505.
Very truly yours,
Veleta Wilson
Coordinator - MTS Network
Network Compliance
Mzar
LIAR 2 4 2006
CPUC06.0084
Notification Letter
Sacramento Valley Limited Partnership (U -3004-C)
March 15, 2006
Page 2
Attachment A
CPUC CELL SITE REPORT Sacramento Valley Limited Partnership (U -3004-C)
1. PROJECT LOCATION: NORTH ESPLANADE —Add/Mod
SITE NAME: NORTH ESPLANADE
SITE ADDRESS: 3902 Esplanade
LOCATION: Chico, CA 95926
COUNTY: Butte
APN: 006-400-056
COORDINATES: 37° 47'27.0"/ 121° 53'35.0" (NAD83)
2. PROJECT DESCRIPTION:
Sacramento Valley Limited Partnership (U -3004-C) proposes the installation of one (1) new
30kW diesel powered emergency electrical generator onto a new concrete equipment pad with
four (4) additional equipment cabinets at an existing wireless communications facility.
ANTENNAS:' N/A
TOWER DESIGN: N/A
TOWER APPEARANCE: N/A
TOWER HEIGHT: N/A
BUILDING SIZE: N/A
OTHER: One (1) 30kW diesel powered generator
Four (4) equipment cabinets
CPUC06.0084 .
Notification Letter
Sacramento Valley Limited Partnership (U -3004-C)
March 15, 2006
Page 3
3. BUSINESS ADDRESSES OF ALL LOCAL GOVERNMENT AGENCIES:
Cc: Tim Snelling
Planning Director
Butte County Development Services
7 County Center Drive
Oroville, CA 95965
Jim Cook
City Manager
Butte County Development Services
7 County Center Drive
Oroville, CA 95965.
Marianne Reeves
City Clerk
Butte County Development Services
7 County Center Drive
Oroville, CA 95965 .
4. LAND USE APPROVALS:
Minor Changes to Existing Use Permits
Issued: 3/10/2006
Effective: 3/10/2006
Agency: Butte County Planning Commission
Permit No.: N/A
Resolution No.: Minor Changes to MUP 00-15
CPUC06.0084
ri ;,Z�);pwinefess
One Verizon Place
MC: GA3BIREG
Alpharetta, GA 30004
„ (678)339-4269
March 15, 2006
David Rowland
Consumer Protection and Safety Division
California Public Utilities Commission
505 Van Ness Avenue,
San Francisco, CA 94102
Re: Notification Letter for MERIDIAN of Sacramento Valley Limited Partnership -(U -3004-
C), of Chico, CA MSA
This is to provide the Commission with notice according to the provisions of GeneralOrder No.
159. A of the Public Utilities Commission of the State of California ("CPU.0") for the project
described in Attachment A.
A copy of this notification letter is also being provided to the appropriate local government
agency for its information. Should there be any questions regarding this project, or if you
disagree with any of the information contained herein, please contact, Veleta Wilson of Verizon
Wireless at (678) 339-4505.
Verytruly yours,
Veleta Wilson '
Coordinator - MTS Network
Network Compliance
CPUC06.0085
7
Notification Letter
Sacramento Valley Limited Partnership (U -3004-C)
March 15, 2006
Page 2
Attachment A
CPUC CELL SITE REPORT Sacramento Valley Limited Partnership (U -3004=C)
1. PROJECT LOCATION: . MERIDIAN — Add/Mod
SITE NAME: MERIDIAN
SITE ADDRESS: 15082 Hamilton -Nord Cana Hwy
LOCATION: Chico, CA 95926
COUNTY: Butte
APN: 047-100-191
COORDINATES: 390 51'09.4"/ 121° 57' 05.3"•(NAD83)
2. PROJECT DESCRIPTION:
Sacramento Valley Limited Partnership (tJ-3004-C) proposes the installation of one (1) new
30kW diesel powered emergency electrical generator onto a new concrete equipment pad with
four (4) additional equipment cabinets at an existing wireless communications facility.
ANTENNAS: N/A
TOWER DESIGN: N/A
TOWER APPEARANCE: N/A
TOWER HEIGHT: N/A
BUILDING SIZE: N/A
OTHER: One (1) 30kW diesel powered generator
Four (4) equipment cabinets
CPUC06.0085
Notification Letter
Sacramento Valley Limited Partnership (U -3004-C)
March 15, 2006 `
Page 3
3. BUSINESS ADDRESSES OF ALL LOCAL GOVERNMENT AGENCIES:
Cc: Tim Snelling
Planning Director
Butte County Development Services
7 County Center Drive
Oroville, CA 95965
Jim Cook
City Manager
Butte County Development Services
7 County Center Drive
Oroville, CA 95965
Marianne Reeves
City Clerk
Butte County Development Services
7 County Center Drive
Oroville, CA 95965
4. LAND USE APPROVALS:
Minor Changes to Existing Use Permits
Issued: 3/10/2006
Effective: 3/10/2006
Agency: Butte County Planning Commission
Permit No.: N/A
Resolution No.: Minor Changes to MUP 00-10
CPUC06.0085
i. •
'�°�rwir�less
One Verizon Place
MC: GA3BIREG
Alpharetta, GA 30004
(678) 339-4269
March 15, 2006
David Rowland
Consumer Protection and Safety Division
California Public Utilities Commission
505 Van Ness Avenue,
San Francisco, CA 94102
Re: Notification Letter for HONCUT of Sacramento Valley Limited Partnership (U -3004-C),
of Chico, CA MSA
This is to provide the Commission with notice according to the provisions of General Order No.
159. A of the Public Utilities Commission of the State of California ("CPUC") for the project
described in Attachment A.
A copy of this notification letter is also being provided to the appropriate local government
agency for its information. Should there be any questions regarding this project, or if you
disagree with any of the information contained herein, please contact, Veleta Wilson of Verizon
Wireless at (678) 339-4505.
Very truly yours,
Veleta Wilson
Coordinator - MTS Network
Network Compliance
CPUC06.0086
Notification Letter
Sacramento Valley Limited Partnership (U -3004-C)
March 15, 2006
Page 2
Attachment A
CPUC CELL SITE REPORT Sacramento Valley Limited Partnership (U -3004-C)
1. PROJECT LOCATION: HONCUT — Add/Mod
SITE NAME: HONCUT
SITE ADDRESS: 12147 Highway 70
LOCATION: Oroville, CA 95965
COUNTY: Butte
APN: 025-330-006
COORDINATES: 390 23'02.2"/ 121° 36'47.8" (NAD83)
2. PROJECT DESCRIPTION:
Sacramento Valley Limited Partnership (U -3004-C) proposes the installation of one (1) new
30kW diesel powered emergency electrical generator onto a new concrete equipment pad with
four (4) additional equipment cabinets at an existing wireless communications facility.
ANTENNAS: N/A
TOWER DESIGN: N/A
TOWER APPEARANCE: N/A
TOWER HEIGHT: N/A
BUILDING SIZE: N/A
OTHER: One (1) 30kW diesel powered generator
Four (4) equipment cabinets
CPUC06.0086
Notification Letter
Sacramento Valley Limited Partnership (U -3004-C)
March 15, 2006
Page 3
3. BUSINESS ADDRESSES OF, ALL LOCAL GOVERNMENT AGENCIES:
Cc: Tim Snelling
Planning Director
Butte County Development Services
7 County Center Drive
Oroville,- CA 95965
Jim Cook
City Manager
Butte County Development Services
7 County Center Drive
Oroville, CA 95965 '
Marianne Reeves
City. Clerk
Butte County Development Services
7 County Center Drive
Oroville, CA 95965
4. LAND USE APPROVALS:
Minor Chanizes to Existink Use Permits _
Issued: 3/10/2006
Effective: 3/10/2006
Agency: Butte County Planning Commission
Permit No.: N/A
Resolution No.: Minor Changes to UP 00-12
CPUC06.0086
ij
"DRAFT" LEAD IN SHEET
FILE NO: /� cg�'� AP# byI • 22.0 •
APPLICANT:
OWNER:
REPRESENTATIVE: �/°�G w,17,06&,�rj5
PROPOSED REQUEST: (to be filled out by person taking in application)
7�2 7 TffE
FINAL REQUEST: REQUEST: (to be filled out by project planner)
SIZE: / 3 - l 9 i S'
LOCATION: 00 i w b&,,.o��7i Bc�,y0 ih-- iw04-T-L-
1,,4 r.y GSL o �F 7-1-t E i fhR(.� ; vwt vl �tt-►�r'rc P �3GU✓_� P11 P
SUPERVISORIAL DISTRICT # i EXISTING ZONING: (A
GENERAL PLAN DESIGNATION: oxiJ 6AP"10
C
ASSIGNED PLANNER: Z:--- T. PLANNER's If
Date Application Received c7A,,-[ .
Date Proiect Assigned Fe�
IDR Date
30 Day Complete
Tentative Hearing Date
KAPlanningTormsTead In Sheet.doc
i�
COMMENT DISTRIBUTION LIST
APPLICANT:
PLANNING `
PROJECT DESCRIPTION:
FILE NO.:
DATE:
AP NO:
County Offices and Cities:
_ Planning Division
X Assessor's Office - Mapping
BCAG
X Environmental Health
City of Biggs
ALUC
_ Building Manager
City of Chico
APCD
X LAFCa
City of Gridley
Butte Co. Farm Bureau
X Agricultural Commission
City of Oroville
Chico Airport Commission
X Public Works/Land De
Town of Paradise
Chief Administrative Officer
Fire Protection:
X California Department of Forestry _ EI Medio Fire Protection
District
Domestic Water:
S.F.W & P. Agency (OWID)
_ Butte Water District
_ Del Oro Water Co.
California Water Service Co.
_ Thermalito Irrigation District
_ Other
Utilities:
_ PG&E North - Chico
_ Pacific Bell
_ Chambers Cable TV
PG&E South - Oroville
Viacom Cable TV
Irrigation District:
Biggs / West Gridley Water
_ Durham Irrigation Dist.
_ Paradise Irrigation Dist.
Richvale Irrigation Dist.
_ Table Mountain Irrigation Dist.
Sewer:
L.O.A.P.U.D. _
Sterling City Sewer Main_ Skansen Subdivision (CSA 21)
Drainage Districts:
Sacramento & San Joaquin Drainage Dist. _ Reclamation District
No. 833
_ Drainage District 200
_ Reclamation District
No. 2054
Reclamation District No. 2056
State Agencies:
_ CalTrans
_ Dept. of Water Resources
f
_ Dept. of Fish and Game
Federal Agencies:
U.S. Forest Service
_ U.S. Bureau of Land Management
Other Districts, Agencies, Committees, etc.:
K:\Planning\FORMS\APPLICATIONS\Lead-in Sheet Distribution List.doc
wireless
"For. ebay"
Table Mountain Boulevard
Oroville, California
Project Description/Justification Statement
Introduction
Sacramento Valley Limited Partnership, d/b/a Verizon Wireless, formerly AirTouch
Cellular is a partnership of Bell Atlantic Wireless, GTE Mobilnet and AirTouch Cellular,
organized to bid on radio frequency spectrum licenses auctioned by the Federal
Communications Commission ("FCC".). In addition to mobile phone services, Verizon
Wireless also offers wireless email, text messaging, internet access, paging, photo messaging
and data transmission. As the nation's largest. wireless service provider, Verizon Wireless is
continuing to expand its network in California and the Sacramento area. The existing
wireless communication site includes anexisting 150 -lattice tower with various Verizon
antennas and 2 radio cabinets. No changes are proposed to the tower and antennas.
Proposal
Verizon Wireless is seeking permission of to upgrade the equipment for an existing wireless
communication facility located on Table Mountain Boulevard north of Oroville (APN 041-
220-064). The service objective is primarily to improve emergency service in the Highway
99 rural area by adding the emergency only generator and improve the capacity.of the radio
equipment at the site by adding additional cabinets. ,
The proposed generator is a Generac SD030. Copies of a description of the unit are
attached. Also attached is a Statement of Exhaust Emissions for Diesel Fueled Generator.
The generator hours of operation are limited to testing once a week for about an hour. The
generator will operate 24/7 if the power grid fails out due to an emergency. The generators
are fueled with diesel stored on site. The tank holds 210 gallons in a duel wall, alarmed tank
that detects leaks. Noise levels are 65 db when operating as measured 7 meters or 23 feet
from the center of the tank.
Verizon Wireless will install equipment four (4) cabinets on a concrete pad to be
located in the equipment compound. The additional cabinets are 66" tall by 56" wide by 34"
deep. The cable will run from the pole to the equipment shelter, connecting the antennas in
the pole with the equipment.
December 14, 2005
Verizon. Wireless "Forebay"
Page 1.
Once the construen work is complete and the telephone Otching equipment is
fine-tuned, visitation to the site by service personnel for routine maintenance typically occurs
an average of once per month. "The site is entirely self -monitored and connects directly to a
central office where sophisticated computers alert personnel to any equipment malfunction.
This includes the testing and operation of the generator. Because the wireless facility will be
unstaffed, there will be no regular hours of operation and no impact to existing local traffic
patterns. No water or sanitation service is required for this facility. No advertising or
signage is proposed, except signs required by the FCC and facility emergency contact
information.
Verizon Wireless will comply with safety requirements of the Uniform Building
Code, as well as all other applicable regulations and permits, FCC rules governing
construction requirements, technical standards, interference protection, power, height
limitations, radio frequency standards and FAA rules governing construction and operation.
If the Verizon Wireless equipment is unused or becomes obsolete, it will be removed within
six months after its operation has ceased.
Justification Statement
The economic, business and residential growth along with increased general public
usage of Verizon Wireless' services in Yuba County and surrounding area have significantly
increased the volume of calls on the Verizon Wireless facilities. Verizon Wireless users have
expressed major concerns about the poor coverage, dropped and blocked calls on the network
throughout the area. Verizon Wireless radio engineers have conducted analysis of the
existing network and services. in the area and have determined that Verizon Wireless capacity
is very marginal in the area. This general location is necessary for Verizon Wireless to
provide seamless coverage in the area.
The FCC mandates that licensed service providers comply with stringent
requirements such as providing high quality in -building coverage to the general public within
a very aggressive timeframe. The FCC mandates 911 -locator functionality and the
maintenance of sufficient capacity to accommodate developing wireless data transmission
technology for internet access, instant messaging and other wireless services. Sufficient
wireless coverage not only meets the general service expectations of wireless customers, but
also enhances the safety of travelers by allowing immediate access to emergency assistance.
Land Use Compatibility
The proposed project is not inconsistent with the other existing uses. The facility is
proposed in an area used as support for the farming function. The facility will not interfere
with the farming function and is a'reasonable use for the "U", Unclassified zone district.
Visually, no alterations are being made at the site that the public will notice. The Verizon
Wireless facility will result in no impact to the environment to the area in which it is located.
The facility will not contribute significantly noise, smoke or odor. Construction will result in
minimal modifications and disturbance to the surroundings.
December 14, 2005
Verizon Wireless " Forebay"
Page 2
RFR/EMF Description
The total output and number of channels for the Forebay site is 120 watts. That represents no
change in output from the current set up as no changes are proposed to the antennas. The six
cabinets will produce 20 watts each for a total of 120 watts.
Benefits to the Community
The proposed Verizon Wireless facility will provide many benefits to area residents,
businesses and motorists in the general area. These benefits include:
➢ 911 capability allowing motorists to summon aid and report dangerous
situations
➢ The site will be capable of operating fully when power is out due to an
emergencyor severe weather.
➢ Support for emergency services by providing wireless communications to
paramedics, firefighters, and law enforcement agencies
➢ The ability to transmit data allowing for immediate access to vital information
➢ A back-up system to the land -line system in the event of power outages,
natural or man-made disasters
➢ Communication capabilities in remote areas, enhancing the safety of travelers
by allowing immediate access to emergency assistance
➢ Provide quality wireless communications including voice, paging, digital data
capabilities for email, facsimile and internet access
➢ Enhance the communications systems of residents who telecommute from
their homes
Summary
The new Verizon Wireless facility will provide an improved "State of the Art"
wireless telecommunication services to the surrounding community and become an important
part of the areas infrastructure for residents. Verizon Wireless respectfully requests approval
of its application.
December 14, 2005
Verizon Wireless "Forebay"
Page 3
0
USE PERMIT
BUTTE COUNTY PLANNING COMMISSION
•
DEC 17 1991
DATE: (Certified Mail. Rec.)
UP -98-05
PERMIT NO.
041-220-064
ASSESSOR'S PARCEL NO.
Pursuant to the provisions of the Zoning Ordinance of the County of Butte and the special
conditions set forth below: SMART SMR of California ;d.b.a. NEXTE! Communications).
ishereby granted a Use Permit in accordance with application filed: August 27, 1997, to
allow a communications tower in a U (Unclassified) zone, identified as APN 041-220-064:
1. 'Failure to comply with the conditions specified herein as the basis for approval of
application and issuance of.Permit, constitutes cause for the revocation of said
permit in accordance with the. procedures set forth in the Butte County Zoning
Ordinance, including Butte County Code Sec. 24-62.
2. Unless otherwise provided for in a special condition to this use permit, all conditions
must be completed prior to or concurrently with the establishment of the granted use.
The use granted by this permit must be established within 24 months of the delivery
of the countersigned permit to the Permittee.
3. Minor -changes -may be approved administratively by the Directors of Development
Services, Environmental Health, or Public Works upon receipt of a substantiated
written request by the applicant, or their respective designee, Prior to such approval,
�v,;rTlic—ation--qall be made by each Department or Division that the modification is
consistent with the application, fees paid and environmental determination as
(conditionally approved. Changes deemed to be major or significant in nature shall
require a_f_ormal application for amendment.
4. If any use for which a use permit has been granted is not established within two
years of the date of receipt of the countersigned permit by the Permittee, the permit
shall become null and void and reapplication and a new permit shall be required to
establish the use.
5. The terms and conditions of this permit shall run with the land and shall be binding
upon and be to the benefit of the heirs, legal representatives, successors, and
assigns'of the Permittee.
FINDINGS:
Section 1: Environmental Findings.
A. An Initial Study - was completed in compliance with the California
Environmental Quality Act identifying potentially significant environmental
effects that the project may have. Provisions and the design of the project and
I
the conditions added to the project will mitigate such effects to a level of
insignificance; and
B. The design of the proposed project improvements will not cause
environmental damage to fish, wildlife, or their habitat; and
r
C. The Planning Commission has independently reviewed, analyzed and
considered the proposed Negative Declaration with mitigation measures prior
to making its decision on the project, and the Negative Declaration reflects
the independent judgement of the County of Butte; and
Section 2: Zoning Ordinance Findings.
A. The proposed use will not impair the integrity and character of the zone in
which the land lies, and that the use would not be unreasonably incompatible
with, or injurious to, surrounding property, or be detrimental to the health and
general welfare of the persons residing or working in the neighborhood, or to
the general health, safety, and welfare of the residents of the County as
supported by the following facts:
1. The project site is located in an area that has few residential uses and,
a limited potential for additional new residential uses, and
2. The use will not generate any noise, significant light, or traffic that
would conflict with adjacent land uses; and
3. The use will not create any aesthetic impacts due to its location
adjacent to four high-voltage power lines and support towers; and
B. The proposed project is a Secondary Use under the Grazing and Open Land
General Plan Land Use designation and is conditionally consistent with the
U (Unclassified) Zoning District.
Section 3: Action.
A. Subject to the findings indicated in Sections 1 and 2.of this report, move to
approve the Use Permit for SMART SMR of California (d.b.a. NEXTEL
Communications) on APN 041-220-064. for a communications tower.
Approval shall be subject to the following conditions:
B. Conditions of Approval:
1. Limit soil work to periods of dry weather between April 15 to November
15. Mulch protect, Hydro -seed, or otherwise stabilize the soil on all
areas that have been disturbed or have been cleared of vegetation and
are of erodible material, or submit an Erosion Control Plan using best
management practices to the Department of Public Works prior to
issuance of building permits. (MM)
2. All outside lighting shall utilize cut-off shielding so that no direct
illumination will leave the project site. (MM)
3: The project site shall be developed in -accordance with the approved
project site plan and the conditions contained herein. Said site plan is
on file in the Planning Division, is identified as "Exhibit B" and dated
8/26/97 and is incorporated herein by this reference.
4. Prior to issuance of building permits, obtain a Grading Permit, if
required, from the Department of Public Works.
5. Construction, installation or development of structures or facilities on
the parcels/lots. sha!! Comply with the lGtest California Fire Safe
Regulations, (Public Resources Code 4290),,and all other applicable
State and County codes, ordinances and regulations in effect at the
time of application for improvement permits.
6. Prior to the issuance of the Use Permit, prove, to the satisfaction of the
Director of Public Works, that the parcel of the subject application is'
a legal parcel.
7. Prior to the issuance of building permits a plan for a permanent
solution for drainage shall be submitted to and approved by the
Department of Public Works. The drainage plans shall specify how
drainage waters shall be detained on-site and/or conveyed to the
nearest natural or publicly maintained drainage channel or facility and
shall provide that there shall be no increase in the peak flow runoff to
said channel or facility.
8. Applicant must also comply with all other applicable State and local
statutes, ordinances and regulations.
9. The applicant shall paint the top 50 ft. of the cellular antenna tower
with an orange and white striped pattern for easy identification from
the air.
10. 'Prior to construction of any facility, the operator of the facility shall
submit a site plan to the Butte County Agricultural Commissioner for
comment and send a notification letter to all aerial agricultural
applicators registered in the County I nforming them of the site location
and tower height.
11. All facilities that are not in continual use for a period of six months
shall be removed from the site and the site shall be returned to its
original condition or use.
12. Obtain a grading permit fromthe Department of Public Works prior to
issuance of building permit.
13. Install a flashing red light on the top of the tower.
I hereby declare under penalty of. perjury that I have read the foregoing conditions,
that they are in fact the conditions which were imposed upon the granting of this use permit,
and that I agree to abide fully by said conditions.
Dated: 7 J,�/�l� L,
Applicant
NOTE: Issuance of this Use Permit does not waive requirement of obtaining Building and
Health Department permits before starting construction, nor does it waive any other
requirements.
Butte ounty Planning Commission Chairman
CC: Land Development Division
Building Division
Health Department
Department of Forestry
Smart SMR of California - proposed Negative Declaration with mitigation
measures regarding environmental impacts and Use Permit for a
communications tower on property zoned "U" (Unclassified) located on the east
side of Table Mountain Blvd., approximately 1 mile south of Cottonwood Road,
identified as APN 041-220-064, north of Oroville. (SB) (UP98-05) (VIDEO)
A video of the site was shown. Mr. Betts gave a brief summary of the project. Same
type of tower as the previous hearing. He asked the Commission to add a condition
stating "A grading permit must be issued by the Department of Public Works prior to
issuance of building permits."
Chairman Lambert also wanted to add the same two conditions in the previous permit
regarding notification and removal.
Commissioner Mooney said this tower should be red or orange and white striped.
Commissioner Cage asked the location of the tower.
Mr. Betts said where it has already been graded. There is a dirt road entrance. .
The hearing was opened to the public.
Mr. Simpson, representative of SMART, explained construction and grading for the
tower. He said they do not intend to install whip antennas here. 100 ft. towerr wit with
antenna panels. He asked that the dates in Condition 1 be changed to dry periods
the provision to prepare an erosion control plan using best management practices to be
submitted to Public Works.
The hearing was closed.
Commissioner Leland wanted high contrast painting on the tower.
It was moved by Commissioner Leland, seconded by Commissioner Mooney, and
unanimously carried to approve this request with the corrections and additions of the
conditions as follows:
FINDINGS.
Section 1: Environmental Findings.
A. An Initial Study was completed in compliance with the California
Environmental Quality Act identifying potentially significant environmental
effects that the project may have. Provisions and the design of the project
and the conditions added to the project will mitigate such effects to a level
of insignificance; and
B. The design'of the proposed project improvements will not cause
environmental damage to fish, wildlife, or their habitat; and
n ni i== rni INTY PLANNING COMMISSION MINUTES - NOVEMBER 13, 1997 0
C. The Planning Commission has independently reviewed, analyzed and
considered the proposed Negative Declaration with mitigation measures
prior to making its decision on the project, and the Negative Declaration
reflects the independent judgement of the County of Butte; and
Section 2: Zoning Ordinance Findings.
A. The proposed use will not impair the integrity and character of the zone in
which the land lies, and that the use would not be unreasonably
incompatible with, or injurious to, surrounding property, or be detrimental
to the health and general welfare of the persons residing or working in the
neighborhood, or to the general health, safety, and welfare of the
residents of the County as supported by the following facts:
1. The project site is located in an area that has few residential uses
and a limited potential for additional new residential uses; and
2. The use will not generate any noise, significant light, or traffic that
would conflict with adjacent land uses; and
3. The use will not create any aesthetic impacts due to its location
adjacent to four high-voltage power lines and support towers; and
B. The proposed project is a Secondary Use under the Grazing and Open
Land General Plan Land Use designation and is conditionally consistent
with the U (Unclassified) Zoning District.
Section 3: Action..
A. Subject to the findings indicated in Sections 1 and 2 of this report, move
to approve the Use Permit for SMART SMR of California (d.b.a. NEXTEL
Communications) on APN 041-220-064 for a communications tower.
Approval shall be subject to the following conditions:
B. Conditions of Approval:
Limit soil work to periods of dry weather between April 15 to
November 15. Mulch protect, Hydro -seed, or otherwise stabilize the
soil on all areas that have been disturbed or have been cleared of
vegetation and are of erodible material, or submit an Erosion
Control Plan, prepared by a Civil Engineer or other qualified
professional, using best management practices to the Department
of Public Works prior to issuance of building permits. (MM)
2. All outside lighting shall utilize cut-off shielding so that no direct
illumination will leave the project site. (MM)
n BUTTE COUNTY PLANNING COMMISSION MINUTES - NOVEMBER 13, 1997 0
3. The project site shall be developed in accordance with the approved
project site plan and the conditions contained herein. Said site plan
is on file in the Planning Division, is identified as "Exhibit B and
dated 8/26/97 and is incorporated herein by this reference.
4. Prior to issuance of building permits, obtain a Grading Permit, if
required, from the Department of Public Works.
5. Construction, installation or development of structures or facilities
on the parcels/lots shall comply with the latest California Fire Safe
Regulations, (Public Resources Code 4290), and all other.
applicable State and County codes, ordinances and regulations in
effect at the time of application for improvement permits. .
6. Prior to the issuance of the Use. Permit, prove, to the satisfaction of
the Director of Public Works, that the parcel of the subject
application is a legal parcel.
7. Prior to the issuance of building permits a plan for a permanent
solution for drainage shall be -submitted to and approved by the
Department of Public Works. The drainage plans shall specify how
drainage waters shall be detained on-site and/or conveyed to the
nearest natural or publicly maintained drainage channel or facility
and shall provide that there shall be no increase in the peak flow
runoff to said channel or facility.
8. Applicant must also comply with all other applicable State and local
statutes, ordinances and regulations.
9. The applicant shall paint the top 50 ft. of the cellular antenna tower
with an orange and white striped pattern for easy identification from
the air.
10.. Prior to construction of any facility; the operator of the facility shall
submit a site plan to the Butte County Agricultural Commissioner for
comment and send a notification letter to all aerial agricultural
applicators registered in the County informing them of the site
location and tower height.
11. All facilities that are not in continual use for a period of six months
shall be removed from the site and the site shall be returned to its
original condition or use.
12. Obtain a grading permit from the Department of Public Works prior
to issuance of building permit.
13. Install a flashing red light on the topof the tower.
Pi iTTF (-ni iNTY PLANNING COMMISSION MINUTES - NOVEMBER 13, 1997 0
KNKA463
y
;.',.,FCc
Op`
0 08/16/2001
Federal Communications Commission
Wireless Telecommunications Bureau
Radio Station Authorization
•
Name of Licensee:
Call Sign
File.Number .
Print Date
Attention: NETWORK COMPLIANCE, GA361REG
SACRAMENTO VALLEY LIMITED PARTNERSHIP
KNKA463
Structure Hgt to Tip
(meters)
08/16/2001
Market Number
Channel Block
ONE VERIZON PLACE
CMA215
B
ALPHARETTA GA 30004-8511
Sub -Market Designator
0
SID
0294
Market Name
1209136
Chia, CA
Address
Effective Date
Five Yr Build -Out Date
Expiration Date
County
06/17/1988
KHSL 1700 BRUCE ROAD
01/22/2008
SITE INFORMATION
Location
Latitude
Longitude
Ground Elevation
(meters)
Structure Hgt to Tip
(meters)
Antenna Structure
Registration No.
1
39-43-59.6 N
121-47-13.9 W
80.1
95.1
1209136
Address
City
County
State Construction Deadline
KHSL 1700 BRUCE ROAD
CHICO
BUTTE
CA
Antenna: 1 Azimuth (degrees from true north)
.0°
45°
90'
135' 180°
225'
270°
315°
Antenna Height AAT (meters)
-87.5
-214.1
-145.0
58.6 108.7
113.4
109.2
94.2
Transmitting ERP (watts)
2.590
39.170
91.890
54.090 6.360
0.190
0.190
0.190
Antenna: 2 Azimuth (degrees from true north)
0°
45'
90•
135' 180'
225'
270°
315'
Antenna Height AAT (meters)
-87.5
-214.1
-145.0
58.6 108.7
113.4
109.2
94.2
Transmitting ERP (watts)
0.190
0.190
0.190
7.'640 57.950
91.870
30.400
1.750
Antenna: 3 Azimuth (degrees from true north)
0°
45°
900.
135' 180°
225°
270°
315°
Antenna Height AAT (meters)
Transmitting ERP (watts)
-87.5
74.670
-214.1
14.230
-145.0
0.330
58.6 108.7
0.190 0.190
113.4
0.750
109.2
19.190
94.2
76.190
Antenna: 4 Azimuth (degrees from true north)
0°
45'
90°
135° 180°
225°
270°
315'
Antenna Height AAT (meters)
-87.5
-214.1
-145.0
58.6 108.7
113.4
109.2
94.2
Transmitting ERP (watts)
99.970
99.970
99.970
99.970 99.970
99.970-
99.970
99.970
KNKA463 • 081162001 1
SITE INFORMATION
Location
Latitude
Longitude
Ground Elevation
(meters)
Structure Mgt to Tip
(meters)
Antenna Structure
Registration No.
2
39 44 49.6 N
121-3&13.9 W
93.6
50.0
121-27-45.9 W
Address
City County
State
Construction Deadline
PG&E PARRADISE RADIO VAULT SKYWA
PARADISE BUTTE
CA
BUTTE .
Antenna: 1 Azimuth (degrees from true north)
0°
45°
90° -
135°
1800
225°
270'
31S°
Antenna Height AAT (meters)
31.2
-296.1
-83.9
186.4
338.2
352.4
338.0
143.8
Transmitting ERP (watts)
100.000
100.000
100.000
63.000
20.000
7.000
20.000
63.000
Location
Latitude
Longitude
Ground Elevation
(meters)
Structure Mgt to Tip
(meters)
Antenna Structure
Registration No.
3
39-28-41.6 N
121-32-57.9 W
93.6
50.0
121-27-45.9 W
Address
City
County
State
Construction Deadline
5646 LINCOLN BLVD.
OROVILLE
BUTTE .
CA _
90°
Antenna: 1 Azimuth (degrees from true north)
0°
45°
9o°
135°
180'
225°
270°
315°
Antenna Height AAT (meters)
-32.9
-28.6
-62.6
0.6
31.6
31.7
30.5
25.1
Transmitting ERP (watts)
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
Location
Latitude
Longitude
Ground Elevation
(meters) .
Ground Elevation
(meters)
Antenna Structure
Registration No.
Structure Mgt to Tip
(meters)
39-33-03.6 N
Antenna Structure
Registration No.
4
39-39-02.6 N
121-27-45.9 W
Address
893.1
County State Construction Deadline
48.8
NELSON
BUTTE CA
Address
City
County
90°
State
180°
Construction Deadline
BLOOMER HILL
BERRY CREEK
BUTTE
19.0
GA
15.7
30.9
Antenna: 1 Azimuth (degrees from true north)
00
45°
90°
135°
180°
225°
270°
315°
Antenna Height AAT (meters)
342.6
347.5
182.5
397.5
606.2
623.2
703.9
486.7
Transmitting ERP (watts)
22.080
22.080
22.080
22.080
22.080
22.080
22.080
2 O80
Location
Latitude
Longitude
Ground Elevation
(meters) .
Structure Mgt to Tip
(meters)
Antenna Structure
Registration No.
5
39-33-03.6 N
121-46-57.9 W
Address
City
County State Construction Deadline
WATER DISTRICT ON NELSON ROAD
NELSON
BUTTE CA
Antenna: 1 Azimuth (degrees from true north)
0°
45°
90°
135°
180°
225°
270°
315°
Antenna Height AAT (meteor)
19.0
7.8
15.7
30.9
39.81
41.3
37.1
30.7
Transmitting ERP (watts)
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
KNKA463 06!16/2001 •
SITE INFORMATION
Location
Latitude
Longitude
Giouna Elevation
(meters)
Ground Elevation
(meters)
Structure Hgt to Tip
(meters)
Antenna Structure
Registration No.
6
39-25-03.6 N
121-41-18.9 W
121-51-40.9 W
30.5
49.7
54.6
Address
42.7
City County
State
Construction Deadline
0.25 MILE NORTHWEST OF UNION HIGHS
BIGGS
BUTTE
City
CA
County
Antenna: 1 Azimuth (degrees from true north)
0°
45'
90'
136'
180•
226'
2700
3161
Antenna Height AAT (meters)
39.9
32.8
35.5
51.4
52.7
54.6
54.7
49.4
Transmitting ERP (watts)
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
Location
Latitude
Longitude
Giouna Elevation
(meters)
Structure Hgt to Tip
(meters)
Ground Elevation
(meters)
Structure Hgt to Tip
(meters)
Antenna Structure
Registration No.
7
39-44-03.6 N
121-51-40.9 W
Address City County
54.6
Construction Deadline
42.7
CA
1012016
-0°
Address
90°
City
180°
County
270°
Construction Deadline
Chico Iron Works 1300 Nord Ave.
Chico
-119.9
-88.8
BUTTE
--:::State
550.0
CA
140.5
Transmitting ERP (watts)
63.100
Antenna: 1 Azimuth (degrees from true north)
0°
450
90°
135°
180'
225°
270°
315°
Antenna Height AAT (meters)
8.8
-126.2 -48.4
45.7
58.2
59.8
53.8
48.9
Transmitting ERP (watts)
5.010
40.160 911.2101
57.420
9.960
0.710
0.200
0.230
Antenna: 2 Azimuth (degrees from true north)
0'
45'
90°
135°
180°
2250
270°
315'
Antenna Height AAT (meters)
8.8
-126.2 -48.4
45.7
58.2
59.8
53.8
48.9
Transmitting ERP (watts)
0.200
0.200 0.790
11.920
61.230
91.290
36.860
4.570
Antenna_ 3 Azimuth (degrees from true north)
0°
45'
90'
135•
180•
225'
270'
315•
Antenna Height AAT (meters)
8.8
-126.2 -48.4
45.7
58.2
59:8
53.8
48.9
Transmitting ERP (watts)
78.230
20.080 1.780
0.200
0.200
2.340
22.970
81.690
Antenna: 4 Azimuth (degrees from true north)
0°
45°
90°
135'
180°
225'
270'
315'
Antenna Height AAT (motors)
11.5
-123.4 -45.6
48.51
61.0
62.5
56.5
51.7
Transmitting ERP (watts)
99.990
99.990 99.990
99.990
99.990
99.990
99.990
99.990
Location
Latitude
Longituda
Giouna Elevation
(meters)
Structure Hgt to Tip
(meters)
Antenna Structure
Registration No.
8
39-49-10.6 N
121-35-25.9 W
747.4
38.1
Address City County
State
Construction Deadline
14147 LAKERIDGE COURT MAGALIA BUTTE
CA
Antenna: 1 Azimuth (degrees from true north)
-0°
45°
90°
135°
180°
225°
270°
315°
Antenna Height AAT (meters)
-100.3
-119.9
-88.8
136.4
326.1
550.0
343.3
140.5
Transmitting ERP (watts)
63.100
- 63.100
63.100
63.100
63.100
63.100
63.100
63.100
Control Points
Control Point Address City County State Telephone Number
No
1 255 PARKSHORE DRIVE FOLSOM SACRAMENTO CA 9163571000
,I F;7[�QWIN CELLULAR GEOGRAPHIC&ICE W�nSR�AVE BEEN COMBINED (LISTED BASIGN, MARKET NUMBER AND
LOCK, AND M 4 KET NAME): KNKN227, 3376 -CA 2, KNKA751 2548 - REDDING AND KNKN229 3438 -CA 8
is authorization does not convey to the licensee the right to receive protection from the capture of subscriber traffic, co-channel interference or
rstacent-channel interference in any area outside of the authorized cellular geographic service area (CGSA) of the system. Moreover, any
cility authorized
he with a service area boundary (SAB) extending into the CCGSA of any other operating cellular system on the same channel
lock, reguardless of when such other cellular system was authorized, Is subject to the following condition: In the event that the licensee of the other
Ilular system requests that the SAB of the facilities authorized herein be removed from its CGSA, the licensee herein must reduce transmitting
ower or antenna height (or both) as necessary to remove the SAB from the CGSA, unless written consent from the licensee of the other cellular
ystem, allowing the SAB extension to remain, is obtained.
ONDITIONS of GRANT
Wect to the provisions of the Communications Act of.1934, as amended, subsequent acts, treaties, and all regulations herefore or hereafter made.
y this Commission, and further subject to the conditions and requirements set forth in this authorization, the licensee hereof is authorized to use and
pe the radio transmitting facilities herein described. This authorization shall not vest in the licensee any right to operate the station nor any right
n the use of the frequencies designated in the authorization beyond the term hereof, nor any other manner than authorized herein.
either this authorization nor the right granted herein shall be assigned or otherwise transferred to any person, firm, company, or corporation except
y specific authorization of the Commission.
Project Description:
Verizon Wireless proposes to install an emergency generator at their existing wireless
communication facility on Table Mountain Boulevard in Oroville, CA. The facility has
an approximately 100' high lattice tower with antennas from multiple wireless service
prove
Surrounding properties are agricultural in nature. The installation of the generator at this
existing communication facility compound will no result in any negative impact to plants
or animals or have any significance to cultural, historical or scenic aspects.
A copy of the existing Use Permit is attached. Additionally, please find information on
the proposed generator (Generac SD030, or similar) and a Statement of Exhaust
Emissions for the Diesel Fueled Generator.
COMMUNICATION LOG
SITE NUMBER:o�
EPIC
WdRELEtSS GROUP ANC.
Sent/ Via
Transmittal
Epic Wireless Group, Inc.
381 S. Lexington Dr. Suite 103
Folsom, CA 95630
Phone: (916) 984-5926
Fax: (916) 984-3866
❑ U.S. Postal Service ® Express Delivery ❑ Courier .. ❑ Blueprint Company
❑ Verizon Inter -office Mail ❑ Faxed ❑ Faxed and Hard Copy to follow ❑ Other
To: Steve Troster
Butte County Development Services
7 County Center Drive
OrovWe, CA 95965
From: Brad Kortick
Date: January 13, 2006
Items Transmitted: Zoning Application
For Site Named: Forebay
Comments: Please find the attached check #5459 & 5398 in the amounts of $202.00 and $3,550.50
and plans for the above referenced site.
Respectfully,
Greta Valencia
916-984-5929
Greta.Valencia@epicwireless.net
❑ Urgent ® For Your Review ❑ Reply ASAP ❑ Please Comment
The above information is confidential information intended only for the viewing and use of
the intended recipient. Any unauthorized review; use, communication, dissemination,
distribution or copying of this information is strictly prohibited. If you receive this in error,
please call the above number and the mail the original to the above address. Thank You.
V
Brad Kortick
From: Michelena, Mark [MMichelena@buttecounty.net]
Sent: Monday, October 31, 2005 11:17 AM
To: Brad Kortick
Subject: RE: Verizon Wireless Projects
Brad,
Please find my answers below. I hope they help. Verizon Wireless just relecently received a -Use Permit for
adding an emergency generator in the Magalia Area (UP 05-12). The included a project narrative, detail
information on the type of generator, a sound study for the type of generator proposed and site plans. If you
would like any of this information as examples, please let me know and I will mail them to you.
Mark Michelena, Senior Planner
Butte County Department of Development Services
Planning Division
7 County Center Drive. Oroville. CA 95965
530-538-7376, FAX: 530-538-7785
From: Brad Kortick[mailto:brad.kortick@epicwireless.net]
Sent: Monday, October 31, 2005-10:45 AM
To: Michelena, Mark
Subject:.Verizon Wireless Projects
Hi Mark, You had corresponded with Ken Stockero on Sept. 29 regarding several Verizon Wireless projects. I
will be completing these five files and have a few questions. These five applications will be additions of
cabinets and. generators to existirig wireless sites.
The sites are
APN 041-220-064 Table Mountain'Road, Use Permit
040-520-045, 4842 Media Way, Minor UP
025-180-036, 2147 Hwy. 70, Use Permit
006-400-056, 3902 Esplanade, Use Permit
047-100-191, 15082 Hamilton Nord Cana Way, Minor Use Permit
The following pertains to checklist requirements for application submittals As long as no additional
collocations are being done (only additional ground equipment and generators), the following applies.
2. Are fees to change soon? - Not at this time.
3. Are the 35 11" X 17" drawings suitable if they contain the detail requested? Yes, as long as it includes a
location map showing the whole parcel.
5. Is a transparency required of site plan? No.
10/31/2005
How much detail do you want for the equipment? You should provide as much detail as you would if there
was a collocation involved.. (Elevations, descriptions, locations, detailed site plan showing existing equipment
and proposed equipment), -
-9. Visual photo simulations may not show much because of the change will be simply equipment additions on
the ground. Are they needed? No. Since it is only ground equipment.
11. Alternative site selections are probably unnecessary. Not necessary.
12. Do you need a service are map for the 20 miles. surrounding due to the nature of these applications? No.
13. Same as above for search ring? No.
14. Tower failure will not be an issue with this application. 'No.
15. Not a tower project.
16. Notice to other carriers? No.
18. RF/EMF report No.
19. No landscaping plans proposed No.
20. Is notice required to Agriculture Commissioner if no change proposed outside of the existing compound?
No.
21. Airport influence not necessary, in my opinion as all equipment mounted on ground. No.
These questions are so I can assemble the application correctly the first time. I appreciate your help and let
me know if you have any questions
. ° Brad Kortick
Epic Wireless Group, Inc.
381 S. Lexington Dr., Suite 103
Folsom, California 95630
Tel. (916) 984-5924
Fax (916) 984-3866
Epic
w o R C 6.. ■ Q a o w ..Mobile (916) 798-0079
10/31/2005
County of Butte
Oroville, California
GENERAL CLAIM
CLAIMANT: Epic Wireless Group Inc
ADDRESS: 381 South Lexington -Dr, Suite 103 6
/0/y/
CITY & STATE: Folsom, CA 95630
rI ATG nC rl AIRA• nil MMR
SUMBIT CLAIM TO DEPARTMENT RECEIVING GOODS OR SERVICES
DATE REC'10
DESCRIPTION OF CLAIM (DESCRIBE FULLY TO AVOID DELAY)
AMOUNT
SUB. OBJ
REFUND CLAIM - ATR #91995, Receipt #443574, Check #5398:
INV NO.
Application: UP 06-11..-.___J
PAID
RETAINED
REFUND
Development Services
$ 2,970.00
$ 480.00
$ 2,490.00
Land Development
$ -
$ -
$ -
Environmental Health
$ -
$ - 1
$ -
CDF/Fire
$ -
$ -
$
Agricultural Department
$ -
$ -
$ -
NOD/NOE Clerk's Filing Fee
$ 36.00 1
$ -
$ 36.00
TOTAL
$ 3,006.00
$ 480.00
$ 2,526.00
:.............................................................I...
:::::::::::::::::::::::::::.:::BKEAKDQW)��:::::::::::::::::.:::::::::::::::::::BUD.GET:::
ACCOUNT
------
..............
.::A-K0.UNT::
Development Services
440001
4210900
$ 2,490.00
Land Development
440004
4611700
$ -
Environmental Health
540003
.4614901
$ -
CDF/Fire
0100
4617240
$ -
Agricultural Department
460001
4612200
$ -
NOD/NOE
470001
46123191's
36.00
TOTALI
1 $ 2,526.00
1 $ 2,526.00
I, the undersigned, declare under penalty of pepury tnat the services or arncles aalmea nave oeen perrormeo or aenverea, ano Inal uns
claim is true and correct as stated.
Dated this day of 006; at Q&WAL
I, the undersigned, hereby certify that, to the best of my knowledge, the services or articles specille�above have been performed or
delivered and that there is a Budget Appropriation or Specific Board Approval (Check one) for the same.
Dated this day of 2006, at Oroville Calif.
Department Head or Authorized Deputy
Dept SEE Exp.
Code BREAKDOWN Code PAYABLE FROM FUND
DO NOT WRITE BELOW THIS LINE
- AUDITOR'S USE ONLY
DEPT & SUB.
PROJ
SUB. OBJ
CLAIM NO.
INV NO.
INV. DATE
ENCUMB.
GROSS AMT.
Claimant - Submitted for your approval/signature. Please return signed form to:
Development Services Department
Accounts Receivable
7 County Center Drive
Oroville, CA 95965
1121
11 -
Butte County Department of Development Services,
TIM SNELLINGS, DIRECTOR I PETE CALARCO, ASSISTANT DIRECTOR
7 County Center Drive
Oroville, CA 95965
(530) 538-7601 Telephone
(530) 538-2140 Facsimile ,
www.buttecounty.net/dds
ADMINISTRATION " BUILDING " PLANNING
9/1/2006
Epic Wireless Group, Inc.
ATTN: Regina
381 South Lexington Dr., Suite 103 ,
Folsom, CA 95630
RE: Permit No. UP 06-11 APN#041-220-064
On 12/8/2005, a deposit was made in the amount of $3006.00, of which $480.00 was
retained. Please sign, date, and return the enclosed claim form to this office. Once we
receive the claim form, we will then process your refund in -the amount of $2526.00.
Should you have any questions, please contact this office Monday -through Friday, 8:00
a.m. to 4:00 p.m., at 538-7601.
Sincerely,
Diane Lewellen
Account Clerk, Senior
Administrative Division
enclosure
UP 06-11.1tr
County of Butte
Oroville, California
GENERAL CLAIM
CLAIMANT: Epic Wireless Group Inc
ADDRESS: 381 South Lexington Dr, Suite 103
CITY & STATE: Folsom, CA 95630
DATE OF CLAIM: 9/1/2006
SUMB/T CLAIM TO DEPARTMENT RECEIVING GOODS OR SERVICES
DATE REC'C
DESCRIPTION OF CLAIM (DESCRIBE FULLY TO AVOID DELAY)
AMOUNT
SUB. OBJ
REFUND CLAIM - ATR #91995, Receipt #443574, Check #5398:
INV NO.
Application: UP 06-11
PAID
RETAINED
REFUND
Development Services
$ 2,970.00
$ 480.00
$ 2,490.00
Land Development
$ -
$ -
$ -
Environmental Health
$ -
$ -
$ -
CDF/Fire
$ -
$ -
$
Agricultural Department
$ -
$ -
$ -
NOD/NOE Clerk's Filing Fee
$ 36.00
$ -
I $ 36.00
.
TOTAL
$ 3,006.00
$ 480.00
$ 2,526.00
................................................................................
)
::::::::::::KWi::::::::::::::
: BUDGET:::
ACC0UN
..............
:::AMOUNT::
Development Services
440001
4210900
$ 2,490.00
Land Development
440004
4611700
$ -
Environmental Health
540003
4614901
$ -
CDF/Fire
0100
4617240
$ -
Agricultural Department
460001
4612200
$ -
NOD/NOE
470001
4612319
$ 36.00
TOTAL
$ 2,526.00
$ 2,526.00
I, the undersigned, declare under penalty of perjury that the services or articles claimed have been performed or delivered, and that this
claim is true and correct as stated.
Dated this day of 2006, at Calif.
Signature of Claimant
I, the undersigned, hereby certify that, to the best of my knowledge, the services or articles specified above have been performed or
delivered and that there is a Budget Appropriation or Specific Board Approval (Check one) for the same.
Dated this day of 2006, at Oroville Calif.
Department Head or Authorized Deputy
Dept SEE Exp.
Code BREAKDOWN Code PAYABLE FROM FUND
DO NOT WRITE BELOW THIS LINE
- AUDITOR'S USE ONLY
DEPT & SUB.
PROJ
SUB. OBJ
CLAIM NO.
INV NO.
INV. DATE
ENCUMB.
GROSS AMT.
Claimant - Submitted for your approval/signature. Please return signed form to:
Development Services Department
Accounts Receivable
7 County Center Drive
Oroville, CA 95965
County of Butte
Oroville, California
GENERAL CLAIM
CLAIMANT: Epic Wireless Group Inc
ADDRESS: - 381 South Lexington Dr, Suite 103
CITY & STATE: Folsom, CA 95630
DATE OF CLAIM: 8-11-06
SUMBIT CLAIM TO DEPARTMENT RECEIVING GOODS OR SERVICES
DATE REC'C
DESCRIPTION OF CLAIM (DESCRIBE FULLY TO AVOID DELAY)
AMOUNT
CLAIM NO.
REFUND CLAIM - ATR #91995, Receipt #443574, Check #5398:
INV. DATE
Application: UP 06-11
PAID
RETAINED
REFUND
Development Services
$ 2,970.00
$ 480.00
$ 2,490.00
Land Development
$ -
$ -
$ -
Environmental Health
$ -
$
$ -
CDF/Fire
$ -
$
$
Agricultural Department
$ -
$
$ -
NOD/NOE Clerk's Filing Fee
$ 36.00
$ -
$ 36.00
TOTAL
. $ 3,006.00
$ 480.00
$ 2,526.00
...............................................................................................
BKEAKDOWN ........... :...::
...................................................
BUDCET:::ACCOUNT
..............
.............
: AMOUNT-:
...............
Development Services
440001
4210900
$ 2,490.00
Land Development
440004
4611700
$ -
Environmental Health
540003
4614901
$ -
CDF/Fire
0100
4617240
$ -
Agricultural Department
460001
4612200
$ -
NOD/NOE
470001
.4612319
$ 36.00
TOTAL
$ 2,526.00
$ 2,526.00
I, the undersigned, declare under penalty of perjury that the services or articles claimed have been performed or delivered, and that this
claim is true and correct as stated.
Dated this day of , 2006, at Calif.
Signature of Claimant
I, the undersigned, hereby certify that, to the best of my knowledge, the services or articles specified above have been performed or
delivered and that there is a Budget Appropriation or Specific Board Approval (Check one) for the same.
Dated this day of 2006, at Oroville Calif.
Department Head or Authorized Deputy
Dept. SEE Exp.
Code BREAKDOWN Code PAYABLE FROM FUND
DO NOT WRITE BELOW THIS LINE - AUDITOR'S USE ONLY
DEPT & SUB.
PROJ
SUB. OBJ
CLAIM NO.
INV NO.
INV. DATE
ENCUMB.
GROSS AMT.
Claimant - Submitted for your approvallsignature. Please return signed form to:
Development Services Department
Accounts Receivable
7 County Center Drive
Oroville, CA 95965
0
Project Log/Activity She,
Project #
APN#
7dl- '5
CIO 4�-
AEC)
t4tlD
6-0
0.0
COUNTY OF BUTTE
AUDITOR'S CERTIFICATE AND TREASURER'S RECEIPT
OROVILLE, CA
RECEIVED FROM PLANNING
BAG:. 316
FUND
DESCRIPTION TITLE
DEPOSIT DATE: IW
FOR 1927
RECEIPTS: 443574 443660
-
PLANNING APPL FEES GENL
APN 041-22!:084, EPIC: V1JRELESS; UP 06-11
APN 031-281-920; SERE !PERE WEBS; MUP 0-01
:APN 027-120-094, 015; RON GRAVES; LLA -1%
FUND DEPT ACCT
CODE CODE CODE
ATR NO
DATE
CASH
CODE
0010 . 440031 4210900 101001
� 2,970.00 ✓
$ 555.00
113012006
AMOUNT
3,616.77 ✓
L-SUMU 0010
.440004 4611700 101001
524.00
Project Number
Amount of Fee
APP-) 041=220-084: EPIC WRELESS; UP 06-11
$ 165.00
AP.N 027-12(1-014,015; RON GRAVES, LLA 06-10$
359.00
ENI MONMENTAL HLTH GENL 0010
5400+03 4614901 101001
416.010
Project Number.
Amount of Fee
APN 041-220-084;-EPIC''►AARELESS; UP 0&11
APN 027-920-094,,015 RON GRAVES; LLA O6-�$
+,
'$ 2.14.00
,
FIRE PLNG APPL FtE . FIRE PROTECT 0100
4517240 101001
401.00
Project. Number
Amount of Fee
APN 049-220-084; EPIC WRELESS; UP 05-19
$ 347.00
APN 027-120-014, 095; RON GRAVES; LLA 06-'j$
- $ 54.00
NODINOE CLERK'S FILING FE GENL 001 !
. 470001 .4612319 101001
72.00
,($36) Project Number .
Amount of Fee
APN 041-220-064; EPIC'AIRE! ESS; UP 00-i i
$ 36.00
615rReN ORAVE95, •
$ 36.00
AGRICULTURE . AG FEE- 0010
46=1 4612200 101001
65.00
Project Number
of Fee
APN 041-220-084; EPIC WRELESS; UP 06-19
_Amount
$ 32.53
APN 027-i2G-W4, Oi6;.RON GRAVES; LLA 06A
$ 32.50
$3L �
6�7a ' 380 • r�o5 j (-�en rYc�reT TT .V,0"77
APPROVED BY:
RECEIVED BY:
AUDITOR -CONTROLLER
TREASURER
9*0
/,/,' ? s -"
whitp--treasurer pink=-auffitor
canahry---d positor golden rmd=Fale
9*0
/,/,' ? s -"
0
Friday, January 27, 2006
$0.00 1
Development Services
PLANNING DIVISION Ver.- 1.0
I $0.00
$0.00
Counter
F -
DDS Planning
$2,970.00
Person Gwyn
(General Fund)
Payment Date
V/27/2006
FPublic Works
$165.00
I(Land Development)
Receipt Number
443574'
Environmental H
$202.00
Received From
'Epic Wireless
S
CDF (Fire Department)
-$347.00
Applicant
sarn
NOD NOE
$36.00
(Recording F
Aunt Minnie
-$0.00- 1
Application Number
UP 0 6-11
1, 500 or $2,000
$1
$
or In Reference To
Planning Re
$0.00
Parcel Number
041-220-064
Check�Numb 15398/5459
Total Received r— $3,752.50
Total , Fees $3, 752.50
Fish/Game
$0.00 1
ALUC
(Airport Land
I $0.00
$0.00
Non Sufficient
Funds ($25.00 Fee)
Cell Tower
($2500.00)
$0.00
Public Sales i $0.00 1
Other: I $32.50
COUNTY OF BUTTE
p p fOFFICIAL RECEIPT
Received from
The Sum o
For iii
Received-_
CASH ❑
CHECK
DAVGO BU5114E55 FORMS - (530) 743.8511 FORM 84702
ISSUING RECEIPT
443574
C� 3 20
xpr
cq,,$ x.752- �a
J: Ocli-z2,->-66
Received By- L "' F—
Title pc -,,t, —1 -
By
COUNTY; OF BUTTE y 436193
OFFICIAL RECEIPT
�7 200
OFFICE 08 DEPARTMENT ISSUING RECEIPT
Received from �'�/ " ( Qk
The Sum ofICV
For r( ( QW -Z-2--D -66,�
Received: Received By
CASH ❑ Tide
CHECK By
BUSINESS FORMS • (530) 743-8577 roan tWUe �v �
*
• 1 � � ,- + � Verizon Site
UP 01-02
�� �•`, UP98-05
`1
X041-2 02 064
\�♦ � ^• ,fir i'� -'✓
°-
w.
�c.
- l t N3,�
Ask
GENEA L NOTES
I. DRAWINGS ARE NOT TO BE SCALED. WRITTEN DIMENSIONS TAKE PRECEDENCE.
AND THIS SET OF PLANS IS INTENDED TO BE USED FOR DIAGRAMMATIC
PURPOSES ONLY, UNLESS NOTED OTHERWISE. THE GENERAL CONTRACTOR'S
SCOPE OF WORK SHALL INCLUDE FURNISHING ALL MATERIALS, EQUIPMENT,
LABOR, AND ANYTHING ELSE DEEMED NECESSARY TO COMPLETE
INSTALLATIONS AS DESCRIBED HEREIN.
2. PRIOR TO THE SUBMISSION OF BIDS. THE CONTRACTORS INVOLVED SHALL VISIT
THE JOB SITE AND FAMILIARIZE THEMSELVES WITH ALL CONDITIONS AFFECTING
THE PROPOSED PROJECT, WITH THE CONSTRUCTION AND CONTRACT
DOCUMENTS, FIELD CONDITIONS AND CONFIRM THAT THE PROJECT MAY BE
ACCOMPLISHED AS SHOWN PRIOR TO PROCEEDING WITH CONSTRUCTION. ANY
ERRORS, OMISSIONS, OR DISCREPANCIES ARE TO BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT/ENGINEER. AND PROJECT MANAGER. (C.C.)
3. THE GENERAL CONTRACTOR SHALL RECEIVE WRITTEN AUTHORIZATION TO
PROCEED WITH CONSTRUCTION PRIOR TO STARTING WORK ON ANY ITEM NOT
CLEARLY DEFINED BY THE CONSTRUCTION DRAWINGS/ CONTRACT DOCUMENTS.
4. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE PROJECT DESCRIBED
HEREIN. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL
CONSTRUCTION MEANS, METHODS. TECHNIQUES. SEQUENCES AND PROCEDURES
AND FOR COORDINATING ALL PORTIONS OF THE WORK UNDER.THE CONTRACT.
5. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS
ACCORDING TO MANUFACTURER'S/ VENDOR'S SPECIFICATIONS UNLESS NOTED
OTHERWISE OR WHERE LOCAL CODES OR ORDINANCES TAKE PRECEDENCE.
6. ALL WORK PERFORMED ON PROJECT AND MATERIALS INSTALLED SHALL BE IN
STRICT ACCORDANCE WITH ALL APPLICABLE CODES. REGULATIONS. AND
ORDINANCES. CONTRACTOR SHALL GIVE ALL NOTICES AND COMPLY WITH ALL
LAWS. ORDINANCES. RULES. REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC
AUTHORITY, MUNICIPAL AND UTILITY COMPANY SPECIFICATIONS. AND LOCAL
AND STATE JURISDICTIONAL CODES BEARING ON THE PERFORMANCE OF THE
WORK.
7. GENERAL CONTRACTOR SHALL PROVIDE AT THE PROJECT SITE A FULL SET OF
CONSTRUCTION DOCUMENTS UPDATED WITH THE LATEST REVISIONS AND
ADDENDUM'S OR CLARIFICATIONS FOR THE USE BY ALL PERSONNEL INVOLVED WITH THE
PROJECT, STAMPED ORIGINALS SHALL NOT BE USED FOR REDLINE PURPOSES.
B. THE STRUCTURAL COMPONENTS OF THIS PROJECT SITE/ FACILITY ARE NOT TO BE
ALTERED BY THIS CONSTRUCTION PROJECT UNLESS NOTED OTHERWISE.
9. DETAILS INCLUDED HEREIN ARE INTENDED TO SHOW END RESULT OF DESIGN.
MINOR MODIFICATIONS MAY BE REQUIRED TO SUIT JOB CONDITIONS OR
SITUATIONS, AND SUCH MODIFICATIONS SHALL BE INCLUDED AS PART OF THE
SCOPE OF WORK.
10. SEAL PENETRATIONS THROUGH FIRE -RATED AREAS WITH U.L LISTED OR FIRE
MARSHALL APPROVED MATERIALS IF APPLICABLE TO THIS FACILITY AND OR
PROJECT SITE.
11. PROVIDEA PORTABLE FIRE EXTINGUISHER WITH A RATING OF NOT LESS THAN 2-A
OR 2-AIOBC WITHIN 75 FEET TRAVEL DISTANCE TO ALL PORTIONS OF THE PROJECT
AREA DURING CONSTRUCTION.
12. THE CONTRACTOR SHALL MAKE NECESSARY PROVISIONS TO PROTECT EXISTING ,
IMPROVEMENTS. EASEMENTS. PAVING. CURBING. ETC. DURING CONSTRUCTION.
UPON COMPLETION OF WORK, CONTRACTOR SHALL REPAIR ANY DAMAGE THAT
MAY HAVE OCCURRED DUE TO CONSTRUCTION ON OR ABOUT THE PROPERTY.
13. CONTRACTOR SHALL ENSURE THAT GENERAL WORK AREA IS KEPT CLEAN AND
HAZARD FREE DURING CONSTRUCTION AND DISPOSE OF All DIRT, DEBRIS.
RUBBISH AND REMOVE EQUIPMENT NOT SPECIFIED AS REMAINING ON THE
PROPERTY. PREMISES SHALL BE LEFT IN CLEAN CONDITION AND FREE FROM PAINT
SPOTS. DUST, OR SMUDGES OF ANY NATURE. SITE SHALL BE SECURED, SAFE AND
CLEAN UPON COMPLETION OF WORK EACH DAY.
14. THE ARCHITECTS/ENGINEERS HAVE MADE EVERY EFFORT TO SET FORTH IN
THE CONSTRUCTION AND CONTRACT DOCUMENTS THE COMPLETE SCOPE OF
WORK.CONTRACTORS BIDDING THE JOB ARE NEVERTHELESS CAUTIONED THAT
MINOR OMISSIONS OR ERRORS IN THE DRAWINGS AND OR SPECIFICATIONS SHALL
NOT EXCUSE SAID CONTRACTOR FROM COMPLETING THE PROJECT AND
IMPROVEMENTS IN ACCORDANCE WITH THE INTENT OF THESE DOCUMENTS. THE
BIDDER SHALL BEAR THE RESPONSIBILITY OF NOTIFYING (IN WRITING) THE
ARCHITECT/ENGINEER OF ANY CONFLICTS. ERRORS. OR OMISSIONS
PRIOR TO THE SUBMISSION OF CONTRACTOR'S PROPOSAL IN THE EVENT OF
DISCREPANCIES THE CONTRACTOR SHALL PRICE THE MORE COSTLY OR EXTENSIVE
WORK. UNLESS DIRECTED OTHERWISE.
15. THE CONTRACTOR SHALL FURNISH SANITARY FACILITIES PRIOR TO START OF WORK.
16. ALL SITE CONSTRUCTION, AND SITE CONDITIONS FROM MOBILIZATION TO DEMOBILIZATION
SHALL BE IN STRICT ACCORDANCE WITH CAL-OSRA, 24 HOURS EACH DAY.
VICINITY MAP
•
w'lreless
SITE NAME:
FOREBAY
TABLE MOUNTAIN BLVD.
. 'ORO-VILLE, CA
PROJECT N U M B E R# 2004026777
LOCATION NUMBER # 115337
REVISIONS
NO DESCRIPTION
DATE
r
1 90% CONST. DOC'S
PROJECT SUMMARY
PROJECT
CONSULTANTS
8-9-05
SHEET INDEX
'
11-28-05
CONSTRUCTION MANAGER
SURVEY
T-1 -
TITLE SHEET
1
SITE NAME: FOREBAY -
JEREMY JORDAN
GEIL ENGINEERING
EPIC WIRELESS
1226 HIGH STREET
SITE SURVEY
SITE ADDRESS: TABLE MOUNTAIN BLVD.
381 S. LEXINGTON OR. X103
AUBURN, CALIFORNIA 95603
C->
jy
OROVILLE. CA
FOLSOM. CA 95630
Tel. (530) 885-0426
-
eeejjj
(916) 704-0898A-1
AS BUILT SITE PLAN
SCALE
OWNER: EARL & EVA GARDENER
_
-
5700 EVE'S LANE
A-1.1
SITE PLAN
CHICO. CA 95928
APPLICANT: VERIZON WIRELESS
-
A-2
DETAILS SHEET
APPLICANTS ADDRESS: 255 PARKSHORE DRIVE
-
JECT, .
FOLSOM, CA 95630
E-1
ELECTRICAL SHEET
A
ASSESSORS PARCEL NUMBER: 041-220-064
JURISDICTION: GLENN COUNTY
PROJECT
DESCRIPTION:
E-2
GROUNDING SHEET
CURRENT ZONING: A-2-40
CONST. TYPE: 5-N (NON-COMBUSTIBLE)
A. NEW 3OKW GEN. LOCATED ON AN OUTSIDE CONC. PAO
OCCUPANCY: N.A.
STAND-BY GENERATOR
B.NEW AUTOMATIC TRANSFER SWITCH
NOTE:
DRIVING DIRECTIONS
C. NEW CONI. EQUIP. PAD
D. NEW ELEc./TELCO RACK
ELECTRICAL
CONTRACTOR SHALL FIELD VERIFY
ALL CALCULATIONS
AND CONDUIT. ANY CHANGES
1. Start out going SOUTHWEST on PARKSHORE OR toward FOLSOM BLVD.
SHALL BE APPROVED BY THE ARCHITECT PRIOR
2. Tarn RIGHT onto FOLSOM BLVD.
TO CONSTRUCTION.
-
3. FOLSOM -BLVD becomes AMERICAN RIVER BRIDGE.
4. AMERICAN RIVER BRIDGE becomes FOLSOM AUBURN RD.
S rru SNI EI im;aii nn t111Xi:: wownn rQ6901A RB:
'
6. Turn LEFT onto DOUGLAS BLVD.
7. Turn RIGHT onto E ROSEMLLE PKWY.
8.Turn RIGHT onto GALLERIA BLVD.
9. Merge onto CA -65 N ria the ramp on the LEFT.
10. CA -65 N becomes CA_ 70 N.
I. Turn RIGHT onto CA-20/CA-70/9THI ST.
_
12. Turn LEFT onto CA-20/CA-70/8 ST. Continue to follow CA -70 N.
13, Take the MONTGOMERY ST exit- EXIT 47.
14. Turn RIGHT onto MONTGOMERY ST/CR-B2. -
15. Turn RIGHT onto MYERS ST/CA-70 BR.
16. End of O—Alle. CA US
REVISIONS
NO DESCRIPTION
DATE
BY
1 90% CONST. DOC'S
1-18-05
VRT
2 REV 90% CONST. DOC'S
8-9-05
CDH
3 REV 90% CONST. DOC'S
11-28-05
PLS
PROJECT
FOREBAY
TABLE MOUNTAIN BLVD.
OROVILLE, CA
CONTACTS .
��.
verlLn
wireless
255 Porkshore Drive
F_o t solo, cD t i Porn i D 95630
CONTACT: Rick Griggs
PH:' (916)952-4648
FAX: (916) 357-2537
Peek Site—Com
853 Lincoln Way, Suite 106 —
0 Aub u, California 95603
Phone
Phone (916) 947-3155
E—Mail topeek®garlic.com
SEAL
NO. C 38407
m. os/TDAa
'r OF CAL LE�
(APPROVALS
DATE I BY:
DRAWN BY: VRT
CHECKED BY:
SHEET TITLE
TITLE
SHEET NUMBER
T- i'
U)
>
,
r �
M 3
I
d�
N
tt
n
�c
tt
N
tt
w
o i
p
D
O
0
pd0
m
•
/
o
\,
y AA
OA
O
o
ti
D
N
O
D
n
o m
o [^
vNumv
N
\>
V. \
l
vm
C
u -1
a Or
m
O
O v
0 \
\
baAo
TA
�.• r
I.
p
\
r0•r
m m
O
1�
D
� m� m
\
\ m m x
\
100.6 (TOP PIPE)
' c In o n .
\
>
99.8' (TOP TOWER)
• `1'S
0 >
99.3' (TYP. 3 PANELS 0 2 -SECTORS)
y
\plo z m y
95.8
r7• m
/
y
95.5
• n
n \SO
SSS /
m
89.7
85.9' (TYP. 4 PANELS 0 3 -SECTORS)
m
� oo. �
p00\/
85.0
•
84.4
O
83.7
82.3
r /
n
80.8
m m m y
73.8
(TYP.' 2- PANELS)
't
n 5 rm- /
m
F••3
69.2
m
om0
m O O
m '>
O
'
y'
►�
29.8
x z
/
33.2
r
m
d
/
LI
�/^-�J
D
Z
C N N
Oy1 OD S� 1y --z -mm 6-
Z r -
0>r^
CTD COS
np D
ll
/'
O
O
z N O
VI O m g
>C c
AP
0Z �.
m�
Z
A 'm
D Nbmm> 7p
oz m
-n -i
O
O
y
D
O
N
m -.0 z�Z, z-'
..l Ooz
N
Zm
apo
N
/
~
N
v
N'
1A
r•1 UN Dm� Z Nm
uta
mN
O--D11Z
ZZ�
O
Gp
Z' D
2 Cea 000xy m 20
otiz G 00
;480
�O r=.1
D
r�
A K
LTJ
/
00D mSm
0>
pC
?m
Om
D Z -m
O DO >y, 0 Z 0
A
Z
O N
m
O�
>
O mm
00l m0 O y O
O10
m
I
/
�n
mNRe
m
IArG
iOmn
m .ZyOO
A -K>Z
O ; l't 4� mVIOGy
m m ?9Cm C
r5•N
my
NUt 0
N0
0
m
0m
O>m
m
K
m O Or Dy m
N
Dr
m
ZC C
O
r•1 W
y'
0
A
�_ Z
K
6] � O D N a�
Z Z
� p _i
O
,'DZ
I O
-Z
> ;mO Oi
Dm
D
N
0
y
;: N. 2- "m N
~S
r
Dyy
T
('•� Cti
D N4 a
>
OZ
cc
Zc m
A
lYM-•J
F+
a n
O
Tm
c' a m
4 �i
m
O
o m O
�~
z
m
I
I1�1
m ]nl ra•10 O
o
nOVCi
Z
CO
l -J II
ZD
>O >oT
Imj10
NZ
C
O
O
NN y,nO.
N
<C
GO Z
m
O :
n
n
> >
o
-
T
j
ADO -O 01/Im rrz z z
<yymm ° > ° >
D� nmm=:0
°o mm
". OD
�'
V1)
< SJD-'m0
RI Jc N3°
A �
Dm
'm lo,
2950
1
Q
(,
-
v
^i
9
ACG _ -."..O
°'•<vn �c�
o
,p °
o ,'9.3
m'm'
.^. .^-
c .;,
z R'3: m,3°m
Acmm-c
0
.o
�'n°v �mt°Di
o<-ni xmz on o'.o
O O
K
O
o A�
O
oz
-'
Inm155
i0i
omoil_^D
A
n0..A m
O Z 02�. EZ0 FZo D
p
O\
aV
1°\
o-
A O -v)
DOAZOK
c
J?O�- ZOOa°
gyp �bo
,Q3
r •Oo3ANa
y
p~
_�o
9.
n VNin NNH w
^�Onc
E
R m
�ry
,n O� Y.
9P5Oc-
('
OL
G
- ti° 4.. G.. 0
V
--P'
^doQ
°
aC
O
014
OCmZN
cDym
`�
1
o,
Oo a Oo
A00 uN U N%
N Fn
V
A<A,nm�Vnl
'P
A^onON
O
m
.{41
Oi+O v0 O 4
3aa F
Z
v AO
-�o
ADO
m
X U
AA zcco
i min
� •
a
°n `°°n `rv''1_n ^,
O
O m,
�mm
u,
Z, vtA A'Z
.
o
4
"- ''< S 2
^nen
Y
'
Op
Z D
!'rCK
O
C 0 9 9 Z y 0
rte•, 'Ommoxc
m
Q
OZ
m
N
Z-rmmD Ni
.en
SIS
m0
Z'
Z
`�
Nr AONZ
`a xi
mo
D
S..
rt
UVIZOD
Dy
mOiAz=1n0
9M
I
l>2Oo
m
0
a
DOOrA.IZ
n
ut� n m
ti
3
m
-IO ZO>o DO
Gm
•
-3
z c
°mac 0
m
o
�A>Dov
vInmp D
0mz OZo
'
0
CNOm Pm4
Dy0>0m
on3a DD
Ni�J
=tizrm'IOCS
'co
C
rrl�/rl
•d
>0 9m
(7
oann
o
0 moo
ZinZ
_
•
�Az
00>A
Z
r9.IZ
m
^
ti 'I�S�O
D
>
°'
0
°
z=Z
o
a
S
REVISIONS
FOREBAY
N<hill
tt
Surveyor
REVNRI-O6-05 As -Built
DEPT
APPROVED
DATE
TABLE
MOUNTAIN BOULEVARD
GEIL ENGINEERING
A&C
REV
OROVILLE, CA
•
[NCIMECMNO • BUNVLTINC •MANNING
RE
REV
1226 RICH STREET
AUBURN, CAUFORNIA 03003
RF
O
INT
OHen•: 13301 883-0128
I— 13301 82x1300
Rn
EE IN
PLOT• PLAN AND
REV
OPS
SITE TOPOGRAPHY
'255 PARKSHORE DRIVE
FOISOM. CALIFORNN 95630 916-357-2581
EE\OUT
1
P 1 P.G.& E. EASEMENT
ER 1758/OR/137
E) ACCESS ROAD/VERIZON WIRELESS ACCESS
\ 02
2• � 9�
APN:041-220-064 \
,rte y � •, � -
\ \ 9
S"9� •� 9090
p \
EE'PROJECT AREA
•� ENLARGEMENT
OVERALL SITE PLAN
SCALE: NTS.
(E) GROUND
(E) GATE
(E) CABLE TRAY /
/
/d (E) CONC. SLAB \
Q . (E) ELEC. CABINET \ \
d � \
(E) LATTICE TOWE
n a \ -
_ i
G�Z_
1.10
i'
/ (E) SKID MOUNTED (E) FENCELINE (TYP.) \
(E) ICE BRIDGE CABINETS \
\ (E) USIOUITEL ELEC. METER \
\ J` (E) GATE
\ \ \E) TELCO. BOX \ \
\ `\ a / l
y (E) ELEC. BOX /
LLL /
(E) SERVICE LE /
DESCRIBED LEASE AREA
/
AS BUILT SITE PLAN
SCALE: 1/4' = 1'-e'
'
1 90% CONST. DOC'S
1-18-05
VRT
2 REV 90% CONST. DOC'S
8 -9 -OS
CDH
3 REV 90% CONST. DOC'S
11 -28 -OS
PLS
REVISIONS rao ocsereanor+ WE By
PROJECT
FOREBAY-
TABLE MOUNTAIN BLVD.
OROVILLE, CA
CONTACTS
9_
MOM'?
wireless
255 eorkshore Dr ve
Folsom, coliForn o 95630
CONTACT:. Rick Griggs
PH: �(916) 952-4648
FAX- (916) 357-2537
Peek - Site— Com
853 Lincoln Way, Suite 106
Auburn, California 95603
Phone (916) 947-3155
E -Mail tapeek®9arlic.com
SEAL
NO. C 33b1
gf.....
''
:�
APPROVALS
DATE BY:
DRAWN BY: VRT
CHECKED BY:
SHEET TITLE
AS BUILT SITE PLAN
SHEET NUMBER
A-1
•
NEW' I.L.C. ELEC
CABINET
NEW UNISTRUT—
MOUNTED UTILITY
RACK
NEW TELCO CA
(E) CABLE TRAY
� (E) CABINETS/
(E) GROUND BOX
(E) LATTICE TOWE
¢ \\ �(E) GATE .
NEV U//G ELEC. CONDUITS 6
(SEE DETAIL 3/E-1) '
O\
(E) CAB.
\ / (E) CAB. O \
(N) CAB. \
CAB ..i.. \ .
\,-NEV 12' THICK CONC. SLAB W/
.N) CAB., "G Q \ NID REBAR SLAB. @ 12' O.C. EACH WAY @
j (N) CAB.
E METER V
/ (E) ICE BRIDGE
�\ o
\ (E) ELEC
\ (E) SERVICE POLE /
\
('E')"METER MAIN (E) 100 AMP VERIZON METER MAIN
TO BE REPLACED WITH
\ - NEW 200 AMP METER MAIN
\ j /
ENLARGED SITE PLAN
SCALE: 1/4' = 1'-0'
LEASE )
REVISIONS
NO UESCRIPIIaN DATE By
1 90% CONST. DOC'S 1-18-05 VRT
2 REV 90% CONST. DOC'S 8-9-05 CDH
3 REV 90% CONST. DOC'S 11-28-05 PLS
PROJECT
FOREBAY
TABLE MOUNTAIN BLVD.
OROVILLE, CA
CONTACTS
Ilk
ver�Lon
wireless
255 Porkshore Drive
Folsom, coltfornla 95630
CONTACT: Rick Griggs
PH: (916) 952-4648
FAX .( 916) 357-2537
Peek Site—Com
853 Lincoln Way, Suite 106
0 Auburn, California 95603
Phone (916) 947-3155
E—Mail iopeek®garlic.com
SEAL
'ppessi .
"'. Sr •.,..CIV IL. ,.'�y2 .'
'•f Or CAL%i..'
APPROVALS
DATE BY:
DRAWN BY: VRT
CHECKED BY: •
SHEET TITLE
SUP PLAN
SHEET NUMBER
A-1. 1
NEW 60KW DIESEL
POWER 4
DIMENSIONS FOR CONDUIT
TELCO CABINET
GENERATOR
NOTE:
6' SUB -BASE NOT SHOWN
TYP. EQUIP. CABINET
1/2' M.B.,NUT, t WASHERS
SCALE: N,T.5.
METAL EQUIPMENT CABIN
PROVIDE 5/8' HILTI
TTP. OF (5) PER 51DE
KWIK BOLT-III'S WITH
4' EMBEDMENT TTP. OF
SEE MFGR. SPECS
(4) ONE EACH CORNER
6' THK. CONC. SLAB WITH #A
(10) TOTAL
ICBG ER -1385
REBAR AT 12' OC. EACH WAY
-
DIESEL FUEL TANK
$14 REBAR TY "
I
BELOW
o
a
PROVIDE 1/2' HILTI KWIK
-
Q o I
I !b. o
BOLT -111'5 WITH MIN. 31/2'
EMBEDMENT TTP. OF (5)
PER SIDE (10) TOTAL
ICBG' E5R-1385
ao
- 12' THICK CONC. SLAB
^
W/ tt4 REBAR AT 12'
D.C. EACH WAY P it
v
`
MID SLAB.
'
SECTION A -A
NOTE:
PROVIDE A 2A:20BC FIRE EXTINGUISHER
INSTALLED WITHIN 75 FEET OF ANY
,
PUMP, DISPENSER, OR FILL PIPE
OPENING. PER UFC, SEC. 5201.q
5'-4'
-
A /
A
Il
NEW 60KW DIESEL
GENERATOR
!
1
DIESEL FUEL TANK I
_.
ib
\ 1
BELOW. (210 GALLON.)
12' THICK CONC. SLAB W/ 94
3
/
REBAR AT 12' O.C. EACH.WAY
MID SLAB.
—
PLAN VIEW
60KW GENERATOR
DETAILS
SCALE: N.T.S.
CONCRETE PAD SPECS.
CONCRETE MIX DESIGNS SHALL CONFORM TO UBC SECTION Ig06
PORTLAND CEMENT SHALL BE TYPE II AND CONFORM TO A5TM 0150
CONCRETE SHALL HAVE A MIN. 25 DAY COMPRE551VE STRENGTH OF
2500 PSI. tt4 REBAR AT 12" O.G. EACH WAY MID SLAB REINFORCEMENT
FOR SLAB ON.GRADE
FIELD VERIFY LOCATIONS t
POWER 4
DIMENSIONS FOR CONDUIT
TELCO CABINET
PLACEMENT
NOTE:
6' SUB -BASE NOT SHOWN
TYP. EQUIP. CABINET
DETAILS
SCALE: N,T.5.
METAL EQUIPMENT CABIN
PROVIDE 5/8' HILTI
PREFAB EQUIPMENT B
KWIK BOLT-III'S WITH
4' EMBEDMENT TTP. OF
SEE MFGR. SPECS
(4) ONE EACH CORNER
6' THK. CONC. SLAB WITH #A
ICBG ER -1385
REBAR AT 12' OC. EACH WAY
AT MID. SLAB TYP.
$14 REBAR TY "
I
o
a
;�
Q o I
I !b. o
CABINET BOLT DOWN DETAIL
SCALE: N.T.5.
REVISIONS
NO DESMON DATE I
1 90% CONST. DOC'S 1-18-05 VRT
2 REV 90% CONST. DOC'S 11-28-05 PLS
PROJECT
FOREBAY
TABLE MOUNTAIN BLVD.
OROVILLE, CA
CONTACTS
ver�Ln
wireless
255 Porkshore.Drive
Folsom, collFornlo 95630
CONTACT:
PH: (916) 952-4648
FAX: ( 916) 357-2537
Peek Site—Com
853 Lincoln Way, Suite 106
Auburn, California95603
Phone (916) 947-3155
E—Mail topeek@gorlic.com
SEAL
,'�'•
a. )
::
•.... �F CAFE,:
APPROVALS
DATE BY:
DRAWN BY: PLS VRT
CHECKED BY:
SHEET TITLE
DETAILS
SHEET NUMBER
A-2
REVISIONS
NO DESCRIPTION IDATE BY
1 90% CONST. DOC'S 1-18-05 VRT
121 REV 90% CONST. DOC'S 11 -28 -OS PLS
PROJECT
FOREBAY
TABLE MOUNTAIN BLVD.
OROVILLE, CA
CONTACTS
rmp
wireless
255 Porkshore Drive
Folsom, coliFornio 95630
CONTACT:
PHI (916) 952-4648
FAX: (916) 357-2537
Peek Site—Com
853 Lincoln Way, Suite 106
Auburn, Californiani 95603
Phone (9 16) 947-3155
E -Mail iapeek@garlic.com
SEAL
C3 1
•.,.qrf ., .crv......... `
APPROVALS
DATE I BY:
DRAWN BY: PLS VRT
CHECKED BY:
SHEET TITLE
CTRICAL PLAN
SHEET NUMBER
E- ,
PCS PANEL MULE
NorEs:
1. EXCAVATE TO REQUIRED DEPTH
ELECTRICAL LEGEND
PANEL DE5IGNATNl1.-240/Ip VOLTS I WASE 3 WIRE SURFACE nTNO,Y FWN BREAKER�Y
wlT SEPARATE GROUND BUS 2P• X0A
" U110
STEI� Y TWA R
AA ,I� ,AA
NO. DESCRIPTION IE DESCRIPTION
� EXISTING
LOAD yn PO P01.5Iya yn LOAD
W.
120/240 WET
IPK 3wg
SERVICE
CR1,TCR
200/2MROCK Rn
A °••- ., 9
_ - _1, FL
ma mla I
2. VERIFY ALL TRENCHING REQUIREMENTS WITH SERVING UTILITIES.
3. CALL BEFORE YOU DIG!I CONTACT SERVING UTILITIES
® PANEL BOARD, SURFACE MOUNTED
ELI DRY TYPE TRANSFORMER
'
METER '
SPACE . - - - - SPACE- 2
3 SPACE SPACE 4
4• RESTORE GRADE TO ORIGINAL CONDITION OR BETTER.
5- RETURN ORIGINAL MATERIAL TO TRENCH, (TOP 12")
COMPACT TO 95% OF MAXIMUM DENSITY IN ACCORDANCE
WITH ASTM 0-1557.
5 SPACE SPACE c
7 SPKe - - - - SPACE a
10
9
SPACE - - - - - SPACE
NNEE
200 AYPC7P. NW
I od vu¢ I
fly¢ 91Q i
[,
�\ CIRCUIT BREAKER
II SPACE _ _ _ _ _ _ SPACE IZ
13
SPACE - - SPACE
I.
Z wt —I
12' MIN. COVER
IS
SPACE - - - - - - SPACE
.1
NOTE:
6 ML RED WARNING
20' MIN. SAND TAPE NIGH VOLTAGE'
NON -FUSIBLE DISCONNECT
�
7
SPACE - - - - SPACE
a
as six
swR ma 1
THIS BRAVING COKPLETED VITH
TELCO CONDUIT 12' ABOVE CONDUITS.
SWITCH, MOUNTED 54" A.F.F.
w
SPACE - - - SPACE
p
91¢ sPa
9•¢ 4¢ '
R
06 i= i1DDv2
ISA/I; �,.,�
INFORMATION PROVIDED BY OTHERS.
FINISH GRADE? ELECTRICAL CONDUIT -
'
_ //
III—I I—)
LEE) FUSIBLE DISCONNECT SWITCH, MOUNTED 54'A.F.F.
.
Ks TRANSIENT VOLTAGE SURGE SUPPRESSOR WITH
21 SPACe - - - SPACE n
n SPACE - - _ _ _ SPACE 2n
25
SPACE - - - - - SPACE
26
)
r t I I / /// III-
BUILT-IN FUSES, SURFACE MOUNTED
P
SPACE
SPACE - - - - BPE
2D
1 �`
suRa I 1M� 7
¢a0 - - - - - -
154 GFCI INSIDE CABINET
-)
•�y-
i= -I I2':'
NN'. III
DUPLEX OUTLET, SURFACE MOUNTED,
20 AMPS, 125 VOLTS, SINGLE PHASE
Z9 SPACE - - - SPACE 30
31 S - - n
SURGE PROPOSED VERIZON
PROTECTOR NO/2 RlD/2 I-)EOUIPnEEM
'
I-
33
_ S _ pyp ROWER CA&uET
Sd
TO EACH POWER
�_'"
4' 1
O JUNCTION BOX, SURFACE MOUNTED 18• A.F.F.
35 OFCI RECEPTACLE 200 Rin FUTURE
37
VERIZON
1W/S to OROLA) EOI—ENT
SPACE - - pn - ROWER C.•BI.0
3e
GNaTYP.
SCE ONE UNE OWGWUI
CABINET
MIN. I ISI Ul�i 1 NN.
I1
SK KEYED SWITCH, SURFACE MOUNTED
39 SPACE - - - - M
pn FUTURE VER
'�� Ew1 ENT
.1
_ _ ROwER CABINET
SPACE 20n
.2
PREWIRED ILC SCHEMATICe
E I
EXISTING U.C. CONDUITS DETAIL(E - 1
WALL MOUNTED, ENCLOSED, AND GASKETED
Q INDUSTRIAL INCANDESCENT FIXTURE WITH ONE
TOTAL—I!CTED VA:JS.M
D— __J.0___J.0_IT15.,,-, ;'RR"Fc`n nmaron"`1„
scnLe N.r.s.
DCMAND LOAD, VA,-16,o1Q „D,''�"'wD1os 111UN1O•D,TS)
-
SCALE: N.T.S.
100 AMP LAMP MOUNT 72- A.F.F.
EXPOSED WRING
HOME RUNS; MINIMUM 2#10 + I#IOG IN 3/4'
CONDUIT U.O.N.
_
t
A.F.F. ABOVE FINISHED FLOOR
GENERAL NOTES:
NEW 200 METER MAIN
NEW 200 AMP GENERAL ILC. (INTEGRATED LOAD CENTER).
U.O.N. UNLESS OTHERWISE NOTED
+ PROVIDE MIN. 36" WORK CLEARANCE
_AMP
(3) 03/0 TNWN CU IN 2'C. 200 AMP, 120/240 VOLT, I -PHASE, NEMA -31R, SEE MFGR. SPECS COMBINATION AUTOMATIC TRANSFER
IN FRONT OF PANELS/SERVICE EQUIPMENT
TO UTIL. SERVICE DEMAP.K POINT TO REPLACE (E) IOOA METER MAIN
SWITCH AUTOMATIC GENERATOR CONTROL, LOAD CENTER
WP WEATHERPROOF
VERIFY W/ UTIL. SERVICE PLAN
D15TRIgUTION, d SURGE 5UPPRE55ION
F ALL BREAKERS SHOWN SHALL BE RATED MIN.,
GFI GROUND FAULT INTERRUPTER
10,000 RMS SYMETRICAL AMPS, 240V AC MAX
CABINET
75 DEG. C. OR TO EXCEED AIC PROVIDED
5C4812ET
BY UTILITY, WHICHEVER IS GREATER
j;
ELECTRICAL NOTES
+ ALL WIRING SHALL BE RATED 75 DEG. C.
F200/2 1
I. ALL ELECTRICAL WORK SHALL CONFORM TO THE REQUIREMENTS SET
FORTH IN THE NATIONAL ELECTRICAL CODE (NEC) AS WELL AS
°e,APPLICABLE
STATE AND LOCAL CODES.
2. ALL ELECTRICAL ITEMS SHALL BE U.L. APPROVED OR LISTED AND
PROCURED PER SPECIFICATION REQUIREMENTS.
u3/0TNWN CU !
j
cli
3. THE ELECTRICAL WORK INCLUDES ALL LABOR AND MATERIAL
D 4CU GND I 2 C.
TYP. EACH POWERP° & iIrEg
DESCRIBED BY DRAWINGS AND SPECIFICATION, INCLUDING
CABINET SEE PLANINCIDENTAL
WORK, TO PROVIDE COMPLETE, OPEP.ATING AND
3 03/0 TNWN CU d
APPROVED ELECTRICAL SYSTEM.
.
I a 4 CU GND IN 2 C.
4. CONTRACTOR SHALL PAY FEES FOR PERMITS, AND BE RESPONSIBLE
'
3 01/0 TNWN CU !
FOR OBTAINING SAID PERMITS AND COORDINATION OF INSPECTIONS.
'
I 0 4 CU GND IN 2-C.
S. ELECTRICAL AND TELCO WIRING INSIDE A BUILDING SHALL RUN IN
(N) GENERATOR
NEW 30KW DIESEL GENERATOR
EMT OR SCHEDULE 40 PVC, PER PLAN. (AS PERMITTED BY CODE)
02 BCW GND.
120/240 VOLT I -PHASE NEMA -3R. I
6. ELECTRICAL AND TELCO WIRING OUTSIDE A BUILDING AND EXPOSED
W/MAIN CIRCUIT BREAKER i
TO WEATHER SHALL BE IN WATERTIGHT GALVANIZED RIGID STEEL ,
CONDUITS OR SCHEDULE B0 PVC (AS PERMITTED BY CODE) AND,
'
—
RE -FEED (E) VERIZON (MOTOROLA) I
WHERE REQUIRED, IN LIQUID TIGHT FLEXIBLE METAL OR
NEW SERVICE GROUND
POWER CABINET
NONMETALLIC CONDUITS.
' 5/8'X 10' LONG COPPER CLAD GROUND ROD-
r - - ,
F - - j
7. BURIED CONDUIT SHALL BE SCHEDULE 40 PVC. U.O.N.
OR 20' LIFER CENTERED WITHIN BOTTOM 3'
OF MIN. 20' LONG 12' 50. CONC. ENVELOPE 1 r--- !
(E) IOOA METER MAIN 4
I i
PPC (COMBO. MANUAL
8. ELECTRICAL WIRING SHALL BE COPPER WITH TYPE XHHW, TNWN, OR
WHERE REQUIRED. (PER NEC ART. 250-) M I ':c-jI
l ';
I I TRANSFER 5WITCH 4 ;
THNN INSULATION, PER PLAN
( )'
I �
I DIST. PANEL) TO BE j
9. RUN ELECTRICAL CONDUIT BETWEEN ELECTRICAL UTILITY DEMARCATION
I
I I ABANDONED 4 REMOVED 1
POINT AND VERIZON WIRELE55 51TE ELECTRICAL PANEL/PEDESTAL
AS INDICATED ON T14I5 DRAWING. PROVIDE FULL LENGTH PULL ROPES.
I-
!
ORDINATE INSTALLATION WITH UTILITY COMPANY.
L y _ _ J
L _. i U _
1
10. RUN TELCO CONDUITS BETWEEN TELEPHONE UTILITY DEMARCATION
I
POINT AND VERIZON WIRELESS CELL 51TE TELCO SERVICE CABINET AND
EOUIPMENT CABINET(5) AS INDICATED ON T14I5 DRAWING. PROVIDE '
PROVIDE MINIMUM OF 30' COVERAGE
ONE LINE DIAGRAM
FULL LENGTH PULL ROPES AND TRUE TAPE IN INSTALLED CONDUITS.
OVER MAIN SERVICE CONDUITS.
e
I1.. WHERE CONDUIT BETWEEN CELL EQUIPMENT AND VERIZON WIRELE55 CELL
-
SCALE: N.T.S.
1
SITE ELECTRICAL PEDESTAL AND BETWEEN CELL EQUIP. AND VERIZON
WIRELESS CELL 517E TELCO SERVICE CABINET ARE UNDERGROUND, USE
'
PVC SCHEDULE 40 CONDUIT. ABOVE THE GROUND PORTION OF THESE
CONDUITS SHALL BE FLEXIBLE CONDUIT.
'
IL. ALL E6NUIPMENT SHALL HAVE NEMA 3R ENCLOSURE.
•
13. GENERATORS 4 AUTOMATIC TRANSFER 5WITCHE5 SHALL BE SUPPLIED
_
BY VER!ZON WIRELE55
14. CALL U.S.A. I -WO -642-2444 24 HOURS PRIOR TO COMMENCING
-
ELECTRICAL OR TELCO WORK.
'
15. CONTRACTOR SHALL COORDINATE WITH UTILITY COMPANY FOR FINAL
' -
AND EXACT WORK/MATERIAL5 REO. AND CONSTRUCT TO UTILITY
COMPANY ENGINEERING PLAN AND SPECIFICATIONS ONLY.
- N/A
4E4
16. CONTRACTOR SHALL FURNI514 AND INSTALL ALL CONDUIT PULLWIRES,
SCALE: N.T.S.
1
CABLE PULLBOXE5 CONC ENCASEMENT OF CONDUIT (IF OEO .)
TRANSFORMER PAb, BARRIERS, POLE RISERS, TRENCHING, BACKFILL,
-
AND INCLUDE ANY UTILITY COMPANY REO. IN SCOPE OF WORK
REVISIONS
NO DESCRIPTION IDATE BY
1 90% CONST. DOC'S 1-18-05 VRT
121 REV 90% CONST. DOC'S 11 -28 -OS PLS
PROJECT
FOREBAY
TABLE MOUNTAIN BLVD.
OROVILLE, CA
CONTACTS
rmp
wireless
255 Porkshore Drive
Folsom, coliFornio 95630
CONTACT:
PHI (916) 952-4648
FAX: (916) 357-2537
Peek Site—Com
853 Lincoln Way, Suite 106
Auburn, Californiani 95603
Phone (9 16) 947-3155
E -Mail iapeek@garlic.com
SEAL
C3 1
•.,.qrf ., .crv......... `
APPROVALS
DATE I BY:
DRAWN BY: PLS VRT
CHECKED BY:
SHEET TITLE
CTRICAL PLAN
SHEET NUMBER
E- ,
.MDED WIRE
42 AWG INSU744
.
TYP. 02 TINNED BCW (BARE COPPER WIRE)
U.G. GROUND RING @ MIN. 30' BELOW FINISH
TO COLLECTO
' GRADE, OR 6' BELOW LOCAL FR05T LINE
- TEST LOOP 12' BE1,08 6RADE PAX,
STAINLE55 STEEL HARDWARE
u2 AWG INSUANDED WIRE
EMPLOY AN OWNER APPROVED 3rd PARTY !PAID FOR BY OWNER)
TO ALLOK CLAP ON PETER AS RED.
(18-8 DOMESTIC) MIN.
TO MGB @ S
TEST FOR APPROVAL TO EITHER THE OWNER OR ARCHITECT/ENGINEER.
TTP. FINAL DOUBLE CRIMPED CONNECTIONS
LONG BARREION LUGS, TTP.
TYP. TWO HOLE LONG BARREL COMPRESSION
6ROIND ROD INSPECTION HELL CHRISTY
GROUNDING CAME —_
WITH (2) 5/1LOCK WASHERS
LOCK WASHERS.
—O —
FI4 BOX KITH ADAPTERS AND EXTENSION
r
SEE DETAIL 2/E-2
—O—
TYP. 5/8' DIA, . I01-0' LONG COPPER CLAD
• AS REO. AND 17210 CONC. LID COORDINATE
GROUND ROD, IB' BELOW FINISH GRADE, OR
-UD TO REBAR IN
6' BELOW LOCAL FROST LINE, WHICHEVER 15
SLAB MIN (2) PLACES
DEEPER. 10'-0' O.C. 14ARGER 05810.
INSTALLATION NITH OYPER I ABET '6ROUND'
SEE DETAIL 2/E-2
COAX GABLE
MONOPOLE FOUNDATION.
STRANDED WIRE TYP.
OR '6ROUND ROD'
GROUNDING K
APPLIED THAN WHAT 15 PROVIDED WITH THE MFGR. KIT.
(CONTRACTOR TO FURNISH).
-6RCUND
CONDUUCTOR o2 SOLID
TINFED BAFE COPPERO
O
O0
101
O O
00 C1
- . FINISH GRADE
�; \�• ;i �i :
V2 SOLID, TINNED, BARE
COPPER WIRE DOWNLEAD
CADWELD TO GROUND BAR
d TO U.G. GRUND RING.
HARGER GROUNDING BAR 33GBI14420 OR EQUAL'
W/INSULATORS B BRACKETS AS NEEDED.
MASTER GROUND BAR IMGBI n
SCALE: N.T.S. -
FROM ANTENNA PIPE MOUNT5 --—,
FROM COAX CABLE
GROUNDING KITS
LONG BARREL COMPRESSION LUGS, TYP.—
WITH (2) 5/16" BOLTS 6 LOCK WASHERS ""��
WITH 42 AWG INSULATED STRANDED 1g;-
JUMPER FROM WAVEGUIDE PLATE.
01
0 0
HARGER GROUNDING BAR O O
VGB114410 OR EQUAL W/INSULATORS
d BRACKETS AS NEEDED. _
02 AWG STRANDED COPPER WIRE
DOWNLEAD. RUN TO MGB @ BASE OF
ANTENNA SUPPORT STRUCTURE.
ANTENNA GROUND BAR (AGBI 4.
SCALE: N.T.S. E -
V2 AWG TO AG 02 AWG GND. (TYP. EA. SECTOR)
@ EA. SECTOR AGB (TYP. EA. SECTOR) e
PCS ANTENNA
tt2 AWG GND. ANT.
(TYP. EACH ANT)
GROUND KIT, TYP.
EACH COAX CABLE
COLLECTOR AGB e
COAXIAL CABLE
GROUND KIT
COAX CABLE
TO GND @ ANTENNA -N MGB LOCATED e
SUPPORT STRUCTURE NEAR MONOPOLE
. I /_/ .r_89 AWr,
TO MGB @ OUTSIDE
OF SHELTER
TYP. GROUNDING RISER DIAGRAM n
SCALE: N.T.S.
4ADKID -
CONNECT ION
TYPE '6Y'
COPPER CLAD STEEL 6Rouw0
POD 5/6' ROUND
AT 10' OC. AROUND EQUIPMENT
INSPECTION WELL /
GROUND ROD DETAIL e
SCALE: N.T.S.
N/A
SCALE: N.T.S.
92 AWG TO GR= BUS BAR AT -
EASE OF VERTICAL COAX CABLE RUN
BOND TO REBAP. IN
SLAB MIN (2) PEACES
GROUND PING —
DI5PECTIOH WELL
NEW MTO1ATIC TRANSFER SWITCH
NEW 02 TINNED DCH GRORID
RDIG. @ 30 BELCW GRADE.
NEW GPQRIDDIG RODS
(5/8' X 10 COPPEP CIADI
AT Hl- 10 O.C.
BOND TO ROW,, W
SLAB MIN (2) PlACES�
I �(OA%IA1 CABLE
GROUNDING PLAN DIAGRAM 6�
SCALE: N.T.S. -
EXISTING
WALL OR
POLE MOUNT
GROUND BAR
TWOROLE LONG BBL. TlB
BURNDY OR APPROVED E0.
COMPRESSION LW
ELEVATI GROUND BAR
3/841 1/2' HEX BOLT WITH LOCK
WASHER (ONLY ONE LOCK WASHER -
NOT STACKED TO COMPENSATE
FOR INCORRECT BOLT LENGTH)
HAVE ./- 4'TNREADS SHOWING
`NUT (TYPICAL) WITH
SPLIT LOCK WASHER
GROUNDING CAME - `EXP05ED DARE COPPER 15 NOT PERMITTED
SECTION 'A -A' FOR INSULATED CONDUCTORS, NO
INSULATION ALLOWED WITHIN THE
NOTE: COMPRESSION TERMINAL (TTPICAL)
'DOUBLING UP' BACK TO BACK OR 'STACKING ' OF CONNECTION 15 NOT PERMITTED.
COPPERSHIELD TO BE USED ON ALL LOCATIONS.
TYPICAL GROUND BAR
CONNECTIONS DETAIL
SCALE: N.T.S.
GROUNDING LEGEND
.
TYP. 02 TINNED BCW (BARE COPPER WIRE)
U.G. GROUND RING @ MIN. 30' BELOW FINISH
' GRADE, OR 6' BELOW LOCAL FR05T LINE
WHICHEVER IN DEEPER.
TYP, 02 TINNED BCW DOWN LEAD
EMPLOY AN OWNER APPROVED 3rd PARTY !PAID FOR BY OWNER)
TTP. CADWELD CONNECTION. SEE DETAIL 5/E-1
TEST FOR APPROVAL TO EITHER THE OWNER OR ARCHITECT/ENGINEER.
TTP. FINAL DOUBLE CRIMPED CONNECTIONS
TO INTERIOR HALO RING ONLY
TYP. TWO HOLE LONG BARREL COMPRESSION
-CADNELD TO (E) SITE GROUND
LUG, TWO (2) 5/16' DIA. BOLTS, 4 STAR
RING MIN (2) PLACES
LOCK WASHERS.
—O —
TYP. CADWELD INSPECTION WELL. TOTAL OF
r
SEE DETAIL 2/E-2
—O—
TYP. 5/8' DIA, . I01-0' LONG COPPER CLAD
GROUND ROD, IB' BELOW FINISH GRADE, OR
-UD TO REBAR IN
6' BELOW LOCAL FROST LINE, WHICHEVER 15
SLAB MIN (2) PLACES
DEEPER. 10'-0' O.C. 14ARGER 05810.
'
SEE DETAIL 2/E-2
GROUNDING NOTES
I. GROUNDING SMALL COMPLY WITH NEC ART. 250.
2. GROUND COAXIAL CAME SHIELDS MINIMUM AT BOTH ENDS L151NG
MANUFACTURERS COAX CABLE GROUNDING KITS SUPPLIED BY OWNER
3. IU5E 112 COPPER STRANDED WIRE WITH GREEN COLOR INSULATION FOR
ABOVE GRADE GROUNDING (UNLESS OTHERWISE SPECIFIED) AND 02
SOLID TINNED BARE COPPER WIRE FOR BELOW GRADE GROUNDING AS
INDICATED ON TRE DRAWING.
4. ALL GROUND CONNECTION TO BE BURNDT LONG BBL. COMPRESSION
TYPE CONNECTORS OR APPROVED EQUAL. CADWELD EXOT14ERMIC WELD 514ALL
BE USED WREN MAIN CONDUCTOR ADJOINS TWO BUS5 BAPS
UNLESS OTHERWISE INDICATED ON DRAWINGS.
DO NOT ALLOW BARE COPPER WIRE TO BE IN CONTACT WITH
GALVANIZED STEEL.
5. ROUTE GROUNDING CONDIUCTOR5 ALONG THE SHORTEST AND
STRAIGHTEST PATH POSSIBLE, EXCEPT AS OTHEP.W15E INDICATED.
GROUNDING LEADS SMCULD NEVER BE BENT AT RIGHT ANGLE.
ALWAYS MAKE AT LEAST 12' RADIUS BENDS. 06 WIRE CAN BE BENT AT
6' RADIUS WHEN NECESSARY.
6. BOND ANY METAL OBJECTS WITHIN 7 FEET OF NEW METALLIC EQUIPMENT
GROUNDING CONNECTION DETAIL t
5 7' OR FARTHER FROMCABINETS SHALL HAVE A DEDICATED DOWN CONDUCTOR
SCARE: N.T.S.IROUTED PDIRECTLY ERMITTED) O GROUND 1ZNG. (DAISY CHAIN 'SERIES' GROUNDING
_ �CA vao TO (E) SITE m@
P % MM (2) PLACES
/ \ Y
REVISIONS
NO DESCRIP00N DATE BY
1 90% CONST. DOVS 1-18-05 VRT
2 REV 90% CONST. DOC'S 11-28-05 PLS
PROJECT
FOREBAY
TABLE MOUNTAIN BLVD.
OROVILLE, CA
CONTACTS
v✓ei��n
wireless
255 Porkshore Dr1ve
FOISO"
, colIforn10 95630
CONTACT:
PHS c916> 952-4648
FA,
C 916> 357-2537
Peek Site -Com
853 Lincoln Way, Suite 106
Auburn, Californiani 95603
Phone (916) 947-3155
E—Mail topeek@garlic.com
SEAL
...PE.....
ryCC
oLN
Lai NO.0 3lA01 '��
.... OF CALF,
APPROVALS
DATE BY:
x
DRAWN BY: PLS VRT
CHECKED BY:
SHEET TITLE
CROUIV01NG PIAN
SHEET NUMBER
E— 2
7. SYSTEM GROUND RESISTANCE MUST BE 5 OHMS OR LESS. TO ACHIEVE T915
LEVEL OF RE515TANCE THE CONTRACTOR SHALL PURSUE ONE OF THE
FOLLOWING THREE OPTIONS:
a. CONNECT 10 EY15TING GROUNDING SYSTEM.
b. CONNECT TO BUILDING STEEL COLUMNS.
M.
d. INSTALL NEW CHEEMMINCAL RDING OD (5).
UPON COMPLETION OF THE GROUNDING INSTALLATION THE CONTRACTOR SHALL
EMPLOY AN OWNER APPROVED 3rd PARTY !PAID FOR BY OWNER)
CONDUCT A 'FALL OF POTENTIAL' TF�ST AND SUBMIT A REPORT OF SUCH
TO CONDUCT A 'FALL OF POTENTIAL TEST AND SUBMIT A REPORT OF SIKH
TEST FOR APPROVAL TO EITHER THE OWNER OR ARCHITECT/ENGINEER.
8. CONNECTIONS TO GROUND BAR5 SHALL BE MADE WITH TWO HOLE LONG BARREL-
COMPRE551ON TYPE COPPER LUGS AND KOPR514IELD PLACED BETWEEN LUGS AND
GROUND BAR.
-CADNELD TO (E) SITE GROUND
q. THE GROUND ELECTRODE SYSTEM SMALL CON515T OF DRIVEN
RING MIN (2) PLACES
GROUND RODS. TME GROUND RODS SHALL BE 5/6' . 10 COPPER CLAD STEEL.
SPACED AT f0' APART MAX. THE RODS SHALL BE
r
INTERCONNECTED WITH 02 SOLID TINNED COPPER GROUND WIRE
BURIED A MINIMUM 2-1/2 FEET BELOW TME SURFACE OF THE SOIL.
AN ONSITE INSPECTION BY OWNER SHALL BE REO. PRIOR TO ANY BACKFILL.
-UD TO REBAR IN
SLAB MIN (2) PLACES
10. ALL UNDERGROUND ELECTRODES SHALL BE BONDED TO STEEL
REINFORCING EMBEDDED IN THE CONCRETE SLAB AND CO CRETE
- C2 AWG WSIRATED
MONOPOLE FOUNDATION.
STRANDED WIRE TYP.
11. CONTRACTOR MUST APPLY BUTTL l ELECTRICAL TAPE AT ALL LOCATION. FOR
WEATHER -PROOFING OVER GROUND KITS. MORE BUTYL TAPE MAY NEED TO BE
APPLIED THAN WHAT 15 PROVIDED WITH THE MFGR. KIT.
(CONTRACTOR TO FURNISH).
_ �CA vao TO (E) SITE m@
P % MM (2) PLACES
/ \ Y
REVISIONS
NO DESCRIP00N DATE BY
1 90% CONST. DOVS 1-18-05 VRT
2 REV 90% CONST. DOC'S 11-28-05 PLS
PROJECT
FOREBAY
TABLE MOUNTAIN BLVD.
OROVILLE, CA
CONTACTS
v✓ei��n
wireless
255 Porkshore Dr1ve
FOISO"
, colIforn10 95630
CONTACT:
PHS c916> 952-4648
FA,
C 916> 357-2537
Peek Site -Com
853 Lincoln Way, Suite 106
Auburn, Californiani 95603
Phone (916) 947-3155
E—Mail topeek@garlic.com
SEAL
...PE.....
ryCC
oLN
Lai NO.0 3lA01 '��
.... OF CALF,
APPROVALS
DATE BY:
x
DRAWN BY: PLS VRT
CHECKED BY:
SHEET TITLE
CROUIV01NG PIAN
SHEET NUMBER
E— 2