HomeMy WebLinkAboutB16-2260 000-000-000x -'.SEQU01A E N: G I N E E R I `N .G & STRUCTURAL Structural Calculations Client: Chris and Louise Massa Job#: 16-054 Project: Massa Addition ' Address: 4285 Keefer Road, Chico, CA APN: 047-320-051-000 4 Calculation Index Page # • Project Layout 1 • Gravity Analysis 2 0 Lateral Analysis 3-13 Timber Frame Analysis — Line A 14-16 • Beam Analysis - 17-27 • Column Analysis 28 • Footing Analysis 29 312016 BUTTE COUNTY PERMIT# OCT 112016 BUTTE COUNTY DEVELOPMENT SERVICES REVIEWED FOR DEVELOPMENT CODE COMPLIANCE, >� SERVICES DATE2 This calculation package is only valid for the project location as listed above and may not be used for another site without the authorization of Sequoia Engineering. Sequoia Engineering claims no responsibility for any structural design not specifically addressed in this calculation package. Calculations and plans are not valid until reviewed and approved by the governing building department. 11�- V—A (D"RIJ 467 East 2"d Ave, Chico, CA 95926 • (530) 591-7258 chad(g�seAuoiacivil.com r ' SEQUOIA E N 'G I N E E R I N G Project Layout 1 2 53.3 Pg. 1 ILL,& FLUSH --' (I.&E 2200 FID MINJ I-V HU210 j J015T HOR5. --- ____-•i/ NA 467 East 2"d Ave., Chico, CA 95926 (530)-591-7258 chad@sequoiacivil.com Pg. 2 Gravity Load Development Project: Massa Addition Date: 10/3/2016 Comments: 16-054 Units: lbs & feet (UNO) Gravity Loads: Slope= 6 to 12 Roof Dead Load Ply 2.5 psf Roofing 5.0 psf Framing 5.0 psf Gyp 2.5 psf Insul 1.0 psf Sprinklers (if Req'd) 0.0 psf Misc 1.8 psf Total (sloped) 17.8 psf Total (horiz) 19.0 psf Roof Live Load Construction 20.0 psf Roof Snow Load 0.0 psf Wall Dead Load Siding 10.0 psf (exterior) .3/8 Ply. 1.8 psf 2x Framing 1.7 psf Gyp. 2.2 psf Insul. 1.0 psf Misc. 2.3 psf Total 19.0 psf Wall Dead Load 2x Framing @ 16" o.c. 2.2 psf (interior) Gyp. 2 sides 4.4 psf Misc 2.4 psf Total. 9.0 psf Floor Dead Load Framing @ 24" o.c. 2.5 psf • 3/4" ply 2.25 psf Gyp. 2.2 psf Flooring 2.5 psf Misc. 5.5 psf Total 15.0 psf Floor Live Load Residential 40.0 psf Sleeping 30.0 psf Pg. 2 Pg. 4 Equivalent Lateral Force Procedure ASCE 7-10 Seismic Loads Project: Massa Addition Date: 10/3/2016 Comments: Units: kips & feet (UNO) Description Symbol Value Units Source Zip Code ft^2 psf kis Longitude Roof Floor 39.81468 Deg Google Earth Latitude 1 121.91036 Deg Google Earth Occupancy 0.57 2 2 Table I=I Site Class D 0.57 Chapter 20 Seismic Deisgn Category 185 D Table 11.6-1 Mapped 0.2 sec spectral response Ss 0.618 %g USGS website Mapped 1 sec spectral response S, 0.277 %g USGS website Response Modification R 6.5 4.86 Light Framed Shear Walls - Table 12.2-1 Importance Factor I + 1 Table 11.5-1 (Upper level governs for R value Lower level Strutural Height h„ 10 ft R = 7.0 or steel plate shear walls. Use R = 6.5) Peroid Parameter Ct 0.02 English Table 12.8-2 Peroid Parameter x 0.75 English Table 12.8-2 Long Period T,, 16 sec Figure 22-16 Aprx. Fundamental Period Ta 0.1125 sec Section 12.8.2.1 Site Coefficient Fa 1.3060 Table 11.4-1 Site Coefficient Fv 1.8460 Table 11.4-2 MCE Spectral Response Sms 0.8071 Eq. 11.4-1 MCE Spectral Response Sml 0.5113 Eq. 11.4-2 Design Spectral Response (0.2 Sec) SDS 0.538 %g Eq. 11.4-3 Design Spectral Response (1.0 Sec) So, 0.341 %g Eq. 11.4 Coefficient for Upper Limit Cu 1.400 Table 12.8-1 Deflection Amplification Factor Cd 4 Table 12.2-1 Overstrength Factor Wo 3 Table 12.2-1 Max Seismic Response Coeff Cs max 0.466 , Eq. 12.8-3 MinSeismic Response Coeff Cs min, 0.024 Eq. 12.8-5 Seismic Response Coefficient Cs 0.083 Section 12.8.1.1 Vertical Dist Exp k I Section 12.8.3 Vertical Distribution oJSeismic Forces LEVEL STORY HT hi wi wi*hi^k Cvx VEQ E VEQ Dia hra m Diaph Max Diaph Min Roof 10 10 131.96 1320 1.00 10.92 10.92 14.20 28.40 14.20 0 0 0.00 0 0.00 0.00 10.92 0.00 0.00 0.00 0 0 0.00 0 0.00 0.00 10.92 0 0.00 0.00 0 0 0 0 0.00 0.00 10.92 0 0.00 0.00 C„ml 1'tl 96 1 1 I 1 RoojLevel Story Shear (kips) 10.9 Area Weight Mass Trib Area (ft^2) Line Shear Line Shear ft^2 psf kis Wall Line Roof Floor Deck ULT kis W/S (kips) Roof 3694 19 70.11 1 340 0.82 0.57 Roof Snow 0 0.00 2 340 0.82 0.57 Floor 1065 15 15.92 A 185 0.45 0.31 Deck 18 0.00 B 300 0.72 0.51 Exterior Wall 1967 19 37.37 C 1740 350 4.86 3.40 Interior Wall 950 9 8.55 Sum (kips) 131.96 - L � . � C r . a • - L � . � C "ASCE710W ASPOroilram Version 2.2 WIND LOADING ANALYSIS Main Wind -Force Resisting System Per ASCE 7-10 Code for Enclosed or Partially Enclosed Buildings UsingMethod 2: Analytical Procedure Section 27 & 28 for Low -Rise Buildings Job Name: Massa Addition Subject: Job Number: 16-046 Ori inator: Checker: Input Data: , ' r' - Wind Speed, V = --110 mph (Wind Map, Figure 26.5 -1A -C), Bldg. Classification = II (Table 1.5-1 Risk Category) w_� Exposure Category = C (Sect. 26.7) _ B J, ' Ridge Height, hr = 25.00 ft. (hr >= he) . ti Eave Height, he = ,. 20.00 ft. (he - hr) Building Width= 48.00' ft. (Normal to Building -Ridge)" Building Length = 40.00 ft. (Parallel to Building Ridge) L 'Roof Type = Gable (Gable or Monoslope) plan Topo. Factor, Kzt = 1.00 , (Sect. 26.8 & Figure 26.8-1)' Direct. Factor, Kd = 0.85 (Table 26.6) Enclosed? (Y/N) '' ' Y (Sect.'26.2 & Table 26.11-1) Hurricane Region? " "N 8 hr h< 60' e Resulting Parameters and Coefficients: T Roof Angle, 9 = 26.57 deg:• J L Mean Roof Ht., h = 22.50 ft. (h = (hr+he)/2, for angle >10 deg.) Elevation Check Criteria for a Low -Rise Building: 1. Is h <= 60'? Yes, O.K.- 2. Is h <= Lesser of,L or B? ` Yes, O. K: External Pressure Coeffs., GCpf (Fig. 28.4-1): (For values, see following wind load tabulations.) P •f & N t" I t 10 C fr. • t GC ' T bl 26 11 1 osi ive ega ive n erna ressure oe Iden s, pi (a e - ). ` +GCpf Coef. = 0.18 (positive internal pressure) . ` ,GCpf Coef. = 0.18 (negative internal pressure)' ' r If h < 15 then: Kh = 2.01*(15/zg)^(2/a) (Table 28.3-1) If h >= 15 then: Kh = 2.01*(z/zg)^(2/a) (Table 28.3-1) ,.. a = 9.50 (Table 26.9-1) „ . zg = 900 (Table 26.971) ' Kh'= 0.92 (Kh = Kz evaluated at z = h) Velocity Pressure: gz = 0.00256*Kz*Kzt*Kd *VA 2 (Sect. 28.3.2, -Eq. 28.3-1) qh = 24.34 psf •qh = 0.00256*Kh*Kzt*Kd*V^2 (qz evaluated at z = h) f Design Net External Wind Pressures (Sect. 28.4.1): p = qh*[(GCpf) - (+/-GCpi)l (psf, Eq. 28.4-1). i { Wall and Roof End Zone Widths'a' and '2*a' (Fig. 28.4-1): a = 4.00 Iftft. . 10/3/2016 12:24 PM "ASCE710WASPRrAram Version 2.2 MWFRS Wind Load for Load Case A MWFRS Wind Load for Load Case B Surface GCpf p =Net Pressures sf Surface *GCpf p = Net Pressures s w/ +GC i w/ -GCpi) w/ +GC i w/ -GCpi) Zone 1 0.55 9.00 17.76 Zone 1 -0.45 -15.34 -6.57 Zone 2 -0.10 -6.80 1.97 Zone 2 _ -0.69 -21.18 -12.41 Zone 3 -0.45 -15.27 -6.50 Zone 3 -0.37 -13.39 ___.,,...,..,..-- -4.63 Zone 4 -0.39 -13.89 -5.13 Zone 4 -0.45 -15.34 -6.57 Zone 5 --- --- --- Zone 5 0.40 5.36 14.12 Zone 6 --- -- --- Zone 6 -0.29 -11.44 -2.68 Zone 1E 0.73 13.33 22.10 Zone 1 E -0.48 -16.07 -7.30 Zone 2E -0.19 -9.01 -0.25 Zone 2E -1.07 -30.43 -21.66 Zone 3E -0.58 -18.62 -9.86_ Zone 3E -0.53 -17.28 -8.52 Zone 4E -0.53 -17.40 -8.64 Zone 4E -0.48 -16.07 -7.30 Zone 5E --- -_- --- Zone 5E 0.61 10.47 19.23 Zone 6E --- --- --- Zone 6E -0.43 -14.85 -6.09 *Note: Use roof angle 0 = 0 degrees for Longitudinal Direction.", For Case A when GCpf is neg. in Zones ME: For Case B when GCpf is neg. in Zones 2/2E: Zones 2/2E dist. =F-24.00 Ift. Zones ME dist. =1 20.00 Ift. . Remainder of roof Zones ME extending to ridge line shall use roof Zones ME pressure coefficients. MWFRS Wind Load for Load Case A, Torsional Case MWFRS Wind Load for Case B, Torsional Case Surface GCpf p = Net Pressure s Surface GCpf p = Net Pressure s w/ +GC i w/ -GCpi) w/ +GC i w/ -GCpi) Zone 1T --- 2.25 4.44 Zone 1T --- -3.83 -1.64 Zone 2T --- -1.70 0.49. Zone 2T --- W� -5.29 -3.10 Zone 3T --- -3.82 -1.63 Zone 3T --- -3.35 -1.16 Zone 4T --- -3.47 -1.28 Zone 4T --- -3.83 -1.64 Zone 5T --- --- --- Zone 5T --- 1.34 3.53 Zone 6T --- =-- --- Zone 6T --- -2.86 -0.67 Notes: 1. For Load Case A (Transverse), Load Case B (Longitudinal), and Torsional Cases: Zone 1 is windward wall for interior zone. Zone 1 E is windward wall for end zone. Zone 2 is windward roof for interior zone. Zone 2E is windward roof for end zone. Zone 3 is leeward roof for interior zone. '. Zone 3E is leeward roof for end zone. Zone 4 is leeward wall for interior zone. Zone 4E is leeward wall for end zone. Zones 5 and 6 are sidewalls. Zone 5E & 6E is sidewalls for end zone. Zone 1T is windward wall for torsional case Zone 2T is windward roof for torsional case. Zone 3T is leeward roof for torsional case Zone 4T is leeward wall for torsional case. Zones 5T and 6T are sidewalls for torsional case. 2. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces. 3. Building must be designed for all wind directions using the 8 load cases shown below. The load cases are applied to each'building corner in turn as the reference corner. 4. Wind loads for torsional cases are 25% of respective transverse or longitudinal zone load values. Torsional loading shall apply to all 8 basic load cases applied at each reference corner. Exception: One-story buildings with "h" <= 30', buildings <= 2 stories framed with light frame construction, and buildings <=2 stories designed with flexible diaphragms need not be designed for torsional load cases. 5. Per Code Section 28.4.4, the minimum wind load for MWFRS shall not be less than 16 psf. . 10/3/2016 12:24 PM Pg. 7 ASCE 7-10 Wind Loads - Low Rise Walls and Roofs (Section 28) "'. Project: Massa Addition , Date: 10/3/2016 ' 1' �- Comments: Units: lbs &feet (UNO) .' Wall Line ID A Roof , Direction Transverse Trib Area p= Net Desi Press. s = Net Desi Press. lbs to Ride (ft -2) w/ +GC i w/ -GCpi) w/ +GC i w/ -GCpi) Zone 1 9.00 = 17.76 •- Zone 2 -6.80 1.97 . ' Zone 3 -15.27 . -6.50 ' - " Zone 4 r - -13.89 -5.13 4 _ Zone 5 L - - ' Zone 6 - Zone 1E 13.33 22.10 Zone 2E 42 9.01 0.25 •t -169.30 4.70 _ Zone 3E 42 -18.62 ,'-9.86 349.76 185.16 c ti r Zone 4E 17.40' yx . 8.64' Zone 5E =r r Zone 6E Total (lbs) ULT 180.46 189.86 `. Total (lbs) WIS 108.27 113.92 Wall Line ID B • Roof Direction Transverse Trib Area p= Net Desig2 Press. sf) ign Press. Ibs to Ride(ft-2) w/+GC i w/ -GCpi) w/ +GC i w/ -GC i ` Zone 1 27.5 •, 9.00 , 17.76 247.48 488.47 . Zone 2 62.50 -6.80 1.97 - -189.93 55.01 Zone 3 62.50 -15.27 -6.50 426.73 -181.78, `" r �. • •' Zone 4 b' 27.5 ` -13.89 ... f. -5.13 - 381.98 140.99 Zone 5 ' .. S Zone 6 --- --- Zone IE 13.33 22.10 +, Zone 2E -9.01 t -0.25 _ Zone 3E _1.8.62 -9.86 r . , Zone 4E 1 - -17.40. -8.64 Zone 5E ., .. Zone 6E - -r L w Total (Ibs) ULT 866.25 866.25 Total (Ibs) WIS 519.75 519.75 - Wall Line ID C Roof .." Direction Transverse Trib Area=Net Desi Press. s = Net Desi Press. Ibs to Ride (ft^2) (w/ +GC i w/ -GC i w/ +GC i w/ -GC i Zone 1 250 9.00 r 17.76 ,.2249.82 4440.64 Zone 2 35 b ,-6.80 `t 1.97.106.36 30.81 Zone 3 35 -15.27 -6.50 , . 238.97 _101.80 Zone 4 250- . -5.13 , 3472.51 1281.69 ' a Zone 5 .-13.99, Zone 6 Zone I F 1333 22.10 , Zone 2E t -9:01 -0.25 Zone 3E -18.62 -9.86-. Zone 4E -17.40 `'�, -8.64- .. Zone 5E y , 5-7- ` . Zone 6E Total (Ibs) ULT 1 5854.94 5854.94 Total (Ibs) WIS 3512.96 3512.96 A+ Pg. 8 Shear Force Summary Project: Massa Addition Date: 10/3/2016 Comments: Units: kips & feet (UNO) Wall Line Seismic Shear Wind Shear Controls Roof Level 1 574 Seismic 2 574 Seismic A 312 114 Seismic B 506 520 Wind C 3400 3513 Wind 2012 NDS Bolt Yield Limit Analysis For Single Shear Wood -to -Concrete Connections Project: Massa Addition Date: 10/3/2016 Comments: Units: lbs & inches(UNO Connection ID: Typical 1/2" dia A.B. in 2xlate Loadings Dead = 0 lbs. Bolt Diameter = 0.500 inches Floor = 0 lbs. Fyb = 45 ksi (for A307 bolt) Snow = 0 lbs. is = 1.50 inches (sill member) Const. = 0 lbs. width, s = 5.50 inches (sill member) Seismic = 1,404 lbs. (ds = 0 degrees - 11 Wind = 1,638 lbs. Es = 1,600 ksi (sill member) Eq and W load are in ULT Fes (parallel) = 5,600 psi (parallel) Fes (perpendicular) = 3,158 psi (sill member) SGs = 0.50 DF -L Side Member Specific Gravity, EWP, DF -L, HF, SP or SPF Fese.= 5,600 psi (sill member) Re = 1.0000 Rt = 2.0000 Ke = 1.0000 kl = 0.6794 k2 = 1.1087 U = 1.4054 CM = 1.00 Wet Service Factor C, = 1.00 Temperature Factor Cd= 1.00 Geometry Factor N.D.S. 11.3.1 Eq.'s Cs= 1.00 Group Action Factor Eq 11.3-1 Z = 2,100 Ib. Mode Im Rea = 0.25 Member Stiffness Ratio Eq 11.3-2 Z = 1,050 Ib. Mode I, m = 0.9253244 Eq 11.3-3 Z= 793 Ib. Mode II u = 1.0030132 Eq 11.3-4 Z = 970 lb. Mode III", n= l number of fasteners in a row Eq 11.3-5 Z = 615 Ib. Mode III, s= 1 inches, Bolt Spacing (In a row) Eq 11.3-6 Z= 716 lb. Mode IV now = I total number of rows motel = I total number of fasteners Z. = Z(CD*CM*C,*CF*CD) 2012 IBC & ASCE 7-10 Load Combinations: Design Loads Conn Capacity DL RLL FLL Snow Wind E lbs Cd Z' (Ibs) EQ 16-8 1 0 0.9 553 OK!!! EQ 16-9 1 1 0 1.25 769 OK!!! EQ 16-10 1 1 0 1615 OK!!! EQ 16-10 1 1 0 1.25 769 OK!!! EQ 16-11 1 0.75 0.75 0 1.25 769 OK!!! EQ 16-11 1 0.75 0.75 0 1.15 707 OK!!! EQ 16-12 1 0.6 983 1.6 984 OK!!! EQ 16-12 1 -0.6 -983 1.6 984 OK!!! EQ 16-12 1 0.7 982.745824 1.6 984 OK!!! EQ 16-12 1 -0.7 -982.745824 1.6 984 OK!!! EQ 16-13 1 0.75 0.75 0.45 737.25 1.6 984 OK!!! EQ 16-13 1 0.75 0.75 -0.45 -737.25 1.6 984 OK!!! EQ 16-13 1 0.75 0.75 0.45 737.25 1.6 984 OK!!! EQ 16-13 1 0.75 0.75 -0.45 -737.25 1.6 984 OK!!! EQ 16-14 1 0.75 0.75 0.525 737.059368 1.6 984 OK!!! EQ 16-14 1 0.75 0.75 0.525 737.059368 1.6 984 OK!!! EQ 16-15 0.6 0.6 983 1.6 984 OK!!! EQ 16-15 0.6 -0.6 -983 1.6 984 OK!!! EQ 16-16 0.6 0.7 982.745824 1.6 984 OK!!! EQ 1646 0.6 -0.7 -982.745824 1.6 984 OK111 Pg. 10 w 2012 NDS Bolt Yield Limit Analysis For Single Shear Wood -to -Concrete Connections Project: Massa Addition Date: 10/3/2016 Comments: Units: lbs & inches(UNO Connection ID: Typical 1/2" dia A.B. in 3x plate Loadings Dead = 0 lbs. Bolt Diameter = 0.500 inches Floor = 0 lbs. Fyb = 45 ksi (for A307 bolt) Snow = 0 lbs. is = 3.00 inches (sill member) Const. = 0 lbs. width, s = 5.50 inches (sill member) Seismic = 1,635 lbs. Os= 0 degrees Wind = 1,908 lbs. Es = 1,600 ksi (sill member) Fes (parallel) = 5,600 psi (parallel) Fes (perpendicular) = 3,158 psi (sill member) SGs = 0.50 DF -L Side Member Specific Gravity, EWP, DF -L, HF, SP or SPF Fese = 5,600 psi (sill member) Re = 1.0000 Rt = 2.0000 ICa = 1.0000 kl = 0.6794 k2 = 1.0277 U = 1.1087 Cm= 1.00 Wet Service Factor C, = 1.00 Temperature Factor Cd= 1.00 Geometry Factor N.D.S. 11.3.1 Eq.'s . C6= 1.00 Group Action Factor Eq 11.3-1 Z = 4,200 Ib. Mode Im Rea = 0.25 Member Stiffness Ratio Eq 11.3-2 Z = 2,100 Ib. Mode I, in = 0.946593 Eq 11.3-3 Z= 1,585 Ib. Mode II u = 1.0015066 Eq 11.3-4 Z = 1,798 lb. Mode III, n= 1 number of fasteners in a row Eq 11.3-5 Z = 970 Ib. Mode III, s= l inches, Bolt Spacing (In a row) Eq 11.3-6 Z= 716 Ib. Mode IV n,ow = l total number of rows nmmi = 1 total number of fasteners Z' = Z(CO*CM*C,*Cs*CO) 2012 IBC & ASCE 7-10 Load Combinations: Design Loads Conn Capacity DL RLL FLL Snow Wind E lbs Cd Z' (Ibs) EQ 16-8 1 0 0.9 644 OK!!! EQ 16-9 1 1 0 1.25 895 OK!!! EQ 16-10 1 1 0 l 716 OK!!! EQ 16-10 1 1 0 1.25 895 OK!!! EQ 16-11 l 0.75 0.75 0 1.25 895 OK!!! EQ 164 l 1 0.75 0.75 0 1.15 823 OK!!! EQ 16-12 1 0.6 1145 1.6 1146 OK!!! EQ 16-12 1 -0.6 -1145 1.6 1146 OK!!! EQ 16-12 1 0.7 1144.643924 1.6 1146 OK!!! EQ 16-12 1 -0.7 -1144.64392 1.6 1146 OK!!! EQ 16-13 1 0.75 0.75 0.45 858.75 1.6 1146 OK!!! EQ 16-13 1 0.75 0.75 -0.45 -858.75 1.6 1146 OK!!! EQ 16-13 1 0.75 0.75 0.45 858.75 1.6 1146 OK!!! EQ 16-13 1 0.75 0.75 -0.45 -858.75 1.6 1146 OK!!! EQ 16-14 1 0.75 0.75 0.525 858.4829428 1.6 1146 OK!!! EQ 16-14 1 0.75 0.75 0.525 858.4829428 1.6 1146 OK!!! EQ 16-15 0.6 0.6 1145 1.6 1146 OK!!! EQ 16-15 0.6 -0.6 -1145 1.6 1146 OK!!! EQ 16-16 0.6 0.7 1144.643924 1.6 1146 OK!!! EQ 16-16 1 0.6 1 -0.7 -1144.64392 1.6 1146 OK111 Pg. 11 Shear Wall Design CBC 2013 Project: Massa Addition Date: 10/3/2016 Comments: Units: lbs & inches (UNO) Panel Thickness 3/8 Spec Grav Of Framing 0.5 Panel Orientation Short Dimension Across Studs Spec Grav Of Plywood C -D, C -C, APA Rated Shear Ply Nail Type 8d Fnd Sill Plate Grade DF -L Anchor Bold Diam. 1/2 AB in 2X Sill 983 lbs/bolt (see design) Stud Spacing 16 inches o.c. AB in 3X Sill 1146 lbs/bolt (see design) Floor Split Anchorage Adjusted Nail Nail Length Diam Embed Cd CD NDSValue Value 10d 3 0.148 1.50 0.84 1.33 118 133 12d 3.25 0.148 1.75 0.99 1.33 118 155 16d 3.5 0.162 2.00 1.00 1.33 141 188 20d 4 0.192 2.50 1.00 1.33 170 226 30d 4.5 0.207 3.00 1.00 1.33 186 247 1/4" Screw 0.25 2.00 1.00 1.33 220 293 3/8" Screw 0.375 3.00 1.00 1.33 400 532 A35 695 A34 515 Shear Wall Design Edge Nail Alowable Loads Sole Plate Fastening Rim Joist Fastening AB Spacing (ft) Spacing (in) note Seismic Wind, Fastener Spacing (in; Fastener Spacing (in) 2X Sill 3X Sill 6* 164 164 12d 11 A35 51 6.00 6.00 6 260 260 12d 7 A35 32 3.78 4.41 4* 350 350 12d 5 A35 24 2.81 3.27 4 1 380 532.5 12d 5 A35 22 1.29 3.02 3 1 490 685 12d 4 A35 17 1.00 2.34 2 1 640 895 16d 4 A35 13 NG 1.79 44 1 760 1065 16d 3 A35 11 NG 1.51 33 1 980 1370 16d 2 A35 9 NG 1.17 22 1 1280 1790 16d 2 A35 7 NG 0.90 1. Use 3X framing at adjacent panel edges and stagger nailing _ Segmented Shear Wall Design ANSI/AF&PA SDPWS-2008 Edition Project: Massa Addition Date: 10/3/2016 Comments: Units: lbs & ft (UNO) Walla Wall Fnd Wall aspect Point Load Uplift from OTM Net Required Holdown Req'd Stem Line Load Wall Wall Height Length System A.B. Stress ratio Res extra end of wall above OTM Res Uplift Anchor or Width Wall Type (kips) Number Location (ft) (ft) T Location (If) penalty (plf) (lbs) (k) (Id -ft) (kip -ft) (kips)* Bolt - Strap (in) Wall Line ID: 1 - Roof HD Conn. Type (I=FND, 2=FTF): I Seismic I Ext8 5.50 Stem Comer 115 1.0 .5.1 1.2 0.70 SST B16 liD3.J2(DRL.2X) 6 6° 3.40 2 Ext 8 6.5 Stein Middle 115 1.01 6.0 1.7 0.66 SSTB16 HDU2 (DBL 2X) 6 6- 3 Ext 8 17.5 Stem Middle 115 1.0 16.1 12.2 0.22 SSTB16 HDU2(DB L.2X) 6 6° Wind I Ext 8 5.5 Stem Comer 119 5.2 1.4 0.70 SSTB16 FTDU2(DB L.2X) 6 6- 3.51 2 Ext 8 6.5 Stem Middle 119 6.2 1.9 0.66 SST1316 HDU2(DBL2X) 6 6- 3 Ext 8 17.5 Stem Middle 119 16.7 14.0 0.15 SSTB16 IIDI.J2(DBL 2X) 6 6° Wall Line ID: I HD Conn. Type (I=FND, 2=FTF): I Seismic I Ext 8 3.50 Stein Comer 164 0.9 4.6 0.5 1.17 SSTB16 HDU2(DBL2X) 6 6 0.57 Wind 1 Ext 8 3.50 Stem Comer 0 0.0 0.6 -0.16 Ila uplift no hd recjd 6 6" 0.00 Wall Line ID: 2 HD Conn. Type (1=FND, 2=FTF): I Seismic i Ext 8 2.5 Stem Corner 229 0.6 180 4.6 0.5 1.62 SSTB16 HD1.J2(DB I..2X) 6 4 0.57 Wind I Ext 8 2.5 Stem Comer 0 180 0.0 0.6 -0.25 no uplift no lid rcq'd 6 6" 0.00 ; Perforated Shear Wall Design ANSUAF&PA SDPWS-2008 Edition Project: Massa Addition - Date: 10/3/2016 Comments: - Units: lbs & fl (UNO) Wall Line B HD Conn. Type I=FND 2=FTF : I Total. Wall Line Wall Wall Fad Wall Length Wall Opening % Full Sheathing Capacity aspect - Uplift from Wall Net Required Holdown Req'd Stem Load Load Wall Height Length System A.B. £Li Stress Area, Ao Height Area Adjust. ratio above Uplift Uplift Anchor - or Width Wall Type Source Ibs Location n n T Location 11 I fl^2 SheathingRatio, r Factor, Co penalty (k) kis kis Bolt Strap (in) Seismic 506 Ext 8 13.50 Stem Comer 6.50 78 24.5 0.48 0.68 0.86 0.75 0.599 0.599 SSTBIC, HDU2IDBL2Xt 6 fi• Wind 520 80 0.601 0.601 SSTIII6 HDU2 t DIIL 2Xt 6 6• Wall Opening into Wall Wall Pier Info Shear Wall Design Modified Shear Wall desi n Opening Location Length. Height Area Pier Length Aspect .Len. Used fD Seismic Wind ID Seismic Wind Number- xi (III L;(11) Hi (ft) (11^2) Number (ft) Ratio (n) Check 6• 164 164 6 260 260 6• 6 106 168 141 224 1 3.00 7 3.5 24.50 1 3.00 2.67 3.00 OX 2 2 3.50 2.29 3.50 OX 4• 350 350 4• 226 301 3 3 4 380 533 4 245 458 4 4 3 490 685 3 316 589 5 5 2 640 895 2 413 770 - - 6 44 760 1065 44 491 916 33 980 1370 33 633 1179 22 1280 1790 22 826 1540 ; SEQUOIA Pg. 14 E N 'G' 1 N E I R I N G ' A - & STRUCTURAL Timber Frame Connection at Line A _ I�I AT EA T LONa�I'-u ►C� 1 ��1 i It LT . T �--- Ped- °11,10.1 � sty=,- W) 31a BOLTS P>_-4 L Gt�►NEc1�o� PtTx�i � ' 1 5U-T LA's4OJf 4T 5 EA" -p q OWL- Q0 W ��.►-r AT Ct7n�" t C.Ttc� Q0 •. al ��.►n,,.FG- T, M = o q2.14�."' j saes k,Ps.. Z ' Z�► SEE SOL,Ttn c�6t.SFI�Q, pe�LtLt��ry rt've TZ .���= L A, A L--j 1515 Z I �2 SSM S 5OL;r .r> t>SL, SkAe ANAt-ySiS 467 East 2"d Ave., Chico, CA 95926 (530)-591-7258 Chad@sequoiacivil.com ` Pg. 15 2012 NDS Bolt Yield Limit Analysis For Double Shear Wood -to -Metal Connections Steel Side Members Connection ID: Beam End Connection at for T1 Loadings Dead = 0 lbs. Bolt Diameter = 0.750 inches Floor = 0 lbs. Fyb = 45 ksi (for A307 bolt) Snow = 0 lbs. . tm = 5.50 inches (main member) Const. = 0 lbs. width, m = 11.50 inches (main member) Seismic = 10,929 lbs. Om = 45.0 degrees I Wind = 1,912 lbs. Em = 1,600 ksi (main member) Fern (parallel) =- 5,600 psi (parallel) DF -L Fern (perpendicular)- 2,578 psi (main member) SGm = 0.50 DF -L Main Member Specific Gravity, EWP, DF -L, HF, SP or SPF Femo = 3,531 psi (main member) is = 0.19 inches (side member) width, s = 10.00 inches (side member) Fes = Fu = 58 ksi (for A36 steel) Es = 29,000 ksi (side member) Re = 0.061 Ko = 1.125 k3 = 16.749 CM = 1.00 Wet Service Factor Ct = 1.00 Temperature Factor CD= 1.00 Geometry Factor Cg = 1.00 Group Action Factor Rea = 0.930575 Member Stiffness Ratio M = 0.8680 n = 2 number of fasteners in a row S = 6 inches, Bolt Spacing (In a row) now = 2 total number of rows ntotai = 4 total number of fasteners N.D.S. 8.3.2.1 Eq.'s Eq 8.3-1 Z = " 3,237 Ib. Mode Im Eq 8.3-3 Z = 2,242 Ib. Mode III., Eq 8.3-4 Z = 3,123 Ib. Mode IV Z'= Z(CD`CM`Ct`Cg"CD) Conn Design Capacit 2013 CBC $ ASCE 7-10 Load Combinations: Loads y DL RLL FILL Snow Wind EQ Obs Cd Z' Obs EQ 16-8 1 0 0.9 8068 OK111 EQ 16-9 1 1 0 1.25 11205 OK111 EQ 16-10 1 1 0 1 8964 OK111 EQ 16-10 1 1 0 1.25 11205 OK111 EQ 16-11 1 0.75 0.75 0 1.25 11205 OK111 EQ 16-11 1 0.75 0.75 0 1.15 10309 OK111 EQ 16-12 1 0.6 1147.21004 1.6 14342 OK111 EQ 16-12 1 -0.6 -1147.21 1.6 14342 OK111 EQ 16-12 1 0.7 7650.32969 1.6 14342 OK111 EQ 16-12 1 -0.7 -7650.3297 1.6 14342 OKM EQ 16-13 1 0.75 0.75 0.75 1434.01255 1.6 14342 OK111 EQ 16-13 1 0.75 0.75 -0.75 -1434.0126 1.6 14342 OK111 EQ 16-13 1 0.75 0.525 5737.74727 1.6 14342 OKIII EQ 16-13 1 0.75 -0.525 -5737.7473 1.6 14342 OK111 EQ 16-14 0.6 0.6 1147.21004 1.6 14342 OKIII EQ 16-14 0.6 -0.6 -1147.21 1.6 14342 OK111 EQ 16-15 0.6 0.7 7650.32969 1.6 14342 OK111 EQ 16-15 0.6 -0.7 -7650.3297 1 1.6 1 14342 lOK111 Pg. 16 2012 NDS Bolt Yield Limit Analysis For Double Shear Wood -to -Metal Connections Steel Side Members Connection ID: Beam End Connection at force T2 Loadings Dead = 0 lbs. Bolt Diameter = 0.750 inches Floor = 0 lbs. r Fyb = 45 ksi (for A307 bolt) Snow = 0 lbs. tm = 5.50 inches (main member) Const. = 0 lbs. width, m = 5.50 inches (main member) Seismic = 16,861 lbs. Om = 0.0 degrees I Wind = 2,950 lbs. Em = 1,600 ksi (main member) Fern (parallel) = 5,600 psi (parallel) DF -L Fern (perpendicular) = 2,578 psi (main member) SGm = 0.50 DF -L Main Member Specific Gravity, EWP, DF -L, HF, SP or SPF Femo = 5,600 psi (main member) is = 0.19 inches (side member) width, s = 3.00 inches (side member) Fes = Fu = 58 ksi (for A36 steel) Es = 29,000 ksi (side member) Re = 0.097 Ko = 1.000 Q = 13.227 CM = 1.00- Wet Service Factor Ct = 1.00 Temperature Factor. CD= 1.00 Geometry Factor Cg = 0.98 Group Action Factor Rea = 0.67407 Member Stiffness Ratio M = 0.8274 n = 3 number of fasteners in a row S = 4 inches, Bolt Spacing (In a row) nrow = 1 total number of rows n1Otei = 3 total number of fasteners N.D.S. 8.3.2.1 Eq.'s Eq 8.3-1 Z = 5,775 Ib. Mode Im Eq 8.3-3 Z = 3,105 Ib. Mode Ills Eq 8.3-4 Z = 4,352 Ib. Mode IV Z' = Z(CD*CM-Ct-Cg'CD) Conn Design Capacit 2013 CBC & ASCE 7-10 Load Combinations: Loads y DL RLL FLL Snow Wind EQ Obs Cd Z' Ibs EQ 16-8 1 0 0.9 8252 OK111 EQ 16-9 1 1 0 1.25 11461 OK111 EQ 16-10 1 1 0 1 9168 OK111 EQ 16-10 1 1 0 1.25 11461 OKII! EQ 16-11 1 0.75 0.75 0 1.25 11461 OK111 EQ 16-11 1 0.75 0.75 0 1.15 10544 OK!11 EQ 16-12 1 0.6 1769.89091 1.6 14669 OK111 EQ 16-12 1 -0.6 -1769.8909 1.6 14669 OK111 EQ 16-12 ' 1 0.7 11802.7636 1.6 14669 OK111 EQ 16-12 1 -0.7 -11802.764 1.6 14669 OK111 EQ 16-13 1 0.75 0.75 0.75 2212.36364 1.6 14669 OK111 EQ 16-13 1 0.75 0.75 -0.75 -2212.3636 1.6 14669 OK111 EQ 16-13 1 0.75. 0.525 8852.07273 1.6 14669 OK111 EQ 16-13 1 0.75 -0.525 -8852.0727 1.6 14669 OK111 EQ 16-14 0.6 0.6 1769.89091 1.6 14669 OK111 EQ 16-14 0.6 -0.6 -1769.8909 1.6 14669 OK111 EQ 16-15 0.6 0.7 11802.7636 1.6 14669 OK111 EQ 16-15 0.6 -0.7 -11802.764 1.6 14669 OK111 Massa Addition P 17 L ®. S E Q U. O 1 A Beam1 Wood Wo r ks E N G I N E E R N Oct. 3, zo,fi ,z:os SOFrWAREfOR WOOD DESIGN Design Check Calculation Sheet woodworks sizer 10.4 Loads: Load Type Distribution Pat- tern Location [ft) Start End Magnitude Start End Unit Roof Of, - New Dead Full Area E' 1.8 million - 1.00 - - - 2576 18.00(6.00') psf Roof LL - New Roof live Full Area 8464 - 2041 20.00(6.00') psf Floor DL Dead Full Area Min r 'd 2.41•• 15.00(7.00'1 psf Floor LL Live Full Area 0.51 Total Defl'n 40.00(7.00') psf wall DL Dead Full Area 0.99 19.00(8.00.1 psf Roof DL - Uppr Dead Full Area 18.00(7.001) psf Roof LL - Uppr Roof live Full Area 20.00(7.00') psf Self-wei h[ Dead Full UDL 24.2 if Maximum Reactions (lbs) and Bearing Lengths (in) : 18'4.8" 18'-2.4" Unfactored: _ Cr Cfr[ Ci Cn LC8 Dead 4738 Fb'+ 2800 1.00 - 1.00 0.937 0.96 - 4738 Live 2576 E' 1.8 million - 1.00 - - - 2576 Roof Live Factored: 2392 Fv- 2392 Total Bearing: 8464 - 2041 8464 Length2.4] psi �AnalySia/3esiShear-Fv'-285psifv fb/Fb' - 2.41 Min r 'd 2.41•• - L/709 2.41'• Minimum Dearing iengm governed oy me required mdm or me Supporting member. Kitchen Beam LVL n -ply, 1.812, 2800Fb, 1-314"x16", 3 -ply (5-1/4"x16") Supports: All 'Timber -soft Beam, D.Fir-L No.2 Total length: 18'4.8"; volume = 10.7 cu.ft.; Lateral support: top= at supports, bottom= at supports; Repetitive factor. applied where permitted (refer to online help); Analysis vs. Allowable Stress and Deflection using NDS 2012: Criterion!Analysis Value Cr Cfr[ Ci Cn LC8 Value Unit Fb'+ 2800 1.00 - 1.00 0.937 0.96 - 1.04 1.00 - - 3 Fcp' 750 - - 1.00 - - - - 1.00 - - - E' 1.8 million - 1.00 - - - - 1.00 - - 3 Eminy' 0.93 million - 1.00 - - - - 1.00 - - 3 Fv- 0.99 Bending)+) fb - 2041 �De.iqri Fb• - 2730 psi �AnalySia/3esiShear-Fv'-285psifv fb/Fb' - 0.75 Live Defl'n 0.31 - L/709 0.61 - L/360 CALCULATIONS: 0.51 Total Defl'n 0.90 - L/242 0.91 - L/240 in 0.99 Additional Data: FACTORS: F/E(psi)CD CM Ct CL CV Cfu Cr Cfr[ Ci Cn LC8 Fv' 285 1.00 - 1.00 - - - - 1.00. - 1.00 3 Fb'+ 2800 1.00 - 1.00 0.937 0.96 - 1.04 1.00 - - 3 Fcp' 750 - - 1.00 - - - - 1.00 - - - E' 1.8 million - 1.00 - - - - 1.00 - - 3 Eminy' 0.93 million - 1.00 - - - - 1.00 - - 3 CRITICAL LOAD COMBINATIONS: Shear LC 13 - D+.75(L+Lr), V - 8374, V design - 7055 lbs Bending(+): LC 13 - D+.751L+Lr), M - 38104 lbs -ft Deflection: LC 13 - D+.751L+L r) (live) LC 13 - D+.75(L+Lr) (total) D -dead L -live S -snow w -wind I -impar[ Lr -roof live Lc -concentrated E -earthquake All IX a are listed in Che Analysis output Load combinations: ASCE 7-10 / IBC 2012 CALCULATIONS: Deflection: EI - 1075e06 lb-int/ply "Live. deflection - Deflection from all nn -dead loads (live, wind, snow...) Total Deflection - 1.50(Dead Load Deflection) + Live Load Deflection. Lateral stability (+): Lu - 18'-2.44•' Le - 33•-8.00" RB - 15.31 Design Notes: 1. WoodWorks analysis and design are In accordance Wth the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verity that the default defection limits are appropriate for your application. 3. System factor KH may not apply to field -assembled multi -ply beams. 4. SCL-BEAMS (Structural Composite Lumber): the attached SCL selection is for preliminary design only. For final member design contact your local SCL manufacturer. 5. Size factors vary from one manufacturer to another for SCL materials. They can be changed in the database editor. 6. BUILT-UP SCL-BEAMS: contact manufacturer for connection details when loads are not applied equally to all plys. 7. FIRE RATING: Joists, wall studs, and multi -ply members are not rated for fire endurance. M11 assa Addhion SEQUOIA Q U O I A 1054 Pg. 18 WoodWorks® Oct. E: N G I N E E R ) N G O 3, zols 12:06 SOFTWARE AOR WOOD OCROV Design Check Calculation Sheet Wood Works Sizer 10.4 Loads: Load Type Distribution Pat- Location (ft] Magnitude Unit Roof Live Factored: 245 165 tern Start End Star[ End 299 Roof DL Dead Full Area No 13.00(24.0") psf Roof LL Roof live Full Area No 20.00(24.0") Ps Self h[ Dead Full UDL No 3.3 olf Maximum Reactions (lbs) and Bearing Lengths (in) : 1r -1o.1" 1'-9- W.2 W Unfactored: Analysis Value Dead 201 135 Roof Live Factored: 245 165 Total Bearing: 446 299 Length 5.50 0.50• Min req'd 0.50` 0.50• -Minimum beat hill lencit setting used: 112" for end si pports 1138 maximum reaouon on of Ieasf one suppon is from a amereni load combination than the crrucal one for beanng design, shO here, due to Kd factor. See Analysis malts for reaction from critical load combination. New Rafter Lumber -soft, D.Fir-L, No.2, 2x10 (1-112"x9-1/4") Supports: 1 - Timber -soft Beam, D.Fir-L No.2; 2 - Non -wood; Roof joist spaced at 24.0' c/c; Total length: 11'-1D.1'; volume = 1.1 cu.ft.; Pilch: 6112; Lateral support: top= full, bottom= at Supports; Repetitive factor. applied where permitted (refer to online help); Analysis vs. Allowable Stress and Deflection using NOS 2012: Criterion Analysis Value Desi Value Unit Anal sis/Desi - - 1.00 Shear fv - 25 Fv'n= 180 psi fv Fv' - 0.14 Bending(+) Eb -. 336 Fb' - 1138 psi fb/Fb' - 0.30 Bending(-) fb - 62 Fb' 793 psi fb/Fb' - 0.08 Deflection: 0.03 - <L/999 0.47 - L/240 in 0.0: Interior Live Total 0.07 - <L/999 0.63 L/180 Load combinations: ASCE 7-10./ IBC 2012 0.1: Cantil. Live -0.02 " <L/999 0.20 - L/120 in 0.10 Total -0.04 - L/540 0.26 - L/90 in calculated for each 0.17 Additional Data: FACTORS: F/E(psi)CD CM Ct CL' CF Cfu Cr Cfrt Ci Cn LCI Fv' 160 1.00 1.00 1.00 - - - - 1.00 1.00 1.00 2 Fb'+ 900 1.00 1.00 1.00 1.000 1.100 1.00 1.15 1.00 1.00 - 2 Fb'- 900 1.00 1.00 1.00 0.696 1.100 1.00 1.15 1.00 1.00 - 2 Fc p' 625 - 1.00 1.00 - - - - 1.00 1.00 - - E' 1.6 million- 1.00 1.00 - - - - 1.00 1.00 - 2 Emin' 0.58 million 1.00 1.00 - - - - 1.00 1.00 - 2 CRITICAL LOAD COMBINATIONS: She":LC 12 - D' LrV - 288, V design - 230 lbs Bending(+): LC 12 - D+Lr, M - 599 lbs -ft Bending(-): LC 12 - D+ Lr M17111 lbs -ft Deflection: LC 12 - D+ Lr (live) LC 12 - D+Lr (total) D -dead L -live S. snowW-wind I -impact Lr -roof live Lc -concentrated E -earthquake A11 Lt's are listed in the Analysis output Load combinations: ASCE 7-10./ IBC 2012 CALCULATIONS: Deflection: EI - 158e06 lb -int "Live" deflection - Deflection from all non -dead loads (live, wind, snow -1, To W1 Deflection - 1.50(Dead Load Deflection) + Live Load Deflection. Bearing: Allowable bearing at an angle F'theta calculated for each support as per NDS 3.10.3 Lateral stability (-): Lu - 9-5.75" Le - 15-11.56" RB - 28.06 Design Notes: 1. Wood Works analysis and design are in accordance with the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verity that the default deflection limits are appropriate for your application. 3. Continuous or Cantilevered Beams: NDS Clause 4.2.5.5 requires that normal grading provisions be extended to the middle 2/3 of 2 span beams and to the full length of cantilevers and other spans. 4. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1. 5. SLOPED BEAMS: level bearing is required for all sloped beams. 6. FIRE RATING: Joists, wall studs, and multi -ply members are not rated for fire endurance. Massa Addition Pg. 19 S E. Q U 0 1 A 16-054 I WoodWorks® Oct.am3 E N G I N f f R) N G o 3, 2016 12:07 SDiTWAPFiDP WOOD DELCN CIVIL & STRUCTURAL I Design Check Calculation Sheet WoodWorks Sizer 10.4 Loads Load, Type Distribution Pat- Location (ft) Magnitude Unit Anal. sis/Desi 1392 tern Start End Start End 1361 Roof DL Dead Full Area fv/Fv' = 2754 19.00(10.00') psf Roof LL Roof live Full Area Min re 'd 0.85 20.00(10.00') psf Self -weight Dead Full UDL <L/999 0.45 = 14.7 if Maximum Reactions (Ibs) and Bearing Lengths (in) : 14' - 13'-6.5' Unfactored: Anal sis Value Design Dead 1467 Anal. sis/Desi 1392 Roof Live Factored: 1439 57 1361 Total Bearing: 2906 fv/Fv' = 2754 Length 5.50 960 0.80 Min re 'd 0.85 fb/Fb' = 0.80 Eave Beam at Patio Timber -soft, D.Fir-L, No. 1, 6x12 (5-1/2"x11-1/4") Supports: 1 -Timber-soft Beam, D.Fir-L No -2; 2 - Non -wood; Total length: 114% volume = 6.0 cu.ft.; Beam and stringer, Lateral support: top= at supports, bottom= at supports; Analysis vs. Allowable Stress and Deflection using Nos 2012: Criterion Anal sis Value Design Value Unit Anal. sis/Desi n Shear fv = 57 Fv' = 170 psi fv/Fv' = 0.33 Bend ing(+) 1 fb = 960 Fb' = 1332 psi fb/Fb' = 0.72 Live Defl'n 0.15 = <L/999 0.45 = L/360 in 0.32 Total Defl'n 0.37 L/442 0.68 - L/240 in 0.54 Additional Data: FACTORS: F/E(psi)CD CM Ct CL CF Cfu Cr Cfrt Ci Cn LC# Fv' 170 1.00 1.00 1.00 - - - - 1.00 1.00 1.00 2 Fb'+ 1350 1.00 1.00 1.00 0.987 1.000 1.00 1.00 1.00 1.00 - 2 Fcp' 625- 1.00 1.00 - - - - 1.00 1.00 - - E' 1.6 million 1.00 1.00 - - - 1.00 1.00 - 2 Emin' 0.58 million 1.00 1.00 - - - - 1.00 1.00 - 2 CRITICAL LOAD COMBINATIONS: Shear: LC #2 = D+Lr, V = 2741, V design = 2348 lbs Bending(+): LC #2 = D+Lr, M = 9279 lbs -ft Deflection: LC #2' = D+Lr (live) LC #2 = D+Lr (total) D=dead L=live S=snow W=wind I=impact Lr=roof live Lc=concentrated E=earthquake All LC's arelisted in the Analysis output . Load combinations: ASCE 7-10 / IBC 2012 CALCULATIONS: Deflection: EI = 1044e06 lb -int "Live" deflection -= Deflection from all non -dead loads (live, wind, snow...) ' Total Deflection = 1.50(Dead Load Deflection) + Live Load Deflection. Lateral stability (+): Lu - 13-6.50" Le = 24-11.06" RB = 10.55 Design Notes: 1. WoodWorks analysis and design are in accordance with the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verify that the default deflection limits are appropriate for your application. 3. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1. ® Type S 'E Q U O.1 A Massa Addition P9. 20 l WoodWorks Unit E N G I N E 'E R I N G eam4 B, m4 Oct. zols 12:07 Design Check Calculation Sheet WoodWorks Sizer 10.4 I Loads: Load Type Distribution Pat- Location [ft] Magnitude Unit Roof Live Factored: 1190 - - 1190 tern Start End Start End 2417 Roof DL Dead Full Area Min re 'd 19. 00(8.50') psf Roof LL Roof live Full Area Nos 2012: 20.00(8.50') psf Self-wei ht Dead Full UDL 0.44 = 14.1 if Maximum Reactions (lbs) and Bearing Lengths (in) : 14' 13'1.7" Unfactored: - Dead 1227 1227 Roof Live Factored: 1190 - - 1190 Total Bearing: 2417 2417 Length 5.50 5.50 Min re 'd 0.70 0,70 Additional Data: FACTORS: F/E(psi)CD CM Ct CL CF Cfu Cr Cfrt Ci Cn LC# Fv' 170 1.00 1.00 1.00 - - - - 1.00 4.00 1.00 2 Fb'+ 1350 1.00 1.00 1.00 0.987 1.000 1.00 .1.00 1.00 1.00 - 2 Fcp' 625 - 1.00 1.00 - - - 1.00 1.00 - . - - E' 1.6 million 1.00 1.00 - - - 1.00 1.00 2 Emin' 0.58 million 1.00 1.00 - - - - 1.00 1.00 - 2 CRITICAL LOAD COMBINATIONS: - Shear : LC #2 = D+Lr, V - 2275, V design = 1940 lbs Bending(+): LC #2 = D+Lr, M = 7474 lbs -ft Deflection: LC #2 = D+Lr (live) LC #2 = D+Lr (total) D=dead L=live S=snow W=wind I=impact Lr=roof live Lc=concentrated E=earthquake All LC's are listed in the Analysis output Load combinations: ASCE 7-10 / IBC 2012 CALCULATIONS: Deflection: EI = 1044e06 lb -int "Live"deflection- Deflection from all non -dead loads (live, wind, snow...) Total Deflection = 1.501Dead Load Deflection) + Live Load Deflection. - Lateral stability-(+): Lu = 13-1.69" Le - 24-2.81" RB = 10.40 Design Notes: 1. WoodWorks analysis and design are in accordance with the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verity that the default deflection limits are appropriate for your application. 3. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1. Ridge Beam at Patio Timber -soft, D.Fir-L, No. 1, 6x12 (S7/2"x11-1/4") = 47 Supports: All -Timber-soft Column, D.Fir-L No.2 170 psi `_v/Fv' Total length: 14% volume = 6.0 cu.ft.; Beam and stringer, Bending(+) fb = 773 Lateral support: top= at supports, bottom= at supports; Analysis vs. Allowable Stress and Deflection using Nos 2012: Criterion Analysis Value Design Value Unit Analysis/Design 0.44 = Shear - f 0.25 Total Defl'n 0.28 = L/564 0.66 = L/240 in 0.42 Additional Data: FACTORS: F/E(psi)CD CM Ct CL CF Cfu Cr Cfrt Ci Cn LC# Fv' 170 1.00 1.00 1.00 - - - - 1.00 4.00 1.00 2 Fb'+ 1350 1.00 1.00 1.00 0.987 1.000 1.00 .1.00 1.00 1.00 - 2 Fcp' 625 - 1.00 1.00 - - - 1.00 1.00 - . - - E' 1.6 million 1.00 1.00 - - - 1.00 1.00 2 Emin' 0.58 million 1.00 1.00 - - - - 1.00 1.00 - 2 CRITICAL LOAD COMBINATIONS: - Shear : LC #2 = D+Lr, V - 2275, V design = 1940 lbs Bending(+): LC #2 = D+Lr, M = 7474 lbs -ft Deflection: LC #2 = D+Lr (live) LC #2 = D+Lr (total) D=dead L=live S=snow W=wind I=impact Lr=roof live Lc=concentrated E=earthquake All LC's are listed in the Analysis output Load combinations: ASCE 7-10 / IBC 2012 CALCULATIONS: Deflection: EI = 1044e06 lb -int "Live"deflection- Deflection from all non -dead loads (live, wind, snow...) Total Deflection = 1.501Dead Load Deflection) + Live Load Deflection. - Lateral stability-(+): Lu = 13-1.69" Le - 24-2.81" RB = 10.40 Design Notes: 1. WoodWorks analysis and design are in accordance with the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verity that the default deflection limits are appropriate for your application. 3. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1. = 47 Fv' = 170 psi `_v/Fv' 0.28 Bending(+) fb = 773 Fb' = 1333 psi, fb/Eb' = 0.58 Live Defl'n 0.11 <L/999 0.44 = L/360 in 0.25 Total Defl'n 0.28 = L/564 0.66 = L/240 in 0.42 Additional Data: FACTORS: F/E(psi)CD CM Ct CL CF Cfu Cr Cfrt Ci Cn LC# Fv' 170 1.00 1.00 1.00 - - - - 1.00 4.00 1.00 2 Fb'+ 1350 1.00 1.00 1.00 0.987 1.000 1.00 .1.00 1.00 1.00 - 2 Fcp' 625 - 1.00 1.00 - - - 1.00 1.00 - . - - E' 1.6 million 1.00 1.00 - - - 1.00 1.00 2 Emin' 0.58 million 1.00 1.00 - - - - 1.00 1.00 - 2 CRITICAL LOAD COMBINATIONS: - Shear : LC #2 = D+Lr, V - 2275, V design = 1940 lbs Bending(+): LC #2 = D+Lr, M = 7474 lbs -ft Deflection: LC #2 = D+Lr (live) LC #2 = D+Lr (total) D=dead L=live S=snow W=wind I=impact Lr=roof live Lc=concentrated E=earthquake All LC's are listed in the Analysis output Load combinations: ASCE 7-10 / IBC 2012 CALCULATIONS: Deflection: EI = 1044e06 lb -int "Live"deflection- Deflection from all non -dead loads (live, wind, snow...) Total Deflection = 1.501Dead Load Deflection) + Live Load Deflection. - Lateral stability-(+): Lu = 13-1.69" Le - 24-2.81" RB = 10.40 Design Notes: 1. WoodWorks analysis and design are in accordance with the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verity that the default deflection limits are appropriate for your application. 3. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1. t Massa Addition Pg. 21 S. E Q _U O 1 ^ 16.054 WoodWorks® Beam5 . snmvurrrrw w000 nracx E N G L .N E 'E R I N G opt. 3, 2016 12:07 r -CIVIL & STRUCTURAL Design Check Calculation Sheet WoodWorks Sizer 10.4 I Loads: Load Type Distribution Pat- Location [ft) Magnitude Unit gyred: n tern Start End Start End Fv' Roof DL Dead Point 8.42 1227 lbs Roof LL Roof live Point 8.42 1190 lbs Self -wet ht Dead Full UDL 0.53 = 14.7 if Maximum Reactions (lbs) and Bearing Lengths (in) : L 15- 1 stored: ad 731 731 Df Live 595 595 gyred: n tal 1326 1326 ing: Fv' 3th 5.50 5.50 re 'd 0.50+ 0.50' num bearing length setting used: 1/2" for end supports fb = Ridge Beam at Patio Timber -soft, D.Fir-L, No. 1, 6x12 (5.1/2"x11-1/4") Supports: All - Timber -soft Column, D.Fir-L No.2 Total length: 16-10.0'; volume = 7.2 cu.ft.; Beam and stringer; Lateral support: top= at supports, bottom= at supports; Analysis vs. Allowable Stress and Deflection using Nos 2012: Criterion Analysis Value Desi n Value Unit Anal e Additional Data: FACTORS: F/E(psi)CD CM Ct CL CF Cfu Cr Cfrt Ci Cn LC# Fv' 170 1.00 1.00 1.00 - - - 1.00 1.00 1.00 2 Fb'+ 1350 1.00 1.00 1.00 0.984 1.000 1.00 1.00 1.00 1.00 - 2 Fcp' 625 - 1.00 1.00 - - - - 1-00. 1.00 - - E' 1.6 million 1.00 1.00 - - - - 1.00 1.00- 2 Emin' 0.58 million 1.00 1.00 - - 1.00 1.00 - 2 - CRITICAL LOAD COMBINATIONS: Shear : LC #2 - D+Lr, V - 1312, V design = 1312 lbs Bending(+): LC 42 - D+Lr, M - 10111 lbs -ft Deflection: LC #2 - D+Lr (live) - LC #2 = D+Lr (total) D=dead L=live S=snow W=wind I=impact Lr=roof live Lc=concentrated E=earthquake All LC's are listed in the Analysis output Load combinations:_ASCE 7-10 / IBC 2012 CALCULATIONS: Deflection: EI = 1044e06 lb -int "Live" deflection.= Deflection from all non -dead loads (live, wind, snow...) - .. .Total Deflection=.1.50(Dead Load Deflection) + Live Load Deflection. - Lateral stability (+): Lu = 15-11.50" Le = 29-9.38" RB = 11.45 Design Notes: 1. WoodWorks analysis and design are in accordance with the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verify that the default deflection limits are appropriate for your application. 3. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1. . 5 n Shear fv =- 32 Fv' 170 psi fv/Fv' = 0:19 Bending(+) fb = 1046 Fb' = 1328 psi fb/Pb' = 0.79 Live Defl'n 0.17 = <L/999 0.53 = L/360 in 0.31 Total Defl'n 0.46 = L/420 0.80 = L/240 in 0.57 Additional Data: FACTORS: F/E(psi)CD CM Ct CL CF Cfu Cr Cfrt Ci Cn LC# Fv' 170 1.00 1.00 1.00 - - - 1.00 1.00 1.00 2 Fb'+ 1350 1.00 1.00 1.00 0.984 1.000 1.00 1.00 1.00 1.00 - 2 Fcp' 625 - 1.00 1.00 - - - - 1-00. 1.00 - - E' 1.6 million 1.00 1.00 - - - - 1.00 1.00- 2 Emin' 0.58 million 1.00 1.00 - - 1.00 1.00 - 2 - CRITICAL LOAD COMBINATIONS: Shear : LC #2 - D+Lr, V - 1312, V design = 1312 lbs Bending(+): LC 42 - D+Lr, M - 10111 lbs -ft Deflection: LC #2 - D+Lr (live) - LC #2 = D+Lr (total) D=dead L=live S=snow W=wind I=impact Lr=roof live Lc=concentrated E=earthquake All LC's are listed in the Analysis output Load combinations:_ASCE 7-10 / IBC 2012 CALCULATIONS: Deflection: EI = 1044e06 lb -int "Live" deflection.= Deflection from all non -dead loads (live, wind, snow...) - .. .Total Deflection=.1.50(Dead Load Deflection) + Live Load Deflection. - Lateral stability (+): Lu = 15-11.50" Le = 29-9.38" RB = 11.45 Design Notes: 1. WoodWorks analysis and design are in accordance with the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verify that the default deflection limits are appropriate for your application. 3. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1. . WoodWorks® ,. SOFIWAeFFORWOODMION I Loads: Load SEQ:UO1Aa�s Massa Addition E' N G I N E E R I CIVIL & STRUCTURAL N .G I Oct. 3, 201612:07 Mag Sta Roo IDL - New Dead Design Check Calculation Sheet Area Total Bearing: Wood Works Sizer 10.4 18.0 Roof LL - New Roof live Fu 11 Area nitude Unit rt End 20.0 Floor DL L/360 016.00•) psf Full Area Total Defl'n 016.00.1 Re Floor LL - Load Type Distribution Pat- Cern Location [ft] Start End Mag Sta Roo IDL - New Dead 7u11 Area Total Bearing: 2456 18.0 Roof LL - New Roof live Fu 11 Area 1.12 Live Defl'n 20.0 Floor DL L/360 Dead Full Area Total Defl'n 0.06 - <L/999 15.0017.00') psf Floor LL in Live Full Area 40.0017.00') psf Wall OL Dead Full Area 19.0018.00') psf Roof DL - Uppr Dead Full Area 18.00(7.00') psf Roof LL- Uppr Roof live Full Area 20.0017.00') psf Set f-wei ht Dead Full UDL 7.7 if Maximum Reactions (lbs) and Bearing Lengths (in) : 5-5.2" Pg. 22 Unfactored: - Dead 1355 1355 Live 761 761 Roof Live Factored: 707 707 Total Bearing: 2456 2956 Length 1.12 1.12 Min re 'tl 1.12 1.12 Pocket Door at Pantry Lumber -soft, D.Fir-L, No.2, 4x10 (3-1/2"x9-1/4") Supports: All - Timber -soft Beam, D.Fir-L No.2 Total length: 5-5.7; volume = 1.2 w.ft.; Lateral support: top= at supports, bottom= at supports; Analysis vs. Allowable Stress and Deflection using NDS 2012: in Additional Data: FACTORS: F/E(psi)CD CM C[ CL CF Cfu Cr Cfct Ci Cn LCA Fv' 180 1.00 i.00 1.00 - - - - 1.00 1.00 1.00 3 Fb'+ 900 1.00 1.00 1.00 0.991 1.200 1.00 1.00 1.00 1.00 - 3 Fc P. 625 - 1.00 1.00 - - - - 1.00 1.00 - - E' 1.6 million 1.00 1.00 - - - - 1.00 1.00 - 3 Froin' 0.58 million 1.00 1.00 - - - - 1.00 1.00 - 3 CRITICAL LOAD COMBINATIONS: Shear : LC f3 - 0+,75(L+Lc), V - 2414, V design - 1676 lbs .ending(+): LC 13 - D+.75 (L+Lr), M- 3225 lbs -ft Deflection: LC 13 - D+.75(L+Lr) (live) LC 13 - D+.75(L+Lr) (total) D -dead L -live 8=snow W -wind 1 -impact Lr -roof live L-Oncentrated E -earthquake All LC's are listed in the Analysis output Load combinations: ASCE 7-10 / SBC 2012 CALCULATIONS: Deflection: EI - 369:06 lb -int "Live" deflection Deflection from all non -dead loads (live, wind, snow_) Total Deflection - 1.50(Dead Load Deflection) + Live Load Deflection. Lateral stability (+)r Lu - 5'-4.13" Le - 11'-0.06" RB - 9.99 Design Notes: 1. WoodWorks analysis and design are in accordance with the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verify Nat the default deflection limits are appropriate for your application. 3. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1. Criterion Anal sis Value Desi n Value Unit Anal sis/Desi Shear Ev - 1B0 psi fv, Fv'- 0.4' Bending(+) fb - 775 Fb' - 1070 psi fb/Fb' - 0.7<' Live Defl'n 0.02 - <L/999 0.18 - L/360 O.lY Total Defl'n 0.06 - <L/999 0.27 - L/290 in 0.21 Design Check Calculation Sheet WoodWorks Sizer 10.4 Loads: Load Type Distribution S. E' Q .0 O. 1 A Massa Addition 16-054 WoodWorks® SOFRYABt inP WODD DEW.A Floor DL Dead E N G I N F E R I N G Beam? oDl. 3, rots 12:08 Design Check Calculation Sheet WoodWorks Sizer 10.4 Loads: Load Type Distribution Pat- tern Location [ft] Magnitude Start End Start End Unit Floor DL Dead Full Area Roof Live Factored: 15.0018.00') psf Floor LL Live Full Area Length 40.0018.00') psf Wall DLDead 1.59•" Full Area psi 19.00(8.00') psf Roof DL - Uppr Dead Point 0.39 = 8.63 1094 lbs Roof LL - Uppr Roof live Point 0.51 = 8.63 1171 lbs Self-wei ht Dead Full UDL 0.87 11.3 plf Maximum Reactions (lbs) and Bearing Lengths (in) : 11'-9.5' Pg. 23 11'-7.7' Unfactored: Analysis Value Dead 1957 2476 Live 1884 - 1888 Roof Live Factored: 310 861 Total Bearing: 3841 4538 Length 1.59 1.87 Min re 'd 1.59•" 1,87.* rvmmimum bearing iengm governed Dy me required vndm or me supporting member. Floor Beam LVL n -ply, 1.8E, 22001Fb, 1-3/4"x11-1/4", 2 -ply (3-1/2"x11-1/4") Supports: All - Timber -soft Beam, D.Fir-L No.2 Total length: 11'-9.5"; volume = 3.2 cu.ft.; Lateral support: lop= at supports, bottom= at supports; Analysis vs. Allowable Stress and Deflection using NDS 2012: Criterion Analysis Value Desi n Value Unit Anal s'_s/Desi n Shear fv = 151 Fv' = 285 psi fv. = 0.53 Bending(+) fb = 1977 Fb' - 2130 psi fb!Fb' = 0.93 Live Defl'n 0.18 = L/772 0.39 = L/360 in Deflection: LC 13 - D+.75(L+Lr) (live) 0.47 Total Defl'n 0.51 = L/276 0.58 = L/240 in All LC's are listed in the Analysis output 0.87 Additional Data: FACTORS: F/E(psi)CD CM Ct CL CV Cfu Cr Cfrt Ci Cn LC# Fv' 285 1.00 - 1.00 - - - - 1.00 - 1.00 3 Fb'+ 2200 1.00 - 1.00 0.960 1.01 - 1.00 1.00 - - 3 Fcp' 750 - - 1.00 - - - - 1.00 - - - E' 1.8 million - 1.00 - - - - 1.00 - - 3 Eminy' 0.93 million - 1.00 - - - - 1.00 -. - 3 CRITICAL LOAD COMBINATIONS: Shear LC #3 = D+.75(L+Lr), V = •4498, V design 3967 lbs Bending(+): LC #3 - D+.75(L+Lr), M = 12165 lbs -ft Deflection: LC 13 - D+.75(L+Lr) (live) LC #3 = D+.75(L+Lr) (total) D=dead L=live S=snow W=wind I=impact Lr=roof live Lc=concentrated E -earthquake All LC's are listed in the Analysis output Load combinations: ASCE 7-10 / IBC 2012 CALCULATIONS: Deflection: EI 374e06 lb-int/ply "Live" deflection = Deflection from all non -dead loads (live, wind, snow...) Total Deflection = 1.50(Dead Load Deflection) + Live Load Deflection. Lateral stability (+): Lu = 111-7.75" Le = 21-9.50" RB = 15.50 Design Notes: 1. WoodWorks analysis and design are in accordance with the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verity that the default deflection limits are appropriate for your application. 3. SCL-BEAMS (Structural Composite Lumber): the attached SCL selection is for preliminary design only. For final member design contact your local SCL manufacturer. 4. Size factors vary from one manufacturer to another for SCL materials. They can be changed in the database editor. 5. BUILT-UP SCL-BEAMS: contact manufacturer for connection details when loads are not applied equally to all plys. 6. FIRE RATING: Joists, wall studs, and multi -ply members are not rated for fire endurance. Massa Addition P WoodWorks S E Q U O I A 1-054 g. 24 BeamB snmvAarrna wona nryn+v E N G I N E- -E R I 'N' G oct. 3, 201 12:08 Design Check Calculation Sheet WoodWorks Sizer 10.4 ILoads: Load Type Distribution Pat- tern. Location [ft] Start End Magnitude Start End Unit Roof DL Dead Full Area Total Bearing: 8.00(2.00') psf RoofLL Roof live Full Area Min re 'd 20.00(2.001) psf Ceilinf DL Dead Full Area 1 0.10 = L/885 10.00(6.001) psf Ridge Beam DL Dead Point 4.00 _ 1227 lbs Ridge Beam LL Roof live Point 4.00 1190 lbs Self-wei ht Dead Full UDL 12.1 plf Maximum Reactions (lbs) and Bearing Lengths (in) 8' Unfactored: Analysis Value - -. Dead 963 - 963 Roof Live Factored: 755 755 Total Bearing: 1718 - 1718 Length 3.00 3.00 Min re 'd 0.50* 0.50* Window (1) at Nook Timber -soft, D.Fir-L, No. 1, 6x10 (5-1/2"x9-1/4") Supports: All - Lumber n -ply Column, D.Fir-L Stud Total length: 8; volume = 2.8 cu.ft.; Beam and stringer; Lateral support: top= at supports, bottom= at supports; Analysis vs. Allowable Stress and Deflection using NDS 2012: Criterion Analysis Value Desi n Value Unit Analysis/Design Shear fv = 47 Fv' = 170 psi fv/Fv' = 0.28 Bending(+) fb = 837 Fb' = 1350 psi fb/Fb' = 0.62 Live Defl'n 0.04 = <L/999 0.25 = L/360 in 0.15 Total Defl'h 1 0.10 = L/885 0.38 = L/240 in 0.27 Additional Data: FACTORS: F/E(psi)CD CM Ct CL CF Cfu Cr Cfrt Ci Cn LC# Fv' 170 1.00 1.00 1.00 - - - - 1.00 1.00 1.00 2 Fb'+ 1350 1.00 1.00 1.00 1.000 1.000 1.00 1.00 1.00 1.00 - 2 Fcp' 625 - 1.00 1.00 - - - - 1.00 1.00 - - E. 1.6 million 1.00 1.00 - - - - . 1.00 1.00 - 2. CRITICAL LOAD COMBINATIONS: Shear : LC #2 = D+Lr, V - 1691, V design = 1590 lbs Bending(+): LC 42 = D+Lr, M = 5468 lbs -ft Deflection: LC 42 = D+Lr (live) LC 42 = D+Lr (total) D=deadL=live S=snow W-ind I=impact Lr=roof live Lc=concentrated E=earthquake All LC's arelisted in the Analysis output Load combinations: ASCE 7-10 / IBC 2012 -, CALCULATIONS: Deflection: EI = 580e06 lb -int - "Live" deflection = Deflection from all non -dead loads (live, wind, snow...) Total Deflection = 1.50(Dead Load Deflection) + Live Load Deflection. Design Notes: 1. WoodWorks analysis and design are in accordance with the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verify that the default deflection limits are appropriate for your application. 3. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1. - - Massa Addition S E Q U O I A 16-054 WoodWorks® Beam9 -SO ASFF"WOOD0MGM E N G I N E€ R I 'N C Oct. 3, 2016 12:08 ®L & STRUCTURAL Design Check Calculation Sheet WoodWorks Sizer 10.4 I Loads: Load Type Distribution Pat- Location [ft] Magnitude Unit 523 Roof Live Factored: tern Start End .Start End Total Bearing: Roof DL Dead Full Area Length 18.00(7.00') psf. Roof LL Roof live Full Area 0.50* 20.00(7.001) psf Self-wei ht Dead Full UDL fb/Fb' = 9.5 Plf Maximum Reactions (lbs) and Bearing Lengths (in) T -9 - Pg. 25 Unfactored• Analysis Value Dead 523 523 Roof Live Factored: 543 543 Total Bearing: 1065 1065 Length 3.00 3.00 Min re 'd 0.50* 0.50* Window Hdr at Kitchen Timber -soft, D.Fir-L, No. 1, 6x8 (5-1/2"x7-1/4") Supports: All - Lumber n -ply Column, D.Fir-L Stud Total length: T-9.0"; volume = 2.1 cuff; Post and timber; Lateral support: top= at supports, bottom= at supports; I Analysis vs. Allowable Stress and Deflection usina NDS 2012 Criterion Analysis Value Design Value Unit Analysis/Design Shear fv = 31 Fv' = 170 psi fv/Fv' = 0.18 Be 0ding(+) fb= 456 Fb' = 1200 psi fb/Fb' = 0.38 Live Defl'n 0.03 = cL/999 0.24 = L/360 in. 0.13 Total Defl'n 0.08 <L/999 0.36 = L/240 in 0.21 Additional Data: FACTORS: F/E(psi)CD CM Ct CL CF Cfu Cr Cfrt Ci Cn LC# Fv' 170 1.00 1.00 1.00 - - - - 1.00 1.00 1.00 2 Fb'+1200 1.00 1.00 1.00 1.000 1.000 1.00 1.00 1.00 1..00 - 2 Fcp' 625 - 1.00 1.00 - - - - 1.00 1..00 - - E' 1.6 million 1.00 1.00 - - - - 1.00 1.00 - 2 CRITICAL LOAD COMBINATIONS: Shear : LC $2 = D+Lr, V = 1004, V design = 832 lbs - Bending(+): LC $2 = D+Lr, M = 1831 lbs -ft Deflection: LC 42 = D+Lr (live) , LC U2 =D+Lr (total) D=dead L=live S=snow W=wind I=impact Lr=roof live Lc=concentrated E=earthquake All LCs are listed in theAnalysis output Load combinations: ASCE 7-10 / IBC 2012 CALCULATIONS:' Deflection: EI = 279e06 lb -int "Live" deflection Deflection from all non -dead loads (live, wind, snow...)- Total Deflection = Deflection Load Deflection) + Live Load Deflection. Design Notes: 1. WoodWorks analysis and design are in accordance with the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verify that the default deflection limits are appropriate for your application. 3. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1. ® Type Distribution C E� Q 0 1 A16-054 Massa Addition WoodWorks . Unit 50 .S .0 -E N C I N E E R I 'N C, 'I CIVIL & STRUCTURAL Beam10 oa. 3, zols 12:08 Design Check Calculation Sheet WoodWorks Sizer 10.4 Loads Load Type Distribution Pat- Location [ft) Magnitude Unit 50 Live Factored: 116 tern Start End Start End 164 Roof DL Dead Full Area No 3.50 15.00(16.0") psf Roof LL Live Full Area No fb = 40.00(16.0") psf Self -weight Dead Full UDL No Live Defl'n 2.0 if Maximum Reactions (Ibs) and Bearing Lengths (in) : 1r s'-4.5" Pg. 26 10'-5.3" Unfactored: Analysis Value Desi n Dead 48 143 50 Live Factored: 116 348 122 Total Bearing: 164 492 172 Length 1.75 3.50 5.50 Min re 'd 0.50` 0.42** 0.50* Minimum Dearing length setting used: 12- for end supports "Minimum bearing length governed by the required width of the supporting member. Floor Joist Lumber -soft, D.Fir-L, No.2, 2x6 (1-1/2"x5-112") Supports: 1 - Hanger; 2 - Lumber -soft Beam, D.Fir-L No.z; 3 - Lumber -soft Sill plate, D.Fir-L No.3; Floor joist spaced at 16.0" dc; Total length: 11 ; volume= 0.6 cu.ft.; Lateral support: top= full, bottom= at supports; Repetitive factor. applied where permitted (refer to online help); Analysis vs. Allowable Stress and Deflection using Nos 2012: Criterion Analysis Value Desi n Value Unit Anal sis/Desi n Shear fv = 37 Fv' = 180 psi fv Fv' = 0.21 Bending(+) fb = 252 Fb' - 1345 psi fb/Fb' = 0.19 Bending(-) fb = 408 Fb' = 1270 psi fb/=b' = 0.32 Live Defl'n 0.01 = <L/999 0.18 = L/360 in 1.00 - 0.07 Total Defl'n 0.02 - <L/999 0.27 = L/240 in 206 lbs 0.08 Additional Data: FACTORS: F/E(psi)CD CM Ct CL CF Cfu Cr -Cfrt Ci Cn LC# Fv' 180 1.00 1.00 1.00 - - - - 1.00 1.00 1.00 2 Fb'+ 900 1.00 1.00 1.00 1.000 1.300 1.00 1.15 1.00 1.00 - ' 2 Fb'- :900 1.00 1.00 1.00 0.944 1.300 1.00 1.15 1.00 1.00 - 2 Fcp' 625 - 1.00 1.00 - - - - 1.00 1.00 - - E' 1.6 million 1.00 1.00 - - - - 1.00 1.00 - 2 Emin' 0.58 million 1.00 1.00 - - - - 1.00 1.00 - 2 CRITICAL LOAD COMBINATIONS: Shear : LC #2 = D+L, V = 250, V design = 206 lbs Bending(+): LC #2 = D+L, M = 159 lbs -ft Bending(-): LC #2 = D+L, M = 257 lbs -ft Deflection: LC #2 = D+L (live) LC #2 = D+L (total) D=dead L=live S=snow W=wind I=impact Lr=roof live Lc=concentrated E=earthquake All LC 'sare listed in the Analysis output Load combinations: ASCE 7-10 / IBC 2012 CALCULATIONS: Deflection: EI = 33.3e06 lb -int "Live" deflection - Deflection from all non -dead loads (live, wind, snow...) Total Deflection = 1.50(Dead Load Deflection) + Live Load Deflection. Lateral stability (-): Lu = 5-4.50" Le = 10-1.63" RB = 17.24 Design Notes: 1. WoodWorks analysis and design are in accordance with the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verity that the default deflection limits are appropriate for your application. 3. Continuous or Cantilevered Beams: NDS Clause 4.2.5.5 requires that normal grading provisions be extended to the middle 2/3 of 2 span beams and to the full length of cantilevers and other spans. 4. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1. 5. FIRE RATING: Joists, wall studs, and multi -ply members are not rated for fire endurance. Wood W' orks® -SOnWABFFOR WOOD DEVr:N Loads: Design Check Calculation Sheet WoodWorks Sizer 10.4 Load Massa Addition ,S E - Q .0 O.1 A. 16.054 E N G I N E 'E R 1 N G Beam11 Oct. 312016 12:09 Roof DL Dead RAL Design Check Calculation Sheet WoodWorks Sizer 10.4 Load Type Distribution Pat- Location (ft] Magnitude unit 562 191 Live 557 Factored: tern Start End Start End 557 Roof DL Dead Full Area No 15.00(5.50') f Roof LL Live ` Full Area Yes 40.00(5.501) :PlSf Self-wei ht Dead Full UDL No 4.6 f Maximum Reactions (lbs) and Bearing Lengths (in) 10'-10.5" Pg. 27 1 Unfactored: Analysis Value Design Dead 191 Unit 562 191 Live 557 Factored: fv 1421 557 Total 748 Bearing: psi 1983 748 Length 3.50 fb 3.50 3.50 Min re 'd 0.50' psi 0.53 0.50" ,mn �c u,y ,enyu uny u gnu aupp.n Maximum reaction on at least one support is from a different load combination than the critical one for bearing design, shown here, due to Kd factor. See Analysis results for reaction from critical load combination. - Floor Girder Lumber -soft, D.Fir-L, No.2, 06 (3-1/2"x5-1/2") Supports: All - Lumber Post Column, D.Fir-L No.2 Total length: 10'-10.5'; volume = 1.5 cu.ft.; Lateral support: top= at supports, bottom= at supports; I Analvsis vs. Allowable Stress and Deflection using NDS 2012 Criterion Analysis Value Design Value Unit Analysis/Desi n Shear fv - 63 Fv' = 180 psi fv/Fv' = 0.35 Bending(+) fb = 491 Fb' = 1170 psi fb/Fb' = 0.42 Bending(-) fb = 697 Fb' = 1170 psi fb/Pb' = 0.60 Live Defl'n 0.03 - <L/999 0.17 = L/360 in 0.19 Total Defl'n 0.04 - <L/999 0.26 = L/240 in 0.17 Additional Data: , FACTORS: F/E(psi)CD CM Ct CL CF Cfu_ Cr Cfrt Ci Cn LC# Fv' 180 1.00 1.00 1.00 - - - - 1.00 1.00 1.00 2 Fb'+ 900 1.00 1.00 1.00 1.000 1.300 1.00 1.00 1.00' 1.00 3 Fb'- 900 1.00 1.00 1.00 1.000 1.300 1.00 1.00 1.00 1.00 - 2 Fcp' 625 - 1.00 1.00 - - - - 1.00 1.00 - - E' 1.6 million 1.00 1.00 - - - - 1.00 1.00 - 3 CRITICAL LOAD COMBINATIONS: Shear : LC #2 = D+L, V = 992, V design = 810 lbs Bending(+): LC #3 - D+L (pattern: L_), M = 722 lbs -ft Bending(-): LC #2 =.D+L, M = 1025 lbs -ft Deflection: LC #3 = (live) - LC #3 = (total) D=dead L=live S=snow W=wind I=impact Lr=roof live Lc=concentrated E=earthquake All LC's are listed in the Analysis output Load Patterns: s=S/2, X=L+S or L+Lr, =no pattern load in this .span Load combinations: ASCE 7-10 / IBC 2012 CALCULATIONS: Deflection: EI = 77.6e06 lb -int "Live" deflection = Deflection from all non -dead loads (live, wind, snow...) Total Deflection = 1.50(Dead Load Deflection) + Live Load Deflection. Design Notes: 1. WoodWorks analysis and design are in accordance with the ICC International Building Code (IBC 2012), the National Design Specification (NDS 2012), and NDS Design Supplement. 2. Please verify that the default deflection limits are appropriate for your application. 3. Continuous or Cantilevered Beams: NDS Clause 4.2.5.5 requires that normal grading provisions be extended to the middle 2/3 of 2 span beams and to the full length of cantilevers and other spans. 4. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1. Pg. 28 Timber Column Design Per NDS 2013 Chapter 3.6 & 3.7 Project: Massa Addition Date: 10/3/2016 Comments: Units: kis & feet (UNO) 6x Members DF -L Fc E d cE c 6x 1000 1600000 5.5 0.3 0.8 Stability Reduction Column Capacity Obs) le (ft) Cp Fc' (psi) 6X6 6X8 6X10 6X12 5 0.94 943 28511 38879 49247 59614 6 0.91 912 27586 37618 47649 57681 7 0.87 872 26373 35963 45553 55143 8 0.82 821 24841 33874 42908 51941 9 0.76 761• 23015 31384 39753 48122 10 0.69 694 20989 28621 36253 43886 11 0.63 625 18906 25781 32656 39531 ' 12 0.56 559 16902 23048 29194 35340 13 0.50 498 15061 20538 26015 31492 14 0.44 444 13421 18302 23183 28063 15 0.40 396 11984 16342 20700 25057 16 0.35 355 10734 14637 18541 22444 17 0.32 319 9650 13159 16669 20178 18 0.29 288 8710 11877 15044 18212 19 0.26 261 7892 10762 13632 16502 20 0.24 237 7179 9789 12400 15010 4x Members DRL Fc E d KCE c 1350 1600000 3.5 0.3 0.8 Stability Reduction Column Capacity Obs) le (ft) Cp Fc' (psi) 4X4 4X6 4X8 4X10 4X12 5 0.75 1016 12444 19554 26665 33776 40886 6 0.63 848 10387 16322 22257 28193 34128 7 0.51 689 8445 13271 18097 22923 27749 8 0.41 559 6848 10761 14674 18587 22500 9 0.34 457 5602 8802 12003 15204 18405, 10 0.28 379• 4640 7292 9943 12595 15246 11 0.24 318 3894 6119 8344 10570 12795 12 0.20 270 3308 5199 7089 8979 10870 13 0.17 232 2842 4466 6090 7714 9338 14 0.15 201 2466 3875 5284 6693 8102 15 0.13 176 2158 3392 4625 5858 7092 Multi 2x Members DF -L Fc E d KCE c 1350 1600000 3 0.3 0.8 Stability Reduction Column Capacity Obs) le (ft) Cp Fc' (psi) (2) 2x4 (3) 2x4 (2) 2x6 (3) 2x6 (4) 2x6 5 0.65 876 10132 13798 14455. 21683 28911 6 0.51 689 8445 10858 11376 17063 22751 7 0.40 540 6617 8508 8913 13369 17826 8 0.32 429 5253 6754 7076 10613 14151 9 0.26 346 4244 5457 5716 8575 11433 10 0.21 285 3488 4485 4699 7048 9398 11 0.18 238 2913 3745 3923 5885 7846 12 0.15 201 2466 3170 3321 4982 6642 13 0.13 172 2113 2716 2846 4268 5691 14 0.11 149 1829 2352 2464 3696 4928 15 0.10 131 1599 2056 2154 3231 4308 I(Note: all loads are inkips) Pg. 28 Pg. 29 ound 3EionAeisgn� r " CBC 2010 Project: Massa Addition Date: 10/3/2016 Comments: Units: kips & feet (UNO) Soil Bearing: 1200 psf Concrete Strength: 2500 psi Temp and Shrickage Ratio 0.0018 Concrete stem wall (Non -retaining): (fc' = 2500 psi) 6" wide with (1) #4 continuous at top of wall and #4 at 18" O.C. full height. Provide #4 at 18" O.C. vertical developed by hook into footing, U.N.O. Continuous footings: (fc' = 2500 psi) Width Thickness Ca 1 Reinforcing 12 12 1200 (2) #4 cont. 15 12 1500 (2) #4 cont 18 12 1800 (3) #4 cont. 24 12 2400 (3) #4 cont. 30 12 3000 (4) #4 cont. Spread Footings:(fc'=2500 psi) Reinforcing Reinf. Reg' d Cap. Connnector Label Size Thickness Bar Size Ea Way Kips Simpson F1 1'-0" Sq. 12 4 2 1.2 PB 171.5 1'-6" Sq. 12 4 2 2.7 PB F2 2'-0" Sq. 12 4 3 4.8 PB F2.5 2'-6" Sq. 12 4 4 7.5 PB F3 T-0" Sq. 12 4 4 10.8 CB F3.5 3'-6" Sq. 12 4 5 14.7 CB F4 4'-0" Sq. 12 4 6 19.2 CB F4.5 4'-6" Sq. 12 4 6 24.3 CB F5 5'-0" Sq. 18 4 10 30 CB F5.5 5'-6" Sq. 18 4 11 36:3 CB F6 6'-0" Sq. 18 4 12 43.2 CB F6.5 6-6" Sq. 18 4 13 50.7 CB Note: Bottom of each footing shall be at least 12" below finished grade or as per local requirements. (Note: all loads are in kips) Footing ID DL FLL RLL SL Wind EQ Total Footing Size FTG1 2:784 2.722 5.51 F2.5 Gov'n E n EQ 16-16 DL+FLL Beam B5 FTG2 4.738 2.576 2.392 8.46 F3 Gov'n E n . EQ 16-13 DL+075RLL+0.75RLL FTG3 0.00 F1 Gov'n E n EQ 16-16 DL FTG4 0.00 F1 Gov'n E n EQ 16-16 DL FTG5 0.00 F1 Gov'n E n EQ 16-16 DL FTG6 0.00 F1 Gov'n E n EQ 16-16 DL FTG7 0 F1 Gov'n E n EQ 16-16 DL - FTG8 0 F1 Gov'n E n EQ 16-16 DL FTG8 0 F1 Gov'n E n EQ 16-16 DL FTG9 0 F1 Gov'n E n EQ 16-16 DL FTG10 0 F1 Gov'n Eqn EQ 16-16 DL a BUILDING ENERGY ANALYSIS REPORT PROJECT: The Massa Residence 4285 Keefer Road Chico, CA - Project Designer: Donna Rose Residential Design 630 Salem Street #110 Chico, CA 95928 530 717-3710 Report Prepared by: Atousa Yazdanfar Energy Compliance Services 5702 Hersholt Avenue Lakewood , CA 90712 56246.1-3749 pp PERMIT # alf. - Z ,6-c9 BUTTE COUNTY DEVELOPMENT SERVICES REVIEWED FOR CODE COMPLIANCE t DATE Job Number: BUTTE 14968 COUNTY OCT 112016 .Date: DEVELOPMENT -9/28/2016 SERVICES The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is " authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC—www.energysoft.com. EnergyPro 6. by EnergySoft User Number: 5634 ID: 14968 � 1� Copy TABLE OF CONTENTS Cover Page 1 '. Table of Contents 2 Form CF -1 R -PRF -01-E Certificate of Compliance 3 Form MF -1 R Mandatory Measures Summary 11 EnergyPro 6. by EnergySoft Job Number: ID: 14968 User Number: 5634 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CFI R -PRF -01 Project Name: The Massa Residence Calculation Date/Time: 14:31, Wed, Sep 28, 2016 Page 1 of'8 Calculation Description: Title 24 Analysis Input File Name: 14968.ribdx ' GENERAL INFORMATION 01 Project Name The Massa Residence s 02 Calculation Description Title 24 Analysis 03 Project Location 4285 Keefer Road 04 City Chico 05 Standards Version Compliance 2015 06 Zip Code 07 Compliance Manager Version BEMCmpMgr 2013-4b (433) 08 Climate Zone CZ11 09 Software Version EnergyPro 6.8 10 Building Type Single Family 11 Front Orientation (deg/Cardinal) 0 12 Project Scope Newly Constructed (Addition Alone) 13 Number of Dwelling Units 1 14 Total Cond. Floor Area (ft2) 260 15 Number of Zones 1 16 Slab Area (ft2) 0 17 Number of Stories 1 18 Addition Cond. Floor Area 260 19 Natural Gas Available Yes r2O Addition Slab Area (ftZ) 0 21 Glazing Percentage (%) 33.8% ADDITION ALONE PROJECT ANALYSIS PARAMETERS 01 02 03 04 05 06 Existing Area (excl. new addition) ft2 Addition Area (excl. existing) ft2 TOTAL AREA Existing Bedrooms Addition Bedrooms Total Bedrooms 390 260 650 0 4 4 Registration Number: Registration Date/Time: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 HERS Provider: Report Generated at: 2016-09-28 14:31:48 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD .Project,Name: The Massa Residence Calculation Daterrime: 14:31, Wed, Sep 28, 2016 Calculation Description: Title 24 Analysis Input File Name: 14968.ribdx COMPLIANCE RESULTS 01 Building Complies with Computer Performance 02 This building DOES NOT require HERS Verification CFI, R -PRF -01 Page 2 of 8 REQUIRED SPECIAL FEATURES The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis. NO SPECIAL FEATURES REQUIRED HERS FEATURE SUMMARY The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is provided in the building components tables below. Building -level Verifications: -- None -- Cooling System Verifications: • --None — HVAC Distribution System Verifications: • —None -- Domestic Hot Water System Verifications: • -- None — Registration Number: Registration Date/Time: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 HERS Provider: Report Generated at: 2016-09-28 14:31:48 - ENERGY USE SUMMARY 04 05 06 07 08 Energy Use (kTDV/ft2-yr) Standard Design Proposed Design Compliance Margin Percent Improvement Space Heating 13.60 11.03 2.57 18.9% Space Cooling 103.44 124.45 -21.01 -20.3% IAQ Ventilation 0.00 0.00 0.00 0.0% Water Heating 70.73 -49.97 20.76 29.4% Photovoltaic Offset -- 0.00 0.00 -- Compliance Energy Total 187.77 185.45 2.32 1.2% REQUIRED SPECIAL FEATURES The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis. NO SPECIAL FEATURES REQUIRED HERS FEATURE SUMMARY The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is provided in the building components tables below. Building -level Verifications: -- None -- Cooling System Verifications: • --None — HVAC Distribution System Verifications: • —None -- Domestic Hot Water System Verifications: • -- None — Registration Number: Registration Date/Time: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 HERS Provider: Report Generated at: 2016-09-28 14:31:48 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project dame: The Massa Residence Calculation Date[Time: 14:31, Wed, Sep 28, 2016 Calculation Description: Title 24 Analysis Input File Name: 14968.ribdx CF1 R -PRF -01 Page 3 of'8 ENERGY DESIGN RATING This is the sum of the annual TDV energy consumption for energy use components included in the performance compliance'approach for the Standard Design Building (Energy Budget) and the annual TDV energy consumption for lighting and components not regulated by Title 24, Part 6 (such as domestic appliances and consumer electronics) and accounting for the annual TDV energy offset by an on-site renewable energy system. Reference Energy Use " Energy Design Rating Margin Percent Improvement Total Energy (kTDV/f2-yr)' 292.85 2.32 0.8% includes calculated Appliances and Miscellaneous Energy Use (AMEU) BUILDING - FEATURES INFORMATION 01 02 03 04 05 06 07 Project Name Conditioned Floor Area (ft2) Number of Dwelling Units Number of Bedrooms Number of Zones Number of Ventilation Cooling Systems Number of Water Heating Systems The Massa Residence 260 1 0 1 0 1 ZONE INFORMATION 01 02 03 04 05 06 07 Zone Name Zone Type HVAC System Name Zone Floor Area (ft2) Avg. Ceiling Height Water Heating System 1 Water Heating System 2 1st Floor Addition Conditioned HVAC1 260 8 DHW Sys 1 Gross Area (ft2) OPAQUE SURFACES 01 02 03 04 05 06 07 08 Name Zone Construction Azimuth Orientation Gross Area (ft2) Window & Door Area (ft2) Tilt (deg) North Wall 1 st Floor Addition R-13 Wall 0 Front 45 90 East Wall 1st Floor Addition R-13 Wall 90 Left 104 56 90 East Wall 2 1st Floor Addition R-13 Wall 90 Left 104 90 South Wall 1st Floor Addition R-13 Wall 180 Back 96 16 90 West Wall 1 st Floor Addition R-13 Wall 270 Right 96 16 90 Roof 1 st Floor Addition R-38 Roof Attic 260 Raised Floor 1 st Floor Addition R-19 Floor Crawlspace 260 Registration Number: Registration Date/Time: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CFSR-03112016-433 HERS Provider: Report Generated at: 2016-09-28 14:31:48 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: The Massa Residence Calculation Date/Time: 14:31, Wed, Sep 28, 2016 Calculation Description: Title 24 Analysis Input File Name: 14968.ribdx CFI R -PRF -01 Page.4 of 8 ATTIC 01 02 03 04 05 06 07 08 Name Construction Type Roof Rise Roof Reflectance Roof Emittance Radiant Barrier Cool Roof Attic 1st Floor Addition Attic Rooflst Floor Addition Ventilated 0 0.1 0.85 Yes No WINDOWS 01 02 03 04 05 06 07 08 09 10 Name Type Surface (Orientation -Azimuth) Width (ft) Height (ft) Multipli er Area (ft2) U -factor SHGC Exterior Shading' East Windows Window East Wall (Left -90) ---- -- 1 56.0 0.31 0.29 Insect Screen (default) South Windows Window South Wall (Back -180) --- -- 1 16.0 0.31 0.29 Insect Screen (default) West Windows Window West Wall (Right -270) -- -- 1 16.0 0.31 0.29 Insect Screen (default) OPAQUE SURFACE CONSTRUCTIONS 01 02 - 03 -04 .05 06 07 Total Cavity Winter Design - Construction Name Surface Type Construction Type Framing R -value U -value Assembly Layers ,- • Cavity/ Frame: no insul.'/2x4 Top Chrd 2x4 Top Chord of Roof Truss @ 24 Roof Deck., Wood Siding/sheathing/decking Attic Roof st Floor Addition Attic Roofs Wood Framed Ceiling in. O.C. none 0.644 Roofing: Light Roof (Asphalt Shingle) • Inside Finish: Gypsum Board • Sheathing/ Insulation: R5 Sheathing • Cavity/Frame: R -13/2x4 • Sheathing/ Insulation: R2 Sheathing R-13 Wall Exterior Walls Wood Framed Wall 2x4 @ 16 in. O.C. R 13 0.056 Exterior Finish: 3 Coat Stucco • Floor Surface: Carpeted Floors Over Floor Deck: Wood Siding/sheathing/decking R-19 Floor Crawlspace Crawlspace Wood Framed Floor 2x6 @ 16 in. O.C. • R 19 0.049 • Cavity/Frame: R -19/2x6 • Inside Finish: Gypsum Board Ceilings (below • Cavity/Frame: R-9.1 /2x4 R-38 Roof Attic attic) Wood Framed Ceiling 2x4 @ 24 in. O.C. R 38 0.025 • Over Ceiling Joists: R-28.9 insul. BUILDING ENVELOPE - HERS VERIFICATION 01 02 03 04 Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage CFM50 Not Required Not Required Not Required — Registration Number: Registration Date/Time: HERS Provider: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 Report Generated at: 2016-09-2814:31:48 U CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD ,Project Name: The Massa Residence Calculation Date/Time: 14:31, Wed, Sep 28, 2016 Calculation Description: Title 24 Analysis - - Input File Name: 14968.ribdx CF1 R -PRF -01 Page 5 of 8 WATER HEATING SYSTEMS 01 02 03 04 05 - 06 Name System Type Distribution Type Water Heater. Number of Heaters Solar Fraction (%) DHW Sys 1 - 1/1 DHW Standard DHW Heater 1 1 .0% WATER HEATERS 01 02 03 04 05 06 07 08 Name Heater Element Type Tank .Type Tank Volume (gal) Energy Factor or Efficiency Input Rating Tank Exterior Insulation R -value Standby Loss (Fraction) DHW Heater 1 Natural Gas Small Storage 50 0.75 40000-Btu/hr 0 0 WATER HEATING - HERS VERIFICATION - 01 02 03 04 - 05 06 07 Name Pipe Insulation - Parallel Piping Compact Distribution Point -of Use Recirculation Control. Central DHW Distribution DHW Sys 1 - 1/1 Cooling Component 1 — -- — — — SPACE CONDITIONING SYSTEMS 01 02 03 04 05 06 SC Sys Name System Type Heating Unit Name Cooling Unit Name Fan Name Distribution Name HVAC1 Other Heating and Cooling System Heating Component 1 Cooling Component 1 HVAC Fan 1 Air Distribution System 1 HVAC - HEATING UNIT TYPES 01 02 03 Name Type Efficiency Heating Component 1 CntrlFurnace - Fuel -fired central furnace 80 AFUE Registration Number: Registration Date/Time: HERS Provider: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 Report Generated at: 2016-09-28 14:31:48 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: The Massa Residence Calculation Date/Time: 14:31, Wed, Sep 28, 2016 Calculation Description: Title 24 Analysis Input File Name: 14968.ribdx CF1 R -PRF -01 - • Page 6 of 8 HVAC - COOLING UNIT TYPES 01 02 03 04 05 06 07 Name Verified Airflow Efficiency Verified EER Multi -speed Verified Refrigerant Charge Name System Type EER SEER Zonally Controlled Compressor HERS Verification Cooling Component 1 SplitAirCond 11.1 13 Not Zonal Single Speed Cooling Component - A -hers -cool HVAC COOLING - HERS VERIFICATION 01 02 03 04 05 06 Name Verified Airflow Airflow Target Verified EER Verified SEER Verified Refrigerant Charge Cooling Component 1 -hers -cool Not Required Air Distribution System 1 Not Required Not Required Not Required HVAC - DISTRIBUTION SYSTEMS 01 02 03 04 05 06 07 Name Type, Duct Leakage Insulation R -value Duct Location Bypass Duct HERS Verification Air Distribution System 1 DuctsAttic Existing (not specified) 2.1 Attic None Air Distribution System 1 -hers -dist HVAC DISTRIBUTION - HERS VERIFICATION 01 02 03 04 05 06 07 08 Name Duct Leakage Verification Duct Leakage Target (%) Verified Duct Location Verified Duct Design Buried Ducts Deeply Buried Ducts Low -leakage Air Handler Air Distribution System 1 -hers -dist Not Required Not Required Not Required Not Required Not Required — HVAC -FAN SYSTEMS 01 02 03 04 Name Type Fan Power (Watts/CFM) HERS Verification HVAC Fan 1 Single Speed PSC Furnace Fan 0.58 HVAC Fan 1 -hers -fan HVAC FAN SYSTEMS - HERS VERIFICATION 01 02 03 Name Verified Fan Watt Draw Required Fan Efficiency (Watts/CFM) HVAC Fan 1 -hers -fan Not Required Registration Number: Registration Date/Time: HERS Provider: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 Report Generated at: 2016-09-28 14:31:48 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD ,Project Name: The Massa Residence Calculation Daterrime: 14:31, Wed, Sep 28, 2016 Calculation Description: Title 24 Analysis Input File Name: 14968.ribdx Registration Number: Registration Date/Time: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 CF1 R -PRF -01 Page 7 of 8 HERS Provider: Report Generated at: 2016-09-2814:31:48 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: The Massa Residence Calculation Date/Time: 14:31, Wed, Sep 28, 2016 Calculation Description: Title 24 Analysis Input File Name: 14968.ribdx CF1 R -PRF -01 Page 8 of 8 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. . Documentation Author Name: - _ _ _ Atousa Yazdanfar Documentation Author Signature: f}tOGffGi i�G�10iGi�1 fG�Y Company: Signature Date: Energy Compliance Services 9/28/2016 Address: CEA/HERS Certification Identification (If applicable): 5702 Hersholt Avenue City/State/Zip. ewood , CA 90712 Phone: 562 461-3749 RESPONSIBLE PERSON'S DECLARATION STATEMENT " I certify the following under penalty of perjury, under the laws of the State of California: 1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design- identified on this Certificate of Compliance. 2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. '3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. Responsible Designer Name: Responsible Designer Signature: Donna Rose L -- Company: Date Signed: Donna Rose Residential Design jJ 5' 69 = ` Address: License: 630 Salem Street #110 City/State/Zip: Phone: Chico, CA 95928 530 717-3710 Registration Number: Registration Date/Time: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-03112016-433 HERS Provider: Report Generated at: 2016-09-28 14:31:48 1 2013 Low -Rise Residential Mandatory Measures Summary NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the compliance aDDroach used. Exceptions may annly. Review the respective code section for mnre infnrmntinn Building Envelope Measures: § 110.6(a)1: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage. § 110.6(a)5: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain Coefficient SHGC , and infiltration that meets the requirements of § 10-111 (a). § 110.7: Exterior doors and windows are weatherstripped; all joints and penetrations are caulked and sealed. §110.8(a): Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the CF2R. § 110.8(i): The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of § 110.8(i) when the installation of a cool roof is specified on the CF 1 R. § 110.80): A radiant barrier shall have an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CF1R. Minimum R-30 insulation in wood -frame ceiling; or the weighted average U -factor shall not exceed 0.031. Minimum R-19 in a § 150.0(a): rafter roof alteration. Attic access doors shall have permanently attached insulation using adhesive or mechanical fasteners. The attic access shall be gasketed to prevent air leakage. §150.0(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -value. § 150.0(c): Minimum R-13 insulation in 2x4 inch wood framing wall or have a U -factor of 0.102 or less (R-19 in 2x6 or 0.074 maximum U - factor). § 150.0(d): Minimum R-19 insulation in raised wood -frame floor or 0.037 maximum U -factor. In Climate Zones 14 and 16 a Class II vapor retarder shall be installed on the conditioned space side of all insulation in all exterior § 150.0(g)l: walls, vented attics and unvented attics with air -permeable insulation. § 150.0(g)2: In Climate Zones 1-16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a Class I or Class II vapor retarder. In a building having a controlled ventilation crawl space, a Class I or Class II vapor retarder shall be placed over the earth floor of §150.0(g)3: the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section 150.0(d). § 150.0(1): Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.3%; have water vapor permeance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration; and when installed as part of a heated slab floor meets the requirements of § 110.8 150.0 § (q)' Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U- factor of 0.58; or the weighted average U -factor of all fenestration shall not exceed 0.58. Fireplaces, Decorative Gas Appliances and Gas Log Measures: § 150.0(e)IA: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox. §150.0(e)1B.. Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is equipped with a readily accessible, operable, and tight -fitting damper or a combustion -air control device. §150.0(e)1C: Masonry or factory -built fireplaces have a flue damper with a readily accessible control. § 150.0(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of the building, are prohibited. Space Conditioning, Water Heating and Plumbing System Measures: §1 10.0-§110.3: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified to the Energy Commission. § 110.3(c)5: Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of § 110.3(c)5. Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appli- §110.5: ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and spa heaters. §150.0(h)1: Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified in §150.0(h)2. § 150.0(h)3A: Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least five feet from the outlet of any dryer vent. § 150.0(i): Heating systems are equipped with thermostats that meet the setback requirements of § 110.2(c). § 150.00)IA: Storage gas water heaters with an energy factor equal to or less than the federal minimum standards shall be externally wrapped with insulation having an installed thermal resistance of R-12 or greater. § 150.00)1B: Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water -heating systems, have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the tank. For domestic hot water system piping, whether buried or unburied: the first 5 feet of hot and cold water pipes from the storage tank, all piping with a nominal diameter of 3/4 inch or larger, all piping associated with a domestic hot water recirculation system § 150.00)2A: regardless of the pipe diameter, piping from the heating source to storage tank or between tanks, piping buried below grade, and all hot water pipes from the heating source to kitchen fixtures must be insulated according to the requirements of TABLE 120.3- A. §150.00)2B: All domestic hot water pipes that are buried below grade must be installed in a water proof and non -crushable casing or sleeve that allows for installation, removal, and replacement of the enclosed pipe and insulation. 2013 Low -Rise Residential Mandatory Measures Summary § 150.00)2C: Pipe for cooling system lines shall be insulated as specified in § 150.00)2A. Piping insulation for steam and hydronic heating systems or hot waters stems with pressure > 15 psig shall meet the requirements in TABLE 120.3-A. § 150.00)3: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Insulation exposed to weather shall either be rated for outdoor use or installed with a cover suitable for outdoor service. For § 150.00)3A: example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation protected as specified or painted with coating that is water retardant and provides shielding from solar radiation that degrades the material. Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I § 150.00)3B: or Class II vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class II vapor retarder. Systems using gas or propane water heaters to serve individual dwelling units shall include: a 120V electrical receptacle within 3 feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the §150.0(n)l: space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the installed water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000 Btu/hr. § 150.0(n)2: Recirculating loops serving multiple dwelling units shall meet the requirements of § 110.3(c)5. § 150.0(n)3: Solar water -heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC) or by a testing agency approved by the Executive Director. Ducts and Fans Measures: All air -distribution system ducts and plenums installed are sealed and insulated to meet the requirements of CMC §601.0, §602.0, §603.0, §604.0, §605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition. Supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-6.0 (or higher if required by CMC §605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing (RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts are mechanically fastened. Openings shall be sealed § 150.0(m)1: with mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than ''A inch, the combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. Factory -Fabricated Duct Systems shall comply with specified requirements for duct construction, connections, and closures; joints § 150.0(m)2: and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and draw bands. §150.0(m)3-6: Field -Fabricated Duct Systems shall comply with requirements for: pressure -sensitive tapes, mastics, sealants, and other requirements specified for duct construction; duct insulation R -value ratings; duct insulation thickness; and duct labeling. § 150.0(m)7- All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic dampers. § 150.0(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers except combustion inlet and outlet air openings and elevator shaft vents. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not § 150.0(m)9: limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation. §150.0(m)10: Flexible ducts cannot have porous inner cores. When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be §I50.0(m)11: sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3. Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal §150.0(m)12: conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of §150.0(m)12. Space conditioning systems that utilize forced air ducts to supply cooling to an occupiable space shall have a hole for the placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum. The §150.0(m)13: space conditioning system must also demonstrate airflow 2:350 CFM per ton of nominal cooling capacity through the return grilles, and an air -handling unit fan efficacy:5 0.58 W/CFM as confirmed by field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3. Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode, §150.0(m)15: an airflow from the dwelling, through the air handler fan and delivered to the dwelling, of> 350 CFM per ton of nominal cooling capacity, and operating at an air -handling unit far, efficacy of < 0.58 W/CFM as confirmed by field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3. All dwelling units shall meet the requirements of ASHRAE Standard 62.2. Neither window operation nor continuous operation of §150.0(o): . central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of providing the Whole Building Ventilation. §150.0(o)IA: Whole Building Ventilation airflow shall be confirmed through field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3. Pool and Spa Heating Systems and Equipment Measures: Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency § 110.4(a): Regulations; an on-off switch mounted outside of the heater that allows shutting off the heater without adjusting the thermostat setting; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating. 2013 Low -Rise Residential Mandatory Measures Summary § 110.4(b)1: Any pool or spa heating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction and return lines, or built-up connections for future solar heating. § 110.4(b)2: Outdoor pools or spas that have a heat pump or gas heater shall have a cover. § 110.4(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or pro- ammed to run only during off-peak electric demand periods. § 110.5: Natural gas pool and spa heaters shall not have a continuous burning pilot light. § 150.0(p): Residential pool systems or equipment shall meet specified pump sizing, flow rate, piping, filters, and valve requirements. Lighting Measures: § 110.9: All lighting control devices and systems, ballasts, and luminaires shall meet the applicable requirements of § 110.9. §150.0(k)IA: Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with §I50.0(k) in accordance with TABLE 150.0-A or TABLE 150.0-B, as applicable. §150.0(k)1B: When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply with the applicable provisions of § 150.0(k). The wattage and classification of permanently installed luminaires in residential kitchens shall be determined in accordance with § 150.0(k)1C: § 130.0(c). In residential kitchens, the wattage of electrical boxes finished with a blank cover or where no electrical equipment has been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as 180 watts of low efficacy lighting er electrical box. §150.0(k)1D: Ballasts for fluorescent lamps rated 13 watts or greater shall be electronic and shall have an output frequency no less than 20 kHz. Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume no §150.0(k)IE: more than 5 watts of power per luminaire or exhaust fan as determined in accordance with § I30.0(c). Night lights do not need to be controlled by vacancy sensors. § 150.0(k)1F: Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable requirements of § 150.0(k). § 150.0(k)2A: High efficacy luminaires must be switched separately from low efficacy luminaires. § 150.0(k)2B: Exhaust fans shall be switched separately from lighting systems. § 150.0(k)2C: Luminaires shall be switched with readily accessible controls that permit the luminaires to be manually switched ON and OFF. § 150.0(k)2D: Controls and equipment are installed in accordance with manufacturer's instructions. § 150.0(k)2E: No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with § 150.0(k). § 150.0(k)2F: Lighting controls comply with applicable requirements of § 110.9. An Energy Management Control System (EMCS) may be used to comply with dimmer requirements if. it functions as a dimmer § 150.0(k)2G: according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements of § 130.5; and all other requirements in §150.0(k)2. An Energy Management Control System (EMCS) may be used to comply with vacancy sensor requirements of § 150.0(k) if. it §150.0(k)2H: functions as a vacancy sensor according to §110.9; meets Installation Certificate requirements of §130.4; the EMCS requirements of § 130.5; and all other requirements in § 150.0(k)2. § I50.0(k)2I: A multiscene programmable controller may be used to comply with dimmer requirements of this section if it provides the functionality of a dimmer according to § 110.9, and complies with all other applicable requirements in § 150.0(k)2. § 150.0(k)3A: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy. Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only § 150.0(k)3B: the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are considered kitchen lighting if they are not separately switched from kitchen lighting. § 150.0(k)4: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated cabinet. §150.0(k)5: A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom shall be high efficacy or controlled by vacancy sensors. § 150.0(k)6: Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and controlled by vacancy sensors. §150.0(k)7: Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high efficacy, or shall be controlled by either dimmers or vacancy sensors. Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other nationally recognized testing/rating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing § 150.0(k)8: and ceiling, and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and allow ballast maintenance and replacement without requiring cutting holes in the ceiling. For recessed compact fluorescent luminaries with ballasts to qualify as high efficacy for compliance with § 150.0(k), the ballasts shall be certified to the Energy Commission to comply with the applicable requirements in § 110.9. For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements: i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of Items ii or iii below; and §150.0(k)9A: ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically reactivates the motion sensor within 6 hours; and iii. Controlled by one of the following methods: 2013 Low -Rise Residential Mandatory Measures Summary a. Photocontrol not having an override or bypass switch that disables the photocontrol; or b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is programmed to automatically turn the outdoor lighting OFF during daylight hours; or c. Energy management control system which meets all of the following requirements: At a minimum provides the functionality of an astronomical time clock in accordance with §110.9; meets the Installation Certification requirements in §130.4; meets the requirements for an EMCS in § 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and, is programmed to automatically tum the outdoor lighting OFF during daylight hours. For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the § 150.0(k)9B: following requirements: i. Shall comply with § 150.0(k)9A; or ii. Shall comply with the applicable requirements in §110.9, §130.0, §130.2, §130.4, § 140.7 and §141.0. § 150.0(k)9C: For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by § 150.0(k)9B or 150.0(k)9D shall comply with the applicable requirements in 110.9, 130.0, 130.2, 130.4, 140.7 and 141.0. § 150.0(k)9D: Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall comply with the applicable requirements in § 110.9, § 130.0, § 130.2, § 130.4, § 140.7 and § 141.0. §150.0(k)10: Internally illuminated address signs shall comply with §140.8; or shall consume no more than 5 watts of power as determined according to § 13 0.0 c . §150.0(k)11. Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for nonresidential garages in 110.9,130.0, 130.1, 130.4, 140.6, and 141.0. In a low-rise multifamily residential building where the total interior common area in a single building equals 20 percent or less of §150.0(k)12A: the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or controlled by an occupant sensor. In a low-rise multifamily residential building where the total interior common area in a single building equals more than 20 percent of the floor area, permanently installed lighting in that building shall: § 150.0(k)12B: i. Comply with the applicable requirements in § 110.9, § 130.0, § 130. 1, § 140.6 and § 141.0; and ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of ingress and egress. Solar Ready Buildings: Single family residences located in subdivisions with ten or more single family residences and where the application for a §1 10.10(a)l: tentative subdivision map for the residences has been deemed complete, by the enforcement agency, on or after January 1, 2014, shall comply with the requirements of §110.10 b through 110.10(e). §1 10.10(a)2: Low-rise multi -family buildings shall comply with the requirements of §1 10.10(b) through §1 10.10(d). The solar zone shall have a minimum total area as described below. The solar zone shall comply with access, pathway, smoke ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a local jurisdiction. The solar zone total area shall be comprised of areas that have no dimension less than 5 feet and are no less than 80 square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for § 110.10(b)l : buildings with roof areas greater than 10,000 square feet. For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less than 250 square feet. For low-rise multi -family buildings the solar zone shall be located on the roof or overhang of the building or on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the building project and have a total area no less than 15 percent of the total roof area of the building excluding any skylight area. § 110.10(b)2: All sections of the solar zone located on steep -sloped roofs shall be oriented between 110 degrees and 270 degrees of true north. § 110.10(b)3A: No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equipment, shall be located in the solar zone. Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least twice § 110.10(b)3B: the distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the horizontal projection of the nearest point of the solar zone, measured in the vertical plane. § 110.10(b)4: For areas of the roof designated as solar zone, the structural design loads for roof dead load and roof live load shall be clearly indicated on the construction documents. The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit § 110.10(c): from the solar zone to the point of interconnection with the electrical service (for single family residences the point of interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water -heating system. § 110.10(d): A copy of the construction documents or a comparable document indicating the information from § 110.10(b) through § 110.10(c) shall be provided to the occupant. § 110.10(e)1: The main electrical service panel shall have a minimum busbar rating of 200 amps. The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a § 110.10(e)2: future solar electric installation. The reserved space shall be: positioned at the opposite (load) end from the input feeder location or main circuit location, and permanently marked as "For Future Solar Electric".