HomeMy WebLinkAboutB16-0706 000-000-000r GREGORY A. PEITZ ARCHITECT 383 Rio Lindo Ave. Chico, CA. 95926 (530) 894-5719 Structural Calculations for: BUTTE COUNTY APR 0 8 2016 DEVELOPMENT SERVICES PERMIT 3-1�E SUN --TY DEVELOPMENT SFRVIrES REVIEWED FOR CODE Qi5M LIANCE >� � ,o ARC �pRY q No. C21 REN. 7/17 00, • ! • uce-7 60e�-( Pio Cte J:\StruchuaRDesip Data - Residential.doc DESIGN DATA Code used: 2013 California Building Code Floor loading: Live loads: Uninhabitable attics w/o storage: 10psf Uninhabitable attics w/ limited storage: 20psf Habitable attics and sleeping areas: 30psf All others except balconies and decks: 40psf Dead load —101bs/square foot Roof loading: Live loads: 14lbs/SF Dead loads: Typical roof — 20lbs/SF Comp. roof Wind loading: Basic 3 -second gust wind speed (mph) 110 Wind importance factor, 1 1.00 Wind exposure category B Internal pressure coefficient, GCpi +/-0.18 Seismic: Seismic importance factor, l 1.00 Mapped spectral response acceleration; Ss 0.70 S1 0.25 Site class D Design spectral response coefficients; SDS 0.579 SDI 0.317 Seismic design category D Basic seismic -force -resisting systems) Bearing wall system — plywood shearwalls Seismic response coefficient(s), Cs 0.089 Response modification factor(s). R 6.5 Analysis procedure; a Equivalent lateral force procedure Z WIND ANALYSIS Simplified Envelope Procedure Per ASCE 7-10, Chapter 28. 1. Risk category 2 (table 1.5-1) 2. Basic wind speed: 110 mph (figure 26.5-1A) 3. Exposure: B (section 26.7) 4. Kzt = 1.0 (section 26.8) 5. % = 1.0 (figure 28.6-1) 6. Roof slope: 22.620 (5/12) 7. Mean roof height: less than 30 ft. Ps = X K,,t poo ( eq. 28.6-1) Wind Pressures Roof internal zone: (0.24 psf) (.6) = 0.15 psf Roof end zone: (-1.29 psf) (.6) = -0.77 psf Wall internal zone: (17.55 psf) (.6) = 10.53 psf Wall end zone: (25.3 psf) (.6) = 15.18 psf 0 (,/-C-,,(=1 E-�f � t J (�. C {'1F'f !r'i . /C? �cl � Cj �J J r t= `� � •'- - �? c �� �' d' rt ,` r j LINE i , t --SHEARWALLS ` M_R M1 % , :.. _ _.. GDX ply w/ 8d ,S 12 0: _._. 3 coat faster p - - .._ANCHOR BOLTS" „ _1 : i GBG. specified /? O d b s ca 6 -0 o.c. V# rrmin _, - . _-. -. (2� a b 's perwal l is .adecw to i_ a - _❑ _ ch0r'boits' - - - A351RBC _..._... A5s @ t o c -_ _ _ _ - - ---..._... _.. . LJ f . NONE REQ'D OVERTURNING_ i 7- ' U17,- ZJ- : __...... ❑ t No holdown's recta -- - _ G516._Holddown Straps to' Rirn Joist below ..._,,..._... a ,; � p Portal .Frome wl..."5'impson... 5T622.4..str_a s. from 4x. - _..:. p ost to continous header. - HDU2; 55TB16 ,0; 5mgle pour;--S5T520-z 2-Pour-. i _..._ ._.;_.....:........ _._.... .. HDU4------55TB20Povr...----..._........ _. '.- _ .. COLLECTOR/CHORD-�__-__.._._.......... ..._. -_. _ .. p P :E ..... p .. 5T6224 stra s Iices " :.. rag :.. runs ;/�/ COLLECTOR/ CHORD ❑ ( ) 16d's per top q splice ❑ G516 strop sp I ices ❑ 5T&224 strop splices F-1 Drog Truss 2 ❑ RBG's A551s ❑ NONE REO'D COLLECTOR'/ CHORD t. F -I ( ) 16d's per top e sp I ice FJ 6516 strap splices ❑ 5T6224 strap sp I ices ❑ Drag Truss . Project: Location: RAFTER Roof Rafter [2015 International Building Code(2012 NDS)] 1.5 IN x 5.5 IN x 14.0 FT (12 + 2) @ 24 O.C. #2 - Douglas-Fir-Larc g Use ` Section Adequate B 3.5% Controlling Factor: De ion DEFLECTIONS Center Right Live Load 0.60 IN 1_/249 0.04 IN 21J1246 Dead Load 0.20 in 0.00 in Total Load 0.80 IN U186 0.00 IN 2L/Infinity Live Load Deflection Criteria: U240 Total Load Deflection Criteria: U180 RAFTER REACTIONS Reg'd Provided Section Modulus: LOADS REACTIONS Upper Live Load @ A 120 plf 240 Ib Upper Dead Load @ A 42 plf 84 Ib Upper Total Load @ A 162 plf 324 Ib Lower Live Load @ B 164 plf 327 Ib Lower Dead Load @ B 59 pif 118 Ib Lower Total Load @ B 223 plf 445 lb RAFTER! DATA A_ B Bearing Length 0.35 in 0.47 in Span Length 12 ft 2 ft Rafter Pitch 3 :12 Roof sheathing applied to top of joists -top of rafters fully braced. Roof Duration Factor 1.25 Peak Notch Depth 0.00 Base Notch Depth 0.00 MATERIAL PROPERTIES #2 - Douglas -Fir -Larch Base Values Adjusted Bending Stress: Fb = 900 psi FW = 1682 psi C&1.25 CF=1.30 Cr -1.15 Shear Stress: Fv = 180 psi Fv' = 225 psi Cd=1.25 Modulus of Elasticity: E = 1600 ksi E'= 1600 ksi Comp. 1- to Grain: Fc -1- = 625 psi Fc -1' = 625 psi Controlling Moment: 965 ft -Ib 5.995 Ft from left support of span 2 (Center Span) Created by combining all dead loads and live loads on span(s) 2 Controlling Shear. -326 Ib 11.642 Ft from left support of span 2 (Center Span) Created by combining all dead loads and live loads on span(s) 2, 3 Gregory A Peitz, Architect page StruCalc Version 9.0.2.5 4/1/2016 10:20:12 PM Uniform Roof Loading Reg'd Provided Section Modulus: Roof Live Load: LL = 20 psf Roof Dead Load: DL= 7 psf Non -Snow Roof Loaded Area: RLA = 0 sf Slope Adjusted Spans And Loads 1238 lb NOTES Interior Span: L -a4 = 12.37 ft Eave Span: L-Eave-adj = 2.06 ft Rafter Live Load: wL-adj = 38 plf Eave Live Load: wL-Eave-adj = 38 plf Rafter Dead Load: wD adj = 14 plf Rafter Total Load: WT-adj = 51 plf Eave Total Load: wT-Eaveadj = 51 plf Comparisons with required sections: Reg'd Provided Section Modulus: 6.89 in3 7.56 in3 Area (Shear): 2.17 in2 8.25 in2 Moment of Inertia (deflection): 20.09 in4 20.8 in4 Moment: 965 ft -Ib 1060 ft -lb Shear: -326 lb 1238 lb NOTES Project: Location: CEILING JOIST Roof Ratter [2015 International Building Code(2012 NDS)] 1.5 IN x 925 IN x 22.0 FT @ 24 O.C. JJ` #1 - Douglas -Fir -Larch, -Dry Use Section Adequate B�: 8.311 Controlling Factor kpme nEFLECTIONS Center Live Load 0.67 IN U409 Dead Load 0.48 in Total Load 1.15 IN 1-1237 Live Load Deflection (feria: 1-/240 Total Load Deflection Criteria: U180 RAFTER SUPPORT DATA A B Bearing Length 0.40 in 0.40 in Span Length 22 ft Rafter Pitch 3 :12 Roof sheathing applied to top of joists -top of rafters fully braced. Sheathing/sheetro& applied to bottom of joists -bottom of rafters fully braced. Roof Duration Factor 1.00 Peak Notch Depth 0.00 Base Notch Depth 0.00 MATERIAL PROPERTIES #1 - Douglas -Fir -Larch Base Values LOADS REACTIONS Upper Live Load Q A 110 plf 220 lb Upper Dead Load @ A 80 pif 159 Ib Upper Total Load @ A 190 plf 379 Ib Lower Live Load Q B 110 plf 220 Ib Lower Dead Load @ B 80 plf 159 Ib Lower Total Load (g B 190 pif 379 Ib RAFTER SUPPORT DATA A B Bearing Length 0.40 in 0.40 in Span Length 22 ft Rafter Pitch 3 :12 Roof sheathing applied to top of joists -top of rafters fully braced. Sheathing/sheetro& applied to bottom of joists -bottom of rafters fully braced. Roof Duration Factor 1.00 Peak Notch Depth 0.00 Base Notch Depth 0.00 MATERIAL PROPERTIES #1 - Douglas -Fir -Larch Base Values Adiusted Bending Stress: Fb = 1000 psi FW = 1265 psi Cd=1.00 CF=I. 10 Cr -1.15 Shear Stress: Fv = 180 psi FV = 180 psi Cd=1.00 Modulus of Elasticity: E = 1700 ksi E'= 1700 ksi Comp. -I- to Grain: Fc --L= 625 psi Fc - I' = 625 psi Controlling Moment: 2083 ft -ib 11.001 Ft from left support of span 2 (Center Span) Created by combining all dead loads and live loads on span(s) 2 Controlling Shear: -367 Ib 22.313 Ft from left support of span 2 (Center Span) Created by combining all dead loads and live loads on span(s) 2 Comparisons with required sections: Read Provided Section Modulus: 19.76 in3 21.39 in3 Area (Shear): 3.06 in2 13.88 in2 Moment of Inertia (deflection): 75.01 in4 98.93 in4 Moment: 2083 ft -Ib 2255 ft -Ib Shear: -367 lb 1665 lb NOTES t GregoryA Peitz, Architect page of StruCalc Version 9.0.2.5 4/1/2016 10:23:21 PM Project: Location: GARAGE DOOR HEADER Read Roof Beam Section Modulus: [2015 International Building Code(2012 NDS)] 106.31 in3 3.5 IN x 13.5 IN x 16.6 FT 17.81 int ?4F=�ly Graded Western Species - Dry Use Moment of Inertia (deflection): Section Adequate By: 62.9% 717.61 in4 Controlling Factor: Moment 16321 ft -Ib DEFLECTIONS Center Shear. Live Load 0.33 1N L1609 10434 lb Dead Load 0.30 in 474 Total Load 0.63 IN 1-1318 LL = Live Load Deflection Criteria: LI240 Total Load Deflection Criteria: 0180 REACTIONS A B Roof Dead Load: Live Load 2054 lb 2054 Ib 15 Dead Load 1879 Ib 1879 Ib Tributary Width: Total Load 3933 Ib 3933 Ib 2 Bearing Length 1.73 in 1.73 in Wall Load: BEAM DATA 0 Span Length 16.6 ft Non -Snow Roof Loaded Area: Unbraced Length Top 0 ft 220.8 Unbraced Length -Bottom 0 ft Roof Pitch 5 :12 Roof Duration Factor 1.25 MATERIAL PROPERTIES 24F -V4 - Visually Graded Western Species Base Values Adjusted Bending Stress: Fb = 2400 psi ContiVW by. - Fb cmpr = 1850 psi FW = 3000 psi Cd --1.25 Shear Stress: Fv = 265 psi FV = 331 psi Cd --1.25 Modulus of Elasticity. E= 1800 ksi E= 1800 ksi Comp. -L to Grain: Fc --L = 650 psi Fc --L = 650 psi Controlling Moment: 16321 ft -ib 8.3 ft from left support Created by combining all dead and live loads. Controlling Shear. -3933 Ib At support. Created by combining all dead and live loads. Comparisons with required sections: Read Provided Section Modulus: 6528 in3 106.31 in3 Area (Shear): 17.81 int 47.25 in2 Moment of Inertia (deflection): 406.32 tn4 717.61 in4 Moment: 16321 ft -Ib 26578 ft -Ib Shear. -3933 lb 10434 lb v . / f Gregory A Peitz, Architect page StruCalc Version 9.0.2.5 4/1/2016 10:17:23 PM Side One: Adjusted Beam Length: Ladj = 16.6 Roof Live Load: LL = 18.6 psf Roof Dead Load: DL = 15 psf Tributary Width: TW = 11.3 ft Side Two: Total Uniform Load: WT = 474 Roof Live Load: LL = 18.6 psf Roof Dead Load: DL = 15 psf Tributary Width: TW = 2 ft Wall Load: WALL = 0 Non -Snow Roof Loaded Area: RLA = 220.8 iolf SLOPE/PITCH ADJUSTED LENGTHS AND LOADS Adjusted Beam Length: Ladj = 16.6 ft Beam Self Weight: BSW = 10 plf Beam Uniform Live Load: wL = 247 ptf Beam Uniform Dead Load: wD adj = 226 plf Total Uniform Load: WT = 474 ptf Y STATE OF CALIFORNIAJ Prescriptive Residential Additions 300 Ft' or Less, or Additions That Do Not Require HERS Field Verifiicatiion LIFORNIA ENERGY COMMISSION CEC-CFIR-ADD-02-E Revised 01/15 CF1R-ADD-02-E CERTIFICATE OF COMPLIANCE Prescriptive Residential Additions 300 Ft or Less, or Additions That Do Not Require HERS Field Verification (Page 1 of 9) Project Name: Date Prepared: 7-8-1 6 Coaoock Addition V This compliance document is only applicable to additions 300fe or less, or additions that do not require HERS field verification for compliance. When HERS verification is required, a CF1R-ADD-01 shall first be registered with a HERS Provider Data Registry. Alterations to Space Conditioning Systems that are exempt from HERS verification requirements may use the CFIR-ADD-02 and CF2R- ADD -02 Compliance Documents. Possible exemptions from duct leakage testing include: less than 40 ft of ducts were added or replaced; or the existing duct system was insulated with asbestos; or the existing duct system was previously tested and passed by a HERS Rater. If space conditioning systems are altered and are not exempt from HERS verification, then a CFIR-ADD-01 must be completed and registered with a HERS Provider Data Registry. Additions or alterations that utilize Closed Cell Spray Polyurethane Foam (ccSPF) with a density of 1.5 to less than 2.5 pounds per cubic foot having an R -value other than 5.8 per inch, or Open Cell Spray Polyurethane Foam (ocSPF) with a density of 0.4 to less than 1.5 pounds per cubic foot having an R -value of 3.6 per inch, shall complete and register a CFIR ADD -01 with a HERS Provider Data Registry. If more than one person has responsibility for installation of the items on this certificate, each person shall prepare and sign a certificate applicable to the portion of construction for which they are responsible. Alternatively, the person with chief responsibility for construction shall prepare and sign this certificate for the entire construction. All applicable Mandatory Measures shall be met. Temporary labels shall not be removed before verification by the building inspector. A. GENERAL INFORMATION 01 Project Name: Coppock Addition 02 Date Prepared: 7-8-16 03 Project Location: 15089 RICHARDSON SPINGS RD. 04 Building Front Orientation (deg): 165 CA City: Chico 06 Number of Dwelling Units with Additions: 1 05 95973 08 Fuel Type: propane 07 Zip Code: 11 10 Total Conditioned Floor Area (ft) (Addition): 381 09 Climate Zone: Single Family 12 Slab Area (ft): NA 11 Building Type 13 Project Scope: 300-400 sq. ft. BUTTE JUL 212016 DEVELOPMENT SERVICES 4MY14- PERM17 httVll=vvG� I vt t CA Building Energy Efficiency Standards - 2013 Residential Compliance CODE COMPLIANCE January 2015 DATE RY——""` FF L(:—:: - Co p .1 STATE OF CALIFORNIA Prescriptive Residential Additions 300 Ft2 or Less, or Additions That Do Not Require HERS Field Verification :EC-CF1 R -ADD -02-E (Revised 01/15) CALIFORNIA ENERGY GUMMISSIUN CERTIFICATE OF COMPLIANCE CF1R-ADD-02-E Prescriptive Residential Additions 300 Ft or Less, or Additions That Do Not Require HERS Field Verification (Page 2 of 9) Project Name: Coppock Addition Date Prepared: 7-8-16 B. OPAQUE SURFACE DETAILS — Framed (Section 150.2(a)) 01 02 03 04 05 06 07 08 09 10 11 Tag/ID Assembly Type Frame Type Frame Depth (inches) Frame Spacing (inches) Proposed Required Comments Cavity R -value Continuous Insulation R -value U -Factor Appendix JA4 Reference LI -Factor Table Cell wall wood 6 16 19 NA NA NA NA NA ceiling wood 6 16 38 NA 0.025 4.2.1 A21 0.025 floor o/ crawlsp2 wood 6 16 19 NA 0.037 4.4.1 A4 0.037 CA Building Energy Efficiency Standards - 2013 Residential Compliance January 2015 STATE OF CALIFORNIA PrpCCrintivp RpSidpntial Additions 300 Ft2 or Less, or Additions That Do Not Require HERS Field Verification ,...r- - - -- - - - -- __ COMMISSION ;EC-CF1 R -ADD -02-E Revised 01/15 CALIFORNIA EN R CERTIFICATE OF COMPLIANCE CF1R-ADD-02-E Prescriptive Residential Additions 300 Ft or Less, or Additions That Do Not Require HERS Field Verification (Page 3 of 9) Project Name: Coppock Addition I Date Prepared: 7-8-16 C. OPAQUE SURFACE DETAILS — Non -framed (Section 150.1(c)1) 01 02 03 04 05 06 07 08 09 10 11 Tag/ID Assembly Type Assembly Materials Thickness (inches) Proposed Required Comments Core Insulation R -value Continuous Insulation R -value LI -Factor AppendixJA4 Reference LI -Factor from Package A Table Cell I R -value LI -factor Table Cell R -value U -factor R -value LI -factor D. OPAQUE SURFACE DETAILS — Mass Walls (Section 150.1(c)1) 01 02 03 04 05 06 07 08 1 09 10 11 Tag/ID Walls Above 1 Grade Mass Type Mass Thickness (inches) Furring Strip Thickness (inches) Proposed Required Interior Insulation Exterior Insulation Appendix JA4 Reference Interior Insulation Exterior Insulation R -value U -factor R -value LI -factor Table Cell R -value U -factor R -value LI -factor CA Building Energy Efficiency Standards - 2013 Residential Compliance January 2015 STATE OF CALIFORNIA Prescriptive Residential Additions 300 Ft2 or Less, or Additions That Do Not Require HERS Field Verification -EC-CFIR-ADD-02-E (Revised 01/15) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE CFIR-ADD-02-E Prescriptive Residential Additions 300 Ft or Less, or Additions That Do Not Require HERS Field Verification C (Page 4 of 9) Project Name: Coppock Addition Date Prepared: 7-8-16 E. SLAB INSULATION (Table 150.1-A) 01 02 03 04 05 06 Floor Type Proposed Required Comments Insulation R -value Insulation U -factor Insulation R -value Insulation U -factor • Heated slab floors require mandatory slab insulation (see Table 110.8-A). F. RADIANT BARRIER (Section 150.1(c)2 01 02 Radiant Barrier installed below the roof deck and on all gable end walls Comments YES A radiant barrier is required (for Climate Zones 2-15) • Radiant barriers shall meet specific eligibility and installation criteria to receive energy credit for compliance with the Building Energy Efficiency Standards for low-rise residential buildings. Refer to RA4.2.1 • The emittance of the radiant barrier shall be less than or equal to 0.05 as tested in accordance with ASTM C1371 or ASTM E408. For Prescriptive Compliance the attic shall be ventilated to provide a minimum free ventilation area of not less than one square foot of vent area for each 300 ft2 of attic floor area with no less than 30 percent upper vents. Ridge vents or gable end vents are recommended to achieve the best performance. The material should be cut to allow for full airflow to the venting. CA Building Energy Efficiency Standards - 2013 Residential Compliance January 2015 STATE OF CALIFORNIA Prescriptive Residential Additions 300 Ft2 or Less, or Additions That Do Not Require HERS Field Verification 'EC-CFIR-ADD-02-E (Revised 01/15) UALR'VRMA rNrMOT UUMN11001UN CERTIFICATE OF COMPLIANCE CFIR-ADD-02-E Prescriptive Residential Additions 300 Ft or Less, or Additions That Do Not Require HERS Field Verification (Page 5 of 9) Project Name: Coppock Addition Date Prepared: 7-8-16 G. ROOFING PRODUCTS (COOL ROOF) (Section 150.1(c)11) 01 02 03 04 05 06 07 08 09 10 11 12 Mass Roof 25lb/ft2or Greater Roof Pitch Method of Compliance Product Type CRRC Product ID Number Proposed Required Initial Solar Reflectance Aged Solar Reflectance Thermal Emittance SRI (Optional) Aged Solar Reflectance Thermal Emittance SRI (Optional) NO 5:12 ASR/TE asphalt Allowed NA 0.20 0.75 0.20 0.75 Calculated Maximum Calculated Maximum LI -factor SHGC Calculated Calculated based on Allowed ftZ based on Allowed ftZ Allowed % Allowed <400 114.3 75 NA 60 0.32 0.25 NOTES: • Any roof area covered by building integrated photovoltaic panels and solar thermal panels are exempt from the above Cool Roof requirements. • Liquid field applied coatings must comply with installation criteria from section 110.8(i)4. H. FENESTRATION/GLAZING AREAS ALLOWED (Section 150.2(a)1) 01 02 T 03 04 1 05 06 07 08 Maximum Allowed Maximum Allowed Fenestration Area For All Orientations ftZ West -Facing Fenestration Area Only ftZ The Greater The Greater Maximum Maximum Addition Type ftZ Allowed Allowed Comments Maximum Maximum Calculated Maximum Calculated Maximum LI -factor SHGC Calculated Calculated based on Allowed ftZ based on Allowed ftZ Allowed % Allowed <400 114.3 75 NA 60 0.32 0.25 CA Building Energy Efficiency Standards - 2013 Residential Compliance January 2015 STATE OF CALIFORNIA Prescriptive Residential Additions 300 Ft2 or Less, or Additions That Do Not Require HERS Field Verification 'EC-CFIR-ADD-02-E (Revised 01/15) CALIFORNIA ENERtt IT l VIV NIIJJIVIV CERTIFICATE OF COMPLIANCE CFIR-ADD-02-E Prescriptive Residential Additions 300 Ft or Less, or Additions That Do Not Require HERS Field Verification (Page 6 of 9) Project Name: Coppock Addition Date Prepared: 7-8-16 I. FENESTRATION PROPOSED AREAS AND EFFICIENCIES 01 02 03 04 05 06 07 08 09 10 11 12 13 Tag/ID Fenestration Type Frame Type Dynamic Glazing Orientation N, S, W, E or Roof Number of Panes Proposed Fenestration z Area ft Proposed West Facing Fenestration Area ftz Proposed U -factor Proposed SHGC Source Exterior Shading Device Combined SHGC from CFIR-ENV- 03 4040xo operable window vinyl ---------- N 2 16 0 0.32 0.25 NFRC none 0.25 4040xo operable window vinyl ------------- N 2 16 0 0.32 0.25 NFRC none 0.25 4036xo operable window vinyl ------------- S 2 14 0 0.32 0.25 NFRC none 0.25 14 Total Proposed Fenestration Area 46 15 Maximum Allowed Fenestration Area 114.3 16 Compliance Statement Total Proposed Fenestration Area <_ Maximum Allowed Fenestration Area ® Yes ❑ No 17 Total Proposed West -Facing Fenestration Area 0 18 Maximum Allowed West -Facing Fenestration Area 60 19 Compliance Statement Total Proposed West -Facing Fenestration Area 5 Maximum Allowed West -Facing Fenestration Area M Yes ❑ No 20 Proposed Fenestration U -factor 0.32 21 Required Fenestration LI -factor 0.32 22 Compliance Statement Proposed Fenestration U -factor <_ Required Fenestration U -factor ® Yes ❑ No 23 Proposed Fenestration SHGC 0.25 24 Required Fenestration SHGC 0.25 25 Compliance Statement Proposed Fenestration SHGC:5 Required Fenestration SHGC ® Yes ❑ No CA Building Energy Efficiency Standards - 2013 Residential Compliance January 2015 STATE OF CALIFORNIA Prescriptive Residential Additions 300 Ft2 or Less, or Additions That Do Not Require HERS Field Verification EC -CFI R -ADD -02-E (Revised 01/15) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE CF1R-ADD-02-E Prescriptive Residential Additions 300 Ft or Less, or Additions That Do Not Require HERS Field Verification (Page 7 of 9) Project Name: Coppock Addition Date Prepared: 7-8-16 J. SPACE CONDITIONING(SC) SYSTEMS - HEATING/COOLING (Prescriptive section 150.2(b). Alterations to Space Conditioning Systems shall be exempt from HERS verification requirements as prerequisite for use of the CF1R-ADD-02 and CF2R-ADD-02 Compliance Documents. If new space conditioning systems are installed or existing systems are altered and are not exempt from HERS verification, then a CF111-ADD-01 shall be completed and registered with a HERS Provider Data Registry. In each row below for each dwelling unit in the building, check the box that indicates the exemption from HERS verification compliance: ❑ a: space conditioning system was not altered; ❑ b: less than 40 ft of ducts were added or replaced; ❑ c: (exempt from duct leakage testing) if: the existing duct system was insulated with asbestos; ❑ d: (exempt from duct leakage testing) if: the existing duct system was previously tested and passed by a HERS Rater. 01 02 03 04 Dwelling Unit Name SC System Identification or Name SC System Location or Area Served Exemption from HERS Verification Addition existing HVAC existing house + addition ❑ a ® b ❑ c ❑ d 0 0 11 0 11 0 0 0 0 0 0 13 ❑a 0 0 0 0 0 0 0 ❑a 0 0 0 ❑a 0 0 0 0 0 0 11 El 11 0 0 0 0 13 ❑d 0 0 0 0 0 ❑b 0 0 0 ❑b 0 ❑d CA Building Energy Efficiency Standards - 2013 Residential Compliance January 2015 J � STATE OF CALIFORNIA Prescriptive Residential Additions 300 Ft2 or Less, or Additions That Do Not Require HERS Field Verification is. 'EC-CFIR-ADD-02-E (Revised 01/15) CALWUMN1A CNCKU7 I.VMMIJJIVN CERTIFICATE OF COMPLIANCE CF111-ADD-02-E Prescriptive Residential Additions 300 Ft or Less, or Additions That Do Not Require HERS Field Verification (Page 8 of 9) Project Name: Coppock Addition Date Prepared: 7-8-16 K. WATER HEATING SYSTEMS (Section 150.1(c)8) List water heaters and boilers for both domestic hot water (DHW) heaters and hydronic space heating. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 Dwelling Unit Name Water Heating System Identification or Name Water Heating System Location or Area Served Water Heating System Type Water Heater Type # Water Heaters in System Water Heater Storage Volume (gal) Fuel Type Rated Input Type Rated Input Value Heating Efficiency Type Heating Efficiency Value Standby Loss I%) Exterior Insulation R -Value Back -Up Solar Savings Fraction NA CA Building Energy Efficiency Standards - 2013 Residential Compliance January 2015 STATE OF CALIFORNIA Prescriptive Residential Additions 300 Ft2 or Less, or Additions That Do Not Require HERS Field Verification :EC-CF1 R -ADD -02-E (Revised 01115) CALFORNIA ENERGY COMMIS CERTIFICATE OF COMPLIANCE CF1R-ADD-02-E Prescriptive Residential Additions 300 Ft or Less, or Additions That Do Not Require HERS Field Verification (Page 9 of 9) Project Name: Coppock Addition Date Prepared: 7-8-16 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Docume 'on Author Signature: Gregory A. Peitz Company: Sienature Date: Gregory A. Peitz, Architect 7-8-16 Address: CEA/ HERS Certification Identification (if applicable): 383 Rio Undo Ave. City/State/Zip: Phone: Chico, CA 959261(530)894-5719 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. That the energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. 1 will ensure that a registered copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a registered copy of this Certificate of Compliance is requir be included w' a documentation the builder provides to the building owner at occupancy. Responsible Designer Name: Responsiblesign Signature: Gregory A. Peitz � 1,2 Company: Dater DateSign Gregory A. Peitz, Architect 7-8 Address: License: 383 Rio Undo Ave. C21283 City/State/Zip: Phone: Chico, CA 95926 (530) 894-5719 For assistance or questions regarding the Energy Standards, contact the Energy Hotline at: 1-800-772-3300. CA Building Energy Efficiency Standards - 2013 Residential Compliance January 2015 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Coppock Addition Calculation Date/Time: 15:57, Fri, Apr 01, 2016 Calculation Description: Addition Alone Slab ex HVAC Input File Name: Coppock Add.ribd CF1 R -PRF -01 Page 1 of 8 GENERAL INFORMATION CaICERTS inc. 01 01 Project Name Coppock Addition Addition Area (excl. existing) ft2 TOTAL AREA Existing Bedrooms Addition Bedrooms Total Bedrooms 1680" 02 Calculation Description Addition 500 ft2 03 Project Location 15089 RICHARDSON SPINGS RD. 04 City CHICO, CA 05 Standards Version Compliance 2015 06 Zip Code 95973 07 Compliance Manager Version BEMCmpMgr 2013-4b (433) 08 Climate Zone CZ11 09 Software Version CBECC-Res 2013-4b (812) 10 Building Type Single Family 11 Front Orientation (deg/Cardinal) 165 12 Project Scope Newly Constructed (Addition Alone) 13 Number of Dwelling Units 1 14 Total Cond. Floor Area (ft) 381 15 Number of Zones 1 16 Slab Area (ft2) 0 17 Number of Stories 1 18 Addition Cond. Floor Area 381 19 Natural Gas Available No 20 Addition Slab Area (ft2) 0 21 Glazing Percentage (%) 12.1% ADDITION ALONE PROJECT ANALYSIS PARAMETERS CaICERTS inc. 01 02 , 03 04 05 06 Existing Area (excl. new addition) ft2 Addition Area (excl. existing) ft2 TOTAL AREA Existing Bedrooms Addition Bedrooms Total Bedrooms 1680" 381 2061* 2 0 2 BUTTE COUNTY APR 0 8 2016 DEVELOPMENT PERMIT #A - 0? �: G SERVICES BUTT ECOUNTY DEVEL PMENT SERVICES 816-0706 ---,REVIEWED FOR E 0.8MP�CE� DAl-E___ Registration Number: 216-NO12310OA-000000000-0000 Registration Date/Time: 2016-04-01 16:05:56 CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 HERS Provider: CaICERTS inc. Report Generated at: 2016-04-0115:58:21 1 " CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01 Project Name: Coppock Addition Calculation Date/Time: 15:57, Fri, Apr 01, 2016 Page 2 of 8 Calculation Description: Addition Alone Slab ex HVAC Input File Name: Coppock Add.ribd COMPLIANCE RESULTS 01 Building Complies with Computer Performance 02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider. 03 This building incorporates one or more Special Features shown below 06 REQUIRED SPECIAL FEATURES The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.:> Window overhangs and/or fins HERS FEATURE SUMMARY ENERGY USE SUMMARY provided in the building components tables below. 04 05 06 07 08 Energy Use (kTDV/ft2-yr) Standard Design Proposed Design Compliance Margin Percent Improvement Space Heating 66.29 57.66 8.63 13.0% Space Cooling 55.17 56.72 -1.55 -2.8% IAQ Ventilation 0.00 0.00 0.00 0.0% Water Heating 0.00 0.00 0.00 0.0% Photovoltaic Offset ---- _ _ 0.00 0.00 — Compliance Energy Total 121.46 k Ale 114.38 7.08 5.8% REQUIRED SPECIAL FEATURES The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.:> Window overhangs and/or fins HERS FEATURE SUMMARY The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is provided in the building components tables below. Building -level Verifications: • -- None -- Cooling System Verifications: e ?-i° NTT �` i t • Minimum Airflow • Fan Efficacy Watts/CFM -x i Ji`J 9SION HVAC Distribution System Verifications: • Duct Sealing • e, :• y .� ( t CAJED Domestic Hot Water System Verifications: • —None -- Registration Number: 216-NO12310OA-000000000-0000 Registration Date/Time: 2016-04-01 16:05:56 HERS Provider: CaICERTS inc. CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 Report Generated at: 2016-04-0115:58:21 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Coppock Addition Calculation DatelTime: 15:57, Fri, Apr 01, 2016 Calculation Description: Addition Alone Slab ex HVAC Input File Name: Coppock Add.ribd CFI R -PRF -01 Page 3 of 8 ENERGY DESIGN RATING * This is the sum of the annual TDV energy consumption for energy use components included in the performance compliance approach for the Standard Design Building (Energy Budget) and the annual TDV energy consumption for lighting and components not regulated by Title 24, Part 6 (such as domestic appliances and consumer electronics) and accounting for the annual TDV energy offset by an on-site renewable energy system. Reference Energy Use Energy Design Rating 'F Margin Percent Improvement Total Energy (kTDV/f2-yr)* 182.72 - 175.64 7.08 3.9% includes calculated Appliances and Miscellaneous Energy Use (AMEU) BUILDING - FEATURES INFORMATION 01 02 03 04 05 06 07 Project Name Conditioned Floor Area (ft2) Number of Dwelling Units Number of Bedrooms Number of Zones Number of Ventilation Cooling Systems Number of Water Heating Systems Coppock Addition 381 1 2 1 0 0 ZONE INFORMATION 01 02 03 04 05 06 07 Zone Name Zone TypeHVAC System Name ,.:; Zone Floor Area (ft - Avg. Ceiling Height Water Heating System 1 Water Heating System 2 Addition Conditioned - ; New System .381 ,. 8 ; Gross Area (ft) Window & Door Area (ft2) OPAQUE SURFACES 01 02 03 04 05 06 1 1'107J V L L 08 Name Zone Construction Azimuth Orientation Gross Area (ft) Window & Door Area (ft2) Tilt (deg) Add Wall Front Addition 2x6 R-19 165 Front 142 14 90 Add Wall Back Addition 2x6 R-19 345 Back 142 32 90 Add Wall Right Addition 2x6 R-19 75 Right 85 90 Add to Gar Wall Addition»Garage House to Garage R19 Wall 202 20 Addition Ceiling Addition R-38 Ceiling 381 Floor Over Crawlspace Addition Raised Crawl R19 381 Gwall Front Garage Wall RO 165 Front 171 128 90 Gwall Back Garage Wall RO 345 Back 171 90 Gwall Left Garage Wall RO 255 Left 202 90 Gar Ceiling Garage R-38 Ceiling 418 Registration Number: 216-NO12310OA-000000000-0000 Registration Date/Time: 2016-04-01 16:05:56 CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 HERS Provider: CaICERTS inc. Report Generated at: 2016-04-0115:58:21 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Coppock Addition Calculation DatefTime: 15:57, Fri, Apr 01, 2016 Calculation Description: Addition Alone Slab ex HVAC Input File Name: Coppock Add.ribd CFI R -PRF -01 Page 4 of 8 ATTIC 01 02 03 04 05 06 07 08 Name Construction Type Roof Rise Roof Reflectance Roof Emittance Radiant Barrier Cool Roof Attic Shingle RB Ventilated 5 0.1 0.85 Yes No WINDOWS 01 02 03 04 05 06 07 08 09 10 Name Type Surface (Orientation -Azimuth) Width (ft) Height (ft) Multipli er Area (ft) U -factor SHGC Exterior Shading 4036 xo Window Add Wall Front (Front -165) 4.0 3.5 1 14.0 0.34 0.29 Insect Screen (default) (2) 4040 xo Window Add Wall Back (Back -345) 4.0 4.0 2 32.0 1 0.34 1 0.29 1 Insect Screen (default) DOORS 01 02 03 04 Name Side of Building Area (ft2) U -factor 3068 ); Add to Gar Wall 4r 20.0 0.50 Garage Door Gwall Front 128.0 1.00 OVERHANGS AND FINS 01 02 03 04 OS 06 07 08 09 10 11 12 13 14 Overhang Left Fin Right Fin Window Depth Dist Up Left Extent Right Extent Flap Ht. Depth Top Up DIstL Bot Up Depth Top Up Dist R Bot Up 4036 xo 1.5 1.33 20 7 0.5 0 0 0 0 0 0 0 0 (2) 4040 xo 1.5 1.33 20 7 0.5 0 0 0 0 0 0 0 0 Registration Number: 216-NO12310OA-000000000-0000 Registration Date/Time: 2016-04-01 16:05:56 CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 HERS Provider: CaICERTS Inc. Report Generated at: 2016-04-0115:58:21 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Coppock Addition Calculation Date/Time: 15:57, Fri, Apr 01, 2016 Calculation Description: Addition Alone Slab ex HVAC Input File Name: Coppock Add.ribd CF1R-PRF-01 Page 5 of 8 OPAQUE SURFACE CONSTRUCTIONS 01 02 03 04 05 06 07 System Type Heating Unit Name Cooling Unit Name Fan Name Total Cavity Winter Design Other Heating and Cooling System Construction Name Surface Type Construction Type Framing R -value U -value Assembly Layers • Inside Finish: Gypsum Board Wall RO Exterior Walls Wood Framed Wall 2x4 @ 16 in. O.C. none 0.387 • Cavity/ Frame: no insul. /2x4 - Floor Surface: Carpeted Floors Over • Floor Deck: Wood Siding/sheathing/decking Raised Crawl R19 Crawlspace Wood Framed Floor 2x6 @ 16 in. O.C. R 19 0.049 • Cavity/Frame: R -19/2x6 • Inside Finish: Gypsum Board Ceilings (below • Cavity/Frame: R-9.1 /2x4 R-38 Ceiling attic) Wood Framed Ceiling 2x4 @ 16 in. O.C. R 38 0.025 • Over Ceiling Joists: R-28.9 insul. • Cavity/ Frame: no insul. / 2x6 - Roof Deck: Wood Siding/sheathing/decking Shingle RB Attic Roofs Wood Framed Ceiling 2x6 @ 16 in. O.C. none 0.624 • Roofing: Light Roof (Asphalt Shingle) • Inside Finish: Gypsum Board • Cavity/Frame: R -19/2x6 2x6 R-19 Exterior Walls Wood Framed Wall 2x6 @ 16 in. O.C. R 19 0.072 • Exterior Finish: 3 Coat Stucco • Inside Finish: Gypsum Board • Cavity/ Frame: R -19/2x6 House to Garage R19 Wall Interior Walls Wood Framed Wall 2x6@ 16 in.:O.C. R 19 0.067 Other Side Finish: Gypsum Board BUILDING ENVELOPE - HERS VERIFICATION 01 02 03 04 Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage CFM50 Not Required Not Required Not Required --- SPACE CONDITIONING SYSTEMS 01 02 03 04 05 06 SC Sys Name System Type Heating Unit Name Cooling Unit Name Fan Name Distribution Name New System Other Heating and Cooling System Furn92 14 Seer New Fan New Ducts Registration Number: 216-NO12310OA-000000000-0000 Registration Date/Time: 2016-04-01 16:05:56 CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 BUTTE C'OUNTY BU'! ._, I p HERS Provider: CaICERTS inc. Report Generated at: 2016-04-0115:58:21 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Coppock Addition Calculation Date/Time: 15:57, Fri, Apr 01, 2016 Calculation Description: Addition Alone Slab ex HVAC Input File Name: Coppock Add.ribd HVAC - HEATING UNIT TYPES 01 02 03 Name Type Efficiency Furn92 CntrlFurnace - Fuel -fired central furnace 92 AFUE CFI R -PRF -01 Page 6 of 8 HVAC - COOLING UNIT TYPES 01 02 03 04 05 06 07 Name System Type Efficiency EER SEER Zonally Controlled Multi -speed Compressor HERS Verification 14 Seer SplitAirCond 11.7 14 Not Zonal Single Speed 14 Seer -hers -cool HVAC COOLING - HERS VERIFICATION 01 02 03 04 05 06 Name Verified Airflow Airflow Target Verified EER Verified SEER Verified Refrigerant Charge 14 Seer -hers -cool Required 350 Not Required Not Required Not Required st. LJ '.J ! i L l it i1 dE, 3 `f HVAC - DISTRIBUTION SYSTEMS 'JILDING DI V10 leu 01 02 03 04 ,.•. ,; ,.°' 05 06 �: `' "r Name Type Duct Leakage Insulation R -value Duct LocationDu Bypass ct -HERS Verification New Ducts DuctsAttic Sealed and tested 6 Attic None New Ducts -hers -dist HVAC DISTRIBUTION - HERS VERIFICATION 01 02 03 04 05 06 07 08 Name Duct Leakage Verification Duct Leakage Target (%) Verified Duct Location Verified Duct Design Buried Ducts Deeply Buried Ducts Low -leakage Air Handler New Ducts -hers -dist Required 6.0 Not Required Not Required Not Required Not Required --- HVAC-FAN SYSTEMS 01 02 03 04 Name Type Fan Power (Watts/CFM) HERS Verification New Fan Single Speed PSC Furnace Fan 0.58 New Fan -hers -fan HVAC FAN SYSTEMS - HERS VERIFICATION 01 02 03 Registration Number: 216-NO12310OA-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2016-04-01 16:05:56 Report Version - CF1R-03112016-433 HERS Provider: CaICERTS inc. Report Generated at: 2016-04-0115:58:21 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1 R -PRF -01 Project Name: Coppock Addition Calculation Date/Time: 15:57, Fri, Apr 01, 2016 Page 7 of 8 Calculation Description: Addition Alone Slab ex HVAC Input File Name: Coppock Add.ribd Name Verified Fan Watt Draw Required Fan Efficiency (Watts/CFM) New Fan -hers -fan Required 0.58 BUTTE C0Ui,` 5 °+ BUILDING. eg n$a 6 Registration Number: 216-NO123100A-000000000-0000 Registration Date/Time: 2016-04-01 16:05:56 HERS Provider: CaICERTS inc. CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 Report Generated at: 2016-04-0115:58:21 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Coppock Addition Calculation Date/Time: 15:57, Fri, Apr 01, 2016 Calculation Description: Addition Alone Slab ex HVAC Input File Name: Coppock Add.ribd CF1 R -PRF -01 Page 8 of 8 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Documentation Author Signature: Cres Aitz Greg Peitz Company: Signature Date: Gregory A. Peitz Architecture 2016-04-01 16:05:56 Address: CEA/HERS Certification Identification (If applicable): 383 Rio Lindo Ave City/State/Zip: Phone: Chico, CA 95926 530-894-5719 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance. 2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. Responsible Designer Name: Responsible Designer Signaturew Seitz Greg Peitz Company: Date Signed: Gregory A. Peitz Architecture s' 2016-04-01 16:05:56 Address: License: 383 Rio Lindo Ave C21283 City/State/Zip: Phone: Chico, CA 95926 530-894-5719 BUIFTE COUNITYYpq� II BUi€�L.f"NGA i...%I�.� S!ON Po Digitally signed by CaICERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration Provider responsibility for the accuracy of the information. Registration Number: 216-NO12310OA-000000000-0000 Registration Date/Time: 2016-04-01 16:05:56 HERS Provider: CaICERTS inc. CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 Report Generated at: 2016-04-0115:58:21 PROPOSED ADDITION - BUT T F, DDITION- -EXI STI NO RESIDENCE MUD GREEK �(E) WELL SEPTIC TANK hh �2-1 PERMIT# b/f, "0'7,U G BUTTE COUNTY DEVELOPS .,4FNT SEPVICES REVIEWEf: F= CODE PE DATE Z BY G MINIMUM EROSION AND SEDIMENT CONTROLS FOR PROJECTS DISTURBING LEW THAN ONE ACRE THE BMP'S ($EST MANAGEMENT PRACTICES) LISTED BELOW MUST BE IN PLACE DURING THE RAINY SEASON (OCTOBER 15 THROUGH APRIL 15) AND MAY BE REQUIRED AT OTHER TIMES BASED ON WEATHER AND 51TE CONDITIONS THROUGHOUT THE YEAR. THE BMP'S LISTED ARE MINIMUM REQUIREMENTS AND ADDITIONAL 5MP'5 COULD BE REQUIRED BASED ON SITE CONDITIONS. `` Gj I. STABILIZED ENTRY PROVIDE MINIMUM 5" TO b" FRACTURED POCK 50' LONG x IS' WIDE BY �ON 6" DEEP OVER CONSTRUCTION SRADE FABRIC. 2 STREETS TRACKED RACK OR ONTO DURING A RAIN ADKAYS MUST BE CLEANED ON A DAILY BASIS. WHEN NT THERE SHALL BE NO I TRACKING OF SOILS +�L�G ONTO THE STREET. 5. WATTLES SHALL BE INSTALLED PROPERLY, BEHIND CURB OR SIDEHALK5. 4. ROCK 5A65 (MINIMUM 2 PER SIDE) AT ALL DRAIN INLET LOCATIONS WITHIN 150OF THE PROJECT SITE. 5. INTERNAL FILTERS SHALL BE PLACED INSIDE EACH DRAIN INLET. b. TRASH BARS SHALL BE PLACED ACROSS THE BACK OF ALL DRAIN INLETS. 'I. 5TABILIZE ALL DISTURBED SOILS IN THE FRONT YARD AREAS WITHIN I5' OF THE BACK CURB OR SIDEWALK. (5TRAW OR ER05ION BLANKETS MAY BE USED FOR THIS APPLICATION) b. STABILIZE ALL SLOPES WHERE EROSION COULD OCCUR AND CAUSE SILT RUN OFF. (STRAW, VISQUEEN OR ER05ION BLANKETS MAY BE USED FOR THIS APPLICATION) Q. ALL PAINT, FUEL, CONSTRUCTION PRODUCTS ETC. SHALL BE STORED IN A COVERED LOCATION AWAY FROM 51DEWALK5 AND STORM DRAIN INLETS. 10. PORTABLE CHEMICAL TOILETS IF PROVIDED ON THE 51TE MUST BE KEPT OFF OF 5TREETS AND 51DEWALK5 AND A LEAST 50' FROM THE NEAREST STORM DRAIN. 11. ALL TRASH MUST BE COLLECTED AND STORED PROPERLY. DO NOT LET ITEMS SUCH AS DRYWALL MUD BOXES, PAINT BUCKETS, CLEANIN6 MATERIAL CONTAINERS, ETC. COME IN CONTACT WITH ANY RAINFALL OR STORM HATER RUNOFF. 12. PROVIDE A DES16NATED AREA FOR CONCRETE WASHOUT. HAY 5AIL5 LINED WITH VISOUEEN MAY BE USED FOR THI5 APPLICATION. ROLLAWAY BINS MAY ALSO BE USED. ALL CONCRETE WASHOUT SYSTEMS SHALL BE PLACED OFF OF THE PAVED STREETS. 15. AFTER INSTALLATION OF THE ABOVE ITEMS ARE COMPLETE, A MAINTENANCE PR06RAM NEEDS TO BE DEVELOPED TO INSURE THE CONTINUED EFFECTIVENESS OF YOUR BMP'S_ BUTTE COUNTY SITE PLAN 0 9 Zola ,R14 ~ 0706 G R E G O R Y A. P E I T Z OWNER: PHIL COPPOCK SITE INFO: SHEET ADDRE55:1508Q RICHARDSON SPRINGS RD 15051 RIOHARD50N SPRINGS RD. ARCHITECT CHICO,CA CHICO,GA 383 Rio Lindo Ave. Chico, CA. 95926 (530) 894-5719 PHONE: 550-545-1051 APN: 047-250-107 of: ONE 4/4/2016 11:12:57 AM O O t O I .2 I � (u) 3066 Y42 LT. 111 (R) (E) 66310 FX r (-======= --- --- --- (R) (E) 4030 GRDN. `\ BATN LAUNDRY ' JJl 142 LITE. 0 II \ �I lyyp II - - - -I �- II 24 J I ISI JI I r------- --24 6�------------ r------- - - - ------ I I (E) 4646 DBL. CASE. I� COMPLETELY (R) (E) GARAGE, BATHROOM, 4 LAUNDRY ROOM O INCLUDING FOUNDATION w m III I �mllll I II I (R) (E) \ i 3068 � I i i"F� (E) II � (R) (E) I FX 6 3068 I OVAL it IR O ARAO r :LU: I, C� C� V I I alil � I II II II II II IIII Li=====__-__----------�_____�=_-___�� (R) (E) 6070 O.G.D. (R) (E) 4030 XO AS -BUILT / DEMOLITION PLAN 1/4" = l'-0" (E) 2468 �(E) N.I.O. 6' GLC. (E) 22 ATTIC (E) BEDROOM 2 5'01_6. (E)I (E) 4040 XO 1020 FX (E) 4646 DBL. CASE. 37'-3 op I I' -.T,211 6'-7Y2"e 00 5.6' 6.6' B A 7.0' 2E) E BATH 6 6 2 2 6 FR. 8' GLC. - -(N) 4040 XO (N) 4040 O (E) 4646 XO (E) 4646 XO (N) 4040 XO E _ S � P _ - 3068 (E) 2468 /�� (N) (E) 1! `L 2468 it 1N.I.0. 2 2468 6' GLC. 0 (E) `9 �L-L 5 8 P _� 26618 m DEN - � 6' GLC. BEDROOM I I (N) ( i) (N) 2668 z O ARAO E HALL (E)22ATTIC. x5C 4 6' PL. HT. 8 GLC. y� (E) ACC CONC. I?k4 1626 2'-O" FX S P SHELVES `�'-`12" OVAL k N(E) (N) (2) 2468 (N) (2) 2468 110.6' =ry (E) I 2468 3068 50. . N a t't� TREE I I I BEDROOM 2 0 Q C1_5R. LAUNDRY 6 GLC. I I N.I.G. D_ _►^I i 5'01_0. 16060 GAR. DR. (N) 4036 X0 A �) (E) 4040 XO IQ " '-0 2 2 16'-O" 1020 FX FLOOR PLAN 1/4" = I'_O" 500pf= OF V40RK THIS PERMIT SHALL BE LIMITED TO: I. THE COMPLETE DEMOLITION OF ALL STRUCTURAL, PLUMBING, MECHANICAL, 4 ELECTRICAL IN THE EXISTING ATTACHED GARAGE, LAUNDRY, 4 BATHROOM AS SHOWN ON THE DEMOLITION 'PLAN. 2. THE CONSTRUCTION OF A NEW ATTACHED GARAGE, DEN, IHALLHAY, LAUNDRY ROOM, $ WALK -IN -CLOSET AS 5HOHN. 5HEARV4ALL SGHEDULE SYMBOL: SHEARWALL: GDX PLYWD. OR OSB Q w/ 6d'5 ® 6",12" O.G., 16d SINKER SILL NAILS ® 6" O.G. Q5/8" GDX PLYWD. OR OSB 4 w/ 8d'S ® 411,1211 O.G., w/ 4x STUDS ® ADJ. PANEL SPLICES, 16d SINKER SILL NAILS ® 5Yy O.0 Q5/51, GDX PLYHD. OR 055 V# 6d'5 ® 5",12" O.G. w/ 4x STUDS ® ADJ. PANEL SPLICES, Ibd SINKER SILL NAILS ® 4Y2" O.G. 5/8" GDX PLYHD. OR O55 Q w/ 6d'S ® 211,121, O.G. w/ 4x STUDS ® ADJ. PANEL SPLICES, Ibd SINKER SILL NAILS ® 2Yy O.G. I. NAILS SHALL BE COMMON NAILS (2Y2"x.131"), TYP., U.O.N. 2. ALL PLYWOOD PANELS SHALL HAVE ALL EDGES BLOCKED. ir 111 ITO. GOVERNING CODES: 2013 GBG, 2013 CRC, 2013 GEC, 2013 GPO, 2013 CMG, 2013 CFC, 2013 CALIF. HEALTH $ SAFETY CODE AMENIDMENTS 2013 CALIF. ENERGY CODE EFFICIENCY STANDARDS, ZONE II 2013 CALIF. AGGE5515IL17Y REQUIREMENTS AMERIGAN5 w/ DISABILITIES ACT, 2012 EDITION NFPA 101, 2013 GGBSC OCCUPANCY GROUP: OROUP: R3 / U ALLOWABLE HEIGHT AND BUILDING AREAS (TABLE 503) ALLOHABLE AREA: UNL I M I TED ACTUAL FLOOR AREA: 247cl S.F. ALLOWABLE 5TORY/HEIOHT: (3) STORIES / 40'-0" ACTUAL STORY/HEIGHT: (1) STORY / 21'-0" CONSTRUCTION TYPE: TYPE VB AUTOMATIC SPRINKLER: NOT REQUIRED HILDLAND URBAN FIRE INTERFACE: NOT APPLICABLE MINIMUM TITLE 24 REOU I REMENTS 1. ALL NEW WINDOWS AND DOORS WITH GLAZING SHALL HAVE A MAX. SHOO OF 0.25 AND A MAX. U -VALUE OF 0.32. 2. NO MORE THAN 40' OF NEW DUCTS SHALL BE INSTALLED. NEW DUCTS TO BE MIN. R-6. 3. RADIANT BARRIER ROOF SHEATHING REQUIRED OVER ADDITION AREA ONLY. O ENERAL NOTES G-1 MISCELLANEOUS I. PROVIDE 4" HIGH x I" WIDE STREET ADDRESS NUMBERS OF CONTRA5TING COLOR, VISIBLE FROM STREETS. CONCRETE I. CONCRETE TO BE 5 SACK MIX, 2500 PSI ® 28 DAYS 2. RE I NFORG I NG STEEL TO BE I NTERMED I ATE ORADE DEFORMED BARS -TYPE N OR 40. ROUGH CARPENTRY 1. INSTALL BLOCKING AS REQUIRED TO SUPPORT FINISH HARDWARE AND FIRE STOPPING TO OUT OFF CONGEALED DRAFT OPENINGS AS REQUIRED BY CODES. 2. STRUCTURAL FRAMING SHALL BE DOUGLAS FIR TO THE GRADES INDICATED OR BETTER (MPA GRADING RULES) UNLESS NOTED OTHERWISE. CONGEALED BEAMS AND POSTS ......................... NO. 2 EXPOSED BEAMS AND POSTS...............................NO. I 2x JOISTS AND RAFTERS........................................NO. 2 STUD, 51 LLS, PLATES...................................................NO. 2 SILLS ON CONCRETE....................................................PTHF M15C. FRAMING NOT NOTED....................................NO. 2 3. PLYWOOD SHALL BE OF THE DE51ONATED GRADE AND SHALL MEET THE REOUIREMENTS OF THE U.S. PRODUCT STANDARDS P5 4. NAILS AT PLYWOOD PANELS SHALL HAVE 5/8" EDGE DISTANCE AND SHALL NOT PENETRATE FAGS -PLY. 5. NO PIECE OF PLYWOOD ROOF, FLOOR OR WALL SHEATHING SHALL BE LESS THAN 12" IN LEAST DIRECTION. 6. FRAMING HARDWARE SHALL BE SIMPSON STRONG -TIE OR APPROVED EQUAL, WITH CONNECTORS AS SPECIFIED 7. PROVIDE 50LID BEARING CONTINUOUS FROM ALL BEAMS TO FOUNDATION. 8. PROVIDE FIRE BLOCKING IN CONGEALED SPACES VERTICALLY AND HORIZONTALLY IN ACCORDANCE w/ 2013 G.R.G. SECTION 8302.11. Q. FASTENERS FOR PRESERVATIVE TREATED AND FIRE TREATED WOOD SHALL BE OF HOT DIPPED ZING COATED GALVANIZED STEEL, SILICON BRONZE OR COPPER. THE COATING WEIGHTS FOR ZING COATED FASTENERS SHALL BE IN ACCORDANCE w/ ASTMA 153. 2013 G.R.G. SECTION R317.3. 10. BEARING WALL HDR5. SHALL BE 4x10 #2 OR 6x8 D.F. #1 MIN., TYP., U.O.N. PLUMBING I. THE AGGREGATE AREA OF PLUMBING VENTS SHALL BE 12.57 502. INCHES, MIN. 2. OAS FIRED WATER HEATER TANKS SHALL BE FASTENED TO THE ADJACENT FRAMING w/ 16 OAUOE METAL STRAP (0516 OR EG) w/ MIN. 2" LONG #12 WOOD 50REH5 ® 4" ABOVE CONTROLS AND WITHIN 12" OF THE TOP OF THE TANK. 3. ALL NON-COMPLIANT PLUMBING FIXTURES SHALL BE REPLACED w/ HATER CONVERSING PLUMBING FIXTURES. NON-COMPLIANT PLUMBING FIXTURES AS FOLLOWS: A. ANY TOILET MANUFACTURED TO USE MORE THAN 1.28 GAL. OF WATER PER FLUSH. B. ANY SHOWER HEAD MANUFACTURED TO HAVE A FLOW CAPACITY OF MORE THAN 2.0 GAL. OF HATER PER MIN. G. ANY KITCHEN FAUCET THAT EMITS MORE THAN 1.8 GAL. OF WATER PER MIN. D. ANY LAVATORY FAUCET THAT EMITS MORE THAN 1.5 GAL. OF HATER PER MIN. 4. SHOWER AND TU5-5HOHER COMBINATIONS SHALL BE PROVIDED w/ INDIVIDUAL CONTROL VALVES OF THE PRE55URE BALANCE OR THE THERMOSTATIC MIXING VALVE TYPE. 5. INSTALL A 4" DRAIN FOR BUILDINGS PROVIDING MORE THAN (3) HATER CLOSETS. 6. HORIZONTAL DRAINAGE PIPING SHALL BE 2% MIN.5 0 MECHANICAL I. DRYER DUCT TO BE MIN. 4" (P TO THE OUTSIDE, EQUIPPED WITH A BACK -DRAFT DAMPER. 4" 4) DUCT LENGTH 15 LIMITED TO 14' WITH 2 ELBOHS. OTHER LENGTHS OR SIZES A5 PERMITTED OR REQUIRED BY THE MANUFACTURE'S INSTALLATION INSTRUCTIONS MUST BE APPROVED BY BUILDING OFFICIAL. (SUBMIT REQUEST FOR MODIFICATION5) 2. 51NOLE-WALL METAL PIPE SHALL NOT BE USED AS A VENT IN DWELLINGS AND RESIDENTIAL OCCUPANCIES. 3. ALL ENVIRONMENTAL AIR DUCTS SHALL BE A MIN. OF 3' AWAY FROM ANY OPENINGS INTO THE BUILDING. 4. ALL BATH BATH FANS SHALL HAVE A BACKDRAFT DAMPER. BUTTE COUNTY IJUL 21 2016 DEVELOPMENT SERVICES re5T� NORTH PERMIT # BUTTE COUNTY DEVELOPMENT SERVICES REVIEWED FOR CODE COMPLIANCE DATE L BY Revision: Date: (E) 4646 DBL. CASE. 00 N (E) BST 2468, (E) 4646 DBL. CASE. FR. (E) 00 3068 (E) C*A .Q " 2468 rn (E) 2468 ) L:22 UU� BEDROOM 66,8 5' CLO. AS -BUILT / DEMOLITION PLAN 1/4" = l'-0" (E) 2468 �(E) N.I.O. 6' GLC. (E) 22 ATTIC (E) BEDROOM 2 5'01_6. (E)I (E) 4040 XO 1020 FX (E) 4646 DBL. CASE. 37'-3 op I I' -.T,211 6'-7Y2"e 00 5.6' 6.6' B A 7.0' 2E) E BATH 6 6 2 2 6 FR. 8' GLC. - -(N) 4040 XO (N) 4040 O (E) 4646 XO (E) 4646 XO (N) 4040 XO E _ S � P _ - 3068 (E) 2468 /�� (N) (E) 1! `L 2468 it 1N.I.0. 2 2468 6' GLC. 0 (E) `9 �L-L 5 8 P _� 26618 m DEN - � 6' GLC. BEDROOM I I (N) ( i) (N) 2668 z O ARAO E HALL (E)22ATTIC. x5C 4 6' PL. HT. 8 GLC. y� (E) ACC CONC. I?k4 1626 2'-O" FX S P SHELVES `�'-`12" OVAL k N(E) (N) (2) 2468 (N) (2) 2468 110.6' =ry (E) I 2468 3068 50. . N a t't� TREE I I I BEDROOM 2 0 Q C1_5R. LAUNDRY 6 GLC. I I N.I.G. D_ _►^I i 5'01_0. 16060 GAR. DR. (N) 4036 X0 A �) (E) 4040 XO IQ " '-0 2 2 16'-O" 1020 FX FLOOR PLAN 1/4" = I'_O" 500pf= OF V40RK THIS PERMIT SHALL BE LIMITED TO: I. THE COMPLETE DEMOLITION OF ALL STRUCTURAL, PLUMBING, MECHANICAL, 4 ELECTRICAL IN THE EXISTING ATTACHED GARAGE, LAUNDRY, 4 BATHROOM AS SHOWN ON THE DEMOLITION 'PLAN. 2. THE CONSTRUCTION OF A NEW ATTACHED GARAGE, DEN, IHALLHAY, LAUNDRY ROOM, $ WALK -IN -CLOSET AS 5HOHN. 5HEARV4ALL SGHEDULE SYMBOL: SHEARWALL: GDX PLYWD. OR OSB Q w/ 6d'5 ® 6",12" O.G., 16d SINKER SILL NAILS ® 6" O.G. Q5/8" GDX PLYWD. OR OSB 4 w/ 8d'S ® 411,1211 O.G., w/ 4x STUDS ® ADJ. PANEL SPLICES, 16d SINKER SILL NAILS ® 5Yy O.0 Q5/51, GDX PLYHD. OR 055 V# 6d'5 ® 5",12" O.G. w/ 4x STUDS ® ADJ. PANEL SPLICES, Ibd SINKER SILL NAILS ® 4Y2" O.G. 5/8" GDX PLYHD. OR O55 Q w/ 6d'S ® 211,121, O.G. w/ 4x STUDS ® ADJ. PANEL SPLICES, Ibd SINKER SILL NAILS ® 2Yy O.G. I. NAILS SHALL BE COMMON NAILS (2Y2"x.131"), TYP., U.O.N. 2. ALL PLYWOOD PANELS SHALL HAVE ALL EDGES BLOCKED. ir 111 ITO. GOVERNING CODES: 2013 GBG, 2013 CRC, 2013 GEC, 2013 GPO, 2013 CMG, 2013 CFC, 2013 CALIF. HEALTH $ SAFETY CODE AMENIDMENTS 2013 CALIF. ENERGY CODE EFFICIENCY STANDARDS, ZONE II 2013 CALIF. AGGE5515IL17Y REQUIREMENTS AMERIGAN5 w/ DISABILITIES ACT, 2012 EDITION NFPA 101, 2013 GGBSC OCCUPANCY GROUP: OROUP: R3 / U ALLOWABLE HEIGHT AND BUILDING AREAS (TABLE 503) ALLOHABLE AREA: UNL I M I TED ACTUAL FLOOR AREA: 247cl S.F. ALLOWABLE 5TORY/HEIOHT: (3) STORIES / 40'-0" ACTUAL STORY/HEIGHT: (1) STORY / 21'-0" CONSTRUCTION TYPE: TYPE VB AUTOMATIC SPRINKLER: NOT REQUIRED HILDLAND URBAN FIRE INTERFACE: NOT APPLICABLE MINIMUM TITLE 24 REOU I REMENTS 1. ALL NEW WINDOWS AND DOORS WITH GLAZING SHALL HAVE A MAX. SHOO OF 0.25 AND A MAX. U -VALUE OF 0.32. 2. NO MORE THAN 40' OF NEW DUCTS SHALL BE INSTALLED. NEW DUCTS TO BE MIN. R-6. 3. RADIANT BARRIER ROOF SHEATHING REQUIRED OVER ADDITION AREA ONLY. O ENERAL NOTES G-1 MISCELLANEOUS I. PROVIDE 4" HIGH x I" WIDE STREET ADDRESS NUMBERS OF CONTRA5TING COLOR, VISIBLE FROM STREETS. CONCRETE I. CONCRETE TO BE 5 SACK MIX, 2500 PSI ® 28 DAYS 2. RE I NFORG I NG STEEL TO BE I NTERMED I ATE ORADE DEFORMED BARS -TYPE N OR 40. ROUGH CARPENTRY 1. INSTALL BLOCKING AS REQUIRED TO SUPPORT FINISH HARDWARE AND FIRE STOPPING TO OUT OFF CONGEALED DRAFT OPENINGS AS REQUIRED BY CODES. 2. STRUCTURAL FRAMING SHALL BE DOUGLAS FIR TO THE GRADES INDICATED OR BETTER (MPA GRADING RULES) UNLESS NOTED OTHERWISE. CONGEALED BEAMS AND POSTS ......................... NO. 2 EXPOSED BEAMS AND POSTS...............................NO. I 2x JOISTS AND RAFTERS........................................NO. 2 STUD, 51 LLS, PLATES...................................................NO. 2 SILLS ON CONCRETE....................................................PTHF M15C. FRAMING NOT NOTED....................................NO. 2 3. PLYWOOD SHALL BE OF THE DE51ONATED GRADE AND SHALL MEET THE REOUIREMENTS OF THE U.S. PRODUCT STANDARDS P5 4. NAILS AT PLYWOOD PANELS SHALL HAVE 5/8" EDGE DISTANCE AND SHALL NOT PENETRATE FAGS -PLY. 5. NO PIECE OF PLYWOOD ROOF, FLOOR OR WALL SHEATHING SHALL BE LESS THAN 12" IN LEAST DIRECTION. 6. FRAMING HARDWARE SHALL BE SIMPSON STRONG -TIE OR APPROVED EQUAL, WITH CONNECTORS AS SPECIFIED 7. PROVIDE 50LID BEARING CONTINUOUS FROM ALL BEAMS TO FOUNDATION. 8. PROVIDE FIRE BLOCKING IN CONGEALED SPACES VERTICALLY AND HORIZONTALLY IN ACCORDANCE w/ 2013 G.R.G. SECTION 8302.11. Q. FASTENERS FOR PRESERVATIVE TREATED AND FIRE TREATED WOOD SHALL BE OF HOT DIPPED ZING COATED GALVANIZED STEEL, SILICON BRONZE OR COPPER. THE COATING WEIGHTS FOR ZING COATED FASTENERS SHALL BE IN ACCORDANCE w/ ASTMA 153. 2013 G.R.G. SECTION R317.3. 10. BEARING WALL HDR5. SHALL BE 4x10 #2 OR 6x8 D.F. #1 MIN., TYP., U.O.N. PLUMBING I. THE AGGREGATE AREA OF PLUMBING VENTS SHALL BE 12.57 502. INCHES, MIN. 2. OAS FIRED WATER HEATER TANKS SHALL BE FASTENED TO THE ADJACENT FRAMING w/ 16 OAUOE METAL STRAP (0516 OR EG) w/ MIN. 2" LONG #12 WOOD 50REH5 ® 4" ABOVE CONTROLS AND WITHIN 12" OF THE TOP OF THE TANK. 3. ALL NON-COMPLIANT PLUMBING FIXTURES SHALL BE REPLACED w/ HATER CONVERSING PLUMBING FIXTURES. NON-COMPLIANT PLUMBING FIXTURES AS FOLLOWS: A. ANY TOILET MANUFACTURED TO USE MORE THAN 1.28 GAL. OF WATER PER FLUSH. B. ANY SHOWER HEAD MANUFACTURED TO HAVE A FLOW CAPACITY OF MORE THAN 2.0 GAL. OF HATER PER MIN. G. ANY KITCHEN FAUCET THAT EMITS MORE THAN 1.8 GAL. OF WATER PER MIN. D. ANY LAVATORY FAUCET THAT EMITS MORE THAN 1.5 GAL. OF HATER PER MIN. 4. SHOWER AND TU5-5HOHER COMBINATIONS SHALL BE PROVIDED w/ INDIVIDUAL CONTROL VALVES OF THE PRE55URE BALANCE OR THE THERMOSTATIC MIXING VALVE TYPE. 5. INSTALL A 4" DRAIN FOR BUILDINGS PROVIDING MORE THAN (3) HATER CLOSETS. 6. HORIZONTAL DRAINAGE PIPING SHALL BE 2% MIN.5 0 MECHANICAL I. DRYER DUCT TO BE MIN. 4" (P TO THE OUTSIDE, EQUIPPED WITH A BACK -DRAFT DAMPER. 4" 4) DUCT LENGTH 15 LIMITED TO 14' WITH 2 ELBOHS. OTHER LENGTHS OR SIZES A5 PERMITTED OR REQUIRED BY THE MANUFACTURE'S INSTALLATION INSTRUCTIONS MUST BE APPROVED BY BUILDING OFFICIAL. (SUBMIT REQUEST FOR MODIFICATION5) 2. 51NOLE-WALL METAL PIPE SHALL NOT BE USED AS A VENT IN DWELLINGS AND RESIDENTIAL OCCUPANCIES. 3. ALL ENVIRONMENTAL AIR DUCTS SHALL BE A MIN. OF 3' AWAY FROM ANY OPENINGS INTO THE BUILDING. 4. ALL BATH BATH FANS SHALL HAVE A BACKDRAFT DAMPER. BUTTE COUNTY IJUL 21 2016 DEVELOPMENT SERVICES re5T� NORTH PERMIT # BUTTE COUNTY DEVELOPMENT SERVICES REVIEWED FOR CODE COMPLIANCE DATE L BY Revision: Date: By: N 00 • C*A .Q " rn � 1� U UU� bA a Wo a M h o0 W Q W W�Z� �0C) di z H c H 4.j LO AR cAZ * No. 212 RE 7/ GA�- popf=001< ADDITION PHASE 2 Date APRIL 2016 Scale Dom' 05TR0\/5K I Y Job 12-1605 Sheet Of FIVE Sheets i' 1 L>= Lc3 r t 2 a rn IRTti Ln ri co 0 N 0 N N (`i) I bd GOMMON5, (7) I bd COMMONS, CINCHED ® EACH CINCHED ® EACH G.J. SPLICE G.J. SPLICE (N) COMP. SHINGLES o/ 15# Ixb TIES FELT o/Y2" GDX OR OSB. 4'-0" O.G. (N) COMP. SHINGLES o/ 15# 460 I O.C. FELT o/ Y2" GDX OR OSB. W/ 8d'5 ®6 ", 12" O.G. ---SEE ROOF O.G. ---SEE ROOF SEE ROOF PLAN (N) SEE ROOF PLAN SEE ROOF N) SEE ROOF PLAN (N) 14"x24" G.E. VENT, TYP. PLAN FfIRAMING PLAN FRAMING PLAN 2x10 TIE ®�7 MATCH ADJOINING �" 6YP. BD. ®GLC. 4'-O" O.G. (N) R-55 IN5UL. ROOF. 5/B" GYP. BD. � GLC. _ (N) 2x4 STUDS ®I6" O.G. 4)_ �� 2x10 TIE (N) 2x6 5TUD5 ® 16 O.G. 4'-0" O.G. o C ARRC:1 -d�' (N) Y2" GYP. BD. ® WALLS - (N) Y2" 6YP. BD. ® WALLS TOP OF (N) R-19 INSUL. STEMWALL (N) SEE FDN. PLAN SEE FDN. PLAN U 7 L u u j =1 I H I I I H I H I I-1 I I-1 I i= I I-1 11=1 I i -1I H I I-1 I I—i I I—I 11=1 11=1 11=1 11=t 11=i I i-1 I I-1=_- 111=1 I 11=1 11=1 11=1 11=1 I I I I� I i I; I I 1-1 11-1 11=1 I I-1 i I=I i 1=ITi=III=1 I-1 1-1 I I; J I ,ll� II I t=l =1=111=1 _=1 I I; �' =1 I I I I I I i -1 1=1 I I-1 I I I -1 I I- I=- _ _—___ -III I I_I 11-1 I I—III III_ I I I I I I I 1 I I I_I I I—I 11-1 I I_i I I—I I—III—III—III—III—I I I l - _ — — =III„ _ I I I� I I I� III I I 1-III-III-ITI-111_1 i l— — _I I I_I I-(IHIHII— —_-111 EXISTING ADDITION (E) SECTION 5-2 1/4" = I' -O" SECTION A-2 1/4" = 1'-0" LEFT r -L i / TION 1/4" = 1'-011 COMP. SHINGLES, MATCH (E) — 6" FA5GIA ix4 TRIM CORNERS, DRS, WDW5, MATCH (E) GEMENT BOARD LAP 51DINO o/ 516" GDX PLY. OR OSB w/ 8d'5 ® (011,12" O.G., TYP., U.O.N. ADDITION EXISTING FRONT ELE1/ATION 1/4" = 1'-0.. PERMIT # BUTTE COUNTY DEVELOPMENT SERVICES REVIEWED FOR CODE POMPLIANCE DATER'. I EXISTING ADDITION REAR t=Lrz\/ATION 1/4" = I' -o" Revision: Date: By: a r �n W00 I�1 L) in `� W C • W I N .Q � H U w � 1 � U � O `/ wo cl v° W W o a I M WI Q �I �I WI��o O O w H O O H � H CC) O H LO � ^H H S�0 ARcy J��ppRY A. \C * No. C NJ RE . 7/1 F L /V 00PPOGK ADDITION PHASE 2 Date APRIL 2016 Scale Drawn 05TR0\/5K 1 Y Job 12-1605 Sheet ON Of FIVE Sheets P.T. SILL H/ Y2 " DIA. x 12" A.B. ® V O.G. AND 12" MAX. FROM ENDS H/ 3 "x3 "x.229" PLATE WASHERS, TYP. z GONG. 5LAB, SEE y- FOUNDATION PLAN FINISH GRADE II ........................... it -11 _I I III-III=1 I i=i P z NAT. GRADE - III—I I —Iii—III—I i' � I-111=1II III-III—II'- � #4 TOP 4 III=III II1=1I1= BOTTOM —I I I—I' 'I .,III„ _z00 12" m OARAC E FOOT I NC 1=-18 I" = LINE OF STEMHALL BEYOND FELT TYPICAL STRIP EASED EDGE DRI VEHAY GONG. SLAB, SEE 5L AB ml�r FOUNDATION PLAN Y' ° ° _ _ .... a z N CONT. #4 TOP BOTTOM �MM.IN.4z m /e-216ARA5E DOOR OFEN I NC F-141 1" = I'—O" P.T. SILL W/ Y2 " DIA. x 12" A.B. ® 6' O.G. AND 12" MAX. FROM ENDS W/ �J IL -11- . ---ll -1 A -r ..1 A -. I--- — I - STORY FOOT I NC I F -I 1" = 1'-0 6" x 6" MIN. PLYHD. GUSSETS EA. 51 DE H/ (3) Sd'5 EA. TO POST SEE FOUNDATION PLAN l$ GIRDER— VFOR FRAMING SIZES NAT. GRADE v 4x4 POST z z PRECAST GONG. PIER 2" EMBEDMENT z_ II-III LII � — ° 1=III=III-1 -III= z -II .=. d III—III—III -11 — 1=III—II i - IS" SQ. F I ER FOOT I N5 >2 I " — 1'—O" A35 ® 4'-0" O.G., TYP., ROOF PLY. U.O.N. SOLID BLOCKINO--.- .,f I" MIN. AIR SPACE TO INSULATION VENTS SHEARPLY, - SEE PLAN EAVE DETA I L R -I I" = 1'-0" SHINGLE MOLD FA501 A, SEE ELEVATION ROOF PLY Ll I.F E.N. E.N. 2x4 OUTLOOKER 2x STUDS 16" o. IC. SHEARPLY, Ibd ®16" O.G. SEE FLOOR PLAN CEILING LINE E.N. E.N. RH C ABILE END R-13 1" = I' -O ROOF NOTES: I. ROOF FRAMING SHALL BE: PRE -MFR TRUSSES ® 24" O.G. TYP. U.O.N. 2. ROOF PITCH SHALL BE: VARIES, SEE PLAN 3. ROOF O.H. SHALL BE: 1'-0" ® ALL G.E. I'-6" ® 5:12 PITCH 1'-6" ® 5:12 PITCH 4. ROOF COVERING SHALL BE: COMP. SHINGLES o/ 15# FELT o/'Y2" GDX OR OSB. H/ 5d'S ® 6", 12" O.G. 5. REQUIRED ATTIC VENTILATION: 800 / 300 = 2.61 50. FT. OF NIST FREE AREA VENTILATION REQUIRED. • LOW VENTING: PROVIDE MIN.. (4) 3�"x225" EAVE VENTS ® .33 50. FT. EACH. TOTAL LOW VENTING R'ROVIDED: 1.52 SQ. FT. OF NET FREE AREA • HIGH VENTING: PROVIDE 34' CONT. RIDGE VENT ® 0.12550. FT. PER FT. TOTAL HIGH VENTING PROVIDED: 4.25 50. FT. OF NET FREE AREA. FOUNDATION NOTES: 1. PROVIDE 15"x24" MIN., SCREENED U.F. ACCESS 2. UNDER FLOOR VENTING: 387 / 150 = 2.58 S.F. OF NET FREE AREA. PROVIDE (1) 18"x24" CRAWL HOLE ® 1.6 50. FT. PROVIDE (4) 5Y2"x14Y2" UNDER FLOOR VENTS ® 0.5 50. FT. EACH. TOTAL UNDER FLOOR VENTING PROVIDED: 2.8 50. FT. PROVIDE A VENT 3' FROM EACH CORNER. 3. GROUND IMMEDIATELY ADJACENT TO THE FOUNDATION SHALL BE 5LOPED AWAY FROM THE BUILDING AT A SLOPE OF NOT LESS THAN 6" WITHIN THE FIRST 10 FT. (5% SLOPE). PER 2013 ORO SECTION R401.3; ROOF FRANC I NC PLAN 1/4" = 1'-o" 36'-9y2" 19'-O" N r 1 I I r 3 I 3 in�IL I t Z(N) 4 GONG. SLAB H/ #3 BAR ® 2'-0" O.G. BOTH WAY5 o/ 2" SAND o/ 6 MIL. VB (H/JOINTS I in LAPPED 6" MIN.) o/ 4" BASE I 4 l ssTBI6 I I 3 r N 3'x3' MIN. GONG. LANDING, 73/4" MAX. I L t ( THRESHOLD, TYP. ® ALL EXTERIOR IN --SWI GING I DOORS I (N) 3/4" T$G PLYWD. GLUED I r SSB/AND NAILED H/ IOd RING. t 6 I SHANK NAILS ® 6", 12" O.G. -� o/ 2x6 F.J.'5 ® I6" O.G. N in j �R.O. FOR 2r 51-01, DR. R.O. FOR I6GAR. DR. 3 ( = r II ZN L gni nn i In tft- I —4x6 p GIRDER, - I TYR I I I 9'-2Y2" .n FOUNDATION PLAN 1/4" =1'-0" 12" #4 PINS TOP 6 BOT. ® ALL (N) TO (E) FOOTING LOCATIONS ERMIT # — 0.— BUTTE COUNTY DEVELOPMENT SERVICES REVIEWED FOR CODE COMPLIANCE DATE RY Revision: Date: By: N v� o� W U o O1 a rn Msl V w° `.) � c b C W o M w Q n OF� W LO LOQ �j ARcA��� * No. 283 RE 7/17 A�- GOPPOGK ADDITION PHA5E 2 Date APRIL 2016 Scale Drawn 05TROV5K I Y Job 12-1605 Sheet Of FIVE Sheets 4 VENTILATION REQUIREMENTS WHOLE - SUILDIN5 VENTILATION: NOT REQUIRED FOR ADDITIONS LESS THAN 1,000 50. FT. WP/ � CFI \ 4 VENT r-LEGTRI CAL PLAN 1/4a = 11-011 Revision: Date: By: ✓c -j' �, PERMIT # COUNTY OEVELOPMENT SERvIOES N I3UTfE REVIEWED FOR 4 W E-� CODE CO P� NCS W 1 • rn Mei DATE ELECTRICAL NOTE5: 'r aJ a ELECTRICAL 5YM 3OL5 U"� I. PROVIDE AN ADDITIONAL 20 AMP BRANCH CIRCUIT FOR EACH BATHROOM AND LAUNDRY. THESE CIRCUITS SHALL SINGLE POLE SWITCH GLC. MTD. FIXT. CEILING FAN w/ LIGHT SERVE NO OTHER OUTLETS. $3 THREE WAY SWITCH FLUORESCENT o 2. ALL 15 4 20 AMP BRANCH CIRCUITS SUPPLYING OUTLETS GLC. MTD. FIXT. a INSTALLED IN BEDROOMS, FAMILY ROOMS, DININGDIMME>'R c� SWITCH LED GLC. MTD. FIXT. CEILING FAN NO LIGHT ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, ip SUNROOM5, RECREATION ROOMS, HALLWAYS, CLOSETS OR SIMILAR ROOMS, SHALL BE INSTALLED WITH A D3 DIMMER/5-WAY SWITCH -0 RECESSED CLO. FIXT. UNDER CABINET COMBINATION ARG -FAULT CIRCUITS INTERRUPTERS. I—I O FLUORESCENT LIGHTING W�z� T TIMER SWITCH ELEG. BALLAST, 5. PROVIDE (2) OR MORE 20 -AMP SMALL APPLIANCE V 1 H AIR -TIGHT, IG RATED r :S I FLUORESCENT FIXTURE BRANCH CIRCUITS EVENLY PROPORTIONED IN THE DUPLEX REGEPT. FLUORESCENT � KITCHEN, PANTRY, BREAKFAST ROOM, DINING ROOM, OR O RECESSED GLC. FIXT. Q SIGNAL PUSH BUTTON .. SIMILAR AREA TO SERVE ALL WALL AND FLOOR OUTLETS. SUCH CIRCUITS SHALL HAVE NO 6 220 VIOLT OUTLET 0 E-4 OTHER F ---I ICJ LED OUTLETS. RECESSED GLC. FIXT. 0 PUCK LIGHT ($ DUPLEX SPLIT WIRED * No. C21 3 7k N� 4. ALL 125 VOLT, SINGLE PHASE, 15 AND 20 AMP 1/cOFFOOK PANEL BOARD RECEPTACLES SHALL BE LISTED TAMPER RESISTANT + QUAD. REGEPT. Scale MINI RECESSED GLC. FIXT. Drawni 05TROV5IG I Y Job 12-1605 RECEPTACLES. Sheet AR Of FIVE Sheets -}- WALL MTD. FIXTURE DJ ELEC. DISCONNECT 5. FIXTURES, LAMP HOLDERS AND RECEPTACLES OUTLETS FLOOR: OUTLET SHALL BE SECURELY SUPPORTED. A FIXTURE THAT FLUORESCENT ® 110 V. SMOKE DETECTOR 1^EI6145 MORE THAN bibs OR EXCEEDS I&In. IN ANY a TV OUTLET WALL MTD. FIXTURE DIMENSION SHALL NOT BE SUPPORTED BY THE SCREW SHELL OF A LAMP HOLDER PER 2015 GEC SECTION -�- TRACK FIXTURE EXHAUST FAN 410.15. (0). OUTLET BOXES SHALL NOT BE USED AS THE PHONE OUTLET SOLE SUPPORT FOR CEILING FANS PER 2015 SECTION PENDANT LIGHT � WHOLE HOUSE VACUUM CONNECTION 514.21 (0 4 d). e TV/PH0NE OUTLET 6. ALL HARDWIRED DETECTORS SHALL BE SCONCE FIXTURE Gm IIOv CARBON MONOXIDE INTERCONNECTED. VP SUITABLE FOR DAMP ALARM w/ BATTERY LOCATION BACKUP MINI SCONCE FIXTURE "1. ALL GARAGE, LAUNDRY ROOM, AND UTILITY ROOM -{— FUEL GAS OUTLET L15HTIN5 SHALL BE HIGH -EFFICACY AND CONTROLLED MOTION -ACTIVATED_- AUTOMATIC GARAGE BY A MANUAL -ON OCCUPANCY SENSOR. SECURITY LIGHT — r § 1 DOOR OPENER LISTED IN — ACCORDANCE w/ UL 525 **ALL LIGHTING FIXTURES SHALL BE ASSUMED INCANDESCENT U.O.N. AS LED OR FLUORESCENT. Revision: Date: By: N 4 W E-� W � o • rn Mei U 'r aJ a U"� O W o a M Wq I—I O W�z� V V 1 H (D � � O O .. H 0 E-4 c F ---I ICJ p E-4 ° ARcA��F * No. C21 3 7k N� REN. /1 1/cOFFOOK ADDITION PHA5E 2 Date APRIL 2016 Scale Drawni 05TROV5IG I Y Job 12-1605 Sheet AR Of FIVE Sheets A. TITLE 24 MANDATORY MEA5URF-5 6-7 BU I LD I N5 ENVELOPE MEASURES MANUFACTURED TO LIMIT AIR EAKA6E. 1. DOORS AND WINDOWS BETWEEN CONDITIONED AND UNCONDITIONED SPACES SHALL BE L 2. FENESTRATION PRODUCTS (EXCEPT FIELD -FABRICATED WINDOWS) SHALL HAVE A LABEL LISTING THE CERTIFIED U -FACTOR, CERTIFIED SOLAR HEAT GAIN COEFFICIENT (SHOO), AND INFILTRATION THAT MEETS THE REQUIREMENT5 OF §10-111(0). 3. EXTERIOR DOORS AND WINDOWS SHALL BE WEATHER-5TRIPPED; ALL JOINTS AND PENETRATIONS CAULKED AND SEALED. 4. INSULATION SPECIFIED OR INSTALLED SHALL MEET STANDARDS FOR INSULATING MATERIAL. INDICATE TYPE AND INCLUDE ON GF -(OR FORM. 5. THE THERMAL EMITTANCE AND SOLAR REFLECTANCE VALUES OF THE COOL ROOFING MATERIAL MEETS THE REQUIREMENTS OF §110.8() WHEN THE INSTALLATION OF A COOL ROOF 15 SPECIFIED ON THE GF -IR FORM 6. A RADIANT BARRIER SHALL HAVE AN EMITTANGE OF 0.05 OR LE55 WHEN THE INSTALLATION OF A RADIANT BARRIER 15 SPECIFIED ON THE CFIR. 7. L005E FILL INSULATION SHALL CONFORM WITH MANUFACTURER'S INSTALLED DESIGN LABELED R -VALUE FIREPLACES DECORATIVE GA5 APPLIANCES AND GAS LOG MEASURES: I. MASONRY OR FACTORY -BUILT FIREPLACES SHALL HAVE A OL05ABLE METAL OR GLASS DOOR COVERING THE ENTIRE OPENING OF THE FIREBOX. 2. MASONRY OR FACTORY -BUILT FIREPLACES SHALL HAVE A COMBUSTION OUTSIDE AIR INTAKE, WHICH 15 AT LEAST SIX SQUARE INCHES IN AREA AND 15 EQUIPPED w/ A READILY ACCE551BLE, OPERABLE, AND TIGHT -FITTING DAMPER AND OR A COMBUSTION -AIR CONTROL DEVICE. 3. MASONRY OR FACTORY -BUILT FIREPLACES HAVE A FLUE DAMPER WITH A READILY ACCESSIBLE CONTROL. 4. CONTINUOUS BURNING PILOT LIGH;j~S ANIP THE USE OF INDOOR AIR FOR GOOLIN6 A FIREBOX JACKET, WHEN THAT INDOOR AIR )S VENTED TO THE OUTSIDE OF THE BUILDING, ARE PROHIBITED. T� APPLIANCES SHALL BE CERTIFIED BY THE ENERGY COMMISSION. I. HVAC EQUIPMENT, WATER HEATERS; SH WERHEADS, FAUCETS AND ALL OTHER REGULATED L UNITS MEET THE AIR RELEASE VALVE BACKFLOW PREVENTION PUMP ISOLATION VALVE AND RECIRCULATION LOOP CONNECTION 2. WATER HEATER RECIRCULATION L'OOt�SERYIN6 MULTIPLE, REQUIREMENTS. 5. CONTINUOUSLY BURNING PILOT LIGHTS ,¢ARE PROHIBITED FOR NATURAL GA5: FAN -TYPE CENTRAL FURNACES, HOUSEHOLD GOOKIN6 APPLIANCES (APPLIANCES w/OUT AN ELECTRICAL SUPPLY VOLTAGE CONNECTION w/ PILOT'"LIGHTS THAT CONSUME LE55 THAN 150 Btu/hr ARE EXEMPT), AND POOL AND 5PA HEATERS. 4. HEATING AND/OR COOLING LOADS SHALL BE CALCULATED IN ACCORDANCE w/ ASHRAE, SMAGNA OR ALGA. 5. INSTALLED AIR CONDITIONER AND HEAT' PUMP OUTDOOR CONDENSING UNITS SHALL HAVE A CLEARANCE OF AT LEAST V FROM THE OUTLET OF ANY DRYER VENT. 6. HEATING SYSTEMS SHALL, BE EQUI'PED w/ THERM05TAT5 THAT MEET THE SETBACK REQUIREMENTS OF SECTION 1102(C). 7. STORAGE GAS WATER`' HOATER5 RATED w/ AN ENERGY FACTOR NO GREATER THAN THE FEDERAL MINIMAL STANDARD SHALL BE EXTERNALLY WRAPPED W/ INSULATION HAVING AN INSTALLED THERMAWRE5I5TANCE OF R-12 OR GREATER. 6. UNFIRED HOT HATER TANKS, 5UC AS 5TQRA6E TANKS AND BACKUP STORAGE TANKS FOR SOLAR WATER -HEATING SYSTEMS, HAVE R-12 EXTERNAL INSULATION OR R-16 INTERNAL INSULATION R -VALUE 15 INDIGATEPt ON -THE EXTERIOR OF THE TANK. el. FIRST 5 FT. OF HOT AND COLD WATER PIPES CLOSEST TO WATER HEATER TANK, ALL PIPING WITH A NOMINAL DIAMETER OF J" OR LARGER, ALL PIPING ASSOCIATED w/ A DOMESTIC, HOT WATER RECIRCULATION SYSTEM RE6AI�ZDLESS OF THE PIPE DIAMETER, PIPING FROM THE HEATING SOURCE TO STORAGE TANKS, PIPING BURIED BELOW GRADE, AND ALL HOT WATER PIPES FROM, THE HEATING SOURCE TO KITCHEN FIXTURES MUST BE INSULATED AGGORDIN6 TO THE REQUIREMENTS TABLE 120.3-A. 10. ALL DOMESTIC WATER ATER PIPI'_`S THAT R T ARE BURIED BELOW GRADE MUST BE INSTALLED IN A WATER PROOF AND NON CRUSHABLE CASING OR SLEEVE THAT ALLONS FOR INSTALLATION, REMOVAL, AND REPLACEMENT OF Tf4E kNGLOSED PIPE AND INSULATION. 11. PIPE FOR COOLING SYSTEM LINt5 SHALUDE INSULATED AS SPECIFIED IN §150.0(j)2A. PIPING INSULATION FOR STEAM AND HYDRONIC HEATING SYSTEMS OR HOT WATER SYSTEMS WITH PRESSURE >15 psig SHALL MEET THE REQUIREMENTS IN TABLE 120.3-A. 12. INSULATION SHALL BE PROTECTED FROM DAMAGE, INCLUDING THAT DUE TO SUNLIGHT, MOISTURE, EQUIPMENT MAINTENANCE, AND WIND. 15. INSULATION EXPOSED TO WEATHER SHALL EITHER BE RATED FOR OUTDOOR USE OR INSTALLED WITH A COVER SUITABLE FOR OUTDOOR SERVICE. 14. INSULATION FOR CHILLED WATER PIPING AND REFRIGERANT SUCTION LINES SHALL INCLUDE A VAPOR RETARDANT OR BE ENCLOSED ENTIRELY IN CONDITIONED SPACE. E ICA RECEPTACLE WITH( 3 OF THE HATER HEATER• A 16 UNITS SHALL INCLUDE: A 120) EL GTR L L N 15. SYSTEMS USING GA5 OR PROPANE WATER HEATERS TO SERVE INDIVIDUAL DWELL N , CATEGORY III OR IV VENT, OR A TYPE B VENT WITH A STRAIGHT PIPE BETWEEN THE OUTSIDE TERMINATION AND THE SPACE WHERE THE WATER HEATER IS INSTALLED; A CONDENSATE DRAIN THAT IS NOT MORE THAT 2" HIGHER THAT THE BASE OF THE INSTALLED WATER HEATER, AND ALLOWS NATURAL DRAINING WITHOUT PUMP A5515TANCE; AND A OAS SUPPLY LINE WITH A CAPACITY OF AT LEAST 200,000 BTU/HR. 16. RECIRCULATING LOOPS SERVING MULTIPLE DWELLING UNITS SHALL MEET THE REQUIREMENTS OF §110.3(c)5 17. 50LAR WATER -HEATING 5Y5TEM5 AND COLLECTORS SHALL BE CERTIFIED AND RATED BY THE SOLAR RATIN65 AND CERTIFICATION CORPORATION OR BY A TE5TIN5 AGENCY APPROVED BY THE EXECUTIVE DIRECTOR. MOTS AND FAN MEASURES: I. ALL AIR -DISTRIBUTION SYSTEM DUCTS AND PLENUMS INSTALLED, ARE SEALED AND INSULATED TO MEET THE REQUIREMENTS OF GMC, SECTIONS 601, 602, 603, 604, 605 AND A ANSI/SMAGNA-006-2006 HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE 3rd ADDITION. SUPPLY -AIR AND RETURN AIR DUCTS AND PLENUMS ARE INSULATED TO A MINIMUM INSTALLED LEVEL OF R-6.0 OR ENCLOSED ENTIRELY IN CONDITIONED SPACE AS CONFIRMED THROUGH FIELD VERIFICATION AND DIAGN05TIC TE5TIN0. CONNECTIONS OF METALS DUCTS AND INNER GORE OF FLEXIBLE DUCTS ARE MECHANICALLY FASTENED. OPENINGS SHALL BE SEALED w/ MASTIC, TAPE OR OTHER DUCT -CLOSURE SYSTEM THAT MEETS THE APPLICABLE REQUIREMENTS OF UL -161, UL 151A, OR UL ►&IB OR AER050L SEALANT THAT MEETS THE REQUIREMENTS OF UL -125. IF MASTIC OR TAPE 15 USED TO SEAL OPENINGS GREATER THAN V4 INCH, THE COMBINATION OF MASTIC AND EITHER MESH OR TAPE SHALL BE USED. 2. BUILDING CAVITIES, SUPPORT PLATFORMS FOR AIR HANDLERS, AND PLENUMS DEFINED OR CONSTRUCTED w/ MATERIALS OTHER THAN SEALED SHEET METAL, DUCT BOARD OR FLEXIBLE DUCT SHALL NOT BE USED FOR CONVEYING CONDITIONED AIR. BUILDING CAVITIES AND SUPPORT PLATFORMS MAY CONTAIN DUCTS. DUCTS INSTALLED IN CAVITIES AND SUPPORT PLATFORMS SHALL NOT BE COMPRESSED TO CAUSE REDUCTIONS IN THE CRO55-5ECTIONAL AREA OF THE DUCTS. 3. FACTOR FABRICATED DUCT SYSTEMS SHALL COMPLY w/ SPECIFIED FOR DUCT CONSTRUCTION, AND CLOSURES; JOINTS AND SEAMS OF DUCT SYSTEMS AND THEIR COMPONENTS SHALL NOT BE SEALED w/ CLOTH BACK RUBBER ADHESIVE DUCT TAPES UNLESS SUCH TAPE 15 USED IN COMBINATION w/ MASTIC AND DRAW BONDS. 4. FIELD FABRICATED DUCT SYSTEMS SHALL COMPLY w/ REQUIREMENTS FOR DUCT CONSTRUCTION, CONNECTIONS, AND CLOSURES, AND OTHER REQUIREMENTS SPECIFIED FOR DUCT CONSTRUCTION DUCT INSULATION R -VALUE RATING; DUCT INSULATION THICKNESS; AND DUCT !LABELING. 5. ALL FAN 5Y5TEM5 THAT EXCHANGE AIR BETWEEN ORIGINAL CONDITIONED SPACE AND THE OUTSIDE SHALL HAVE BACK DRAFT OR AUTOMATIC, DAMPERS. 6. GRAVITY VENTILATING SYSTEMS SERVING CONDITIONED SPACE SHALL HAVE EITHER AUTOMATIC OR READILY ACCESSIBLE, MANUALLY OPERATED DAMPERS EXCEPT COMBUSTION INLET AND OUTLET AIR OPENINGS AND ELEVATOR SHAFT VENT5. 7. INSULATION SHALL BE PROTECTED FROM DAMAGE, INGLUDIN6 THAT DUE TO SUNLIGHT, M015TtURE, EQUIPMENT MAINTENANCE, AND WIND, BUT NOT LIMITED TO THE FOLLOWING; INSULATION EXPOSED TO WEATHER SHALL BE SUITABLE FOR OUTDOOR SERVICE. CELLULAR FOAM INSUVLATION SHALL BE PROTECTED AS ABOVE OR PAINTED WITH A COATING THAT 15 WATER RETARDANT AND PROVIDES SHIELDING FROM 50LAR RADIATION THAT CAN CAUSE DEGRAflATION OF THE MATERIAL. 5. FLEXIBLE DUCTS CANNOT HAVE POROUS INNER GORES. cl. WHEN SPACE CONDITIONING SYSTEMS USE FORGED AIR SYSTEMS TO SUPPLY CONDITIONED AIR TO AN OCCUPIABLE SPACE, THE DUCTS SHALL BE SEALED AND DUCT LEAKAGE TESTED, AS CONFIRMED THROUGH FIELD VERIFICATION AND DIA6N05TIG TESTING, IN ACCORDANCE WITH REFERENCE RESIDENTIAL APPENDIX RA5. 10. MECHANICAL SYSTEMS THAT SUPPLY AIR TO AN OCCUPIABLE SPACE THROUGH DUCTWORK EXGEEDIN6 10' IN LENGTH AND THROUGH A THERMAL GONDITIONIN6 COMPONENT, EXCEPT EVAPORATIVE COOLERS, SHALL BE PROVIDED w/ AIR FILTERS DEVICES THAT MEET THE REQUIREMENTS OF §150.0(m)12. 11. SPACE CONDITIONING 5Y5TEM5 THAT UTILIZE FORGED AIR DUCTS TO SUPPLY COOLING TO AN OCCUPIABLE SPACE SHALL HAVE A HOLE FOR THE PLACEMENT OF A STATIC, PRESSURE PROBE (HSPP), OR A PERMANENTLY INSTALLED STATIC PRESSURE PROBE (PRPP) IN THE SUPPLY PLENUM. THE SPACE GONDITIONIN6 SYSTEM MUST ALSO DEMONSTRATE AIRFLOW :5 0.55 W/CFM AS CONFIRMED BY FIELD VERIFICATION AND DIAGNOSTIC, TESTING, IN ACCORDANCE w/ REFERENCE RESIDENTIAL APPENDIX RA5. 12. ZONALLY CONTROLLED CENTRAL FORGED AIR COOLING SYSTEMS SHALL BE CAPABLE OF SIMULTANEOUSLY DELIVERING, IN EVERY ZONAL CONTROL MODE, AND AIRFLOW FROM THE DWELLING, THROUGH AIR HANDLER FAN AND DELIVERED TO THE DWELLING, OF 5 350 GFM PER TON OF NOMINAL COOLING CAPACITY, AND OPERATING AT AN AIR -HANDLING UNIT FAN EFFICACY OF SOS& W/GFM AS CONFIRMED BY FIELD VERIFICATION AND DIAONOSTIG TE5TIN5, IN ACCORDANCE WITH REFERENCE APPENDIX RA3. 15. ALL DWELLING UNITS SHALL MEET THE REQUIREMENTS OF ASHRAE STANDARD 622. NEITHER WINDOW OPERATION NOR CONTINUOUS OPERATION OF CENTRAL FORGED AIR SYSTEM AIR HANDLERS USED IN CENTRAL FAN INTEGRATED VENTILATION SYSTEMS ARE PERMISSIBLE METHOD OF PROVIDING THE WHOLE BUILDING VENTILATION. 14. WHOLE BUILDING VENTILATION AIRFLOW SHALL BE CONFIRMED THROUGH FIELD VERIFICATION AND DIAGN05TIC TESTING, IN ACCORDANCE w/ REFERENCE RESIDENTIAL APPENDIX RA5.YAH izE51DENTIAL LICHTINC MEASURES: I. INSTALLED LUMINARIES SHALL BE CLASSIFIED AS HIGH -EFFICACY OR LOW -EFFICACY FOR COMPLIANCE WITH §I50.0(k) IN ACCORDANCE WITH TABLE 150.0-A OR TABLE 150.05, AS APPLICABLE. 2. WHEN A HIGH EFFICACY AND LOW EFFICACY LIGHTING SYSTEM ARE COMBINED IN A SINGLE LUMINAIRE, EACH SYSTEM SHALL SEPARATELY COMPLY WITH THE APPLICABLE PROVISIONS OF §150.0(k). 3. THE WATTAGE AND CLASSIFICATION OF PERMANENTLY INSTALLED LUMINARIES IN RESIDENTIAL KITCHENS SHALL BE DETERMINED IN ACCORDANCE w/ §130.0(c). IN RESIDENTIAL KITCHENS, THE WATTAGE OF ELECTRICAL BOXES FINISHED w/ A BLANK COVER OR WHERE NO ELECTRICAL EQUIPMENT HAS BEEN INSTALLED, AND WHERE THE ELECTRICAL BOX CAN BE USED FOR A LUMINAIRE OR A SURFACE MOUNTED CEILING FAN, SHALL BE CALCULATED AS 160 WATT5 OR LOW EFFICACY LIGHTING PER ELECTRICAL BOX. 4. BALLASTS FOR FLUORESCENT LAMPS RATED 15 WATTS OR GREATER SHALL BE ELECTRONIC AND SHALL HAVE AN OUTPUT FREQUENCY NO LESS THAN 20 kHz. 5. PERMANENTLY INSTALLED NIGHT LIGHTS AND NIGHT INTEGRAL TO INSTALLED LUMINAIRE OR EXHAUST FAN SHALL BE RATED TO CONSUME NO MORE THAN FIVE WATTS OF POWER PER LUMINAIRE OR EXHAUST FAN AS DETERMINED IN ACCORDANCE w/ §150.0(c). NIGHT LI5HT5 DO NOT NEED TO BE CONTROLLED BY VACANCY SENSORS. 6. LIGHTING INTEGRAL TO EXHAUST FANS, IN ROOMS OTHER THAN KITCHENS, SHALL MEET THE APPLICABLE REQUIREMENTS OF §150.0(k) 7. H16H EFFICACY LUMINIAIRE5 MUST BE 5WITGHED SEPARATELY FROM LOW EFFICACY LUMINAIRES. 6. EXHAUST FANS SHALL BE 5WITGHED SEPARATELY FROM LIGHTING SYSTEMS. a. LUMINAIRES SHALL BE 5WITGHED w/ READILY ACCESSIBLE CONTROLS THAT PERMIT THE LIMINAIRES TO BE MANUALLY SWITCHED ON AND OFF. 10. NO CONTROL SHALL BYPASS A DIMMER OR VACANCY SENSOR FUNCTION IF THE CONTROL IN INSTALLED TO COMPLY w/ §150.0(k). 11. LIGHTING CONTROLS COMPLY w/ APPLICABLE REQUIREMENTS OF §110A. 12. AN ENERGY MANAGEMENT CONTROL SYSTEM (EMGS) MAY BE USED TO COMPLY w/ DIMMER REQUIREMENT5 IF; IT FUNCTIONS AS A VACANCY SENSOR. 13. A MULTISCENE PR06RAMMABLE CONTROLLER MAY BE USED w/ DIMMER REQUIREMENTS IF IT PROVIDES THE FUNCTIONALITY OF A DIMMER. 14. A MINIMUM OF 50 PERCENT OF THE TOTAL RATED WATTAGE OF PERMANENTLY INSTALLED LIGHTING IN KITCHENS SHALL BE HIGH EFFICACY. 15. KITCHEN LIGHTING INCLUDES ALL PERMANENTLY INSTALLED LIGHTING IN THE KITCHEN EXCEPT INTERNAL LIGHTING IN CABINETS THAT ILLUMINATE ONLY THE INSIDE OF CABINETS. L16HTIN5 IN AREAS ADJACENT TO THE KITCHEN, INCLUDING BUT NOT LIMITED TO DINING AND NOOK AREAS, ARE CONSIDERED KITCHEN LIGHTING IF THEY ARE NOT SEPARATELY 5WITGHED FROM THE KITCHEN LIGHTING. 16. PERMANENTLY INSTALLED LIGHTING THAT IS INTERNAL TO CABINETS SHALL USE NO MORE THAN 20 WATTS OF POWER PER LINEAR FOOT OF ILLUMINATED CABINET. 17. A MINIMUM OF ONE HIGH EFFICACY LUMINAIRE SHALL BE INSTALLED IN EACH BATHROOM; AND ALL OTHER LIGHTING INSTALLED IN EACH BATHROOM SHALL BE HIGH EFFICACY OR CONTROLLED BY VACANCY SENSOR. 16. PERMANENTLY INSTALLED LUMINAIRES IN ATTACHED AND DETACHED GARAGES, LAUNDRY ROOMS, AND UTILITY ROOMS SHALL BE HIGH EFFICACY, AND CONTROLLED BY VACANCY SENSORS. let. PERMANENTLY INSTALLED LUMINAIRES LOCATED IN ROOMS OR AREAS OTHER THAN KITCHENS, BATHROOMS, GARAGES, LAUNDRY ROOMS, AND UTILITY ROOMS SHALL BE HIGH EFFICACY LUMINAIRES, OR CONTROLLED BY EITHER DIMMER5 OR VACANCY SENSORS. 20. LUMINAIRES RECESSED INTO INSULATED CEILINGS SHALL BE LISTED FOR ZERO CLEARANCE INSULATION CONTACT (IC) BY UNDERWRITTEN LABORATORIES OR OTHER NATIONALLY RECOGNIZED TE5TING/RATING LABORATORY; AND HAVE A LABEL THAT CERTIFIES THE LUMINAIRE 15 AIRTIGHT WIT AIR LEAKAGE LESS THEN 2.00FM AT 75 PASCALS WHEN TESTED IN ACCORDANCE WITH ASTM E255; AND BE SEALED WITH A GASKET OR CAULK BETWEEN THE LUMINAIRE HOUSING AND CEILING. FOR RECE55ED COMPACT FLUORE50ENT LUMINAIRES w/ 5ALLA5T5 TO QUALIFY AS HIGH EFFICACY. 21. LUMINAIRES PROVIDING OUTDOOR LIGHTING, INGLUDIN6 LICHTING FOR PRIVATE PATIOS IN LOW-RISE RESIDENTIAL BUILDINGS WITH FOUR OR MORE DWELLING UNITS, ENTRANCES, BALCONIES, AND PORCHES, WHICH ARE PERMANENTLY MOUNTED TO A RESIDENTIAL BUILDING OR TO OTHER BUILDIN65 ON THE SAME LOT SHALL BE HIGH EFFICACY. EXCEPTION h PERMANENTLY INSTALLED OUTDOOR LOW EFFICACY LUMINAIRES SHALL BE ALLOWED PROVIDED THAT THEY ARE CONTROLLED BY A MANUAL-ON/OFF 5WITGH, A MOTION SENSOR NOT HAVING AN OVERRIDE OR BYPASS 5WITGH THAT DISABLES THE MOTION SENSOR, AND ONE OF THE FOLLOWING CONTROLS: A PHOTOGONTROL NOT HAVING AN OVERRIDE OR BYPASS SNITCH THAT DISABLES THE PHOTOGONTROL; OR AN ASTRONOMICAL TIME CLOCK NOT HAVING AN OVERRIDE OR 5YPA55 SWITCH THAT DISABLES THE ASTRONOMICAL TIME CLOCK; OR AN ENERGY MANAGEMENT CONTROL SYSTEM (EMGS) NOT HAVING AN OVERRIDE OR BYPASS 5WITGH THAT ALLOWS THE LUMINAIRE TO BE ALWAYS ON. EXCEPTION 2: OUTDOOR LUMINAIRES USED TO COMPLY WITH EXCEPTIONAL MAY BE CONTROLLED BY A TEMPORARY OVERRIDE 5WITGH WHICH BYPASSES THE MOTION SENSING FUNCTION PROVIDED THAT THE MOTION 5EN50R 15 AUTOMATICALLY REACTIVATED WITHIN 51X HOURS. 22. INTERNALLY ILLUMINATED ADDRESS SIGN5 SHALL COMPLY WITH SECTION 140.6; OR SHALL CONSUME NO MORE THAN 5 WATTS OF POWER. 25. LIGHTING FOR PARKING LOTS AND CARPORTS WITH A TOTAL OF 8 OR MORE VEHICLES PER SITE SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS IN SECTIONS 130, 132, 134, AND 147. LIGHTING FOR PARKING GARAGES FOR 5 OR MORE VEHICLES SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF SECTIONS 150, 131, 134, AND 146. 24. PERMANENTLY INSTALLED LIGHTING IN THE ENCLOSED, NON DWELLING SPACES OF LOW-RISE RE51DENTIAL BUILDING WITH 4 OR MORE DWELLING UNITS SHALL BE HIGH EFFICACY LUMINAIRES. EXCEPTION: PERMANENTLY INSTALLED LOW EFFICACY LUMINAIRES SHALL BE ALLOWED PROVIDED THAT THEY ARE CONTROLLED BY AN OCCUPANT 5EN50R(5) CERTIFIED TO COMPLY WITH THE APPLICABLE REQUIREMENTS. SOLAR READY BU I LD I NGS: I. THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A MINIMUM BUSBAR RATING OF 200 AMPS. 2. THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR THE INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR A FUTURE SOLAR ELECTRIC INSTALLATION. THE RESERVED SPACE SHALL BE: POSITIONED AT THE OPPOSITE (LOAD) END FROM THE INPUT FEEDER LOCATION OR MAIN CIRCUIT LOCATION, PERMANENTLY MARKED AS "FOR FUTURE SOLAR ELECTRIC.". 2013 CALGreen Residential Mandatory Measures Planning amd Design 4.106.2 - Stiorm Water Drainage and Retention - Projects which disturb less than one acre of soil and are not part of a larger common plan of development shall manage storm water drainage during construction. 4.106.3 - Grading and Paving - Construction plans shall indicate how the site grading and drainage system will manage all surface water flows to keep water from entering building. Exception: Additions or alterations not altering the drainage path. 4.106.4.1- (Electric Vehicle (EV) charging - For new constructed dwelling units, install a listed raceway to accommodate a dedicated 208/240 -volt branch circuit. The raceway shall not be less than trade size 1(nominal 14nch inside diameter). The raceway shall originate at the main service or subpanel and shall terminate into a listed cabinet, box or other enclosure in close proximity to the proposed location of an EV charger. Raceways are required to be continuous at enclosed, inaccessible or concealed areas and spaces. The service panel and/or subpanel shall provide capacity to install a 40 -ampere minimum dedicated branch circuit ands ace(s) reseryed to permit t installation of a branch circuit overcurrent protective device. The service panel or subpanel circuit directory shall identify the overcurrent protective device spaces(s) reserved for future EV charging as "EV CAPABLE". The raceway terminaition location shall be permanently and visibly marked as "EV CAPABLE". Energy Efffeciency 4.201.1-5.2(01.1- Low-rise residential (Section 4.201.1) and high-rise residential/hotel/motel (Section 5.201.1) building shall mecet or exceed the minimum standards design required by the California Energy Standards. Standards for residenthal buildings do not require compliance with levels of minimum energy efficiency beyond those required by the 20131 California Energy Code. Water Efficiency and Conservation Indoor Use - 4.303.1- Wfater Conserving Plumbing Fixtures and Fittings. - Plumbing fixtures and fittings shalt comply with the followinEg: 4.303.1.1 - Water closets flush volume shall not exceed 1.28 gals per flush. 4.303.1.2 - Urinals flush volume shall not exceed 0.5 gals per flush. 4.303.1.3.1. - Single showerheads shall have a maximum flow rate of not more than 2.0 gpm. 4.303.1.32 - Multi le showerheads shall have a combined flow rate of all showerheads and/or shower outlets controlled by a single valve shall not exceed 2.0 gpm or only one shower outlet to be operation at a time. 4.303.1.4.1. - Residential lavatory faucets maximum flow rate shall not exceed 1.5 gpm. The minimum flow rate shall not be less than 0.8gp m. 4.303.1.4.2 - Lavatory faucets in common and public areas of residential buildings shall not exceed 0.5 gpm. 4.303.1.4.3 - Metering faucets shall not deliver more than 0.25 gals per cycle. 4.303.1.4.4 - Kitchen faucets maximum flow rate shall not exceed 1.8 gpm. Kitchen faucets may temporarily increase he flow above the maximum rate, b x t a but not to Geed 2.2 gpm. Note: When complying faucets are unavailable, aerators or other means may be used to achieve reduction. 4.303.2 - Plumbing fixtures and fittings shall be installed in accordance with the Plumbing Code. Outdoor Use - 4.304.1- Inrigation Controllers - Automatic irrigation system controllers for landscaping by the builder and installed at the time! of final inspection shall comply with the following: 1. Controllers shall be weather- or soil moisture -based controllers that automatically adjust irrigation in response to changes' in plant watering needs as weather or soil conditions change. 2. Weatherr-based controllers without integral rain sensors or communication systems that account for rainfall shall have a separate wired or wireless rain sensor which connects or communicates with the controller(s). Material Cionservation and Resource Efficiency 4.406.1- Rcodent Proofing - Annular spaces around pipes, electric cables, or other openings in sole/bottom plates at exterior iwalls shall be closed with cement mortar, concrete masonry or a similar method acceptable to the enforcing agency tto prevent passage of rodents. 4.408.1- Ceonstruction Waste Reduction of at least 50% - A minimum of 50•� of the construction waste generated at site is diwertedsa or o recycle I t y nage. 4.408.2 Cornstruction Waste Management Plan - Submit a construction waste management plan meeting items 1-5 in Section 44.408.2. Plans shall be undated as necessary and shall be available for examination during construction. 4.408.3 - Waste Management Company - Utilize a waste management con anY. approved by the enforcing agency, which can provide verifiable documentation that diverted construction and demolition waste materials meet the requirements in Section 4.4081. i I 4.408.4 - Waste Stream Reduction Alternative ernative - Generate e erste a total combined weight of construction and demolition waste dfisposed in landfills that is equal to or less than 4 lbs per sq. ft. of the building area. 4.408.4.1 - Waste Stream Reduction Alternative (High -Rise Residential) - Generate a total combined weight of construcction and demolition waste disposed in landfills that is equal to or less than 2 lbs per sq. ft. of the building area. 4.410.1- Opperation & Maintenance Manual - An operation and maintenance manual shall be provided to the building owner oar occupant. Environmental Quality 4.503.1 Getneral - Any installed gas fireplace shall be a direct -vent sealed -combustion type. Any installed woodstove or pellet stove shall comply with US EPA Phase II emission limits where applicable. Woodstoves, pellet stoves, and fireplaces shall also comply with applicable local ordinances. 4.504.1 Coverings of Duct Openings and Protection of Mechanical Equipment during Construction - Duct openings and other rellated air distribution component openings shall be covered during construction. 4.504.2.1- Adhesives, Sealants and Caulks - Shall be compliant with VOC and other toxic compounds limits. 4.504.2.2 •- Paints and Coatings - Shall be compliant with VOC limits. 4.504.2.3 - • Aerosol Paints and Coatings -Shall be compliant with product weighted MIR limits for ROC and other toxic compouinds. 4.504.3 - Carpet Systems - Shall be compliant with VOC limits. 4.504.4 - Rtesilient Flooring Systems - 80% of floor areas receiving resilient flooring shall comply with the VOC - emission limits defined in the Collaborative for High Performance Schools (CHPS) Low -emitting Materials List or to be certiffied under the Resilient Floor Covering Institute (RFCI) FloorScore Program. 4.504.5 - G:omposite Wood Products - Particleboard, medium density fiberboard (MDF) and hardwood plywood used in interior Ifinish systems shall comply with low formaldehyde emission standards. 4.505.2 - Cfoncrete Slab Foundations - Avapor retarder and capillary break is installed at slab on grade foundations. 4.505.3 - NAoisture Content of Building Materials - Wall and floor framing materials shall be checked before enclosure. 4.506.1- Blathroom Exhaust Fans - Exhaust fans which terminate outside the building are provided in every bathroom. 4.507.2 - Hleating and Air Conditioning System Design - Duct systems are sized, designed, and equipment selected using thee following methods: 1. Establish heat loss and heat gain values according to ACCA Manual J or equivalent. 2. Size dluct systems according to ACCA 29-D (Manual D) or equivalent. 3. Select heating and cooling equipment accordimg to ACCA 36-S (Manual S) or equivalent. Installed S& Special Inspection Qualifications 702.1- HV/AC system installers are trained and certified in the proper installation of HVAC systems and equipment. 702.2 Speecial inspectors must be qualified and able to demonstrate competence to the enforcing agency in the disciplinae in which they are inspecting. 703.1- Doccumentation - Verification of compliance with the code may include construction documents, plans, specificaations, builder or installer certification, inspection reports, or other methods of acceptable to the enforcing agency vwhich show substantial conformance. TABLE 4.504,11 ADHESIVE VOC LIM70 r.. w AR CHRECTU RA.L APPU CATIONS CUPP EN T VOC f,.INIf T Irdc, nr ;tr . kt adllit3 hvs 2Y) Ca . , t rud adhostat?s til nOnor -o arlhesisx- 150 'Wood (low -Ti nn ndha KL Inn I"?:ubb cr t1mr adhc5tms .419) Subfloor aJh­£ia " Cmrnic tile. adh ives 65 '%'t'T and ms 1, ttt the n(ihe sines TXl -175 Dr,,�yyr�'alglnt� anet a�d17cstves 501) 'K -la ri ne dlecic 51 I L11ti „tl ? constn taction adh t 7.'.f' Structural 1n7inZ adh :t4x IEC( S i nx le- pty mof in einihra w a]tY'sNr� s X50 Othi r nut mi,.es nit wmif imlly lig i Cbmte.Meli ma pmmb S E WLTY ALPPLICATI NS N � C PVC v-eldin :5,10 CTV C weltft e< 4T ABS , ,a,Ming _31 - 31-Plastic PI a-sticcement w ldi n 250 Adhel;hx- rirwr ("qtri,,nsti c 550 Cnintaa:t adhcsi� O r i tiu ..ttise,wntact3�JNAPs 150 5tnaictiura.t -%-oM lnemk+er a dbs.,siNv 14n 'Th . and trim adh rw 250 liBSTfl.ATE SPE4iC APPLICATIONS NkId h"MCA 31 - PI astic foamy Porous matk: ri al (exc e . t -wrcd ) 420 Woind - TO 1. If an udbe-she h, u sed ten bond di ssimi Lu- substrabes tc t1wr, the adhs sive ea.-ith th. hich:2.st leVNC eont>, nt shall 'Ne of cra d. 2- Pbrndditionariiinfciimati,:)n arc1in- Tnethods tomensurethe YW_content specified in this tabic, set, Styuth Cc asst Air QualityMan3-irerrient District Rule ll68. TABLE 45D4.2 SEAL AM VQ LlttiU Less Water°-nnd Lem Exemptrrir pound in Grarns FQr Lito_r SEALATITS CURPENT X110 LIMIT rchitecturrat 2Y) A1Ya.riw dedw 700,_ No r :� ? Roadivay, 2-11 i riff I' v r. -4 in embra`n^ .419) Other E41LANT 171a111AEIM . r Arch Itectura:d Nall rc ot1 k Pannus TXl -175 Nlo d irii,,d biturnimu ITY) 'K -la ri ne dlecic 51 Other ,, i TABLE t VOC CONTE NT L IM n FOR • • ° t. O• Gramg of M. por Utgr of Coating, COATING CATFQO EFFECTIVE ill/23% EFFECTAS lAl 20112 lnat€o3tin Ls �J A �I�ut'Iat �,a,�fn 0.1 a"' odium dernity fltw rls+ r,td t1.11 Thin medium densitfi'Ivzrboind= 0 L1, SPECtALT Y COA1lKC; S At u iti'lii no m roo-f cortins . r xT, ment qpeci itty conttrw 1 Rt hl"inonq v"40 matt of 51 ?i tutrainLm% roof rnm­rs AND ITT 00 'Atli Iii ake 3_° Cbmte.Meli ma pmmb _53 N � C t`oncreh'-ft n a�nr at r t H I a M, Hwa ' sealer U Rip covj t Eaux finishigit �A O rip r°esi ti tlt'lag, M r � 1+t+r° 14tan I V 1 Orwhic nrLs "-ti rips (Sim rinti �[r0 t tt h tern entre coatinAl 420 Indullialmaint nunr_ C.imfinv, TO Low Lids om6npl l *) `.J hire niedto cement c: matin 450 lr OSOV, to tLue tittn s i � > �J Mo tk. r4pMent6l « ratrill C itilttiot matin ,s 2 3 . f'crtreaEnnt wasli rirrters � Pimp rx,,*rl~;.ani un.derco tery 100 W 1 ar_kive: ew_tmt11i . seav_," ' 351 coitin s _ 250 V1 ROA "in ,s W r, Fact o-matalive cki inf J100 250 Sh ell s Clear Opaque '736 i I -I s. -illi ty primles. Wsilersatid mi-dez atets 3In_ 100 tr` 6 * No. C �l REN to vml lidant .tom S�.tcnrnlrl�. _ of taun s RA DENTIAL JtALCREEN Co -t . Tr>iil`ficmatt�ln a.In s n. l .D Date 2016 Tub and the refriigh c>0;7fts 420 ii 'aler rw i li7 membranes `2' Job Wcod cointirys 271-5 Wood prevfrallim 3�01 Sheets ti is-Ticb 6m ers 340 1. Crams of VOC Ivr liter of coating. inclltdi,rL! -3.wand iml.udin exempt corn". inds. 2.-aeTLt-iriedlimi,tsrreTniininetYc.:tunl+ sr isedfi:Iniisar U-4elinstibsL qu nt columns in ttf c table. 3. '&Aces in this table are d?rivW from 'those „ cxifjed ISN. t1w Califiarnia Air lZe-scurces :3owd Amhitectural Coatings;Sugg-estod Control N ea_vure: Tabruary 1. ` 008. Adore i-nfcrrrtatitn is alsmilable fr)6m the Air I'e�,�ir��s` roam. TA -BLE 4.504.5 FORMALUME LIF11TS'; Maximum Form aldphMp- Erne sionr, in Pbdr, Qe-r lifiitim F'RODUCT RRE"T L"AIT 14ardwood -)vvvf til ntvrcele 0,05 H,Td ood 1y�=sem m nSitE N, ' A riticlLboa rd 0.1 a"' odium dernity fltw rls+ r,td t1.11 Thin medium densitfi'Ivzrboind= 0 L1, t. in tbiz Liblc ars �krhV 4 fivm theme Tccitiid to thc, Calif Qnnia., Air Ile nrcem Board.. Air Toxi" Ck-utmI NLasure frr C"ci1npo%ite Wood a ti? -d i n air. lordunce -with AS"Th•'1 E`t 4313. For add iticmzd infrormiationw s �: ►1^i.:�r�icx C'��e �i:��°„�tfx�>as;'f"itt�� l7,1-xectinn59 �,f 2n [finauph 93 i 2tJ. t2 . 2e .L- trldium dit fihyr.rd fa is a rnaci mum thiclalcs cif i� h (8 rnrn). PERMIT B(!TTE COUNTY DEVELOPMENT SERVICES REVIEWED FOR CODE COMPLIANCE DATE BY NOTE: THE PRC'>JEGT MANAOER OR GENERAL CONTRACTOR WILL BE THE RESPONSIBLE PARSON TO COLLECT AND PROVIDE VER I F I GATI ON OF GALOREEN C.,Ot,-1FLIANC.,E TO THE BUILDING INSPECTOR PRIOR TO BUILDING SINAL. Revision: Date: By: N n V / H ITT 00 [� • N � C H U @) o � u U bA O � W �A O M r � 00 M V 1 I V1 W W `.J I� � > �J O I®i H Z W Q I -I V1 W r, I -I A 0 A. C 0 * No. C �l REN 28 7//17 RA DENTIAL JtALCREEN MANDATORY MEASURE5 Date 2016 Scale Drawn Job Sheet Of Sheets 2 N N N M 44 V-1 O N N N r t Uo G O