HomeMy WebLinkAboutB16-2476 000-000-000BUILDING ENERGY ANALYSIS REPORT PROJECT: Conditioned Storage at Patrick Ranch Museum 10381 Midway Durham, CA 95938 Project Designer: North Valley Building Systems #30 Seville Court Chico, CA 95928 530-345-7296 Report Prepared by: Donna Wallace Donna Wallace 399 E. 9th Avenue Chico, CA 95926 530-893-4982 PERMIT# Nb_?''l _Q2 BUTTE COUNTY DEVELOPMENT SERVICES REVIEWED FOR CODE COMPLIANCE DATE,_„ BY, Job Number: NVBS72 Date: ty 11/4/2016 V? t9l-It BUTTE COUNTY NOV 0 7 2016 DEVELOPMENT SERVICES The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program h as approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC—www.energysoft.com. EnergyPro 6. by EnergySoft User Number: 4997 ID: NVBS72 Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 1 of 19 Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx A. PROJECT GENERAL INFORMATION § 140.1 1. Project Location (city) Durham 8. Standards Version Compliance2015 2. CA Zip Code 95938 9. Compliance Software (version) EnergyPro 6.8 3. Climate Zone 11 10. Building Orientation (deg) (E) 98 deg 4. Total Conditioned Floor Area in Scope 1,600 ft' 11. Permitted Scope of Work ExistingAdditionAndAlteration S. Total Unconditioned Floor Area . 3,200 ft2 12. Building Types) Nonresidential 6. Total # of Stories (Habitable Above Grade) 1 13 Gas Type Propane 7. Total # of dwelling units 0 Indoor Lighting 25.7 13.4 B. COMPLIANCE RESULTS FOR PERFORMANCE COMPONENTS (Annual TDV Energy Use, kBtu/ft z -yr) § 140.1 BUILDING COMPLIES 1. Energy Component 2. Standard Design (TDV) 3. Proposed Design (TDV) 4. Compliance Margin (TDV) S. Percent Better than Standard Space Heating 36.2 16.3 19.9 55.0% Space Cooling 29.0 37.6 -8.6 -29.7% Indoor Fans 32.4 34.5 -2.1 -6.5% Heat Rejection Pumps & Misc. -- Domestic Hot Water 23.2 23.2 -- 0.0% Indoor Lighting 25.7 13.4 12.3 47.9% COMPLIANCE TOTAL 146.5 125.0 21.5 14.7% Receptacle 12.9 12.9 0.0 0.0% Process Other Ltg -- - TOTAL 159.4 137.9 21.5 13.5% CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-04 13:46:15 1 ail Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 2 of 19 Project Address: 10381 Midway Durham 95938 Calculation DatefTime: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx C. PRIORITY PLAN CHECK/ INSPECTION ITEMS (in order of highest to lowest TDV energy savings) 1st Space Heating: Check envelope and mechanical Compliance Margin By Energy Component (from Table 8 column 4) Space Heating Indoor Lighting Heat Rejection Pumps & Misc. Domestic Hot Water Indoor Fans Space Cooling _ _� PenaltyEnergy Credit -..4 2nd Indoor Lighting: Check lighting 3rd Heat Rejection: Check envelope and mechanical 4th Pumps & Misc.: Check mechanical 5th Domestic Hot Water: Check mechanical 6th Indoor Fans: Check envelope and mechanical 7th Space Cooling: Check envelope and mechanical D. EXCEPTIONAL CONDITIONS The building does not include service water heating. Verify that service water heating is not required and is not included in the design. E. HERS VERIFICATION This Section Does Not Apply F. ADDITIONAL REMARKS None Provided CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-04 13:46:15 Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 3 of 19 Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY Identify which building components use the performance or prescriptive path for compliance. "NA"= not in project For components that utilize the performance path, indicate the sheet number that includes mandatory notes on plans. Location of Mandatory Notes on Plans CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-04 13:46:15 Building Component Compliance Path Compliance Forms (required rorsuamirrat/ Z Performance NRCC-PRF-ENV-DETAILS (section of the NRCC-PRF-OS-E) Envelope ❑ Prescriptive NRCC-ENV-01 / 02 / 03 / 04 / 05 / 06-E ❑ NA ® Performance NRCC-PRF-MCH-DETAILS (section of the NRCC-PRF-01-E) Mechanical ❑ Prescriptive NRCC-MCH-01 / 02 / 03 / 04 / 05 / 06 / 07-E ❑ NA ❑ Performance NRCC-PRF-PLB-DETAILS (section of the NRCC-PRF-01-E) Domestic Hot Water ❑ Prescriptive NRCC-PLB-01-E ®TNA ® Performance NRCC-PRF-LTI-DETAILS (section of the NRCC-PRF-01-E) Lighting (Indoor Conditioned) ❑ Prescriptive NRCC-LTI-01 / 02 / 03 / 04 / 05-E ❑ NA ❑ Performance S2 (section of the NRCC-PRF-01-E) Covered Process: Commercial Kitchens Covered Process: Computer Rooms ❑ Prescriptive NRCC-PRC-01/ 03-E ® NA ❑ Performance S3 (section of the NRCC-PRF-01-E) ❑ Prescriptive NRCC-PRC-01/ 04-E ® NA ❑ Performance S4 (section of the NRCC-PRF-01-E) Covered Process: Laboratory Exhaust ❑ Prescriptive NRCC-PRC-01/ 09-E INA Location of Mandatory Notes on Plans CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-04 13:46:15 Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 4 of 19 Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY The following building components are only eligible for prescriptive compliance. Indicate which are The following building components may have mandatory requirements per Part 6. Indicate relevant to the project. which are relevant to the project. Yes NA Prescriptive Requirement Compliance Forms Yes NA Mandatory Requirement Compliance Forms Commissioning: §120.8 ® ❑ Lighting (Indoor NRCC-LTI-01 / 02 / 03 / 04 / 05-E ❑ ® Simple Systems NRCC-CXR-01 / 02 / 03 / 05-E Unconditioned) §140.6 ❑ ® Complex Systems NRCC-CXR-01 / 02 / 04 / 05-E ❑ ® Lighting (Outdoor) §140.7 NRCC-LTO-01 / 02 / 03-E ❑ ® Electrical: §130.5 NRCC-ELC-01-E ❑ ® Lighting (Sign) §140.8 NRCC-LTS-01-E ❑ ® Solar Ready: §110.10 NRCC-SRA-01 / 02-E Covered Process: §120.6 NRCC-PRC-01-E ❑ ® Parking Garage NRCC-PRC-02-E Solar Thermal Water ❑ ® Commercial Refrigeration NRCC-PRC-05-E ❑ ® Heating: §140.5 NRCC STH 01-E ❑ ® Warehouse Refrig Refrigeration NRCC-PRC-06/07/08-E ❑ ® Compressed Air NRCC-PRC-10-E ❑ ® Process Boilers NRCC-PRC-11-E CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance I Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-04 13:46:15 --- -- NRCC-PRF-01-E Page 5 of 19 Project Name: Conditioned Storage at Patrick Ranch Museum Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Project Address: 10381 Midway Durham 95938 Input File Name: NV8572.cibdx Compliance Scope: Exist! ngAdditionAndAlteration MARY H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTEed forCtheEfeO to eRltoCbe rOe ognized for compllicomplianceNRCV) — Documentation Author to indicate which Certificates mu be subm tt eld Inspector to ver (Retain copies and verify forms LTI Detaleted and ils Sections 'gned to post in for Ac eptance Tests and for lforms by equipment. y) See Tables G. and H. in MCH an Building Component Compliance Forms (required for submittal) ® NRCI-ENV-01-E - For all buildings Envelope ®NRCA-ENV 02-F NFRC label verification for fenestration ® NRCI-MCH-01-E - For all buildings with Mechanical Systems ® NRCA-MCH-02-A- Outdoor Air ® NRCA-MCH-03-A— Constant Volume Single Zone HVAC ❑ NRCA-MCH-04-H- Air Distribution Duct Leakage ❑ NRCA-MCH-05-A- Air Economizer Controls ❑ NRCA-MCH-06-A- Demand Control Ventilation ❑ NRCA-MCH-07-A—Supply Fan Variable Flow Controls ❑ NRCA-MCH-08-A- Valve Leakage Test ❑ NRCA-MCH-09-A— Supply Water Temp Reset Controls Mechanical ❑ NRCA-MCH-10-A- Hydronic System Variable Flow Controls ❑ NRCA-MCH-1I-A—Auto Demand Shed Controls ❑ NRCA-MCH-12-A- Packaged Direct Expansion Units ❑ NRCA-MCH-13-A- Air Handling Units and Zone Terminal Units ❑ NRCA-MCH-14-A- Distributed Energy Storage ❑ NRCA-MCH-15-A—Thermal Energy Storage ❑ NRCA-MCH-16-A- Supply Air Temp Reset Controls ❑ NRCA-MCH-17-A—Condensate Water Temp Reset Controls ❑ NRCA-MCH-18-A- Energy Management Controls Systems ❑ NRCV-MCH-04-H- Duct Leakage Test Confirmed Report Version: NRCC PR F -01-E-08122016-3995 Report Generated at: 2016-11-0413:46:15 CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance l Dov Ivo ■v� Report Version: NRCC PR F -01-E-08122016-3995 Report Generated at: 2016-11-0413:46:15 CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance l Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 6 of 19 Project Address: 10381 Midway Durham 95938 - Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV) - Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify). See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment. Confirmed Building Component Compliance Forms (required for submittal) Pass Fail Plumbing ❑ NRCI-PLB-01-E - For all buildings with Plumbing Systems ❑ ❑ ❑ NRCI-PLB-02-E - required on central systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCI-PLB-03-E - Single dwelling unit systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCI-PLB-21-E - HERS verified central systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCI-PLB-22-E -HERS verified single dwelling unit systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCV-PLB-21-H- HERS verified central systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCV-PLB-22-H - HERS verified single dwelling unit systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCI-STH-01-E - Any solar water heating ❑ ❑ Indoor Lighting ® NRCI-LTI-01-E - For all buildings ❑ ❑ ❑ NRCI-LTI-02-E - Lighting control system, or for an Energy Management Control System (EMCS) ❑ ❑ ❑ NRCI-LTI-03-E - Line -voltage track lighting integral current limiter, or for a supplementary overcurrent protection panel used to energize only line -voltage track lighting ❑ ❑ ❑ NRCI-LTI-04-E - Two interlocked systems serving an auditorium, a convention center, a conference room, or a theater ❑ ❑ ❑ NRCI-LTI-05-E - Lighting Control Credit Power Adjustment Factor (PAF) ❑ ❑ ❑ NRCI-LTI-06-E - Additional wattage installed in a video conferencing studio ❑ ❑ ❑ NRCA-LTI-02-A - Occupancy sensors and automatic time switch controls. ❑ ❑ ❑ NRCA-LTI-03-A - Automatic daylighting controls ❑ ❑ ❑ NRCA-LTI-04-A - Demand responsive lighting controls ❑ ❑ Outdoor Lighting ❑ NRCI-LTO-01-E - Outdoor Lighting ❑ ❑ ❑ NRCI-LTO-02-E- EMCS Lighting Control System ❑ ❑ ❑ NRCA-LTO-02-A -outdoor Lighting Control ❑ ❑ Sign Lighting ❑ N RCI-LTS-01-E -Sign Lighting ❑ ❑ Electrical ID NRCI-ELC-01-E - Electrical Power Distribution ❑ ❑ Photovoltaic ❑ NRCI-SPV-01-E Photovoltaic Systems ❑ ❑ CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-0413:46:15 Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 7 of 19 Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV) — Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance Confirmed (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify). 1. See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment. 1,600 ft2 Building Component Compliance Forms (required forsubmittal) Pass Fail Confirmed ❑ NRCI-PRC-01-E Refrigerated Warehouse ❑ ❑ ❑ NRCA-PRC-01-F- Compressed Air Systems ❑ ❑ d ElNRCA-PRC-02-F- Kitchen Exhaust ❑ El ❑ NRCA-PRC-03-F-Garage Exhaust ❑ ❑ Covered Process ❑ NRCA-PRC-04-F- Refrigerated Warehouse- Evaporator Fan Motor Controls ❑ ❑ North Wall ❑ NRCA-PRC-05-F- Refrigerated Warehouse- Evaporative Condenser Controls ❑ ❑ 00.0% ❑ NRCA-PRC-06-F- Refrigerated Warehouse- Air Cooled Condenser Controls ❑ ❑ ❑ NRCA-PRC-07F- Refrigerated Warehouse- Variable Speed Compressor ❑ ❑ ❑ ❑ NRCA-PRC-08-F- Electrical Resistance Underslab Heating System ❑ ❑ I. ENVELOPE GENERAL INFORMATION (See NRCC-PRF-ENV-DETAILS for more information) 1. Total Conditioned Floor Area 1,600 ft2 S. Number of Floors Above Grade 1 Confirmed 2. Total Unconditioned Floor Area 3,200 ft2 6. Number of Floors Below Grade 0 d 3. Addition Conditioned Floor Area 1,600 ft2 4. Addition Unconditioned Floor Area 0 ft2 7. Opaque Surfaces & Orientation 8. Total Gross Surface Area 9. Total Fenestration Area 10. Window to Wall Ratio North Wall 207 ft2 0 ft2 00.0% ❑ ❑ East Wall 760 ft2 0 ft2 00.0% ❑ ❑ South Wali 207 ft2 0 ft2 00.0% ❑ ❑ West Wall 0 ft2 0 ft2 00.0% ❑ ❑ Total 1,174 ft2 0 ft2 00.0% ❑ ❑ Roof 1,600 ft2 0 ft2 00.0% ❑ ❑ CA Building Energy Efficiency Standards 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-04 13:46:15 Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 9 of 19 Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13AS, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx J. FENESTRATION SUMMARY § 110.6 This Section Does Not Apply K. OPAQUE SURFACE ASSEMBLY SUMMARY § 120.7/ § 140.3 Confirmed 1. 2. 3. 4. S. 6. 7. 8. 'a Aged Solar Reflectance Surface Name Surface Type Area (W) Type Type Cavity R -Value Continuous R -Value U -Factor / F -Factor / C -Factor N .08 T R-19 Wall Metal Stud8 ExteriorWall 640 Metal 19 NA U -Factor: 0.191 N ❑ ❑ R-13 Wall Metal Stud10 ExteriorWall 534 Metal 13 NA U -Factor: 0.229 N ❑ ❑ R-25 Roof Metal Rafter14 Roof 1600 Metal 25 NA U -Factor: 0.070 N ❑ ❑ Slab On Grade16 Underground Floor 1600 NA 0 NA F -Factor: 0.730 N ❑ ❑ R-0 Metal Building WaII18 ExteriorWall 2510 NA 0 NA U -Factor: 0.565 E ❑ ❑ R-11 Metal Building Roof29 Roof 3200 NA 11 NA U -Factor: 0.139 E ❑ ❑ Existing Grade32 Underground Floor 3200 NA 0 NA F -Factor: 0.730 r E ❑ ❑ ' Status: N - New, A -Altered, E- Existing L. ROOFING PRODUCT SUMMARY I § 140.3 Confirmed 1. 2. 3. 4. S. 6. 7. 7. 8. Product Type Product Density (Ib/ft2) Aged Solar Reflectance Thermal Emittance SRI Cool Roof Credit Roofing Product Description H R-25 Roof Metal Rafter14 4.20948 .08 .75 NA No NA ❑ ❑ R-11 Metal Building Roof29 2.54281 .08 .75 NA No NA ❑ ❑ M. HVAC SYSTEM SUMMARY (see NRCC-PRF-MCH-DETAILS for more information) I § 110.1 / § 110.2 Dry System Equipment 1(Fan & Economizer info included below in Table N) Confirmed 1. 2. 3. 4. S. 6. 7. 8. 9. 10. 11. System T3 Pe Total Heating Supp Heat Supp Heat Total Cooling Efficiency Acceptance Testing vd+ Equip Name Equip Type (Simple or City Output Source (Y/N) Output Output Required? (Y/N) * N '^ Complex °) (kBtu/h) (k6tuh) (kBtu/h) Cooling Heating HP -1 SZHP (SpIit3Phase) Simple 1 47 Yes 27 46 EER -12.5 SEER -15.0 / HSPF-8.7 Yes N El El - 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-04 13:46:15 Iroject Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 9 of 19 Iroject Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 :ompliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx Wet System Equipment 2 Pumps Confirmed Confirmed 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 1 22. 23. 24. SZHP No Economizer Equip Name Equip Type Qty Vol (gal) Rated Capacity Efficiency Standby Loss Tank Ext. R Qty GPM HP VSD d N — ❑ ❑ (kBtu/h) TSP Equip NameTSP (if present) (Y/N) CFM CFM HP BHP (inch Control CFM HP BHP Value Control Non ResBaseWaterHeater Storage 1 0 0 EF: .675 NA NA I NA NA NA No N ❑ ❑ Dry System Equipment includes fumaces, air handling units, heat pumps, etc. 2 Wet System Equipment includes boilers, chillers, cooling towers, water heaters, etc. 3 Simple Systems must complete NRCC-CXR-03-E commissioning design review form 4 Complex Systems must complete NRCC-CXR-04-E commissioning design review form 5 A summary of which acceptance tests are applicable is provided in NRCC-PRF-MCH-DETAILS 6 Status: N - New, A — Altered, E — Existing Discrepancy between modeled and designed equipment sizing? (if "Yes", see Table F. "Additional Remarks" for an explanation) No N. ECONOMIZER & FAN SYSTEMS SUMMARY' § 140.4 Confirmed 1. 2. 3. 4. 5. Equip Name Equip Type Controls Outside No DCV Controls HP -1 SZHP No Economizer Supply Fan Return FanAir V No Supply Air Temp. Control Economizer Type N r NonResBaseSHWSystem Service Hot Water, Primary Only Fixed Temperature Control, No DDC ❑ ❑ TSP Equip NameTSP (if present) CFM CFM HP BHP (inch Control CFM HP BHP (inch Control WC) WC) HP -1 240 1600 .721 .721 1.43 ConstantVolume NA NA NA NA NA NoEconomizer ❑ ❑ Mechanical ventilation calculations and exhaust fans are included in the NRCC-PRF-MCH-DETAILS section O. EQUIPMENT CONTROLS I § 120.2 Confirmed 1. 2. 3. d Equip Name Equip Type Controls No DCV Controls HP -1 SZHP No Economizer ❑ ❑ No Supply Air Temp. Control No Optimum Start NonResBaseSHWSystem Service Hot Water, Primary Only Fixed Temperature Control, No DDC ❑ ❑ CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-04 13:46:15 -- --- T- - -- - ---- — Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 10 of 19 Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx P. SYSTEM DISTRIBUTION SUMMARY I § 120.4/ § 140.4(1) Confirmed Dry System Distribution Confirmed 1. 2. 3. 4. 5. d a Equip Name Equip Type Dud Leakage and Sealing— Required per 140.4(1) Dud Leakage will be verified per NAI and NA2 Ducts Insulation R -Value Location HP -1 SZHP No No 0 Conditioned ❑ 1 ❑ Does the Project Include Zonal Systems? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information) No Does the Project Include a Solar Hot Water System? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information) No Multifamily or Hotel/ Motel Occupancy? (if "Yes", see NRCC-PRF-MCH-DETAILS for DHW system information) No Q. INDOOR CONDITIONED LIGHTING GENERAL INFO (see NRCC-PRF-LTI-DETAILS for more info)3 § 140.6 Confirmed 1. 2. 3. 4. S. Occupancy Type 1 Conditioned Floor Area 2 Installed Lighting Power Lighting Control Credits Additional (Custom) Allowance N d (ft2) (Watts) (Watts) Area Category Footnotes Tailored Method (Watts) ❑ ❑ (Watts) Commercial and Industrial Storage Areas (conditioned 1,600 500 0 0 0 ❑ ❑ or unconditioned) Building Totals: 1,600 500 0 0 0 1 See Table 140.6-C 2 See NRCC417-01-E for unconditioned spaces 3Ughting Information for existing spaces modeled is not included in the table CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-04 13:46:15 project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 11 of 19 )roject Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 -ompliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx R. INDOOR CONDITIONED LIGHTING SCHEDULE (Adapted from NRCC-LTI-01-E)1 § 230.0 Luminaire Schedule (includes all permanent installed lighting in Proposed Design Site (MWh) Confirmed conditioned space, and portable lighting over 0.3 w/ft' in Installed Watts (Conditioned) Margin (MBtu) offices) -- 1.4 -- Complete Luminaire Description i.e., p P ( -- How Wattage is Determined Total Number 1.0 1.3 Fail CEC Default According to Name or Item Tag 3 -lamp fluorescent troffer, F32T8, Watts per luminaire Luminaires Installed Watts Pass -- - one dimmable electronic ballast) — from NAB §130.0(c) - -- A 50w LED 50 No Yes 10 500 ❑ ❑ -'if lighting power densities were used in the compliance moael nuumng ueparrmenrs will nrruw «� _ • N..=ice• ^ r• -...... •-•• - it COVERED PROCESS SUMMARY— ENCLOSED PARKING GARAGES § 140.9 Phis Section Does Not Apply i2 COVERED PROCESS SUMMARY—COMMERCIAL KITCHENS § 140.9 Fhis Section Does Not Apply >3 COVERED PROCESS SUMMARY — COMPUTER ROOMS § 140.9 chis Section Does Not Apply >4 COVERED PROCESS SUMMARY— LABORATORY EXHAUSTS § 140.9 Phis Section Does Not Apply r. UNMET LOAD HOURS Phis Section Does Not Apply U. ENERGY USE SUMMARY Energy Component Standard Design Site (MWh) Proposed Design Site (MWh) Margin (MWh) Standard Design Site (MBtu) Proposed Design Site (MBtu) Margin (MBtu) Space Heating -- 1.4 -- 13.9 -- -- Space Cooling 1.0 1.3 -0.3 — Indoor Fans 2.2 2.4 -0.2 -- -- - Heat Rejection — -- - -- CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-0413:46:15 Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 12 of 19 Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx U. ENERGY USE SUMMARY Energy Component Standard Design Site (MWh) Proposed Design Site (MWh) Margin (MWh) Standard Design Site (MBtu) Proposed Design Site (MBtu) Margin (MBtu) Pumps & Misc. -- — -- — -- -- Domestic Hot Water -- — -- 9.9 9.9 0.0 Indoor Lighting 1.6 .8 0.8 -- -- COMPLIANCE TOTAL 4.8 5.9 -1.1 23.8 9.9 13.9 Receptacle .8 .8 0.0 -- -- Process -- -- - - -- -- Other Ltg -- -- - -- -- TOTAL 5.6 6.7 -1.1 23.8 9.9 13.9 CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-0413:46:15 Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 13 of 19 Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx DOCUMENTATION AUTHOR'S DECLARATION STATEMENT § 10-103 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Donna Wallace Signature:Qb0 h ✓tR� Company: Donna Wallace Address: 399 E. 9th Avenue Signature Date: 11/04/2016 City/State/Zip: Chico CA 95926 CEA Identification (If applicable): 4997: EnergyPro User Number Phone: 530-893-4982 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1 I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect. 2 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. 3 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538 and 6737.1. Responsible Envelope Designer Name: Andy Wood Signature: Company: North Valley Building Systems —f—g-C-7— %'yvd Address: #30 Seville Court Date Signed: It. City/State/Zip: Chico CA 95928 Declaration Statement Type: Phone: 530-345-7296 Title: V1ZE ?Q License#: Responsible Lighting Designer Name: Jack Thorpe ignatu Company: Agri Electric _ Address: 11011 Midway Date ign City/State/Zip: Chico CA 95928 Declaration Statement Type: Phone: 530-342-4203 Title: W �( License #: C-10 443455 Responsible Mechanical Designer Name: John Gray Signature: Company: Jessee Heating & Air Conditioning, Inc. Address: 3025 Southgate Lane Date Signed: City/State/Zip: Chico CA 95928 Declaration Statement Type: Phone: 530-891-4926 Title: wk4(s License #: C-20 405424 CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-0413:46:15 Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 14 of 19 Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx NRCC-PRF-ENV-DETAILS -SECTION START- A. TART A. OPAQUE SURFACE ASSEMBLY DETAILS Confirmed 1. 2. 3. 4. m '^ d Surface Name Surface Type Description of Assembly Layers Notes Metal Siding - 1/16 in. R-19 Wall Metal Stud8 ExteriorWall Metal framed wall, 16in. OC, 5.51n., R-19 ❑ ❑ Gypsum Board - 1/2 in. Metal Siding -1/16 in. R-13 Wall Metal Stud10 ExteriorWall Metal framed wall, 16in. OC, 3.5in., R-13 ❑ ❑ Gypsum Board -1/2 in. Metal Standing Seam - 1/16 in. R-25 Roof Metal Rafter14 Roof Metal framed roof, 24in. OC, 9.25in., R-25 ❑ ❑ Gypsum Board -1/2 in. Slab Type = UnheatedSlabOnGrade Slab On Grade16 UndergroundFloor Insulation Orientation = None ❑ ❑ Insulation R -Value = RO Metal Siding -1/16 in. ❑ ❑ R-0 Metal Building WaII18 ExteriorWall Air - Cavity - Wall Roof Ceiling - 4 in. or more Metal Standing Seam -1/16 in. ❑ ❑ R-11 Metal Building Roof29 Roof Metal screw down roof, R-11 Slab Type = UnheatedSlabOnGrade Existing Grade32 UndergroundFloor Insulation Orientation = None ❑ ❑ Insulation R -Value = RO B. OVERHANG DETAILS (Adapted from NRCC-ENV-02-E) This Section Does Not Apply CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-04 13:46:15 Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 15 of 19 Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx C. OPAQUE DOOR SUMMARY Confirmed 1. 2. 3. 4. 5. 6. 7. 8. 3 Opaque Door Assembly Name / Tag or I.D. Door Type Certification Method Operation Area Overall U -factor Status' Pass Fail OH Door21 Meta IUninsulatedSingleLayerRollupDoor DefaultPerformance NonSwinging 336 1.450 E ❑ ❑ Hollow Metal Door23 MetalUninsulatedDoubleLayerpoor DefaultPerformance Swinging 42 .700 E ❑ ❑ 1 Status: N - New, A —Altered, E— Existing NRCC-PRF-MCH-DETAILS -SECTION START A. MECHANICAL VENTILATION AND REHEAT (Adapted from 2013-NRCC-MCH-03-E) Confirmed 1. DESIGN AIR FLOWS 2. VENTILATION (§ 120.1) 3. 4. 5. 6. ami+ 8. 3 3 3 Rated Capacity G H g .0 m (kBtuh) Z aZ In System ID C Qty o Economizer c, ? < c tA Heating Cooling Design Min. V 70 � O C -n 0 3 A m Z 1 2 Z ;< m Z m 20 „ O �3 °c �c ° 1 O nm Z TZ --I < A „ CONDITIONEDo 0 T D D T y _ �+ _ NA N A m 9 --4 3 �� n T Z NA < ❑ ❑ ZONE NAME = _ 3D _ 3D �� r y 3 '—n' 3 a RI ° a ° Z cZi < T 3 Z V z `G)i z 0 Z v a o N O � r 3 a D D v O n O T 3 9 m Z 3 3 1 -Conditioned HP -1 1,600 NA NA NA NA N HP -1 1,600 NA 3 75.0 240 240 NA N ❑ ❑ Storage TOTAL 4,800 NA NA NA NA ❑ ❑ B. ZONAL SYSTEM AND TERMINAL UNIT SUMMARY § 140.4 1. 2. 3. 4. 5. 6. 7. 8. Confirmed Rated Capacity (kBtuh) Airflow, (cfm) Fan System ID System Type Qty Economizer Zone Name N - Heating Cooling Design Min. BHP Cycles ECM Ratio Motor Conditioned Storage3-TRM Uncontrolled 1 NA NA NA 1 -Conditioned Storage1600 NA NA NA NA ❑ ❑ ❑ CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version- NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-0413:46:15 0 ao a V 2 0 d a I Q T H Q Z Q W 0 Z. o cr W O 3 O N � FL• - H W O W N N x D J Z u 0 J � o LQL� C 0 J N C' N L LL tE ri 0 u U w - Z E 0 'a a, a M v Q CQ CGC L c7 ZZa u7 x LU W Q O x g I LL T Q Y Z �n FL_• tea, Fail ❑ ❑ E v cc M c Pass ❑ ❑ La. R LL u o ECMS MCH -18A v v c +� Condenser Water a MCH 17A Controls = 0 Reset Z O Y M Supply Air Temp. Reset m .N MCH -16A v c N M m TES Systems v MCH -15A Y a N CL E T LU J a ° Dist. Energy Storage v M MCH -14A DX AC O V E w> o Auto FDD for Air & MCH -13A Zone 0 c Q FDD for DX Units W m MCH -12A C a v Q w CL u Ww Auto Demand Shed MCH -31A Control v oc x -, -d Hyd. Variable HOW W Y MCH -SOA Control o � v a, Supply Water Temp. MCH -09A Reset V E Valve leakage Z Y MCH -08A M vi O Y N u Supply Fan VAV c tf MCH -07A 4 a V1 u � aJ 4.r DCV MCH-06A CL Q u H Q Economizer Controls MCH -05A 1 0 u O LL Z NAir Dist. Ducts ., MCH -04A H u H LU W W Single Zone Unitary Z U MCH -03A X m a u d Outdoor Air MCH -02A X Q Q ` a / E J .0 T C N O C ri ri V K L o Y x O Z 0o a N c E o Q 0 U° ai v c 0 2 E `- m Y U W c u ami > a N �a 0 d .� S C _ d �"- trN aJ Lu�f'> 0 2 ZLn Ln M v 0 0 N Y A W W (U c a) t± 0 0. v Cr Ln m m M kb 0 0 N N N 00 O W 0 LL d U U Cr Z E 0 0 0 CL ar U C 20CL E U v v_ •N c 0 Z M � N Q N m g v Y N > T LU J a v a U O V 0 w> 0 c Q C W C C a Q w Ww CO x -, v Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 17 of 19 Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx NRCC-PRF-LTI-DETAILS -SECTION START- A. TART A. INDOOR CONDITIONED LIGHTING CONTROL CREDITS (Adapted from NRCC-LTI-02-E) § 140.6 Lighting Control Credits Schedule (includes all lighting controls installed in conditioned space for 0 General lighting power from special function areas (see Table E) NA compliance credit per §140.6(a)2 and Table 140.6-A) Control Credit Calculation -4 If Acceptance Test Required Confirmed Location in Occupancy Type (must meet Type/Description of Lighting NA Watts of Power Control Credit NA NA Building requirements of Table 140.6-A) Control (i.e., partial on occupancy # of Units Controlled Adjustment Watts sensor, manual dimming, etc.) Lighting Factor Pass Fail S -1 -Conditioned Commercial and Industrial Storage Storage Areas (conditioned or - none specified - 1 .00 0 ❑ ❑ Unconditioned) B. INDOOR CONDITIONED LIGHTING MANDATORY LIGHTING CONTROLS (Adapted from NRCC-LTI-02-E) § 130.1 This Section Does Not Apply §130.1(a) = Manual area controls; §130.0(6) = MultiLevel; §130.1(c) = Auto Shut -Off,• §130.1(d) = Mandatory Daylight; §130.1(e) = Demand Responsive C. TAILORED METHOD CONDITIONED LIGHTING POWER ALLOWANCE SUMMARY AND CHECKLIST (Adapted from NRCC-LTI-04-E) § 140.6 General lighting power (see Table D) 0 General lighting power from special function areas (see Table E) NA Additional "use it or lose it" (See Table G) 0 Total watts 0 D. GENERAL LIGHTING POWER (Adapted from NRCC-LTI-04-E) § 140.6-D This Section Does Not Apply E. GENERAL LIGHTING FROM SPECIAL FUNCTION AREAS (Adapted from NRCC-LTI-04-E) § 140.6(c) 3H Room Number Primary Function Area Illuminance Value (LUX) Room Cavity Ratio (Table G) Allowed LPD Floor Area (ftz) Allowed Watts Confirmed Pass Fail NA NA NA NA NA NA NA ❑ ❑ CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-04 13:46:15 r—----- – 'roject Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-F Page 18 of 19 )roject Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 .ompliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx F. ROOM CAVITY RATIO (Adapted from NRCC-LTI-04-E) - Rectangular Spaces Room Number Task/Activity Description Room Length (ft) Room Width (ft) Room Cavity Height (ft) RCR Confirmed Pass Fail NA NA NA NA NA NA ❑ ❑ Non -Rectangular Spaces This Section Does Not Apply NOW: An appucame spaces are usaea unser ane roan-rtecwnyufui �PULe -- G. ADDITIONAL "USE IT OR LOSE IT" (Adapted from NRCC-LTI-04-E) 1. 2. 3. 4. Allowed Watts Confirmed Wall Display Combined Floor Display and Task P y Combined Ornamental and Special p Very Valuable Merchandise 0 H r d Lighting Effects Lighting 0 0 0 0 0 ❑ ❑ i. Wall Display Phis Section Does Not Apply 6. Floor Display and Task Lighting This Section Does Not Apply F. Combined Ornamental and Special Effects Lighting 'his Section Does Not Apply 3. Very Valuable Merchandise Fhis Section Does Not Apply CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-04 13:46:15 Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 19 of 19 Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx H. INDOOR & OUTDOOR LIGHTING ACCEPTANCE TESTS & FORMS (Adapted from NRCC-LTI-01-E and NRCC-LTO-01-E) § 130.4 Declaration of Required Acceptance Certificates (NRCA) —Acceptance Certificates that must be verified in the field. (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify). Indoor Outdoor Confirmed Test Description NRCA-LTI-02-A NRCA-LTI-03-A NRCA-LTI-04-A NRCA-LTO-02-A # of units Occ Sensors / Auto Time Switch Auto Daylight Demand Responsive Outdoor Controls Equipment Requiring Testing or Verification 0 1:1❑ 13 11❑ El Occupant Sensors 0 0 0 0 ❑ ❑ 171❑ ❑ ❑ ❑ ❑ 1:1 ❑ ❑ ❑ ❑ ❑ ❑ ❑ El El 1:1 ❑ 11Automatic El 11 ❑ Time Switch Automatic Daylighting Demand Responsive Outdoor Controls CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance 1 Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-0413:46:15 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Conditioned Storage at Patrick Ranch Museum Date 11/4/2016 System Name HP -1 Floor Area 1,600 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL COOLING PEAK COIL HTG. CFM Sensible Latent CFM Total Room Loads 1,240 24,236 3,200 615 Return Vented Lighting 0 Return Air Ducts 1,212 Return Fan 0 Ventilation 240 7,509 757 240 Supply Fan 3,167 Supply Air Ducts 1,212 TOTAL SYSTEM LOAD 37,335 3,957 PEAK Heating System Sensible Output per System 46,500 17,403 Total Output Btuh 46,500 Output Btuh/s ft 29.1 870 Cooling System 0 Output perSystem 47,500 11,405 Total Output Btuh 47,500 -3,167 Total Output Tons 4.0 870 Total Output Btuh/s ft 29.7 Total Output s ft/Ton 404.2 27,382 Air System CFM per System 1,600 HVAC EQUIPMENT SELECTION Airflow cfm 1,600 Carrier Corp. 25HCC548A"30 38,835 4,306 28,251 Airflow cfm/s ft 1.00 8.0 kW Supplemental Electric 27,304 Airflow cfm/Ton 404.2 Total Adjusted System Output 38,835 4,306 55,555 (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK Jul 3 PM Jan 1 AM Outside Air % 15.0% Outside Air cfm/s ft 0.15 Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 25 OF Outside Air 240 cfm 69 OF 65 OF 97 OF 97 OF 97 OF Aux. Heat Coil Supply Fan Heating Coil 96 OF 1,600 cfm ROOM 70 OF COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 104/72°F Outside Air 240 cfm 75 / 62 OF 81/64°F 55/54°F 55/54°F v uµ Cooling Coil Supply Fan 56 / 54 OF 1,600 cfm 48.9% ROOM 74 / 61 OF EnergyPro 6. by EnergySoft User Number: 4997 ID: NVBS72 Page 21 of 21 ® CRANDALL ENGINEERING 5448 Merrill Mill Road Mariposa, CA 95338 Phone: 209-966-4844 �uit-nylc o P.r-4L.�. E- rue- SHEET I OF `Q JOB NO. I `E'® -A5 DATE: N O Tam f E �P Q�0fESSiG,, t u , q OFC V4A -- - -�� -z:-p16 Vic' t BUTTE COUNTY PER IT# NOV U 7 2x16 BUTTE COUNTYDEVELOPMENT SERVICES REVIEWED FOR DEVELOPMENT COaE OOMPLIANC SERVICES DATE r -e-lE eo p./ -USGS=Provided Output Ss = 0.613 g SMs = 0.803 g Sos = 0.535 g S1 = 0.272 g SMi = 0.504 g So, = 0.336 g For information on how the SS and S1 values above have been calculated from probabilistic (risk -targeted) and deterministic ground motions in the direction of maximum horizontal response, please return to the application and select the "2009 NEHRP" building code reference document. MCER Response Spectrum Design Response Spectrum II 4.94 -U. VL- _- ___._.._-__-- __..__._ __..__... ___.-.___. .. ____- - Ch 4.6v D.42 r, o.ss A, 4.36 0.45 � 0.34 4.3€ 0.24 4.27 4.13 0.18 4.12 0.09 4.06 0.00 1 4.44 0.00 4.20 0.40 0.&0 0.00 1.00 1.20 1.40 1.60 1.30 2.00 0.00 0.20 0.44 4.60 0.00 1.00 1.20 1.40 1.60 1.80 2.00 Period, T (sec) Period, T (sec) For PGA, TI, CRs, and CRI values, please view the detailed report. Although this information is a product of the U.S. Geological Survey, we provide no warranty, expressed or implied, as to the accuracy of the data contained therein. This tool is not a substitute for technical subject -matter knowledge. http://ehp2-earthquake.wr.usgs.gov/designm aps/us/summ ary.php?template=minimal&latitude=39.6842&longitude=-121.8007&siteciass=3&riskcategory=0&edit.. 1/1 CRANDALL ENGINEERING SHEET OF 5448 Merrill Mill Road JOB NO. Mariposa, CA 95338 / t Phone: 209-966-4844 DATE: at A-10 f i^ m. o- _ - I CRANDALL ENGINEERING SHEET �' OF 5448 Merrill Mill Road JOB NO. (OO 1� Marlposa, GA 95338 DATE: Phone: 209-966-4844 .��� oG 2c- e res = f, V 'Web height -to -thickness ratio exceeds 200. Web stiffeners are required at all support points and concentrated loads. 'Allowable moment includes cold work offorming. See Table Notes on page 7. j i Usi� f ro Pr3ssrt�asn i"`, EffecfivaP ertibs� �`�� i0FsldflalPmpSrtie5 `m xt �tfia►r� .: Ycknes�,'-�. a �� _-+�"*��''�:. Vin) � T �� Area .,Weight �.Ix -1 �fSz �LRx rnilly'�' 7�.RY� „ (in�)r., ':(Ibin)� '� n!j..`(10'►':...?I�n)._.�;a�_Gn�'�;`(ih) ..�(�n`) -1xe'� :r�^(m' 1.224 Sxeu �, _ 0.503 Mat;., :(jn""k'1. � 9.93 fARad . (in-�ijT 10.41 Yag Ib) ;»..:i(Ib) 1739 Vanet} � 810 Jz'�OOO.,Gw , y��Ro�;u, ,`(111"j,_ inn ~�Gn)" �;(�o � �n �_ 0.303 1.486 -2.139 1.252 2.864 �0�' ,r., ::...� 0.443 4Cuj r 63.7 40OS250-43 0.0451 33 0.447 1.52 1.224 0.612 1.655 0.399 0.945 4005250-54 -33 0.556 1.89 1.512 0.756, ;1.649 ;0 49, ' ;0:938 1.512 `0.653 12.9 13.91. 2603 944 0.594 ' 1:821 ' 2.124 1.244 ,:2.848::;, 0 444 ,_;'63.8 _0:0566 400S250-54 0.0566 50 0.556 1.89 1.512 0.756 1.649. 0.49 0.938 1.506 0.576 17.24 16.42 3372 1223 0.594 1.821 -2.124 1.244 2.848 0.444 51.6 40OS250-68 : `0.0713 33 0.693 " 2.36 1.864 0.932 1.64 `0.599 ` 0.929 1.864 `;0.663 17,45' 18.42 . 3215 - 895 1 1:174 2.225 , -2.105 •1:235. 2.826 ,0.445 64 ' 4005250-68 0.0713 50 0.693 2.36 1.864 0.932 1.64 0.599 0.929 1.864 0.775 23.19 24.76 4871 1356 1.174 2.225 -2.105 1.235 2.826 0.445 51.6 4005250-97 :0:1017 33 '0.966 3.29 " 2.541 ;1.271 1.622 0.801 .0.911 2.541 = '1.253 '28.31 -28.7'' 4394 797 3.329 2.976 -2.066-1.214 2.78 0.448, ;,60.3 4005250-97 0.1017 50 0.966 3.29 - 2.541 1.271 1.622 0.801 , 0.911 2.541 1.191 40.06 41.47 6658 1207 3.329 2.978 -2.066 1.214 2.78 0.448 48.8 4005300.54 ` 0.0566 33 '0.613 2.09 1.732 "0.866 1.681 ;,0.760 1.114 1.723 - 0.680 .13.44 14.70 2603 944 0.655 .,2.802 -1594.1'.'.1.496 3.285>'s.0.377 '74.0 4003300-54 0.0566 50 0.613 2.09 1.732 0.866 1.681 0.760 1.114 1.637 0.592 17.72 19.25 3372 1223 0.655 2.802 -2.594 1.496 3.285 0.377 59.9 4005300-68 `-0.0713 33 _ 0.764 2.60 2.139 1.070 1.673 (0.933 1.105 2.139 0.914 :18.06 19.68 3215 ,;895 1195 3.432 --2.574 1.486 3.263 0.378• 74;3 ;. 4003300-68 0.0713 50 0.764 2.60 2.139 1.070 1.673 0.933 1.105 2.099 0.805 24.09 26.05 4871 1356 1.295 3.432 -2.574 1.486 3.263 0.378 60.0 40CS300.97 :'0.1017. '-33 1.067 3.63 2.928 1.464 1.656 1:086 2.928: 1.381 A0.58 32:4 4394 .797 3.679 4.619 '-2.535 1.465 3.216: ,0.379 70.8 4005300-97 0.1017 50 1.067 3.63 2.928 1.464 1.656 11.258 1.258 1.086 2.897 1.307 39.12 40.72 6658 ' 1207 3.679 4.619 -2.535 1.465 3.216 0.379 60.3 550Si37-33 : 0.0346 0.301, 1.02 ;1.283 0.467 2.064 0.067 =0.472. 1.283..0.453 8.95 7.48 699 699 0:12 0.411-.-0.841 ;-0.536 2.278 0.864, :33.7 5505137-43 0.0451 733 33 0.391 1.33 1.655 0.602 2.059 0.085 0.467 1.655 0.592 13.08 11.6 1550 1199 0.265 0.52 -0.83 0.53 2.268 0.866 31.7 5505137-54 0.0566 33 0.486 1.65 ,:2.039 6.741 .2.049 ,A.103 0.46 2.039', 0.741 '16,77 15.9 .2739 1666 0.519 0.632 ;-0.817 0;523 2.254„ 6.868 , 31.1,' 5505137-54 0.0566 50 0.486 1.65 2.039 0.741 2.049 0.103 0.46 2.039 0.714 24.03 20.88 3093 1881 0.519 0.632 -0.817 0.523 2.254 0.868 25.4 5505137-68 '-0.0713 . 33 0:604 2.05 2.503 -0.91: .2.036 0.123 0;451 1.0.123 2.503 0.91 21.22 21.22 4347 2057. 1:.023 !'0.764 : -0.801 ; 0:514 2234 0.871 :30.4 550S137-68 0.0713 50 0.604 2.05 2.503 0.91 2.036 0.451 2.503 0.909 31.42 28.69 5350 ' 2532 1.023 0.764 -0.801 0.514 2.234 0.871 24.9 550S137-97 .0.1017 33 0.838 2.85 ''3.38 :1:229 :2.008 0.155 :0:43 3.38 ` 1229 30.35 30;35 6282 '1997' :2.891, - 0.997 -0.766 '0:497 2.192 0.876 '29.2 5505137-97 0.1017 50 0.838 2.65 3.38 1.229 2.008 0.155 0.43 3.38 1.229 44.72 44.72 9518 3026 2.891 0.997 -0.766 0.497 2.192 0.878 23.9 5505162-33 0.0346 x33 , .0.327 '1.11 1.458` 0.530, 2.112 ,.0113 0,589. 1.458;; 0.512 10.11 `8.63= fi99 ', ';E99 ,. 1).130 ,.,0.713 =-1:114 0;697 :2.459_ ;.,0.795 =41.4 5505162.43 0.0451 33 . 0.424 1.44 1.883 0.685 2.107 0.145 0.584 1.883 0.681 14.79 13.14 1550 1199 0.288 0.905 4.103 0.691 2 448 0.797 39.2 550S162-54 33 0.528 " 1,80 2!324 ;0:845 2098';;0.176 ..0;577, 2.324; 0.845 .18.76' 17.87„ 2739 ;1666„0:564„ 1105090,'0:684 2.434' ,0800, : 8.7,:; 5505162-54 .0.0566 0.0566 50 0.528 1.80 2.324 0.845 2.098 0.176 0.577 2.324 0.811 26.86' 23.52 3093 1881 0.564 1.105 4.090 0.684 2.434 0,800 31.6 550S162-68 0.0713 33 0.657 ' 2.24 2.661 .1.040 2.086 ;0.212 ; ,0:566 .2.861' 1.040 23.72' 23.72 4347 .2057 1.114 ^1.342 °' 1072 , 0:675 ; ` 2.414 0.803 38.0 550S162-68 0.0713 50 0.657 2.24 2.861 1.040 2.086 0.212 0.568 2.861 1.031 34.94' 32.28 5350 2532 1.114 1.342 4.072 0.675 2.414 0.803 31.1 5508162-97 ''0.1017 , 33 . 0.915 3:11 3.886 -1.413 2 061 ''0.276. 0:549. 3.886' 7,413 '33 91 .33:91 ' 6262 _ ;1997 3:154 , 1.775 1.037 5505162-97 0.1017 50 0.915 3.11 3.886 1.413 2.061 0.276 0.549 3.886 1.413 50.13 50.13 9518 3026 3.154 1.775 4.037 0.656 1 2.372 0.809 30 5505200-33 0.0346 33 6.362 • 1,23 1:694 •0.616. 2.164 , "0.204 0.751: 1.678 0.559 11.05 , ,9.80' ..699 :699. .0.144 1.326:; 1:508 0:925 2.742 0.698 =51:9 't 550S200-43 0.0451 33 0.469 1.60 2.189 0.796 2.159 0.261 0.746 2.189 0.776 15.33 13.96 1550 1199 0.318 1.691 -1.496 0.918 2.731 0.700 51.7 550S260-54 ' 0.0566 33 0.585 1.99 12.706 '0.964 2.152 <0.32 , 0:739 1906 0.984 11.41 19.08 2739 _:1666 • 07624 2,072':,4;483- 0:911 2.716 0.702 '-49.2 i 5505200-54 0.0566 50 0.585 , 1.99 2.706 6.984 2.152 0.32 0.739 2.706 6.901 26.98 24.84 3093 1881 0.624 2.072 1.483 0.911 2.716 0.702 41.6 550S200=68.70_07.13 :, 33 x.729.2.48 :3.341._ 121 2.141 ':0,389231_ 3.341_ 1.215,27.03_2703.}3347 -12057 = 1235_ 2 531.:_ 1463-'0 902 2.695 Q ip5 , ::48.5 39.6 `,:47.4 ,t 55OS200-68 0,0713 50 0.729 2.48 3.341 1.215 2.141 0.389 0.731 3.341 1.17 38.83 •35.92 5350 2532 1.235 2.531 4.465 0.902 2.695 0305 JD 5509200-97 :0,1017 33 .: '1.016. 3.46 .0:563 .1.659 2.119 .0.516, 0.712 .0;563' ':1.659' 38.58 38:58 8282,:'1997 :ItI64 .'3:384 1428 ;4,882 ;2.652 .710 -- 5505200-97 0.1017 50 1.016 3.46 4.563 1.659 2.119 0.515 0.712 4,563 1.659 5725 57.25 9518 3026 3.504 3.384 1428 0.882 2.652 0.710 'j 38.6 56013250-43 5505250-43 .0.0451 33'L 10.515 t. .?.524 -' 0.918 '.2.215 '0.445 {0.93 2.524 `.. 0.817 .1615 , ;14,74 , 1550 ` :1199 , Q,349 2.837 .,1933.. "1;163 ,;3.083, 0 5505250-54 0.0566 33 0.641 ,1.75 2.18 3.126 1.137 2.208 0.547 0.923 3.126 1.033 20.40 19.87 -2739 1666 0.685 3.486 1.919 1.155 3.067 9.609"._62.6, 5545250-54 _0:0566 ' ;50 0.641;: 3.18 - ' 3:126 ;. 1.137 2 208.10 547 ,.; 0.923 , ; 3,064 ",,, 0 95 ;28.44 '26.11 , ,3093 `1881 ,.fi85, ,3 486rs 1 919 ,,;1:155 '.3.067 0 609 5505250-68 0.0713 33 0.800 , 2.72 3.866 -_ 1.406 2.198 0.669 0.914 3.866 1.345 29.28 28.52 4347 2057 1.356 4.274 -1.900 1.146 3.046­'­0.611 59.5 5505250-68 ' -0.0713 X50 '0:800 ,•.2.72 :3:866' 2.198 :':0 669 0;914 u :3.884;, ,1.233 36 9,1 „'3543 5350' ` 2532 1:356 4.274 ,1.800 ' 1;146 ;3:046 , 0 5505250-97 0.1017 33 1.118 3.80 5.304 _IA06 1.929 2.178 0 897 0.895 '0.697 5.304 1925 43 47 43.57 6282 1997 3.855 5 761 1862 1 y 1.862, ;1126 3.002 3:655 :126 3 002 0615 0615 58.4 47 6 5505250-97 ' '0.1017 ' . '50 1.118 " 9.80 5"!304 1.929 2.178. :: 0:895' 5.304 1.837 .-:fi1.77,.80:32 9518=3026 •.5.761 ;' 6005137-33 0.0,346 33 0.318 108 1.582 0.527 2.229 0.069 0.464 1.548 0.455 8.98 8.19 638 638 0.127 0.500 -0.807 0.519 2.416 0.889 33.5 600§137-43, :,0.0'451 33'0,4f3; 141 =_'?:042,;0.661 2223 ;;0067, :0;459 „2041;;,.0.645 1274 , 11,82 1,416 '.1240 0.280 0.633_? 0,7,96 ,,0513, ,2405.• 0890? '333 ; 6005137 54 0.0566 33 0.514 1.75 2.518 0.839 2.213 0.105 0.452 2.518 0.832 16.44 15.95 2739 1890 0.549 0.769 -0.784 0.506 2.391 0.893 33.0 -,606S137-54 '0 0566 . ;; 50 0.514 ;!,,, t 75 . 2,518 D 839 213, ::0105 0;452 -2.518, , 0 777. -23 26_ 21:24 , 2823 '.1947 ,-:0149 0 769 --_ , 0 784„ ,0.506 ,. Z 391 0 893 , - 666S137-68 , 0.0713 33 0.640 218 3.094 _ �2 1.031 2.200 0.125 0.443 3.094 1.031 24.052 24.05 4347 2339 1.084 0.930 -0.768 0.497 2.371 0.895 90.1 6005137 68 ' 0 0713 50 0.8W-:`2.18,,3:094 1.031, 2200 0125, 1030 ;'30 84 _ 28;89 5350 '?,2879 _ 1084 _0 930_. , 0 768 'Q A97. 2 3y1 0 895 600S137-97-01,017-----33 .0.889 - 3 03 x1_188 _ x-396 2170 _0159 -0.422 4.188 _x,396_34 48 2 34.49 6911 9 512 3.066 .0.480 2 330 _L216-0i.734 0.901 -28-8.- 6005137-97 01p17 50:,` 0.889 303,.'4168 2170 „0159 .0:422, 4.188:- 1396;50802 ,50:80, 10472_ ;3805 x;566{„,.1216" 0734 .0:4801.2330 0901 _236: : _ 6005137-118 01242 33 1.065 _ 3.62 4.913 ,•,1398. 1.638 2.147 0.176 0.406 4.913 1.638 42.05 42.05 8267 2391 5,477 1 391 0 709 0.467 2.298 0 905 27 9 800S137118 ; , 'S0 1:U85'- '3.62 4 913 `1.636 X3.147 `i 0178' _ 0.406, 4:913, 1638 . L6 9 - 8669 12526 ::'3622„, 5;477 .1.391 k, 0709 „0' 467 '2:298 , 0 905 , ,22 9 '# ,'-10.1242 600S162-33 0.0346 33 0.344 117 1.793 0.598 2.282 0.116 0.581 1.793 0.577 1141 9.47 638 638 0.137 0.861 4.072 0.677 2.587 0.828 411 - 6005162 43 ;, 0.0451 , 33 0.447`:;J&-_'-'.2 316 4 :, 0.772 ,2276' 018 ,0.576 .2,316` . 0 767 , ,16 68 r 14.06 1416 • ' 1240 , , 0.303 1.095 1062 ;.0_670 2527, , 0 830",39,10- 6005162-54 0.0566 33 0.556 1.89 2.860 0.953 2.267 0.180 0.570 2.860 0.953 2117' 19.75 2739 1890 0.594 1.337 1049 0.663 2.562 0.832 38.4 fi00S162-54 0566 50 0:556- 1.89 - :2.860 0.953 2 267 `: `_ 0180 ..0:570, 2 860 0 916, ; 30 33?, F25;90. 2823 -;;1941 0:594 , ,1337ww 1049, 0 ;863 2 562 0 832 ,..`;0 6003162-68 0.0713 33 0.693 2.36 3.525 1.175 2.255 0.218 0.560 3.525 1.175 26.79 2 26.78 4347 2339 1.174 1.626 1 032 1­01,6.551 _-2.543.10.835 835 37.7 30c8 600S162 68 ;0.0713 ` : `50 •,0.693;' '2.36 3 525 .1,125 255 ;'_ 0 218 `3.525., 1164 ; 39 472 ,'36169 5350 ,-. 2879 1:174 1626;' ,1032 _",655 2:543 , ,0 6005162-97 0.1017 _. 33 0.966 3.29 4.797 _2 1.599 2.229 _0:560" 0.283 0.541 4.797 1.599 38.37 2 38.37 6911 2512 3.329 2.153 0 997 0.636 2.5 - 0 - 1 2„,OB41 0 841 36.4 600S16297 `01017,';;50, 0.968";, 329, `4797 ;1.599 x2229<,0283 ;0:541,,,4797, 1599.,:5673,56.72,10472-.'„38052153._„0997 ;0,636 ,298; 60OS162-118 01242 33 1.158 3.94 5.652 1.884 2.209 0.321 0.526 5.652 1.884 46.82 2 46.82 8267 2391 5.956 2.487 0.971 0.623 2.470 0.845 35.6 "19A 8'00$162-118 ° `0.1242 '''50 . '1:158' 3.94- ;5.652..:1:1364 ' 2:209 ','A 321 P,0tb26 >5.852 1.864 "68.94', '6893 =12526:` 3622 .5:956..2.487 OJ7,1" 0623 2.470 0.845' I 'Web height -to -thickness ratio exceeds 200. Web stiffeners are required at all support points and concentrated loads. 'Allowable moment includes cold work offorming. See Table Notes on page 7. j i 4- A" - f Web be, ratio exceeds 200. Web stiffeners are required at all support points and concentrated loads. 'Allowable moment includes cold work of forming. 'Where web helgh t -to -thickness ratio exceeds 260 or flange width -to -thickness ratio exceeds 60, effective propertles are not calculated. See AISI 5100 Section BI. Application of these products in a non -composite design shall be approved by a design professional. See Table Notes on page 15. D25ign.1 dt� Properties E y ��ffi4[1r� Prop33 ksi Effabffva`Prapr(501csiIdtsio yai=tl� Weight x Rx ly Ry Ixe SSce lint slag s Izb ice ala liag 3x1000 t1vCo mfo B Sactiotl #Thfekeess Area Ix" xSx ; ;',(in') (m') M;(inj (in*) ir(m);; s 'Gn`I (In')Qn:k) �Ib) .`'lm�) lm�.�1°!._...,, r __..In) 0.0451 ,(in') :(Ibl1t) 0.405 1.38 u 2.072 0.673 2.261 0.073 0.424 1.890 0.474 9.36 1377 0.275 0.504 -0.680 0.437 2.398 0.920 600T150-43 600T150 54 0.0566 ' 0.509 1.73 2:611 `0.843 2.266 0;091 .0.422 2.473 :'0.689 13.62 2728' 2.400 0.609 18.24 2728 '0.543 0.632 ,•-0.675 :"0.434 , 2:401 0:921 600T150.68 0.0713 0.641 . 2.18 3.309 1.059 2.273 0.113 0.419 3.262 0.963 19.03 4347 3.162 0.891 26.68 5350 '10885 1.086 0.797 -0.669 0.430 2.406 0.923 '3.148 1:138 ;.2:415 0.926 600T150-97 0.1017 0.913 f3.11 4.778 1.504':`2.288 :;0:156 0:413 4.778 1.504 29.71 7359 - 4.778 -1.444 43.23 5.886 1.829 61.64 13539 -0.656:0.421 5.730 1.389 -0.647 0.415 2.422 0.929 600T150-118 0.1242 1.115 3.79 1.18 5.886 1.829 2.298 1.913 0.622.352 2' 0.186 0.126 0.409 0.604 - 1.542 - 0.333 6.59 622' 0.138 -0.847 •1.046' 0.855 2.645 0.843 60OT200-33 60OT200-43 0.0346 -: 0.0451 0.346 0.451 1.53 2.494 0.809 2.353 0.163 0.602 2.076 0.565 11.16 1377 0.305 1.098 -1.044 0.652 2.643 0.844 60OT200-54 '0.0566 0,565 _1.92 -:3.145 1.015' 2.359 0.203 .;0:600 2.759 0.759 15.00 2728 ' 2.641 . 0.717 21.48 2728 :0.604 .1:381 -1.038 0.649 '2.646 :0.846 1.206 1.746 -1.031 0.644 2.650 0.849 60OT200-66 0.0713 0.712 2.42 3.990 1.277 2.367 2.385 ';0.354 0.254 ' 0.597 0.591 3.696 5.758 ';1:667 1.034 20.42 :32.95 4347 7359 - 3.540 0.973 29.12 5350 5.558 "1.568 46:94 :90885- '3.499 2.510 4.016 0.635 2:659 '0.854 60OT200-97 600 T200-118 0.1017 0.1242 1.015 1.239 3.45 4.21 - 5.773 1.816 7.122 2.214 2.398 0.426 0.586 7.122 2.051 61.42 13539 6.369 3.083 4.006 0.628 2.665 "0.858 60OT25043 .0.0451 r 0.496 1.69 2.916 -0.946 2.425 .0.303 -0.781 2.269 0.563 11.13 1377 2728 1 - - - - - - 2.881 0.732 21.92 2728 0.336 '2.004 -1.436 0.878 -2,925 0.759 0.664 2.523 -1.430 0.874 2.927' 0.761 60OT250-54 0.0566 0.622 2.12 3.678 1.187 2.432 , 4.670 1.495 2.442 ' 0.377 0.472 0.779 0.776 3.014 4.065 0.794 .1.085 15.68 :21.45 4347 3.871 x:1:017 `30.46 5350. ? 1.327-, ; :3.198 -1422 0.869 ' 2:930 ' 0.764 60OT250-68 60OT250-97 0.0713 0.1017 0.783 1.117 .2.67 3.80 6.767 2.129 2.462 0.662 0.770 6.441 - 1.775 35.08 7359 6.158 1.656 49.58 10885 3.849 4.616 -1.406 0.859 2.938 0.771 600T250-118 0.1242 1.363 4.64 -8.359 2.598 %2.477 ';0.798 0.765 8.306 12.343 '46.30 8936 ` 7.990 ".2.188 <65.51 13539 , 7.008 5.686 -1.394` '0.852. '2.943 0:776 80OT125.33' 0.0346 0.363 1.24 2.895 0.711 2.824 0.036 0.313 2.441 0.407 8.03 465 - - 0.145 0.456 -0.439 0.294 2.875 0.977 0.321 0.589 -0.436 3:674 0.977 80OT125-43 0.0451 - 0.473 "1.61 2.02 :3.773 0.924 2,824 4.745 1.158 2.827 "0.046 0.057 -0.311 0.309 3.484 4.668 .0.640 0.940 '12.65 18.58 1030 2039 - - 4.426 0.824 24.66 2039 ,0.292 0.634 0.735 -0.432 0.289 2.877 0.977 800T125-54 800T125-68 0.0566 0.0713 0.594 0.748 "2.54 5.998 1.454' 2.833 0.070 0.306 5.998 :1.356 26:80 4087'': 5.956 1:216 .36.39 4087 1.267 •'0.920 x0:427 0.286 2:881 .0.978 800T125-97 0.1017 1.066 3.63 8.613 2.062 2.843 0.096 0.301 8.613 2.062 40.74 8843 8.613 2.062 61.72 10885 '10.569 3.674 1.296 -0.417 6.279, 2.889 0.979 6 688. 1.567 -0.410 0.274 2.895 0.980 8OOT125-118 0.1242: ' 1.301 =4.43 10:569 - 2:506 •2.850 , 0.114 0:297 -' - 2.506 86:21- 16235 0.152 0.751 -0.588 0.388 2.977 0.961 BOOT150-33' 0.0346 0.380 1.29 3.180 0.781 2.891 " 0.060 0.397 2.569 0.414 8.18 12.95 ` 465 1030? '- 0.336 ' 0:972 =0.584: 0.386 "2:978 0.961 BOOT150-43 0.0451" 0.496 `1.69 4:144 `1.015 - 2.891 5.214 1.272 2.896 0.077 0.096 "0.395' 0.393 3.689 4.976 10.655 0.969 19.15 2039 4.692 0.844 25.27 2039 0.664 1.215 -0.580 0.383 2.979 0.962 80OT150.54 80OT150-68 0.0566 -0 0.622 0.783 2.12 2.67 +6:594 1.599 2:902 ;0.119 `.0.390 6.527 1.412 :27.91 4087 6.361 1.255 :37.58 4087 : 1.327 1:526 , -0.5751 `0.379 .2.984 ;0.963 800T150-97 .0713 0.1017 1.116 3.80 9.479 2.269 2.914 0.165 0.384 9.479 ", '- 2.269 44.83 8843 9.479 2.192 65.62 10885 11.641 2.760 93:00 16235 3.849 2.162 -0.564 0.372 2.993 0.965 ; 7008 2627 -0.555 0366 .2;999 ,0.966 800T150418 A.1242 ' 1.363 ,'`4.64 1.41 11.641 "x2.760' '2.923 3.749 0.921 3.005 :0.197 0.135 =0.360. 0.571 2.786 0.424 8.37 465 0166 1.638 -0.917 0.589 3.194 0.918 - ,. 80OT200-33' 8007200 43 '� 0.0346 -0.0451 0.415 0.541 '1.84 4.887 '1.197. ,3:006 A.175 ::0.$69 4.043 - 0 676 -13.35 A030 A 367 .21124 =0:913' 0 587 .'.3:193 ;0.916 80OT200-54 :' 0.0566 0.679 2.31 6.152 1.501 3.011 .; 0.218 0.567 5.505 1.009 19.93 2039 ' 5.149 0.871 26.09 2039 0.725 2.664 -0.908 0.584 3.196 0.919 0357 =0.902 0.580.3.2101 0.921 BOOT200-68 '0.0713 0.854 2.91 1.888 3.019 0.272 0.564 7.306 1.490 ;29.45 4087 ` 7.051 - ;1.310 39.22 4087 1.448 8007200-97 0.1017 1.218 4.15 ,7.786 11.212 2.683 3.034 0.379 0.558 11.176 2.491 - 49.22 "_ 8843 =- 10.833 2.347 70.27 10885 3785 -3:059-91:59 16235 4.200 4.792 -0.889 0.571 3.210 0.923 5.848 --5854 41899--1-."5-­3.217-0.125` 80OT200418 -01242- -1:487 --5-.06--13.785--3.269-,-,3.045 -0:455--0:553- 0.326 0.746 - 4.593 =- 0.739 14.60 1030 - - 0.397 3.877 -1.274 0.801 3.433 0.862 80OT250-43 80OT250-54 0.0451 0.6566 ` 0.586 0.735 1.99 2.50 5.629 1.380 3.100 '7.090 1.730 3.106 0.407 ,C744 5.948 1.193 23.57 2039 5.816 ..959 28:71 2039 ': > 0.785 4:670 •-1:268 , 0.798 <3.436 %0.864 80OT250-68 , 0.0713 0.926 3.15 8.978 2.177 3.114 0.509 0.741 7.917 112.361 1.648 32.57 4087 7.588 1.560 46.72 4087 11.872 '2.487-- 74;47 ' 10885''` 1.569 6.151 -1.261 0.793 3.441 0.866 4.550 •81818 .-1.247 0._784 '-3;150 0.869 BOOT250-97 . 0:1017 1.320 + 4.49 5.48 :12.944 3:098 3.132 15.930 3.777 3.144 (0.713 0.860 n.735 0.731 15.822 2.641 3.448 -52.19 68.14 8843 12009 15.272 3.248 97.26 16235 , 8.285 10.807 -1.236 0.177 3.457 0.872 80OT250-118 1000T125-43',0:0451 0.1242 1.611 0.563 ',1.92 6,630 1;305 3.431 "0.047..0290 5.886;:.:0.819 .16.19 :822' -_ ,'? - -' -:x,0.362.,0.973 0.3790,259 3A84.0.088 10DOT125-54 0.0566 0.707 2.41 8.333 1.634 3.434 0.059 0.288 7.960 1.216 24.03 '35.19 1628 7.479 1.055 31.59 1628 10.155 0.755 1.212 -0.376 0.256 3.466 0.988 1508 0.372 0253 :-;3470 ;0.969 70007725-68 0.0713 0.890 "3.03. 10.522 '2.053` .3.438 :0.073 0.100 .Ot?86 0.280 10.452: 15.077 1.781 2.907 5744 ;`3261:; 8843 :1575 .-07:75 .''3261 15.077 2.753 82.42 9507 .9.515, 4.375 2.123 0.363 0.247 3.477 0.989 1000T125.97 10007125-116 0.1017 0.1242, 1.269 4.32 -. ;x5.27 15.077 2.912`. 3.447 18:471 ; 3.540;,.3 453 '0118 -_ 0.276 - - 18.471, '3 535 .105.85 "16235 7966 , 2.558 0.35? 0243'' 9 482 0.990 1000T150.43' 0.0451 - ,1.549 0.586 1.99 7.207 1.419 3.507 .' 0.080 0.370 6.195 0.837 16.54 822 - 32:29 1628:; 0.397 1.612 0.513 0.345 3.564 0.979 0 785 :2;013 "0.509 342.3 567 :'D:980 10007150-54 : 0:0566 _" 0.735..2.50 .' 9.061 1.777:. 3511 .; '0100 ,0.368 ; '8.430 -1.249_:;24:69 , 1628. 7.880 ; 1079 , _ „70 1.569 2.522 0.505 0.339 3.571 0.960 1000T150.68 - 0.0713 0.926 3.15 11.445 2.233 3.516 0.124 0.366 11.342 1.846 `3.165 36.48 3261 10374 1.621 48.53 3261 16413 '"2.902 '86;90 9507 41;50 0.495 .'3.579' 0.981 10007150-97. 0:1017 1.320 .'4.49 16:413 -3.17P „ 3.528',0.171 0.360 16.413 _ '62.54 .8843 20121 3.852 115._32 16235 ,3:557 ,. -0332 8.285 4.307 0.488 0.328 3.585 0.982 1DOOT150.118 0.1242 1.611 5.48 20.121 3.857 3.534 '8:361 "3.640 0.204 0.356 ' ' - 0 661, ';17.01 822 '0;426 3:540 0.813 0 534 3 769 0.953 t000T2003' '0.0451 0.631 -,: 2.15 " - '-1,646 --3.645--0-.228--0.537- 0183 .'0.539 6.722' -9.231 -1.295 --25-.60--1628- B 560 1111 33.26 1628 0 841.434 0 809 0.531---3.772 0.954 1000T200=54 10007200-68 0.0586" 0 0713; D.792 0.997 2.69-IG.-516--2.062 ti 3 39 x3:292 2 594 3 651 "'0 284 .. 10.534,, 12 551;. 1.936 , :38.26 ;, 326;:,', 11.820 _:_1.684. 50:42 , 3261 :' 115 1690 5576 ' 0 E03 „ 0 527 _.:3776 10,955 1000T200-97 0.1017 1422 4'.84 , • 19.087 3.686 3.664 0.397 0.528 19.031 3.427 67.7-2 8843 18.683 3.081 92.25 9507 23 422 ;:+1206 125:99 16235-` 4.901 7.924 -0.791 0.519 3.786 0.956 8 924 9.649 0.7 83 0 514 3 793 0.957 10007200=118 ,0.1242' 'f 736 '., 5 91 s 23;422 „'4:489 „ 3 674 =-0 476..0.$24, , 7.172 . 0.376 822 0.458 6,477 -1:147­10.7373.987 0.917 1000T250-43' 0.0451 10007250.54 0.0566 0.676 0.648'` 2.30 2 89 9.515 1.873 3.752 , ` 17:972 2.34$ 3577.:0 0.344 0.713 429 `0.711 , 9 913 ; 1326 _17.32 ' 26 20 ',1628 9141 , ::_1132. 33:89 - 1628 0 9106 , ,8125 ,1142 , 0 734 „3 990, 0:918 t 000T250-68 ., 0.0713 1.068 3.64 15.138 2.954 3.764 0.536 -0.708 0.702' 13.578 20.671 1.997 s 3596 39.46 3261 12.708 1.726 51.68 3261 20.254.,3201 95;84 9507;< 1.811 10.240 4.135 0.730 3.995 0.919 5252 „0721 ,-4.005 9.921 10007250-97 1000T250-118 , fld017 0.1242 1523.:` 1.860 518 6.33 '21y760 4:203 -3780 26.723 5.122 3.791 ,..;0751.,, 0.905 0.698 26.538 4.721 .7.1.05,"8843' 93.29 13189 „ 25.721 4.422 132.38 16235 ,-14617 ,.,1.122 9.562 17.858 -1.112 0.715 4.012 0.923 120OT125-54' 0.820 2.79 13.335, . 2:186 ,4.033 -:,0.060, -:0:271 , 122964;1491 29.471- 1354. 11.460, .286 38.51 , 1354 0.876 7:,,,1;82.0 ,.,=0:333 - 0.230- ,4.055-- 0:993 0.993 1200T125-68 .0.0566. 0.0713 1.033 3,51 - 16.826 2.747 4.036 0.074 0.268 16.246 2.206 43.60 2713 15.686 1.934 1 .157.90 2713 1.750 2.270 -0.329 0.227 4.059 120OT125.97 0.1017 1.472 " 5,01 24.078 .3.897 .4.044 ;_0.102 9.263 24.078; '3.690 ,72.92 , 7902 , 23.751 , 3.442 103:06 7902, 5 076 ..-3171. ._ 0 ®22 0.222 '4.065 ' 0.994 1200T125.118 0.1242 1.798 6.12 29.472 4.740 4.049 0.121 0.260 - 29.472 4.490 134.44 14434 9.243 3,812 -0.316 0.218 4.070 0.994 12007150.54' '.0.0566 0.848 2.89 14.378 " 2:357 4117 ;:0103 1,,0.348 '12.962. « 1.530. , 30.23 - 1354 ' 12.020 ."1313 _:39:31 1354;; 0 906.w 3 033 , OA54, 0 310 56 0.988 1200TI50.68 0.0713 , 1.068 3.64 , , 18.148 2.963 4.121 , 0.127 0.345 17.568 2.281 45.08 2713 "; 7902 16.566 1.987 59.48 2713 `:.3.616 F' 10827 ` 7902' 1810 3 795 0 450 0 307 4160 0.988 5 252 335 -0.441.,4168 12007750.97 0.9017';, 1.523 ' 5.18 SMT-`4 .206 4130 0176 ° 0;340 , 25.987; 3 996 ., 78 97 :'25.719 31825 4 865 145 66 14434 -,`5 9 562 6 444 0 435 0 296 4173 0.989 1200T150-118 0.1242 12007200:54' 0.0566 1.860 " 0.905 6.33 3 OS 31.825 5.119 4.137 0.210 :16 464 2.699. " 4 265 " 10.236 0.336 A:510 , 14.OZ8,, 1.5$2 "31.26 '1354 .. 12:962 ;,1350 „40:41 , 1354 "', 0 966 , ,>3 714 ` =0.730 0,407 120OT200-68 0.0713 1.140 3.88 - 20.791 3.395 4.271 0.294 0.508 19.277 2.383 47.09 2713 18.026 2.058 61.62 2713 1.931 8.431 -0.725 0.483 4.362 0.972 f Web be, ratio exceeds 200. Web stiffeners are required at all support points and concentrated loads. 'Allowable moment includes cold work of forming. 'Where web helgh t -to -thickness ratio exceeds 260 or flange width -to -thickness ratio exceeds 60, effective propertles are not calculated. See AISI 5100 Section BI. Application of these products in a non -composite design shall be approved by a design professional. See Table Notes on page 15. .... � e BmX001 10007200E 0.00 ASTM A570 Grade 33 N001 N002 19 60 dRigi digi Normal (2 -way) Beam 8 Nodal Su orts Nbde .,.. -`Flx DX. .0Eix.DY [.. Fik DZ ,. F.ix.RJ(," �.» �.., .. FIX RY, , .x'^ : < W FIS Z Y Yes yes Yes No N001 Yes es N002 No Yes Yes No No No _ .. Load Cases Load Case ^: Y„ • ., h[fe'sf"n,Ch"ebks;i eismrT e.,..-'-: =fie�U)(s'', ...aAnal •., i D -NA--NA-.... -. Yes Yes Yes Yes No No 23 W+Y. _Np,_ -NA- 34 .6D+.6W s+Y Allowable ASD -NA- 35 Allowable ASD -NA- Yes Yes Yes To. No No No .6D+.70i 36 D+.6H ASD -NA- Yes Yes Yes No we 37 D+.6W a+Y Allowable ASD -NA• -NA- Yes Yea Yes 30 D+,75 L+.6W+Lr s+Y Allowable ASD 39 Wind s+Y Defl.'W or Yea . Yes No Nodal Extreme Reactions Nbde FX FY fZ ri rMSi Ib ,�, , ,..Iti. , z,J. Ib R.du�: >, .,, 16 k'' M,,;,,lb,m •,." ,._ N001 M 0.00 7 ,. 35 0.00 1 0 00 1 0.00 'I -NA-,� 0.00 1 NA - .. N001 0.00 7 14A 5.66 23 0.00 1 N002 -NA, 0.00 1 0 1 00 -NA- -NA' -NA- -NA- _NA- �r► (. -NA- 969.74 23 0.00 I 1 -NA- (Ic) = Load Case index, shown in'Load Cases' or'Result Cases' table. n Member Stresses ,MEmberr Si -.�.,.._ ...-.- -" sf sf ',PST, -BmX001 0.00 ,. 0.00 3793669.90 -3793670.60 A.00 0.00 204477.33 0.00 Design Group Results Design Group: CFS Beam X G01 per 2012 NAS/US ASD Designed As: 1000S200E6, Material: tSteeMSTM A570 Grade 33 Stron Deflection Cheek Offset Code Details Member Result; " Cases ft Ref:„ I Chity eck Name IBC 1604.3.1 BmX001 Wind s+Y 9.41 0.49 OK Axial+Flexure Check 1 Member Result , Offset Code Unity Details - .Name Case :: ft Check , Page 2 Page 1 - W-81Ana1ysis 12.00.0019(wxa¢kswe6.com) VisualAnalysis 12.00.0019 (w ieS_b.00m) p _ CRANDALL ENGINEERING SHEETF 0 5448 Merrill Mill Road Mariposa, CA 95338 JOB NO.li021b Phone: 209-966-4844 DATE: JCI 7,( /(4p mj- L... � i��l..� G y Cpl- � O,�G�"t � a� •�;, rl 45 i E� CRANDALL ENGINEERING SHEET OF 5448 Merrill Mill Road JOB NO. (COO VP%!:' i Mariposa, CA 95338 Phone: 209-966-4844 DATE: a E �rD� --------------- t2/10 Screw capacities Table Notes 6. Pull-out capacity is based on the lesser of pull-out capacity in 1. Capacities based on AISI S100 Section E4. sheet closest to screw tip or tension strength of screw. 2. When connecting materials of different steel thicknesses or 7. Pull -over capacity is based on the lesser of pull -over capacity for tensile strengths, use the lowest values. Tabulated values closest to screw header or tension strength of screw. assume two sheets of equal thickness are connected. sheet 3. Capacities are based on Allowable Strength Design (ASD) and 8. Values are for pure shear or tension loads. See AISI Section E4.5 include safety factor of 3.0. for combined shear and pull -over. Where multiple fasteners are used, screws are assumed to 9. Screw Shear (Pss), tension (Pts), diameter, and head diameter 4. have a center -to -center spacing of at least 3 times the nominal are from CFSEI Tech Note (F701-12). diameter (d). 10. Screw shear strength is the average value, and tension strength assumed to have a center -of -screw to edge -of -steel is the lowest value listed in CFSEI Tech Note (F701-12). 5. Screws are dimension of at least 1.5 times the nominal diameter (d) of the 11. Higher values for screw strength (Pss, Pts), may be obtained by screw. specifying screws from a specific manufacturer. �it;E '. - !' G'$ "'�M;M. - j'SLE64Y�.f � 4 •S1 � 1ZSerew a d, 55 _ 38 102 57 105 159 .''110 Weld Capacities Table Notes 1. Capacities based on the AISI S100 Specification Sections E2.4 for 6. Transverse capacity is loading in perpendicular direction of the fillet welds and E2.5 for flare groove welds. length of the weld. 2. When connecting materials of different steel thicknesses or 7. For flare groove welds, the effective throat of weld is -- -tensile-strengths,zasethe lovvestvalues, --------------. - -- - - -conservatively -assumed to -be less than 2t:- 3. Capacities are based on Allowable Strength Design (ASD). 8. For longitudinal fillet welds, a minimum value of EQ E2.4-1, 4. Weld capacities are based on E60 electrodes. For material E2.4-2, and E2.4-4 was used. thinner than 68 mil, 0.030" to 0.035" diameter wire electrodes 9. For transverse fillet welds, a minimum value of EQ E2.4-3 and may provide best results. E2.4-4 was used. 5. Longitudinal capacity is considered to be loading in the direction 10. For longitudinal flare groove welds, a minimum value of of the lenath of the weld. EQ E2.5-2 and E2.5-3 was used. !Weld capacity for materia/ thickness greater than a zu requires ....... •-> -• • - --. -- - - - ...t'5� �-i�;;-`-moi- �, � wry � ..,s�. �4x�+--,.-a. r'^z ,� '''' 2330IsPts - 13251bs) (Pss 304bsPts 3201166), % L � �a i:_y, d { �raFG�aR alcness E �esig�eld: Tens[le , _ ; Pss:`643;Ibs Pts9lbsj, (: Ew .(Pss 1278,IbS�Pts 386IbS) (Qss�L6441s,pts 1181bsj;IPss p 0 27 "Head 0110: dia,r03FrAmad 0 16& 340 1�ead � � "M 9250 tlia, 0409 Heid Y, ]711115: �Thicknes3 [ksl). lks ;' F 0138 1a; 0 272 Hea 0'164 dia R a..�,s. .€ N _ "- Shear 'Pull Out Pu11Over "Shear •Pu11-Out• Pub -Over ^Shear;' Pull-Out`>Pull•Over Shear ;Bull -Out Pull Over ,Shear-Pu11=0uC PUK-Over �it;E 44 24 ` 84 48 29 84 52 33 105 127 89 43 127 96 50 -- .159 55 _ 38 102 57 105 159 .''110 60 44 127 ', '.66 18 0.0188 33 33 27 0.0263 33 33 33 :82 37 95 40 140 103 48 140 111 55 175 18& 63 175 73 211 30 0.0312 33 83.. 0.0346 33 ;. 45 151 61 , „140 c X64:,. 72 195 177 ,. • .84 , ; 265 ,, 95 280 124 265 ,; 345 .;203 110 .318... 302 144 415 . 43 0.0451 33 45 ' 214 79 `:':214 100 140 244 94 195 263 109 345 140 ",144 ' ; >'116 195 t 370 =__ 137 ''= 386 -, 394-' `;156 ;433 -. '` t24 180 - 521.' 's 54 "- 0.0566 -33 '` , 45 : 68 0.0713 33 45 214 125 , 140 426 149 195 523 173 386 " `• 548 a '' = 557 196 - 777 =:280 545 ' 775. 600 227 656 1j016 ".324 " :,936' -, 97 0.1017 33 •45 • , 214 140 '140 426 ° 195 195.' .246 .386 140 426 195 195 548 301 386 _ 777 342 775 1613 396 1,067 118 0.1242 33 45 54-, 0.0566 50 65 214 140 " 4, .:.140 140 426 r J71 ;. -6195 534=; . 196 366 ` '. 569. ;` 225 625 ., 775 261 752 666 328 948 68 0.0713 50 65 214 140 -140"" 140 426 195 195 548 249 386 ••-140 " 42 ---195` -'-195- 54$ 356 386' 777 284 - 777 -4 5 „ 775 - Ibi6 t68 1067v 140 140 426 195 195 548 386 386 777 494 775 1,016 1 572 1,067 118 0.1242 50 65 214 Weld Capacities Table Notes 1. Capacities based on the AISI S100 Specification Sections E2.4 for 6. Transverse capacity is loading in perpendicular direction of the fillet welds and E2.5 for flare groove welds. length of the weld. 2. When connecting materials of different steel thicknesses or 7. For flare groove welds, the effective throat of weld is -- -tensile-strengths,zasethe lovvestvalues, --------------. - -- - - -conservatively -assumed to -be less than 2t:- 3. Capacities are based on Allowable Strength Design (ASD). 8. For longitudinal fillet welds, a minimum value of EQ E2.4-1, 4. Weld capacities are based on E60 electrodes. For material E2.4-2, and E2.4-4 was used. thinner than 68 mil, 0.030" to 0.035" diameter wire electrodes 9. For transverse fillet welds, a minimum value of EQ E2.4-3 and may provide best results. E2.4-4 was used. 5. Longitudinal capacity is considered to be loading in the direction 10. For longitudinal flare groove welds, a minimum value of of the lenath of the weld. EQ E2.5-2 and E2.5-3 was used. !Weld capacity for materia/ thickness greater than a zu requires ....... •-> -• • - --. -- - - - COMPLIANCE FORMS AND WORKSHEETS Construction Waste Management (CWM) Plan Note: This sample form may be used to assist in documenting compliance with the waste management plan. Project Name: Job W: Project, Manager: Waste Hauling Company: Contact Name: All Subcontractors shall comply with the project's Construction Waste Management Plan. All Subcontractor foremen shall sign the CWM Plan Acknowledgment Sheet Subcontractors who fail tocomply with the WasteManagement Plan will be subject to backcharges or withholding of payment, as deemed appro- priate. For instance, Sul.vontractors who contaminate debris boxes that have been designated for a single material type will be subject to back -charge or withheld payment, as deemed appropriate. 1. The project's overall rate of waste diversion will be— %. 2. This project shall generate the leastamount of waste possible by planningand ordering carefully, following all proper storage and handling procedures to ireducchroken and damaged materials and reusing materials whenever possible- The majority of the waste that is generated on this jobsite will be diverted from the landfill and. recycled for other use, 3. Spreadsheet 1, enclosed, identifies the waste materials that will begenerAted on this project, the diversion strategy foreach waste type is the anticipated diversion rate. 4. Waste prevention and recycling activities will be discussed at, the beginning of weekly subcontractor meetings. As each new subcontractor comes on-site, the WNIPCoordinatorwill present him/her with a copy ofthe CWM Plan and provide a tour of the jobsite to identify materials tobesalvaged and the Procedures for handling jobsite debris. All Subcontractor foremen will acknowledge in writing thatthey have read and will abide by the CWM Plan. Subcontractor Acknowledgment Sheet enclosed. The CWM Plan will be posted at the jobsite trailer. S. Salvage: Excess materials thatcannot be used in the project, nor returned to the vendor, will be offered to site workers, the owner, ordonated to charity if feasible. 6. IHAULING COMPANY] will provide a commingled drop box at the jobsite for most of the construction waste. nese commingled drop boxes will betaken to [Sorting Facility Name and Location]. The average diversion rate for commingled waste will be %.Assitecondi- tions permit, additional drop boxes will be used for particular phases of construction► (e.g., concrete and wood waste) to ensure the highest waste diversion rate possible. 7. In the event that the waste diversion rate achievable via the strategy describe[/ in (6) above, is projected to he lower than what is required, then a strategy of source -separated waste diversion and/or waste stream reduction will be implemented. Source separated waste refers to jobsite waste that is not commingled but is instead allocated to a debris box designated. for a single material type. such as clean wood or metal. Notes: 1. Waste stream reduction refers to efforts, taken by the builder to reduce, the amount of waste generated by the project to below four (4) pounds persquare foot of building area. 2. When using waste stream reduction measures, the gross weight of the product is subtracted from abase weight of four (4) pounds per square foot of building area. This reduction is considered additional diversion and can be used in the waste reduction percentagecal- culations. R. tliAULING COMPANY] will track and calculate the quantity (in tons) ofall waste leaving the project and calculatethe waste diversion rate for the project. [HAULING COMPANY] will provide Project Manager with an updated monthly report on gross weight hauled and the waste diversion rate being achieved on the project. [HAULING COMPANY's] monthly report will track separately the gross weights and diver- sion rates for commingled debris and foreach source -separated waste stream leaving the project. In the event that [HAULING COMPANY] does not service any or all of the debris boxes on the project. the [HAULING COMPANY] will work with the responsible parties to track the material type and weight (in tons) in such debris boxes in order to detennine waste diversion rates for these materials. 9. In the event that Subcontractors furnish their own debris boxes as part of their scope of work. such Subcontractors shal I not be excluded from complying with the CWM Plan and will provide [HAULING COMPANY] weight and waste diversion data for their debris boxes. 10. In the event that site, use constraints (such as limited space) restrict the number of debris boxes that can be used for collection of designated waste the project Superintendent will, as deemed appropriate, allocate specific areas onsite where individual material types are to be consoli- dated. These collection points are, not to be contaminated with non -designated waste types. IL Debris from jobsite office and meeting rooms will ben eo] lected by [DISPOS Al.. SERVICE COMPANY]. [DISPOSAL SERVICE COM- PANY] will, at a minimum, recycle off -ice paper, plastic, metal and cardboard. 64 2013 CALIFORNIA GREEN BUILDING STANDARDS CODE COMPLIANCE FORMS AND WORKSHEETS Construction Waste Management (CWM) Worksheet Note: I his sampte form may he used to assist in documenting compliance with the waste management plan. Project Name: Job Number: Project Manager: Waste Hauling Company: Construction Waste Manag gent (CNVNI) Plan n PROJECTED COMMINGLED AND SORTED OFF SITE SOURCE SEPARATED ON SITE DIVERSION RATE Asphalt Concrete, Shotcrete Metals Wood Rigid insulation Fiberglass insulation Acoustic ceiling the Gypsum drywall Carpet/carpet pad Plastic vim Plastic buckets Plastic Hardiplank siding and fxxirxis Glass Cardboard Pallets Job office trash, paper, glass & plastic bottles, cans, plastic Alkaline and rechargeable batteries, toner cartridges, and electronic devices Other: Other: Other: Other: 2013 CALIFORNIA GREEN BUILDING STANDARDS CODE 65 COMPLIANCE FORMS AND WORKSHEETS Co . nstruction Waste Management (CWM) Acknowledgment Note: This sample form may be used to assist in documenting compliance with the waste management plan. Project Name: job Number: Project Manager: Waste, Hauling Company: CWM Plan Acknowledgment The Foreman for each new Subcontractor that comes on site is to receive a copy of the Construction Waste Management. Plan and complete this Acknowledgment Form. I have read the. Waste Management Plan for the project; I understand the goals of this plan and agree to follow the procedures described in 'S 7 this plan. A kf� FI MR 65 2013 CALIFORNIA GREEN BUILDING STANDARDS CODE t7 . Y Q g •W I' 9 5.403.3 EXCAVATED SOIL AND (AND CLEARING DEBRIS. ,13sq 100 percent of trees, stumps, rocks grid associated vegetation and soils resulting primarily from land clearing shaft be reused or recycled. For a phased ptoirct; such material may be stockpiled on site until the storage site is devefo e , Elccepifoa: L euse; edheron or 4-s a, of vegetabon or soil c6ntaminatad by disease or nest infAstatiori. f Y _ t If CMilafr7l[,atl�rn L7k.` QK@a d3[ pet rft.� arv!�t it Suspo led— Cori act the�CautstY Ag:turL`urat • Commissmar and follow its direction for recycling or disposal of the material 7 ":For a map of know post and/or disease quarantine zoneg consult web the Cehfomia DppaMnent of Food and Agriculture, (wnvw-odfa ca gov):-• SECTiON,5.410 BUILDING MAINTENANCE AND OPERATIONS 5.410.1 RECYCLING BY OCCUPANTS. Provide readily accessible areas that serve the entire building and are identified. for the depositing, storage and collecbm of non -hazardous m.ateAals, for'recyciY+g, including (at a mmerium) Paget; Corrugated oaidbeard, glass, plasties and metals or meet lawfully enacted locat recycling ordmanea, d mote restrictive _ ; 5 410:1.1 Additioets (Aj Alt add tions conducted within a 12 -month period under single or m0ple, pP^rr4s: resulting Jr, an increase of 30% or more in floor aro*, shah provkfel recycling areas on sle Exception' Additions within a tariart space resulting in less than a 30% increase in the tenant sir -4,e floor area: SA".1.2 Sampte, ordinance. Space allocation forrecyctirtg areas shall comp% with Chapter 18, Bart 3, DvdsvIm 30 of the Pubtfc Retofrrres f4de. Chapter D a known as the Gekfom a 3o1id Waste Reuse and Recyc Iirg Access Act of 1991' (Actj ' , " . :.. t Adhesives, adheSlVe P „ - -, 1111-1-1-11— ' w.r•5 n'ttT� • _. 1 - - _ .. DOndng pnrners RdheSlve primers: sealants, sealant pnmr rt: and CeUMta Shall - L_ Comply xnh local or iegktnal a!C po:tuf 0A Corttraf Or airqual.lY managerrien tTsttict rtrt2s what BITUMINOUS ROOF PRIMERS350 epplit&Ne, orSCAOMD Rule 1160 VOC 11mds, as shown in Tables 5 504 41 and 5 504 4 ' , 2 Such BOND BREA1ERS 350 . products also Shad Comply with the Rule' 1168 prohihinon on the use of Certain toxic compounds (chloroform, ethylene dichtori fe, methytene chtoride, peteMomethirl" and trtchloroethytene), except fa CONCRETE CURING COMPOUNDS aerosol products as sWi" in subsection 2, below CONCRETE(MASOflRY SEALEIRS 100 i 2` Aerosol adhesNes, and smaaet' writ saes of adhesives,, and sealant or Catdki ca `'_ ._ :, _ ' . ,, z • . , °. ng mpost of fm '. DRIVEWAY SEALERS writs of poduct loss Packaging which do rtd>T vp 50 �J � _ gfi rrare than one pound and do not consist of rnora' , than 16 fluid ounces) Shap comply with stateutde VOC standards and otherrAquimmetits Including, DRY FOG COATINGS c, pnohibibOris an use of certain toxic co 150 r with 9oction 94507mPOi'rtds of Caklarrrie Code ofRrguleta�s, Title iT, commencing 50 FAUX FINISHING OnAT1NG5 , _ _ " ;; :', • : ' ` ... .. _ _ , , .. • - - .., - <.. .. • _ . • • :- . - .:_ .:; . . r . ' '=' •. .. ... ,,; -, manuat • .' .• .:: _ . r : ' , -, � - ' ..' _ . .-. . , . , - ,- , . � - `: : c ; _ x .. , .. - , , • .. ,: .. „ :, ,. ,.' , r: .,. e .. ., _.. ; _ +. ` . •.' , t ,. : , _ <. :• _ ,, ,. ,, r : , .. , c :_ ;_ ,: •. , .:.. , .. , , .. n i .. .. .. i : ,. .. `:..- .., r :x - 5.504:4. ADHESIVE L(MITr� .Com FIRE RESIST COAT GS 350 ., 54 .10.2.4 Functional performance iestMg.AFunctional pedo[nere rests iii demonstrate are contact instaltation t , and operation of each cnmaxhert. system itis s stem�o-. st in Y� Y 'tY ertt interface in aocordatSce wrLh ttte approved . : pp vat plans and specifications, Funo5onai porfarmance tis repOrLtc shaC contain nMormation a b^g dustm ng : ';, "each of the t>dtrkltr+g cpmsx>nents tested, the toong utikz a irx i ng rid kt4e any read and ad shnerts made, : , . N . _... .::.. _ .41 ,, 5 0.2.3 Doe end trafntirxy �vj A Systems Manual and stems frons. TraiMn " Sy Chhera g are Irgitsed, Including Oacupatbmat Safety and f�alth Act' OSHA 7 itemerts n Cafiftrr * +; ) requirements rile Code of Fiegrtlatiorts (CCR). � ilii 8 Sect t 4 iot15 2, and or►te[rerated regulations-; � S�4f®1A i Syssems man�1. (N} Documentation of the operational a of the building shall to 9 completedMASTiC within the systems rnarivat and �lelrvrxed to the buadi owner sire -- etrtabve" The ng t� systems manual shatltnCiude°tthefaMawhg , I- Sits, intormatwn, tnctudnng mit description' histo edit wire dYhistory current .. Z:' Sdecontact into-rmathon 3. Base operations and maintenance, including general aaoperaxg prodedtr tiesisPRETREATMENT tfrwbteshoobng; raconrrthended trztintenance requirements, site everts bg: ,; 4 Maar systems.' S 5. , de r ! n „_ .. equ Pnrien Mn1e tory and ma�tenanca notes: '. _ . , 6 : A of vnrAatans •- SPY required by ttw enrorcmg ancY or tl�a code: _, ..SEALERS 7 > Other resources andciocumentabon #a ticatae PP 5.410.2.51 S ms o rations Yin iNi A progrAmfor training of the a*opnate maintenannce staff far each equipment typo arifYar system shad be developed and documented in the fog 1 . the cammssianin refo4rt and s'ag mrequrpmenfovetviaw{whatdis,Naktdoes and Atthat oMestema+d/oreq iPon'tit It ntaaces). 2 Review ' a ixdderno+istratan of servaarrgfpreventNe maintenance. Review of the information in the ems Manual anual 4 Review of the red record drawings on the systgmiequ m . � ::. 5-410.2.6 Commtsslon{rrg report A reportaf comrrdssam s atitvdidrs u. ng purees undertaken through fie desrgri,: :': construction phases :I i Dh the txr. d ng project shah be completed an Dro, rep d provided to the owner or representative, , , .. .... Guidance on implementation and enforcement of commissioning �ntai ncd'dng sample Compliance forms to fates may be found in A rep Y pperhdtt AS, Division A6.1, of this code: 5 10,4 TESTING AND ADAIS T + TRIC Testing and a iprs.mg of system shall be red for butt w rigs less than 10,001) square feet or new s tents to serve an addition Ys ion or eltaratprt subject to Section 303 1. ,- SAICA S toand:.. 1 y= rrn, Develop a written of ..,..urns fortesbn t>�r g adlrr_stmg systems Systeme to be irtC included for testing and adjustng_ shaft ncttxie at a mnmwrm, as applicable the prplrstt t , HVAC stem an systems 4 contrite '- - : Indoor 2 r,door and outdoor bgl+ and controls. 3 Water hieng Sysfems. • 4.Renerbieenetgio systems, S Landscape Mngatan systems, 6.Water rouse systems. 5.410.4.3 Procedures. Perforin tech -and a ng djusting pmeedures an accordance with manulacturer's > IxMifitatrons and applicable standards on each s _ Ystem sFIBERGLASS , _ 5.410,4.S.f HVAC bila In addition to testing an ad' flcilly. g d luKmg, before a TIBJN SpeC9-CObditgRit)Q SyStenl .. serving a building or space i9 operated for nommt use. , the -system sn all be balanced in accordance with the procedures defined the Testing Adjusting and B P by 9 1 n9 Balancing Bureau Nat anal Standards; the Notional EnvirnnarentalBalancingBureau Procedural Standards; AsstfdatedAeBatance(bunCiNatfonaf dards Stan oras approved t>! the aMorcing agency, 4� ' `" _ 5.410.e.4 Reportln0. Ager completion of testing,�9 and balancing provide a final report of testing signed by the individualresPonsibie for performing these services, paraUen and matMenanee (O 3 P , +:: • Less Water and Less Exemptin Grartte; Ldet :: , .. FLOW caanNGs - _100 ARCHITECTURAL APPLiCAT10N9 CURRENT V r'iT OC LIMIT' FCf2M RELEAS_ OOMR7t1tdL?S 250 - IfdpOORCARPETACHESNES. 50 - ` GRAPHIC ARTS COATINGS SIGN PAINT : , ( Si 500.,_ - PET PAD 50 TEhffrERATURE COATINGS, '4?0..,. ..: ., ., OUTDOOR CARPET ADFfESNES, _ 1 50.. '. _ s INDUSTRIAL MAINTENANCE tit , COA IGS ,. � 2.50 WOOD GORtNc a . ,.. FL ADHESIVES Loa t , IOW SC>L DS COATNrGSe120, _ RUBBER0 BE�Ti FLOOR MAGNESITE CEMENT COATINGS'_ SUBFLOOR ADHE..SNES 50 TEXTURE COATINGS 100 , CERAMIC TILE AD1iESNES 65 METALLIC PIGMENTED COATINGS 500: _ VCT B ASPHALT ADFESNES MULTICOLOR COATINGS , 250 - DRYWALL &PANELADHESNES 50 PRET T RFA MENT WASH PRIMERS 420 , , - CONE F3ASE ADHESNES 50 PRIMERS: SEALERS & UNDEftCCk17ERS _ 100 MULTIPURE'CSECONSTRtICTtONADHESNES 70 . REACTIVE PL-NETRATING 350 - , .. STRUCTURAL GLAZING ADHESIVES - t00 RECYCLED COAT ING3 SINGLE -PLY ROOF MEMF?i?ANEAtJHESNES 250 1200E COATINGS 50 D 50include FClLi5T OTHER ADHESIVES NO7:SPE IIAYSyse 0RUST PREVENTATIVE GS 25 SPECIALTY APPLGA70N SHELLACS , ; ,. PVC WEL.OING „ -< 51a . '. CLEAR 730 , CPVG VLELDiNG 490 OPAQUE 550 A BS WELDING 3�5 .. SPPRIMERSr t CIALTY SFALERS 8 UNDERCOATERS 1{l0 :. , - , :, "... ,..... PLASTIC CEMENT V\£LDtNG ?50 STAINS 250 ADHESIVE PRIMER FOR PLASTIC STONE CONSOLIDANT 5 : 450 CONTACT ADHESIVE _ � SWIMMING POOL . 340 SPECIAL PURPOSE CONTACFADHESIVE 250 TRAFFIC MARKING COATINGS 100 , T 5 RUCTU RAL WOOD MEMBER ADHESIVE140 .. , T L$ $ Ttl_E R.EF,NISN COAT .. 420 TOP S TRIM A DNEStVE 250 _ WAT ERPROOFING MEMBRANES ?50 `: SUBSTRATE SPECIFIC APPLICATIONS _ COAT!NGS 275 TMETAL 30 , WOOD hREeERVAMETL TNES PLASTIC FOAMS 50 - 33540 ZINC-RK-PR1DEtS POROUS(EXCEPT WOOD) 50 I: GRAMS OFGER LITER OF COATING,'XCLUDING WATER6EJ�T O" MPO1tD$VOP„ THE SPECIFIED R£nc4}NI f : NEFECTUNLESaREtrISEDUMIT3ARE i LISTED W 3li�EQt:£MCOtUM!dS IN THE t E ABLE ` W000 3Q:" .- 80 - 3. VALUES IN THIS TRPLE APE DERIVED R T VEU FROM FK3SE SPECIFIED BY THE CAUf-0RNtANR RESOURCES BOARD.. ARCHITECTURAL COATINGS SUGGEST E'D CONTROL MEASURE FEB. i zona- MORE INF' INFORMATION IS AVAILABLE FROM THE A!R RE�'KIYIRCES BOARD. , 1. IF AN ADHESIVE IS USED TO BON DI D DISSIMILAR SUBSTRATES TOGETHER. _ THE AFHES NE WITH THE HIGHEST VOC CONTENT SHALL BE ALLOWED ' 2 FOR ADDITIONAL MFOR AT M KNJ REGARDING METHODS TO A+IFA9l1RE THE VOC CONTENT SPECIFIES? IN THiS TABLE_ SEE SOUTH COAST Ai R QUALITY MANAGEMENT DISTRICT RULE 1168, re+ wwarbca.povlGROF3lSGcxlFriiTMLrt2t169.PDF . 5.504.4:E1 W irykatian. �enSc n oho of cort�iiance with this section shalt be provxted at the est of fhqu the enfnrc- nig agency. Documentation may include, buts not limited to, the iodic 1, Manufacturer's product specdreatton 2. `:f1ek1 verification of product contaahers tMj rovide ttie bu lding owner or representative with detailed operating and maintenance instructions and copies of Qua raMres/warranties for each system. O 8 M instructions shall be consistent with OSHA requirements in CCR, Trite 8, Sedan 5142, and other related ' . ` reputations 5.410A.S.1 tnspectfons and reports. Include a copy of of inspection verefrCabons and reports required �: '•: , by, the enforcing agency. DIVISION 5,5`; ENVIRONMENTAL QUALITY 1711, M' SECTION 5.501 GENERAL 5.501.1 SCOPE, The provhsons of this chapter shag'outtine means of reducing the quantity of at contaminants that are odorous, irritating, and/or harmful to the comfort and voe8 being of a building's srrdakrs, occutroms and •1. neighbors. . 0 � .:SECTION 5.502 DEFlNiTiONS ; © 5.502.1 DEMOTIONS. The following terms ani defined in Chapter 2 {and are included here frriaterenc¢) © fin \ COMMUNITY NOISE'EQUIVALENT LEVEL KN@4 A metric stmi�rto the day ni9lhf average soun4 levet {Ldn); except that a 5 decibel edtustment Is added to the equivaietd continuous sound exposure level for evening hours (7pn to 10pn) in addition to the 10 d8 nighttrrne adjustment used in the Ldn" © 0 COMPOSITE MOOD PRODUCTS. Compos2[a wood products include hardwood plywood particleboard and medium density fiberboard. `Compoede wood products` does not Include hardboard, structural plywood, structural perils, r structural composite lumber. oriented strand board, glued lartiztated timber, tirnbw. p i bricated wood i -•gists or finger=jointed lumber, aH as sPeeftid in California Code of Regulations (CCR), Title 17, Sed bon 93120.1{a} No1r: See CCR, 7711017, Section 931201,: P1 5' MrIlty: t=ihar mi.ii,.— pie. TABLE 5.504,4.2 - SEALANT VOC LIMIT Less Water and Less Exempt Compounds in Grams per Lier SEALANTS CURRENT VOC L9VnT ARCHITECTURAL ' 250 MARINE DECK 760 NONMEMBRANE ROOF 300 ROADWAY : 250 SINGLE -PLY ROOF MEM81ME 450 OTHER 420 SEALANT PRIMERS ARCHtTFCTURAL NONPOROUS 250 POROUS 775 MODIFIED BITUMINOUS 500 MARINE DECK ltd OTHER 750 TABLE 5.504,4.2 - SEALANT VOC LIMIT Less Water and Less Exempt Compounds in Grams per Lier SEALANTS CURRENT VOC L9VnT ARCHITECTURAL ' 250 MARINE DECK 760 NONMEMBRANE ROOF 300 ROADWAY : 250 SINGLE -PLY ROOF MEM81ME 450 OTHER 420 SEALANT PRIMERS ARCHtTFCTURAL NONPOROUS 250 POROUS 775 MODIFIED BITUMINOUS 500 MARINE DECK ltd OTHER 750 3 ,F-1 El F-1 F-1 (E) PANEL H o 7YP .— — o ISTI G �r AGE ARE 0 _ STOP o EM�I • �G I ❑ TYP#O HF -1 5-10 9u❑ # El S ��- I IL - ig v ��o E -X I eTNG- I ARN- ELECTRIC',AL PLAN E: 1 011 SCALE: /8 = I ELECTRICAL 5YMBOL5 �. o QD 15 OR20AMP 125Y DUPLEX RECEPTACLE @ +181 LINO �,��, 12204206 d wo . AWMAIN FF 166 15 OR 20 AMP 125V 6f-10 DUPLEX RECEPTACLE ® IS LINO� � � � il�� 5 51N6LE POLE TOGGLE SWTIGH , ®+46N UNO A 5W/ AOE El 5WR HH ,0H „ .�JNGTION BOX SIZE � TYPE A5 INDICATED OR REQUIRED �H,,,,,,, d� .! ,-1 v ITEM ITEM ti' El/ DISCONNECT SWITCH L16/57,HTS H � ERMIT # L ®A PANELOATYRPDE MOUNED AS NOTED ON PANEL SCHEDULE 1 � � BUTTE COU N TY DEVEOPMENT SERVICES g00 I AL REVIEWED FORREGSPTAGLES20 I CODE COMPLIANCE Ii O.� q LIGHTS 20 I I 500 '780 15 2G I TE_ 0 FLUORESCENT. OR L.E.D. LIGHT FIXTU RE - SURFACE OR PENDANT MOS iNTED SPACE 780 S Jij 2g62 12 40 2 HP REGENCY LIGHT WITH BATTERY BACK UP 510E MOUNT LAMP HEX6 0 14 Date 10/21/16 .1060 860 5842 5362 LOAD 13224/208 63.6A GU MEGHANIGAJ. EQUIPMENT DE516NATION / MOTOR 1002 6222 X 1259 = -141.5A TOTAL —�, Scale 1/511 CONDUIT RUN CONGEALED BELOW FLOOR OR FINISHED 6RAVE CONDUIT CONCEALED IN WALL OR CEILING HONERUN TO RESPECTIVE PALL OR TERMINAL GABIt�i — UNDERGROt SND HOMERIJN TO RESPECTIVE PANEL OR TERMINAL CABINET OVERHEAD DENOTES # OF WIRES. NO MARKS = 2-#12,1/2' G; CURVED HATCH DENOTES 61ROUND W IRE. WIRE SIZE INDICATED WIN OTHER THA #12. YVP YVATHERPROOF EXISTING LIGHT FIXTURE SCooHEDULE TfPE MAWJFAG'MZER GATAL06 NUMBER DESCRIPTION WATTS LUMENS MOUNTINb A MAXLITE LED UTILITY WRAP LIGHT WITH LSU48065U50DY50(MS) BUILT-IN MOTION DETECTION CEILING � 4123 5URFAGE LED EMERGENCY LIGHT W/BATTERY 2.1 _ WALL Em E-GONOLIGHT E-XMLIRGW g,4GK UP +S � V , k F-1 (E) ELECTRICAL - PANEL EX 15T 1NG 5TOIRA6E , IS RETURN S X 16 TY P OF 4 �li� 5fi' I RADUCT L G 14 10 .aa ❑ F -1F-1 iiiiiiiiiiiiiiii X I-5TNG --BARN EGU I PMENT 50EL7 L =G -I . G�ZZI � � M#�34G11�060600 INDOOR ��N COIL, L HORIZONTAL I N ATTIC ����, I �5 LAS, I X50OFM 208/2 / 5011 I PH 5 4HP FAN MOTOR "7 5MGA, 15 AMP CIRCUIT A I TROUT ELECTRIC HEAT STRI P5, Yell TH 8 i< A EAT STR I P5 44.1 MIN. AMP5 45 AMP MAX. CIRCUIT. 5 DUCT TO OUT51 DE FOR FRE5H AIR. Date 10/21/16 # HP—I: CARRIER M 25HGG548A005, 208/23011 1PH, 28.5 MOA, 40 AMP MAX. CIRCUIT. OUTDOOR MEAT 46 500 +MEATI NG OAPAG I TY 15.00 5Et=R Scale 1/8 = PUMP GON17�1�.� I NG UNIT, 4,500 BTU GOOL I NG G���G I TY, , 5. H5FF, 260E�7 L�3. - 5 REFRIGERANT L I N�5. 55 X 55 50. UNIT. . /8 X 5 / .. A M / Ir -- A. PROJECT GENERAL INFORMATION Conditioned Storage at Patrick Ranch Museum § 140.1 Page 2 of 19 2nd 1. Project Location (city) Durham S. Standards Version Compliance2015 2. CA Zip Code 95938 9. Compliance Software (version) EnergyPro 6.8 3. Climate Zone 11 10. Building Orientation (deg) (E) 98 deg 4. Total Conditioned Floor Area in Scope 1,600 ft2 11. Permitted Scope of Work ExistingAdditionAndAlteration S. Total Unconditioned Floor Area 3,200 ft2 12. BuildingType(s) Nonresidential 6. Total # of Stories (Habitable Above Grade) 1 13 Gas Type Propane 7. Total # of dwelling units 0 25.7 13.4 12.3 B. COMPLIANCE RESULTS FOR PERFORMANCE COMPONENTS (Annual TDV Energy Use, kBtu/ft z -yr) Conditioned Storage at Patrick Ranch Museum § 140.1 Page 2 of 19 2nd BUILDING COMPLIES 10381 Midway Durham 95938 Calculation Date/Time: 1. Energy Component 2. Standard Design (TDV) 3. Proposed Design (TDV) 4. Compliance Margin (TDV) S. Percent Better than Standard Space Heating 36.2 16.3 19.9 55.0% Space Cooling 29.0 37.6 -8.6 -29.7% Indoor Fans 32.4 34.5 -2.1 -6.5% Heat Rejection ❑ Prescriptive NRCC-PRC-01/ 03-E • NA - El Performance S3 section of the NRCC-PRF-01-E Pumps & Misc. ❑ Prescriptive NRCC-PRC-01/04-E N NA - ❑ Performance S4 (section of the NRCC-PRF-01-E) Domestic Hot Water 23.2 23.2 - 0.D% Indoor Lighting 25.7 13.4 12.3 47.9% COMPLIANCE TOTAL 146.5 125.0 21.5 14.7% Receptacle 12.9 12.9 0.0 0.0% Process - Heating: §140.5 - - Other Ltg NRCC-PRC-06/07/08-E N ❑ - TOTAL 159.4 137.9 21.5 13.5% Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 2 of 19 2nd Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Pumps & Misc.: Check mechanical Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx 7th C. PRIORITY PLAN CHECK/ INSPECTION ITEMS (in order of highest to lowest TDV energy savings) 1st Space Heating: Check envelope and mechanical P B P Compliance Margin By Energy Component (from Table B column 41 Space Heating u�ww�assmewx..waa Indoor Lighting Heat Rejection Pumps & Misc. Domestic Hot Water Indoor Fans Space Cooling y, , / CON/. 2nd Indoor Lighting: Check lighting 3rd Heat Rejection: Check envelope and mechanical 4th Pumps & Misc.: Check mechanical 5th Domestic Hot Water: Check mechanical 6th Indoor Fans: Check envelope and mechanical 7th Space Cooling: Check envelope and mechanical D. EXCEPTIONAL CONDITIONS ' The building does not include service water heating. Verify that service water heating is not required and is not included in the design. E. HERS VERIFICATION This Section Does Not APPLY F. ADDITIONAL REMARKS None Provided G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY IdentfY which building components use the performance orprescriptive path forcompliance. NA'= not in project For components that utilize the performance path, indicate the sheet number that includes mandatory notes on plans. Building Component Compliance Path Compliance Forms (required for submittal) ' Location of Mandatory Notes onPlans Envelope ® Performance NRCC-PRF-ENV-DETAILS (section of the NRCC-PRF-OS-E) Yes NA ❑ Prescriptive NRCC-ENV-01 / 02 / 03 / 04 105 / 06-E ❑ NA Mechanical ® Performance NRCC-PRF-MCH-DETAILS (section ofthe NRCC-PRF-OS-E) NVBS72.cibdx ❑ Prescriptive NRCC-MCH-01 / 02 / 03 / 04 / 05 / 06 / 07-E ❑ NA Domestic Hot Water ❑ Performance NRCC-PRF-PLB-DETAILS (section of the NRCC-PRF-01-E) ❑ ❑ Prescriptive NRCC-PLB-01-E N NA Lighting (Indoor Conditioned) N Performance NRCC-PRF-LTI-DETAILS (section of the NRCC-PRF-01-E) ❑ NRCA-MCH-05-A- Air Economizer Controls ❑ ❑ Prescriptive NRCC-LTI-01 / 02 / 03 / 04 / 05-E ❑ NA Covered Process: Commercial Kitchens ❑ Performance S2 (section of the NRCC-PRF-01-E) NRCC-CXR-OS J 02 / 04 / OS -E ❑ Prescriptive NRCC-PRC-01/ 03-E • NA Covered Process: Computer Rooms El Performance S3 section of the NRCC-PRF-01-E Electrical: §130.5 ❑ Prescriptive NRCC-PRC-01/04-E N NA Covered Process: Laboratory Exhaust ❑ Performance S4 (section of the NRCC-PRF-01-E) ❑ ® ❑ Prescriptive NRCC-PRC-01/ 09-E N NA G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY '- The following building components are only eligible for prescriptive compliance. Indicate which are Thefollowing building components may have mandato ryrequirements per Part 6. Indicate relevant to the project. which are relevant to the project. Yes NA Prescriptive Requirement Compliance Forms Yes NA Mandatory Requirement Compliance Forms ExistingAdditionAndAlteration Lighting (Indoor NVBS72.cibdx • NRCI-MCH-01-E - For all buildings with Mechanical Systems Commissioning: §120.8 ❑ 171 ❑ NRCC-LTI 01 02 03 04 OS -E ❑ Simple Systems NRC -CXR-01 02 03 05-E ❑ NRCA-MCH-05-A- Air Economizer Controls ❑ Unconditioned) 4140.6 ❑ NRCA-MCH-06-A- Demand Control Ventilation ❑ ❑ ® Complex Systems NRCC-CXR-OS J 02 / 04 / OS -E ❑ ® Lighting (Outdoor) §140.7 NRCC-LTO-01 / 02 / 03-E ❑ ® Electrical: §130.5 NRCC-ELC-OS-E ❑ ® Lighting (Sign) §140.8 NRCC-LTS-01-E ❑ ® Solar Ready: §110.10 NRCC-SRA-01 / 02-E ❑ NRCA-MCH-13-A- Air Handling Units and Zone Terminal Units ❑ ❑ ❑ NRCA-MCH-14-A- Distributed Energy Storage ❑ ❑ Covered Process: §120.6 NRCC-PRC-01-E ❑ NRCA-MCH-16-A- Supply Air Temp Reset Controls ❑ ❑ ❑ NRCA-MCH-17-A- Condensate Water Temp Reset Controls ❑ ❑ N Parking Garage NRCC-PRC-02-E El ® Solar Thermal Water NRCC-STH-01-E ❑ ® Commercial Refrigeration NRCC-PRC-05-E ❑ Heating: §140.5 Photovoltaic ❑ ® Warehouse Refrigeration NRCC-PRC-06/07/08-E N ❑ ❑ ❑ ® Compressed Air NRCC-PRC-10-E Metal 25 NA ❑ N Process Boilers NRCC-PRC-11-E n I i i i CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at. 2016-11-0413.46•15 _A Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version. NRCC PRF Ol E 08122016 3995 Report Generated at. 2016-11-04 13.46.15 CA Building ldmg Energy Efficiency Standards 2013 Nonresidential Compliance Report Version:n. N CC PRF Ol E-08122016 3995 Report Generated at. 2016-11 041 :46:15 C BuildingngEnergyEfciencYStandards- 20 3 Nonresidential Compliance e Report Version: NRCC-PRF-01-E-08122016 3995 Reportort Generated at: 2016-11-04 13:46:15 L i Project Name: N NRCC-PRF-OI-E Page 6 of 19 Compliance Forms (required forsubmittal) Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 ❑ i I ExistingAdditionAndAlteration I i i i CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at. 2016-11-0413.46•15 _A Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version. NRCC PRF Ol E 08122016 3995 Report Generated at. 2016-11-04 13.46.15 CA Building ldmg Energy Efficiency Standards 2013 Nonresidential Compliance Report Version:n. N CC PRF Ol E-08122016 3995 Report Generated at. 2016-11 041 :46:15 C BuildingngEnergyEfciencYStandards- 20 3 Nonresidential Compliance e Report Version: NRCC-PRF-01-E-08122016 3995 Reportort Generated at: 2016-11-04 13:46:15 L i Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-OI-E Page 6 of 19 Compliance Forms (required forsubmittal) Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 ❑ Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx • NRCI-MCH-01-E - For all buildings with Mechanical Systems F INSTALLATION CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY NRCI NRCA NRCV - H. CERTIFICATE O ( / / ) Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify). See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment. Confirmed Confirmed Building Component Compliance Forms (required forsubmittal) Pass Fail Envelope •NRCI-ENV-O3-E- For all buildings ❑ ❑ N NRCA-ENV-02-F- NFRC label verification for fenestration ❑ ❑ ❑ NRCI-PLB-03-E - Single dwelling unit systems in high-rise residential, hotel/motel application. ❑ • NRCI-MCH-01-E - For all buildings with Mechanical Systems ❑ ❑ N NRCA-MCH-02-A-Outdoor Air ❑ ❑ N NRCA-MCH-03-A-Constant Volume Single Zone HVAC ❑ ❑ ❑ NRCA-MCH-04-H- Air Distribution Duct Leakage ❑ ❑ ❑ NRCA-MCH-05-A- Air Economizer Controls ❑ ❑ ❑ NRCA-MCH-06-A- Demand Control Ventilation ❑ ❑ ❑ NRCA-MCH-07-A-Supply Fan Variable Flow Controls ❑ ❑ Mechanical ❑ NRCA-MCH-08-A- Valve Leakage Test ❑ ❑ ❑ NRCA-MCH-09-A- Supply Water Temp Reset Controls ❑ ❑ ❑ NRCA-MCH-10-A- Hydronic System Variable Flow Controls ❑ ❑ ❑ NRCA-MCH-1I-A-Auto Demand Shed Controls ❑ ❑ ❑ NRCA-MCH-12-A- Packaged Direct Expansion Units ❑ ❑ ❑ NRCA-MCH-13-A- Air Handling Units and Zone Terminal Units ❑ ❑ ❑ NRCA-MCH-14-A- Distributed Energy Storage ❑ ❑ ❑ NRCA-MCH-15-A-Thermal Energy Storage ❑ ❑ ❑ NRCA-MCH-16-A- Supply Air Temp Reset Controls ❑ ❑ ❑ NRCA-MCH-17-A- Condensate Water Temp Reset Controls ❑ ❑ ❑ NRCA-MCH-18-A- Energy Management Controls Systems ❑ ❑ ❑ NRCV-MCH-04-H- Duct Leakage Test ❑ ❑ H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV) - Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify). See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment. Confirmed Confirmed Building Component Compliance Forms (required for submittal) Pass Fail S. Number of Floors Above Grade ❑ NRCI-PL13-01-E - For all buildings with Plumbing Systems ❑ ❑ ❑ NRCI-PLB-02-E - required on central systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCI-PLB-03-E - Single dwelling unit systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCI-PLB-21-E - HERS verified central systems in high-rise residential, hotel/motel application. El 11Plumbing ❑ NRCI-PLB-22-E - HERS verified single dwelling unit systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCV-PLB-21-H- HERS verified central systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCV-PLB-22-H - HERS verified single dwelling unit systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCI-STH-01-E- Any solar water heating ❑ ❑ Indoor Lighting 0NRCI-LTI-01-E- For all buildings ❑ ❑ ❑ NRCI-LTI-02-E - Lighting control system, or for an Energy Management Control System (EMCs) ❑ ❑ ❑ NRCI-LTI-03-E - Line -voltage track lighting integral current limiter, or for a supplementary overcurrent protection panel used to ❑ energize only line -voltage track lighting ❑ ❑ NRCI-LTI-04-E -Two interlocked systems serving an auditorium, a convention center, a conference room, or a theater ❑ ❑ ❑ NRCI-LTI-OS-E -Lighting Control Credit Power Adjustment Factor (PAF) ❑ ❑ ❑ NRCI-LTI-06-E - Additional wattage installed in a video conferencing studio ❑ ❑ ❑ NRCA-LTI-02-A- Occupancy sensors and automatic time switch controls. ❑ ❑ ❑ NRCA-LTI-03-A- Automatic daylighting controls ❑ ❑ ❑ NRCA-LTI-04-A - Demand responsive lighting controls ❑ ❑ Outdoor Lighting ❑ NRCI-LTO-01-E- Outdoor Lighting ❑ ❑ ❑ NRCI-LTO-02-E- EMCS Lighting Control System ' ❑ ❑ ❑ NRCA-LTO-02-A-Outdoor Lighting Control ❑ ❑ Sign Lighting ❑ NRCI-LTS-OI-E-Sign Lighting ❑ ❑ Electrical ❑ NRCI-ELC-01-E - Electrical Power Distribution ❑ ❑ Photovoltaic ❑NRCI-SPV-01-E Photovoltaic Systems ❑ ❑ H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCI/NRCA/NRCV) - C recognized r compliance Documentation Author to indicate which Certificates must be submitted for the features to be recognl d fo (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify). See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms b equipment. P Y Confirmed Confirmed Building Component Compliance Forms (required forsubmittalJ Pass Fail S. Number of Floors Above Grade ❑ NRCI-PRC-01-E Refrigerated Warehouse ❑ ❑ Covered Process ❑ NRCA-PRC-01-F- Compressed Air Systems ❑ ❑ ❑ NRCA-PRC:-02-F- Kitchen Exhaust ❑ ❑ ❑ NRCA-PRC-03-F-Garage Exhaust ❑ ❑ ❑ NRCA-PRC-04-F- Refrigerated Warehouse- Evaporator Fan Motor Controls ❑ ❑ ❑ NRCA-PRC: 05-F- Refrigerated Warehouse- Evaporative Condenser Controls ❑ ❑ ❑ NRCA-PRC-06-F- Refrigerated Warehouse- Air Cooled Condenser Controls ❑ ❑ ❑ NRCA-PRC-07F- Refrigerated Warehouse- Variable Speed Compressor ❑ ❑ ❑ NRCA-PRC-08-F- Electrical Resistance Underslab Heating System ❑ ❑ 1. ENVELOPE GENERAL INFORMATION (See NRCC-PRF-ENV-DETAILS for more Information) Dry System Equipment' (Fan & Economizer info included below in Table N) Confirmed 1. 2. 1. Total Conditioned Floor Area 1,600 ft2 S. Number of Floors Above Grade 1 This Section Does Not Apply , Confirmed 2. Total Unconditioned Floor Area 3,200 ft2 6. Number of Floors Below Grade 0 20. V d 3. Addition Conditioned Floor Area 1,600 ft2 4. Addition Unconditioned Floor Area 0ft2 7. Opaque Surfaces & Orientation 8. Total Gross Surface Area 9. Total Fenestration Area 10. Window to Wall Ratio North Wall Roofing Product Description 207 ft2 0 ft2 00.0% ❑ ❑ East Wall 2. 760 ft2 0 ft2 00.0% ❑ ❑ South Wall NA 207 ft2 0 ft2 00.0% ❑ ❑ West Wall Continuous R -Value 0 ft2 oft, 00.0% ❑ ❑ Total 640 1,174ft, Oft, 00.0% ❑ ❑ Roof ❑ 1,600 ft2 0 ft, 00.0% , ❑ ❑ J. FENESTRATION SUMMARY Dry System Equipment' (Fan & Economizer info included below in Table N) Confirmed 1. 2. 3. I § 140.3 § 110.6 1. This Section Does Not Apply , 3. 4. S. 6. 7. 20. Product Type Product Density (Ib/ft) Aged Solar Reflectance K. OPAQUE SURFACE ASSEMBLY SUMMARY SRI Cool Roof Credit Roofing Product Description N d R-25 Roof Metal Rafter14 § 120.7/ § 140.3 .08 Confirmed 1. 2. 3. 4. S. 6. 7. S. NA No Surface Name Surface Type Area (ftz) Framing Type Cavity R -Value Continuous R -Value U -Factor / F -Factor / C -Factor ; � N T R-19 Wall Metal Stud8 ExteriorWall 640 Metal 19 NA U -Factor: 0.191 N ❑ ❑ R-13 Wall Metal Stud10 ExtedorWall 534 Metal 13 NA U -Factor: 0.229 N ❑ ❑ R-25 Roof Metal Rafter14 Roof 1600 Metal 25 NA U -Factor: 0.070 N ❑ ❑ Slab On Grade16 UndergroundFloor 1600 NA 0 NA F -factor: 0.730 N ❑ ❑ R-0 Metal Building Wa1118 ExteriorWall 2510 NA 0 NA U -Factor: 0.565 E ❑ ❑ R-11 Metal Building Roof29 Roof 3200 NA 11 NA U -Factor: 0.139 E ❑ ❑ Existing Grade32 UndergroundFloor 3200 NA 0 NA F -Factor: 0.730 E ❑ ❑ ,Status: N -New, A-Ahered, E-ExBting - 1 L. ROOFING PRODUCT SUMMARY Dry System Equipment' (Fan & Economizer info included below in Table N) Confirmed 1. 2. 3. I § 140.3 Confirmed 1. 2. 3. 4. S. 6. 7. 20. Product Type Product Density (Ib/ft) Aged Solar Reflectance Thermal Emittance SRI Cool Roof Credit Roofing Product Description N d R-25 Roof Metal Rafter14 4.20948 .08 .75 NA No NA ❑ ❑ R-11 Metal Building Roof29 2.54281 .08 .75 NA No NA ❑ ❑ M. HVAC SYSTEM SUMMARY (see NRCC-PRF-MCH-DETAILS for more information) I § 110.1 / § 110.2 Dry System Equipment' (Fan & Economizer info included below in Table N) Confirmed 1. 2. 3. 4. S. 6. 7. 8. 9. 10. 11. 19. 20. 21. 22. System Type 24. Total Heating Supp Heat Supp Heat Total Cooling Efficiency N Acceptance Testing g V d N d - Equip Name Equip Type s (Simple or Qty Output Source (Y/N) Output Output HP Required? (Y/N) N CFM CFM HP BHP Complex 4) Control (kBtu/h) HP (kBtuh) (kBtu/h) s 500 0 a Cooling Heating HP -1 SZHP (SpIit3Phase) Simple i 47 Yes 27 46 SEER-15.0/HSPF-8.7 NA Yes N ❑ ❑ No N 1 ❑ ❑ 1.43 ConstantVolume NA NA EER -12.5 NA NA NoEconomizer ❑ ❑ O a•+ i nl S _i V Project Address: J 10381 Midway Durham 95938 - Y i O 14. O a•+ ! CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version. NRCC-PRF-01-E-08122016-3995 Report Generated at. 2016-11-0413.46.15 -4 Building Energy Efficiency Standards_ 2013 Nonresidential Compliance Report Version. NRCC PRF Ol E 08122016 3995 RepoGenerated at. 2016 11 04 13.46.15 CA Building Energy Nonresidential Compliance ReportVersion: NRCC PRF OSE 08122016 3995 Report Generated at. 2016 11 04 13.46.15 CA Building Energy 2013 Nonresidential ntial Com liance Report Version. NRCC PRFO3 E-081220 6 3995 Reportort Generated at. 2016-11-04 13:46:15 00 U Project Name: 1 Conditioned Storage at Patrick Ranch Museum g NRCC-PRF-01-E I Confirmed Project Address: J 10381 Midway Durham 95938 - Y i O 14. ! CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version. NRCC-PRF-01-E-08122016-3995 Report Generated at. 2016-11-0413.46.15 -4 Building Energy Efficiency Standards_ 2013 Nonresidential Compliance Report Version. NRCC PRF Ol E 08122016 3995 RepoGenerated at. 2016 11 04 13.46.15 CA Building Energy Nonresidential Compliance ReportVersion: NRCC PRF OSE 08122016 3995 Report Generated at. 2016 11 04 13.46.15 CA Building Energy 2013 Nonresidential ntial Com liance Report Version. NRCC PRFO3 E-081220 6 3995 Reportort Generated at. 2016-11-04 13:46:15 00 U Project Name: 1 Conditioned Storage at Patrick Ranch Museum g NRCC-PRF-01-E Page 10 of 19 Confirmed Project Address: J 10381 Midway Durham 95938 - Y Calculation Date/Time: 13:45, Fri, Nov 04, 2016 14. • Compliance Scope. ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx 19. i Wet System Equipment 2 Pumps Dry System Distribution Confirmed 1, 2. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. SZHP No No I v d ❑ Equip Name Equip Type Qty Vol (gal) Rated Capacity (kBtu/h) Efficiency Standby Loss Tank Ext. R Qty GPM HP VSD (Y/N) N CFM CFM HP BHP (inch Control CFM HP Value (inch Control 500 0 a 0 ❑ ❑ or unconditioned) NonReseaseWaterHeater Storage 1 0 0 EF: .675 NA NA I NA NA NA No N 1 ❑ ❑ t Dry System Equipment includes fumoces, air handling units, heat pumps, eta 2 Wet System Equipment includes boilers, chillers cooling towers, water heaters, eta - : - 3 Simple Systems must complete NRCC CXR -03 f commissioning design neviewforni, 4 Com x Systems must complete NRCCCXR-04-E commissioning design review arm .Does the Project Include Zonal Systems?(if Yes„ see NRCC-PRF-MCH-DETAILS for system Information) No _. - �. A summa o which acceptance rests ore applicable is provided m NRCC PRF MCH DETAILS DOCS the Project Include a Solar Hot Water System? if Yes see NRCC-PRF-MCH-DETAILS fors stem information r summary f P PP PY ( rY ) Status. N New A Altered E Exrstrn Multifamily or Hotel Motel Occu an ? if Yes see NRCC-PRF-MCH-DETAILS for DHW stem Information No Y / P cY ( r system ) I Discrepancy between modeled and designed equipment sinng7 (if Yes ,see Table F. Additional Remarks for an explanation) No i P. SYSTEM DISTRIBUTION SUMMARY § 120.4/ § 140.4(t) § 140.4 Confirmed Dry System Distribution Confirmed 1, 2. 3. 4. S. H Outside Equip Name Equip Type Duct Leakage and Sealing Required per 140.4(1) Dud Leakage will be verified per NAI and NA2 Ducts Insulation R -Value Location P-1 SZHP No No 0 Conditioned ❑ ❑ N. ECONOMIZER & FAN SYSTEMS SUMMARY' § 140.4 Confirmed 1. 2. 3. 4. S. Equip Type Controls Outside Supply Fan Return Fan Lighting Control Credits HP -1 SZHP No Economizer Air ❑ (Watts) Economizer Type N �' _ No Optimum Start TSP Area Category Footnotes NonResBaseSHWSystem Service Hot Water, Primary Only Fixed Temperature Control, No DDC TSP ❑ Equip Name (if present) (Watts) CFM CFM HP BHP (inch Control CFM HP BHP (inch Control 500 0 0 0 ❑ ❑ or unconditioned) WC) WC) Building Totals: 11,600 Soo 10 HP -1 240 1600 .721 .721 1.43 ConstantVolume NA NA NA NA NA NoEconomizer ❑ ❑ s Mechanical ventilation calculations and exhaust fins ore included in the NRCC-PRF-MCH-DETAILS section _ O. EQUIPMENT CONTROLS I § 120.2 Confirmed 1. 2. 3. 2. 3. Equip Name Equip Type Controls Occupancy Type z No DCV Controls Installed Lighting Power Lighting Control Credits HP -1 SZHP No Economizer ❑ ❑ (Watts) (Watts) No Supply Air Temp. Control No Optimum Start Area Category Footnotes NonResBaseSHWSystem Service Hot Water, Primary Only Fixed Temperature Control, No DDC ❑ ❑ Q. INDOOR CONDITIONED LIGHTING GENERAL INFO (see NRCC-PRF-LTI-DETAILS for more info)s § 140.6 Confirmed 1. 2. 3. 4. S. Occupancy Type z Conditioned Floor Area , Installed Lighting Power Lighting Control Credits Additional (Custom) Allowance (ft) (Watts) (Watts) Area Category Footnotes Tailored Method (Watts) ❑ ❑ (Watts) Commercial and Industrial Storage Areas (conditioned 1,600 500 0 0 0 ❑ ❑ or unconditioned) Building Totals: 11,600 Soo 10 0 0 See Table 140.6{ See NRCC-LU-01-Efor unconditioned spaces - - BUTTE 'COUNTYDEVELQ-v ENT SERVICESLi Lighting information forexistin spaces modeled is not Included in the table I I .REVIEW ED FOR CODE COMPLIANCE ANCE >1 AT , ^ i D 2 U 1 tt r E l - - BY S_ oject Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 11 of 19 Confirmed Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 12 of 19 Total Number Luminaires oject Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 According to §130.0(c) Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Yes impliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx - Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx 1.6 R. INDOOR CONDITIONED LIGHTING SCHEDULE (Adapted from NRCC-LTI-03-E)t § 130.0 luminaire Schedule (includes all permanent installed lighting in conditioned space, and portable lighting over 0.3 w/ft' in offices) Installed Watts (Conditioned) Confirmed Name or Item Tag Complete Luminaire Description (i.e., 3 -lamp fluorescent troffer, F32T8, one dimmable electronic ballast) Watts per luminaire How Wattage is Determined Total Number Luminaires Installed Watts Pass Fail CEC Default from NAB According to §130.0(c) A 50w LED 50 No Yes 10 500 ❑ ❑ r[ If fighting power densities were used in the compliance model Building Departments will need to check prescriptive forms jo u rm'noire5chedule derails. Si. COVERED PROCESS SUMMARY- ENCLOSED PARKING GARAGES § 140.9 This Section Does Not Apply U. ENERGY USE SUMMARY § 10-103 1 certify that this Certificate of Compliance documentation is accurate and complete 2. Energy Component Standard Design Site (MWh) Proposed Design Site (MWh) Energy Component Standard Design Site (MWh) Proposed Design Site (MWh) Margin MWh (MWh) Standard Design Site MBtu ( ) Proposed Design Site MBtu) Margin (MBtu) Pumps & Misc. - Indoor Fans _ - -0.2 - - Heat Rejection Domestic Hot Water -- - - - 9.9 9.9 0.0 Indoor Lighting 1.6 .8 0.8 - - - COMPLIANCETOTAL 4.8 5.9 -1.1 23.8 9.9 13.9 Receptacle .8 .8 0.0 _ -- -- Process Blom n 0 Responsible Mechanical Designer Name: John Gray - - _ Roof Other Ltg - - Declaration Statement Type: Phone: 530-891-4926 Title: W (tZ License#:C-20405424 Gypsum Board -1/2 in. TOTAL 5.6 6.7 -1.1 23.8 9.9 13.9 - COMMERCIAL KITCHENS 140.9 ED CESS SUMMARY S2. COVER PRO This Section Does Not Apply Y 53. COVERED PROCESS SUMMARY -COMPUTER ROOMS § 140.9 - This Section Does Not Apply - 140.9 SUMMARY LABORATORY EXHAUSTS 4 S4. COVERED PROCESSSU This Section Does Not Apply UNMET LOAD HOURS its Section Does Not Apply U. ENERGY USE SUMMARY § 10-103 1 certify that this Certificate of Compliance documentation is accurate and complete 2. Energy Component Standard Design Site (MWh) Proposed Design Site (MWh) Margin Standard Design Site Proposed Design Site Margin (MWh) (MBtu) (MBtu) (MBtu) Space Heating - 1.4 - 13.9 Space Cooling 1.0 1.3 -0.3 - Indoor Fans 2.2 2.4 -0.2 - - Heat Rejection licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect. ❑ - - DOCUMENTATION AUTHOR'S DECLARATION STATEMENT § 10-103 1 certify that this Certificate of Compliance documentation is accurate and complete 2. Documentation Author Name:. Donna Wallace Signature: g K eE C.0 Company:Donna Wallace O� Address: 399 E. 9th Avenue Signature Dater 11/04/2016 City/State/Zip: Chico CA 95926 CEA Identification (If applicable): 4997: EnergyPro User Number Phone: 530-893-4982 l RESPONSIBLE PERSON'S DECLARATION STATEMENT Pass Fail I certify the following under penalty of perjury, under the laws of the State of California: N R-19 Wall Metal Stud8 I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that 1 am 1 licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect. ❑ I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section 5537.2 or 6737.3 to sign this document as the person iresponsible for its g 2 preparation; and that) am a licensed contractor performing this work. P g Gypsum Board -1/2 in. I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to 8 3 Business and Professions Code Sections 5537, 5538 and 6737.1. ❑ ❑ Responsible Envelope Designer Name: Andy Wood goes Company: North Valley Building Systems Signature: WOs�•D Address: #30 Seville Court Date Signed: ((p City/State/Zip: Chico CA 95928 Declaration Statement Type: Phone: 530-345-7296 Title: License #: - �':'7j Ji Responsible Lighting Designer Name: Jack Thorpe Signature: Company: Agri Electric b W Address: 11011 Midway Date e I City/State/Zip: Chico CA 95928 Declaration Statement Type: Phone: 530-342-42.03 Title: w License #: C-10 443455 Blom n 0 Responsible Mechanical Designer Name: John Gray Signature: Company: Jessee Heating & Air Conditioning, Inc. Roof Address: 3025 Southgate Lane Date Signed: City/State/Zip: Chico CA 95928 Declaration Statement Type: Phone: 530-891-4926 Title: W (tZ License#:C-20405424 NRCC-PRF-ENV-DETAILS -SECTION START- A. TART A. OPAQUE SURFACE ASSEMBLY DETAILS , Conflilmeid 1. 2. 3. 4. d 8 '.. ;U" - Surface Name Surface Type Description of Assembly Layers Notes Area l Metal Siding -1/16 in. Pass Fail Ta or I.D. / g N R-19 Wall Metal Stud8 ExtenorWall Metal framed wall, 161n. OC, 5.51n., R-19 -t Z ❑ ❑ MetalUninsulatedSingleLayerRollupDoor DefaultPerformance NonSwinging Gypsum Board -1/2 in. 1.450 E ❑ ❑ Hollow Metal Door23 MetalUninsulatedDoubleLayerpoor DefaultPerformance Metal Siding -1/16 in. 42 .700 E R-13 Wall Metal Stud10 ExteriorWall Metal framed wail 16in. OC 3.5 in. R-13 , INA O 2 ❑ none specified - 1 b W Gypsum Board -1/2 in. n 70 A V -3 �3 OC Metal Standing Seam -1/16 in. n 0 2 1 -4 O R-25 Roof Metal Rafter14 Roof Metal framed roof, 241n. OC, 9.25m., R-25 2 - ❑ ❑ O w Gypsum Board -1/2 in. CONDITIONED 000 n- r 3 3 IS O D „ o Slab Type - UnheatedSiabOnGrade YP - r3 x 2 -4 j0 NA Slab On Gradel6 UndergroundFloor Insulation Orientation = None ,-t m m ❑ ❑ r < Insulation R -Value = RO ZONE NAME r 2 3? --{ n Metal Siding -1/16 in. n 3� ❑ ❑ R-0 Metal Building Wall18 ExtenorWal) Air- Cavity- Wall Roof Ceiling - 4 in. or more O x g �+ o n. r Metal Standing Seam -1/16 in. ❑ 2 R-11 Metal Building Roof29 Roof Metal screw down roof, R-11 o COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 0 3!,ae 104 1 72 IF : 81 164 IF 55 / 54 IF 55154 IF Slab Type = UnheatedSlabOnGrade o 0v m Vo ExistingGrade32 Under roundFloor g Insulation Orientation = None n� ❑ ❑ �.. -... _.._ ' Equipment Requiring Insulation R -Value = RO .,z Z a 0 a • _ - - - - 4 13:46:15 9 Report Generated at. 2016 11-0 12 1639 5 I _ F-01 E 08 2 0 Report Version: NRCC PR Nonresidential Compliance ante P Efficiency Standards 2013 Nonres M P 1 CA Building Ener ffici P _ PRF Ol E 08122016 3995 Report Generated at. 2016-11-04 13.46.5 g gY cY _ 2 1 Nonresidential Compliance Re ort Vernon. NRCC p _ _ _ _ - CA Building Energy Efficiency Standards 0 3 p P ,• - 2 1 3995. Report Generated at. 2016 11 04 13.46.15 g rgY cY . _ Report Version. NRCC PRF Ol E 0812 0 6 p _ _ dards 2013 Nonresidential Compliance p . .. _ _ _ _ .A Bwldin Ener Efficiency Stan P _ Version: PRF -01 E 08122016 3995 Report Generated at. 2016 11 04 13.46.15 g Energy Y CA Building Energy Efficiency Standards 2013 Nonresidential Compliance Report Vernon p g r8Y cY P 1 . l SIV I C. OPAQUE DOOR SUMMARY O U 1. 2. 3. 4. �m 6. 7. UL i n l Door Type Certification Method W I Area l Status 1 Pass Fail Ta or I.D. / g N 3 a m 0 O -t Z Descriptiono _ I • _ - - - - 4 13:46:15 9 Report Generated at. 2016 11-0 12 1639 5 I _ F-01 E 08 2 0 Report Version: NRCC PR Nonresidential Compliance ante P Efficiency Standards 2013 Nonres M P 1 CA Building Ener ffici P _ PRF Ol E 08122016 3995 Report Generated at. 2016-11-04 13.46.5 g gY cY _ 2 1 Nonresidential Compliance Re ort Vernon. NRCC p _ _ _ _ - CA Building Energy Efficiency Standards 0 3 p P ,• - 2 1 3995. Report Generated at. 2016 11 04 13.46.15 g rgY cY . _ Report Version. NRCC PRF Ol E 0812 0 6 p _ _ dards 2013 Nonresidential Compliance p . .. _ _ _ _ .A Bwldin Ener Efficiency Stan P _ Version: PRF -01 E 08122016 3995 Report Generated at. 2016 11 04 13.46.15 g Energy Y CA Building Energy Efficiency Standards 2013 Nonresidential Compliance Report Vernon p g r8Y cY P 1 . l SIV I C. OPAQUE DOOR SUMMARY Confirmed 1. 2. 3. 4. S. 6. 7. 7. Opaque Door Assembly Name Door Type Certification Method Operation Area Overall U -factor Status 1 Pass Fail Ta or I.D. / g Airflow (dm) 3 a m 0 0 -t Z Descriptiono OH Door21 MetalUninsulatedSingleLayerRollupDoor DefaultPerformance NonSwinging 336 1.450 E ❑ ❑ Hollow Metal Door23 MetalUninsulatedDoubleLayerpoor DefaultPerformance Swinging 42 .700 E ❑ ❑ r -Altered, E-Existin Status: N-New,A g NRCC-PRF-MCH-DETAILS -SECTION START Project Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 16 of 19 Project Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 Compliance Scope: ExistingAdditionAndAlteration Input File Name: NVBS72.cibdx Confirmed C. EXHAUST FAN SUMMARY NRCC-PRF-LTI-DETAILS -SECTION START- This 7ART This Section Does Not Apply D. DHW EQUIPMENT SUMMARY - (Adapted from NRCC-PLB-01) This Section Does Not Apply E. MULTI -FAMILY CENTRAL DHW SYSTEM DETAILS This Section Does Not Apply Y I F. SOLAR HOT WATER HEATING SUMMARY (Adapted from NRCC-STH-01) A. MECHANICAL VENTILATION AND REHEAT (Adapted from 2013-NRCC-MCH-03-E) Confirmed 1. DESIGN AIR FLOWS 2. VENTILATION (§ 120.1) 3. 4. 5. 2 7. v N 3 33y 3 3 Rated Capacity Z 3 Airflow (dm) 3 a m 0 0 -t Z Descriptiono n T (kBtuh) n 2 0 O v Z T? p3 X T 03 v O < O 3 2 ,Om,, O Z ? < INA O 2 1 m none specified - 1 b W b O n 70 A V -3 �3 OC �C n 0 2 1 -4 O Tin C rm 7rZ 2 - �<, O w u CONDITIONED 000 n- r 3 3 IS O D „ o 3 x r3 x 2 -4 j0 NA z p 2 3 i 3 ,-t m m Storage3-TRM 3 Z r < ZONE NAME r 2 3? --{ n 33 n 3� �T 0 K T Z m -a O x g �+ o n. r 1,600 dm ROOM O oNo Do o COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 0 3!,ae 104 1 72 IF : 81 164 IF 55 / 54 IF 55154 IF o 0v m Vo 240 dm Cooling Coil Supply Fan 56154 °F 1,600 dm 46.9 n� 75162 °F 74! 61 IF �.. -... _.._ ' Equipment Requiring # of .,z Z a 0 a 2ct a 2 o x :a 0 nO O m d R s 0 a M n� N T m Testing or units $ 1 -Conditioned HP -1 1,600 NA NA NA NA N HP -1 1,600 NA 3 75.0 240 240 NA N ❑ ❑ Storage z < o f a Q° m TOTAL 4,800 NA - NA NA NA - ❑ ❑ B. ZONAL SYSTEM AND TERMINAL UNIT SUMMARY § 140.4 1. 2. 3. 4. 5. 6. 7. S. Confirmed 3 3 3 Rated Capacity 3 3 Airflow (dm) Fan 3 3 , ma sensor, manual dimming, etc.) Descriptiono n T (kBtuh) n n n n x m n ? System ID System Type Qty Economizer Zone Name N _ n n xTest Confirmed none specified - 1 b W b O ECM O1 V W Heating Cooling 5 Design Min. Ratio BHP Cycles Motor Air System Conditioned Uncontrolled T1 a NA NA NA 1 -Conditioned Storage 1600 NA NA NA NA ❑ ❑ ❑ Storage3-TRM Outside Air % 15.0 1 Total Adjusted System Output - 38,835 (Adjusted for Peak Design conditions) 4,306 55,555 inti Outside Airdm/sgft TIME OF SYSTEM PEAK - Jul 3 PM1 I Jan 1 AM - C 2 C This Section Does Not Apply i G. MECHANICAL HVAC ACCEPTANCE TESTS &FORMS (Adapted from 2013-NRCC-MCH-0i-E) § RA4 Declaration of Required Acceptance Certificates (NRCA) -Acceptance Certificates that may submitted. (Retain copies and verify forms are completed and signed to post infield for Field Inspector to verify). Control Credit Calculation 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 , ma sensor, manual dimming, etc.) Descriptiono n T n n n n n x n n ? n ? n ? n ? n n n n n n xTest Confirmed none specified - 1 b W b O b ut O1 V W o to O 5 W A r N • df a � -4 a DO a Air System a a a a a a a a 28,251 Airflow dmfs n 1.00 a a a 27,304 Airflow dm/ron 404.2 Outside Air % 15.0 1 Total Adjusted System Output - 38,835 (Adjusted for Peak Design conditions) 4,306 55,555 inti Outside Airdm/sgft TIME OF SYSTEM PEAK - Jul 3 PM1 I Jan 1 AM - C 2 C T C Outside Air `^"'"-"•~� n. 96 °F 1,600 dm ROOM O oNo Do o COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 104 1 72 IF : 81 164 IF 55 / 54 IF 55154 IF o 0v Ev 240 dm Cooling Coil Supply Fan 56154 °F 1,600 dm 46.9 n� 75162 °F 74! 61 IF �.. -... _.._ ' Equipment Requiring # of c m 3 < -N :a < O nO O m d � 0 a M n� N T m Testing or units $ Verification D ? H D o4 m m ? v d z < o f a Q° m INonResBase1 - -- -- - - - -- -- - -- -- - - -- - El ❑ SHWSystem HP -1 1 X X - - - - - - - - - - - - ❑ ❑ A. INDOOR CONDITIONED LIGHTING CONTROL CREDITS (Adapted from NRCC-LTI-02-E) § 140.6 Lighting Control Credits Schedule (includes all lighting controls installed in conditioned space for Control Credit Calculation Room Width (ft) Room Cavity Height (ft) Confirmed compliance credit per §140.6(a)2 and Table 140.6-A) NA Y If Acceptance Test Required NA ❑ ❑ Location in Occupancy Type (must meet Type/Description of Lighting Control partial on occupancy # of Units Watts of Controlled Power Adjustment Control Credit 0 0 Building requirements of Table 140.6-A) , ma sensor, manual dimming, etc.) ❑ Lighting Factor Watts ❑ ❑ Pass Fail � Commercial and Industrial Storage This Section Does No tApply ❑ V ❑ ❑ Outdoor Controls 0 ❑ ❑ ❑ ❑ S -1 -Conditioned Areas (conditioned or none specified - 1 11,405 .00 0 - ❑ ❑ Storage unconditioned) Total Output Btuh/s ft 29.7 Total Output s on 404.2 1 37,3351 27,382 C. TAILORED METHOD CONDITIONED LIGHTING POWER ALLOWANCE SUMMARY AND CHECKLIST (Adapted from NRCC-11I-04-E) § 140.6 General lighting power (see Table D) 0 General lighting powerfrom special function areas (see Table E) NA Additional "use it or lose it" (See Table G) 0 Total watts 0 F. ROOM CAVITY RATIO (Adapted from NRCC-LTI-04-E) Rectangular Spaces Room Number Task/Activtty Description Room Length (ft) Room Width (ft) Room Cavity Height (ft) Confirmed RCR Pass I Fail NA NA NA NA NA NA ❑ ❑ Non -Rectangular Spaces This Section Does Not Apply Note: All applicable spaces are listed under the Non -Rectangular Spaces table G. ADDITIONAL "USE IT OR LOSE IT" (Adapted from NRCC-LTI-04E) 1. 2. - 3. 4. Allowed Watts Confirmed Wall Display Combined Floor Display and Task P Y Combined Ornamental and Special P Very Valuable Merchandise v N ,, m This Section Does Not Apply Lighting Effects Lighting v NA NA 0 0 0 0 0 ❑ ❑ U 'L` Q nnc� U 140.6-D Special Effects Lighting ted from NRCC LTI 04E § 7. Combined Ornamental and Sp g g � D. GENERAL LIGHTING POWER (Adapted ) This Section Does Not Apply This Section Does Not Apply O E. GENERAL LIGHTING FROM SPECIAL FUNCTION AREAS (Adapted from NRCC-LTI-04-E) S. Wall Display-� Room Number Illuminance Value Primary Function Area (LUX) Room Cavity Ratioz (Table G) Allowed LPD Floor Area (ft) Allowed Watts Confirmed Pass Fail This Section Does Not Apply NA NA �J v NA NA ❑ I ❑ ❑ ❑ Automatic Time Switch 0 6. Floor Display and Task Lighting P Y g g ❑ n 1 �I Automatic Daylighting 0 ❑ ❑ ❑ (] � Demand Responsive 0 This Section Does No tApply ❑ V ❑ ❑ Outdoor Controls 0 ❑ ❑ ❑ ❑ �1 140.6-D Special Effects Lighting ted from NRCC LTI 04E § 7. Combined Ornamental and Sp g g � D. GENERAL LIGHTING POWER (Adapted ) This Section Does Not Apply This Section Does Not Apply O E. GENERAL LIGHTING FROM SPECIAL FUNCTION AREAS (Adapted from NRCC-LTI-04-E) § 140.6(c) 3H Room Number Illuminance Value Primary Function Area (LUX) Room Cavity Ratioz (Table G) Allowed LPD Floor Area (ft) Allowed Watts Confirmed Pass Fail NA NA NA NA NA NA NA ❑ I ❑ 8. Very Valuable Merchandise V J This Section Does Not Apply '73 Note. Tailored Method for Special Function Areas is not currently implemented _ .. iI H. EVAPORATIVE COOLER SUMMARY .. ;This Section Does Not Apply O ttom`` �� I -i--' � 3995 Report Generated at. 2016-11-04 13.46.15 CA Building Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-i1-0413:46:15 - _ Report Version: NRCC_PRF_01_ _08122016_3995 Report Generated at. 2016-11-0413.46.15 CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version. NRCC-PRF 01 E 08122016 CA Building Energy Efficiency Standards- 2013 Nonresidential al Compliance Report Version: NRCC-PRF -01-E- 8122016-3995 Report Generated at. 2016-11_04 13.46.15 rA Bu. din Energy Standards- Nonresidential Compliance 75 I O O - (1 - oject Name: Conditioned Storage at Patrick Ranch Museum NRCC-PRF-01-E Page 19 of 19 Test Description oject Address: 10381 Midway Durham 95938 Calculation Date/Time: 13:45, Fri, Nov 04, 2016 m )mpliance Scope: ExistingAdditionAndAlteration Input File Name: NVB572.cibdx d _ H. INDOOR & OUTDOOR LIGHTING ACCEPTANCE TESTS & FORMS (Adapted from NRCC-LTI-01-E and NRCC-1.1`0-014) § 130.4 Declaration of Required Acceptance Certificates (NRCA) -Acceptance Certificates that must be verified in the field. (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify). Test Description Indoor NRCA-LTI-02-A NRCA-LTI-03-A NRCA-LTI-04-A Outdoor NRCA-LTO-02-A Confirmed m Equipment Requiring If of units Testing or Verification Occ Sensors /Auto Time Auto Daylight Switch Demand Responsive Outdoor Controls d _ Occupant Sensors 0 ❑ ❑ ❑ ❑ ❑ ❑ Automatic Time Switch 0 ❑ ❑ ❑ ❑ ❑ ❑ Automatic Daylighting 0 ❑ ❑ ❑ (] ❑ ❑ Demand Responsive 0 ❑ ❑ ❑ ❑ ❑ ❑ Outdoor Controls 0 ❑ ❑ ❑ ❑ ❑ ❑ i CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-11-0413:46:15 I HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Date Conditioned Storage at Patrick Ranch Museum 11/412016 System Name Floor Area HP -1 1,600 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 1 COIL CFM Total Room Loads 1,240 Return Vented Lighting Return Air Ducts Return Fan - Ventilation'240 Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COOLING PEAK COIL HTG. PEAK Heating System Sensible Latent CFM Sensible Output Pe S tem 46,500 tte. 24,236 3,200 615 17,403 Total O ut 46,500 0 Output Btuh/s ft 29.11 1,212 870 Cooling System 0 0 Output per System 47,500 7,509 757 240 11,405 Total Output Btuh 47,500 3,167 - -3,167 Total Output ons 4A 1,212 870 Total Output Btuh/s ft 29.7 Total Output s on 404.2 1 37,3351 27,382 Air System CFM per System 1,600 HVAC EQUIPMENT SELECTION Airflow dm 1,600 Carrier Corp. 25HCC548A"30 38,835 4,306 28,251 Airflow dmfs n 1.00 8.0 kW Supplemental Electric 27,304 Airflow dm/ron 404.2 Outside Air % 15.0 1 Total Adjusted System Output - 38,835 (Adjusted for Peak Design conditions) 4,306 55,555 0.15 Outside Airdm/sgft TIME OF SYSTEM PEAK - Jul 3 PM1 I Jan 1 AM Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 25 IF 65 °F 97 IF 97 IF 97 °F Outside Air `^"'"-"•~� 240 dim Heating Coil Aux. Heat Coil Supply Fan 96 °F 1,600 dm ROOM 69 IF 70 IF COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 104 1 72 IF : 81 164 IF 55 / 54 IF 55154 IF "" Outside Air °�^" . ..... 240 dm Cooling Coil Supply Fan 56154 °F 1,600 dm 46.9 ROOM 75162 °F 74! 61 IF �.. -... _.._ i EnergyPro6. by EnergySoft User Number 4997 ID: NVBS72 Page 2f of 2f 7 I G i q �. �, �, i �i, �� - ` _.