Loading...
HomeMy WebLinkAboutB16-0984 000-000-000MSP fel 180° �,� Trail Dr n 1. THIS SYSTEM IS GRID-INTERTIED VIA (40) UL -LISTED POWER CONDITIONING V) V) INVERTERS - ENPHASE M250-60-2LL-S22 (240 VAC) W/INTEGRATED GROUND 2. THIS SYSTEM HAS NO UPS, NO BATTERIES 3. THIS IS A ROOF -MOUNTED SYSTEM, ADDING 2.81 LB/sq FT. ROOF IS (1) LAYER COMP SHINGLE ROOFING (ROOF SLOPE IS 4:12) 04. ROOF JOISTS ARE 2X4" ENGINEERED TRUSSES AT 24" O.C. SPACING 5. LAG SCREWS ARE 5/16" x 4" AT 72" O.C. MAX, W/3" INTO FRAMING. Z6. LABELING DETAIL ON ATTACHED SHEET 7. BUILDING IS (1) STORIES. Roof Plan & Truss Section Drawn By: David W Client: Lisa & Erwin Williams 1495 Lazy Trail Dr, Chico CA 95926 Date: 05/05/2016 ' Ph. - Email - Scale - NTS 11.20kW DC Photovoltaic System (40 SolarWorld SW280M9) Rev. Date Description (16) Enphase M250-60-2LL-S22 240(VAC) micro -inverters Pmax (Each): 250 watts, Imax (Each) = 1.OA, 240(VAC) (16) Enphase M250-60-2LL-S22 240(VAC) micro -inverters Pmax (Each): 250 watts, Imax (Each) = 1.OA, 240(VAC) (40 Total) Solarworld SW280MB V)1. THE PV SOURCE CIRCUIT IS NEGATIVELY GROUNDED 2. WIRE AND SIZES ARE AS INDICATED OR LARGER. UJ 3. ALL EQUIPMENT IS BONDED BY ENPHASE & UNIRAC INTERGRATED GROUNDING 4. THE ELECTRIC SERVICE PANEL WILL BE CLEARLY LABELED AS FOLLOWS: O "THIS PANEL IS FED BY THREE SOURCES: SOLAR PHOTOVOLTAIC SYSTEM ON PREMISES" "WARNING: ELECTRIC.SHOCK HAZARD. DO NOT TOUCH zTERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. " Single Line Drawing 'Drawn By: David W Client : Lisa & Erwin Williams 1495 Lazy Trail Dr, Chico CA 95926 r Date: 05/05/2016 Ph. - t Email - Scale - NTS 11.20kW DC Photovoltaic System (40 SolarWodd SW280MB) "-Rev 240V electric service from ; utility 200A Utility - Meter Main - Date AC CALCULATIONS Circuit 1 - Continuous Current = Imax x 1.25 = 16.0 A x 1.25 = 20.0 A Derate Ampacity = 90deg Rating of Conductor (T-310,16) . x 90deg Temp Correction Factor (T-310.16) h x Conduit Fill Factor (T-310.15(B)(2)(a) = 40 A x .87 x 1.00 = 34.8 A So that, Derate Ampacity > Continuous Current = 34.8 A > 20.0 >> OK And, Derate Ampacity > Overcurrent Device Rating = 34.8 A > 20.0 A >> OK Circuit 2 Continuous Current = Imax x 1.25 = 16.0 A x 1.25 = 20.0 A Derate Ampacity = 90deg Rating of Conductor (T-310.16) x 90deg Temp Correction Factor (T-310.16) h x Conduit Fill Factor (T-310.15(B)(2)(a) = 40 A x .87 x 1.00 = 34.8 A So that, Derate Ampacity > Continuous Current = 34.8 A > 20.0 >> OK And, Derate Ampacity > Overcurrent Device Rating = 34.8 A > 20.0 A >> OK Circuit 3 Continuous Current = Imax x 1.25 = 8.0 A x 1.25 = 10.0 A Derate Ampacity = 90deg Rating of Conductor (T-310.16) x 90deg Temp Correction Factor (T-310.16) h x Conduit Fill Factor (T-310.15(B)(2)(a) ' = 40 A x .87 x 1.00 = 34.8 A So that, Derate Ampacity > Continuous Current = 34.8 A >, 10.0 >> OK And, Derate Ampacity > Overcurrent Device Rating = 34.8 A > 15.0 A >> OK CIRCUIT 1 - SOLAR CIRCUIT MAXIMUM CURRENT: 20.0 A SOLAR CIRCUIT OPERATING VOLTAGE: 240V CIRCUIT 2 - SOLAR CIRCUIT MAXIMUM CURRENT: 20.0 A SOLAR CIRCUIT OPERATING VOLTAGE: 240V CIRCUIT 3 - SOLAR CIRCUIT MAXIMUM CURRENT: 10.0 A SOLAR CIRCUIT OPERATING VOLTAGE: 240V NEC 705.12 120% Rule Calclulations Center Fed Panelboard Adjustment - N/A Supply Breakers + 20% <_ Busbar Rating Busbar Rating = 200A 175A Main 20A Solar + 20A Solar + 15A 175A + 55A <_ 200A * 1.20 Description 0 • • Y - • -,.. ;+� )ter y V`i ` f`t • +,. , - Enphase® Microinverters f .,Enphaseo M250 C9 V _ s e • + .. k. . fir• The Enphase® M250 Microinverter delivers increased energy -harvest and reduces design and' y installation complexity with its all -AC approach. With the M250, the DC circuit. is isolated and insulated, from ground, so no Ground Electrode Conductor -(GEC) is required for the microinverter, This ' further simplifies installation, enhances safety, -and saves on labor and materials costs. The Enphase M250 integrates seamlessly with the Engage® Cable, the Envoy® Communications Gatewa' im,-and Enlighten®, Enphase's monitoring and analysis software. PRODUCTIVE SIMPLE RELIABLE - - Optimized for higher -power - No GEC needed for microinverter -4th-generation product modules - No DC design,or string calculation - More than 1. million hours of testing t� • _, Maxi mizes`energy'production required + ` j and millions of units shipped i. - Min imizes:impact of shading, Easy installation with Engag '� -Industry-leading warranty, up to 25 dust, and debris ' Cable �' • A. years +;Y enphase [e] E N E R 'G Y . a �� c Us me ted grow nd '► x. , � � rsR i The DC circuit meets the requirements for'ungrounded'PV�arrays'in' y - NEC 690.35.,Equlpment ground is provided in the Engage Cable:' No u.a w r additional GEC or ground is required. Ground fault protectioh(GFP) is integrated into the microinverter. )nitoring v Enlighten Manager and MvEnliahten,monitorina options Compliance UL1741/IEEE1547, FCC Part 15 Class B, CAN/CSA-C22.2 NO..0-M91, 0.4-04, and 107.1-01 S *Frequency ranges can be extended beyond nominal if required by the utility ; To learn more about EnphaseMiroinverter technology, _ A - . cen _. ..[jEk11 phase e visit enphase.com k JE N E R G Y © 2015 Enphase Energy. All rights reserved. All trademarks or brands in this document are registered by their respective owner. MKT -00070 Rev 1.0 • 1 _ Enphase° M250 Microinverter // DATA ' INPUT DATA (DC) M250=60=2LL-S22, M250-60-2LL-S25 Recommended input power (STC) 210 - 310 W 4 Maximum input DC voltage 48V ' 'Peak power tracking voltage 27 V - 39 V . Operating range 16 V - 48 V Min/Max start voltage : 22 V / 48 V Max DC short circuit current 15 A OUTPUT DATA (AC) • @208 VAC @240 VAC Peak output power, 250 W 250 W Rated (continuous) output power 240'W 240 W Nominal.output current 1.15 A (A rms at nominal duration) 1.0 A (A rms at nominal: duration) „ Nominal voltage/range ,208 V / 183-229 V 240 V / 211-264 V Nominal frequency /range 60.0/57-61 Hz 60.0/57-61 Hz 1 Extended frequency range* 57-62.5 Hz 57-62.5 Hz . 5 .,. PowerNfactor,' M1 ^.} ;� R. , ti' G °Y��F Maximum units per 20 A branch circuit 24 (three phase) ` 16 (single phase) Maximum'output fault current 850 mA rms for 6 cycles 850 mA rms for 6 cycles EFFICIENCY CEC weighted efficiency 96.5% 11 Peak inverter efficiency 96.5%o rrj Static-MPPT efficiency (weighted, reference EN50530) 99.4% .. Night time power consumption 65 mW max MECHANICAL DATA ?Ambienyt temperature range-- -40°C to +65°C ►-- Dimensions (WxHxD) 171 mm x 173 mm x 30 mm`(without mounting bracket) t kWeight 1.6 kg (3.4 lbs) Cooling +`. y - Natural convection - No fans , Enc -77 losure environmental rating Outdoor -NEMA 6 ' .' Connector typeV 4 M250-60-2LL-S22: MC4 ` ' r ' M250-60-2LL-S25: Amphenol H4 - FEATURES tC mpatlbllity Compatible with 60 -cell PV modules Communication Power line me ted grow nd '► x. , � � rsR i The DC circuit meets the requirements for'ungrounded'PV�arrays'in' y - NEC 690.35.,Equlpment ground is provided in the Engage Cable:' No u.a w r additional GEC or ground is required. Ground fault protectioh(GFP) is integrated into the microinverter. )nitoring v Enlighten Manager and MvEnliahten,monitorina options Compliance UL1741/IEEE1547, FCC Part 15 Class B, CAN/CSA-C22.2 NO..0-M91, 0.4-04, and 107.1-01 S *Frequency ranges can be extended beyond nominal if required by the utility ; To learn more about EnphaseMiroinverter technology, _ A - . cen _. ..[jEk11 phase e visit enphase.com k JE N E R G Y © 2015 Enphase Energy. All rights reserved. All trademarks or brands in this document are registered by their respective owner. MKT -00070 Rev 1.0 • 1 _ :! - i s. .r .�. r ' 1 • -. - ` l' r.j t7 ••. - �G•k te4. , P1 u e U °�°¢g�vSW 280 I [-ONO BLACK. 33mm frame M . TUV Porver controlled: • TOVtiheinland Lowest nleasuringtolerance in industry r. , Every ccmponent is tested to meet 3 times IEC requirements y DesignFd to withstand heavy accumullatioris of snow and ice A OSunmoc ule Plus. ` Positive, performance tolerance 25 -year inear performance warranty Y - and 10 -rear product warranty r r� Glass w,th anti ,ref lective coating - , r + _ jo - Worid-class uaIit +• _ , •. l ' • Qualified, IEC 61215 - 9 Y' N } a . " i t Safety tested, IEC 61730 Cc Fully-automated production lines and seamless monitoring of the'process and mate- AVE :Ammunie �esisian ce IEC 627160068-2-68 (V Salt mist corroslon,IEC61701 C us rial ensure the qualitythatthe'company sets as its benchmark for its sites worldwide. r Periodic inspection - Y UL 1703 f • Periodic inspection e SolarWorld Plus -Sorting �. Power controlled , Plus -Sorting guaranteeE highest system efficiency. SolarWorld only delivers modules • ' that have greater than o�r,equal to the nameplate rated power. •l 1 C E Homelnnovation NOBS GREEN CERTIFIED.. 25 -year linear performance gLarantee and extension of product warranty to 10 years SolarWorld guarantees a maximum performance digression of 0.7% p.a. in the course' m�` ' - of 25 years,'a significa'rt added value compared,to the two-phase warranties com w' Mcs; # , 1 �. r- - -f'..� !^- by 20 mon in the industry, alcng with our industry -first 10-yea_r product warranty' 17 'in accordance with the applicable SolarWorldLimitedWarranty at purchase. www.solarworld.com/warranky . I P11 • ' �` MADE IN USA OF US solarworld.com • . , AND IMPORTED PARTS 3 :! - i s. .r .�. r ' 1 • -. - ` l' r.j t7 ••. - �G•k te4. , P1 u e U °�°¢g�vSW 280 I [-ONO BLACK. 33mm frame M . TUV Porver controlled: • TOVtiheinland Lowest nleasuringtolerance in industry r. , Every ccmponent is tested to meet 3 times IEC requirements y DesignFd to withstand heavy accumullatioris of snow and ice A OSunmoc ule Plus. ` Positive, performance tolerance 25 -year inear performance warranty Y - and 10 -rear product warranty r r� Glass w,th anti ,ref lective coating - , r + _ jo - Worid-class uaIit +• _ , •. l ' • Qualified, IEC 61215 - 9 Y' N } a . " i t Safety tested, IEC 61730 Cc Fully-automated production lines and seamless monitoring of the'process and mate- AVE :Ammunie �esisian ce IEC 627160068-2-68 (V Salt mist corroslon,IEC61701 C us rial ensure the qualitythatthe'company sets as its benchmark for its sites worldwide. r Periodic inspection - Y UL 1703 f • Periodic inspection e SolarWorld Plus -Sorting �. Power controlled , Plus -Sorting guaranteeE highest system efficiency. SolarWorld only delivers modules • ' that have greater than o�r,equal to the nameplate rated power. •l 1 C E Homelnnovation NOBS GREEN CERTIFIED.. 25 -year linear performance gLarantee and extension of product warranty to 10 years SolarWorld guarantees a maximum performance digression of 0.7% p.a. in the course' m�` ' - of 25 years,'a significa'rt added value compared,to the two-phase warranties com w' Mcs; # , 1 �. r- - -f'..� !^- by 20 mon in the industry, alcng with our industry -first 10-yea_r product warranty' 17 'in accordance with the applicable SolarWorldLimitedWarranty at purchase. www.solarworld.com/warranky . I P11 • ' �` MADE IN USA OF US solarworld.com • . , AND IMPORTED PARTS r r Sunmodule;//'Plus 4� 4 # . 48 °C Sunmodule;//'Plus Mono crystalline 4 # . 48 °C TC LSC 0.044 %/'C SW 280 MONO BLACK (33mm frame) REALVALUE PERFORMANCE UNDER STANDARD TEST CONDITIONS (STC)' PERFORMANCE AT 800 W/mz, NOCT, AM 1.5 -40°C to 85°C Maximum power _ Pmax 280 Wp Maximum power Pmax 207.2 Wp Open circuit voltage VoC 39.5 V Open circuit voltage Voc 35.8 V Maximum power point voltage VmPP 31.2 V Maximum power point voltage VmPP 28.3 V Short circuit current I5C 9,71 A Short circuit current ISC 7.85 A Maximum power point current Impp 9.07 A Maximum power point current Impp 7.33 A Module efficiency nm 16.7%. Minor reduction in efficiency under partial load conditions at 25°C: at 200 W/m2,100% instructions for the details associated with (+/-2%) of the STC efficiency (1000 W/mz) is achieved. 'STC: 1000 W/m2, 25°C, AM 1.5 Power sorting' 1) Measuring tolerance (Pax)traceable toTUVRheinland: 2%(TUV Power Controlled). COMPONENT MATERIALS I P65 THERMAL CHARACTERISTICS Cells per module 60 Zi! 1.30 (33) Module voltage [V] —37.8(961) —� 4.20 00 (106.65) _ 4x =L- 7.12 00.26 (6.6) - (180.85) o 00.3S(9) o o 0 0 oMi M o o � 0 rn v �o 11.32 (287.50) -r o 00.35 (9) 39.4 (1001) V. All units provided are imperial. SI units provided in parentheses. SolarWorld AG reserves the right to make specification changes without notice. Cell type Mono crystalline NOCT 48 °C TC LSC 0.044 %/'C TC V. -0.31 %/°C TC P.m -0.43 %/°C Operating temperature -40°C to 85°C Maximum system voltageSC11/NEC 1000 V Zi! 1.30 (33) Module voltage [V] —37.8(961) —� 4.20 00 (106.65) _ 4x =L- 7.12 00.26 (6.6) - (180.85) o 00.3S(9) o o 0 0 oMi M o o � 0 rn v �o 11.32 (287.50) -r o 00.35 (9) 39.4 (1001) V. All units provided are imperial. SI units provided in parentheses. SolarWorld AG reserves the right to make specification changes without notice. Cell type Mono crystalline Cell dimensions 6.17 in x 6.17 in (156.75 x 156.75 mm) Front Tempered glass (EN 12150) Frame Black anodized aluminum Weight 39.7 lbs (18.0 kg) SYSTEM INTEGRATION PARAMETERS Maximum system voltageSC11/NEC 1000 V Maximum reverse current 25A Number of bypass diodes 3 Design Loads" Two rail system 113 psf downward 64 psf upward Design Loads* Three rail system 178 psf downward 64 psf upward Design Loads' Edge mounting 178 psf downward 41 psf upward ' Please refer to the Sunmodule installation instructions for the details associated with these load cases. ADDITIONAL DATA Power sorting' -0 W p / +5 W p J -Box I P65 Module leads PV wire per UL4703 with H4 connectors Module type (UL 1703) 1 Glass Low iron tempered with ARC Compatible with both "Top -Down" and "Bottom" mounting methods 4—Grounding Locations: —4 locations along the length of the module in the extended flange. 1.30 (33) t �_7 1.14 (29) SW-01-7112US 12-2014 II mJ , SOLAR STANDARD'SYSTEM COMPONENTS OD - INSTALLATION GUIDE ; PAGE ,. • .� PY Z - - - - - - - - - - - - - - - - - -- {---- -- ------ - - - -,- n -_-! -- - �-- ------------- -:------- -------------------------------� '------J----ter----- .. y •• J• , ti< > ,F , ' - • -' x - ' . , ,- ORAIL: Supports PV modules:'Use: at least two per = •„ . • , ' ,. ; Y �* row of modules. Aluminum extrusion, available in mill, clear anodized, or dark'* nodized. n _ ? • '' - r d �� ``� :. ♦ , «� r ©RAILSPLICE: Non structural splice joins;aLigns,and j �; - ♦ ♦ electrically bonds rail sections into single length of r* ' ►� "� --r •�} rail. Forms either a rigid,o`rsthermal expansion joint, - N 4 inches long, pre -drilled (see page F). Anodized aluminum extrusion available -in clear or dark.. © ( 3 y r • :.�� "' ,�-�•.�♦•"4♦ •"� -per n lice or 2 SCREW:� • TN„ n n int Stainless may♦ -p E gid sspl per;expa sio joint., se steel. Supplied with splice. In.combination with rigidAll s splice, provides rail to rail bond. < OL -FOOT: Use to secure `rails through 'roofing . `' " k I •<< �{ material to building structure. Refer to loading tables-. , or U -Builder for spacing �. , ^ • . ©L-FOOTT BOLT: (3/8"'x,3/4") 'Use one per L -foot ,- }" r ' 's to secure rail to L -foot. Stairiless steel: Supplied: with '�_• .` �,� ,♦`' : - L -foot. In, combination' with. flange nut, provides ' ♦ ♦ . ` . - - '' electrical bond between rail'•and L -foot. ; „ -- y ♦ ♦��y �`. OSERRATED FLANGE NUT ,(3/8"): Use one per r ' ♦ �" ©{ `� L -foot to secure and -bond rail to L -foot. Stainless S a fi t. T r ,., r. . steel. Supplied with L -foot:' ' ° {• r " r OMODULE ENDCLAMP: Provides bond from rail to < F - © _ fi` a L endclamp. Pre-assembled,aluminum clamp available in clear or dark finish. Supplied washers keep clamp ' - ^ µ : • • , 44`. �, and bolt upright for ease of assembly. - . ,}'` • ' ... • V • . _ i . . . 1 t ,' 7• +Ili . I'h . • • 3 x yOMODULE • MIDCLAMP:;•• Pre -assembled clampAl ' ,,Wrenches anal Torque-...'.,� Wrench Size Recommended Torque (ft -lbs) 1/4" Hardware o00 7/16" `10 3/8" Hardware © 9/16" '30 #12 Hardware © 5/16" 10 Torques are not designed for use with wood connectors Lw/Anti-Seize. - provides module to module and module to rail bond. - y Anti!Seie; Stainless steel clamp and T -bolt. Available in `clear. Stainless steel hardware can seize up, a process .. _ z' or dark finish.. , called galling. To significantly reduce its likelihood.,. ' 1. Apply minimal Lubricant to bolts, preferably , � `.OMICROINVERTERMOUNTINGBOLT:Pre-assembled: - - bolt and nut attaches. and bonds microinverter to ' "Anti -Seize commonly found at auto parts stores ; w i 2. Shade hardware prior to installation, and ; f <`rall.,Washer at base keeps' bolt upright for ease of s t 3: Avoid spinning stainless nutonto bolts at high "`' : `assembly. - speed rNOTE - POSITION INDICATOR: T -bolts have a slot in - �s ;' v�the hardware end corresponding to the direction of s "the -T-_Head. ' '� . _ • � , � • .. _. � �-, � •,-fit... ,iM Y - - SOLAR MO.DULE COMPATIBILITY NT ­ INSTALLATION GUIDE ; PAGE-mou ----------------- -------------------------------------------- SIZE -.'ya • • ' . -" . ,_: ° ; _:. -. -,:., - �' ;:: - 'F SIZE._ �' ENDCLAMP' - ♦ _ - "' .. _ a„ D SIZE _' K SIZE # ENDCLAMP, .- ' . SIZE"F ♦ _ • ♦ ,-+^ - Y• • - • _ r. ' •, -• r • . •.. • ' ,W ws F>t'� _ B SIZE •. ' - - , ENDCLAMP ENDCLAMP ENDCLAMP .� _ • . : 'Y'� ess , 4 r Le Th ENDCLAMP - •f �'; Ma { Modu ickri f _ f50mm to 52mm • a' r• ; Module Thickness s • �: .s# • 45mm to 47mm 1.97in to 2.05in , • a Module Thickness : • Module Thickness`-`. G 38mm to 40mm ' 39mm to 41mm ' `'• 1.77in to 1.85in, ' Module Thickness .. .' a Module Thickness ; 33mm to 36mm ; 1.50in to 1.571n • t 1.54in to 1.61in w S m f 30mm to 32mm • 1.30in to 1.42in _ 1.18in to 1.26in • ` • y 3. , •1 , • • � t • T , - • r t� Ah • • / � J,' Y..'i � .f 1 ' - • • . ------------------ ----------------------------- ------ w. p, 4 . - c •y ' , l • - � •/ v •. . . e ♦ t.r d•-..• x -C z. .. • ... \e.1 . � -�`S ,fia'y� C'y: •• ., . a W �Li. ` i - .r a� - / t.-♦ . ., • .. - • . �'��� • ' moi•• Y�', '"- .. \ • , - r ... �} , - F .:- ' '•tis ..+ • .. v .. e t�,.'fi' - w1 ° s��• •K,+ i,{1 a: S.. - .:.. yr .. +. ,. 1 • , +' - ., / •' v d" fi • . � .. �' A .^� .F r + � � y� S i ;a .. a r _ F - ' - r ..rt a _ ^t . - `4 , i., -' - t l ' . , *� yf' / rT: I,• . _ k J _ . 7 . , WN SOLAR'. M SYSTEM LAYOUT ®®S- h INSTALLATION, GUIDE ; PAGE { k — — — — — — — — — — — — — — — — — — — — — — — — — — — — - — — — — — — — — — — — 7 - — — - — — — — — — — _ — _ y — — — — — — — — — — — — _ — — - — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — T 3— --- — — — — — — — — — — — — — PLANNING YOUR SOLARMOUNT INSTALLATIONS ;, LAYING OUT L -FEET FOR TOP CLAMPS. The installation can be laid outwith Trails parallel to the rafters sor perpendicula(-' L -feet, in conjunction with proper flashing equipment and techniques,, can be x s ' to the rafters. Note that SOLARMOUNT rails make excellent straightedges for`,,,' used for attachment through existing roofing material, such as asphalt shingles, doing layouts. a,f '- sheathing or sheet metal to the building structure., - t - � + - .,✓ .r •' ,,• tel. , ..� - .f - ... i.. i r' 7 . u .r r � ,` -3 �i ,f4 A, Center the installation area over the structural members as'much as possible.` Locate and mark the'position of the L -feet lag screw holes within the installation �. area as shown below.'F'ollow manufacturer module guide for rail spacing based - , }. r Leave enough room to safely move' around the array during installation. ' -,on appropriate mounting Locations.," • Some building _codes and fire codes require minimum' clearances around such. installations,and the installer should check local building code requirements for,, -t If multiple rows are to.be installed adjacent to•one another, it is not likely that' ° compliance. - r" each row will be centered above the rafters. Adjust ;as needed; following the .guidelines below as closely as possible. ' The length of the installation•area is equalrto: • the total width of the modules, • plus '/a"inch for each space between modules (for mid- clamp), Tr•• • '� • plus approximately 3 inches (1'/2 inches for each Endclamp)� - Y - r • _ � - .1 .+ �.. �.. 't. - - •rte RAILS MAY BE PLACED PARALLEL OR PERPENDICULAR TO -RAFTERS LAYOUT WITH RAILS PERPENDICULAR TO RAFTERS (RECOMMENDED) I_ TI W J, _T Y Peak (Ridge) ,I01 ._ g-33°rb L max �F—Overhanit 1`l J 1 _ LAW PROFILE MODE 147 WJ I_ TI W J, _T ,- - Peak (Ridge) ,I01 ._ g-33°rb L max �F—Overhanit t _ _ .__ 1 _ LAW PROFILE MODE 147 WJ HIGH,PROFILE MODE - T _ �` 1. ..� �, �l ► 1_ _ Lower Roof Edge .I_—I�y ._I +' Rakers {Building struct re)'�i_�l =�-1 �__.:L�JLL l !'I Note:-Mods-ule must be- ec ntered msy met it call o the -rails(+/ -T2") -,T — - - - _I L� _ _ l_ r I L I I I 1 1 1 1 1 1 1- 1 1 1 1, 1 1 1 '1 1 '1 1 1# f Gutter— I. I I I I I I I f .. g-33°rb L max �F—Overhanit t I �J j• _I_ _ -I I Foo Ra�if1� sspapicnirrig� - r .1�11/211j3�4" T; T _ �` 1. ..� �, �l ► 1_ _ Lower Roof Edge .I_—I�y ._I +' Rakers {Building struct re)'�i_�l Note:-Mods-ule must be- ec ntered msy met it call o the -rails(+/ -T2") 1 I I I I I `,�� � _ .. . , - .:� • .. '" i RRa �,�•�. .. i+_r� t ,Y�''4�- f lL �T,# f..� i r.. ,� � -e L r •1 . y 0 F,IRE.*CO SM S LAR D.E. COMP.LIAN.CE NOTES' ` , '.`J • - - ,...•` • ., INSTALLATIO.R.GUIDE PAGE ----- ------------------------------ ------------------------- - -----------------------------------------------7- SYSTEM LEVEL FIRE CLASSIFICATION �:• . The system -fire class rating requires installation in the manner specified in the SOLARMOUNT Installation Guide. SOLARMOUNT has been 'classified to the `system #� level fire portion of UL 1703. This UL •1703 classification has been incorporated into our UL 2703 product certification. SOLARMOUNT has achieved' Class A, B & C = sstem level erformance for stee slo ed roofs when used in con unction with.tyoe,l, type 2, type 3 and type. 10 module constructions. Class A; B & C s stem level fire performance is inherent in the SOLARMOUNT design, and no additional mitigation measures are required. The fire classification rating is only,v"alid on roof pitches t ' greater than 2:12 (slopes >,2 inches per foot, -or 9.5 degrees). There is no required minimum or maximum height limitation above the roof deck to maintain the Class .Y• . `'� ' . ,' A, B & C fire rating for SOL.ARMOUNT. 3, - � . ?-. '1' w. . �.:. yam- c• n, Module Type System Level Fire Rating Rail Direction, , .• Module Orientation '' Mitigation Required Type 1, Type 2, Type 3'& Type 10 Class A, CLass B & East-West ""` Landscape OR Portrait None Required":2" , . s ClasC . - North-South Landscape,OR.Portrait None Required:_ `._�.• . � �� l i � - � + - �-' .. - • • �� �Y�r. •\, y 7 , • r - . •-J. Y C 5„ • J I I �fx +1 ! - .. � ..,j • '3 v + 7 s Y � S •i' f ` ! r-� �.•,�. ' - '� •. ' '! -s ' .P r:'.�r ° r !, ( ,� • •'' � r' .. ♦ fr y • - r, - '/ e r Jw ,� , I ` � � � � •' __ ' •• .t ^F 1 � y ' ' f ;`�-y ._ ` a w • . r. � • `iI S .; •, � � ^Y` ' - � 3 t .ti''• - ` r • { • � X11' 1 � w . . - ''��f .. . '- -"� - r ]''Y .r y ; t y r ,, Y • - Y' a a J d••rFt'• ,' Y.... , •i V - ` , ".� '°3 �' •' � " . � r _ , + -. '• , � ` fir. = K � Ar' '}! ♦ , J MM � `9 ` a� - h ' -` - r. � � � • S � � - i � r � i, � �! � ' � Y �, � .• ~t ' .• � i . , .. ' '- r y - . � r J S' .S �1•.;'?.+ / M1 ' .. n � � y .. ... - � 1 � _ ✓�/ 7.. , �i ll. T �'V ' " :-.k.s. • .. •' • r�• _ ' •.' - r> - • , .. J .. N ,-. - cN 5 l 3 > - �� /a. � w � i a � - - -- F . _ o°ooS'M SOLAR ROOF ATTACHMENT-& L FEET ;CEJ 00 MOUNT INSTALLATION GUIDE PAGE --------------------------------------------------------------------------------------------------------- --------- nipp- IWA - ".•�e7.rc !�'1ytC11 _7W+ T _ _ ^""•;'f T ' . 4 Zw- 1' f� `��-,.:'•,�,� •r..tr •; "4 �• : - — - - - '!. _ .::'4 "��,T` �J`�i �'��.ri f"' `�' "5�,�' `'i► =moi - - � 17 `: �%� } ./r .,��`j •,►.+}�",� � . � _3 .-, _ yet ,,.L�, Y • .,mow►' f �-r... .. , _ � r ✓ ''' �'-�ri� yam' G M 6 _ ',"-. _ � ���� e. - .. r r � ROOF PREPARATION: Layout and DRILL PILOT HOLES: Center the roof FLAT FLASHING INSTALLATION: Insert INSTALL LAG BOLTS & L -FOOT: install flashing at rafter . locations attachment over the rafter and drill a the Flat Flashing so the top part is Insert the Lag bolt through the L -Foot determined. per Design and pilot holes) for the lag bolt(s). under the next row of shingles and the in the order shown in the illustration. Engineering Guide. hole lines up with the pilot hole. Verify proper` orientation before NOTE: Determine lag bolt size and embedment depth. a *; tightening lag bolts. ` ` w Quick Tip: Pre -drill the pilot hole through the flat ; See Unirac ;Flat Flashing Manual for ' Additional DetaiLs. F flashing'lag bolt location for easier installation. - - 2 PIECE ALUMINUM STANDOFF WITH FLASHING & L -FOOT: TOP MOUNT TILE HOOK & L -FOOT: • If necessary cut an opening in the roofing material over a rafter to accommodate the 0 Remove or slide up the.roof tile, position the roof hook above the roof rafter flashing riser. 0 Place Tile Hook in the middle.of the underlying interlocking tile's valley. Drill 3/16 • Install the standoff, ensuring that both lag bolts are screwed into the rafter. - inch pilot holes through the underlayment into the center of the rafters. Securely • Insert the flashing under the shingle above and over the shaft of the standoff. fasten each the hook to the rafters with two 5/16" x 31/2" lag screws. Slide down or (No-Calklm collar does not require sealing of the flashing and standoff shaft) re-insert the tile. r • Add L -Foot to top with bolt that secures the EPDM washer to the top of the standoff. ` Attach L Foot to the roof hook. See Standoffs & Flashings Installation Manual 907.2 for Additional Details. See Tile Hook Universal Mount Installation Manual for Additional Information. EEO SOLAR SPLICE & THERMAL BREAK I E MOU1__S_M ------------------------------------------------------------------------------------------------------------------- NT Al Aex- r r v ,te � . �� •+'? •''� .O . , � mow' � �L"�4t�+' r - a�V` •� � '.''' � " � .- ,deer �b 11.0 SPLICE INSTALLATION (IF REQUIRED PER SYSTEM DESIGN) If your installation uses SOLARMOUNT splice bars, attach the rails together before mounting to the L -feet /footings. Use splice bars only with flush installations or those that use low -profile tilt legs. A rail should always be supported by more than one footing on both sides of the splice. There should be a gap between rails, up to 3/16" at the splice connections. T -bolts should not be placed less than a distance of 1" from the end of the rail regardless of a splice. TORQUE VALUE (See Note on PG. A) Hex head socket size,5/16"- Do not exceed 10 ft -lbs. Do not use Anti -Seize. Max length of spliced rail is 40 ft. An expansion joint is required > 40 ft. I F EXPANSION JOINT USED AS THERMAL BREAK Expansion joints prevent buckling of rails due to thermal expansion. Splice bars may be used for thermal expansion joints. To create a thermal expansion joint, slide the splice bar into the footing slots of both rail lengths. Leave approxi- mately '/z" between the rail segments. Secure the splice bar with two screws on one side only. Footings (such as L -feet or standoffs) should be secured normally on both sides of the splice. No PV module or mounting hardware component should straddle the expansion joint. Modules must clearly end before the joint with mounting hardware (top mount Endclamps) terminating on that rail.T-bolts should not be placed less than a distance of 1" from the end of the rail regard- less of a splice. The next set of modules would then start after the splice with mounting hardware beginning on the next rail. Athermal break is required every 40 feet of continuously connected rail. For additional concerns on thermal breaks in your specific project, please consult a licensed structural engineer. Runs of rail less than 40 feet in length, with more than two pairs spliced together, are an acceptable installation for the SOLARMOUNT systems. Bonding connection for splice used as a thermal break. Option shown uses two Ilsco lugs -(Model No. GBL-4DBT P/N GBL-4DBT - see product data sheet for more details) and solid copper wire. o c) 0 SM SOLAR ATTACH RAIL.TO LwFEET ❑ 00 MOUNT INSTALLATION GUIDE I PAGE -------------------------------------------------------------------------------------------------------------------------------------- PLACE T BOLT INTO RAIL: Insert 3/8" T -bolt into rail at L -foot locations. Mrr4 SECURE T BOLT: Apply Anti -Seize to bolt. Rotate T -bolt into position. •'i��y .l ^'^l� a � y� }!' a.. %' 's.r. �„[}.ry �'� ♦ '°ice' '. "� ��;�.a!,, f4.. �.�' y r� •�• a0. '�• d✓ y �f� r '�� :•, # .'� s�� �'Y � .ar9 �.` ^VF7 } i ,^� .�" F.. .� Q ]• .+.~.1r ri ,•ca r _y Y� Y k. ♦ ` ria n rys Ys�''rM1 x '.' —e �'"�' Y r ; �ej ''' ` ..- t r � }�Y r♦ ,r� ; Yy } �l yy s... , .is� y+*�+h s � n.� +. «11•,.. ' ,, � �J'F 31 f._ r , �N ' �� -.n�� K:-' ♦. CONNECT RAIL TO L -FOOT: Raise rail to upright position and attach to L -feet to T -bolt with 3/8" Serrated Flange Nut. Use either slot to obtain desired height and alignment. ALIGN POSITION INDICATOR: Hand tighten nut until rail alignment is complete. Verify that position indica- tor on bolt is vertical (perpendicular to ra i l) TORQUE VALUE (See Note on PG. A) 3/8" nut to 30 ft -lbs ALIGN RAILS: Align one pair of rail ends to the edge of the installation area. The opposite pair of rail ends will overhang installation area. Do not Trim them off until the instal- lation is complete. If the rails are perpendicular to the rafters, either end of the rails can be aligned, but the first module must be installed at the aligned end. If the rails are parallel to the rafters, the aligned end of the rails must face the Lower edge of the roof. Securely tighten all hardware after alignment is complete. Mount modules to the rails as soon as possible. Large temperature changes may bow the rails within a few hours if module placement is delayed. ♦ '°ice' '. "� ��;�.a!,, f4.. �.�' y r� m 1Jr ; tiny A •i '1 i i CONNECT RAIL TO L -FOOT: Raise rail to upright position and attach to L -feet to T -bolt with 3/8" Serrated Flange Nut. Use either slot to obtain desired height and alignment. ALIGN POSITION INDICATOR: Hand tighten nut until rail alignment is complete. Verify that position indica- tor on bolt is vertical (perpendicular to ra i l) TORQUE VALUE (See Note on PG. A) 3/8" nut to 30 ft -lbs ALIGN RAILS: Align one pair of rail ends to the edge of the installation area. The opposite pair of rail ends will overhang installation area. Do not Trim them off until the instal- lation is complete. If the rails are perpendicular to the rafters, either end of the rails can be aligned, but the first module must be installed at the aligned end. If the rails are parallel to the rafters, the aligned end of the rails must face the Lower edge of the roof. Securely tighten all hardware after alignment is complete. Mount modules to the rails as soon as possible. Large temperature changes may bow the rails within a few hours if module placement is delayed. SM S MOUNTOLAR MICROINVERTER MOUNTING � D 0001 MOUNTINSTALLATION6UIUE;PAGE INSTALL MICROINVERTER MOUNT INSTALL MICROINVERTER: Install '' INSTALL MICROINVERTER_ : • - ' ; ' �. ALIGN. POSITION INDICATOR: Verify r �' T BOLT: Apply Anti -Seize and install microinverter on to"rail. Engage with �' ,a that position, ;,indicator on bolt is '' •s TORQUE VALUE (See Nate on PG A)-- !' pre-assembled'/4" dia. bonding T -bolts bolt. ., ' ' s -1/4'" 10,ft lbs w/Anti-Seize perpendicular'to rail - nut�to . - into top' 1/4" rail slot at microinverter - ` �_ • - Locations. Rotate bolts into position. . _ • - .. • .. a w .. i " •' i J r '.ti" - ' tl r�.rye n •Y•r1.�. 1 F . d _ - — * r Ir � 4 • 4 r « , y . ( - ' c, YAP . ♦• t (f " .. .. - •msµ F �•• Y y{��..s.� � t- . • •_S ..t _ r .. r .., A'y - _ . • ' .Xr ti.�t d rt •"•f t , All Ar _ r 0LJ i SOLAR 00 .MOUNTrINSTALLATION GUIDE � PAGE SM EOUIPMENT GROUNDING THROUGH ENPHASE MICROINVERTERS The inphase M215 and M250 microinverters have ' integrated grounding capabilities built in.' In this case' jhe DC circuit is isolated from the AC circuit, an , the AC equipment grounding conductor (EGC) is built into the Enphase Engage integrated grounding'(IG) cabling. {: y n .� In order to ground'the SOLARMOUNT racking systemthrough the Enphase ._ A microinverter and Engage cable assembly, there must be a minimum of three r e PV modules connected. to the same trunk cable within a continuous row. '` t •fix" . /. a Continuous row is defined as a•grouping of modules installed and bonded per the requirements of_ "this• installation guide sharing the same two rails. The microinverters are bonded to the SOLARMOUNT rail via the mounting hardware. h he Enphase Engage cablin _ i " • = .�� _ .. Complete equipment grounding is achieved through t pg with integrated grounding.(IG). No additional EGC grounding cables are required, . - ��R as all fault current is carried -to ground through the Engage cable. ice. %�.�� � p�-• { ,; -. ,-. - � - S - SOLARMOUNT INTEGRATED BONDING ADVANTAGE. LOSE .ALL THE COPPER& LUGS, 7f ' - - • - ' •'trey: - n ^ `�` h..+i-• n a - - � - - ' - °OS���� ��111 a`�"'�"`�"°°"°'"s""'SPLICE �EMICROINVERIFpFpI &THERMAL BREAK �MOUNT ���� IMSTALLATIOPd GUIDE � PA6E --------------------- J ,CONTINUOUS RAIL & ELECTRICAL BONDING SPLICE Enphase Microinverter (MI) Requirements (Model No. M215 & M250) 3 Microinverters sharing same trunk cable & rails -EXPANSIONfJOINT:W/GROUNDING LUGS '& COPPER JUMPER 1 Enphase Microinverter (MI) Requirements (Model No. M215 & M250) 3 or more Microinverters sharing same trunk cable &•-rails , MINIMUM LAYOUT REQUIREMENTS_ ,: J. 3 or more microinverters sharing _ same trunk cable & rails i I _, I— I RAIL SPLICE THERMAL BREAK _L_T_I r I I I I ( + I ( I 1 I I EXPANSION JOINT W/O ELECTRICAL BONDING CONNECTION Enphase Microinverter (MI) Requirements (Model No. M215 & M250) Mln. 3 Microinverters on each side of thermal break MINIMUM LAYOUT REQUIREMENTS MINIMUMILAYOUT REQEQ EMENTS__ _. l: Min. 3 microinverters sharing same trunk cable &rails t I on each side of thermal break I I _ RAIL SPLICE RAIL SPLICE. I I I •.1 I L__ i Vii^ L Min. 3 microinverters sharing same trunk cable & rails I -I s NOT Less than 3=thermaL on each side ok ACCEPTABLE I- -EXPANSIONfJOINT:W/GROUNDING LUGS '& COPPER JUMPER 1 Enphase Microinverter (MI) Requirements (Model No. M215 & M250) 3 or more Microinverters sharing same trunk cable &•-rails , MINIMUM LAYOUT REQUIREMENTS_ ,: J. 3 or more microinverters sharing _ same trunk cable & rails i I _, I— I RAIL SPLICE THERMAL BREAK _L_T_I r I I I I ( + I ( I 1 I I EXPANSION JOINT W/O ELECTRICAL BONDING CONNECTION Enphase Microinverter (MI) Requirements (Model No. M215 & M250) Mln. 3 Microinverters on each side of thermal break ELECTRICAL' BONDING SPLICE EXPANSION JOINT USED AS THERMAL BREAK W/ '• ;' 'EXPANSION JOINT USED AS THERMAL BREAK W/0 ` GROUNDING LUGS & COPPER JUMPER ELECTRICAL BONDING CONNECTION 21 j ^ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ^� 7e - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - NOTE: THE ABOVE IMAGES ARE SAMPLE CONFIGURATIONS TO ILLUSTRATE THE REO_UIREMENTS FOR SM SYSTEM GROUNDING THROUGH ENPHASE MICROINVERTERS DESCRIBED ON PAGE 1-2 MINIMUM LAYOUT REQUIREMENTS l: T, Min. 3 microinverters on each side of thermal break RAIL SPLICE 1 THERMAL BREAK s NOT Less than 3=thermaL on each side ok ACCEPTABLE CE ELECTRICAL' BONDING SPLICE EXPANSION JOINT USED AS THERMAL BREAK W/ '• ;' 'EXPANSION JOINT USED AS THERMAL BREAK W/0 ` GROUNDING LUGS & COPPER JUMPER ELECTRICAL BONDING CONNECTION 21 j ^ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ^� 7e - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - NOTE: THE ABOVE IMAGES ARE SAMPLE CONFIGURATIONS TO ILLUSTRATE THE REO_UIREMENTS FOR SM SYSTEM GROUNDING THROUGH ENPHASE MICROINVERTERS DESCRIBED ON PAGE 1-2 l: T, 1 SM SOLAR STANDARD SYSTEM GROUNDING 00 I��UV�� INSTALLATION GUIDE ;PAGE-------------------------------------------------------------------------------------------------------------------------------------- GROUNDING LUG MOUNTING DETAILS: Details are provided for both the WEEB and Ilsco products. The WEEBLug has a grounding symbol located on the lug assembly. The Ilsco lug has a green colored set screw for grounding indication purposes. Installation must be in accordance with NFPA NEC 70, however the electrical designer of record should refer to the latest revision of NEC for actual grounding conductor cable size. Required if not using approved integrated grounding microinveters GROUNDING LUG - BOLT SIZE & DRILL SIZE GROUND LUG BOLT SIZE DRILL SIZE WEEBLug 7/16" N/A- Place in Top SM Rail Slot ILSCO Lug #10-32 7/32" • Torque value depends on conductor size. • See product data sheet for torque value. WEEBLUG CONDUCTOR - UNIRAC P/N 0080025: Apply Anti Seize and insert a bolt in the aluminum rail and through the clearance hole in the stainless steel flat washer. Place the stainless steel flat washer on the bolt, oriented so the dimples will contact the aluminum rail. Place the lug portion on the bolt and stainless steel flat washer. Install stainless steel flat washer, lock washer and nut. Tighten the nut until the dimples are completely embedded into the rail and lug. TORQUE VALUE 10 ft lbs. (See Note on PG. A) See product data sheet for more details, Model No. WEEB-LUG-6.7 ILSCO LAY -IN LUG CONDUCTOR - UNIRAC P/N 00800913: Alternate Grounding Lug - Drill and bolt thru both rail walls per table. TORQUE VALUE 5 ft lbs. (See Note on PG. A) See product data sheet for more details, Model No. GBL-4DBT. °O; SMSOLARENDCLAMP & FIRST MODULE;❑ 00 ----- o' V��V�V��---------------------------------- INSTALLATION GUIDE PAGE y �t '.� i" • p _ � -0t, n� yi a `a'e +:�rl .fit • . e Y Y L s• 3 Ji SCi•r .�� 4. 4. � � LTi 4. icey. '�Y )� Y.a� r'W ,s � 1: a: e•=a ` n'� 3 A�'f,✓�'.i'� s �� � �!di;s, r,e''{,a�` 'i�`.. ,t INSTALL MODULE ENDCLAMPS: The Endclamp is INSERT ENDCLAMP T BOLT: Insert 1/4" T -bolt into ROTATE ENDCLAMP T BOLT: Rotate T -bolt into supplied as an assembly with a T -bolt, serrated rail. position. Verify that the position indicator & T -bolt flange nut, and two washers. One washer retains the shaft are angled in the correct position. clamp at the top of the assembly. The other washer should be against the bolt head during assembly. End clamps are positioned on rails prior to the first end module and installed after the last end module. This will enable the clamp to remain upright for module installation. INSTALL FIRST MODULE: Install the first end module onto rails. Engage module frame with Endclamps.. Verify that the position indicator & T -bolt shaft are angled in the correct position. TORQUE VALUE (See Note on PG. A) 1/4" nuts to 10 ft -lbs. w/Anti Seize 1 1 1 I 1 v.. i t~� 1 POSITION INDICATOR - SERRATED T BOLT: Verify the T -bolt position indicator is perpendicular to the rail. 1/2" MIN. 47 INSTALL FIRST MODULE: Install the first end module onto rails. Engage module frame with Endclamps.. Verify that the position indicator & T -bolt shaft are angled in the correct position. TORQUE VALUE (See Note on PG. A) 1/4" nuts to 10 ft -lbs. w/Anti Seize 1 1 1 I 1 v.. i t~� 1 POSITION INDICATOR - SERRATED T BOLT: Verify the T -bolt position indicator is perpendicular to the rail. DO ; SM SOLAR BONDING MIDCLAMP D MOUNTINSTALLATION GUIDE I PAGE ------------------------------------------------------------------------ ------------------------------------------ �: -------------------------- INSTALL MIDCLAMPS: Midclamp is supplied as an INSERT MIDCLAMP T BOLT: Apply Anti -Seize• ,and : ROTATE MIDCLAMPT BOLT: Rotate bolt into position assembly with a T -bolt for module installation. insert 1/4"T bolt into rail:- ' ' and slide until bolt and clamp are against module Clamp assemblies may be positioned in rail near +'F' -frame. Do not tighten nut until next module is in point of use prior to module placement. ' - f _ position. Verify that the position indicator & T -bolt shaft are angled in the correct position. r ' a . • i +�+�.. � ■',�d !rte me",' , INSTALL MIDCLAMPS: Midclamp is supplied as an INSERT MIDCLAMP T BOLT: Apply Anti -Seize• ,and : ROTATE MIDCLAMPT BOLT: Rotate bolt into position assembly with a T -bolt for module installation. insert 1/4"T bolt into rail:- ' ' and slide until bolt and clamp are against module Clamp assemblies may be positioned in rail near +'F' -frame. Do not tighten nut until next module is in point of use prior to module placement. ' - f _ position. Verify that the position indicator & T -bolt shaft are angled in the correct position. POSITION INDICATOR - SERRATED T BOLT: Verify the, *: T -bolt position indicator is perpendicular to the rail. f' • t` • - •, 1. r • i n r ' a . • i POSITION INDICATOR - SERRATED T BOLT: Verify the, *: T -bolt position indicator is perpendicular to the rail. f' • t` • - •, 1. r • i n r ' • i Do.oS'MSOLAR REMAINING MODULES; 2❑ DOI.:MOUNT INSTALLATION GUIDE'll PAGE =INSTALL REMAINING ,MID -CLAMPS: POSITION TBOLT ALIGNMENT MARKS: _Proceed .with module .installation. Verify that the position indicator(s) Engage each `module with previously & T -bolt shaft(s) are angled in the positioned Midclamp; assemblies. correct position. NOTE: Apply Anti -Seize to each Mid TORQUE VALUE (See Note on PG. A) Clamp prior to installation.' 1/4" nuts to 10 ft -lbs. w/Anti Seize FINISH MODULE INSTALLATION: Proceed with module installation. Engage each module with the previously positioned clamp assembly: • Install second module 1/2 E .- • � MIN. Install remaining Midclamps & modules �, ' �;•,� , • Install Endclampsr • Position alignment marks • Cut rail to desired length a INSTALL ENDCLAMPS:•Apply Anti -Seize POSITION T BOLTALIGNMENT MARKS 4 and install final Endclamps° in same & CUT RAIL: Verify that the position i - manner as first `Endclamps' Slide indicator(s) -& T -bolt shaft(s) are clamps against module. angled in the correct position. Trim off any excess rail, being careful not _ TORQUE VALUE'(See Note on PG. A) to cut into the roof. Allow'/z" between - 1/4" nuts to 10 ft -lbs. w/Anti Seize ' - the Endclamp and the end of the rail. )61 0001 SM SoLAR BONDING CONNECTION GROUND,PATHS; ❑D ' MOUNT INSTALLATION GUIDE PAG E --------------------------------------------------------------------------------------------------------------------------------------------- BONDING MIDCLAMP ASSEMBLY 5 - BONDING RAIL SPLICE -BAR RAIL TO L -FOOT w/BONDING T BOLT BONDING MIDCLAMP ASSEMBLY ENDCLAMP ASSEMBLY BONDING RAIL SPLICE -BAR RAIL TO L -FOOT w/BONDING T BOLT Stainless steel Midclamp points, 2 per module, ® frame to bond ® Serrated flange nut bonds aluminum Endclamp to T -bolt ® Stainless steel self drilling screws drill and tap into splice bar and rail creating bond between ® Serrated flange.nut removes L -foot anodization to bond L -Foot to stainless steel T -bolt pierce module anodization stainless steel module to module through clamp. 0 Serrated flange nut bonds stainless steel clamp Serrated T -bolt head penetrates rail anodization ® to bond T -bolt, nut, and Endclamp to � splice bar and each rail section Aluminum splice bar spans -across rail gap to ® Serrated T -bolt head penetrates rail anodization to bond T -bolt, nut, and L -foot to rounded SM 9 to stainless steel T -bolt • grounded SM rail 0 create rail to rail bond. Rail on.at least one side rail ® Serrated T -bolt head penetrates rail anodization of splice will be"grounded: u, W N '• to bond T -bolt, nut, clamp, and modules to Note: End clamp does not bond to module frame. s. J Note: Splice bar andibolted connection are , grounded SM rail. - tA non-structural. The,splice bar function is rail V alignment and bonding.' Q BONDING MICROINVERTER MOUNT RACK SYSTEM GROUND - ®Hex nut with captive lock washer bonds metal ® WEEB washer dimples pierce anodized rail to microinverter flange to stainless steel T -bolt create bond between rail and lug ®Serrated T -bolt head penetrates rail anodization to bond T -bolt, nut, and L-footto grounded SM rail Solid copper wire connected to lug routed to System ground including racking and modules may ®Provide final system ground connection. be achieved through the trunk cable of approved microinverter systems. See page I for details NOTE: Ilsco lug can also be used when secured to the side of the rail. See page 1-3 for details Note: Only one lug per module - BONDING MICROINVERTER row required MOUNT A - ,- o _ Z J ac " m 0 ' X •./ u, W N J C tA L Q CO Wkn tA V Q s Z p z BONDING RAIL w m SPLICE BAR .\ o I \ RAILTO L -FOOT w/BONDING T BOLT BONDING MICROINVERTER MOUNT RACK SYSTEM GROUND - ®Hex nut with captive lock washer bonds metal ® WEEB washer dimples pierce anodized rail to microinverter flange to stainless steel T -bolt create bond between rail and lug ®Serrated T -bolt head penetrates rail anodization to bond T -bolt, nut, and L-footto grounded SM rail Solid copper wire connected to lug routed to System ground including racking and modules may ®Provide final system ground connection. be achieved through the trunk cable of approved microinverter systems. See page I for details NOTE: Ilsco lug can also be used when secured to the side of the rail. See page 1-3 for details coo SM SOLARBONDING CONNECTION GROUND PATHS D 00 MOUNT INSTALLATION. GUIDE � PAGE------------------------------------------------------------------------- ------------------------------ ---------------------------------------- ELECTRICAL CONSIDERATIONS' TEMPO °R ,,, _ RE Ullf`. rWEWA SOLARMOUNT is intended`,to be used with PV ir ,""DING D +i RRA�('MANCE modules that have a system voltage less than or equal to 1000• VDC. For standard system grounding a , minimum 10AWG, 105 C copper grounding .conductor should be used to ground a 1000 VDC system, according to the National Electric Code (NEC). It is the installer's responsibility to check local codes which may vary. See below for interconnection. information. l.•t _ .` fes• •t . R! �.+ !/ 1 � K fM' �, - '' iBONDING /: " INTERCONNECTION INFORMATION ' ' fr: �� r There is no size limit on how many SOLARMOUNT CLAMP.SMAINTAIN =�o & PV •modules can be mechanically interconnected '6116UIhb PATH °: a ,5� - t nfi uration provided that the for any .given co g =installation meets the requirements of applicable ;building ana fire codes. _ GROUNDING NOTES The installation must be conducted in accordance TEMPORARY BONDING CONNECTION DURING ARRAY MAINTENANCE , with the National Electric Code (NEC) and the When removing modules for replacement or system maintenance, any module left in place that is secured authority having jurisdiction. Please refer to these with a bonding Midclamp will be properly grounded. If a module adjacent to the end module of. a row is resources in your location for required grounding lug removed or if any other maintenance condition leaves'a module without a bonding mid clamp, a temporary quantities specific to your project. bonding connection must be installed as shown • Attach Ilsco SG64 to wall of rail The grounding / bonding components may overhang • - Attach Ilsco SGB4 to module frame parts of the array so care, must be made when ' -_ • Install solid copper wire jumper to Ilsco lugs , ' walking around the array toravoid damage. ` Conductor fastener torque values depend on a conductor size. See product data sheets for correct torque values. ' S� a R •• aO• U N I RAC ' A HILTI GROUP COMPANY T Solar.Mount Technical Datasheet ' Pub 110818-1 td V1.0 August 2011 SolarMount Module Connection Hardware ....................... 1 ' y Bottom Up Module Clip ..... :...:......................................................................................... 1 MidClamp ....:........................................ ... •'..+ ........ .."....;.......:........................,.y.:.2 End Clamp....... ... ............ .. •............................. �...........:............2 .... ...... ... ... SolarMount Beam Connection Hardware ................. L -Foot ...................................:...= .......:.........:........................................... . ... ... ................. 3 SolarMount Beams................:..............................:.......................................... ........4 1 � � •• h• 1 •.. • M '` tib. • • ♦r ` - � - �' , , ^. � • J • J'tr � `r--• . � r • - SolarMount Module Connection Hardware - v , SolarMount Bottom Up Module Clip k Part No. 302000C Washer. Bottom Up Clip material: One of the following extruded aluminum Bottom n =allo s: 6005-T5 '6105=T5 6061=T6 ' ` Nuf (hidden see Y . _ • .,. . w �. Up Clip • note%) Ultimate tensile: 38ksi' Yield: 35 ksi:="- `'' ,r y_� • . Finish: Clear Anodized I W= Bottom Up Clip weight: 0.031 lbs (14g) S Allowable and design loads are,valid when components are Beam •.assembled with SolarMount series beams according to authorized UNIRAC'documents I *` Assemble with,,one4"L 20'ASTM,F593 bolt; one'/4"-20 ASTM F594 serrated flange nut, andFone'/4°flat washer, Use anti seize andlightento 10 ft=lbs^of,torque , � Z , ,Ka Resistance fact ors;and:safety factors are determined according to • •;�?A, t , J.�,�. -�. , part 1 section 9 of the 2005 Aluminum Design Manual and third- ' ,,� •r �- : = party test resuIts,from an IAS accredited laboratory { - ,� r • : Module edge must be fully.supported by the'beam NOTE ON WASHER: Install washer on bolt head side of assembly: , .DO, NOT'install washer under serrated flange nut ' U as Applied Load Average 4Allowable Safety Design Resistance Direction _ Ultimate Load Factor, Load Factor, lbs (N) lbs (N) FS lbs (N) 4) Tension, Y+ M 1566_(6967) 686 (3052) 2.28 1038 (4615) 1 0.662 Transverse,'X± x,11.28 (5019) „ 329(1463) 3.43 497 (2213), ,. -0:441 Sliding, -Z±" 166 (292) 27 (119) : ' 2.44 41 (181) ' .0.619 I1 ! Average Ultimate lbs (N) t Safety Factor, FS -'Design Load -Ibs (N) Resistance Factor, Tension, Y+ 2020 (8987) 891 (3963) 2.27 1348 (5994) 0.667 SolarMount Mid Clamp a Part No.,302101 C, 302101 D,.302103C, 302104D, s 302105D, 302106D . } •k Mid clamp material: One of the following extruded aluminum j Nl�d rra Bolt alloys: 6005-T5; 6105-T5, 6061-T6 la e Nu Clamps . w,•` Ultimate tensile: 38ksi, Yield: 35 ksi • y� ' x'" � r: • Finish: Clear or Dark Anodized '� t�1 yk•Mid clamp weight: 0.050 lbs (23g) Allowable and design loads are valid when components are ��•; �x r M assembled according to authorized UNIRAC documents Values represent the allowable and design load capacity of a single ..- r mid clamp assembly when used with a SolarMount series beam to retain a module in the direction indicated. . . •' -� ' Assemble mid clamp with one Uni_rac'/4"-20 T,bolt and one'/4"-20 ASTM F594 serrated flange nut Use anti -seize and tighten to 10 ft -lbs of torque :Beam + •„ Resistance factors and safety factors are determined according to �►' = part 1 section 9 of the 2005 Aluminum Design Manual and third - party test results from an IAS accredited laboratory -Applied Load Direction Average Ultimate lbs (N) Allowable • Load lbs (N) Safety Factor, FS -'Design Load -Ibs (N) Resistance Factor, Tension, Y+ 2020 (8987) 891 (3963) 2.27 1348 (5994) 0.667 Transverse, Z±- 520 (2313) 229 (1017) 2.27 346 (1539) 0.665 Sliding, X± 1194 (5312) 490 (2179) 2.44 741 (3295) 0.620 I X r r Dimensions specified in incF es'unless noted Xx S .3 _ Y �°'t. µdu •' - r• �. �.y .j,�. -� � • t.: �,� Y ✓+moi any ti• "! ;,�• _• - ' . r 1 n 3; - 3.F� R* �l•. �y : ! � Y 't v �. 1, ..y',,y �� .• •,�,�•• 4'Y� { SolarMount End Clamp r. Part No. 302001C, 302002C, 302002D, 302003C, 302003D, 302004C, 302004D, 302005C, 302005D, 302006C, 302006D, 302007D, 302008C, 302008D, 3020090, 302009D, 3020100, 3020110, 3020120 End clamp material: One of the following extruded aluminum . '_alloys: 6005 -T5,.6105 -T5, 6061-T6 Aolt� ' `�} Ultimate tensile: 38ksi, Yield: 35 ksi y , ',• �. w ! • •�`' Finish: Clear, or''Dark Anodized., ' End clamp "weight: varies fjased on;height•: 0.058 lbs (26g) di► Clam `' �: �} Allowable and desig n loads are valid when'com onents are �. ¢ _,assembled accordin to authorized UNIRAC documents ' .. .Serrated {r „ g • `:. xJ Flange:Nut °° r•f Values represent the allowable and;desigri load capacity of a single end clamp assembly when used with -a SolaWount series beam to retain a module in the direction indicated • " • t y. • Assemble with one Unirac'/4"-20 T -bolt and one'/4"-20 ASTM F594 serrated flange nut 'Bea • v Use anti -seize and tighten to 10 ft -lbs of torque . Resistance factors and safety factors are determined according to part 1 section 9•of the 2005 Aluminum Design Manual and third- Y party test -results from an IAS accredited laboratory Modules must be installed at least,.1.5 in from either end•of abeam 1 VANES Moouu Tus HIM D. f d ---b a t d Applied Load ; " ; Average • Allowable Safety Design Resistance Direction . ; Ultimate Load Factor, Loads Factor, lbs (N) lbs (N) FS - lbs (N) Tension, Y+ 1321 (5876) ' 529 (2352) 2.50 800 (3557) 0.605 Transverse, Z± 63 (279) 14 (61) 4.58 21 (92) 0.330 Sliding; X± 142 (630) 52 (231). 2.72 79 (349) 0.555 k• � f imensions specs ie-a�-irac es-u� Ess-n.o e _ k 4 ' 1300 ■ d IRAC r A HILTI GROUP COMPANY { SolarMount Beare Connection Hardware SolarMount L -Foot • ' Part No. 304000C, 304000D • L -Foot material: One of the following extruded aluminum alloys: 6005- T5, 6105-T5, 6061-T6 0 Ultimate tensile: 38ksi, Yield: 35 ksi 0 Finish: Clear or Dark Anodized y`0 L -Foot weight: varies based on height: -0.215 lbs (98g) • �` Allowable and design loads are valid when components are :assembled with SolarMount series -beams according to authorized Bea Bolt UNIRAC documents L -Foot For the beam to L -Foot connection: Assemble with one ASTM F593 W-16 hex head screw and one erratedr- ASTM F594 3/8rrserrated flange nut Flange Nu.Use anti -seize and tighten to 30 ft -lbs of torque Resistance factors and safety factors are determined according to part 1 section 9 of the 2005 Aluminum Design Manual and third -party test Y , results from an IAS accredited laboratory NOTE:, Loads are given for the L -Foot to beam connection only;'be . . sure to check load limits for standoff, lag screw, or other ` attachment method 3X $LOT FOR t yW, ,Dimensions specified iri-inches unless noted. Applied Load Direction Average Ultimate lbs (N) Allowable Load lbs (N) ', -Safety Factor, FS -Design Load lbs (N) Resistance Factor, Sliding, Z± 1766 (7856) 755 (3356) 2.34 1141 (5077) 0.646 Tension, Y+ 1859 (8269) 707 (3144) 2.63 1069 (4755) 0.575 ' Compression:`Y-° 3258 (14492) 1325'(5893) '•'2:46 2004 (8913) ' ';; "0.615 Traverse, X± 486 (2162)',: '213 (949) 2.28' • 323 (1436) 1 0.664 ' •i�'r • - .. • C� r ', RFti rr - - { 4 , - "l'•1 , ' i } ft,-/ ` r c r �' '-.11;e„�'I�Tj' •iL `.r.,- Y' si'w '. F ,^ • } y •'•S .� R Lyr �•- n[t '4« r S ..•'� {�t.--tit''i' '�Rt e s �' � ; •, ~ � � �r^j � i R„1. ,x S�' i.,. ! ' � i J -�`•„„ «��,�T` F ;, w � ✓ �R, 4 r� �;tJ S.=t' �}n t ` "r, ,is...r.ti j ', , ; -a{ �r •r^''r� • • { t� 5�,. e T '.� r ..r' .y�..r3.'r� ' { y ••+t�.•f,!•.J � ; ,. .:. ^E _ ° fr��`� _ � �" r�'S'= r' i•- r �, ... dr •F ` .� kr ti` . .. ck.}'. .� N•,e1 i Sia. -' xp , +!• �r zx', ,M.'b��l.� � t ai *. sY � w,, X s tr. '!- ht i, �>:�T- +}�.�. ,A 7 �•`t 1•;fir / � . • ,a��� �� �.5 i - ! a _ 4 • Yr``, j rLr ''l. ..rrat: r+ ._ s � .',yfy �. - • r - �'1 '•�4 j. i• .. i' a 1 j tr. � �.. p T ' ,� + ♦ . t t � A.�, r �ki-�- r., t •'y: - t . �y�. Y ..r • ' . �'.``'i. - r �'� -f n.. { :- i � t c ? - f. a .. ; t +..'� •� •ry , �' � �. t.. ♦ i. .-•.h�. :•� 1 `.i ` ... 'ft lr'. r _ :.+, } -^� r '.J , 1 ! d '.,.,' ,.' l i, 7 !A , a Y �•v�' . _ } ' � f'+ - y"7" - ., Jr... • + 4+"• . 4„ r 'Y i.. }. J a ,,, , . °7•: 1' x..71 G. UNIRAC > A HILTI GROUP COMPANY, ' SolarMount Beams Part No. 310132C, 310132C -B, 310168C, 310168C -B, 310168D'. 310208C, 310208C -B, 310240C, 310240C -B, 310240D, :. 410144M, 410168M, 410204M, 410240M w Properties' .lJnits SolarMount SolarMount HD Beam Height Jn 2.5 3.0 Approximate Weight (per linear ft) plf ' 0.811 1.271 Total Cross Sectional Area int : .0.676 1.059 Section Modulus (X -Axis) in 0.353 0.898 Section Modulus (Y -Axis) in 0.113 0.221 Moment of lnertia.(X-Axis) in 0.464 r Moment,of Inertia (Y --Axis) in 0.044 - 0.267 a r 0.289 1.170 Radius of Gyration (Y -Axis) • Jn 0.254 0.502 Properties' .lJnits SolarMount SolarMount HD Beam Height Jn 2.5 3.0 Approximate Weight (per linear ft) plf ' 0.811 1.271 Total Cross Sectional Area int : .0.676 1.059 Section Modulus (X -Axis) in 0.353 0.898 Section Modulus (Y -Axis) in 0.113 0.221 Moment of lnertia.(X-Axis) in 0.464 1.450 Moment,of Inertia (Y --Axis) in 0.044 - 0.267 Radius of Gyration (X -Axis) 'i in 0.289 1.170 Radius of Gyration (Y -Axis) • Jn 0.254 0.502 e `.,. �.'. ' .\ f�. 1. S•`+ • X _ . • . ' ] � r c: y } � .F fit] _ _ _ � � � -�. . , r y . a SLOT FOR T -BOLT OR `y �,. ! 1.728 , j� 1 k"r ',SLOT FORT BOLT OR 4",HEX HEAD SCREW i ; M ':.HEX HEAD SCREW,-. �, t •'} }: ,�, a��• i- y` }. ,.•.47 yam.• � b�F,.; •t4,f1�. r.'�. f° - ,.R. '�,. �w_""�,'{z.�. "t. , R 2X SLOT FOR, , ;`f r # r� a.:�. .. }-� SLOT FOR'� BOTTOM CLIP •'_S•xj BOTTOM C 2.500 LIP;,` f;, .,.,.. - O► , - ;x}+ , :Cf� _ ; ' r;-, j t, ° k +� 5 .y +.' � 3 _ � r f f . ti .... ,!g Y - f � ! , 1 a r';r � ,�*. r� !•... a . ,,.. �•{. "�•r :_y L+ye.."4"':�`� '•t _ T7 - •! c ' t" s,.., .t .q'r - �a ��,r, ,L a„� 3.000 •...i � .., •) r 417 2�' .+ �• Y� 1.316 dl... F:..•}~ .� d -• 2� _ � ~* �' - 'a •. • a. - t � SLOT FOR •, n . 3/8 HEX BOLT. SLOT FOR 1.385 t 3/” HEX BOLT 387 750 ` t � �� . «�'' _a ;;v .'•� r � '.�t. � �, w � 1.207 •. Si � �rs � K. { r . n. f . a..:;. � ,s,4 T y'' ., ,._'" v!:, �y w � 9'� � _ t� ♦ h L, s s - i iN +� . ' T.' .'W.; � �.� ~E 1� i',1 F "�y'^x�. •a _ ' Y.., • t-�.' i 't� r - 'r. x j ,yip -Y l�. y:5�;:.•. "�'-T •�F i. S -75' 'i t `+q"`�' r•r= J ry �h.. X iip" X ' SolarMount Beam. SolarMount HD Beam Dimensions specified in inches unless noted 1 r t e `.,. �.'. ' .\ f�. 1. S•`+ • X _ . • . ' ] � r c: y } � .F fit] _ _ _ � � � -�. . , r y . a SLOT FOR T -BOLT OR `y �,. ! 1.728 , j� 1 k"r ',SLOT FORT BOLT OR 4",HEX HEAD SCREW i ; M ':.HEX HEAD SCREW,-. �, t •'} }: ,�, a��• i- y` }. ,.•.47 yam.• � b�F,.; •t4,f1�. r.'�. f° - ,.R. '�,. �w_""�,'{z.�. "t. , R 2X SLOT FOR, , ;`f r # r� a.:�. .. }-� SLOT FOR'� BOTTOM CLIP •'_S•xj BOTTOM C 2.500 LIP;,` f;, .,.,.. - O► , - ;x}+ , :Cf� _ ; ' r;-, j t, ° k +� 5 .y +.' � 3 _ � r f f . ti .... ,!g Y - f � ! , 1 a r';r � ,�*. r� !•... a . ,,.. �•{. "�•r :_y L+ye.."4"':�`� '•t _ T7 - •! c ' t" s,.., .t .q'r - �a ��,r, ,L a„� 3.000 •...i � .., •) r 417 2�' .+ �• Y� 1.316 dl... F:..•}~ .� d -• 2� _ � ~* �' - 'a •. • a. - t � SLOT FOR •, n . 3/8 HEX BOLT. SLOT FOR 1.385 t 3/” HEX BOLT 387 750 ` t � �� . «�'' _a ;;v .'•� r � '.�t. � �, w � 1.207 •. Si � �rs � K. { r . n. f . a..:;. � ,s,4 T y'' ., ,._'" v!:, �y w � 9'� � _ t� ♦ h L, s s - i iN +� . ' T.' .'W.; � �.� ~E 1� i',1 F "�y'^x�. •a _ ' Y.., • t-�.' i 't� r - 'r. x j ,yip -Y l�. y:5�;:.•. "�'-T •�F i. S -75' 'i t `+q"`�' r•r= J ry �h.. X iip" X ' SolarMount Beam. SolarMount HD Beam Dimensions specified in inches unless noted October 30, 2014 UniRac 1411 Broadway Boulevard NE Albuquerque, New Mexico 87102-1545 TEL: (505) 242-6411 FAX: (505) 242-6412 Attn.: Engineering Department, STRU(TURAL ENGINEERS. QRpFESS/pN ,NNETH e4 � cy ti CID w m No. S3878 * Exp. 3-31- s�gTSTRUCT U?- F OF CA�\FO Re: Engineering Certification for U�iRac's SolarMount Design & Engineering Guide PZSE, Inc. -Structural Engineers has reviewed UniRac's "SolarMount Design & Engineering Guide" and specifically the enhancements of the SolarMount Flush -to -Roof System, Pressure Lookup Tables, and Downward & Upward Span Length Tables. This certification excludes connections to building structures and the effects on building structure components. All information, data and. analysis contained within the Installation Manual are based on, and comply with the following: 1. 2012 International Building Code, by International Code Council,"Inc:,-.2012',­ 2. 2013 California Building Cede, by California Building Standards Commission, 2013 Sincerely, Paul Zacher, SE - President 8150 Sierra College Boulevard, Sufte 150 • Roseville, CA 95661 • 916.961.3960 P • 916.961.3965 www.pzse.com Su ,•�' CD ' � O LAR MI.CROINVERTER SYSTEM GR-OUND'ING yet O _ --..-INSTALLATION GUIDE" PAGE ----------------- SM EQUIPMENT GROUNDING THROUGH ENPHASE MICROINVERTERS The Enphase M215 and. M250 microinverters have : integrated grounding t: ��.,- , .�,� �,_�.,,�. _•,rte �.��.�,.;,�-�,.� A,� •, 'capabilities built in: In this, case, the.DC circuit is isolated from the AC circuit and , the AC equipment roundin conductor EGC is built into the Enphase Engage integrated grounding (IG) cabling. order to round'_tfie SOLARMOUNT rackingsystem through the Enphase microinverter grid Engage cable assembly, there must"be a minimum of three PV modules connected; to: the same trunk cable within a continuous row. , Continuous row'is defined 'as a grouping of modules installed and bonded per requirements of this; installation guide sharing the _same two rails. The ,p � the - � '` � •' � E�•microinverters are bonded to the SOLARMOUNT rail via the mounting hardware. Complete equipment' grounding is achieved through the Enphase Engage cabling , S with integrated grounding (IG). No additional EGC grounding cables are required, ` as all fault current is, carried to round through the Engage cable. _ _ 9 9 SOLARMOUNT INTEGRATED BONDING ADVANTAGE - W - t S = LOSE ALLTHE- COPPER & LUGS-- l • . I i '` : .' ' • a � - '�•^ • - h 4 - LTi. 1t - a - - c00 SOLA00.__ SM mou �IPHA�SEIMICROINUI�1� FWOR, S P LI C E IT CONTINUOUS RAIL &!ELECTRICAL,BONDING SPLICE Enphase Microinverter (MI) Requirements (Model No. M215 & M250) 3 Microinverters sharing same trunk cable & rails t R.E. _UI.. EME _ T6 ! 1 -L Min. 3 microinverters sharing _ — z same trunk cable & rails c00 SOLA00.__ SM mou �IPHA�SEIMICROINUI�1� FWOR, S P LI C E IT CONTINUOUS RAIL &!ELECTRICAL,BONDING SPLICE Enphase Microinverter (MI) Requirements (Model No. M215 & M250) 3 Microinverters sharing same trunk cable & rails &,THERMA-L BREAK - ..INSTALLATION GUIDE I PACE - ----------------- EXPANSION JOINT W/GROUNDING LUGS '& COPPER 'JUMPER Enphase Microinverter (MI) Requirements -(Model No. M215 & M250) ` 3 or more Microinverters sharing same trunk cable & rails: + _r _M,INI.MUMiLY_OUT R.E. _UI.. EME _ T6 ! 1 -L Min. 3 microinverters sharing _ — z same trunk cable & rails .C_7 _ RAIL SPLICE . Min. 3 microinverters sharing same trunk cable & rails — _L. _ J_ _— k' .r � 1_' s � -1 � -•r l -I� . + i k' + ..C.a.._ IF - -L- - e n. microinverters _ orreach side of thermal break &,THERMA-L BREAK - ..INSTALLATION GUIDE I PACE - ----------------- EXPANSION JOINT W/GROUNDING LUGS '& COPPER 'JUMPER Enphase Microinverter (MI) Requirements -(Model No. M215 & M250) ` 3 or more Microinverters sharing same trunk cable & rails: + �'- MC_ IMUM_ '_Y_OUTLREQU.IREMENTS4r= -'"- 3 or more microinverters sharing --� same trunk cable & rails ij Y i RAIL SPLICE -iTHERMAL BREAK"+ .:� rY _L. _ J_ _— k' .r � 1_' F k' + 1 •,T.�s�w` =Qw +�. 74_ Tye , - F ELECTRICAL BONDING SPLICE EXPANSION JOINT USED AS THERMAL BREAK W/ R' -� EXPANSION JOINT USED AS THERMAL BREAK W/0 'GROUNDING LUGS -& COPPER JUMPER :' :. ` _ ELECTRICAL BONDING CONNECTION NOTE: THE ABOVE IMAGES ARE SAMPLE CONFIGURATIONS TO ILLUSTRATE THE REQUIREMENTS FOR SM SYSTEM GROUNDING THROUGH ENPHASE MICROINVERTERS DESCRIBED ON PAGE 1-2 _h MLNLM_U�M_ Y10 S REQU.IREM.E TN Y � - n. microinverters _ orreach side of thermal break -� RAIL SPLICE =THERMAL BREAK- - Less than 3 microinverters TNOT T — on each side of thermal break-ACCEPTABL-E i- "RAIL SPLICE " T_ - - - - -i- - F •,T.�s�w` =Qw +�. 74_ Tye , - F ELECTRICAL BONDING SPLICE EXPANSION JOINT USED AS THERMAL BREAK W/ R' -� EXPANSION JOINT USED AS THERMAL BREAK W/0 'GROUNDING LUGS -& COPPER JUMPER :' :. ` _ ELECTRICAL BONDING CONNECTION NOTE: THE ABOVE IMAGES ARE SAMPLE CONFIGURATIONS TO ILLUSTRATE THE REQUIREMENTS FOR SM SYSTEM GROUNDING THROUGH ENPHASE MICROINVERTERS DESCRIBED ON PAGE 1-2 1 Y � - 1 O° SMSOLAR STANDARD SYSTEM GROUNDING0001 MOUNTINSTALLATION GUIDE � PACE----------------- ----------------------------------------------------------------------- GROUNDING LUG MOUNTING DETAILS: Details are provided for both the WEEB and Ilsco products. The WEEBLug has a grounding symbol located on the lug assembly.The Ilsco lug has a green colored set screw for grounding indication purposes. Installation must be in accordance with NFPA NEC 70, however the electrical designer of record should refer to the Latest revision of NEC for actual grounding conductor cable size. Required if not using approved integrated grounding microinveters GROUNDING LUG -=BOLT SIZE & DRILL,SIZE GROUND LUG BOLT SIZE DRILL SIZE WEEBLug 7/16" N/A- Place in Top SM Rail Slot ASCO Lug #10-32 7/32" • Torque value depends on conductor size. • See product data sheet for torque value. e r WEEBLUG CONDUCTOR - UNIRAC P/N 0080025: Apply Anti Seize and insert a bolt in the aluminum rail and through the clearance hole in the stainless steel flat washer. Place the stainless steel flat washer on the bolt, oriented so the dimples will contact the aluminum rail. Place the lug portion on the bolt and stainless steelflat washer. Install stainless steel flat washer, lock washer and nut. Tighten the nut.untiI the.dimples are completely embedded into the rail and lug. TORQUE VALUE 10 ft lbs. (See Note on PG. A) See product data sheet for more details, Model No. WEEB-LUG-6.7 r ILSCO LAY -IN LUG CONDUCTOR - UNIRAC P/N 008009P: Alternate Grounding Lug - Drill and bolt thru both rail walls per table. TORQUE VALUE 5 ft lbs. (See Note on PG. A) See product data sheet for more details, Model No. GBL-4DBT. r ••TSULAR iii 'lOIU��T BONDING CONNECTION GROUND PATHS;D IPdSTALLATIOM GUIDE'l PACE ---------------- I . AA TEDD hi BONDING MIDCLAMP ASSEMBLY ENDCLAMP ASSEMBLY , BONDING RAIL SPLICE BAR RAIL TO L-FOOT�W/BONDING T BOLT steel Midclamp points, 2 per module, a_ Stainless steel self drilling screws drill and tap ® into bar and rail creating bond between ••TSULAR iii 'lOIU��T BONDING CONNECTION GROUND PATHS;D IPdSTALLATIOM GUIDE'l PACE ---------------- I . AA TEDD hi BONDING MIDCLAMP ASSEMBLY ENDCLAMP ASSEMBLY , BONDING RAIL SPLICE BAR RAIL TO L-FOOT�W/BONDING T BOLT steel Midclamp points, 2 per module, ® Serrated flange nut bonds aluminum Endclamp y� Stainless steel self drilling screws drill and tap ® into bar and rail creating bond between ® Serrated flange nut removes L -foot anodization to bond L -Foot to stainless steel T -bolt ®Stainless pierce module frame anodization to bond to stainless steel T -bolt a splice , module to module through clamp, Serrated T -bolt head penetrates rail anodization - splice bar and each rail section �_ ;. ® Serrated T -bolt head penetrates rail anodization ® Serrated flange nut bonds stainless steel clamp ® to bond T -bolt, nut, and Endclamp to grounded '' Aluminum splice bar spans across rail gap to: to bond T -bolt, nut, and L -foot to rounded SM' g to stainless steel T -bolt SM rail ® create rail to rail bond. Rail on at least one side rail '* ® Serrated T -bolt head penetrates rail anodization ca W of splice will be grounded. _ to bond T -bolt, nut, clamp, and modules to Note: End clamp does not bond to module frame. Note: Splice bar and bolted connection are grounded SM rail. - - non-structural. The splice, bar function is rail *' • 5 alignment and bonding: y 93 C Z = n g. NOTE W B 6 0 ILSQ LUGj' BONDING MICROINVERTER MOUNT - RACK SYSTEM GROUND ®Hex nut with captive lock washer bonds metal ® WEEB washer dimples pierce anodized rail to microinverter flange to stainless steel T -bolt " create bond between rail and lug ® Serrated T -bolt head penetrates rail anodization Solid copper wire connected to lug is routed to to bond T-bolt,nut,and L -foot to grounded SM rail System ground including racking and modules may provide final system ground connection. be achieved through the trunk cable of approved- microinverter systems. See page I for details NOTE: ILsco lug can also be used when secured to the side of the rail. Seepage 1-3 for details Cs , Note: Only one lug per module BONDING MICROINVERTER row required MOUNT Z J , � 00 0 X 4A a ca W H. 5 a LntA o d � � 5 Z 93 C Z BONDING RAIL Z LU m SPLICE BAR RAIL TO L -FOOT w/BONDING T BOLT = n g. NOTE W B 6 0 ILSQ LUGj' BONDING MICROINVERTER MOUNT - RACK SYSTEM GROUND ®Hex nut with captive lock washer bonds metal ® WEEB washer dimples pierce anodized rail to microinverter flange to stainless steel T -bolt " create bond between rail and lug ® Serrated T -bolt head penetrates rail anodization Solid copper wire connected to lug is routed to to bond T-bolt,nut,and L -foot to grounded SM rail System ground including racking and modules may provide final system ground connection. be achieved through the trunk cable of approved- microinverter systems. See page I for details NOTE: ILsco lug can also be used when secured to the side of the rail. Seepage 1-3 for details Cs , E -Mount Lag I QMSE - LAG THIS EDGE TOWARDS ROOF RIDGE INp DESCRIPTION QTY./BOX - Specific Gravity" 1 FLASHING, 9" X 12" X .040", 5052, MILL 1 798 t. 266 Douglas Fir, South .46 2 QBLOCK, CLASSIC, A360.1 CAST AL, MILL 1 705 235 Hem, Fir 3 PLUG, SEALING, 5/16" X 7/8", EPDM / 18-8 SS 1 .46 705 235 4 LAG SCREW, HEX HEAD, 5/16" x 5-1/2", 18-8 SS 1 Spruce, Pine, Fir .42 5 WASHER, FENDER, 5/16" ID X l-1 /4" OD, 18-8 SS 1 798 266 RACKING COMPONENTS - NOT INCLUDED 5 3.00 4.50 9.00 2.25 .040 ` 1.29 Chuck Mount PV TITLE: QMSE-LAG: QMPV ,E -MOUNT AVAILABLE IN MILL, AND WITH LAG BOLT" BRONZE ANODIZED FINISHES UNLESS OTHERWISE SPECIFIED: SIZE DRAWN BY: RAD REV DIMENSIONS ARE IN INCHES TOLERANCES: A DATE: 3/2/2015 3 FRACTIONAL• 1/8 PROPRIETARY AND CONFIDENTIAL 'TWO PLACE DECIMAL 2.18 THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF QUICK MOUNT PV. ANY REPRODUCTION IN PART ORAS A WHOLE WITHOUT THE WRITTEN PERMISSION OF QUICK MOUNT PV IS PROHIBITED. OO NOT SCALE DRAWING- THREE PLACE DECIMAL 2.125. SCALE: 1:3 WEIGHT:0.96 SHEET 1 OF 1 4 Lag pull-out (withdrawal) capacities (Ibs) in typical lumber: - Lag Bolt Specifications r - Specific Gravity" 5/16" shaft per 3" thread depth' 5/16" shaft per.1" thread depth Douglas Fir, Larch .50 798 t. 266 Douglas Fir, South .46 705 235 ". Engelmann Spruce, Lodge' ole Pine (MSR 1650 f & higher) .46 705 235 Hem, Fir .43 636 212 Hem Fir (North) .46 705 235 Southern Pine .55 921 307 Spruce, Pine, Fir .42 615 205 Spruce, Pine, Fir (E of 2 million psi and higher grades of MSR and MEL) .50 798 266 Sources: American Wood Council, NDS 2005,Table 11.2 A, 11.3.2 A Notes: r Y 1)Thread must be embedded in a rafter or other structural roof member. 2) See NDSTable 11.5.1C for required edge distances. quick Mount. PYD RESPECT THE ROOF BI 7.2.3-31 Mar -2015, Rev 3 ,, a .a ------------------------------------------------- ------------------------- ----------- .1. POINT OF INTERCONNECTION ,.- AC WARNING LABEL" MOUNT ON MAIN SERVICE PANEL OR SUBPANEL WHITE TEXT/RED BACKGROUND ENGRAVED PLACARD y ,3/16"/18pt LETTERING . J ,u a 1 ,, a .a ------------------------------------------------- ------------------------- ----------- .1. POINT OF INTERCONNECTION ,.- AC WARNING LABEL" MOUNT ON MAIN SERVICE PANEL OR SUBPANEL WHITE TEXT/RED BACKGROUND ENGRAVED PLACARD y ,3/16"/18pt LETTERING . J ,u ' SUBPANEL.POINT OF INTERCONNECTION LABEL ` MOUNT ON MAIN SERVICE PANEL + WHITE_ TEXT/RED BACKGROUND ENGRAVED PLACARD 3/16"/13.5pt LETTERING :^ S *. �� •n' e w _*.,, ' , J CAUTION : SOLAR CIRCUIT WARNING LABEL; r ,•_ AFFIX TO CONDUIT @ ENDS & 10' INTERVALS r • • WHITE TEXT/RED BACKGROUND- REFLECTIVE STICKER'- ' ' �. •'� ` '+ .' • + •?,; 7116" / 31.5 t LETTERING�; s �z � �� n'+i a3 - ' ..c t A. r n ; :'x� ,. �.�.'.. — ,....p.£... ... , H r •'�' /^'*'•r- 1` ♦ iF•,a,� i P `R s Irl � ��, •-w� 11 4. f, f 1 s • f. ' SUBPANEL.POINT OF INTERCONNECTION LABEL ` MOUNT ON MAIN SERVICE PANEL + WHITE_ TEXT/RED BACKGROUND ENGRAVED PLACARD 3/16"/13.5pt LETTERING :^ S *. �� •n' e w _*.,, ' , J CAUTION : SOLAR CIRCUIT WARNING LABEL; r ,•_ AFFIX TO CONDUIT @ ENDS & 10' INTERVALS r • • WHITE TEXT/RED BACKGROUND- REFLECTIVE STICKER'- ' ' �. •'� ` '+ .' • + •?,; 7116" / 31.5 t LETTERING�; s �z � �� n'+i a3 - ' ..c t A. r n ; :'x� ,. �.�.'.. — ,....p.£... ... , H r •'�' /^'*'•r- 1` ♦ iF•,a,� i P `R s Irl � ��, •-w� 11 4. f, f �',.♦ .s- _, w f �. *,, ` rAa- i ' +