HomeMy WebLinkAboutB16-1804 024-054-007r)
Butte Copnty`Department of Development
PERMIT CENTER
7 County Center Drive, Oroville, CA 95
Main Phone 530.538.7601 Fax 530.538.7785
www.buttecountv.net/dds
PLAN CHANG"ECHE^CK,
Owner's Nam Z) Jkpn � i �ISSt<
Contact Person Name: r^Clot _5Zx0l_ y
Contact email:
Services FORM NO
96 DBP -06
V�
0
R RETURN
t
Contact Phone Number: 530 237-1pS Date Submitted: �' I
Permit Number: 64- fd d Assessor's Parcel Number: 09q.054• 00�
❑ COMPLETE SET OF PLANS
OfARTIAL SET OR PAGES OF PLANS
(LIST PAGES BELOW)
Pl W check any that apply:
ET Response to Plan Check Letter?
❑ Response to Building Inspection Correction Notice?
❑ Is there additional square footage?
❑ Is unfinished area being in -filled or completed?
❑ Other:
1.
2.
3.
4.
5.
LIST OF ITEMS SUBMITTED
�c3
BUTTE
COUNTY;:
FEB 0 8 20117
DEVELOPMENT.
SE�ZVI(`ES
Minimum 1 hour plan change fee to be collected at time of submission. Plans Examiner
will determine if additional plan checking fees are required:
❑ Minimum $127.00 paid
❑ Additional Fee Amount Due:
Revised 7.20.2015
Page 1 of 1
t
PLAN CHECK #2 RESPONSE: 2/7/2016
TOMMIE MASSENGILL
211 SHELDON AVENUE
GRIDLEY, CA. 95953
237-6305
GENERAL COMMENTS:
OWNER TO PROVIDE SITE PLAN.
NON-STRUCTURAL COMMENTS:
REPLACING THE DECK SURFACE, SHOWN ON SHEET #1 EXISTING FLOOR PLAN.
42. ADDED TWO SECTIONS TO SHEET#2, ONE THRU GARAGE & ONE THRU HOUSE.
STRUCTURAL COMMENTS:
1,2&3 APPROVE WITH ENGINEER & CONTRACTOR OVER COUNTER MEETING.
I(vl��`�
BUTTE
COUNTY
FEB 0 8 2017
I)EVELOPMENT
SERVICES
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
R0.11,
CEC-CF1 R -ALT -05-E (Revised 10/15) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE CF1R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 1 of 8)
Project Name: TOMMIE MASSENGILL Date Prepared: 12/15/2016
This compliance document is only applicable to simple alterations that do not require HERS verification for compliance. When HERS verification is required, a CFIR-ALT-01 shall first be registered
with a HERS Provider Data Registry. -
Alterations to Space Conditioning Systems that are exempt from HERS verification requirements may use the CFIR-ALT-05 and CF2R-ALT-05 Compliance Documents. Possible exemptions from duct
leakage testing include: less than 40 ft of ducts were added or replaced; or the existing duct system was insulated with asbestos; or the existing duct system was previously tested and passed by a
HERS Rater. If space conditioning systems are altered and are not exempt from HERS verification, then a CFIR-ALT-02 must be completed and registered with a HERS Provider Data Registry.
Alterations that utilize close Cell Spray Polyurethane Foam (ccSPF) with a density of 1.5 to less than 2.5 pounds per cubic foot having an R -value other than 5.8 per inch, or Open Cell Spray
Polyurethane Foam (ocSPF) with a density of 0.4 to less than 1.5 pounds per cubic foot having an R -value of 3.6 per inch, shall complete and register a MR -ALT -01 with a HERS Provider Data
Registry.
If more than one person has responsibility for installation of the items on this certificate, each person shall prepare and sign a certificate applicable to the portion of construction for which they are
responsible. Alternatively, the person with chief responsibility for construction shall prepare and sign this certificate for the entire construction. All applicable MandatoryMeasures shall be met.
Temporary labels shall not be removed before verification by the building inspector.
A: General Information
01
Project Name:
TOMMIE MASSENGILL
02
Date Prepared:
12/15/2016
03
Project Location:
211 SHELDON AVE
04
Building Front Orientation (deg or cardinal):
SOUTH 180
05
CA City:
GRIDLEY CA.
06
Number of Altered Dwelling Units:
1
07
Zip Code:
95953
08
Fuel Type:
GAS
09
Climate Zone:
11
10
Total Conditioned Floor Area (ft):
1137
11
Building Type:
SFR
12
Slab Area (ft):
WOOD FLOOR
13
Project Scope:
REMODEL EXISTING HOUSE, NO INCRESS IN SIZE
Of ate._ _
-
Sul -1 � C L%®U -r�,,
iLDNG Di ��
APPiqijo
1t IAC 0
BUTTE
COUNTY
DEC 2 2 2016
DEVELOPMENT
SERVWES
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
CEC-CF1 R -ALT -05-E (Revised 10/15) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE CF1R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 2 of 8)
Project Name:TOMMIE MASSENGILL Date Prepared: 12/15/2016
B. Building Insulation Details (Section 150.2(b)i)
01
02
03
04
05
06 07 08 09
10
11
Tag/ID
Assembly Tye
Frame
Type
Frame
Depth
(inches)
Frame
Spacing
(inches)
Proposed
Required
Comments
Cavity
R -value
Continuous
Insulation
R -value
U -factor
AppendixJA4 Reference
U -Factor
Table
Cell
WALLS
WALL
WOOD
2X4
16"OC.
13
N/A
.102
.102
BATTS
FLOOR
FLOOR
WOOD
2X6
16" CO.
19
N/A
.037
.037
BATTS
CEILING
CEILING
WOOD
2X6
24" OC.
30
NA
.031
.031
BATTS
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
Q•
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
,r
CEC-CFIR-ALT-05-E (Revised 10/15) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE CF1R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 3 of 8)
Project Name :TOMMIE MASSENGILL °a`e°`e°a'ee`12/15/2016
C. Roof Replacement (Prescriptive Alteration, Section 150.2(b)1H)
01
02
03
04
05
06
07 08 09 10
11 12 13
Method of
Compliance
Roof
Pitch
Exception
CRRC Product ID
Number
Product Type
R -value
Deck.
Insulation
Proposed
Minimum Required
Initial Solar
Reflectance
Aged Solar
Reflectance
Thermal
Emittance
SRI
(Optional)
Aged Solar
Reflectance
Thermal
Emittance
. SRI
(Optional)
COOL
4/12
D&F
0986-005
SHINGLES
N/A
.70-
PENDING
.85
85
.20
.75
16
Area For All
Fenestration
Area for All
Fenestration
Allowed
Allowed
Allowed
Allowed
-
Alteration
Orientations
Area Only
Orientations
Area
U -factor
U -factor
SHGC
SHGC
Type
I (ft')
(ft)
(ftp)
(ftZ)
(Windows)
I (Skylights)
I (Windows)
I (Skylights)
I Comments
REPLACE
227.4
56.85
156
0
.32
N/A
1 .28
N/A
NO SKYLIGHTS
NOTES:
• Roof area covered by building integrated photovoltaic panels and solar thermal panels are exempt from the above Cool Roof requirements.
• Liquid field applied coatings must comply with installation criteria from section 110.8(i)4,
D. Fenestration/Glazing Allowed Areas and Efficiencies (Section 150.2(b)1)
01
02
03
04
05
06
07
Maximum
Maximum
Allowed
Allowed West-
Existing
Existing
Fenestration
Facing
Fenestration
West -Facing
Maximum
Maximum
Maximum
Maximum
Area For All
Fenestration
Area for All
Fenestration
Allowed
Allowed
Allowed
Allowed
-
Alteration
Orientations
Area Only
Orientations
Area
U -factor
U -factor
SHGC
SHGC
Type
I (ft')
(ft)
(ftp)
(ftZ)
(Windows)
I (Skylights)
I (Windows)
I (Skylights)
I Comments
REPLACE
227.4
56.85
156
0
.32
N/A
1 .28
N/A
NO SKYLIGHTS
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE CF1R-ALT-05-E
Prescriptive Residential.Alterations That Do Not Require HERS Field Verification (Page 4 of 8)
Project Name: TOMMIE MASSENGILL Date Prepared: 12/15/2016
E. Fenestration Proposed Areas and. Efficiencies —Add (Section 150.2(b)1A)
01
02
03
04
05
06
07
08
09
10
11
12
13
14
Tag/ID
Fenestration
Type
Frame
Type
Dynamic
Glazing
Orientation
N, S, W, E
or Roof
Number
of
Panes
Proposed
Fenestration
Area ftZ .
Proposed West
Facing
Fenestration
Area ft
Proposed
1.1 -factor
Source
Proposed
SHGC
Source
Exterior
Shading
Device
Combined
SHGC from
CF1R ENV -03
15
Total Proposed Fenestration Area
16
Maximum Allowed Fenestration Area
17
Compliance Statement
Existing + Proposed Fenestration Areas Maximum Allowed Fenestration Area ❑ Yes ❑ No
18
Total Proposed West -Facing Fenestration Area
19
Maximum Allowed West -Facing Fenestration Area
20
Compliance Statement
Existing + Proposed West -Facing Fenestration Area 5 Maximum Allowed West -Facing Fenestration Area ❑ Yes ❑ No
21
Proposed Fenestration U -factor (Windows)
22
Required Fenestration LI -factor (Windows)
23
Compliance Statement
Proposed Fenestration U -factor 5 Required Fenestration U -factor ❑ Yes ❑ No
24
Proposed Fenestration SHGC (Windows)
25
Required Fenestration SHGC (Windows)
26
Compliance Statement
Proposed Fenestration SHGC 5 Required Fenestration SHGC ❑ Yes ❑ No
27
Proposed Fenestration U -factor (Skylights)
28
Required Fenestration U -factor (Skylights)
29
Compliance Statement
Proposed Fenestration U -factor 5 Required Fenestration U -factor ❑ Yes ❑ No
30
Proposed Fenestration SHGC (Skylights)
31
Required Fenestration SHGC (Skylights)
32
Compliance Statement
Proposed Fenestration SHGC:5 Required Fenestration SHGC ❑ Yes ❑ No
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
STATE OF CALIFORNIA �
'Prescriptive Residential Alterations That Do Not Require HERS Field Verification
CEC-CFIR-ALT-05-E Revised 10/15 CALIFORNIA ENERGY COMMISSION 'qNF'
CERTIFICATE OF COMPLIANCE CF1R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 5 of 8)
Project Name :TOMMIE MASSENGILL oaceP,e°a`ea`12/15/2016
F. Fenestration/Glazing Proposed Areas and Efficiencies — Replace (Section 150.2(b)16)
01
02
03
04
05
06
07
08
9
10
11
12
13
14
Tag/
ID
Fenestration
Type
Frame
Type
Dynamic
Glazing
Orientation
N, S, W, E
Area
Removed
(ft)
Area
Added
(ft)
Net
Added
Area (ft)
U -factor
. Source
SHGC
Source
Exterior
Shading
Device
Combined SHGC
• from
MR -ENV -03
ALL
WINDOWS
VINYL
NO
ALL
156
0
0
.32
1 STICKER
.28
STICKER
NONE
N/A
15
Net Added West -facing Fenestration Area
Q
4
4
-
16
Is Net Added Fenestration Area 5 for west -facing fenestration?
M Yes
❑ No
17
Net Added Fenestration Area (all orientations)
0
18
Is Net Added Fenestration Area 5 0 for all orientations?
M Yes
❑ No
19
Proposed Fenestration U -factor (Windows)
,32
20
Required Fenestration U -factor (Windows)
.32
21
Is the proposed Fenestration U -factor 5 the Required Fenestration U -factor?
N Yes
❑ No
22
Proposed Fenestration SHGC (Windows)
.26
23
Required Fenestration SHGC (Windows)
26
24
Is the Proposed Fenestration SHGC:5 the Required Fenestration SHGC?
N Yes
❑ No
25
Proposed Fenestration U -factor (Skylights)
N/A
�2
Required Fenestration U -factor (Skylights)
N/A
27
Is the proposed Fenestration U -factor 5 the Required Fenestration U -factor?
❑ Yes
❑ No
28
Proposed Fenestration SHGC
N/A
i2
Required Fenestration SHGC
N/A
30
Is the Proposed Fenestration SHGC:5 the Required Fenestration SHGC?
❑ Yes
❑ No
CA Building Energy Efficiency Standards - 2013 Residential Compliance
October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
l e 1'
CEC-CFIR-ALT-OSE (Revised 10/15) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE CF1R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 6 of 8)
Project Name: TOMMIE MASSENGILL Date Prepared: 12/15/2016
G. Space Conditioning (SC) Systems — Heating/Cooling (Prescriptive Section 150.2(b))
Alterations to Space Conditioning Systems shall be exempt from HERS verification requirements as prerequisite for use of the CF1R-ALT-05 and CF2R- ALT -05 Compliance Documents. If new space
conditioning systems are installed or existing systems are altered and are not exempt from HERS verification, then a CRR -ALT -01 shall be completed and registered with a HERS Provider Data
Registry. In each row below for each dwelling unit in the building, check the box that indicates the exemption from HERS verification compliance:
❑ a: space conditioning system was not altered;
❑ b: less than 40 ft of ducts were added or replaced;
❑ c: (exempt from duct leakage testing) if: the existing duct system was insulated with asbestos;
❑ d: (exempt from duct leakage testing) if: the existing ducts stem was previously tested and passed by a HERS Rater. :; F
01
02
03
04
Dwelling Unit Name
SC System Identification or Name
SC System Location or Area Served
Exemption from HERS Verification
HOUSE
NEW ROOF MOUNT PACKAGE
COMPLETE HOME
❑ a ❑ b ❑ c ❑ d
SEER 15, AFUE 90%
❑ a ❑ b ❑ c ❑ d
13 0 . ❑.c 0
0 0 0 0
13 13 0 0
0 0 ❑c 0
13 0 0 11
E3 0 ❑c 0
13 0 0 C3
0 13 0 13
13 0 0 13
13 13 C3 ❑d
13 13 0 0
13 13 E3 0
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That De Not Require HERS Fipirl Vprificatinn
rioliv
CEC-CFI R -ALT -OSE Revised 1D/15)CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE CF1R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 7 of 8)
Project Name:TOMMIE MASSENGILL - Date Prepared:12/15/2016
H. Water Heating Systems (Section 150.2(b)iG)
-
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Dwelling Unit
Name
Water Heating
System
Identification or
Name
Water Heating
System Location
or Area Served
Water
Heating
System
Type
Water
Heater
I Type
g of
Water
Heaters
In System
Water
Heater
Storage
Volume
(gal)
fuel Type
Rated
Input
Type
Rated
Input
Value
Heating
Efficiency
Type
Heating
Efficiency
Value
Standby
Loss
(%)
Exterior
Insulation
R -Value
Back -Up
Solar
Savings
Fraction
HOUSE
W/H
SFR
DHW
STOR.
1
40
GAS
34,000
.62
.6.7
N/A
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
'STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
'EC-CFIR-ALT-05-E (Revised 10/15) CALIFORNIA ENERGY COMMISSION ''"Aw
CERTIFICATE OF COMPLIANCE CF1R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 8 of 8)
°`oleo Name:TOMMIE MASSENGILL Date Prepared: 12/15/20'16
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documenjat' Au or Signature:
MICHAEL F. SROKA
W1/ 1wo
Company:
Signature Date:
SROKAS DESIGN AND DRAFTING SERVICE
12/15/2016
Address:
CEA/ HERS Certification Identification (If applicable):
4140 DAN AVENUE
N/A
City/State/Zip:
Phone:
OLIVEHURST, CA. 945961
530-742-6148
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible
designer).
3. That the energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of
Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
. worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. 1 will ensure that a registered copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency
for all applicable inspections. I understand that a registered copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building
owner at occupancy.
Responsible Designer Name:
Responsible Designer Signature:
MICHAEL F. SROKA
i�•A�Z �ieD/�A
Company:
Date Signed:
SROKAS DESIGN AND DRAFTING SERVICE
12/15/2016
Address:
License:
4140 DAN AVENUE
N/A
City/State/Zlp:
Phone:
OLIVEHURST, CA. 95961
530-742-6148
For assistance or questions regarding the Energy Standards, contact the Energy Hotline at: 1-800-772-3300.
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
' CEC-CF2R-ALT-05-E Revised 10/15
nAI ICr1D\IIA CHIC �!_`V r`r1AA AA1CC1l1AI
CERTIFICATE OF INSTALLATION CF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 1 of 15)
Project Name: TOMMIE MESSENGILL
Enforcement Agency: UTTE COUNTY Perm"Number: B16-1804 '
Dwelling Address: 211 SHELDON AVENUE
c"YGRIDLEY, CA. Zip Code 95953
This compliance document is only applicable to simple alterations that do not require HERS verification for compliance. When HERS verification is required, a CFIR-ALT-01 shall first be registered
with a HERS Provider Data Registry.
Alterations to Space Conditioning Systems that ore exempt from HERS verification requirements may use the CFIR ALT -05 and CF2R- ALT -05 Compliance Documents. Possible exemptions from dud
leakage testing include: less than 40 ft of duds were added or replaced; or the existing dud system was insulated with asbestos, or the existing dud system was previously tested and passed by a
HERS Rater. /f space conditioning systems are altered and are not exempt from HERS verification, then a CFIR ALT -02 must be completed and registered with a HERS Provider Data Registry.
Alterations that utilize close Cell Spray Polyurethane Foam (ccSPF) with a density of 1.5 to less than 2.5 pounds per cubic foot having an R -value other than 5.8 per inch, or Open Cell Spray
Polyurethane Foam (ocSPF) with a density of 0.4 to less than 1.5 pounds per cubic foot having an R -value of 3.6 per inch, shall complete and register a CFIR-ALT-01 with a HERS Provider Data
Registry.
if more than one person has responsibility for installation of the items on this certificate, each person shall prepare and sign a certificate applicable to the portion of construction for which they ore
responsible. Alternatively, the person with chief responsibilityfor construction shall prepare and sign this certificate for the entire construction. All applicable Mandatory Measures shall be met.
Temporary labels shall not be removed before verification by the building Inspector.
A. General Information
01
Project Name:
TOMMIE MESSENGILL
02
Date Prepared:
12/15/2016
03
Project Location:
211 SHELDON AVENUE
04
Building Front Orientation (deg):
SOUTH 180`
05
CA City:
GRIDLEY, CA.
06
Number of Dwelling Units with Additions:
1
07
Zip Code:
95953
08
Fuel Type:
GAS
09
Climate Zone:
11
10
Total Conditioned Floor Area (ft) (Addition):
1137
11
Building Type:
SFR
12
Slab Area (ft):
WOOD FLOOR
13
Project Scope:
REMODEL EXISTING HOUSE,' NO INCRESS IN SIZE
BUTTE COUNTY
BUILDING DIVISION
/A P ® it
99
Fr�e— c 0X
CA Building Energy Efficiency Standards- 2013 Residential Compliance
October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
CEC-CF2R-ALT-05-E (Revised 10/15) CALIFORNIA FNFRGY COMMISSION 0
CERTIFICATE OF INSTALLATION CF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 2 of 15)
°rojec,Name: TOMMIE MESSENGILL — Enforcement Agency:UTTE COUNTY
umber: B16-1804
0wemoenddre55t211 SHELDON AVENUE c"YGRIDLEY, CA.
7p Code 95953
Insulation
The altered components shall comply with all applicable requirements in The Energy Efficiency Standards Sections 110. 7,110.8,150.0; All joints, penetrations and other openings in the building
envelope that are potential sources of air leakage shall be caulked, Basketed, weather stripped, or otherwise sealed to limit infiltration and exhilaration.
B. Roof/Ceiling Insulation
0102
02
03
04
05
06
07
08
09
10
I.D.
Manufacturer & Brand
Framing
Material
Framing Size &
Spacing
Insulation
Type
ESR Number
Cavity Insulation
R -value
Insulation
Depth
(inches)
Above Deck
Insulation
R -value
Below Deck
Insulation
R -value
CEIL
OWENS
WOOD
2X6@16"OC
BATT
30
10"
N/A
N/A
C. Wall Insulation
01
02
03
04
05
06
07
08
09
10
1. D.
Manufacturer & Brand
Framing
Material
Framing Size &
Spacing
Insulation
Type
ESR Number
Cavity Insulation
R -value
Insulation
Depth
(inches)
Exterior Wall
Insulation
R -value
Interior Wall
Insulation
R -value
WALL
OWENS
WOOD
2X4@16"CO.
BATT
13
3.5
N/A
N/A
CA Building Energy Efficiency Standards - 2013 Residential Compliance
October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
CEC-CF2R-ALT-05-E Revised 10115
f
CALIFORNIA ENERGY ENERGY COMMISSION' s•,
CF2R-ALT-05-E
CERTIFICATE OF INSTALLATION
01
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
(Page 3 of 15)
Project Name:TOMMIE MESSENGILL
Enforcement Agency: UTTE COUNTY
Permit Number: 1316-1804
DweurogAdress:211 SHELDON AVENUE
c"YGRIDLEY, CA. -
Zip Code 95953
D. Mass Insulation
01
02
03
04
05
06
07
08
1. D.
Manufacturer & Brand
Location
Mass Thickness
(inches)
Furring Strip Type/
Depth
(inches)
Insulation Type
Exterior Insulation
R -value
Interior Insulation
R -value
N/A
Insulation
Depth
(inches)
Exterior Floor
Insulation
R -value
Interior Floor
Insulation
R -value
FLR
OWENS
WOOD
2X6@16"OC.
BATT
19
5.5"
N/A
N/A
E. Raised Floor Insulation
01
02
03
04
05
06
07
08
09
10
1. D.
Manufacturer & Brand
Framing
Material
Framing Size &
Spacing _
Insulation
Type
ESR Number
Cavity
Insulation
R -value
Insulation
Depth
(inches)
Exterior Floor
Insulation
R -value
Interior Floor
Insulation
R -value
FLR
OWENS
WOOD
2X6@16"OC.
BATT
19
5.5"
N/A
N/A
I F. Slab Floor/Perimeter Insulation
01
02
03
04
05
06
07
08
1. D.
Manufacturer & Brand
Floor Type
Insulation Type
Insulation
Depth (inches)
Insulation
R -Value
Vertical Insulation
Length (inches)
Horizontal Insulation
Length (feet)
N/A
CA Building Energy Efficiency Standards - 2013 Residential Compliance
October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
CEC-CF2R-ALT-05-E Revised 10/15
rA!!Cnonnn C -DC Vnn�A�IlCMl1L1
CERTIFICATE OF INSTALLATION vCF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 4 of 15)
P`ojeoName: TOMMIE MESSENGILL Enforcement Agency:U17E COUNTY
PermltNumber: B16-1804
Dwelling Address: SHELDON AVENUE `k''GRIDLEY, CA.
7p Code 95953 .
Roofing and Radiant Barrier
G. Radiant Barrier
01
Brand Name and Product Number
TECH SHIELD, 1/2"OSB, ATTACHED
02
Installation Type
A
03
Total Attic Area (ft)
1649 HOUSE AND GARAGE
H. Required Vent Area
01
Combined NFA of installed upper and lower vents (int)
18.7
02
Minimum required combined NFA of upper and lower vents (in')
10.92
-03
NFA of installed upper vents (int)
9.5
04
Minimum required NFA of upper vents (in)
5.46
I. Roofing Products (Cool Roof) Installation Information
01
02
03
04
05
06
07
08
Roof Pitch
CRRC Product ID
Number
Product Type
CRRC Listed Aged
Solar Reflectance
Initial Solar
Reflectance
Aged Solar
Reflectance
Thermal Emittance
SRI
4/12
0986-005
SHINGLES
PENDING
70
PENDING
.85
85
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
CEC-CF2R-ALT-05-E (Revised 10/15)
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF INSTALLATION I CF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 5 of 15)
Project Name: TOMMIE MESSENGILL
Enforcement Agency: UTTE COUNTY Permit Number`B16-1804
Dwelling Address:211 SHELDON AVENUE
city GRIDLEY, CA. Zip Code 95953
J. Radiant Barrier and Attic Ventilation — Additional Requirements
Radiant Barrier
01
Radiant barrier must be installed on all vertical surfaces in the attic including gable ends.
02
The emittance of the radiant barrier shall be less than or equal to 0.05 as tested with ASTM C1371, or E408.
03
The product shall meet all requirements for California certified insulation materials [radiant barriers) of the Department of Consumer Affairs, Bureau of Home Furnishings and Thermal
Insulation, as specified by CCR, Title 24, Part 12, Chapter 12-13, Standards for Insulating Material
04
When determining the Total Attic Area, the area over unconditioned spaces such as the garage is included when the attic spaces are connected.
Lower Vents
05 1 Lower vents are within one foot of the eave.
Upper Vents
06 1 Upper vents are within three feet of the ridge
Vent Area
07
The NFA of upper vents must be within required NFA range of upper vents -
Note: per Exception to R806.2 of the CBC Title 24, Part2, Vol.2.5, if the net free ventilating area is less than 1:150, then the upper ventilation must be at least 40% and no more than 50%.
Part 2 contains additional requirements that must be met if the area Is less than 1:150.
The responsible person's signature on this compliance document affirms that all applicable requirements in this table have been met.
K. Roofing Products (Cool Roof) Additional Requirements
01
Any roof area covered by building integrated photovoltaic panels and solar thermal panels are exempt from the above Cool Roof requirements.
02
Liquid field applied coatings must comply with installation criteria from section 110.8(1)4.
03
Mass roof 25 Ib/ft2 or greater: Mass roofs are not required to have a cool roof even if the climate zone specifies minimum performance requirements. -
The responsible person's signature on this compliance document affirms that all applicable requirements in this table have been met.
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verifications
CEC-CF2R-ALT-05-E Revised 10/15 CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF INSTALLATION CF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 6 of 15)
Project Name: TOMMIE MESSENGILL
Enforcement Agency:LITTE COUNTY
FermItNumber: B16-1804
Dwelling Address: SHELDON AVENUE
c"YGRIDLEY, CA.
ZIP Code 95953
Fenestration
L. fenestration/Glazing
01
02
03
04
05
06
07
08
09
10
11
12
Tag/ID
Manufacturer/
Brand
Fenestration
Area (ft)
Orientation
Chromogenic
U -factor
Source
SHGC
Source
Fenestration
Type
Exterior Shading
Devices
(Describe)
Comments/Special Features
ALL
NOT SELECT
156
ALL
NO
.32
STICKE
.28
STICKEF
VINYL
NONE
SLIDERS
M. Fenestration/Glazing—Additional Requirements
01 For existing buildings the U -factor and SHGC values should be the same or better than the required Energy Commission prescriptive requirements.
02 Temporary labels should not be removed until verified by the building inspector.
03 The fenestration product manufacturer's installation specifications shall be followed when installing these products. The space between the fenestration product and
rough opening shall be completely filled with insulation. If batt insulation is used, it is cut to size and placed properly around the fenestration product.
The responsible person's signature on this compliance document affirms that all applicable requirements in this table have been met.
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
STATE OF CALIFORNIA
r Prescriptive Residential Alterations That Do Not Require HERS Field Verification
CEC-CF2R-ALT-05-E (Revised 10/15)
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF INSTALLATION CF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 7 of 15)
Project Name:TOMMIE MESSENGILL Enforcement Age "n`UTTE COUNTY Permit Number: B16-1804
Owellins Address: 211 SHELDON AVENUE ""GRIDLEY, CA. ZIP Cod, 95953
Mechanical and Plumbing
N. Space Conditioning (SC) Systems — Heating/Cooling (Section 150.2(b))
Alterations to Space Conditioning Systems shall be exempt from HERS verification requirements as prerequisite for use of the CF1R-ALT-05 and CF2R- ALT -05 Compliance Documents. If new space
conditioning systems are installed or existing systems are altered and are not exempt from HERS verification, then a MR -ALT -01 shall be completed and registered with a HERS Provider Data
Registry. In each row below for each dwelling unit in the building, check the box that indicates the exemption from HERS verification compliance:
❑ a: space conditioning system was not altered;
❑ b: less than 40 ft of ducts were added or replaced;
❑ c: (exempt from duct leakage testing) if: the existing duct system was insulated with asbestos;
❑ d: (exempt from duct leakage testing) if: the existing duct system was previously tested and passed by a HERS Rater.
01
02
03
04
Dwelling Unit Name
SC System Identification or Name
SC System Location or Area Served
Exemption from HERS Verification
` HOUSE
NEW, ROOF MOUNT PACHKAGE
COMPLETE HOSUE
❑ a ❑ b ❑ c ❑ d
SEER 15, AFUE 90
❑ a ❑ b ❑ c ❑ d
13 0 0 0
0 0 0 0
0 13 0 0
0 Ii 13 c* 11
11 13 0 0
0 13 0 0
0 11 0 0
0 ❑b. 0 0
0 0 0 0
13 0 0 0
0 0 0 0
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
CFr:.(:F9R_AI T_f1iF /Ravi—i 1 nil 51 -
CERTIFICATE OF INSTALLATION - CF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not.Require HERS Field Verification (Page 8 of 15)
P`oje""a`"e`TOMMIE MESSENGILL
Enforcement Age"n`.UTTE COUNTY Permit Number: B 16-1804
Dwelling Address:
211 SHELDON AVENUE
""GRIDLEY, CA.- _ - ziPcode95953 -
O. Installed Water Heating Systems (Section 150.2(b)iG)
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Dwelling Unit
Name
Water Heating
System
Identification or
Name
Water Heating
System Location
or Area Served
Water
Heating
System
Type
Water
Heater
Type
q
Water
Heaters
In System
Water
Heater
Storage
Volume
(gal)
I Fuel Type
Rated
Input
Type
Rated
Input
Value
Heating
Efficiency
Type
Heating
Efficiency
Value
Standby
Loss I%)
Exteeior
Insul.
R -Value
Back-up
Solar
Savings
Fraction
HOUSE
W/H
SFR
DHW
STOR
1
40
GAS
34,000
.62
6.7
N/A
CA Building Energy Efficiency Standards - 2013 Residential Compliance
October 2015
STATE OF CALIFORNIA y
Prescriptive Residential Alterations That Do Not Require HERS Field Verification r : 'PEN
CEC-CF2R-ALT-05-E Revised 10/15 CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF INSTALLATION CF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 9 of 15)
Project Name: TOMMIE MESSENGILL
Enforcement Agency: UTTE COUNTY - Permit Number: B16-1804
oweutng Aderesa:211 SHELDON AVENUE '
"`�GRIDLEY, CA. .. _ Zip `°de 95953-
P. Installed Water Heater Manufacturer Information
01 02 03
Water Heating System ID or Name Manufacturer Model Number
HOUSE WHIRLPOOL 40 GAL GAS MDL#100261189 SER#1643103760479
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
STATE OF CALIFORNIA '
Prescriptive Residential Alterations That Do Not Require HERS Field Verification T
CEC-CF2R-ALT-05-E Revised 10/15 CALIFORNIA ENERGY COMMISSION'
CERTIFICATE OF INSTALLATION _
CF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
(Page 10 of 15)
Project Name: TOMMIE MESSENGILL -
Enforcement Agency: UTTE COUNTY
Permit Number: B16-1804 -
oWemeenaaress:211 SHELDON AVENUE
"t'GRIDLEY, CA.
Z1pCode95953
Lighting
General Lighting Requirements
Additional new lighting, and altered lighting, shall comply with all applicable requirements specified in Section 150.0(k).
Kitchen Lighting Requirements
150.0(k)iC: The wattage of permanently Installed luminaires should be determined as specified in Section 130.0(c),
150,0(k)1C: In the kitchen, Any electrical boxes finished with a blank cover count as 180 watts of low efficacy lighting.
Compliance demonstrated using Method (a) because only high efficacy luminaires have been Installed in the kitchen.
Compliance demonstrated using Method (b). At least 50% of the installed watts from permanently installed high efficacy. Total A;- Total B in Installed Wattage Calculation Table (below)
Compliance demonstrated with additional low efficacy wattage allowance of EXCEPTION to 150(k)3 -
EXCEPTION to 150.0(k)3: Additional low efficacy watts may be allowed when all luminaires in the kitchen are controlled by a vacancy sensor or dimmers, and
1. See 150.0(k)2A where high efficacy and low efficacy luminaires must be separately controlled.
2. See 1500(k)2G where EMCS may be used as a dimmer; Section 150.0(k)2H where EMCS may be used as a vacancy sensor; or, 150.0(k)21 where multi -scene programmable controller may be used
as a dimmer.
NOTES: Compliance demonstrated using Method.(c). Kitchen lighting qualifies for additional low efficacy lighting and as demonstrated in Installed Wattage Calculation Table in Method (b) (above)
In addition to Additional Low Efficacy Wattage Calculation Table (below).
The responsible person's signature on this compliance document affirms that all applicable requirements in this table have been met.
CA Building Energy Efficiency Standards - 2013 Residential Compliance
October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
CEC-CF2R-ALT-05-E Revised 10/15
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF INSTALLATION CF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 11 of 15)
Project Name:TOMMIE MESSENGILL
Enforcement Agency:UTTE COUNTY pe-11Numhe"B16-1804
oweiling Address: 211 SHELDON AVENUE
"" GRIDLEY, CA. Vp Code 95953
Q. Installed Kitchen Lighting Compliance
In each row below for each dwelling unit in the building, check the box that indicates the method of compliance. If required by the enforcement agency, provide a Kitchen Lighting Requirements
Worksheet for each kitchen in the dwelling unit that complies using method b or c.
❑ Method A: Compliance demonstrated using Method (a) - only high efficacy luminaires have been installed in the kitchen.
❑ Method B: At least 50% of installed watts are from permanently installed high efficacy lighting
❑ Method C: Installation qualifies for additional low efficacy lighting allotment
❑ N/A: No kitchen lighting is installed
01
02
03
04
05
Dwelling Unit Name
Kitchen Lighting Compliance Method
Total High Efficacy
(Method B)
Total Low Efficacy
(Method 8)
Total Additional Low Efficacy
(Method C)
C KITCHEN
@a ❑ b ❑ c ❑ N/A
N/A
N/A
N/A
-
13 13 0 ❑N/A
0 0 0 ❑N/A
E3 C3 0 ❑N/A
0 13 0 ❑N/A
13 13 0 - ❑N/A
0 13 0 ❑N/A
0 11 0 ❑N/A
13 13 0 11 N/A
❑ a ❑ b ❑ c ❑ N/A
❑ a ❑ b ❑ c ❑ N/A
13 CI 0 ❑N/A
0 0 0 ❑N/A
0 0 0 ❑N/A
0 0 0 ❑N/A
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
CEC-CF2R-ALT-05-E Revised 10/15
ner irno�ue r�ironv nnu u�ccinu
CERTIFICATE OF INSTALLATION r CF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 12 of 15)
Project Name: TOMMIE MESSENGILL _
Enforcement Agency: UTTE COUNTY - 7e"n1 Nurnbef B16-1804
DwellngAddre55:211 SHELDON AVENUE
Zip Code 95953
""GRIDLEY, CA. I
Kitchen Lighting Requirements Worksheet
Dwelling Unit Name: N/A
This Tahle is annlicahlp nniv if Kitrhpn I lahtina ucina Mpthnrl fhl nr Irl It cplpr•tprl in Tahlp r)
Method b Total Wattage Calculation
Watts from Method (b)
Luminaire Fixture
Total Watts
High Efficacy Low Efficacy
Luminaire Type Watts Watts Quantity
High Low
Efficacy Efficacy
N/A x
=
x
=
x
x
=
x
=
x
=
Complies with method (b) if Total A > Total B
A > B
Method (c) Total Additional Low Efficacy Wattage Calculation
(see footnote
Watts from Method (b)
Additional
Watts
Low Efficacy
High Low
Efficacy Efficacy
Total Low Efficacy
Watts Allowed
N/A
1. Insert 50 if house is <_ 2.500 square feet; Insert 100 if house is > 2,500 square feet.
CA Building Energy Efficiency Standards - 2013 Residential Compliance
October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification ;fir
CEC-CF2R-ALT-05•E Revised 10/15 CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF INSTALLATION CF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 13 of 15)
Project Name: TOMMIE MESSENGILL
Enforcement Agency: UTTE COUNTY Permit Number: B 16-1804
Dwelling Address: 211 SHELDON AVENUE
c"YGRIDLEY, CA. Zip Code 95953 -
Pool and Spa
R. Pool and Spa System Type
of I Pool and Spa System Type N/A NO POOL
S. Pool and Spa Systems and Equipment Requirements (Section 110.4(a) and 110.5)
01 Heater has a thermal efficiency that complies with the Appliance Efficiency Regulations.
02 A readily accessible on-off switch is mounted on the outside of the heater, which allows the heater to be shut off without the user adjusting the thermostat setting.
03 A weatherproof plate or card containing instructions for the energy-efficient operation of the pool or spa heater is permanently mounted:
04 No electric resistance heating except for listed package units that have fully insulated enclosures and tight fitting covers that are insulated to at least R-6. Or if documentation is provided
that at least 60 % of the annual heating energy is from site solar energy or recovered energy.
05 1 Heating system has no pilot light. �-
The responsible person's signature on this compliance document affirms that all applicable requirements in this table have been met.
T. Pool and Spa System Installation Requirements (Section 130.4(b)) �.
01 To allow for the future addition of solar heating equipment, at least 36" of pipe is installed.between the filter and heater, or dedicated suction and return lines are installed, or built-in or
built-up connections for future solar heating are provided.
02 A cover is provided for outdoor pools or spas that have a heat pump or gas heater.
03 Pool system has directional Inlets to adequately mix the pool water
04 Pool system has a time switch that allows the pump to be set or programmed to run during off-peak periods only
The responsible person's signature on this compliance document affirms that all applicable requirements in this table have been met.
CA Building Energy Efficiency Standards - 2013 Residential Compliance
October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
' CEC-CF2R-ALT-05-E (Revised 10/15) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF INSTALLATION CF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 14 of 15)
Project Name:TOMMIE MESSENGILL
E" r°rcement Agency: UTTE COUNTY
Permit number: B 16-1804
Dwelling Address: 211 SHELDON AVENUE I
CRY GRIDLEY, CA..
Zip Code 95953
U. Pool
Pump Sizing and Flow Rate Specification (Section 150.0(p))
01
The pool pump specified is listed In the CEC database of certified pool pumps.
02
The pool pump flow rate shall not exceed the maximum pump flow rate calculated based on pool sizing in the table below. The return pipe diameter, suction pipe diameter, and filter area
shall be at least as large as the required minimums shown in the table.
Alternatively, a flow calculation or flow test result shall be provided to demonstrate that the pump flow rate is less than 6 hour filtration turnover, and the return pipe flow rate
does not exceed 8 feet per second and that the suction pipe flow rate does not exceed 6 feet per second.
03
An alternative compliance calculation or a flow test result Is provided for this pool or spa
use. (must attach flow calculation or flow test result to this form)
N/A NO POOL
04
The pump is capable of operating at 2 or more speeds (not applicable if pump is less than 1 horsepower).
05
Each auxiliary pool load is served by either a separate pump, or the system is served by a multi -speed pump.
06
Volume of pool (gallons):
N/A
07
Filter Type (Cartridge, Sand, DE):
N/A
08a
Required Min Return Pipe Diameter (inches)
08b
Required Min Suction Pipe Diameter (inches)
08c 08d
Required Min Filter Area (ft) Required Max Pump Flow (gpm)
09
Return Pipe Diameter (inches).
10
Suction Pipe Diameter (inches).
11
Filter Surface Area (ft 2).
12
Max Pump Flow Rate (gallons per minute).
13
Measured flow rate return line (feet per second)
14
Measured flow rate suction line (feet per second)
15
Compliance statement U. 03 = Yes, U. 135 U. 08, and U. 14:5 U. 06 ❑ Yes ❑ No
The responsible person's signature on this compliance document affirms that all applicable requirements in this table have been met.
V. Pool System Piping (Section 150.0(p)2)
01
The suction side pipe is straight for at least 4 pipe diameters before entering the pump (See table below for the required straight run lengths for various pipe sizes).
02
All elbows are sweep elbows, or an elbow type that has a pressure drop that is less than the pressure drop
of a straight pipe with a length of 30 pipe diameters.
The responsible person's signature on this compliance document affirms that all applicable requirements in this table have been met.
W. Pool Filters and Valves (Section 150.0(p)3 and 4)
01 If a filter is used in a pool intended for public use: The size of the filter is at least the size specified in NSF/ANSI 50.
02 If a backwash valve is used: The diameter of the backwash valve is at least 2 inches, or the diameter of the return pipe, whichever is greater.
The responsible person's signature on this compliance document affirms that all applicable requirements in this table have been met.
CA Building Energy Efficiency Standards - 2013 Residential Compliance October 2015
STATE OF CALIFORNIA
Prescriptive Residential Alterations That Do Not Require HERS Field Verification
CEC-CFMALT-OSE !Revised MIS)
CERTIFICATE OF INSTALLATION vCF2R-ALT-05-E
Prescriptive Residential Alterations That Do Not Require HERS Field Verification (Page 15 of 15)
Project Name: TOM M IE MESSENGILL enn: UTTE COUNTY -
p""'" Number: B16-1804
owelu"eAddress:211 SHELDON AVENUE C"YGRIDLEY, CA.
Zip Code 95953
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Installation documentation is accurate and complete.
Documentation Author Name:
MICHAEL F. SROKA
D u ent t MSI ure: _ ��
Documentation Author Company Name:
SROKAS DESIGN AND DRAFTING SERVICE
Date Signed:
12/16/2016
Address:
4140 DAN AVE
CEA/HERS Certification Identification (If applicable):
City/State/Zlp:
OLIVEHUkST CA. 95961
Phone:
530-742-6148
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Installation is true and correct. -
2. 1 am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction, or Installation of features,
materials, components, or manufactured devices for the scope of work identified on this Certificate of Installation, and attest to the declarations in this statement (responsible
builder/installer), otherwise I am an authorized representative of the responsible builder/installer.
3. The constructed or installed features, materials, components or manufactured devices (the installation) identified on this Certificate of Installation conforms to all applicable codes and
regulations, and the installation conforms to the requirements given on the plans and specifications approved by the enforcement agency.
4. 1 reviewed a copy of the Certificate of Compliance approved by the enforcement agency that identifies the specific requirements for the scope of construction or installation identified on this
Certificate of Installation, and I have ensured that the requirements that apply to the construction or installation have been met.
S. I will ensure that a registered copy of this Certificate of Installation shall be posted, or made available with the building permit(s) issued for the building, and made available to the
enforcement agency for all applicable inspections. I understand that a registered copy of this Certificate of Installation is required to be included with the documentation the builder provides
to the building owner at occupancy.
Responsible Builder/Installer Name:
MICHAEL F. SROKA
es on ' �u' r ns r Si Wurn��
,� �
Company Name: (Installing Subcontractor or General Contractor or Builder/Owner)
SROKAS DESIGN AND SRAFTING SERVICE
Position With Company (Title):
OWNER
Address:
4140 DAN AVE
CSLB License:
N/A
City/State/Zip:
OLIVEHURST CA. 95961
Phone
530-742-6148
Date Signed:
12/16/2016
For assistance or questions regarding the Energy Standards, contact the Energy Hotline at: 1-800-772-3300:
CA Building Energy Efficiency Standards - 2013 Residential Compliance
October 2015
BUTTE COUNTY DEPARTMENT ELOPM1 I
EV I . ENT SERVIC ES:-B.VJL01NG
CONSTRUCTION DEBRIS RECOVERY
ECbVERY FWAL REPORT
Final inspection will not be s;6hedu1dtf-'u*,n6j-coffi*pl6t6d report subhiht6d
L-�22e-l— jq
APN:
Building '%Pennft*
Owner Name
Owner Phoh6:
Job9fte Addr"s:
-PiVjbct Type:'. 0 ConstruC A. QPeubn(itlorn
4
50 -mit comp.leted form in person or by
mail 40:
'Butte County Development Services
Building
7 County Center Drive
Orovitlej CA 95965
4v site Contact.
Gompa
Rouse 'MATERIAL'
.-
Tonne.. T.oT ACTUAL FA. 'ACEI
PROVIDER$ USED
Inert Material (Concrete, asphalt)
Lumber.
PlanIffree.-Debris.
Dry Wall..
Metal
Cardboard
Other:
Other.
Total tops of mate rib! - d isposed..O'f'. (,not. r6byci6d, or--'Fe't�e,d)
Total tons of material. not diseased j6ithe'ribe'J 'Os4p
Percent recydl'ed/reu5ed
Please sign i'ndic:a'tihg that *the above. infor"mifion is true and . correct to:t4e 6'F 'ydu
r:kn6w1edgp:
Applicant
(Owner or Contractor): Date:
Circle which
receipts, gate tags, or
:q(W verifying -information --for all materials
that were reuse recycled or disposed.
Final Report returned with cotrr rents:: -
Date.
Final Report. approvod.1:(B6IfdM r4
UBUILDING\201 I \App'roved form s\Res Green Bldg. f6tm-`s\W
aste-.D1V6rsiorr,-Recyqfing f-Qrms;d6c
2013 Low -Rise Residential Mandatory Measures Summary
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the
compliance approach used Exceptions may apply. Review the respective code section for more information.
Building Envelope Measures:
§ 110.6(a)1:
Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
110.6(a)5:
Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient (SHGC), and infiltration that meets the requirements of § 10-111(a).
§110.7:
Exterior doors and windows are weatherstripped; all joints and penetrations are caulked and sealed.
§ 110.8(a):
insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the CF2R.
§110.8(1):
The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of § 110.8(i) when the
installation of a cool roof is specified on the CIF IR.
§110 : go):
A radiant barrier shall have an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CF1R.
Minimum R-30 insulation in wood -frame ceiling; or the weighted average U -11 -actor shall not exceed 0.031. Minimum R-19 in a
§150.0(a):
rafter roof alteration. Attic access doors shall have permanently attached insulation using adhesive or mechanical fasteners. The
attic access shall be gasketed to prevent air leakage.
§150.0(b):
Loose fill insulation shall conform with manufacturer's installed design labeled R -value.
I50.0(c):
Minimum R-13 insulation in 2x4 inch wood framing wall or have a U -factor of 0.102 or less (R-19 in 2x6 or 0.074 maximum U -
factor).
§ 150.0(d):
Minimum R-19 insulation in raised wood -frame floor or 0.037 maximum U -factor.
In Climate Zones 14 and 16 a Class H vapor retarder shall be installed on the conditioned space side of all insulation in all exterior
§150.0(g)l:
walls, vented attics and unvented attics with air -permeable insulation.
In Climate Zones 1-16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a Class 1 or Class 11
§150.0(g)2:
vapor retarder.
In a building having a controlled ventilation crawl space, a Class I or Class H vapor retarder shall be placed over the earth floor of
§150.0(g)3:
the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section
150.0(d).
§150.00):
Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.3%,
have water vapor permeance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration;
and when installed as part of a heated slab floor meets the requirements of § 110.8
150.0
§ (q)'
Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U-
factor of 0.58; or the weighted average U -factor of all fenestration shall not exceed 0.58_
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
§150.0(e)IA:
Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150.0(e)1B:
Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a readily accessible, operable, and tight -fitting damper or a combustion -air control device. _ - �_V%J
§ I50.0(e) I C:
Masonry or factory -built fireplaces have a flue damper with a readily accessible control. ,� r.OUV+ °. Nta
§150.0(e)2:
Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is "' "6d`to'the"outside
v
of the building, are rohibited t'11 t�� ,..
Space Conditioning, Water Heating and Plumbing System Measures:�1�
§110.0-§110.3:
HVAC equipment, water beaters, showerheads, faucets and all other regulated appliancesl*re*re "cert&Jkto the Commission.
r
Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation
§ 110.3(c)5:
valve, and recirculation loop connection requirements of §110.3(c)5.
Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appli-
§ 110.5:
antes without an electrical supply voltage connection with pilot fights that consume less than 150 Btu/hr are exempt), and pool
ands a heaters.
§ 150.0(b)1:
Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified
in §150.0(h)2.
§150.0(h)3A:
Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least five feet from the outlet of any
dryer vent.
§ I50.0(i):
Heating systems are equipped with thermostats that meet the setback requirements of § 110.2(c).
§150.06)IA:
Storage gas water heaters with an energy factor equal to or less than the federal minimum standards shall be externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§150.00)1B:
Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water -heating systems, have R-12 external
insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the tank.
For domestic hot water system piping, whether buried or unburied: the first 5 feet of hot and cold water pipes from the storage
tank, all piping with a nominal diameter of 3/4 inch or larger, all piping associated with a domestic hot water recirculation system
•§150.00)2A:
regardless of the pipe diameter, piping from the heating source to storage tank or between tanks, piping buried below grade, and
all hot water pipes from the heating source to kitchen fixtures must be insulated according to the requirements of TABLE 120.3-
A. BUTTE
§150.00)2B:
All domestic hot water pipes that are buried below grade must be installed in a water proof and non -crushable Ea�jq#Wlt eve
that allows for installation, removal, and replacement of the enclosed pipe and insulation.
��• (��� DEC 2 2 2616
DEVEL0P.ME-NT
r•rrri/'CC'
2013 Low -Rise Residential Mandatory Measures Summary
§ I50.00)2C:
Pipe for cooling system lines shall be insulated as specified in § 150.00)2A_ Piping insulation for steam and hydronic heating
systems or hot waters stems with pressure > 15 psig shall meet therequirements in TABLE 120.3-A.
§150.06)3:
Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Insulation exposed to weather shall either be rated for outdoor use or installed with a cover suitable for outdoor service. For
§150-00)3A--
example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation protected as specified or
anted with coating that is water retardant and provides shielding from solar radiation that degrades the material.
Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I
§150.00)3B:
or Class H vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class H vapor
retarder.
Systems using gas or propane water heaters to serve individual dwelling units shall include: a 120V electrical receptacle within 3
feet of the water heater, a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the
§ 150.0(n)1:
space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the installed
water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000
Btu/hr.
§150.0(n)2:
Recirculating loops serving multiple dwelling units shall meet the requirements of § 110.3(c)5.
§ 150.0(n)3:
Solar water -heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC)
or by a testing agency approved by the Executive Director.
Ducts and Fans Measures:
All air -distribution system ducts and plenums installed are sealed and insulated to meet the requirements of CMC §601.0, §602.0,
§603.0, §604.0, §605.0 and ANSUSMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition.
Supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-6.0 (or higher if required by CMC
§605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing
(RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts are mechanically fastened Openings shall be sealed
§150.0(m)1:
with mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181B or
aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than Y. inch, the
combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums
defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying
conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms
shall not be compressed to cause reductions in the cross-sectional area of the ducts.
Factory -Fabricated Duct Systems shall comply with specified requirements for duct construction, connections, and closures; joints
§150.0(m)2:
and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is
used in combination with mastic and draw bands_
§ I50.0(m)3-6:
Field -Fabricated Duct Systems shall comply with requirements for: pressure -sensitive tapes, mastics, sealants, and other
requirements specified for duct construction; duct insulation R -value ratings; duct insulation thickness; and duct labeling.
§150.0(m)7:
All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic
dampers.
§150.0(m)8:
Graviy ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers
except combustion inlet and outlet air openings and elevator shaft vents.
Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not
§ 150.0(m)9:
limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum,
sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is
water retardant and provides shielding from solar radiation.
§150.0(m)10:
Flexible ducts cannot have porous inner cores.
When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be
§150.0(m)l l:
sealed and dud leakage tested, as confirmed through field verification and diagnostic testing, in accordance with Reference
Residential Appendix RA3.
Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal
§ 150.0(m)12:
conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of
§ 150.0(m)12.
Space conditioning systems that utilize forced air duds to supply cooling to an occupiable space shall have a hole for the
placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum. The
§150.0(m)13:
space conditioning system must also demonstrate airflow > 350 CFM per ton of nominal cooling capacity through the return
grilles, and an air -handling unit fan efficacy:5 0.58 W/CFM as confirmed by field verification and diagnostic testing, in
accordance with Reference Residential Appendix RA3.
Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode,
§ 150.0(m)15:
an airflow from the dwelling, through the air handler fan and delivered to the dwelling, of> 350 CFM per ton of nominal cooling
capacity, and operating at an air -handling unit fan efficacy of:S 0.58 W/CFM as confirmed by field verification and diagnostic
testing, in accordance with Reference Residential Appendix RA3.
All dwelling units shall meet the requirements of ASHRAE Standard 62.2. Neither window operation nor continuous operation of
§150.0(0):
central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of providing the
Whole Building Ventilation.
§150.0(o)1A:
Whole Building Ventilation airflow shall be confirmed through field verification and diagnostic testing, in accordance with
Reference Residential Appendix RA3.
Pool and Spa Heating Systems and Equipment Measures:
Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
§ 110.4(a):
Regulations; an on-off switch mounted outside of the heater that allows shutting off the heater without adjusting the thermostat
setting-, a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating.
2013 Low -Rise Residential Mandatory Measures Summary
§ 110.4(b)1:
Any pool or spa beating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction
and return lines, or built-up connections for future solar heating.
§ 110.4(b)2:
Outdoor pools or spas that have a heat pump or gas heater shall have a cover.
§ 110.4(b)3:
Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or pro -
ed to run only during off-peak electric demand periods.
§110.5:
Natural gas pool and spa heaters shall not have a continuous burning pilot light.
§150.0(p):
Residential pool systems or equipment shall meet specified pump sizing, flow rate, piping, filters, and valve requirements.
Lighting Measures:
§ 110.9:
All lighting control devices and systems, ballasts, and luminaires shall meet the applicable requirements of § 110.9.
§ I50.0(k) IA:
Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with §150.0(k) in accordance with TABLE
150.0-A or TABLE 150.0-13, as applicable.
§150.0(k)113:
When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply
with the applicable provisions of § 150.0
The wattage and classification of permanently installed luminaires in residential kitchens shall be determined in accordance with
§150.0(k)1C:
§130.0(c). In residential kitchens, the wattage of electrical boxes finished with a blank cover or where no electrical equipment has
been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as 180
watts of low efficacy lighting r electrical box.
§150.0(k)1D:
Ballasts for fluorescent lamps rated 13 watts or greater shall be electronic and shall have an output frequency no less than 20 kHz.
Permanently installed night lights and night. fights integral to installed luminaires or exhaust fans shall be rated to consume no
§150.0(k)IE:
more than 5 watts of power per luminaire or exhaust fan as determined in accordance with §130.0(c). Night lights do not need to
be controlled by vacancy sensors.
§150.0(k)1F:
Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable
requirements of §150.0
§150.0(k)2A:
High efficacy luminaires must be switched separately from low efficacy luminaires.
§ 150.0(k)2B:
Exhaust fans shall be switched separately from lighting systems.
§150.0(k)2C:
Luminaires shall be switched with readily accessible controls that permit the luminaires to be manually switched ON and OFF.
§ I50.0(k)2D:
Controls and equipment are installed in accordance with manufacturer's instructions.
§ 150.0(k)2E:
No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with §150.0(k).
§150.0(k)2F:
Lighting controls comply with applicable requirements of §110.9.
An Energy Management Control System (FMCS) may be used to comply with dimmer requirements if: it functions as a dimmer
§ 150.0(k)2G:
according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements of § 130.5; and all other
requirements in § 150.0 2.
An Energy Management Control System (FMCS) may be used to comply with vacancy sensor requirements of §I50.0(k) if. it
§ 150.0(k)2H:
functions as a vacancy sensor according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements
of § 130.5; and all other requirements in § 150.0(k)2.
§150.0(k)21:
A multiscene programmable controller may be used to comply with dimmer requirements of this section if it provides the
functionality of a dimmer according to § 110.9, and complies with all other applicable requirements in §150.0(k)2.
§150.0(k)3A:
A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only
§ 150.0(k)3B:
the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are
considered kitchen lighting if they are not separately switched from kitchen lighting.
§ 150.0(k)4:
Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated
cabinet.
§I50.0(k)5:
A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom
shall be high efficacy or controlled by vacancy sensors_
§I50.0(k)6:
Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§150.0(k)7:
Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high
efficacy, or shall be controlled by either dimmers or vacancy sensors.
Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (1C) by Underwriters Laboratories or other
nationally recognized testingtrating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0
CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing
§150.0(k)8:
and ceiling, and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and
allow ballast maintenance and replacement without requiring cutting holes in the ceiling.
For recessed compact fluorescent luminaries with ballasts to qualify as high efficacy for compliance with §150.0(k), the ballasts
shall be certified to the Energy Commission to comply with the applicable requirements in § 110.9.
For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the
same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of Items ii or iii below; and
§ 150.0(k)9A:
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically
reactivates the motion sensor within 6 hours; and
iii. Controlled by one of the following methods:
2013 Low -Rise Residential Mandatory Measures Summary
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b_ Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is
programmed to automatically tum the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements: At a minimum provides the functionality of
an astronomical time clock in accordance with § 110.9; meets the Installation Certification requirements in § 130.4; meets the
requirements for an EMCS in §130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically tum the outdoor lighting OFF during daylight hours_
For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor
lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
§150.0(k)9B:
following requirements:
i_ Shall comply with §150.0(k)9A; or
ii. Shall comply with the applicable requirements in §110.9, §130.0, § 130.2, § 130.4, §140-7 and § 141.0.
§150.0(k)9C:
For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by §150.0(k)9B or 150.0(k)9D
shall comply with the applicable requirements in §110.9, §130.0, §130.2, §130.4, §140.7 and §141.0.
§150.0(k)9D:
Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall comply
with the applicable requirements in § 110.9, § 130.0, § 130.2, § 130.4, § 140.7 and § 141.0.
§150.0(k)10:
Internally illuminated address signs shall comply with §140.8; or shall consume no more than 5 watts of power as determined
according to §130.0(c).
§ 150.0(k)11:
Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for
nonresidential garages in §110.9, §130.0, §130.1, §130.4, §140.6, and §141.0.
In a low-rise multifamily residential building where the total interior common area in a single building equals 20 percent or less of
§ 150.0(k)12A:
the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or
controlled by an occupant sensor.
In a low-rise multifamily residential building where the total interior common area in a single building equals more than 20
percent of the floor area, permanently installed lighting in that building shall:
§ 150.0(k)12B:
i. Comply with the applicable requirements in § 110.9, §130.0, § 130.1, §140.6 and § 141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of
ingress and egress.
Solar Ready Buildings:
Single family residences located in subdivisions with ten or more single family residences and where the application for a
§110.10(a)l:
tentative subdivision map for the residences has been deemed complete, by the enforcement agency, on or after January 1, 2014,
shall comply with therequirements of § 110.10(b) through § 110.10(e).
§110.10(a)2:
Low-rise multi -family buildings shall comply with the requirements of § 110.10(b) through § 110.10(d)_
The solar zone shall have a minimum total area as described below. The solar zone shall comply with access, pathway, smoke
ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a
local jurisdiction. The solar zone total area shall be comprised of areas that have no dimension less than 5 feet and are no less than
80 square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for
§110.10(b)l:
buildings with roof areas greater than 10,000 square feet.
For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less
than 250 square feet. For low-rise multi -family buildings the solar zone shall be located on the roof or overhang of the building or
on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the
building project and have a total area no less than 15 percent of the total roof area of the building excluding any skylight area
§ 110.10(b)2:
All sections of the solar zone located on steep -sloped roofs shall be oriented between 110 degrees and 270 degrees of true north.
§ 110.10(b)3A:
No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equipment, shall be
located in the solar zone.
Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least twice
§ 110.10(b)3B:
the distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the
horizontal projection of the nearest point of the solar zone, measured in the vertical plane.
§ 110.10(b)4:
For areas of the roof designated as solar zone, the structural design loads for roof dead load and roof live load shall be clearly
indicated on the construction documents.
The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit
§110.10(c):
from the solar zone to the point of interconnection with the electrical service (for single family residences the point of
interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water -heating
system.
§ 110.10(d):
A copy of the construction documents or a comparable document indicating the information from § 110.10(b) through § 110.10(c)
shall be provided to the occupant.
§ 110.10(e)1:
The main electrical service panel shall have a minimum busbar rating of 200 amps.
The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a
§ 1 10.10(e)2:
future solar electric installation. The reserved space shall be: positioned at the opposite (load) end from the input feeder location or
main circuit location, and permanently marked as "For Future Solar Electric".
/3
m
BUTTE
42'-0'
FEB O S 2L ,r
DEVELOPMENT
SERVICES
I
�I
9�
,Ga rage
"
Li ving
16'-0' x 30'-0' Y
480sq.R. � N
�
42'-0' x 24'-0'
1008sq.R.» BUTTE
COlN
`
`
�BgLDING
DIVISION
APPROVED
m
BUTTE
42'-0'
FEB O S 2L ,r
DEVELOPMENT
SERVICES
BUTTE COVNqT`'� N
�, �1�1�1� WALL CONSTRUCTION
BUILgIN
TABLE 9602.3(1-)
FASTENER SCHEDULE FOR STRUCTURAL MEMBERS
ITEM
DESCRIPTION OF BUILDING ELEMENTS
NUMBER AND TYPE OF FASTENER
°•
SPACING OF FASTENERS
Roof
1
Blocking between joists or rafters to top plate, toe nail
3-8d (2'/2" x 0.113')
-
2
Ceiling joists to' plate, toe nail
3-8d (2'/2" x 0.113'
-
3
Ceiling joists not attached to parallel rafter, laps over parti-
tions, face nail
3-10d
-
4
Collar tie to rafter, face nail or 1'/," x 20 gage ridge strap
3-10d (3" x 0.128')
-
5
Rafter or roof truss to plate, toe nail
3-16d box nails (3'/2" x 0.135')
or 3-10d common nails
(3" x 0.148')
2 toe nails on one side and 1 toe nail on
opposite side of each rafter or truss'
6
Roof rafters to ridge, valley or hip rafters: toe nail face nail
4-16d (3'/2" x 0.135')
3-16d (3'/2 " x 0.135')
-
Wall
7
Built-up studs -face nail
IOd (3" x 0.128')
24" o.c.
8
Abutting studs at intersecting wall corners, face nail
16d (3 `/2" x 0.135")
12" o.c.
9
Built-up header, two pieces with '/2" spacer
16d (3'/2" x 0.135')
16" o.c. along each edge
10
Continued header, two pieces .
16d (3'/2" x 0.135')
16" o.c. along each edge
11
Continuous header to stud,.toe nail
4-8d (2`/2" x 0.113')
-
12
Double studs, face nail
10d (3" x 0.128')
24" o.c.
13
Double top plates, face nail
10d (3" x 0:128')
24" o.c.
14
Double top plates, minimum 24 -inch offset of end joints,
face nail in lapped area
g_16d (3`/2" x 0.135'
-
15
Sole plate to joist or blocking, face nail
16d (3'/2"2x 0.135')
16" o.c.
16
Sole plate to joist or blocking at braced wall panels
3-16d (3'/2" x 0.135')
16" o.c.
17
Stud to sole plate, toe nail
3-8d (2'/2" x 0.113')
or
2-16d (3'/2" x 0.135')
-
-
18
Top or sole plate to stud, end nail
2-16d (31/2" x 0.135')
-
19
Top plates, laps at corners and intersections, face nail
2-I0d (3" x 0.128')
-
20
1 " brace to each stud and plate, face nail
2-8d (2'/2" x 0.113')
2 staples 13/,"0.
-
-
21
1" x 6" sheathing to each bearing, face nail
2-8d (2`/2" x 13/,,,
2 staples 1 /,"
-
-
22
1 " x 8" sheathing to each bearing, face nail
2-8d (2`/2" x 0.113'
3 staples 1 /,"
-
-
23
Wider than 1 " x 8" sheathing to each bearing, face nail
3-8d (2'/2" x 0.113'
4 staples 1 /,"
-
-
Floor
24
Joist to sill or girder, toe nail
3-8d (21/2" x 0.113')
-
25
Rim joist to top plate, toe nail (roof applications also)
8d (2'/2" x 0.113')
6" o.c.
26
Rim joist or blocking to sill plate, toe nail
8d (2'/2" x 0.113')
6" o.c.
27
1 " x 6" subfloor or less to each joist, face nail
2-8d (2'/2" x 0.113'
2 staples P/,,"
-
-
28
2" subfloor to joist or girder, blind and face nail
2-16d (3`/2" x 0.135')
-
29
2" planks (plank & beam - floor & roof)
2-16d (3'/2" x 0.135')
at each bearing
30
Built-up girders and beams, 2 -inch lumber layers
1 O (3" x 0.128')
Nail each layer as follows: 32" o.c. at
top and bottom and staggered.
Two nails at ends and at each splice.
31
Ledger strip supporting joists or rafters
3-16d (3'/2" x 0.135')
At each joist or rafter
2013 CALIFORNIA RESIDENTIAL CODE
(continued)
199
WALL CONSTRUCTION
TABLE R602.3(1) --continued
FASTENER SCHEDULE FOR STRUCTURAL MEMBERS
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s; 1 Ksi = 6.895 MPa.
a. All nails -are smooth -common; box or deformed shanks except where otherwise stated. Nails used for framing and sheathing connections shall have minimum
average bending yield strengths as shown: 80 ksi for shank diameter of 0:192 inch (20d common nail), 90 ksi for shank diameters larger than 0.142 inch but
not larger than 0.177 inch, and 100 ksi for shank diameters of 0.142 inch or less.
b. Staples are 16 gage wire and have a minimum'/16 inch on diameter crown width.
c. Nails shall'be spaced at not more than 6 inches on center at all supports where spans are 48 inches or greater.
d. Four -foot by 8 -foot or 4 -foot by 9 -foot panels shall be applied vertically. - "
e. Spacing of fasteners not included in this table shall be based on Table R602.3(2).
f. For regions having basic wind speed of 110 mph or greater, 8d deformed (21/2" x 0.120) nails shall be used for attaching plywood and wood structural panel
roof sheathing to framing within minimum 48 -inch distance from gable end walls, if mean roof height is mote than 25 feet, up to 35 feet maximum.
g. For regions having basic wind speed of 100 mph or less, nails for attaching wood structural panel roof sheathing to gable end wall framing shall be spaced 6
inches on center. When basic wind speed is greater than 100 mph, nails for attaching panel roof sheathing to intermediate supports shall be spaced 6 inches on
center for minimum 48 -inch distance from ridges, eaves and gable end walls; and 4 inches on center to gable end wall framing.
h. Gypsum sheathing shall conform to ASTM C 1396 and shall be installed in accordance with GA 253. Fiberboard sheathing shall conform to ASTM C 208.
i. Spacing of fasteners on floor sheathing panel edges applies to panel edges supported by framing members and required blocking and at all floor perimeters
only. -Spacing of fasteners on roof sheathing panel edges applies to panel edges supported by framing members. and, required blocking. Blocking of roof or
floor sheathing panel edges perpendicular to the framing members need 'not be provided except as required by other provisions of this code. Floor.perimeter
shall be supported by framing members or solid blocking.
j. Where a rafter is fastened to an adjacent parallel ceiling joist in accordance with this schedule, provide two toe nails on one side of the rafter and toe nails from
the ceiling joist to top plate in accordance with this schedule. The toe nail on the opposite side of the rafter shall not be required.
200 2013 CALIFORNIA RESIDENTIAL CODE
SPACING OF FASTENERS
ITEM
DESCRIPTION OF BUILDING MATERIALS
DESCRIPTION OF FASTENER °•`•°
Edges
Intermediate supports`•°
(inches)'
(inches)
Wood structural panels, subfloor, roof and interior wall sheathing to framing and particleboard wall sheathing.to framing
32 3/ „ _ 1/ „ 6d common (2" x 0.113') nail (subfloor, wally a
s z 6 12
8d common (2'/2" x 0.131' nail (roof)'
33 19/32 I - 1 " 8d common nail (2'/2" x 0.131') 6 129
34 11/$ , _ 11/4„ 10d common (3" x 0.148') nail or 6 12
8d (2'/2" x 0.131') deformed nail
Other wall sheathing"
35/z"
structural cellulosic
1'/2" galvanized roofing nail,'/16" crown or 1" crown
fiberboard sheathing
staple 16 ga., 1'/4" long
3
6
36
u/32" structural cellulosic
13/4" galvanized roofing nail,'/16" crown or 1"crown
fiberboard sheathing
staple 16 ga., 1'/2" long
3
6
37
'/2" gypsum sheathing°
1'/," galvanized roofing nail; staple galvanized,
7
7
1 /2" long; 1'/, screws, Type W or S
38
s/8"gypsum sheathing'
1/4galvanized roofing nail; staple galvanized,
7
7
15/,,, long; 15/8" screws, Type W or S
W.00d.`structural- anels;.combinaUonsu6floor-underla mentto-framIn
--39—
— --- 3N=and-less— --
6d deformed 2" x 0_120' nail or
°
8d common (2'12!'•x 0. 13 10 nail
40
7/ „ _ 1 "
s
8d'common (21/2" x 0.131') nail or
6
12
8d deformed (2'/2" x 0.120') nail
41
11/8 _ 11/4
10d common (3"' x 0.148') nail or
6
12
8d deformed (2'/ 2 " x 0.120') nail
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s; 1 Ksi = 6.895 MPa.
a. All nails -are smooth -common; box or deformed shanks except where otherwise stated. Nails used for framing and sheathing connections shall have minimum
average bending yield strengths as shown: 80 ksi for shank diameter of 0:192 inch (20d common nail), 90 ksi for shank diameters larger than 0.142 inch but
not larger than 0.177 inch, and 100 ksi for shank diameters of 0.142 inch or less.
b. Staples are 16 gage wire and have a minimum'/16 inch on diameter crown width.
c. Nails shall'be spaced at not more than 6 inches on center at all supports where spans are 48 inches or greater.
d. Four -foot by 8 -foot or 4 -foot by 9 -foot panels shall be applied vertically. - "
e. Spacing of fasteners not included in this table shall be based on Table R602.3(2).
f. For regions having basic wind speed of 110 mph or greater, 8d deformed (21/2" x 0.120) nails shall be used for attaching plywood and wood structural panel
roof sheathing to framing within minimum 48 -inch distance from gable end walls, if mean roof height is mote than 25 feet, up to 35 feet maximum.
g. For regions having basic wind speed of 100 mph or less, nails for attaching wood structural panel roof sheathing to gable end wall framing shall be spaced 6
inches on center. When basic wind speed is greater than 100 mph, nails for attaching panel roof sheathing to intermediate supports shall be spaced 6 inches on
center for minimum 48 -inch distance from ridges, eaves and gable end walls; and 4 inches on center to gable end wall framing.
h. Gypsum sheathing shall conform to ASTM C 1396 and shall be installed in accordance with GA 253. Fiberboard sheathing shall conform to ASTM C 208.
i. Spacing of fasteners on floor sheathing panel edges applies to panel edges supported by framing members and required blocking and at all floor perimeters
only. -Spacing of fasteners on roof sheathing panel edges applies to panel edges supported by framing members. and, required blocking. Blocking of roof or
floor sheathing panel edges perpendicular to the framing members need 'not be provided except as required by other provisions of this code. Floor.perimeter
shall be supported by framing members or solid blocking.
j. Where a rafter is fastened to an adjacent parallel ceiling joist in accordance with this schedule, provide two toe nails on one side of the rafter and toe nails from
the ceiling joist to top plate in accordance with this schedule. The toe nail on the opposite side of the rafter shall not be required.
200 2013 CALIFORNIA RESIDENTIAL CODE
WALL CONSTRUCTION
TABLE R602.3(2)
ALTERNATE ATTACHMENTS TO TABLE R602.3(1)
NOMINAL MATERIAL THICKNESS
(Inches)
DESCRIPTION 0. b OF FASTENER AND LENGTH
(inches)
SPACING`OF FASTENERS
Edges
(inches)
Intermediate supports
(inches)
Wood structural panels subfloor, roofs and wall sheathing to framing and particleboard wall sheathing to framing'
Up to V,
Staple 15 ga. 13/a 4 8
0.097 - 0.099 Nail 2'/4 3 6
Staple 16 ga. 13/a 3 6
19/32 and s/a
0.113 Nail 2 3 6
Staple 15 and 16 ga. 2 4 8
0.097 - 0.099 Nail 2'/4 4 8
23/
3z and 3/ a
Staple 14 ga. 2 4 8
Staple 15 ga. 13/a 3 6
0.097 - 0.099 Nail 2'/4 4 8
Staple 16 ga. 2 4 8
1
Staple 14 ga. 2'/4 4 8
0.113 Nail 2'/4 3 6
Staple 15 ga. 2'/4 4 8
0.097 - 0.099 Nail 21/Z 4 8
NOMINAL MATERIAL THICKNESS
(inches)
SPACING' OF FASTENERS
DESCRIPTION a°OF FASTENER AND LENGTH
(Inches) Edges Body of panel°
(inches) (inches)
Floor underlayment; plywood -hardboard -particleboard'
Plywood
'/a and s/16
1'/a ring or screw shank nail -minimum
12'/2 ga. (0.099') shank diameter
3
6
Staple 18 ga.,'/8, 3/,, crown- width
2
5
11/3 Is/ and'/
32� s 32� 2
1'/4 ring or screw shank nail -minimum
12'/2 ga. (0.099') shank diameter
6
8`
19/32+ s/s 23/32 and 3/a
1'/2 ring or screw shank nail -minimum
12/2 ga. (0.099' shank diameter
6
8
Staple 16 ga. 1'/2
6
8
Hardboard'
0.200
1'/, long ring -grooved underlayment nail 6 6
4d cement -coated sinker nail. 6 6
Staple 18,ga.,'/along (plastic coated) 3 6
Particleboard
i
/a
4d ring -grooved underlayment nail 3 6
Staple 18 ga., '/8 long, 3/16 crown 3 6
3
/a
6d ring -grooved underlayment nail 6 10
Staple 16 ga., 1'/e long, 3/a crown 3 6
1/2' s/8
6d ring -grooved underlayment nail 6 10
Staple 16 ga., is/a long, 3/a crown 3 6
For SI: 1 inch = 25.4 mm.
a. Nail is a general description and may be T -head, modified round head or round head.
b. Staples shall have a minimum crown width of'/,6-inch on diameter except as noted.
c. Nails or staples shall be spaced at not more than 6 inches on center at all supports where spans are 48 inches or greater. Nails or staples shall be spaced at not
more than 12 inches on center at intermediate supports for floors.
d. Fasteners shall be placed in a grid pattern throughout the body of the panel.
e. For 5 -ply panels, intermediate nails shall be spaced not more than 12 inches on center each way.
f. Hardboard underlayment shall conform to CPA/ANSI A 135.4
g. Specified alternate attachments for roof sheathing shall be permitted for windspeeds less than 100 mph. Fasteners attaching wood structural panel roof
sheathing to gable end wall framing shall be installed using the spacing listed for panel edges.
2013 CALIFORNIA RESIDENTIAL CODE
201
r . L
WALL CONSTRUCTION
TABLE R602.3(3)
REQUIREMENTS FOR WOOD STRUCTURAL PANEL WALL SHEATHING USED TO RFSIST wwn PRFsst tnFca• b,
MINIMUM NAIL
MINIMUM WOOD
MINIMUM
NOMINAL
MAXIMUM
PANEL NAIL SPACING
MAXIMUM WIND SPEED
Maximum spacing 1
STRUCTURAL
PANEL SPAN
PANEL
THICKNESS
WALL
STUD SPACING
(Inches)
(mph)
Size
Penetration
Edges
Field
Wind exposure category
Laterally
(inches)
RATING
(Inches)
assembly or a
(inches o.c.)
(inches o.c.)
B
C
D
6d Common
stud height'ceiling
habitable attic
assembly or
ceiling assembly or a
one floor height'
stud height
(inches)
(feet)
(2.0" x 0.113')
1.5
24/0
1/8
16
6
12
110
90
85
8d Common
16
6
12
130
110
105
(2.5"x 0.131')
1.75
24/16
/ 16
10
16
2 x 4
10
24`
16`
—
24
14
24
3 x 4
10
24
6
12
110
90
85
For SI: 1 inch = 25.4 mm, I mile per hour = 0.447 m/s.
a. Panel strength axis parallel or perpendicular to supports. Three-ply plywood sheathing with studs spaced more than 16 inches on center shall be applied with
panel strength axis perpendicular to supports.
b. Table is based on wind pressures acting toward and away from building surfaces per Section R301.2. Lateral bracing requirements shall be in accordance with
Section R602.10.
c. Wood structural panels with span ratings of Wall -16 or Wall -24 shall be permitted as an alternate to panels with a 24/0 span rating. Plywood siding rated 16
o.c. or 24 o.c. shall be permitted as an alternate to panels with a 24/16 span rating. Wall -l6 and Plywood siding 16 o.c. shall be used with studs spaced a
maximum of 16 inches on center.
TABLE -8602.3(4-) 7 -
ALLOWABLE
ALLOWABLE SPANS FOR PARTICL•EBOARD,WALL SHEATHING'
THICKNESS STUD SPACING —
(Inch).� - GRADE (Inches)
When siding Is nailed to studs When siding Is nailed to sheathing
'/s M-1 Exterior glue ..A6,-
1/2
16; •1/2 M-2 Exterior glue 16 16
For SI: 1 inch = 25.4 mm.
a. Wall sheathing not exposed to the weather. If the panels are applied horizontally, the end joints of the panel shall be offset so that four panels comers will not
meet. All.panel edges must be supported. Leave a'/16 inch gap between panels and nail no closer than'/, inch from panel edges.
TABLE R602.3(5)
SIZE, HEIGHT AND SPACING OF WOOD STUDS°
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square foot = 0.093 m2.
a. Listed heights are distances between points of lateral support placed perpendicular to the plane of the wall. Increases in unsupported height are permitted
where justified by analysis.
b. Shall not be used in exterior walls.
c. A habitable attic assembly supported by 2 x 4 studs is limited to a roof span of 32 feet. Where the roof span exceeds 32 feet, the wall studs shall be increased
to 2 x 6 or the studs shall be designed in accordance with accepted engineering practice.
202 2013 CALIFORNIA RESIDENTIAL CODE
BEARING WALLS'
NONBEARING WALLS
Maximum spacing
when supporting a
Maximum spacing 1
'Maximum spacing
STUD SIZE
Later ally
y
roof -ceiling
when supporting one
when supporting.two
Maximum spacing
Laterally
Maximum
(inches)
unsupported
assembly or a
floor, plus a roof-
floors, plus a roof-
when supporting
unsupported
spacing
stud height'ceiling
habitable attic
assembly or
ceiling assembly or a
one floor height'
stud height
(inches)
(feet)
assembly, only
habitable attic,
assembly (incfies)
habitable attic
assembly (Inches)
(feet)
(feet)
-
(Inches)
2 x 3 b
10
16
2 x 4
10
24`
16`
—
24
14
24
3 x 4
10
24
24
16
24
14
24
2 x 5
10
24
24
—
24
16
24
2 x 6
10
24
24
16
24
20
24
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square foot = 0.093 m2.
a. Listed heights are distances between points of lateral support placed perpendicular to the plane of the wall. Increases in unsupported height are permitted
where justified by analysis.
b. Shall not be used in exterior walls.
c. A habitable attic assembly supported by 2 x 4 studs is limited to a roof span of 32 feet. Where the roof span exceeds 32 feet, the wall studs shall be increased
to 2 x 6 or the studs shall be designed in accordance with accepted engineering practice.
202 2013 CALIFORNIA RESIDENTIAL CODE
^?, Butte County Department of Development Services FORM NO
PERMIT CENTER
7 County Center Drive, Oroville, CA 95965 DBI -3
_ Main Phone (530) 538-7601 Fax (530) 538-7785
araur"a m.ci
www.buttecouniv.net/dcL-
Re-Roofing and the 2008 California Residential Energy Compliance
r Requirements for Cool Roofs
Important information you need to know BEFORE obtaining a
re -roof pennitl
The California Energy Commission (CEQ has adopted new requirements for re -roofing projects.
Beginning January 1, 2010 when more than 60% of the. exterior surface of the roof or more than 1,000 -sq. ft. of
roof Is replaced, whichever Is less, the roofing product must meet the following prescriptive requirements for
Cool Roofs.
For roof slopes of greater than 2:12: h
1. Roofing products with a density of less than 5lbsfsq.ft. (i.e. Asphalt shingles) shall have a minimum 3 -year
aged solar reflectance of 0.20 and a minimum thermal emittance of 0.76, or a Solar Reflectance Index (SRI) of
16.
2. Roofing products with a density of 6lbsfsq.ft. or more (i.e. Concrete, clay tiles or slate) shall have a minimum
3 -year aged solar reflectance of 0.15 and a minimum thermal emittance of 0.75, or a SRI of 10.
Or,
Altematives to the Cool Roof requirement may be one of the following:
1. In with a thermal resistance of at least 0.85hr.ft2.°F/Btu or at least % inch airspace is added to the roof
deck over an attic; or
2. If existing ducts in the attic are insulated and sealed according to CEC Regulations §151(010; or
3. Buildings with at least R-30 ceiling insulation; or
4. If the building with a radiant barrier in the attic meeting the requirements of §151(02 ;or
5. Buildings with no ducts in the attic; or
6. If in climate Zones 10, 11, 13, and 14, R-3 or greater roof deck insulation above vented attic.
7. Roof areas covered by integrated photovoltaic panels and building integrated solar panels and existing roof
areas that have a thermal mass over the roof membrane with a weight of at least 25 Ib/ft= are exempted for this
requirement.
A Certificate of Compliance Energy Form "CF -1R -ALT" must be completed and submitted with the permit
application. The "CF -1R -ALT* form must be signed by the documentation Author and the Building Designer (i.e.
Contractor or Home Owner).
At Final Inspection an Installation Certificate Form "CF -6R -ENV -01" must be completed by the installing contractor,
and submitted to the owner and the building department.
Rooftna products that are used for cmpWw with the energy star xiards am required to be tested and labeled by the
Cool Roof RaUng Council (CRRC).
The roofing products manufacturer avust have Its roofing product tested for solar reft4ance and Overmal ernittOnce,
and be listed In the CRRC*s Rated Product Directory (Gee and be Mated acxa MV to
CRRC procedures. Below Is an axwople of an approved CRRC product label.
.1
I
Cies,ftWWobot
bC
Initial Weather"
Solar Reflettce 0.00 Pending
Thermal Emittance 0.00 Pending
IDMWba ----
COOr1jr.
Ucemcd Scan ID Number
MMGCOUNCM
adftdftft ftafi"Wtof =dUWzdtW
Maoui useF 0 0 fl�aacariQgsareie in wl8t@Ioe Eo
Cad Roof RO&j Coma
AftcW we the CF -IR -ALT and the CF-6114EW-01 form for your use. Or you con vleft the California EMW
Commisslonevvebpage at ymenewcegov for more brIbmwOWL
k drive an %64wtdmgr-01'(K-)MU=1NCv%VEBS1TC FORMSfForw 201011n MoSrOSSIOW rod amouncerrml 014XW0NJS
Project Address:
Butte County Department of Development Services
PERMIT CENTER
7 County Center Drive, Oroville, CA 95965
Main Phonc (530) 538-7601 Fax (530) 538-7785
www.buttccountY. nct/dds
COOL REROOF INFORMATION SHEET
Slope of Roof # of Existing Layers
Check all that applies to NEW roof:
Existing Roofing Material
o Composition o Tile o I Shake o Wood Shingle
a Built up a Bitumen a Metal o Other
o Tear off existing o Overlay o New Sheathing n
FORM NO
DPI -3
The Callfomla Energy Commission (CEC) has adopted new requirements for re -roofing projects.
Beginning Januar 1. 2010 when more than 50% of the exterior surface of the roof or more than 1,000 -sq. IL of roof is replaced,
whichever is less, the new roofing area must meet the roofing product 'Cool Roof' requirements of §152(b)l Hi, 152(b)l Hii, or
152(b)1 Hiii
For roof slopes of greater than 2:12:
INSTRUCTIONS FOR COMMERCIAL PROJECTS -
• Commercial roofs on decks with a slope of 2:12 or less must meet the 2008 Building Energy Efficiency Standards by being a certified Cool Roof.
A cony of the slandads. slaned by the erwlicart mut ar:attoarx this MWcation.
• Overlays that exceed 100 pounds per square must be accompanied by calculations performed by a California licensed Civil or Structural
Engineer. All overlays must be approved by, the Building'Officlal and other requirements listed within Appendix Chapter 15, California
Building Code.
• A scedAcatlon from the dna nwaaciurer roust acmnxkvw Cgs afOlcaliOn- The specification should list the fire class of the material, a description
of the materials or layers that must be installed, the Cool Roof oertl0cation (If required because of the slope of the root), and installation
requirements.
■ Packaging materials w/CRRC labels must be left on the job site to demonstrate compliance with the specification for the cool roof rating If
applicable.
I agree that the Information provided on (his document is accurate and true.
Applicants Signature: Date:
Roofing products with a density of less than 51bs/sq.ft. (i.e.
Roofing products with a density of 5lbs/sq.fL or more (.e.
Asphalt shingles) shall have a minlmum 3 -year aged solar
Concrete, day tiles or slate) shall have a L
O
refiedanee of 0.20 and a minimum thermal emittance of
aged solar reflectance of 0.15 and a minimum thermal
0.75, or a Solar Reflectance Index (SRI) of 16.
o
emiltance of 0.75, or a SRI of 10.
or check alternate (aft)
or check alternate (alt)
Note: Manufacturers specification for Cool Roof compliance when required shall be provided for Inspector. Packaging materials w/CRRC labels must
be left on the )ob site to demonstrate compliance with the specification for the cool roof rating If applicable.
ALTERNATE (ALT)Altematives to §152(b)1Hi and §152(b)HII, Steep -slope roof (pitch > 2:12)
Alternatives to the Cool Roof requirement may be one of the following:
Bulding with at least R-30 ceding Insulation
If In climate Zone 11', R-3 or greater roof deck insulation
alt a
(approximately 11' (or more) thick it blown In)
aft o
above vented attic.
Ex sting ducts Insulated with R-6 and H.E.R.S.
Buldmg has no HVAC ducts in the aft
alt 0
duct tested to verify duds are sealed
all o
(evaporative coding duct exempt)
crit ❑
Building with a radiant barrier In atticmeeting the requirements
all °
Insulation over roof deck or at least % Inch air -space is
of 151(f)2;
added to the roof deck over an attic
Other Exceptions
• Roofing area covered by building Integrated; photovoltaic panels and solar thermal panels are exempt from the below Cool Roof criteria.
• Roof. constructions (hat have thermal mass over the roof membrane with at least 25 fb/ft21s exempt from the below Cool Roof criteria.
• Butte County areas within Climate Zone 11 per T-24. Part 6, 2008 California Energy Code: Bangor, Berry Geek Biggs, Centervae
Powerhouse, Cherokee, Chico, Cohasset, Dayton, De Sable, Durham, East Biggs, Forest Rench, Gridley, Honcut, Lake Omville, Lake
Wyandotte, Las Plumes, Magalia, Nelson, Nord Orovd1e, Orovffle East, Palermo, Paradise, Pentz, Richardson Spdngs, Richvele, south Orovige,
7hennefflo 77rennalilo ARerbay, Thermallo ForebAy. Ther Creek Powerhouse and Voyandoffe.
CLIMATE ZONE 16 (ONLY) Cool roof requirements apply ONLY when Roofing products with a density of 5lbs/sq.ft. or more (I.e. Concrete, day
tiles or slate) shell have a minimum 3 -year aged solar reflectance of 0.15 and a minimum thermal emltlanoe of 0.75, or a SRI of 10.
or chock altemate (aft) as applicable.
INSTRUCTIONS FOR COMMERCIAL PROJECTS -
• Commercial roofs on decks with a slope of 2:12 or less must meet the 2008 Building Energy Efficiency Standards by being a certified Cool Roof.
A cony of the slandads. slaned by the erwlicart mut ar:attoarx this MWcation.
• Overlays that exceed 100 pounds per square must be accompanied by calculations performed by a California licensed Civil or Structural
Engineer. All overlays must be approved by, the Building'Officlal and other requirements listed within Appendix Chapter 15, California
Building Code.
• A scedAcatlon from the dna nwaaciurer roust acmnxkvw Cgs afOlcaliOn- The specification should list the fire class of the material, a description
of the materials or layers that must be installed, the Cool Roof oertl0cation (If required because of the slope of the root), and installation
requirements.
■ Packaging materials w/CRRC labels must be left on the job site to demonstrate compliance with the specification for the cool roof rating If
applicable.
I agree that the Information provided on (his document is accurate and true.
Applicants Signature: Date:
.P
CF460t-EM41- ROOFING
DWALLMION COMMATE (RevUed fare ofUg oal» CFBR�NV-01
Envelope -Roofing
r Pe(mtt NamEer.
mote Man one person lees reapmraMWfbrRtsa Man of ft Rema On M cgdftdg, each pmsmt aW prepare ead stn a oetlfoab
to (rte potflan of oonaltu ma forwhich Mw we respottsM ; afsmedMs4Y, Me person vd h dtfalrespoo MY farmuft9offan d Wpepare and algae
Mls wdit to forMe WOO cmd=ffm AgWpftdb AWXMWWOMM wM dmck bwasareW*e to be dodmd to &we Me maraddwy
auresha(rabsenawL
ATTIC ROOF INSULATION ANDIOR ATTIC RADIANT BARRIER
mamrlak anu d Name:
maw& Mend Hamm
Thtate ate): rnarlaal Reset. vetoer
o �� to(ar Gtsumtlon bts�led meets �tldatds � �at>
o stow. mardaNyvewbo.10 ummm M c bmte zone to
RjagElpft of Roofing Pvodwb
CRRCPtodcd M=zb*m Pe= Roof Raaf Poo,- In dSota< Apd8chr
!D NnmDtn Ana 82m WdAik3t Rrd;ad>�s Raoi Bodtrgam
1. The CRRC Ptodud fD NraafiertwrJ N oDl�ts+dfhxn Nee A'►oJlmo/CoretcSts Rated RoQEvCt DJtedol�a
2 The ")Win b8 paragt"hetOrme mofbr>,ptodud �btsl8dad
*Choi*bcx ffMeAPdRdbftm&stedvalveustrtgMeeoeaftnbvow,fbobtofe4.
4. Me agedmgxtwm M not owftb dt Me Cad RnafRaBrt9 C mcft M&dftxW Muctmy Men use Mebtftlelre6dow vow fiom Me
dbeototy end use Me squdw (a2rR7VkW-0.V to o(Nabt a cabs ted egad value.
BCpC � M7ifERO0AW0 ODUCT f
o The tour area covered by bWWbV kftpaWd phdwmMo pmlde and MdMft integrated soma V=Mal par*W atla tiom dee above Cool
t] Roo! 8teltra4 ttlees over the toot nlembtarle> a vu�tlt at 26 <blp2la Flip lip tom the shove Cool Roof
ctlfmfa.
7b MB oo6lilogtratet0e gppAed wtlli a m8 oto mPsavosa dee et�eroafatohes
meetmbtbntanperfbrtaartoetterateJ6a§!!8(�SendTebb!!8C MeoaefRlg
O AGa(dtaatEPtgtltett4ed come O Ceme(d-eesed Roof Codw 1303M
-4 406M U—M Mufted WORM
AFnoCRRCffilbefb nfe/hodesnrrofOeuaedendenofhertr>eE►(odla lbtaee!
Name: � SuLao�a+>Doa oa aenetes Cotdraotor at 9(adwtOwrl�
Re RrAspa�f Pateotlls
CSL13 Ucense: Dawabned Vem Compaq w.
k Arivcs On'tfs•ItuaLr.p U1'(K.I/H111101N(;.UVFP-%fn? F(xIMS)r-orms'JO1WIn PwgraW limi Alntlo(+ cennica<i i�fri.t of .. _ 1 cos Iv w is
Butte County Department of Development Services
TIM SNELLINGS, DIRECTOR I PETE CALARCO, ASSISTANT DIRECTOR
7 County Center Drive
Oroville, CA 95965
(530) 538-7601 Office
(530) 538-7785 Fax
www.buttecounty.net
www.buttegeneralplan.net
INSTALLATION OF WATER -CONSERVING PLUMBING FIXTURES
S13-407 • California Civil Code Section -11`01.1.0 2013 Green Building -Stan -dards Cade
In. 2009, the, California State:Legislature. passed. Senate. BiII.SB 407 which requires the replacement of
plumbing:fixtures that are not water conserving, effective: January 1, 2014. Similar provisions are found
in both the California Civil Code and the 2013; California.-Green-Building.�Standards Code.. This
informational bulletin has been issued by Butte -County to:clarify how these regulations shall -be applied
by this jurisdiction.
Each one of these codes and regulations:make�reference to the. requirements for replacement of non-
compliant,plumbing fixtures with water -conserving,, -plumbing fixtures -when a property is undergoing
alterations or improvements. The definition of an "alteration" in the California Building Standards.Code
is "Any construction or renovation :to an existing structure other than a repair or addition." Based on
this definition, any building. permit issued for the:repair or. maintenance. of an existing :structure -would
not: be subject to the requirements of Senate,BillAB 407. With respect to "alterations", Section .301. 1.1
of the California Green Building Standards Code specifies the. requirements shall apply only to the
specific area of the addition or alteration. (Please refer to the attached flowchart, and CALBO
Legislative Analysis for further clarification)
Solar Photovoltaic Systems have been aggressively promoted in the State of California with directives
and recommendations from the Governor's Office and the .State Legislature, and to facilitate their
installation and use. For example, Senate Bill SB 1222 was enacted to provide guidelines related to
the reasonable cost of permit fees for the installation of. rooftop solar energy systems. The application
of SB 407 when a solar photovoltaic system is installed on an existing building would incur additional
costs and associated permit fees which would. be in .conflict with therequirements and intent of SB .
1222. Based on this, and the provisions.of the California.Green Building Standards Code related to the
specific area of the alteration, Solar Photovoltaic Systems shall not be subject to the requirements of
SB 407.
Therefore, effective January 1, 2014, the following permits shall.not be subject to SB 4.07 in the County
of Butte:
• Electrical service change -outs
• HVAC and other mechanical change -outs
• Re -roofs
• Sewer line replacement
• Siding or stucco replacement
• Site work: retaining walls, fences, walk ways, etc.
• Water heater replacement
• Window replacement
• Residential solar systems
• Swimming pools
• Other minor repairs or maintenance as determined by the Building Official
All other provisions of SB 407 shall be enforced such as additions or alterations.
01/01120141SB 407 Interpretation handout
SB 407, Padilla
Property Transfers: plumbing
fixtures replacement
Effective January 1, 2014
Civil Code - Section 1101.1
2013 Green Building.Code
Section 301.1.1 — Additions &
Alterations
1. Project: su bmitted to AHJ
Is this.,project ,
Addition. or Alteratic
Yes- it meets the
definition of an Addition
or Alteration as
determined by the AHJ
ADDITION- AN EXTENSION
OR INCREASE IN FLOOR,
AREkOF AN EXISITNG
BUILDING OR
STRUCUTUR.E
ALTERATION- ANY
CONSTRUCTION OR
RENOVATION TO AN
EXISTING STRUCUTURE
OTHER THAN REPAIR FOR
THE PURPOSE OF
MAINTENANCE OR.
ADDITION
Replace non-compliant
plumbing fixtures
Toilet '> 1.6 GPF
Urinal > 1.0 GPF
Showerhead > 2.5 GPM
Interior Faucet > 2.2 GPM
NO -
THIS IS•A REPAIR
RE -ROOF
;What•is a'
repair? i niAc
CHANGEOUT
REPAIR- THE ELEC:.SERVICE
RECONSTRUCTION CHANGE -OUT
OR RENEWAL OF
ANY PART OF AN WINDOW
EXISTING REPLACEMENT
BUILDING FOR THE
PURPOSE OF ITS
MAINTENANCE. WATER HEATER
2813 CBC REPLACEMENT
SIDING
OTHER MINOR
REPAIRS AS
DETERMINED BY
AHJ
Butte County Building Department
California Green Building Standards Code
Residential VOC Checklist
VOC COMPLIANCE CERTIFICATION
ADHESIVE (NONE 0). ' MANUFACTURER CALGreen LIMfr' ACTUALVOCs,
SEALANT (NONE 0) MANUFACTURER CALGreen I ACTUAL VOCs
ARCHITECTURAL COATINGS (NONE O) MANUFACTURER CALGreen ACTUAL VOCs
FORMALDEHYDE COMPLIANCE CERTIFICATION
PRODUCT (NONE 0)
MANUFACTURER CURRENT LIMIT ACTUAL
Hardwood plywood veneer core
0.05
Hardwood plywood composite core
0.08
Particleboard
0.09
Medium density fiberboard
0.11
Thin medium density fiberboard
0.21
All Carpet installed in the building interior meets the testing and product requirements of the following (check one)
O Carpet and Rug Institute's Green Label
O California Department of Public Health Standard Practice for the testing of VOCs
0 NSFIANS1140 at the Gold Level
O Scientific Certifications Systems Indoor AdvantageTro Gold
O No carpet installed on this project
certify that the information provided on this form is accurate and that the materials used on this project
comply with Section 4.504 (Residential) or 5.504 (Non -Residential) of the 2010 California Green Building
Standards Code.
Print name Signature Date
' See other side of page for VOC limits
r
TABLE 4.504.3
VOC CONTENT LIMITS FOR ARCHITECTURAL COATINGS'.'m
Gras of VOC per Literof Coating. Less
Wator and I act Pvomnt f'—nnnnrlc
COATING CATEGORY
EFFECTIVE
11112010
I, it
Bat coati s
so
. Gnun.o; t»VOC per liter of coating. including water and including exempt
Nt>tlibt coatings -
n)0
R • br 71oor odl- c:.lv
Non0at-hip 4gloss'coatings +-
150
qucnt columns in the table.
r
TABLE 4.504.3
VOC CONTENT LIMITS FOR ARCHITECTURAL COATINGS'.'m
Gras of VOC per Literof Coating. Less
Wator and I act Pvomnt f'—nnnnrlc
COATING CATEGORY
EFFECTIVE
11112010
EFFECTIVE
11112012
Bat coati s
so
. Gnun.o; t»VOC per liter of coating. including water and including exempt
Nt>tlibt coatings -
n)0
R • br 71oor odl- c:.lv
Non0at-hip 4gloss'coatings +-
150
qucnt columns in the table.
SJ fltalt\' Coadnas
3. Values in this tnble are derived from thoe tpecified by the Califumia Air
VCT and asphalt tile ooMshcs
Dmtmlland ran.•Iadhcaiv°
Aluminum roofcoatin s.
400
February I, 2008., More information is m:nilobl" fionl the Air R"sauna. "V
B went& daltyoo:ttinRl'
400
Structural gkuin;t gdhes iv
RitumiMUSroofcoatin I.
50
2:0'
Bituminous roof rimers
150
SPECIAI7V APPUCAIIOf
Bond
350
10
490
COilcretc cudog'oompounds.
350
Pbshl.tr-n:erc weldto
Concrde/tansonry sealers
100
5.0-
Driveway sealer.;
50
S i.I:Nwmcosatncr.sdS.ive
Dry foo continlla
ISO
Faux fbri • ' ' coo
350
SUBSTRATE SPECIRC APPLICATIONS
Fire resistivecoorio
).50
3'
Floorcontinn
100
"
Forin-rcicasc tom "'unds'
250
:n
Gro bicwts <si rnJxuntu)
Soo
HIRh to iloetazura condn
420
Indu. tri31 mainleiUincea.alinllll
2SO
Low solidsc<xailill t
120
Magnesite CI.M.'alcoutingl1
450
Ma<Itic texturn. '
t 00
Metallic Phmtented cootinRS
500
Multioolorcoa '
250
mca
ttwIIS!IDrimets
420
Primel!i.sealersAndlmdcn:ootcxs
100
Relldive penetratingSl'4llmii
JSO
Recycled coatings
250
Roof cool'
110
Rustpreverdlltivo continllll
400 s ,°
2SO
Shellll
Clear
Opaque
7.10
sso
Spcxcilllty primers,sealersandundeJCoaters
3.50
100
Srains
2S0
St000 COUI>O!Idards
450
Swimming l coatings
-U
Tmffic markins: coatinlli
100
TUb Wd tile n:6rish c0A1iags
420
Warerprmump,memhnlncs
250
Woodcoalinas
:175
Wo"d s tVmh•ts
350
Zinc-ridlpriJners
340
TABLE 4.504.1
ADHESIVE VOC LIMJJU
T Pp", Wat..•and T n c Pv,mnt (:mmnnirnrici. r:. T :f .
ARCKnECTURALAPPUCAnOHS
CURRENTVOCUNJT
IndoPI UTACI ndhesi\=es
Camet
••)
Y
lutrinort Jli-el'ai: ""1•
. Gnun.o; t»VOC per liter of coating. including water and including exempt
Wrw.wln'lo: ioll a.l i,-.-
compounds.
R • br 71oor odl- c:.lv
2. The specified limit I I remaininctiect unles.revisedlimits an: fi.Nedinsubs. l-
Subdoor adh YCs .
qucnt columns in the table.
.'
3. Values in this tnble are derived from thoe tpecified by the Califumia Air
VCT and asphalt tile ooMshcs
Dmtmlland ran.•Iadhcaiv°
RUSAurces Board, Arehitecrurnl Coatings Suggcs.ted C.onlrrU Measure,
CtNe bme•adhesive -
February I, 2008., More information is m:nilobl" fionl the Air R"sauna. "V
Mulcinn.%011eco: £11RKtion ildh i ro
Boord.
TABLE 4.504.1
ADHESIVE VOC LIMJJU
T Pp", Wat..•and T n c Pv,mnt (:mmnnirnrici. r:. T :f .
ARCKnECTURALAPPUCAnOHS
CURRENTVOCUNJT
IndoPI UTACI ndhesi\=es
Camet
••)
Y
lutrinort Jli-el'ai: ""1•
111
Wrw.wln'lo: ioll a.l i,-.-
r
R • br 71oor odl- c:.lv
- 6-
Subdoor adh YCs .
S0.
Cc:nuni" tile:..the:.ivc
65
VCT and asphalt tile ooMshcs
Dmtmlland ran.•Iadhcaiv°
I
CtNe bme•adhesive -
J
Mulcinn.%011eco: £11RKtion ildh i ro
W
Structural gkuin;t gdhes iv
J00
Silll%lo lib nx.f r-lembr: nc oA l l i°cm'
2:0'
Other ae i. -:s trot s.:a:0<:Allv Ii tal
5-
SPECIAI7V APPUCAIIOf
PVC weldinJt
�elduMl
10
490
AHS Wddillll
lzIi
Pbshl.tr-n:erc weldto
250
dh i'° " wrf<I' ic-
5.0-
C. -:n tlld. v'
80:
S i.I:Nwmcosatncr.sdS.ive
2'0
Strucrvnl wood memberndlleslve
Tc? mud trim .tdhesvirc
o
SUBSTRATE SPECIRC APPLICATIONS
Mttal to mellll
3'
Pbstic foams
50
Porousmalerinl ie Piwoodl
50
W-wd
:n
Fbea o:l: >-s
80
I.- if on ult-lv"c:'" i -t lu I--oond Ci::[.Mmu&Q16'itae-111IIant-it�re7,—rl!o oal,-[iv"
IViIlnlschillhe$1 VOCWQICIIIIlballbetnluws::
2.Fotudditiasnlinfmaatton r_gmetho:IntomVOCeontmt
spp�c':if ed in Lbls Mble. see Sour(l Coast Air Qlulity Maruv< nt Di.sir:Cl
Rulo 1168.
TABLE 4.50:1.2
SEALANT VOCUMIT
I ase W,am mri Lf' . Fvmmnt f`-mmnnunde in r;rnms nor Tit—
SEALANTS -
CURRENTVOC LIMIT
AR:hitecnmd
2SO
Marine deck
Nnn.•. •.••hnon.o I=
760
300
SIMI 11'-nb:m >f r.Ifmhr.11'W
4\0
Other
.420
SEALANT PRNERS
Archffi!Cluml
Nmp-.rr.aut
POVwt
2.0
ITS
MotdifJ.,J bitwruaous
M,crillt deck
S00
760
Utbcr
J