HomeMy WebLinkAboutB15-2136Array:
4
Modules: (66) SolarWorld SW285 Mono 285W Modules
Inverters: (66) Enphase Energy M250 240W AC Microinverters
Mounting Method: Flush Mounted. - (66) modules _
Ironridge roof mount system with XR100 rail
Array Azimuth: (66) Modules at 180°_
PV System Equipment Wall (Plin"View)
Equipment Wall ,Pqment Wall Array
(Adjacent to utility meter) hop) '(on RooA B C D E F G H
A: (Existing) Ap-in -one utility meter and main service panel, 200A,
120/208V, 30 G.
B: (1) (New) Wire Runs
C: (1) (New) PV system dedicated 30A AC Disconnect Switch (fused)
(Visible, Lockable, Labeled) (Adjacent to main service panel)
D: (New) 30 KVA 48OV: 120/208V Transformer
E: (1) (New) PVC SCH. 40 conduit run 175. ft run) (Buried 18"
below grade) '
F: (New) PV system dedicated 125A, AC aggregate panel
G: (1) Wire runs
H: (3) (New) PV sysiem junction box (UL 1741, NEMA 3R)
(Located behind modules)
OWNER / JOBSITE
Anderson Family Orchards -
5498 Ord Ferry Rd.,
Chico, CA 95928
`a APN: 039-050-005
'
CONTRACTOR +
_
North- State Solar Energy
PO 'Box 899
E
Forest Ranch, CA 95942
r
A, B, C, D
Lic. #813508
t
E
PROJECT DETAILS
New 18KW solar PV roof
1,
mount array using
t
microinverters on Ridge,
.Iron
racking system tied into
?Ya
existing load center. All
wiring is AC.
t
.,.., P F (66) 208 WATT Utility Interactive Inverters -
Fdge it Enphase M250-60-208-522
,- CEC Model: Enphase M250-60-2LL-S2x (-ZC)(7NA)(208V)
Page Details: CEC-Inverter Efficiency: 96.5%
Single Line Diagram for 208VAC, 3�, 60Hz L
Anderson Family Farms Voltage and Phase Sensing Neutral
y Listed to UL 1741
` 48 VDC Max Input Voltage
Integrated G.E.C. Ground
Project Details: '
New 18KW Roof Mount PV PV Circut:
s (22) SolarWorld'SW285 Mono Module Module Moduli
Array using microinverters on 285W Modulen
Box
.Iron Ridge mounting system - NEcMA tion 3R� UL 1741
Microimertzr Microinverter Microinverter
going to existing load. center. (At Array)
PV Circut:
(22) SolarWorld SW285 Mono Module Module Module
285W Modules
Main Service Line Side 1' Microinvzrter Microinverter Microinverter
PV Connection l: t
Via NSI Polaris Lugs ' 240 VAC (f20 FT RUN)
Allowed Per CEC 240.21 (D), PV Circut: 6 - #12 AWG THWN-2 CU
705.12 (A), and 230.82 (6) (22)-SolarWorld SW285 Mono Module Module Module 1 - #12 AWG THWN-2 CU (N)
285W Modules E 1 - #8 AWG THWN-2 CU E.G.C.
f� (Gnd to be continuous)
Microinverter Microinverter Microinverter 1" LFMC Conduit
(Run behind array)
(Existing)
Utility Meter (New) Dedicated PV System
Utility AC Disconnect Switch (±175' ft run) 240 VAC
30A, NEMA 3R • 3 J- #3 THHN CU Enphase AC
(3) 30A Fuses 1 �- #3 THHN CITNeutral Engage Cagle
t
o (Visible Blade Type, Lockable, l And Bare #6 AWG ,; #6 THHN CU E.G.C. E.G.C. Ground +
Labeled, Accessible 24/7) (Giid to be continuous)
• 1.25" PVC SCH 40 Conduit
(Buried 18" below grade) ;
w
200A is
t: 60A 3-P 1,
1`
20A 3—P i
F
s 20A 3-P t
20A 3-P
Dedicated PV System
480V 120/208V AC Agregate Panel '
120/208 VAC, 125A, NEMA 3R
PV System Transformer Main Lug Onlyl
30 KVA, NEMA 3R (3) 3P -20A PV Circut Breakers '
3 - #8 THHN CU Adjustable Voltage Taps (Located at Array)
1 - #8 THHN CU Neutral Primary: 120/208V
1 - #8 THHN CU E.G.C. i Secondary: 480 DELTA
(Gnd to be continuous)
1" LFMC conduit -
(Run along equipment wall)