B16-0888 000-000-000
ABBREVIATIONS A AMPERE AC ALTERNATING CURRENT BLDG BUILDING CONC CONCRETE DC DIRECT CURRENT EGC EQUIPMENT GROUNDING CONDUCTOR (E) EXISTING . EMT ELECTRICAL METALLIC TUBING FSB FIRE SET—BACK GALV GALVANIZED GEC GROUNDING ELECTRODE CONDUCTOR GND GROUND HDG HOT DIPPED GALVANIZED I CURRENT .Imp CURRENT AT MAX POWER Isc SHORT CIRCUIT CURRENT kVA KILOVOLT AMPERE kW KILOWATT LBW LOAD BEARING WALL MIN MINIMUM (N) NEW NEUT NEUTRAL NTS NOT TO SCALE OC ON CENTER PL PROPERTY LINE POI POINT OF INTERCONNECTION PV PHOTOVOLTAIC SCH SCHEDULE S STAINLESS STEEL STC STANDARD TESTING CONDITIONS TYP TYPICAL UPS UNINTERRUPTIBLE POWER SUPPLY V VOLT Vmp VOLTAGE AT MAX POWER Voc VOLTAGE AT OPEN CIRCUIT W WATT N MA R RAINTIGHT 3R E 3 , LICENSE" Z rC4-;# `888104, MODULE GROUNDING METHOD: ZEP SOLAR AHJ: Butte °County 'yr` UTILITY: Pacific Gas and Electric Company ELECTRICAL NOTES 1 JURISDICTION NOTES 1. THIS SYSTEM IS GRID—INTERTIED VIA A UL—LISTED POWER—CONDITIONING INVERTER. 2. THIS SYSTEM HAS NO BATTERIES, NO UPS. 3. A NATIONALLY—RECOGNIZED TESTING LABORATORY SHALL LIST ALL EQUIPMENT IN COMPLIANCE WITH ART. 110.3. 4. WHERE ALL TERMINALS OF THE DISCONNECTING JOB NUMBER JB -9596-2-26 00 MEANS MAY *BE ENERGIZED IN THE OPEN POSITION, BUTTE A SIGN WILL BE PROVIDED WARNING OF THE COUNTY HAZARDS PER ART. 690.17. APR 2 9 2016 5. EACH UNGROUNDED CONDUCTOR OF THE. UPLIFT CALCULATIONS MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED BY MODULES: (13) REC # REC260PEZ PHASE AND SYSTEM PER ART. 210.5. DEVELOPMENT 6. CIRCUITS 'OVER 250V TO GROUND SHALL SERVICES COMPLY WITH ART. 250.97, 250.92(B). _ Ug,�f� J316 7 DC CONDUCTORS EITHER DO NOT ENTER BUILDING OR ARE RUN IN METALLIC RACEWAYS OR ENCLOSURES TO THE FIRST ACCESSIBLE DC DISCONNECTING MEANS .PER ART. 690.31(E). 8. ALL WIRES SHALL BE PROVIDED WITH STRAIN RELIEF AT ALL ENTRY INTO BOXES AS REQUIRED BY UL LISTING. , 9. MODULE FRAMES SHALL BE GROUNDED AT THE UL—LISTED LOCATION PROVIDED BY, THE MANUFACTURER USING UL LISTED GROUNDING HARDWARE. 10. MODULE FRAMES, RAIL, AND POSTS SHALL BE BONDED WITH EQUIPMENT GROUND CONDUCTORS. GENERAL NOTES 1. ALL WORK TO BE DONE TO THE 2013 CALIFORNIA BUILDING CODE, 2013 CALIFORNIA PLUMBING CODE, AND THE 2013 CALIFORNIA RESIDENTIAL CODE. 2. ALL ELECTRICAL WORK SHALL COMPLY WITH THE 2011 NATIONAL ELECTRIC CODE AS AMENDED BY THE 2013 CALIFORNIA ELECTRIC' CODE. CONFIDENTIAL — THE INFORMATION HEREIN JOB NUMBER JB -9596-2-26 00 CONTAINED SHALL NOT BE USED FOR THE - BENEFIT OF -ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C PART TO OTHERS OUTSIDE THE RECIPIENTS UPLIFT CALCULATIONS ORGANIZATION, EXCEPT IN CONNECTION WITH THE SAIF AND USE OF THE RESPECTIVE MODULES: (13) REC # REC260PEZ SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PERMISSION OF SOLARgTY INC. ABB# PVI-3.0—OUTD—S—US—Z—A W .Mu Vwncnc ROBERT T BROWN 2465 DURHAM—DAYTON HIGHWAY DURHAM, CA 95938 APN: 039-460-015-000 VICINITY MAP Robert T Brown RESIDENCE 3.38 KW PV ARRAY PAGE NAME: COVER SHEET INDEX PV1 COVER SHEET PV2 PROPERTY PLAN PV3 SITE PLAN PV4 STRUCTURAL VIEWS, : PV5 UPLIFT CALCULATIONS PV6 " . -THREE LINE DIAGRAM Cutsheets Attached REV BY DATE COMMENTS REV A NAME DATE COMMENTS : • s e Nathan Graham SHEET: REV: DATE PV 1 a 4/28/2016 'wo,solarCity 1 • 3055 Clearview Way Sm Mateo, CA 94402 T:(650) 638-1028 F:(650) 638-1029 (888)—SOL—CITY (765-2489) www.solarcity.com �'vY' �\ QD DISTRIBUTION PANEL & LABELS \ \ Lc LOAD CENTER & WARNING LABELS ` QM DEDICATED PV SYSTEM METER - Q STANDOFF LOCATIONS z PITCH: 18 ARRAY PITCH: 18 -- CONDUIT RUN ON INTERIOR — GATE/FENCE j MP1 AZIMUTH: 270 ARRAY AZIMUTH: 270 - - INTERIOR EQUIPMENT IS DASHED MATERIAL: Comp Shingle STORY: 1 Story, L _ J - PITCH: 18 ARRAY PITCH: 18 �- MP2 AZIMUTH: 90 ARRAY AZIMUTH: 90 G Scale: 3/32" = 1'. w E MATERIAL: Comp Shingle STORY: 1 Story 2M N F,S CONFlDFNTIAL THE INFORMATION HEREIN CONTAINED_SHAu-,NO.T_BE USED FOR.THEROBERT JOB NUMBER JB -959622.6 . 00-,. . PREMISE "OWNER -'`, � - T BROWN DESMPTION: � �-- �'• RESIDENCE DESIGN: Nathan �\� _ Robert T Brown Graham ���=SolarCity. MOUNTING SYSTEM: . ' _ " Comp Mount Type C --r--- ' BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN • 2465 DURHAM -DAYTON HIGHWAY •� s • ''- Front Of House 3 PART TO OTHERS OUTSIDE THE RECIPIENTS, ORGANIZATION, EXCEPT IN CONNECTION WITH . _�" ` DUR-HAM, CA 95938 �, Inv a f MODULES: THE SALE AND USE OF THE RESPECTIVE _ . "" ' 5 Cfe ae�le� way ' SHEET: REM. DATE PV 3 a 4/28/2016 SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC PAGE NAME <" ` �'"` `' 2 *.. SITEj PLAN - San GA 94402 T:(650) San Mo28 F: (850) 838-1029 (888)-SOL-aTY (7e5-2489) wwwsala«I►y.�„ INVERTER ABB# PVI-3.0-OUTD-S-US-Z-A LEGEND \ [ y \� s I (E) UTILITY METER &WARNING LABEL \ I Ing INVERTER W/ INTEGRATED DC DISCO EXISTING & WARNING LABELS 4 c vc TE M SYS �� / ,� ° ® DC DISCONNECT & WARNING LABELS �� © AC DISCONNECT & WARNING LABELS JUNCTION/COMBINER BOX & LABELS �\ QD DISTRIBUTION PANEL & LABELS \ \ Lc LOAD CENTER & WARNING LABELS ` QM DEDICATED PV SYSTEM METER - Q STANDOFF LOCATIONS CONDUIT RUN ON EXTERIOR -- CONDUIT RUN ON INTERIOR — GATE/FENCE .0 HEAT PRODUCING VENTS ARE RED INTERIOR EQUIPMENT IS DASHED L _ J SITE PLAN �- Scale: 3/32" = 1'. w E 2M N F,S CONFlDFNTIAL THE INFORMATION HEREIN CONTAINED_SHAu-,NO.T_BE USED FOR.THEROBERT JOB NUMBER JB -959622.6 . 00-,. . PREMISE "OWNER -'`, � - T BROWN DESMPTION: � �-- �'• RESIDENCE DESIGN: Nathan �\� _ Robert T Brown Graham ���=SolarCity. MOUNTING SYSTEM: . ' _ " Comp Mount Type C --r--- ' BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN • 2465 DURHAM -DAYTON HIGHWAY ,...3'38 KW PV ARRAY w PART TO OTHERS OUTSIDE THE RECIPIENTS, ORGANIZATION, EXCEPT IN CONNECTION WITH . _�" ` DUR-HAM, CA 95938 �, " -- -f f MODULES: THE SALE AND USE OF THE RESPECTIVE (13) REC # REC260PEZ "" ' 5 Cfe ae�le� way ' SHEET: REM. DATE PV 3 a 4/28/2016 SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC PAGE NAME <" ` �'"` `' 2 *.. SITEj PLAN - San GA 94402 T:(650) San Mo28 F: (850) 838-1029 (888)-SOL-aTY (7e5-2489) wwwsala«I►y.�„ INVERTER ABB# PVI-3.0-OUTD-S-US-Z-A SIDE.VIEW OF MP1 NTS SIDE VIEW OF MP2 NTS A MPI X -SPACING X -CANTILEVER Y -SPACING I . NOTES S1 - 72" r PORTRAIT S1 (E) LBW LOCATE RAFTER, MARK HOLE _ —7 - 9' (E) LBW SIDE.VIEW OF MP1 NTS SIDE VIEW OF MP2 NTS A MPI X -SPACING X -CANTILEVER Y -SPACING Y. -CANTILEVER NOTES LANDSCAPE 72" 2411 PORTRAIT 48" 20" LOCATE RAFTER, MARK HOLE _ RAFTER C.J. �� 2x6 @ 24 OC 2x6 @16" OC. ROOF AZI 270 PITCH 18 STORIES: 1 . ARRAY' 270 PITCH 0 Comp. -Shingle - Skip Sheathing MP2 X -SPACING X -CANTILEVER Y -SPACING Y -CANTILEVER NOTES LANDSCAPE 72" 24" PORTRAIT 48" 20" LOCATE RAFTER, MARK HOLE _ RAFTER C.J. 2X6 @ 24" OC 2x6 @16" OC ROOF AZI 90 PITCH 18 ARRAY AZI 90 PITCH 18 STORIES: 1 Comp Shingle - Skip Sheathing PV MODULE 5/16" BOLT WITH _ INSTALLATION ORDER - FENDER WASHERS LOCATE RAFTER, MARK HOLE _ ZEP LEVELING FOOT _ (1) LOCATION, AND DRILL PILOT ZEP ARRAY SKIRT (6) HOLE. (4) (2) SEAL PILOT HOLE WITH POLYURETHANE SEALANT. ZEP COMP MOUNT C ZEP FLASHING C (3) (3) INSERT FLASHING. (E) COMP. SHINGLE (1) (4) PLACE MOUNT. r (E). ROOF DECKING , U (2) FINSTALL LAG BOLT WITH (5) 5/16" DIA STAINLESS (5) SEALING WASHER. STEEL LAG BOLT LOWEST MODULE SUBSEQUENT MODULESINSTALL LEVELING FOOT WITH WITH SEALING WASHER (6) BOLT &WASHERS. 1 (2-1/2° EMBED, MIN) _ (E) RAFTER STANDOFF ` Scale:.1.1/2" = 1' CONFIDENTIAL — THE INFORMATION HEREIN CONTAINED SHALL. NOT BE USED FOR THE JOB NUMBER: JB -9596226 -0 0 PREMISE OWNER: ROBERT T BROWN DESCRIPTION - ' Robert T Brown RESIDENCE DESIGN: Nathan Graham ���l, �, BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN MOUNTING SYSTEM: Comp Mount Type C -• • 2465 DURHAM—DAYTON HIGHWAY _ _x�.-3.38 .KW PV ARRAY �� -� �.,� ;SolarCity. ��� PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: DURHAM CA 95938 ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (13) REC .# REC260PEZ T i �, ,, PA( NOME E" ` .. SHEER REV. DATE 3055 CleaNew Way sm, Mateo, CA 94402 SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. ABB . PVI-3.0—OUTD—S—US—Z—A "" STRUCTURAL VIEWS PV 4 0 4%28/2016 T:(650) 638-1028 F:(650) 638-1029 (888) -SOL -Cm (765-2469) ,�.so1aaty.com f is • .. •,a _ F;., r . r - ,, _ �� . UPLIFT CALCULATIONS 04.08.2016 PV System Structural Version #56.4 -- ;,%SolarCity Desian Software Pro ect Information 8c Table Of Contents Risk Category; PVSystem Type: Comp Ro PREMIA OYMER DESCRIPTION: � ROBERT T BROWN Robert 'T Brown RESIDENCE DEscrr: Nathan Graham NN% ■ SolarC�ty. MOUNTING SYSTEM: - Comp Mount Type C � - SII _ �� SolafCNy SleekMounf'" -2465 DURHAM—DAYTON HIGHWAY, .s-3.38 KW PV .ARRAY �:-''"^ �'a�� h, • Comp Roof F - , ers ooff C6m Rao- '� ' NoouLES Roof Slope Rafter- acin ORGANIZATION, EXCEPT IN CONNECTION WITH; THE SALE AND USE OF THE RESPECTIVE 180 ' ^ PACE Nave 24" O.6 SOLARGTY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. PV�System Module: Orientation PV Module Area-_ ` ' UPLIFT CALCULATIONS - Landscape and Portrait T:(6W) 638-1028 F:(650) 638-1029 (BBB) -SOL -CITY (765-2489) wmaolardtysom PV Module Width _ 39" PV Module Length" •• _ Standoff Attachment Hardware 66" '�'"� Comp Mount Type C Reduced Ground/Roof Live/Snow Loads i pg 0.0 psf ASCE Table 7-1 0.0 psf_ _ _ _ _ASCE Eq 7:41 ASCE Eq: 7.4-1 0.0 psf Wind `Design Ciiteri it Wind Design Code Wmd.D�ign Method Basi Wind Speed ExposureCategoryw — Roof Style 7 10 �— _ASCE •-,-----•.+ Pam,_- � Partlall'y/Fully Endosed Method 110 mph C' V �� Fig: 26.5-1A� =Section 26;7_ ay..30.4-2Aje/c-5q/e 'Gable Roof Meart Roof Hefgh_T"`�"" Effective Wind Area 1 Module �`fi�� 15 R �Sedion 26:2 A 17.8 sf° IBC 1509.7.1 Wind: Pressure Calculation Coefficients Wind Pressure_Fxposure Kz Topographic Factor_• ,_ 'Kif:. Wind Directionality Factor _ _ Kd Im ortancefactar L 0.85 Table 30.3-1 i 00 - � „Section 26:_8',_ Section 26.Cr1__ 0.85 NA. Velocity Pressure qh qh =• 0.00256 (Kz) (Kzt) (Kd) (V12) 22.4 Equation 30.3-1 Ext Pressure Coeffident (Up )-� GCp (Up): E Pressure Coeffdent Down GC Down -0.88' ry. 3os/c-5Ne 0.45:, FV. 30.4-2NiVCG5A/B Design Wind Pressure P p = gh GC Equation 30..4-1 Wind_Pressure Up P(up)— Wind Pressure Down down -19.6 psf. 16.0 psf Allowable Standoff Spacings X -Direction Y -Direction Max Allowable Standoff Spacing Max All wable�Canblever��`Landscape Standoff Configuration Landscape 72" 39" Landsca a Not-Sta gered Max-StandoffTrlbuta_ -Area' PV Assembly_Dead Load Net Wind Uplift=atSiandoff Uplift Capacity of Standoff Standoff Demand Ca w,a,_,r,T_rib: _ W -PV 20 Sf: - 3 psf __T actual ;7l ' T -allow 500 Itis ` DCR Max Allowable Standoff Spacing Max Allowablee Cantilever" ..- Standoff Conf ulation Portrait 48" 66" �Porfrait:� Portrait 20" NA; Not-Sta gered Max Standoff_Tributary Area,,,,,,`_ PV Assembly Dead Load NehW nd Upliftat_Standoff Uplift Capacity of Standoff : , _ Trib,,� _ W -PV . 22 sf: 3 psf Ttac!#al= T -allow 219Ibs 500 lbs .Standoff Demand Ca a DCR 418% UPLIFT CALCULATIONS 04.08.2016 PV System Structural Version #56.4 -- ;,%SolarCity Desian Software Pro ect Information 8c Table Of Contents Risk Category; PVSystem Type: Comp Ro PREMIA OYMER DESCRIPTION: � ROBERT T BROWN Robert 'T Brown RESIDENCE DEscrr: Nathan Graham NN% ■ SolarC�ty. MOUNTING SYSTEM: - Comp Mount Type C � - SII _ �� SolafCNy SleekMounf'" -2465 DURHAM—DAYTON HIGHWAY, .s-3.38 KW PV .ARRAY �:-''"^ �'a�� h, • Comp Roof PART ATO OTHERS OUTSIDE THE RECIPIENTS , ers ooff C6m Rao- '� ' NoouLES Roof Slope Rafter- acin ORGANIZATION, EXCEPT IN CONNECTION WITH; THE SALE AND USE OF THE RESPECTIVE 180 ' ^ PACE Nave 24" O.6 SOLARGTY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. PV�System Module: Orientation PV Module Area-_ ` ' UPLIFT CALCULATIONS - Landscape and Portrait T:(6W) 638-1028 F:(650) 638-1029 (BBB) -SOL -CITY (765-2489) wmaolardtysom PV Module Width _ 39" PV Module Length" •• _ Standoff Attachment Hardware 66" '�'"� Comp Mount Type C Reduced Ground/Roof Live/Snow Loads Ground Snow Load Sureounding Roof Snow Roof Snow Over PV Modules pg 0.0 psf ASCE Table 7-1 0.0 psf_ _ _ _ _ASCE Eq 7:41 ASCE Eq: 7.4-1 0.0 psf Wind `Design Ciiteri it Wind Design Code Wmd.D�ign Method Basi Wind Speed ExposureCategoryw — Roof Style 7 10 �— _ASCE •-,-----•.+ Pam,_- � Partlall'y/Fully Endosed Method 110 mph C' V �� Fig: 26.5-1A� =Section 26;7_ ay..30.4-2Aje/c-5q/e 'Gable Roof Meart Roof Hefgh_T"`�"" Effective Wind Area 1 Module �`fi�� 15 R �Sedion 26:2 A 17.8 sf° IBC 1509.7.1 Wind: Pressure Calculation Coefficients Wind Pressure_Fxposure Kz Topographic Factor_• ,_ 'Kif:. Wind Directionality Factor _ _ Kd Im ortancefactar L 0.85 Table 30.3-1 i 00 - � „Section 26:_8',_ Section 26.Cr1__ 0.85 NA. Velocity Pressure qh qh =• 0.00256 (Kz) (Kzt) (Kd) (V12) 22.4 Equation 30.3-1 Ext Pressure Coeffident (Up )-� GCp (Up): E Pressure Coeffdent Down GC Down -0.88' ry. 3os/c-5Ne 0.45:, FV. 30.4-2NiVCG5A/B Design Wind Pressure P p = gh GC Equation 30..4-1 Wind_Pressure Up P(up)— Wind Pressure Down down -19.6 psf. 16.0 psf Allowable Standoff Spacings X -Direction Y -Direction Max Allowable Standoff Spacing Max All wable�Canblever��`Landscape Standoff Configuration Landscape 72" 39" Landsca a Not-Sta gered Max-StandoffTrlbuta_ -Area' PV Assembly_Dead Load Net Wind Uplift=atSiandoff Uplift Capacity of Standoff Standoff Demand Ca w,a,_,r,T_rib: _ W -PV 20 Sf: - 3 psf __T actual 196 lbs T -allow 500 Itis ` DCR Max Allowable Standoff Spacing Max Allowablee Cantilever" ..- Standoff Conf ulation Portrait 48" 66" �Porfrait:� Portrait 20" NA; Not-Sta gered Max Standoff_Tributary Area,,,,,,`_ PV Assembly Dead Load NehW nd Upliftat_Standoff Uplift Capacity of Standoff : , _ Trib,,� _ W -PV . 22 sf: 3 psf Ttac!#al= T -allow 219Ibs 500 lbs .Standoff Demand Ca a DCR 418% • • Via:_, - _ _ �� CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR THE JOB NUMBER: JB -9596226 0 PREMIA OYMER DESCRIPTION: � ROBERT T BROWN Robert 'T Brown RESIDENCE DEscrr: Nathan Graham NN% ■ SolarC�ty. MOUNTING SYSTEM: - Comp Mount Type C � - BENEFIT. OF, ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN -2465 DURHAM—DAYTON HIGHWAY, .s-3.38 KW PV .ARRAY �:-''"^ �'a�� h, • PART ATO OTHERS OUTSIDE THE RECIPIENTS DURHAM CA 95938 r ' NoouLES 3055 ge�vte■ Way Son Mateo, ie 94402 ORGANIZATION, EXCEPT IN CONNECTION WITH; THE SALE AND USE OF THE RESPECTIVE (13) REC # REC260PEZ ' ^ PACE Nave SHEET: REV. DATE SOLARGTY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. INVERTER: ABB PVI-3.0—OUTD—S—US—Z-A ` ' UPLIFT CALCULATIONS - PV 5 a 4/28/2016 T:(6W) 638-1028 F:(650) 638-1029 (BBB) -SOL -CITY (765-2489) wmaolardtysom GROUND SPECS MAIN PANEL SPECS GENERAL NOTES INVERTER SPECS MODULE SPECS LICENSE BOND (N) #6 GEC TO (E) GROUND ROD Panel Number: NoLabel Inv 1: DC Ungrounded INV 1 - (1 )ABB PVI-3.0-OUTD-S-US-Z-A LABEL: A - (13)REC # REC260PEZ CA # 888104 AT PANEL WITH IRREVERSIBLE CRIMP Meter Number: 107 568 400 Downsizing Main Breaker For Tie -In FCI Inverter, Zigbee 3000W, 240V, 967 PV Module; .260W, 236.6W PTC, MC4, 40mm, Black Frame, ZEP Enabled C-10 Underground Service Entrance INV 2 Voc: 37.8 Vpmax: 30.7 INV 3 Isc AND Imp ARE SHOWN IN THE DC STRINGS. IDENTIFIER �E 200A MAIN N) 175A/2P SERVICE PANEL MAIN CIRCUIT BREAKER ADJUST MIN. ACTIVATION VOLTAGES! (E) WIRING Inverter 1 IND 3 ABB 1 DC. VStart = 184V N)175A/2P PVI-3.0-OUTD-S-US-Z-A i Dc MP 2: 1x6 (E) LOADS _____ Ecc ____________E __--____- - - _ - L2 ZDC�,FN 20A/2P 2 vstart - 2DDV EGC DC* DC+ AF ---------------------------- --------- ------------ --- ---TN Dc c MP 1� 1x7--tpj1 ., .,�._ _ — — GND _ _ B I ------------ ------------- --------.---- -------------- GEC EGC--------------------- —----- ---------------- I I - I I N 1 I ,� + (1)Conduit Kit; 3/4' EMT EGC __J.I - p.. z� - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ---� i---------------- _. EGC ABB Dc. - - -, I I" PVI-3.6-OUTD-S-US-Z-A DC- String of 1x10 ' 20A/2P I I I EGC • ---- ---------------- A I ' - L, E F", ------------------------To 120/240V N N DC- SINGLE PHASE UTILITY SERVICEI EGC _ _ _ DC- DC+ I L-------—-----------—--------------- T N Dc Dc String of 1x7 Z' +---=t------------------- .............. EEC __ GNDEGC--------------- ------------ — ---------EGC.-----------------J I ,` EXISTING SYSTEM ` ' 1 8.925 kW INVERTER: (2) ABB # PVI-3.6-OUTD—S—US—Z—A _ ❑ I MODULE: (35) Advantage Module, 255W ABB Dc+ PVI-3.6-OUTD-S-US-Z-A DC" Strin of 1x10 g 20A 2P I I ;1 - - -- ----J r A I I Lt 71 v r------------------------- ------- --- EGC--------- _ I JD. • B I I L2 1 " " N I' I N I 1 EGC DG - DC.I LA---- --------- - t-------------------------- ---� DG String of 1x8 tpj II I N DC" __ GND EGC---------.----------------- -- — ----- ---EGC— 1 ♦----L---------------------------------GEC I Voc* = MAX VOC AT MIN TEMP I L -------------------------=-------------------------------- POI (1) Brreaaker,820AYIP 2DA/2P-20A/iP, 2 Spacc sE Quad A`, DC r 1 AWG 810, THWN-2, Black -(I)AWG 86, Solid Bare Copper GEC (2)AWG 810, PV Wire, 60OV, Black Voc* = 248.84VDC Isc = 9.01 ADC (1)AWG 810, THHN/THWN-2, Green EGC Vmp =184.2 VDC Imp= 8.5 ADC O (1)AWG 810, THWN-2, Red Ok(j)qon0qij L���1LL (1)AWG 810, THWN-2, White NEUTRAL Vmp =240 VAC Imp=14.5 AAC Kit;. 3/4' EMT - (1) AWG 810, THWN-2, .Green.. EGC • . • •- (1) Conduit, Kit; • 3/4' .ENT • ...... • . (2) AWG 810, PV Wire, 60DV, Black Voc* = 290.32 VDC Isc = 9.01 ADC ......... O (1)AWG 810, THHN/1HWN-2, Green EGC Vmp = 214.9 VDC Imp= 8.5 ADC .. � ......... Q) CRnoqitKit:. 3/4', EMT .................................. �. . CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER J[3-9596226 0 0 PRI]11SE OWNEIL _ DESCRIPTION: _ DESIGN: cor►raNED SHALL NOT BE USED FOR THEROBERT T BROWN RoberfwT Brown RESIDENCE Nathan :Graham ���f, • BENEFIT 017-�ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM:- solaruty. -SHALL BE WHOLE OR IN 2465 DURHAM—DAYTON HIGHWAY -3.38 KW PV ARRAY M NOR IT DISCLOSED IN Comp Mount Type C - PART TO OTHERS OUTSIDE THE'RECIPIENTS MooDils DURHAM CA 95938 ORGANIZATION, EXCEPT IN CONNECTION WITH 3055 gearvie� Way THE SALE AND USE OF THE RESPECTIVE (13) REC # REC260PEZ PAGE NAME SHEET: REV DATE San Mateo, CA 94402 SOLARgTY EQUIPMENT, WITHOUT.THE WRITTEN INVERTER: T:(650) 638-1028 F:(650) 638-1029 PERMISSION OF SOLARCITY INC. ABB# PVI-3.0—OUTD—S—US—Z—A THREE LINE DIAGRAM PV; 6 a 4/28/2016 (888)-SOL-aTY (765-2489) •ww.sdorcity.corn • Panel Schedule Load Breaker. Dryer 30A/2P Range 40A/2P NEC 220.83 - Residential Load Calculation version 3.0 NEC 220.83(B) "Existing Dwelling Unit.... to determine if the existing service ... is of sufficient capacity ... The following percentages shall be used for existing ... loads ... First 8 kVA of load at 100%, Remainder of load at 40% Oven Qty 30A/2P I VA Other 20A/2P NEC 220.83(B)(1) General lighting and general -use receptacles at ... 3 volt-amperes/fta as . Other 20A/2P determined by 220.12. Air Conditioner 40A/2P t Sq Ft I VA Laundry 20A/1P Floor.Area (3VA/sq ft)` 1 25381 7614 Bathroom 20A/1P PERMISSION OF SOLARCITY INC. ' Lighting Circuit 15A/1P NEC 220.83(B)(2) 1500 VA for each 2 -wire, 20 -ampere small -appliance branch circuit and each Lighting Circuit •15A/IP 'laundry branch circuit covered in 210.11(C)(1) and (C)(2).- C)(2): Lighting Circuit 15A/1P J NEC 220.83(B)(3) All appliances.... Ranges, wall -mounted ovens, counter -mounted cooking Qty I VA Small Appliance Circuits. 5 7500 Laundry Circuits 1 1500 �} Bathroom Circuits (. 1 1500 NEC 220.83(B)(3) All appliances.... Ranges, wall -mounted ovens, counter -mounted cooking units ... Clothes dryers that are not connected to the laundry branch circuit ... [and) water heaters" ri 1. Breakerl VA Dryer CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER JB -9596226 0 0 CONTAINED SHALL NOT BE USED FOR THE 40 MOUNTING SYSTEM: BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C PART TO OTHERS OUTSIDE THE RECIPIENT'S MODULES: (13) REC # REC260PEZ ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PERMISSION OF SOLARCITY INC. ABB PVI-3.0-OUTD-S7US-Z-A units ... Clothes dryers that are not connected to the laundry branch circuit ... [and) water heaters" ri 1. Breakerl VA Dryer 30 5000 Range 40 7680 Oven 30 5760 Other 20 3840 Other i 20 3840 Total General Load (non -A/C load) 44234 VA First 8 kVA of load at 100% 180001 Remainder of load at 40% 14493 t General Calculated Load (non -A/C load) 22493 VA NEC 220.83(B) The larger connected load of air-conditioning or space -heating, but not both, shall be used ... [at) 100 Percent of Load Max Heating and Air -Conditioning load 7200 VA Total Load Sum of General Calculated Load 29693 VA �i & Heating and'A/C, Load . �, �4a " 123.72 A { PREMISE OWNER: DESORPTION: ROBERT T BROWN, Robert T Brown RESIDENCE y 2465 DURHAM—DAYTON HIGHWAY ' 3.38 KW PV ARRAY .DURHAM, CA 95938 ` - PAGE NAME ELECTRICAL LOAD CALCULATIONS DESIGN: Nathan Graham solarCity. I•. 3055 Clearvies Way SHEET: RE&.. DATE San Mateo, CA 94402 PV 0 4/28/2016 T:(650) 638-1028 F:(650) 638-1029 (686)—SOL—CITY (765-2489) vmr.sdarcity.r Breaker I VA Sum of A/C Equipment Sum of Electric Furnaces 40 0 7200 0 Max Heating and Air -Conditioning load 7200 VA Total Load Sum of General Calculated Load 29693 VA �i & Heating and'A/C, Load . �, �4a " 123.72 A { PREMISE OWNER: DESORPTION: ROBERT T BROWN, Robert T Brown RESIDENCE y 2465 DURHAM—DAYTON HIGHWAY ' 3.38 KW PV ARRAY .DURHAM, CA 95938 ` - PAGE NAME ELECTRICAL LOAD CALCULATIONS DESIGN: Nathan Graham solarCity. I•. 3055 Clearvies Way SHEET: RE&.. DATE San Mateo, CA 94402 PV 0 4/28/2016 T:(650) 638-1028 F:(650) 638-1029 (686)—SOL—CITY (765-2489) vmr.sdarcity.r Label Location L'abet Location: Label Location:, f.�• �,; r *' PHOTOVOLTAIC •• • (C)(IC)(CB),�" (AC) .3.. V SYSTEM . (DC)(INV)(CB) £' :, - `,'' • Per Code: ' ° �. _ . - • • - ELECTRIC Per Coder o. CRC R331.2 • - - •THE . • . . - • HAZARD THIS I CEC 690.35(F) ` Label Location•."r� ' PHOTOVOLTAIC SYSTEM ARE TO BE USED -WHEN "s ; • • • ' (DC) (INV) `s h -• .. • INVERTER IS X w • MAY BE ENERGIZED Per Code: r y . UNGROUNDEDDISC- CEC 690.114-6'2 Label Location: WARNING (PC) Per,Code:ELECTRIC " t Label Location rr' . • • • SHOCK HAZARD CEC 690.17MAXIMUM POWER-= (DC) (INV),:.TERMINALS ON BOTH LINE ANDJA POINT CURRENT (Imp) }.; . - F P •;� ti'` - �t Per Code: LOAD SIDES MAY BE ENERGIZED MAXIMUM IN THE• .EN -•VOLTAGE-� CEC 690.53 - MAXIMUM SYSTEM= V VOLTAGE (Voc) CURRENT (Isc) Label. Location: {.WARNING (POI); Per Code: ;:,� INVERTER OUTPUT �CEC 705.12.D.7 Label Location. . • • • WARNING(DC) (CB) -' • is rt DEVICE Per Code:ELECTRICAL . • •TOUCH• - ■ TERMINALS CEC 690.17. TERN41NALS ON BOTH LINE AND •'. ■ - ., T-,xY - '�..3� .. �.,e:: �:. '.r , ti - y•• _ .tir -. - `.r t�,�w 1' r - IN THE OPEN POSITION 1 _ . Label Location: �T �, ,a ,•� ,f, Y . .� VOLTAGEDC , PHOTOVOLTAIC -• • (POI); + - ALWAYS PRESENT / • • Per Code: ••• G: ELECTRIC SHOCK -..• • • CEC 690.54; CEC 690.17'}'EXPOSED TO SUNLIGHT HAZA .rTERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN POSITION. FOR L - ■ - BO SERVICE• Label Location: IN BREAKER. (INV) PV r . _•SOURCE • - ELECTRIC _ Per Code:WARNING - , IF AGROUND INDIA . CEC 690.5(C) •' MAXIMUM AC V NORMALLY GROUNDED OPERATING VOLTAGE CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED Label Location: 'Label Location:_CAUTION (D) (POI) PHOTOVOLTAIC ' (AC) (POI) 1 Per Code: + vc , .(AC): AC DisconnectPHOTOVOLTAIC SYSTEM r ,1 { , �(C): Conduit DISCONNECTPer Code: ■ CEC 690.64.6.4 CEC 690.14.C.2 '(CB): Combiner`Box a. ` y' ' (D): Distribution Panel ' r - (DC): DC Disconnect _ •� --,. s:. ,�`� '- r ,(IC): Interior Run Conduit -Label Location Label Location:(WV);Jnverter With Integrated DC Disconnect s� . (AC) (POI) "'`"� CAUTION(POI) .,' ", K't"-r`�-s"".." (LC) Load Center •' Per Code: • ' • - • Per Code: - '�_ p r (M) Utility Meter Yyiw AC MAXIMUM AC CEC 690.54 _ • . • CEC405.�D.7 _` •� • • • • tl .( "'- "y'r ` (POI): Point of- Interconnection's • w _. CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR V �* sit . ' ' + I _ <n.r` - r ; :.vv,-� . 3055 Clearview way THE'BENEFlT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED '- �" a D - � - � + �- - � � .. � � �• - � San Mateo, CA 99402 _ IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, Label Set r °*' r, r' ., !����►` T:(650) 638 1028 F:(650) 638 1029 EXCEPT IN CONNECTION,WITH THE SALE AND USE OF THE RESPECTIVE iatfit,(888)-2489)www.SoWrdty,corn SOLARCITY EQUIPMENT. WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. - + r_...�. �' "^«r s' o ± . for composition shingle roofs +, t Leveling Foot A ^ Part No. 850.1172 '' _ ' • ETL listed to UL 467 .. n y Comp Mount r , Part No. 850-1382 , 4 r a 2 ~ r ' Listed to UL 2582 ^ " Mounting Block Listed to UL 2703. �' • ' ' ^� /e�� 4 Description_ , rOPV mounting solution for composition shingle roofs Fp m Works with all Zap Compatible Modules • ' _ e1MPp _ Auto bonding UL -listed hardware creates structural and electrical bond ti Zap System has a UL 1703 Class "A" Fire Rating when installed using modules from any manufacturer certified as "Type 1' or "Type 2" Interlock Ground Zep V2 f` - �' DC Wire Clip ` LISTED _ ' Part No. 8501388 Part No. 850-1511 Part No. 8501448 t ' r Specifications `� j f Listed to UL 2703 ' ' Listed to UL 467 and UL 2703 Listed to UL 1565 Designed for pitched roofs 1 , ' Installs in portrait and landscape orientations Zep System supports module wind uplift and snow load pressures to 50 psf per UL 1703` ' . ; • . y y Wind tunnel report to ASCE 7-05 and 7-10 standards { Zep System grounding products are UL listed to UL 2703 and UL 467 - . • "� `' 'Zep System bonding products are UL listed to UL 2703 t - �� • ~ ' � z��' *= Engineered for spans up to 72° and cantilevers up to 24" ' • - � • *'' `�. • Zep wire management products listed to UL 1565 for wire positioning devices a „ _ w - • Attachmentd UL listed L 25 or Wind Drive Rain S *� method to U 82 f n -•. • a • °� • f. - 'Array Skirt, Grip, End Caps 850-0113,850-1421, ,,. • ; ar _ *� . _ -- � Part Nos.' , , `• � , r 850-1460, 850-1467�d""` _ ~ �— zepsolar.com ' i a_ + , _ �` r� , zepsolar.com Listed to UL 1565 r `` This document does not create any express warranty by Zep Solar or about its products or services. Zep Solar's sole' warranty is contained in the written product warranty for . � . a This document does not create any express warranty by Zep Solar or about its products or services. Zep Solar's sole warranty is contained in the written product warranty for, ..•.-•� ;�-r' a ti each product. The end-user documentation shipped with Zep Solar's products constitutes the sole specifications referred to m the product warranty. The customer is solely - each product The end-user documentation shipped with Zep Solar's products constitutes the sole specifications referred to in the product warranty. The customer is solely responsible for verifying the suitability of ZepSolars products for each use. Specifications are subject to change without notice. Patents'and Apps•zspals.com. responsible for verifying the suitabiltly'of.ZepSolar's products for each use. Spe2ifications are subject to change without notice. Patents and Apps: zspats.com. �r s , • jr " ' 'A - �>w . •rrtrE' r - - ,.-.+ d`•--� l . '.*"*' —fie -•• -- , .� . "'-•„�itFt�,�:r►••"` Document # 800-1890-001?Rev,A _ Data last exported: November 13, 2015 2:23 PM - " 3'" • •Document # 800=1890-001 Rev A - 5 , - . Date last exported: November 13, 2015 2:23 PM .7 •' -v. .7 ° - •' - F,.' �r - .r�','. c _,•�•"�.`,-,` r r '* f� • th , . T • a' .. • C.L. •, it ` y t Pay a } ! �. i . .ice , ..... ',..'r . - '.. - ' - i, •tin - ':y . • x��, �. '.d . ti t. - • - • ' ., • .�^ - - "r n .. , .. _ - ; � iy - -G $olarCity I ZepSolar t = Next -Level PV Mounting Technology '''SolarCity I ZepSolar Next -Level PV Mounting Technology' 'F� Zep Systeme. Components r. - for composition shingle roofs +, t Leveling Foot A ^ Part No. 850.1172 '' _ ' • ETL listed to UL 467 .. n y Comp Mount r , Part No. 850-1382 , 4 r a 2 ~ r ' Listed to UL 2582 ^ " Mounting Block Listed to UL 2703. �' • ' ' ^� /e�� 4 Description_ , rOPV mounting solution for composition shingle roofs Fp m Works with all Zap Compatible Modules • ' _ e1MPp _ Auto bonding UL -listed hardware creates structural and electrical bond ti Zap System has a UL 1703 Class "A" Fire Rating when installed using modules from any manufacturer certified as "Type 1' or "Type 2" Interlock Ground Zep V2 f` - �' DC Wire Clip ` LISTED _ ' Part No. 8501388 Part No. 850-1511 Part No. 8501448 t ' r Specifications `� j f Listed to UL 2703 ' ' Listed to UL 467 and UL 2703 Listed to UL 1565 Designed for pitched roofs 1 , ' Installs in portrait and landscape orientations Zep System supports module wind uplift and snow load pressures to 50 psf per UL 1703` ' . ; • . y y Wind tunnel report to ASCE 7-05 and 7-10 standards { Zep System grounding products are UL listed to UL 2703 and UL 467 - . • "� `' 'Zep System bonding products are UL listed to UL 2703 t - �� • ~ ' � z��' *= Engineered for spans up to 72° and cantilevers up to 24" ' • - � • *'' `�. • Zep wire management products listed to UL 1565 for wire positioning devices a „ _ w - • Attachmentd UL listed L 25 or Wind Drive Rain S *� method to U 82 f n -•. • a • °� • f. - 'Array Skirt, Grip, End Caps 850-0113,850-1421, ,,. • ; ar _ *� . _ -- � Part Nos.' , , `• � , r 850-1460, 850-1467�d""` _ ~ �— zepsolar.com ' i a_ + , _ �` r� , zepsolar.com Listed to UL 1565 r `` This document does not create any express warranty by Zep Solar or about its products or services. Zep Solar's sole' warranty is contained in the written product warranty for . � . a This document does not create any express warranty by Zep Solar or about its products or services. Zep Solar's sole warranty is contained in the written product warranty for, ..•.-•� ;�-r' a ti each product. The end-user documentation shipped with Zep Solar's products constitutes the sole specifications referred to m the product warranty. The customer is solely - each product The end-user documentation shipped with Zep Solar's products constitutes the sole specifications referred to in the product warranty. The customer is solely responsible for verifying the suitability of ZepSolars products for each use. Specifications are subject to change without notice. Patents'and Apps•zspals.com. responsible for verifying the suitabiltly'of.ZepSolar's products for each use. Spe2ifications are subject to change without notice. Patents and Apps: zspats.com. �r s , • jr " ' 'A - �>w . •rrtrE' r - - ,.-.+ d`•--� l . '.*"*' —fie -•• -- , .� . "'-•„�itFt�,�:r►••"` Document # 800-1890-001?Rev,A _ Data last exported: November 13, 2015 2:23 PM - " 3'" • •Document # 800=1890-001 Rev A - 5 , - . Date last exported: November 13, 2015 2:23 PM .7 •' -v. .7 ° - •' - F,.' �r - .r�','. c _,•�•"�.`,-,` r r '* f� • th , . T • a' .. • C.L. •, it ` y t Pay a } Solar inverters Additional highlights: - RS-485 communication interface ` (for connection to laptop or data `ABB string inverterslogger) _ r " • '}, I - Integrated Arc Fault Detection and - ,A, �• 'Interruption (-A Version). .' _ � a�.,.,, t��• f , e - • 2r. , i, ),Jj ~ ''` a i�+ �. R ' ,...r-- ' Technical data and types _ Type code PVI-3.0-OUTD-US PVI-3.6-OUTD-US PVI-18-OUTD-US PVI-4.2-OUTD-US r , ' An_n. specifications ' ^! 3300 i .+.•s'l �`_�'-►!AR + Nominal output power 3000W 3600W 3800W 4200W ........................................................... 000 3300' i 3300' :3600 € 4000' 40............................................................ 0' € 3 00 4200' 1 4200' 1 4200 t 46001 i 4600' - q. r Maximum output power wattage W W W W W W w w w W w w _ - (�:..............................................................................................................._......... 4 - • a Rated rid AC voltage 208V 240V 277V 208V 240V 277V 208V 240V 277V 208V 1 240V 277V 9 }y s ( )Input side (DC) . 'l '' , Number of independent MPPT channels 2 2 ? 2 i" -� ..............:.... ........... ....... bro _ Maximum usable power for each channel......... 2000W..................................... 3000W........... 3000W...................................3000W................ ............. ................. _ Absolute. maximum volts.9e..(Vrn)............................i......................................... .... .......................... .....600V.................................................................................. ..... Start u volts a start 200V (adj. 120-35OV) _ P..............g.....(�..........1...... .......... ....... .......... .......... ......... .... r .:.a. , ............ .. .. .. .. .. w' Sr Full ower MPPT volts a ran a 160-530V 120-530V 140-530V 140-530V s....P........................................g...........g......................................i...........................................................i................................... .....................................................I................... l ..Operating MPPT voltage range...-...-...=.. 0.7 x Vstart - SSOV >=90V) Maximum current (Id"cmax) fo'r bolh M'PP7 in .......................................� ....... � (............................ .....................................................k �u 20A: 32A 32A 32A l - p Parallel......... � r �.. ` - • . Maximum usable current..._erchannel.... ......................10A...... .........................16A.................... ......................16A..... ..............................16A................ P............:...:.............................°.............................................................................................................................................................. hanin Im short circuit current limit per 12,5A 20.OA ' 20.OA 20.OA t ` r ....... i - +• - ,'' Number of wire landin terminals per channel l 2 airs g.................................. - +� ; •' r «„ .,e..,.. ' ` q] Array wiring termination ... Terminal block pressure clamp, AWG1 O-AWG4 • li, I Output side (AC) ! 10Tt SpB —i 10/ Split- i 10/ ci 10 i S 3d- ' 10 0T-Sp t- i 10/ r Grid connection type ` 2W 0/3W ' 2W 2W 0/3W i.. 2W W W • - .. W W W , 183 - 211 - € 244- € 183_......21.1_........244_........183_......_0.2.1.1 ........244_........183_...._0.2..1.1_...1..._244_... 4 J Adjustable voltage range (Vmin Vmax) M , -...-...........................-...._228V._i.._264V i 304V i 228V :' 264V i 304V 228V 264V 304V € 228V 264V 304V - - .. .a . ...... d.f ... ...... _ . ' t Gr d frequency..............................................._........ ......................................................................................................... 60Hz ... r ° - '+r ' �: ? Adlustable gr d fre uency range_ __ 57 60.SHz �-r.^ys:y... E r , • - ; Maximum current(I..—)14.5 ,....14.5..........12.0......17.2...:.... 16.0..........16.0.......16.0.....'.16.0......:...16.0..,.....20.0....:...20.0.........20.0 ............ ............................. ........ .% "s....i.....Aarns ...i.....Aa ns...:... ............Aa"s ....._Awns....:....!4ains....i.....%1a"s ........ rns ..........+s .......... .................. - T'................................ ......... ....i.... " !, Power factor > 0.995 r ,4 M - I...............................:.................................................................................................................................................... .................................................................................................................._ - Ass An W3 Total harmonic distortion at rated..P..ower........._....i....................................................._.:-_..................................................._�_?°.E...................................:............................................................................_ r , This family of single'-phase string The high-speed MPPT offers real- Highlights: Grid wiring termination type Terminal block, Pressure clamp, AWG 10-AWG4 " inverters complements the typical time power tracking and improved - Single phase and split phase output tlnput protection devices i - Y f Reverse polarity protection Yes number of rooftop solar panels energy harvestin rid connection. -"---' ---- ' ............................................... .................. . P P 9Y 9• 9 Over-vol...... e..P..rotection?Y.P..e.........................................i....:...... Varistor,..2.for each channel........................................................>.............................._ enabling home-owners to get the most The flat efficiency curve ensures high - Wide input range for increased r,}•. PV array ground fault detection Pre start-up Riso and Dynamic GFDI (requires floating arrays) „.•' efficient energy harvesting for the size efficiency at all output levels allowing stringing flexibility. ioutput protection devices - l a .Anti-islanding rotection Meets UL 1741/IEEE7547 requirements oftheproperty. a consistent and stable performance - The high speed and precise MPPT P.........................................................................:......................................................................................................................................................................................................................................... . P 9 P p Over-volts e, rotection t o Vanstor, 2,- L: / L, - G v g.....P.......................:XP..............................................:...................:...........:.......:......................................:...................(..................,.....1............:...................:...................:...................:..:............... Maximum AC OCPD Rating 15q,,, 20A, G OA„ [ 20Ap,� i 20Pe, i 20Pe, : 25A„ across the entire input voltage and algorithm offers real time power z This inverter offers a'dual input output power range. - tracking and improved energy )Efficiency 1 rt • ,; .Maximum efficient ._-... 96.9% 97% .... - 97% 97% ry.............................Y.......................................................,.......................................................:.................................................................................................................................................. ........... aw section that processes two strings The transformerless operation groes the harvesting. CEC efficiency 96% 4+ with independent Multiple Power Point,,' highest efficiency of up to 97.0%. - Outdoor NEMA 4X rated enclosure [Operating performance Tracking (MPPT).. +I The wide input voltage range makes for unrestricted use under any Night time consumption < 0.6W_, This is especially. useful for rooftop the, inverter suitable to low power environmental conditions. Stand-by consumption _ < 8W.- 19 W,,, ' c iCommunication r, 4 t' f installations with two different installations with reduced string size. - Integrated DC disconnect switch user-interface 16 characters x 2 lines LCD dis Ia - _ P....y.........................................................................._ • . :, '�-" -'t+ orientations from. two sub arrays This rugged outdoor inverter has been in compliance with international Remote monitoring (1xRS485 incl.) vSN7oo Da(aLogger (Environmental - - . •rs > - .. L r t Standards Version). . r° �r oriented in different directions. (For designed to be a completely sealed S ds (S e ) f .Ambient, air, operating. temperature range -13°F to +140°F with. dentin above 122°F (50°C ' example: East and =West) unit able to withstand the harshest • .Ambient air. storage_temperature range......................................._,_,,,,...,,,._,.._._._ 40°F to +176 F -40°C to +80°b s• ti ' f .. .r . - , Relative humidity - ..................0100% RH,cdndensin... .......... ..........................- tits R •!� c �Sti •,'? The dual input sections-with . �envvonmental conditions.........................................:............ ......... ............ ....._9 .. ............ ........... .......... t - 'ore ".F- Fr- �`'+, t, :Acoustic noiseemis...... vel <50db A ®1m .� independent MPPT enable a more #........................,........,.................................................... rr.�r.......................................db (..).................... ................ - y '^] _Maximum operating altdutde w.! o;M.de...... 9...:................................................_ r.............'..................._-.6560 fl-(2000 m t .... J DD DQ ..... ................)................................................................... _ �i .... optimal energy harvesting condition. 7 1. capability enabled at nominal n_c,voitage entl with Sufficient DC power evaiiebie. .„ Power and p�oduotivfty . nnl v' f for a better world'" Vl;' 01) , 2 ABB Solar Invertef, . �iS+Rf3s....�,,,,�.• '`- - °+� rs I Product Flyer for PVI-3.0/3.6/3.8/4.2-TL-0UTD r R ��,•-:r.,.yt z`_.,r +'" - - t HIGH PERFORMANCE SOLAR PANELS amu' R ECPEAK ENELRGY 7 REC Peak Energy Z -Link Series sola panels are the perfect choice for building solar systems that combine long lasting _ product quality with reliable power output. REC combines,ligh quality design and manufacturing `standards to produce high- performance solar panels with uncompromising quality. QGpMPgT'9 MP 6 . MORE POWER COMPATIBLE WITH PER FT' ZEP GROOVE FRAME 'SPF USIMPORT - EASYTO DUTY FREE INSTALL O • t ENERGIZING LIFE • -�• _REC P E A K ENERGY` Z -LINK SERIES - r - ...,. 65.56 ±9.IY 3902 47.24 r 047 U 'ia .i r - V All measurements in inches Nominal Power -PM„ (Wp) 260 Watt Class Sorting-(Wp) -1-5 NominalPowerVo[tag e -V. (V) .. .... ................ - 303 ............. ... Nominal Power Current - IM„ (A) 8.50 Open Circuit Voltage -VocIV) P 37.8 Short Circuit Current • Isc (A) 9.01 Panel Efficiency(%) 15.8 The electrical characteristics are within ./-10%of the indicated values of l55�� Va and P,,,, at standard Test conditions (5TC). Values at standard test conditions STC (airmass AM I.S. irradiance I000 W/m', cell temperature 77'F (25-C)). At low irradiance of 200 W/m' (AM 1.5 & cell temperature 77-F (25'C)) at least 97% of the STC panel efficiency will be achieved. Nominal Power- Pw„ (Wp) 197 .........................._.................... .... - _ Nominal Power Voltage -VM„ (V) 29.0 Nominal Power Current -IM„ (A) 6.81 Open Circuit Voltage - Vo, IV) 35.7 Sho_rt Circuit Current- Isc (A) 7.24 ............................... .. ........._ .......... _..... Nominal operating cell temperature NOCT (800 W/m', AM 1.5, windspeed I m/s, ambient temperature 6trF (20°C). 10 year product warranty.. c ill ug 25 year linear power output warranty USTto (max, degression in performance of 0.7%p.a.). UL 1703, Fire rating: Type 1, Class C c EFFICIENCY �Q YEAR PRODUCT WARRANTY YEAR LINEAR POWER lQ] OUTPUT WARRANTY �VTYri�R�F US IMPORT DUTY FREE Nominal Operating Cell Temperature(NOCT) 45.7"C(s21C) Temperature CoefhcientofPr.,,, -0.40%/°C -Temperature Coefficien I of Voc -0.27°x6/'C Temperature Coefficient of1.,0.024%/'C - 1 GENERAL t, Cell Type: 60 REC PE mul ti -crystalline 3 strings of 20 cells with bypass diodes Glass: 0.125 in solarglass with anti -reflection 0 surface treatment Back Sheet: Double layer highly resistant polyester Frame: Anodized aluminum (black) Zep Groove compatible Junction Box: IP67rated.,- 0.156 in (12 AWG) solar cable, 2 x 47.24 in Connectors: 114 Amphenol Origin: Made in Singapore MAXIMUM RATINGS Operational Temperature: -40...185°F(-40...+85°0 w Maximum System Voltage: 1000 V UL Design Load: 50lbs/ft' (2400 Pa) long side 30lbs/ft' (1436 Pa) short side Max Series Fuse Rating: ISA Max Reverse Current: 15 A MECHANICAL DATA Dimensions: 65.55 x39.02 xL57 in(1665 x 991 x 40 mm) a Area: 17.75 ft2(1.65 m2) Weight: 43 lbs (19.5 kg) 4 Notel All given specifications are subject to change c without notice at anytime. a REC is a leading global provider of solar energy solutions. With more than 1S years of experience, we offer sustainable, high performing �� ' products, services and investments for the solar industry. Together with our partners, we create. value by providing solutions that betterREC meet the world's growing energy needs. REC is headquartered in Norway and listed on the Oslo Stock Exchange (ticker: RECSOL). Our 1,600 , employees worldwide generated revenues of USD 647 million in 2013.' www.recgroup.com _ ♦ �jj .T a �-',SolarCity ®pSolar Next-LeveLPV'MountingTechnology DWV Debris Guard . for composition shingle roofs s. PHOTOVOLTAIC MODU DWV DEBRIS GUARD - • COMP ROOF MOUNT .. COMP ROOF � . ` O • 01 s DWV-Debris Guard ConstrUction•Detail Debris Guard, close up cDnraT,e� Prevent blockages and keep vents open with the DWV Debris Guard. / Protects against: ~FA m Leaves Rain doMraT Pine needles Insects • Snow J Birds DWV Debris Guard is made of rugged 26 -gauge galvanized steel. iP• This document does not create any express warranty by Zep Solar or about its products or services. Zep'Solar's sole warranty is contained in the written product warranty for each product. The end-user documentation shipped with Zep Solaes products constitutes the sole specifications referred to in the product warranty. The customer is solely responsible for verifying the suitability of ZepSolar's products for each use. Specifications are subject to change without notice. Patents and Apps: zspals.00m.�- A •"''�. Document # 800-1677-001, Rev A _ Date last exported: April 3, 2015 4:04 PM