Loading...
HomeMy WebLinkAboutB15-0621 (2)VINCI ASSOCIATES 61ruclura/ Cn9ineers March 19, 2015 Addy Electric Subject: Review of minimum footing requirements Project: (27) Module Photovoltaic Groundmount Installation (1 Array) Bill & Pat Olsen 118 Ridgeview Lane, Oroville, CA 95966 V&A Project No.: 12-3457 The purpose of this report is to provide a site specific analysis of the minimum footing requirements for the photovoltaic array groundtrac installation at 118 Ridgeview Lane in Oroville, CA 95966. Based upon our review of the 1 Photovoltaic Array, installed 3 modules high and 9 modules wide. The PV Array shall have a transverse spacing of approximately 6.58 feet on center and a longitudinal spacing of 7.58 feet maximum. Based upon a wind speed of 100 mph, Exposure C, it was determined that the minimum required footing depth is 32 inches minimum below grade for.a 12 inch diameter pier footing. The footing sizes are based upon the worst case loading due to horizontal and vertical wind loading. Refer to attached calculations and details for additional information. . Our professional services have been performed using the degree of care and skill ordinarily exercised under similar circu tances by reputable engineers practicing in this locality. No other warranty, express e o Implied, is made as to the professional options included in this report. We hope t 's ides you with the information you need at this time. Please call us if you have any u ns regarding this report. ES S/qy Sincerely, a ?A VINCI SSOCIATES No. 54411 Z Exp. 12/31/15 BUTTE �* J s .Vinci, S.E. COUNTY TgTFOFF�` MAR 2 3 2015 ense No. S-4411 DEVELOPMENT SERVICES PERMIT # tet' BUTTE COUNTY DEVELOPMENT SERVICES REVIEWED FOR CODE COMPLIANCE 175 E. WILBUR ROAD, STE 103 THOUSANDoDAKS, CA 91360 BY P 805.496-2100 • .f 805.496-2442 •. a vinci@vincise.com 4 lcS �! r'� �r DATE: 3/19/2015 VINCI $ :_ASSOCIATES SHEET:. Al PROJECT: Bill & Pat Olsen 61rucfural Cngineers JOB No.: 12-3457 ' 118 Ridgeview Lane 175 E. WILBUR ROAD, STE 103 . THOUSAND OAKS, CA 91360 ENGR.:, JRV Oroville; CA 95966 P 805.496.2100 • f805.496.'2442 • e Anci@VinciSE.com CLIENT: Addy Electric DESIGN DATA: WIND DESIGN CRITERIA: t s BASIC WIND SPEED _ 100 mph (ASCE 740. Risk Category l per Table 1.5-1 & Figure 26.5-1C) ' WIND EXPOSURE C, r GROUND SNOW LOAD _ 0 P' psf SOLAR MODULE ARRAY DATA ' Sloped Dimension of Array" _ 117:3 in , Angle of Array-. _ 20, degrees Slope of Array: _ A.1 0 ... , : 12 . . No. of, Modules in Transverse Direction _ 3• . No. of Modules in Longitudinal Direction = 9 Total No. of Modules in Project _ 27, ' Transverse Post Spacing _ 6.58 ft Longitudinal, Post Spacing = 7.58 ft Number of supports - Transverse Direction _ 2 Diameter of Pier "Footing - 12 in Number of Arrays Array Uniform° Load 2.8. psf SOIL DESIGN CRITERIA (Based upon Chapter 18 of CBC) " Allowable Soil Bearing Pressure = 1500 psf ' Allowable Soil Lateral Bearing = 200 ' pcf Allowable ShaffSkin Friction / Cohesion = 130 pcf AA- PROJECT Bill &Pat Olsen ' ° _. , CLIENT:'1'18.Rldgeview Lane'Orovllle CA `" V y PAGE DESIGN BY +"� A2.`=- �JRV,` 18.88 X95966 r. -1.21 -1.46 -1.31 -1.60 1.51 JOB NO.. X15 -3457':_M. w . DATE : j03/19/15'. REVIEW BY t5 "_°.. a - Wind Arial sis.for:Open Structure (Solar; Panels) Based on ASCE,7=2010 2013 CBC F (kips) -1.01 -1.21 -1.09 -1.33 1.25 1.42 0.38 I� INPUT DATA , Exposure category (13, C or D) = a,• r C` Importance factor, 1.0 only, (Table 1.5-2) IW = 1.00 Basic wind speed (ASCE 7-10 26.5.1) V • _ • x'";100 mph Topographic factor (26.8 8 Table 26.8-1) K = 1 �� " K, '.,� _ 00:.• Flat p Jslope Height of mean roof In , _ ' t 5 i. `= � ft �2 ' Roof slope 4:10 12 Roof length L`s10 l ft / Roof horizontal projected width B = S''10:;'� ft Effective area of component / cladding A . _ ?10 .aft2 8, lP,0, DESIGN SUMMARY 1. Main Wind -Force Resisting System Max horizontal force / base shear from roof = 0.86 kips + 0.09 kips (eave & columns increasing) .�• E 0.95 kips f, Max vertical download force + _ " 2.52 kips - Max vertical uplift force = -2.33 kips Max moment at centroid of base from roof = 7.51 ft -kips " + . 0.75 ft -kips (eave & columns increasing) E 8.26 ft -kips ' 2. Component and Cladding Elements , Max inward pressure = 63 psf~ - ' Max net outward pressure = 67 psf; , f ANALYSIS Velocity pressure qh = 0.00256 Kh Kn Kd V2 = r - 18.50 psf where: qh = velocity pressure at mean roof height, h. (Eq. 28.3-1 page 298 & Eq. 30,3-1 page 316) Kh = velocity pressure exposure coefficient evaluated at height, h, (Tab. 28.3-1, pg 299) = 0.85 Kd = wind directionality factor. (Tab. 26.6-1, for building, page 250) = 0.85 In = height of mean roof �y = 5.00 ft Main Wind -Force Resisting System (Sec. 27.4.3) x p=ghGCN F=pAr r where: G = gust effect factor. (Sec. 26.9) = 0.85 0 = roof angle - .' = 18.881 degree < 45 deg. [Satisfactory] Ar = roof actual area. = 54,8 ' .ft , windward i = 52.8 ft2, leeward ' ' CN = net force coefficients. (Fig. 27.4-4, page 267) • - r Check Fig. 27.4-4 limitation , h / B = 0.50 within [0.25 , 1.0] [Satisfactory] r 0 CASE WIND TO BOTTOM, y = 00 CLEAR FLOW - . OBSTRUCTED 1 CNW CNL CNW CNL WIND TO TOP, y = 180° CLEAR FLOW OBSTRUCTED CNW CNL CNW CNL 18.88 A -1.21 -1.46 -1.31 -1.60 1.51 1.70 0.45 -1.05 P (psf) -19.03 -22.88 -20.55 -25.21 23.69 26.78 7.10 -16.48 F (kips) -1.01 -1.21 -1.09 -1.33 1.25 1.42 0.38 -0.87 B -2.16 -0.16 -2.20 -0.76 2.01 0.65 1.25 0.14 P (psf) -33.94 -2.44 -34.64 -11.87 31.55 10.25 19.68 2.28 F (kips) -1.79 -0,13-1 -1.83 -0.63 1.67 0.54 1.04 -0.12 DATE: 3/19/2015 V I N C I•& ASSOCIATES SHEET: A3 PROJECT:- BIII & Pat Olsen (51mclural Cn9meers 4 JOB NO.: • 09-3457 118 Ridgeview Lane 175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA ENGR.: JRV ' ' a Oroville, CA 95966 p805.496.2100 • ( 805.496.2442 • e vinci@VinciSE.com CLIENT: Addy Electric -91360 V ' FOOTING DESIGN - PV Sloped Dimension: 117.3 in g „TYFICALtARRAY,+F fJ PV Array Angle: 20 degrees - Post Spacing: 7.58 ft - • ' No. of Supports: 2 .-' ` Footing Diameter (d): 12 'in MAXIMUM VERTICAL FORCE: 2.52 k / (10.0 x 10.0 ) = 25.24 psf x 0.6 =; 15.14 psf ' MAXIMUM UPLIFT FORCE: 2.33 k / (10.0 x 10.0 ) = I . 23.26"psf ' x 0.6 = 13.96 psf • ASD Factor GROUNDTRAC SYSTEM CAST INTO EARTH ' Maximum Vertical Load: (Worst Case: DL+Wind) P = 15.14 psf + 2.8 psf DL + 0 psf snow = 17.94 psf - P = 17.94 psf x ( 110 " /12"/ft) x ( 91.0 " /12"/ft) = 1249 lbs for 2 Supports ' P = 625 lbs/footing Try 12" diameter footing Soil Bearing= 625 / (p x 0.50). _ 795.7 psf << 1995 psf t r 1500 psf x 1.33 (CBC Table 1806.2) -Maximum Uplift Load: Therefore O.K. P = 13.96. psf - 2.8 psf DL = 11.16 psf ' P = 11.155 psf x ( 110" /12"/ft) x ( 91.0 " /12"/ft) _ 777` lbs for 2 Supports P = 388 lbs/footing , ' Try 12" diameter x 32 " footing ' ' Allowable uplift = Concrete DL + Soil Cohesion ( 130 psf x 1.33) per CBC Table 1806.2 • [ (n x (d/2)2) x 150 pcf x 2.7 ft ] + [ (n x d) x 2.67 ft x 172.9 psf] = 1764 lbs , Design Ratio = ( 1,764 lbs / 388 lbs) _ 4.5 Therefore O.K. V DATE: 3/19/2015 VINCI & ASSOCIATES SHEET: A4 ' PROJECT: BIII & Pat Olsen JOB NO.: 09-3457 ' 118 Ridgeview Lane 175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360 ENGR.: JRV Oroville, CA 95966 P805.496.2100 • f805.496.2442 • evinci@VinciSE.com CLIENT: Addy Electric DESIGN OF PIER FOOTING & POST CHECK ' Post Spacing: 7.58 ft Number of Columns: 2 Horizontal Load: 9.5 psf Exposed wind surface 3 ft -DESIGN BASED UPON NON -CONSTRAINED CBC FORMULA: (CBC Section 1807.3.2.1) d = (A/2) (1 + ( 1 + (4.36h/A) )^.5)) D h d GOVERNS >>> DESIGN COLUMN Mco1 = Scot = »»> USE: P = h = S1 = b = A = (2.34"P)/(S1 "b) 90 lbs = 9.5 psf x 7.6 ft x 3 ft / 2 columns 5 ft (Average Height) 266 psf/ft x (d/3) (includes 1.33 increase for wind) 12 in (diameter or diagonal of square) Try d = (ft) S1 @ (1/3)d (psf) A Calc d (ft) 1.67 1.92 2.17 2.42 148 170 192 215 1.422 1.237 1.094 0.981 3.58 3.29 3.05 2.85 77_77 2:67% ', a t h 23T . a r 0 889"' ..4, ` 2:69 = ' I 2.92 259 0.813 2.55 Ph = 450 ft -lbs MC01 / Fb = 0.23 in Fb = 0.66 x 35,000 psi ASTM A53, Gr B 1-1/2" Schedule 40 Pipe S = 0.31 in with 12 inch diameter x 32 inch MIN. deep concrete footing.