HomeMy WebLinkAboutB15-2686V I N C I ASSOCIATES cslruclura/ &,Vi leers October 27, 2015 Philo Hunt,.P.E., Plan Check Engineer Butte County Department of Development Services - Building Division 7 County Center Drive, Oroville, CA 95965 Subject: Use of Professional Solar Products Standard Testing Report Project:. (36) Module Photovoltaic Groundmount Installation (1 Array) Carol Lee Court, Chico, CA 95928 V&A Project No. 1273457 The purpose of this letter is to confirm thaf.it is acceptable to utilize the attached standard test report and footing recommendations prepared by Professional; Solar Products for. the construction of the foundation & racking system at the ground mounted photovoltaic array.at,�Carol- Lee Court, Oroville, CA 95965. Refer to attached wet stamped Professional Solar Product Report for additional information. Our professional services have beenperformed using the degree of care and skill ordinarily exercised under similar circumstances by reputable engineers practicing in this locality. No other warranty; expressed. or implied, is made as to the professional options included in.this report. We hope this ' ovides you with the information you need at this time. Please call us if you have any ns regarding this report. Q90ESS��, Sincerely,'ow VINC1 S CIATES �ti4�z No. 54411 Exp. 12/31/15 am . Vi ci, S.E. qr OF C BUTTE S i nse No. S-4411 COUNTY OCT 29 2015 . DEVELOPMENT ]�S,jE<R�VIICES PERMIT # BUTTE COUNTY DEVELOPMENT SERVICES CO RE LLI IOMPANC COE DATE BY�G&_ 175 E. WILBUR ROAD, STE 103 THOUSAND OAKS', CA 91360 p 805.496-2100 f 805.496-2442 a vinci@vincise.comLE ��( V I N C I & A S Structural CLIENT: Professional Solar Products, Inc. (ProSolar) 1551 S. Rose Ave., Oxnard, CA 93033 Tel: 805-486-4700 .S O C I A T E S Enginep� # 1315- -2-0 R,�a___ BUTTECOUNTY DEVELOPMENT SERVICES REVIEWED FOR CODE r%OM LIANCE BY Subject: Static load test results for the following: GroundTrac® Mounting System Frame Length* (in.) Frame Width* (in.) Wind Speed rating (4 modules high - landscape) 2-1/2"x 124D rail (mph per20121BC/2013CBC, ASCE 7-10)** 3"x 164XD RoofTrac® rail 2-1/2"x 136D rail 0.625"/0.813" (4 modules high - landscape) 77 39.5 110 3" x 172XD RoofTrac® rail 62 41.5 110 (4 modules high - landscape) 3" x 172XD RoofTrac® rail 77 41.5 100 (4 modules high - landscape) 2-1/2"x 124D RoofTrac® rail (3 modules high - landscape) 77 39.5 110 2-1/2"x 136D RoofTrac® rail 77 32.5 110 (4 modules high - landscape) TEST SETUP (as shown in attached drawing detail): Modules were bolted to Professional Solar Products (PSP) RoofTrac® support rails using an assembly of 5/16" stainless steel (ss)bolts, ss lock washers and proprietary aluminum clamps and nuts. The RoofTrac® support rail was attached to a pair of 1-1/2" schedule #40 galvanized water pipes with a proprietary PSP insert and 5/16" "U" bolts. The front to rear span was 9' for the 3" tall Xtra Deep rail design and 7' for the 2-1/2" Deep rail. Test Procedure (as shown in attached drawing detail): The test set up was top loaded and remained loaded for an approximate period of 30 minutes. The maximum deflection and any signs of permanent deformation were recorded. The test setup was then inverted and loaded to simulate the uplift condition. The setup remained loaded for an approximate period of 30 minutes. The maximum deflection and any signs of permanent deformation were recorded. Test Results: No permanent deformation. GroundTrac® Mounting System Maximum deflection (top load/uplift) 3"x 164XD rail 0.688'/0.719- (4 modules high - landscape) 2-1/2"x 124D rail 0.500"/0.344" (3 modules high - landscape) 2-1/2"x 136D rail 0.625"/0.813" (4 modules high - landscape) This document certifies the GroundTrac® mounting system used as specified above, achieved stated loads/wind speeds. Sincerely, James R. Vinci, S.E. The GroundTracO mounting system requires installer supplied 1-1/2" schedule #4b galvanized water pipe installed using Hollaender' structural T fittings. All pipe spans referred in this engineering report are absolute maximum limits (see attached detail drawings). Maximum spans: 60" rear vertical legs height from grade (or top of footing) 30" front vertical leg height from grade (or top of footing) 24" max. pipe cantilever for horizontal pipe 63' single horizontal pipe run recommendation (thermal expansion limit on pipe) Maximum spans: 3" Xtra deep rail: 8' on center max lateral pipe span (30 psf static) 2-1/2" deep rail: 10' on center max lateral pipe span (50 psf static) 2-1/2" deep rail: 6' on center max snowload lateral pipe span (25 psf- 2.0 safety factor) Pipe shall be cut square and completely inserted into the fitting. The Hollaenderlm fitting set screw must be torqued to manufacturer specifications of 17 ft -lbs, to meet a minimum of 1,850 pounds of retention. Footings, per attached drawings must be installed in solid soil at level grade, no loose earth backfill. Pipe approx. 2" from footing bottom. Contact local building departmenVAHJ for guidance on unlisted conditions.This office does not field check installations to verify compliance as described in this engineering report. *Modules measuringwithin stated specifications and UL1703 (or equivalent) listed, are included in this engineering For 3 high landscape modules on 2-1/2"x136" rail, 43" max module width. 164" rail design derated to 100mph for 172" rail. **Wind loading values relative to defined load values using wind load exposure and gust factor coefficient "exposure C" as defined in the 2012(IBCV2013(c8C), ASCE 7-10 ***1-1/2" schedule 40 water pipe pair tested to: 3,400 lbs at 10' OC max pipe span, 3,740 lbs at 6' OC max pipe span 175 E. Wilbur Road, Suite 103• Thousand Oaks, CA` 91360 I I<-- 39.5' , 1 OD 0 A C) co 0)3 CA 'a X 0,0 _B N N 7 I I I I I I I I I I I I I I 3' Xtra Deep rail vra eep D " 3 5/16" Stainless ProSolar RoofrracO Steel Hex Bolt & Module Clamps LockW asher Aluminum ProSolar RoofTrac® Intermodule Clamp Aluminum ProSolar Rooff Chhannelannel Nut 7 Aluminum ProSolar DropNlock ProSolar Rooffrac® 3" Xtra Deep Support Rail Professional Solar Products Ground Trac@ Photovoltaic mounting system RoofTraco Patent# 6,360,491 '172" rail design derated Grounffra& 164" x 3" Xtra Deep rail & 172" x 3" Xtra Deep rail TEST SETUP 164" NC ET BF LAS CNC V BA LRS Rail Insert 5/16" SS Locking DropNlock = Flange Nuts Module 5/16" x �>ue Frame 1-1/2" SS Ubolt 1-1/2" Schedule #40 Galvanized Water Pipe (-2" OD) X47 PERMIT # BUTTE COUNTY DEVELOPMENT SERVICES ' COREVIEWED E CE MPDIANCE DATE "5 S BY 1-1/2" HollaenderTM Pipe Tee Fitting/ /15 Ur � /,P,%r 9-1. I, I, I IF 32.5" 1 I o A O °D 3 N vv = x m rn a m _ 1 I ,I 7, II 1 �- 2 12' Deep rail GroundTrac®136"x 2 1/2" & 12455x 2 1/2" Deep rail TEST SETUP 136" NC ET BA LAS C NG ET BA LAS 5/16" Stainless ProSolar RooffracO Steel Hex Bolt & Module Clamps LockWasher Rail Insert 5/16" SS Locking DropNlock Flange Nuts Aluminum ProSolar Rooffrac® I Interrnodule Clamp � m Aluminum ProSolar � / RoofTrac® Module 5/16" x �-�-�> �-'T'`-' - Channel Nut Frame 1-1/2" SS Ubolt + m Aluminum ProSolar 1-1/2" H I en a TM DropNlock 1-1/2" Schedule #40 Galvanized Pipe a Fi i g Rail Insert Water Pipe (-2" OD) ProSolar Roofrrac(D 2 1/2" Xtra Deep Suppo Rail / �lo�� s C PERMIT # �i ,BUTTE COUNTY DEVEL��� ��� OPMENT SERVICES (3 CO REVIEWED FOR P. / j1s COMPLIANCE DATE l / 3 / BY Professional Solar Products Ground Trac® q F F Photovoltaic mounting system RoofTraco Patent# 6,360,491 F�� �� GrounclTrac® 164" x 3" Xtra Deep rail 9' fixed 60" max pipe length from top of footing \ 3-0" max pipe length from top of footing r— — t T j t i I 12 " Sonotube cap OPTIONAL (used to increase grade dearance by 12') Approx. 9' Actual depends on 71l Angle 36" min below 12" ODS grade Pmaxugift= 1,713 lbs perfooting Pmaxf.,i, = 1,302 lbs perfooting Design ratio = 2.4 (3,061 lbs / 1,302 lbs) I i _1 12- OD I �— ' PERMIT # 2—& r& BUTTE COUNTY DEVELOPMENT SERVICES REVIEWED FOR a� COPE POMPLIANCE // ao®� DATE / J / / S BY /y/ moo 1�e 9' fixed 60" max pipe length from 18" OD top of footing Pmaxugia= 1,713 lbs per support rail 30" max pipe Pmaxf.ting = 1,302 lbs perfooting length from Design ratio = 2.5 (3,294 lbs / 1,30 s _ top of footing _ ___ j 1 Sonotube cap OPTIONAL (used to increase grade clearance by 12•) Approx. 9' Actual depends on Tilt Angle I 26" min below grade S . o. S4 Z j P X15 Professional Solar Products GroundTrac@) Photovoltaic mounting system —� 18' OD If Roofirrae Patent# 6,360,491 t _ FLS GroundTrac® 172" x 3" Xtra Deep rail 1�2 +3 9' fixed 60" max pipe length from top of footing \ 30" max pipe length from top of footing r r ' I I I 12 Sonotube ca OPTIONAL used to increase rade dearance b 12" i j I i P ( 9 Y ) Approx. 9' Actual depends on Tilt Angle 36" min below 12" OD grade Pmaxuplift= 1,511 lbs per footing Pmaxfwting = 1,102 lbs per footing Design ratio = 2.6 (2,859 lbs / 1,102 lbs) I I 112" OD _ PERMIT # BUTTE COUNTY DEVELOPMENT SERVICES REVIEWED FOR CODE C MPLIANCE ® 5; --BY Hca` DATE 1/// Voo 9' fixed 60" max pipe length from 18" OD top of footing Pm@xuprift= 1,511 lbs per support rail \ 30" max pipe Pmaxfooting = 1,102 lbs per footing I length from top of footing Design ratio = 2.8 (3,036 lbs / 1,102 - - ) I I I I I t I' 1 Sonotube cap OPTIONAL (used to increase grade dearance by 12°) I I I I I I 1 Approx. 9' Actual depends on Tilt Angle I 26" min _ below grade I 01 31 15 Professional Phot volts Photar ovoltaic ng Products roundTracC� T C 18' OD IF RootTrae Patent# 6,360,491 Chemical Composition Limits per ASTM B 26-98 Si Fe Cu 0.15 0.15 0.05 Temper Ultimate Yield Strenth Stren th (ksi (ksi F . 40 20 (35 min.) (18 min.) Mn Mg Ti Other 0.10-0.25 6.2-7.5, 0.01-0.25 0.15 Typical Mechanical Properties 10 2 1006 lbs. Elongation Shear Compressive Brinell 1-1/4" 17 1 1800 lbs. Strength Yield Strength Hardness (% in 2 in.) (ksi (ksi) listed above are based on a safety factor of 100%. 13 27.45 23.5 70 (9 min.) PERMIT # L� 17 2 3200 lbs. (70 min.) REVIEWED FOR Above data compiled by an independent laboratory using the following test procedures: ,` Standard I.P.S.-sized pipe within the vertical barrel of the test fittings, to the torque CODE O'�//%�,PLLIIANCE Al Remainder Endurance Limit (ksi) 10 ASTM 626-96 • Thermal Conductivity (@ 77F, SI units): 0.24 cal/cm*s*K • Heat Treatment — Achieves its physical and mechanical properties as -cast (F). This eliminates the time and cost of heat treating. • Machinability — Excellent machinability as -cast, excellent surface finish, and high dimensional stability. • Corrosion Resistance — Highest -of any cast alloy. It can be anodized for additional corrosion protection to a 0.7 mil thickness (2151`11). • Finishing — Produces an excellent surface finish by burnishing or polishing. Anodizes well to a clear -satin finish due to the minimal amount of silicon in the alloy. • Weldability — It can be welded by any of the inert gas processes, T.I.G. or M.I.G., using filler rod of 5356 or 5183.. Std. IPS Size Steel Pipe Schedule 40 Aluminum IPS Size Pipe Schedule 40 Fitting Torque No. Push FittingTorque No. Push sizeFt. Lbs. Screws Out SizeFt. Lbs. Screws Out 3/4" 13 1 1000 lbs. 1-1/4" 10 1 937 lbs. 13 2 1900 lbs. 10 2 1006 lbs. 1" 14 1 1200 lbs. 1-1/2" 12 1 950 lbs. 14 2 1800 lbs. 12 2 1020 lbs. 1-1/4" 17 1 1800 lbs. Above data compiled by an independent laboratory using the following procedures: A 17 2 2000 lbs. 30,000 Ib. Universal Testing Machine applied vertical load to the pipe member in an ` attempt to produce pipe slippage through the vertical barrel of the fining. Load capacities 1-1/2' 17 1 1850 lbs. listed above are based on a safety factor of 100%. 17 2 2350 lbs. 2" 17 1 1925 lbs. r 1 6 PERMIT # L� 17 2 3200 lbs. BUTTE COUNTY DEVELOPMENT SERVICES REVIEWED FOR Above data compiled by an independent laboratory using the following test procedures: ,` Standard I.P.S.-sized pipe within the vertical barrel of the test fittings, to the torque CODE O'�//%�,PLLIIANCE shown above. A 30,000 Ib. Universal Testing Machine applied vertical load to the pipe DATE / J member in an attempt to produce pipe slippage. Load capacities listed above are based —BY on a safety factorof 2:1. Call Toll Free: 800-112-8800 • www.hollaendeLcom - Copyright 2001 Hollaender Manufacturing Company. Grounffrac®136 x 2 1/2" & 124" x 2 1/2" Deep rail �y00 ` G® . Op 416 T fixed 60" max pipe length from top of footing 30" max pipe length from top of footing r- --i i i j I 12" Sonotube cap OPTIONAL (used to increase grade dearance by 12') Approx. 7' Actual depends on Till Angle _* 112- OD 36" min below grade 12" OD — Pmaxuplift= 1,349 lbs per footing Pmaxrootirg = 1,775 lbs per footing Design ratio = 2.3 (3,075 lbs / 1,349 lbs) PERMIT # BUTTE COUNTY DEVELOPMENT SERVICES CODE COMPLIANCE DATE �3 Z S gY_-1/dw 136 21��� A � T fixed 60" max pipe 18" OD length from top of footing Pmaxuplilt= 1,349 lbs per support rail \ * Pmaxro ,i, = 1,775 lbs perfooting ' 30" max pipe length +from top of footing ---- ---i t t t . Approx. 7' Actual depends on Till Angle Professional Solar Products Ground Trac® Photovoltaic mounting system RoofTrae Patent# 6,360,491 , Design ratio = 2.4 (3,294 lbs / 1,349 lbs) i t 1 L' Sonotube cap OPTIONAL (used to increase grade clearanceby 12') t I 26" min below grade h' S o. 1 Z j Idp. 1 15 I I I I I I I I I I rte-' FIA 0 20A 0 3 1 I A �Ii 10,000W AC DISCO. DS1 60A B PANE 60A1 IMSA MAINED )FJ2Al0 TO UTILITY COMPONENT SPECIFICATIONS PHOTOVOLTAIC MODULE REF. TYP.MODULE MANUFACTURER MODULE MODEL STC POWER PTC POWER I ISC I IMP I VOC I VMP FUSE RATING PMt 1 36 1 LG ELECTRONICS I LG280S1C-63 280W I 255.2W 19.33A 18.78A 138.8V 131.9V I 15A INVERTER BARS sa ll ARRAY STC POWER NOMINAL I INVERTER MAX I AC MAX MAX CEC REF. TYP. INVERTER OUTPUT MAX OCPD OUTPUT CURRENT INPUT INPUT WEIGHTED 10,000W CEC AC POWER OUTPUT VOLTAGE SIZE POWER CURRENT VOLTAGE EFFICIENCY Ti- 1 1 SOLAREDGE SE10000A-US 240VAC I 60A 10000W I 42A 30.5A I 500V 97.50/6 OVER CURRENT PROTECTION DEVICES REF. TYP. CURRET RATING MAX. VOLTAGE F1.4 4 20A 60OVDC CB1 I 1 60A 240VAC SYSTEM SPECIFICATIONS POWER OPTIMIZER BARS sa ll ARRAY STC POWER 10,080W ARRAY PTC POWER 9,187W POWERBOX MAX OUTPUT CURRENT 14.4A,14.4A POWERBOXES IN SERIES 18,18 POWERBOX MAX OUTPUT VOLTAGE 350V MAX SYSTEM VOLTAGE 500V MAX AC CURRENT OUTPUT 42A MAX AC POWER OUTPUT 10,000W CEC AC POWER OUTPUT 8,850W POWER OPTIMIZER REF. TYP. POLES CURRENT RATING RATED MAX STRING REF. TYP. MODEL INPUT DC OUTPUT VOLTAGE SUITABLE FOR ALL REGIONS. POWER CURRENT OUTDOOR -RATED COMBINER BOX RATED FOR P01 36 SOLAREDGE P300 30OW 15A 350V DISCONNECTS REF. TYP. POLES CURRENT RATING MAX. VOLTAGE DS1 I 1 2 1 60A 240VAC `a CIS NOTES Q BUTTE STRING VOLTAGE OF ARRAY WILL FLUCTUATE 0 WITH TEMPERATURE. THE PAIRING OF THIS COUNTY MODULE AND THIS POWER BOX MAY NOT BE SUITABLE FOR ALL REGIONS. p C T 2 9 2 015 OUTDOOR -RATED COMBINER BOX RATED FOR E U 60OVDC MUST HAVE NOTE:'WARNING ELECTRIC c SHOCK HAZARD. THE DC CONDUCTORS OF THIS DEVELOPMENT CD rn CD PHOTOVOLTAIC SYSTEM ARE UNGROUNDED SERVICES J co C AND MAY BE ENERGIZED! BOTH THE POSITIVE AND NEGATIVE REQUIRE J0 C.0 VVV ONGROUNDEI # o CONDUCTORS ARE PHOTOVOLTAIC OUTPUT STRINGS ARE BUTTE COUNTY DEVELOPMENT SERVICES 0 COMBINED INSIDE THEINVERTERS'DC REVIEWED FOR INTEGRATED DISCONNECTS. INTEGRATED DC DISCONNECT IS PD CODE COMPLIANCE 1 Q WITH INVERTER DISCONNECTS A 8 ` BY \ . FOR USE WITH SOLAREDGE UL 1741 LISTED STRING INVERTERS. OUTPUT OF INVERTERS IS CONNECTED TO 0 UTILITY ON LOAD SIDE OF SERVICE DISCONNECT. OUTPUT IS BACKFED THROUGH BREAKER IN MAIN PANEL =1=u� 1 SINGLE -LINE SCHEMATIC - TO CUSTOMER LOADS E1 Mon SCALE: NTS Tanenanefy apply Sebr ElacOicsuppy mea nd prepare a meats e♦echical drswmge, provide olechical or angumrhp eervhm in m7 (mm The IaMicol mebrbl ebached'o presided M Vmdiamro, kc. , mt Audndud Satsr EIatrE sappy, la. pmbm. The/ aro previdad d no cent m refereme mamrbr any. We a the reepienb mpomABy b mbnnire C ha bchriwl rebrarce material is app b tluuk parbcdar pmal AN bcfiniml nmbrbl obadd be rmiewd by a imncad wnbecta aengineer. All sear yst- =pmmb ehadd be'vrebW by atraneed experienced elauiralwtrecb, m britn®n and dould fallow NEC mal local buMng depatrwu guW*m.Mseptaus mrd use of my products or maWals prwimd by solar Ebcbi Supply, bx a ad merry of im pa —m euhMmriw 1 bbmah eydfrurdb&burinsCmryIbrn anmtvtec defindbe end ate pmAm hmab agree the amamldfS00Ad woutl bs fav campemaAon fm my Imo awtdr dby Ma Cuebrem end Muth. agree Cola amount N remonabb under the cbwreabncea et ColaAms. Dtsbbufmnm pubbcahondarry Wlmkal material,d—b a iterebra prod by Sohn Ebchic Supply, Im.end aany d it. pwr—aed.idarim ts ehicdy proNbibd wilhoulwdll n aut.-c.tm barn Sem awhic Supply, in. U Uz LLX Ua � 0 :) Ul W U) i__ File: Drawn by: SCM Approved by: DMM Scale: NTS Date: 1111812014 Pro ect No.: PO No.: 18290 E1 Q O O O O LL E U C/) c f M U cO j 3 CD rn CD iA 00 Q r- J co C GV J0 C.0 Y M o C1)LLI Cl) N CWn File: Drawn by: SCM Approved by: DMM Scale: NTS Date: 1111812014 Pro ect No.: PO No.: 18290 E1 An A CONDUCTOR LEADS ON MODULES SHOULD BE SECURELY FASTENED TO RACKING TO PREVENT ABRASIVE DAMAGE. USE A SECURING METHOD THAT WILL WITHSTAND HIGH TEMPERATURES AND SUNLIGHT, SUCH AS STAINLESS STEEL PIPE CLAMPS WITH AN EDPM INSERT (PLASTIC TIES ARE NOT RECOMMENDED). ______________________ ADC GROUNDING SYSTEM MUST BE BONDED TO AC GROUNDING SYSTEM PER NEC 690.4-1 (C)(1) IN ACCORDANCE WITH 690.47 (C)(2-8) W a. INSTALLER -PROVIDED OUTDOOR -RATED COMBINER BOX RATED FOR 600VDC. MUST HAVE 0 NOTE: 'WARNING ELECTRIC SHOCK HAZARD. THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY BE ENERGIZED." NEGATIVE CONDUCTOR MUST BE A COLOR OTHER THAN GRAY OR WHITE. IF PV SOURCE A CIRCUITS ARE ROUTED THROUGH BUILDING, NEC 690.31(E) REQUIRES THAT WIRE BE RUN IN A METAL RACEWAY. 4INVERTERS EQUIPPED WITH INTEGRATED DC DISCONNECTS. IF INVERTERS INSTALLED INDOORS, LOCAL JURISDICTION MAY REQUIRE ADDITIONAL EXTERIOR DISCONNECTS. NEC 690.17, 690.53 REQUIRE LABELING ON DC DISCONNECTS STATING: "WARNING: QELECTRIC SHOCK HAZARD. DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OFF POSITION." EXISTING AC LOAD CENTER MUST MEET REQUIREMENTS OF NEC 690.64(B)(2). SUM OF MAIN BREAKER PLUS SOLAR BREAKER (S) MUST BE LESS THAN OR EQUAL TO BUS RATING. IF BACKFED BREAKERS ARE MOUNTED AT OPPOSITE END OF BUS FROM MAIN BREAKER OR FEEDER, THE SUM OF SOLAR BREAKERS AND MAIN BREAKER MAY BE EQUAL TO OR LESS THAN 120% OF BUS RATING. 8 ALWAYS USE MANUFACTURER'S RECOMMENDED GROUND -BAR KIT TO GROUND DISCONNECTS. RECOMMENDED WIRE RECOMMENDED WIRING LIST IS SUGGESTIVE ONLY. INSTALLER IS RESPONSIBLE FOR DETERMINING HOW THE WIRES WILL BE RUN, CONDUIT SIZING, AND FINAL WIRE SIZING. WIRES ONE AND TWO ARE LISTED AS A COMBINED LENGTH. A MODULE CONNECTORS ARE NOT LISTED TO BE DISCONNECTED UNDER LOAD. A FUSEHOLDERS IN COMBINER BOX ARE NOT LISTED TO BE DISCONNECTED UNDER LOAD. WIRING DIAGRAM E2 SCALE: NTS v v a 11 Tenor and CM ft. Satan Ebc*Supply does not PMPae a Mae -Inett nal &WIMP, Mid. alectrcal or engineering eervEm in any toms The to uftal rreterel attached I, provided by Vail—, Inc. , an AutMr�d Set. Elan Supply, I.. paMer. They era pravMed at m cast es'taduni:al mlemirce rretertaf ady.Ire b the re.>pienb mporobiiy b delermiie N the technical relererce rret� le appimb' to their particdm pmjecL AD technical material should be reviv-d by a licensed canbecbr a engineer. Al eolar mtem cornponanb should be msteled by a 4emed experienced electrical cautrecler a bchnlelen and should le0ox NEC and local budding depw ment guideEnm. Acceptance and m army pmducb or materials provided by Saba Ebcbc Supply, be end in any or it, pabmrs or subsidin anetibdm ae eF—et Met al Pend" agreebe fix Me am—et datrrd damages Bre Cut— —Id born in Me&.1 One product, add amet, pm+ided by Soba Becb'c Supply. Inc, me ddectivaIt—Id be imprxtiable or extremely 05PAI to ddnnina it any item a material is defecd+e and the panda hereto agree Me arrountof$5D0D0 mId be fair corrpemaDen for - any lees evetined by the CuMmem r and ftat* wee Ods account b reasonable under the cbevmstancas at this tens. Dhtdbufun or publication d any ftN id aaaael, dacamenb a Ram- provided by Setar Electy Supply. tic. end a any at its part— a submid cries is strictly pmhibitedwittout written au0m®lion hen Solar Electric Supply. Mu. U Uz Cl} �QUd 0�IL :) COM) CONDUCTOR I WIRE DISTANCE GROUND NO. TYPE SIZE 1.0%V DROP TYPE SIZE 1 PV WIRE 10AWG 94FT BARE COPPER 6AWG 2 THWN-2 10AWG 94FT THWN-2 10AWG 3 THWN-2 2AWG 147FT THWN-2 4AWG 4 THWN-2 6AWG 58FT THWN-2 8AWG 5 1 THWN-2 6AWG 58FT I THWN-2 8AWG RECOMMENDED WIRING LIST IS SUGGESTIVE ONLY. INSTALLER IS RESPONSIBLE FOR DETERMINING HOW THE WIRES WILL BE RUN, CONDUIT SIZING, AND FINAL WIRE SIZING. WIRES ONE AND TWO ARE LISTED AS A COMBINED LENGTH. A MODULE CONNECTORS ARE NOT LISTED TO BE DISCONNECTED UNDER LOAD. A FUSEHOLDERS IN COMBINER BOX ARE NOT LISTED TO BE DISCONNECTED UNDER LOAD. WIRING DIAGRAM E2 SCALE: NTS v v a 11 Tenor and CM ft. Satan Ebc*Supply does not PMPae a Mae -Inett nal &WIMP, Mid. alectrcal or engineering eervEm in any toms The to uftal rreterel attached I, provided by Vail—, Inc. , an AutMr�d Set. Elan Supply, I.. paMer. They era pravMed at m cast es'taduni:al mlemirce rretertaf ady.Ire b the re.>pienb mporobiiy b delermiie N the technical relererce rret� le appimb' to their particdm pmjecL AD technical material should be reviv-d by a licensed canbecbr a engineer. Al eolar mtem cornponanb should be msteled by a 4emed experienced electrical cautrecler a bchnlelen and should le0ox NEC and local budding depw ment guideEnm. Acceptance and m army pmducb or materials provided by Saba Ebcbc Supply, be end in any or it, pabmrs or subsidin anetibdm ae eF—et Met al Pend" agreebe fix Me am—et datrrd damages Bre Cut— —Id born in Me&.1 One product, add amet, pm+ided by Soba Becb'c Supply. Inc, me ddectivaIt—Id be imprxtiable or extremely 05PAI to ddnnina it any item a material is defecd+e and the panda hereto agree Me arrountof$5D0D0 mId be fair corrpemaDen for - any lees evetined by the CuMmem r and ftat* wee Ods account b reasonable under the cbevmstancas at this tens. Dhtdbufun or publication d any ftN id aaaael, dacamenb a Ram- provided by Setar Electy Supply. tic. end a any at its part— a submid cries is strictly pmhibitedwittout written au0m®lion hen Solar Electric Supply. Mu. U Uz Cl} �QUd 0�IL :) COM) File: Drawn by: SCM Approved by: DMM Scale: NTS Date: 1111812014 No.: E2 Q 0 0 0 0 wE M m T C;2 E rn U 3 0 U3 v cm 00 F7 CD J CO CD CoC/3 MCn ILLJ C/:) LU U) File: Drawn by: SCM Approved by: DMM Scale: NTS Date: 1111812014 No.: E2 (S. 16.Skg _ C Lir Life's Good BUTTE COUNTY OCT 2 9 2015 DEVELOPMENT SERVICES '. Bis- lil it's 7116paoss•i191e. ° ERMIT • BUT@ COUNTY DEVELOPMENT SERVICES Mono; �: C-0 I �61ANCE � • DATA. _ __ 1..� ��__ BY LG280S1C-B3 LG275SK-B3 LG270SK-B3 } LG265SK-B3 LG260SK-B3 1� 60 cell Mono X° series are LG Electronics' hi h- uali monoc stalline 9 q ty rY module brands. The quality is the result of our strong commitment in developing a module to improve benefits for customers. Features of Mono XO series include higher efficiency and durability than LG previous models, convenient installation, and aesthetic y I exterior. �� //7y � APPROVED PRODUCT DVE lr��� �j) i Intertek- C E KM564573 OSEN61215 1 PhorowhekhW.Ies cif".. :•: Light and Robust With a weight of just 16.8 kg (36.961b), LG modules are proven to demonstrate outstanding durability against external pressure up to 5400 Pa. 100% EL Test Completed All LG modules pass Electroluminescence ELTeO inspection. This EL inspection detects cracks and other imperfections unseen by the naked eye. - Reliable Warranties , LG stands by its products with the strength of Linear Warranty a global corporation and sterling warranty policies. LG offers a 10 year product limited warranty and a 25 year limited linear output warranty. About LG Electronics Convenient Installation • . L� � �1��►�L�S+y�RR1#�c�B�3uvir�ut the carrying, grounding, and connecting stages of. Convenient modules. n, Installation . The Extra 2% Power r ' - ' To minimize losses due to mismatch; LG produces 3 groups of solar modules which are sorted by its • Current Sorting current class. This enables Mono X® to maximize the system's output by around 2% based over the theoretical calculation. VT • 2 •, mit is • . Positive Power Positive Power Tolerances LG provides rigorous quality testing to solar modules ' to assure customers of the stated power outputs of all modules, with a positive nominal tolerance starting at 0%. jr . ' , k L628OSIC-63 LG275SIC-03 LG270S1C-B3 LG265S1C-B3 LG260S1C-B. a Maximum power at STC (Pmpp) ' . 270 265 260 280- 275 31.5 -31.3 31.1 MPP voltage (Vmpp) 31.9 31.7: MPP current (Impp) y - 8.78 8.58 8.49 8.38 - Open circuit voltage (Voc) 38.5 38.3 38.1 t Short circuit current (Isc) , 9.17 9.11 9.05 ~ ; Cells 6 x 10 'Cell vendor LG ` Cell type Monocrystalline ! Cell dimensions 156.5 x 156.5 mm / 6 x 6 in # of busbar 3 r LG Electronics is a multinational corporation committed to expanding its capacity with solar energy business as its future growth engine. Our solar energy source research program was launched in 1985, backed by LG Group's rich experience in semi -conductors, LCD, chemistry and electronic materials industry. We successfully released the first Mono X° series to the market in 2010 which was sold in 32 ' countries in 2 years. In 2013, Mono X® NeON won "Intersolar Award", which proved its leading innovation in the industry.8.68 • Mechanical Properties Electrical Properties (STC') ` 38.8 38.7 Dimensions (L x W x H) 1640 x 1000 9.33. • 9:26 x 35 mm 64.57x39.37xl.38in 17.1 16.8 • Operating temperature (•C) "' -40-+90 Static snow load 5400 Po / 113 psf Maximum system voltage (V) . _ '1000 (IEC), 600 (UL) Static wind load 2400 Po / 50 psf Maximum series fuse rating (A) ` 15 Weight 16.8 t 0.5 kg /36.96 t 1.1 Ib Power tolerance (%) 0-+3 Connector type MC4 connector IP 67 Module efficiency (%) ° . 16.5 16.2: 15.9 Junction box • IP 67 with 3 bypass diodes h STC (standard Test Condition): Irradiance 1000W/m2, module temperature 25 Y, AM 1.5 Length of cables 1000 mm / 39.37 in The nameplate power output is measured and determined by LG Electronics at its sole and absolute discretion. Glass High transmission tempered glass t " , r Electrical Properties (NOCT*) Frame - Anodized aluminum - Certification and Warranty e # PERMIT (� BUTTE COUNTY DEVELOPMENT SERVICES = Co R I®MPLIANCE 1 DATE . - is - •� r. .� � r r � .... Certifications IEC 61215, IEC 61730-1/-Z Salt Mist Corrosion Test (IEC61701), DLG-Fokus Test "Ammonia Resistance', LIL 1703, ISO 9001 Module Fire Performance (LIL1703) Type 2 Product warranty 10 years Output warranty of Pmax Limited Linear Warranty (measurement Tolerance t 3%) 29.3 ' 1) 1 st yeac 97%, 2) After 2nd year. 0.7%p annual degradation, 3) 80.2%for 25 year. Temperature Coefficients 28.6 NOCT 45.0 t 2 °C Pmpp -0.43 %/'C Voc -0.31 %/aC Isc 0.04 %/°C Characteristic Curves 35.5 Q, to y1000 G 8 u' a w 7.52 7 800w 7.34 8 5 4 3 600 W 400 W 2 1 0 200w s 10 is 20 25 30 35 40 Voltage (V) 140 120 Sl loo so 60 40 20 0 ' NOR (Nominal Operating Cell Temperature): Irradiance 800 W/m7, ambient temperature 20 T. wind speed 1 Ms 5.5.4.0 (X Haw Ohh Aoha(4aa) 4A'75 Haw D.aln nw•ga•o) 12.06.3 Gr WkV hWaanba a-08.0(2 vbw) Mawnn�q Adaa(8aa) ) -25 0 .25 so 75 go Temperature (•C) LCm North America Solar Business Team LG Electronics U.S.A. Inc 1000 Sylvan Ave, Englewood Cliffs, NJ 07632 Life's Good Contactlgsolar@lge.com www.lgsolarusa.com LG280S1C-B3 LG275S1C-B3 LG270S1C-B3 LG265S1C-B3 LG260SlC-BF Maximum power at NOCT (Pmpp) 205 202 198 195 191 MPP voltage (Vmpp) 29.3 29.1 29.0 28.8 28.6 MPP current (Impp) 7.00 6.92 6.84 6.77 6.68 Open circuit voltage (Voc) 36.0 35.9 35.7 a 35.5 35.3 Short circuit current (Isc) 7.52 7.46 7.39 7.34 7.29 Efficiency reduction (from 1000 W/m'to 200 Wit) < 4.5% ' NOR (Nominal Operating Cell Temperature): Irradiance 800 W/m7, ambient temperature 20 T. wind speed 1 Ms 5.5.4.0 (X Haw Ohh Aoha(4aa) 4A'75 Haw D.aln nw•ga•o) 12.06.3 Gr WkV hWaanba a-08.0(2 vbw) Mawnn�q Adaa(8aa) ) -25 0 .25 so 75 go Temperature (•C) LCm North America Solar Business Team LG Electronics U.S.A. Inc 1000 Sylvan Ave, Englewood Cliffs, NJ 07632 Life's Good Contactlgsolar@lge.com www.lgsolarusa.com o� 3511.38 10/0.40 10/0.40 - 55/0.22 _ 4.0/0.16 08/0.31 ` R1S/0.06 Dehll X Datall Y Dehll Z 2811.10 22x1.87 to" dd. f- Short dda ft- , The Mance between the center of the me unting/grourding holes. Product specifications are subject to change without notice. -LG Life's Good- is a registrated trademark of LG Corp. • ' All other trademarks are the property of their respective owners.y I w DS -A3.60 -C -US -F -EN -30829 , . With LG, It's all possible.® Copyright m 2014 LG Electronic. All rights reserved. a 06/17n014 Dimensions (mm/in) PERMIT # Z3 /5 BUTTE COUNTY DEVELOPMENT SERVICES R I ED FOR COD C MPLIANCE DATE �/ 3 �`7 BY �' " �ill'llll' I�Ir�lll_1111111I_I111_IIII� o� 3511.38 10/0.40 10/0.40 - 55/0.22 _ 4.0/0.16 08/0.31 ` R1S/0.06 Dehll X Datall Y Dehll Z 2811.10 22x1.87 to" dd. f- Short dda ft- , The Mance between the center of the me unting/grourding holes. Product specifications are subject to change without notice. -LG Life's Good- is a registrated trademark of LG Corp. • ' All other trademarks are the property of their respective owners.y I w DS -A3.60 -C -US -F -EN -30829 , . With LG, It's all possible.® Copyright m 2014 LG Electronic. All rights reserved. a 06/17n014 Dimensions (mm/in) PERMIT # Z3 /5 BUTTE COUNTY DEVELOPMENT SERVICES R I ED FOR COD C MPLIANCE DATE �/ 3 �`7 BY �' " �• f _4 l+ a •tit �.. C ., sola� =@@ a e • �, SolarEdge Single Phase Inverters.,. For North_'America ° • ,,T �`; ,� + SE3000A-US / SE3800A-US / SE5000A-US'/ SE6000A-US / SE760OA-US / SE10000A-US / SE1140OA-US - The best choice for SolarEdge, enabled systems BUTTE Integrated arc fault protection (Type 1) for NEC 2011690.11 compliance COUNTY Superior efficiency (98/) OCT - 2 9 2015 Small, lightweight and easy to install on provided bracket DEVELOPMENT Built-in module -level monitoring SERVICES Internet connection through Ethernet or Wireless Outdoor and indoor installation. • PERMIT # Fixed voltage inverter, DC/AC conversion only BUTTE COUNTY DEVELOPMENT SERVICES FOR Pre -assembled AC/DC Safety Switch for faster installation CO _ _RANCE_ _ s USA GermAny ItAly FrAnce ` JApAn,= chlnA� IsrAeT _ ' �m �. gy ww.solaredge US YNit1 - +_ solar r ' • • Single Phase inverters for north America. se3000A-Us / se3800A-Us / se5000A-Us / se6000A-Us /,, se7600A-Us / ' - se10000A-Us / se11400A,Us SE3000A- SE3800A- SE5000A-US SE6000A-US SE7600A- I SE1000OA-US SE11400A- US US US I US • OUTPUT t Nominal AC Power 3300 3840 • 5000 6000 @ 11520.' , VA Y " Output 208V ' E768O9980. 10000 + is p 240 �• Max. AC Power VA , 3650 4150 5400 + @ - 6000 8350 10800 @ 12000' Output 208 208V .V �: 10950 v , „ 545 a r @240 • 40V , •' AC Output Voltage Min. -Nom. -Max.' 183 - - 3 • - - 3 - 208 � • . . 229 Vac . e AC Output Voltage ,. Min. -Nom. -Max.` .211 3 3!, 3 , 3 • 3 F t 3 3 240 4 264 Vac 59.3 60 . 60.5 (with 'Hl country setting 57 AC Frequency Min. -Nom.- Hz Max.* - 60 60.5) . Max. `Continuous I 24 I@ 208V 4848 L_ @ •A Current .I R 1 •Output * 14 16 ,25 32 , 48 21. @ . 240V 42"240V, GFDl Utility Monitoring, Islanding Protection, Country {-' Configurable Thresholds. '• 4 t 't -_Yes O70 PERMIT # BUTTE COUNTY DEVELOPMENT SERVICES 11 LIEWEI)FORC®D ANCE BY. DATE r '}. , y , .. f r - .. .. • r - ,. 1. .. ,` - . • "' PERMIT # BUTTE COUNTY DEVELOPMENT SERVICES ' REVIEWED FOR • CODE.0911MIANCE 'DATE InPUT , Recommended Max. DC 4100 4800 6250 - 7500 •9600 . ; + 12400. 14400, W Power" . (STC) ' s . Yes + Transformer -less, ' Ungrounded � Max. Input Voltage t - . 500 ".• Vdc - Nom. DC Input, 325-r ' @ ` r 208V /` - 350 3 @ 240V Vdc , • Voltage r` Max. Input Current"` 16 5 @ 33 @ T I ` ;• Adc. „ L.. 208V , I, I .I a. 208V ' - '.111318 • 15.5 @ 240V a 23.535 30.5 @ 240V ; Max. Input Short 30 ' 45 Adc ' - Circuit _ Current r ., ' Reverse Polarity Protection ; - Yes Ground -Fault Isolation - 600kaSensitivity Detection ; 97.7 - 98.2 98.3 98.3 98. 98 :• 98 • Maximum Inverter Efficiency % . CEC . Weighted'Efficiency 97.5 98 97.5 @ 97.5 ` 97.5 97 @ 208V 97.5 % 208 , ` V .Q • ,, •97.5 @ r ' 98 240V r 240 k - • Nighttime Power Consumption W < 2.5 * < 4 , i ADDITIOnAL FEATURES " Supported Communication RS485, RS232, Ethernet, •ZigBee• (optional) 3 Interfaces �. STAnDARD COmPLIAnCE i Safety UL1741, UL1699B, UL1998 , , CSA 22.2t., ,.. {_, 'k Grid Connection " IEEE1547t" Standards rFCC ". a Emissions "'. part15 class 13,.'.—, f InSTALLATIOn SPECIFICATIOnS , 41 AC output conduit _. size 3/4" minimum / y 24-6. AWG 3/4" 4, 'minimum / 8_3' ' / AWG �r : AWG range' DC input conduit ,size' 3/4" minimum / "^r1-2 strings / 3/4" 4ll minimum"/ _ 1-2 / p of y •"`, 24'6 AWG ' strings)./ 4 14=6 + - �% strings- / �ti I- z.�'• ,� r°+. �..t" AWG r '. f i .. • . Y' Nr v in / mm Ib / GI AWG range 9 high temperature is above Dimensions with 30.5 x 30.5 x 12.5 30.5 x 12.5 x AC/DC Safety 12.5 x 7.5 10.5 / 775 Switch (HxWxD) x 0 / 775 to x 315 x do oversizing guide.pdf 7 x , 315 current 260 may be / x 191 will limit its input 775 to the values stated. •"• x P/Ns are eligible for the Ontario 315 and mlcroFIT (microFIT exc. SE1140oA-US-CAN) x 172 Weight with AC/DC 51.2 / S4.7 / 24.7 88 .4 / 40.1 Safety Switch 23.2 Cooling Natural Convection Fans (user . replaceable) Noise < 25 < 50 Min. -Max. Operating Temperature -13 to +140 / -25 to +60 (CAN version**** Range -40 to +60) Protection Rating NEMA 311 • For •' d other regional 125% settings please f locations contact SolarEdge where the support earl average - in / mm Ib / k 9 d8A �F / C: -earl- ,mite to or i high temperature is above 774F/259C and to 135% for locations where it is below 774F/252C. For detailed information, refer to http•//www.solaredge.us/files/odfs/inverter do oversizing guide.pdf •' A higher current source may be used; the inverter will limit its input current to the values stated. •"• CAN P/Ns are eligible for the Ontario FIT and mlcroFIT (microFIT exc. SE1140oA-US-CAN) t"k V ' i Gob - t . COMPLY WITH CALIFORNIA ELECTRICAL CODE- ARTICLE 690 Q ���� REQUIREMENTS FOR SOLAR (� COMPLY WITH CALIFORN64 PHOTOVOLTAIC SYSTEMS q ELECTRICAL CODE AR77CLE250 -- -- - - � G� REQUIREMENTS FOR GROUNDING j{ and'BONDING PROVIDE SEPARATE GROUNDING CONDUCTOR 1 /1,1 FROM MAIN ELECTRICAL SERVICE PANEL TO 'd REMOTE STRUCTURES AND REMOTE SUBPANELS. CEC ART. 250.32 (D) CALL FOR BUTTE COUNTY - �n BUILDING INSPECTION BEFORE grvO( p"16te"i A' COVERING TO VERIFY J g® 0 INSTALLATION 3� i -�, 'Zt's circuit breaker(s), disconnect(s), Label, T�� a e 1, Wtch(eS) and their 6Ar� e. ' t� REMOVE VEGETATION AND DEBRIS to identify their location accessories, , FROM UNDER AND AWAY FROM and or equipment _ �' / �� 1 STRUCTURE. MAINTAIN CLEARANCE _FOR A FIRE SAFE ENVIRONMENT ! Nom , 0 Provide readily accessible capability to circuit breaker(s), disconnect(s), fuse(s),switch(es) and their accessories as required and defined in California Electrical Code I � T Yxi511��) FfNe. - 1 Y% q 8 fee 13 ��- BUTTE COUNTY COMPLY WITH 2013 CAUFOR/VL4 . 0 C T 2.9 2015 ELECTRICAL CODE— AR77CLE 705 REQUIREMENTS FOR Interconnected . DEVELOPMENT Electric Power Production Systems SERVICES PERMIT # AY'- 7 -­– / BU E OUUNVECOPNT SERVICES REVIEWED FOR CO % E OM PLIANCE DATE_- //.' Ti S. BY t