HomeMy WebLinkAboutB17-0338 000-000-000United Sun Energy - Solar. Ground Mount - (1) 4 x.9 GM Table at 11.7 kWp with 36 Modules Pie 2 .
Estimate#: 171.0094
F lE
Design Assumptions:
18
Project
Solar Ground Mount
Size of Project
11.7 kWp with 36 Modules
Module
Canadian Solar CS6X-325P with 325 Wp (76.93 x 38.7 x 1.57 inch, 48.5 lbs)
Orientation & Tilt Angle
Landscape at a 21° Tilt Angle
Basic ASCE 7-10 Wind Speed
110 mph (3 second gust)
Wind Exposure Category
C
Snow Load
0 psf
Risk Category
5
Altitude
150 ft above sea level .
Terrain Type
Flat Lot
Mean Table Height
4.08 ft
Size of Table
approximately 13.4 ft x 58.3 ft
t: Distance between Posts,
Front to Back - 7.3 ft, Left to Right - 12.1 ft :.
Total Dead Load
4.45 psf
Seismic Zones/Loads
up to 0.9 g' •
Connection Safety Factor
2.00
Minimum Height Clearance
24"
Ground Connection
The (10) C -Beam at 40.00" ft'steel Sigma Post lengths have been estimated
22
according to information provided and experience with similar ground mount
10
tables. Foundation engineering by a local, qualified P.E. is highly
Code.Compliance
2012 International Building Code (no specific local amendments)
ASCE 7-10, CBC 2013, ADM 2010
Item No. Description
quantity
per Table
Total
Quantityt
173-X060 Top Rail ST -AK 13/60 (14 ft)
18
18
173-XXXX ST -AK 182%120 (58.3 ft)
2
2
173-0061 Splice 182
4
.4
173-0292 Vertical Post - 037" (3' 1'=)
5
5
173-0296 Vertical Post - 077" (6' 5")
5
5
173-0274 Diagonal Strap - 108" (9'0")
5
5
173-0274 Diagonal Strap - 108" (9' 0")
5
5
173-0053 Bearing Block TH
10
10
702-0381 Module End -Clamp 30-50 (Framed); Z
36
40
700-0155 Module Mid -Clamp 30-50 (Framed) w. Bondir
54
60
704-0044 Cross -Adapter; Z (2) -
72
80
173-0009+0016 M10x080 Bolt w. Serrated Flange Nut (SHCS 1
20
22
173-0010+0016 M10x120 Bolt w. Serrated Flange Nut (SHCS 1
20
22
173-0317 C -Beam at 40.00"
10
10
Option Grounding - (9) Weeb-Lugs:
Option End -Caps for 182/120 Rails- (4) End -Caps 182:
S:FLEX Inc. Phone: (303) 522-3974
6565 S: Dayton Street - Suite 3650 Fax: (720)292-1858
Greenwood Village, CO 80111 ' Email: inquiry@sflex.com
}
S:FLEXInc. Phone: (303) 522-3974
6565 S. Dayton Street - Suite 3650 Fax: (720) 292-1858
Greenwood Village, CO 80111 Email: inquiry@sflex.com
q ry@sflex.com
United Sun Energy - Solar Ground Mount - (1) 4 x 9 GM Table at 11.7 kWp with 36 Modules Page 5,
Estimate#: 1710094
@)FLEX
Description Qty
-s 1 Top Rail 18
2
5
5
5
5
10
40
60
.80
22
22
10
1
parts.
SAEX Inc. Phone: (303) 522-3974
6565 S. Dayton Street - Suite 3650 Fax: (720) 292-1858
Greenwood Village, CO 80111 Email: inquiry@sflex.com
United Sun Energy - Solar Ground Mount - (1) 4 x 9 GM Table at 11.7 kWp with 36 Modules Page
Estimate#: 17 10094
)FLEX
jEnd-'-Clamp Installation
?d on Both Sides -
S:FLEX Inc.
6565 S. Dayton Street - Suite 3650
Greenwood Village, CO 80111
Please also refer to the assembly instructions at www.sflex.com.
Phone: (303) 522-3974
Fax: (720) 292-1858
Email: inquiry@sflex.com
i
United Sun Energy - Solar Ground Mount - (1)4 z 9 GM Table at 11.7 kWp with 36 Modules Z
Estimate#: 1710094
FLEX'
S '
ASCE 7-10 Wind Pressure Calculation p = qh G CN
p = the net design pressure for the MWFRFSs of monoslope, pitched roofs
qh = velocity pressure evaluated at mean roof height, h using the exposure categories defined in 26.7.3
that results in the highest wind loads for any wind direction at the site.
G = gust effect factor from Section 26.9 Taken for rigid structures as F 0.85
CN = net pressure coeffient per Fig. 27.4-4 Extrapolated for.tilt angle (see below).
27.3.2 Velocity Pressure. qh 0:00256 KZ.K, Kd V2
Constant at sea level = 0.00256 Altitude of this location: 150 feet (above sea level)
s Correction of coefficient to: 0.00254
'KZ = the velocity pressure exposure coefficient per table 27.3-1 Page 261 for all heights.
For h up to 15', KZ = 0.57 for Exposure Category B, Kz = 0.85 for Category C, and Kz =1.03 for Category D.
KZ for this location
KZL = the topographic factor. Changes according to hill profiles. See 26.8.1. For flat ground, Ka 1.0
Kd = wind directionality. See Table 26.6-1. Structures except chimneys and trussed towers, Kd 0.85
V2 = basic wind speed in mph, squared. Wind speed for this location= 110 Speed
2= 12100
See section 26.5. For Risk Category II buildings and structures - see Fig 26.5-1A. For Risk Category III & IV buildings
and structures - see Fig 26.5-113. For Risk Category. I buildings and structures - see Fig 26.5-1C.
4n = . 0.00254 K: Kz, Kd.V2 = 22.21 psf G =Gust Factor for structure= 0.85
Tilt Angle = 21 Degrees
Wind Case A <--- CN p
CN Look up from Fig. 27.4-4.. Top CNL _. 176 33.22. psf
extrapolated for given'tilt angle. Bottom 4Nw = 1.62 30.58. psf
Pressure, p, experienced by top or bottom Wind Case B <--- CN p
half of rail supporting modules is given by Top CNL = 0.68 12.84 psf
p = qh G CN Bottom CNw' 2.12 40.02.: psf
Wind Case A ---> CN p
Top
CNw = ::
-1.38
-26.05.
psf.
F . Bottom
CNL =
-1.54.
-29.07
psf
Wind Case B
--->
CN
p
Top
CNw =
-2.30
-43.42
psf'
' Bottom -.:
CNL=
-0.24-
-4.53
psf
S:FLEX Inc. Phone: (303)522-3974'
6565 S. Dayton Street - Suite 3650 Fax: (720)292-1858
.Greenwood Village, CO 80111 . Email: Inquiry@sflex.com
3) D + S
Dead and Snow
4:15.
United Sun Energy - Solar Ground Mount - (1)
4 x 9 GM
Table at 11.7 kWp with 36 Modules Page 88
Estimate#: 1710094
1.59
«
S FLEX
D =
4.45
psf
Tilt Angle =
21
degrees
Dy = D cos angle =
4.15
psf perpendicular to module
S =
0.00
psf
Sy = S cos angle =
0.00
psf perpendicular to module
W =
40.02
psf down
W =
-43.42
psf uplift
- Wind =
40.02
psf down
Uplift =
-40.40
psf uplift
Ballasted roof mount:
a
Downforce =13:33
Wind Pressure Case B
psf down
Uplift =
-18.21
psf uplift
Module Wt. = 2.346 psf
psf psf
Combinations of Loads per ASCE 7-10 2:4.1. top rail D,W
3) D + S
Dead and Snow
4:15.
1.59
4) D + 0.75L + 0.755
Dead, Live & Snow
4.15
1.59
5) D+0.6W
Dead, Wind
28.16
1.59
6a) D + 0.75L+ 0.75(0.6W) + 0.75S
Dead, Snow & Wind •
22.46
1.59
6b) D + 0.75L + 0.75(0.7E) + 0.75S
Dead, Snow & Seismic
Wind Uplift Case A
7) 0.6D+0.6W
Wind uplift
-23.56
Nw - 1.76
8) 0.6D+0.7E
Seismic uplift :
41.15 PCF
•
106.50 PLF�
Max. Downward Load = 28.16
Max. Uplift Load = -23.56
Abs Max_. = 28.16 1.59
Wind Pressures for Footing Reactions:
Trib. Width = 3.21 ft
CNw= -2.30
CN = -1.38
.-43.42= psf
-6.05 psf
-139.17 PLF2.
Ct-850PLF 03 N-.2 4
.. � CNS _ -1.54
29.07 psf
-4.53 psf -
-14.52 PLF
-93:19 PLF
Wind Uplift Case A
Wind Uplift Case B ,
..
CNw = 0.68
Nw - 1.76
12.84 psf
33.22 psf
41.15 PCF
•
106.50 PLF�
� . CNS = 2..12 ..
..
1
40.02 psf
CNt = 1'.62 '
128.28 PLF
30.58 psf. •
. .
. 98.03 PLF
a
Wind Pressure Case A
Wind Pressure Case B
Z0F.ESS/p
Dead Load for top rail: ST -AK
13/60 ? ti
A Aq,q
Module Wt. = 2.346 psf
��� �`S
7.519 plf
Top rail wt. = 0.648 plf
=� -m
Total Top Rail Dead Load = 8.167 plf
�: 6.+81 672 m
Roof Snow Load _ 0 psf
d : exP• 06/17
0. plf
,
S:FLEx Inc.
q OF CA1.�Phone: (303) 522-3974
6565 S. Dayton Street - Suite 3650 '
Fax: (720) 292-1858
Greenwood Village, CO 80111
Email: Inquiry@sflex.com
United Sun Energy - Solar Ground.Mount - (1) 4 x 9 GM Table at 11.7 kWp with 36 Modules
}
Estimate#: 1710094 r. :
r
((
• F`E/�i'"
t
r
e�oFESs,o
�SA•A�� 9�Fy
42 ,L t;a
Bearing Block .
Iw o S1672
a a > exp.06l17-
J
Verkal Post .
`r�yTTR CT.U���
FOF,C'gL�F0?
r
r
"
Digitaliy.Signed by
1
:James A. Aloins; S.E.
0"
r
71
Proiect Location: •' f
20"
15"
r" Solar Address
611
54"
"be^,
`
Not shown here is the rebar which should
used according to common pratice.
DIA,24" ,. t
Post Spacing Front to Back '= 7.35
ft (7'4.1)
a
'Post Spacing between braced frames = 12.15
ft (12' 2")
r,-
Maximum Vertical Force per post= 2.91k
^'
..�.
•
r
- ,
MaximumHips
orizontaLForceperpost= 1.12
..
:kips'for•wiridpressure
YVlna praswre
wusin, uplift
Wlna pressure
causl iiannpression
Y.
.;t ..:..
Mazimum'Momentper,post= 24.71kip-in
for wind pressure
1
Maximum Vertical Uplift Force per post= -2.43
•kips
Main uplift
ro•,a
uplltfo
.
• _ " `
Maximum Horizontal Force per post = 0.97
Maximum Moment per ost'= 21.35'
P P
kips for Wind uplift
kip -in in for wind.pressure
P P
ll
compression
ramie. ul
it
Sigma Post Capacity Mxx = 37.71
ki -in!,.-
�
`
Concrete in contact with soils by code must have:aL 3500 psi compressive strength.
` The location's frost depth requirement is 12" (to be verified
by customer):`. • _
,r
S:FLEXInc. 4_ '
_ '.
Phone: (303) 522-3974 '
! 6565 S. Dayton Street - Suite 3650
Fax: (720) 292-1858. .
17 - Greenwood village, e0 80111.
Email: inquiry@sflex.com " r
CLASS OF MATERIALS
VERTICALFOUNDATION
LATERALBEARINO •
PRESSURE
17-ERWIN
CoeMe_Iont Of frlelbM
,
Foundation Design
PRESSURE (Pat)
(pSOk below natural grade)
' Piers
12,000
1,200.
Uplift Check
—
Uplift Max = 2430 # (from RISA)
4,000.
400
Pier Diameter = 2.00 ft.
—
I Sandy gravel and/orgravel(GW
Pier Length = 4.50 ft.
200
0.35
Coh = 130 psf
and GP),
R DL= 2120.58 #
1
R Coh = 3675.672 #
DL + 50% Coh = 3958.416 #
silty gravel and clayey gravel
Use 2.00 dia. X 4.50 long concrete pier
150
0.25
F.S. = 1.63 r
Lateral Resistance
1
d = O.Mj l + [ I + (4.36h/A'2 } (Equation 18-1) page 155
A = 234PI(Sib)
d=
4.55
ft. (Minimum depth of embedment)
A=
3.25
clayey sift; silt and sandy silt
b =
2.001
ft. (pier diameter)
h =
1.67
ft. (dist. From ground to point of app.)
P =
1120
# (applied lateral load)
S 1=
403
psf (two times tabular value) Section 1806.3.4, page 149
202
psf (allowable lateral bearing pressure at 1/3 depth-33% duration increase)
100
psf/ft. (presumptive lateral bearing pressure) Table 1806.2, page 149
Trial d =
4.55
ft. (trial Depth)
Minimum
ft. diameter pier with embedmet depth = 4.55 ft. MIN
2.00
TABLE 1606.2 ' tr
PRESUMPTIVE LOAD-BEARING VALUES
CLASS OF MATERIALS
VERTICALFOUNDATION
LATERALBEARINO •
PRESSURE
LATERAL SLIDING RESISTANCE
CoeMe_Iont Of frlelbM
CoSwon(Pef)*
-
PRESSURE (Pat)
(pSOk below natural grade)
1. Crystalline bedrock
12,000
1,200.
0.70
—
2. Sedimentary and foliated rock
4,000.
400
035
—
I Sandy gravel and/orgravel(GW
3,000
200
0.35
I
—
and GP),
1
4. Sand, silty sardt, clayey sand,
silty gravel and clayey gravel
2000
150
0.25
—
(SW. SP, SM, SC,,GM and G_ C)
1
5..Clay, sandy clay,, silty clay,
clayey sift; silt and sandy silt
1.500
L00
—
130
(CL. A1L; M.H and CH)
For SI:. I pound per square foot = 0.0479kPa; 1 pound per square foot per foot = 0.157 Wa/m.
a. CnWiclent to be multiplied by the dead load.
b. Cohesion 4ohte to be multiplied by the contact area, as limited by Section 1806:3.2.
5