HomeMy WebLinkAboutB17-0374 028-410-045! i Hydraulic Calculations Project Information Project Name: Henderson Residence Date 03/03/17 Address: 40 Coyote Moon Trail File # 22443-1 Oroville, California Index 202 Calculation Area: Garage Design Criteria Occupancy Classification: Residential Construction ® Combustible ❑ Non Combustible Density: - .05 gpm/sq. ft. QRoFESS �o� �EILI y� F• Area of Operation: N/A c+y Area per Sprinkler: 256 sq. ft. max. W FP / 0 1 Number of Sprinklers Calculated: 2 heads '�� F PROTEo�\o \P qrF OF CALIF Hose Allowance Irrigation Allowance 0 gpm inside 30 gpm 0 gpm outside Water Supply Sprinklers Water Storage Tanks . Make: Tyco Cogcealed Pendent w/ 60 gpm @ 40 psi pump Size: 7/16 K=4.9 Temp: 160° Calculation Summary Total Sprinkler Water Flow: 26.5 gpm Flow & Pressure: (at base of riser): 26.5 gpm @ 33.6 psi (at pump discharge): 56.5 gpm @ 36.6 psi Notes: P€MMIT # BUTTE COUNTY DEVELOPMENT SERVICES REVIEWED FOR CODE COMPLIANCE DATE ='�I I �) BY uel �o SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 DATE: 3/3/2017L\40 COYOTE MOON TRAIL - HENDERSON\CALCULATIONS\22443-1.SDF JOB TITLE: 2 Head Calc - Garage WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS: @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) S - (N/A) 40.0 (N/A) 40.0 56.5 36.6 Required pressure is 3.4 psi (8%) less than available pressure. AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 56.5 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 30.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.5 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE• DISCHARGE (FT) (PSI) (GPM)' 1 16.5 K= 4.90 7.0 13.0 2 16.5 K= 4.90 7.5 13.4 3, 17.0 - - - - 7.5 - - - 4 17.0 - - - - 8.5 - - - 5 17.0 - - - - 19.0 - - - 6 17.0 - - - - 20.2 - - - Rl 8.2 - - - - 24.4 - - - R2 5.0 - - - - 26.1 - - - R3 5.0 - - - - 29.1 - - - R4 1.0 - - - - 31.5 - - - R5 -2.0 - - - - 33.6 - - - S -2.0 SOURCE 36.6 26.5 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 3/3"/2017L\40 COYOTE MOON TRAIL - HENDERSON\CALCULATIONS\22443-1.SDF JOB TITLE: 2 Head Calc - Garage PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS),HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -13.0 1.101 PL 13.50 PF 0.7 1 16.5 4.9 7.0 13.0 4.4 150 FTG ER PE -0.2 3 17.0 0.0 7.5" 0.0 0.031 TL 21.50 PV Pipe: 2 -13.4 1.101 PL 0.50 PF 0.2 2 16.5 4.9 7.5 13.4 4.5 150 FTG T PE -0.2 3 17.0 0.0 7.5 0.0 0.033 TL 5.50' PV Pipe: 3 -26.4 1.101 PL 3.50 PF 1.0 3 17.0 0.0 7.5 0.0 8.9 150 FTG T PE 0.0 4 17.0 0.0 8.5 0.0 0.114 TL 8.50 PV Pipe: 4 -26.4 1.101 PL 64.25 PF 10.5 4 17.0 0.0 '8.5 0.0 8.9 150 FTG 5T3R PE 0.0 5 17.0 0.0 19.0 0.0 0.114 TL 92.25 PV Pipe: 5 -26.4 1.394 PL 18.00 PF 1.3 5 17.0 0.0 19.0 0.0 5.6 150 FTG 2ER PE 0.0 6 17.0 0.0 20.2 0.0 0.036 TL 35.00 PV Pipe: 6 -26.4 1.394 PL 8.79 PF 0.4 6 17.0 0.0 20.2 0.0 5.6 150 FTG R PE 3.8 R1 8.2 0.0 24.4 0.0 0.036 TL 9.79 PV Pipe: 7 -26.4 1.291 PL 3.17 PF 0.3 Rl 8.2 0.0 24.4 0.0 6.5 150 FTG R PE 1.4 R2 5_0 0.0 26.1 0.0 0.052 TL 6.17 PV Pipe: 8 FIXED PRESSURE LOSS DEVICE R3 5.0 .0.0 29.1 0.0 3.0 psi, 26.4 gpm R2 5.0 0.0 26.1 0.0 Pipe: 9 -26.4 1.291 PL� 4.00 PF 0.7, R3 5.0 0.0 29.1 0.0 6.5 150 FTG GV PE 1.7 R4 1.0 0.0 31.5 0.0 0.052 TL 13.00 PV Pipe: 10 -26.4 1.245 PL 3.50 PF 0.8 R4 1.0 0.0 31.5 0.0 7.0 150 FTG 3E PE 1.3 R5 -2.0 0.0 33.6 0.0 0.063 TL 12.50 PV Pipe: 11 -26.5 1.590 PL 125.00 PF 3.1 R5 -2.0 0.0 33.6 0.0 4.3 150 FTG 3ET PE 0.0 S -2.0 SRCE 36.6 (N/A) 0.019 TL 160.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 3/3/2017L\40 COYOTE MOON TRAIL - HENDERSON\CALCULATIONS\22443-1.SDF JOB TITLE: 2 Head Calc - Garage NOTES (HASS): (1) Calculations were performed by the HASS 8.6 computer program in accordance with NFPA13 (2016) under license no. 50040231 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0.011 gpm and a maximum imbalance at any node of 0.114 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 8.9 ft/sec at pipe 3. (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report. * (5) PIPE FITTINGS TABLE Pipe Table Name: HOUSE.PIP PAGE: C: MATERIAL: Cppr-K HWC: 150 Diameter,. Equivalent Fitting Lengths in Feet (in) • E -T R L G A V C Ell Tee RunTee 45 -Ell GateVa Ang1Va ChckVa Cping 1.245 3.00 6.00 2.00 1.00 1.00 14.00 6.00 1.00 PAGE: E- MATERIAL: Cppr-M HWC: 150 Diameter Equivalent Fitting Lengths in Feet , (in) E T R L- G A V C' Ell Tee RunTee 45 -Ell GateVa Ang1Va ChckVa Cping 1.291 3.00 8.00 3.00 2.00 1.00 19:00 8.00-' 1.00 PAGE: F MATERIAL: CPVC HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T R L G A V C Ell Tee RunTee 45 -Ell GateVa'AnglVa ChckVa Cping 1.101 7.00 5.00 1.00 1.00 0.00 0.00 0.00 .1.00 1.394 8.00 6.00 1.00 2.00 0.00 0.00 0.00 1*.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 3/3/2017L\40 COYOTE MOON -TRAIL•- HENDERSON\CALCULATIONS\22443-1.SDF JOB TITLE: 2 Head Calc - Garage PAGE: G MATERIAL: PVC 'HWC:• 150 Diameter' Equivalent Fitting Lengths in Feet (in) E T R L G A V C Ell Tee RunTee 45 -Ell GateVa AnglVa ChckVa Cping . 1.590 9.00 8.00 1.00 2.00 2.00. 0-.00 0.00 1.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE:'3/3/2017L\40 COYOTE MOON TRAIL - HENDERSON\CALCULATIONS\22443-1.SDF JOB TITLE: 2 Head Calc - Garage . WATER SUPPLY ANALYSIS Fixed Source Pressure: 40.00 psi 60.0 LEGEND 50.0 " 1 Available pressure 40.00 psi @ 56.5 gpm G 2 Required pressure A 40. C 1 1 36.64 psi @ 56.5 gpm U 2A 2 - G` lA Avail. OnSite Demand Press. E 30.0 40.00 psi @ 26.5 gpm 2A y� Req. OnSite Demand Press. P 36.64 psi @ 26.5 gpm R20.0 A. Source Supply Curve E B. System Demand Curve S C. Available at Source S 10.0 B U 0.0 E ---- — ---- — ---- — ---- — =-- p s-14.7 i 20 30 40 50 60 70 80 90 100 FLOW (GPM) Note: (1) Dashed Lines indicate extrapolated values from Test Results (2) On Site pressures are based on hose stream deduction at the source Consequently, the Series LFII Residen- tial Concealed Pendent Sprinklers of- fer the features of non -water filled pipe in addition to not having to increase, the number of design sprinklers (hy-. , draulic design area) for systems de- A'rX00 4 .. water filled pipe will permit options for areas sensitive to freezing. ` /� PERMIT # V-7 BUTTE COUNTY DEVELOPMENT SERVICES ' REVIEWEDFOR'' ' www.tyro fire com, Cilia A Rapid Response Series LF11 Residential 4.9 K -factor Concealed Pendent Sprinklers, Flat Plate Wet Pipe and Dry Pipe Systems General 'The Series LFII Residential Concealed Pendent Sprinklers (TY3596) has been _ Description designed with heat sensitivity and wa- • ter distribution characteristics proven The TYCO 'RAPID. RESPONSE Se- to help in the control of residential fires h. ries LFII Residential 4.9 K -factor Con- and to improve the chance for occu- cealed Pendent Sprinklers (TY3596) pants to escape or be evacuated.' are decorative, fast response, fus- ible solder sprinklers designed for use The Series LFII Residential Concealed , in residential , occupancies such as Pendent Sprinklers TY3596 are p ( ) shipped with a Disposable Protective: homes, apartments, dormitories, and Cap. The Protective Cap is temporar- hotels. ily removed for installation, and then = WN I The cover plate assembly conceals it can be replaced to help protect the I f the` sprinkler operating components sprinkler while the ceiling is being in --above the ceiling. The flat profile of the stalled or finished. The tip of the Pro- - cover plate provides the optimum aes- tective Cap can also be used to mark _ thetically appealing sprinkler design. In the center of the ceiling hole into plas- - addition, the concealed design of ter board, ceiling tiles, etc. by gently the Series LFII Residential Concealed pushing the ceiling product against The Series LFII Residential Con - Pendent Sprinklers (TY3596) provides the Protective Cap. When the ceiling cealed Pendent Sprinklers, (TY3596) a ' r 1/2 inch (12,7,mm) vertical adjustment. installation is complete the Protective described herein must be installed This adjustment provides a measure of Cap is removed and the Cover Plate and maintained in compliance with flexibility when cutting fixed sprinkler Assembly installed. this document and with the applica- drops. ble standards of the National Fire Pro- The Series LFII Residential Concealed Dry Pipe System Application tection Association, in addition Ito the Sprinklers are intended for use in the The Series LFII Residential Concealed; standards of any authorities having Ju_ following scenarios: Pendent Sprinklers offers a laboratory risdiction. Failure to do so may impair approved option for designing dry pipe •the performance of these devices. • wet and dry pipe residential sprin- residential sprinkler systems, whereas, Theowner The owner is responsible for maintain- is in- kler systems for one- and two-fam- most residential sprinklers are,labora- their protection system and it _ ily dwellings and mobile homes per tory approved for wet systems only. vices `proper' operating condition. NFPA 13D Through extensive testing,.it has been The installing contractor or sprinkler ` •wet and dry pipe residential sprin- determined that the number of design manufacturer should `be contacted kler systems for residential occu- sprinklers (hydraulic design area) for with any questions. ' pancies up to and including four the Series,LFII Residential Concealed ' stories in height per NFPA 13R Pendent Sprinklers (TY3596) need not �+ Sprinkler be increased over the number of de= • wet and dry pipe sprinkler systems for the residential portions .of any sign sprinklers (hydraulic design area) as specified for wet pipe sprinkler sys- Identification .occupancy per NFPA 13 • - tems, as is .accustomed for., density/, area sprinkler• systems designed per Number NFPA 13. TY3596 Consequently, the Series LFII Residen- tial Concealed Pendent Sprinklers of- fer the features of non -water filled pipe in addition to not having to increase, the number of design sprinklers (hy-. , draulic design area) for systems de- signed to NFPA 13, 13D, or 13R. Non-; .. water filled pipe will permit options for areas sensitive to freezing. ` /� PERMIT # V-7 BUTTE COUNTY DEVELOPMENT SERVICES ' REVIEWEDFOR'' CODE OMPLIANC DATE B Page 1 of 6 APRIL 2013 TFP44 d TFP442 Page 2 of 6 BODY SEALING (1/2" NPT) ASSEMBLY CAP / SPRINKLER p WRENCHING AREA SADDLE SUPPORT COMPRESSION CUP WITH I SCREW ROLLFORMED I THREADS �- LEVER GUIDE I I PIN i i I SOLDER LINK ELEMENT GUIDE PIN HOUSING DEFLECTOR (OPERATED -r DEFLECTOR I - �---r-- - POSITION) SPRINKLER/SUPPORT CUP ' ASSEMBLY THREAD INTO I I RETAINER SUPPORT WITH THREAD CUP UNTIL DIMPLES MOUNTING O - 0 SURFACE IS FLUSH WITH CEILING EJECTION \ SPRING SOLDER TAB %Imvcn ruu cvnc esurvcn ASSEMBLY FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER (TY3596) COVER PLATE WRENCH RECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 2 W -TYPE 18 SPRINKLER WRENCH w 2-1/2" DIA. SPRINKLER- (63,5 mm) 1/2" (12,7 mm) FACE OF SUPPORT CUP 1/2" THREADED SPRINKLER ASSEMBLY NPT \ ADJUSTMENT FITTING OPERATED /Z�SPRINKLER \ COVER JJ 1-7/8"t1/4" PLATE SS (47,6 mm RETAINER 1/8" GAP t6,4 mm) (3,2 mm) 7/8" (22,2 mm) COVER- SPRINKLER ' MOUNTING 1 RETAINER SUPPORT CUP 1/8„2 SURFACE \ (8,6 mm) ASSEMBLY ASSEMBLY (4,8 mm) -T 3-3/16" DIA. DISPOSABLE DEFLECTOR IN (81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER (TY3596) INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR Technical Data Approvals: UL and C -UL Listed. NYC Approved under MEA 44-03-E-2 NSF Certified to NSF/ANSI 61 The TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprinklers are only listed with the Se- ries LFII Concealed Cover Plates hav- ing a factory applied finish. Maximum Working Pressure: 175 psi (12,1 bar) Discharge Coefficient: K=4.9 GPM/psi'/2 (70,6 LPM/bar'12) Temperature Rating: 160°F 71°C Sprinkler with 139°F 59°C; Cover Plate Vertical Adjustment: 1/2 inch (12,7 mm) Finishes: Refer to Ordering Procedure section Physical Characteristics: Body ..................... Brass Cap ...................... Bronze Saddle ................... Brass Sealing Assembly ......... Beryllium Nickel w/ TEFLON Soldered Link Halves ........ Nickel Lever .................... Bronze Compression Screw......... Brass Deflector.......... Copper or Brass Guide Pin Housing ......... Bronze Guide Pins ......... Stainless Steel or Bronze Support Cup ............... Steel Cover Plate .............. Copper Retainer .................. Brass Cover Plate Ejection Spring ........ ................. Stainless Steel Operation When exposed to heat from a fire, the Cover Plate, which is normally sol- dered to. the Support Cup at three points, falls away to expose the Sprin- kler Assembly. At this point the De- flector supported by the Arms drops down to its operated position. The fus- ible link of the Sprinkler Assembly is comprised of two link halves that are soldered together with a thin layer of solder. When the rated temperature is reached, the solder melts and the two link halves separate allowing the sprin- kler to activate and flow water. Design Criteria The TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprinklers (TY3596) are UL and'C-UL Listed for installation in accordance with this section. Note: When conditions exist that are outside the scope of the provided cri- teria, refer -to the Residential Sprinkler Design Guide TFP490 for the manu- facturer's recommendations that may be acceptable to the authority having jurisdiction. System Types Per the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C -UL Listing, only wet pipe systems may be utilized. Refer to Technical Data Sheet TFP485 about the use of residential sprinklers in residential dry pipe systems. Ceiling Types Smooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R, or 13 as applicable. Hydraulic Design (NFPA 13D and 13R) For systems designed to NFPA 13D or NFPA 13R, the minimum required sprinkler flow rates are given in Ta- bles A and B as a function of tem- perature rating and the maximum allowable coverage areas. The sprin- kler flow rate is the minimum re- quired discharge from each of the total number of "design sprinklers" as specified in NFPA 13D or NFPA 13R. The number of "design sprinklers" specified in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems. Hydraulic Design (NFPA 13) For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis- charge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Tables A and B as a function of temperature rating and the maximum allowable coverage area. • A minimum discharge of 0.1 gpm/ ft2 over the "design area" comprised of the four most hydraulically demanding sprinklers for actual coverage areas protected by the four sprinklers. The number of "design sprinklers" specified in NFPA 13 for wet pipe sys- tems is to be applied when designing dry pipe systems. TFP442 Page 3 of 6 Dry Pipe System Water Delivery When using the Series LFII Residen- tial Concealed Pendent Sprinklers (TY3596) in dry pipe sprinkler systems, the time for water delivery must not ex- ceed 15 seconds for the most remote operating sprinkler. Obstruction to Water Distribution Sprinklers are to be located in accor- dance with the obstruction rules of NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described with- in the Technical Data Sheet TFP490. Operational Sensitivity. The sprin- klers are to be installed relative to the ceiling mounting surface as shown in Figure 3. Sprinkler Spacing. The minimum spacing between sprinklers is 8 feet (2,4 m). The maximum spacing be- tween sprinklers cannot exceed the length of the coverage area (Ref. Table A or B) being hydraulically calculated (e.g., maximum 12 feet for a 12 ft. x 12 ft. coverage area, or 20 feet for a 20 ft. x 20 ft. coverage area). The Series LFII must not be used in applications where the air pressure above the ceiling is greater than that below. Down drafts through the Sup- port Cup could delay sprinkler opera- tion in a fire situation. TFP442 Page 4 of 6 (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K -factor. Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL 4.9 K -FACTOR FLAT -PLATE CONCEALED PENDENT SPRINKLER (TY3596) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEM Maximum Minimum Flow and Residual Pressure(", °) Covera e I Maximum Spacing Ordinary Temp. Rating Area Ft' 160°F (71°C) Minimum Ft. x Ft. (m) Deflector to Installation Spacing (m x m) Flow Pressure Ceiling Type Ft. GPM PSI (m) (L/min) (bar) 12 x 12 12 13 7.0 Smooth (3,7 x 3,7) (3,7) (49,2) (0,48) Ceilings 7/8 to 1-1/8 14 x 14 14 13 7.0 inches (4,3 x 4,3) (4,3) (49,2) (0,48) Beamed Ceilings per 8 16 x 16 16 15 9,4 Beamed Ceilings per (4,9) 8 16 x 16 16 13 7.0 (4,9 x 4,9) (4,9) (49,2) (0,48) NFPA 13D or Concealed (2 4) 13R, or 13. Installed in 18 18 13.5 beam 18 x 18 18 17 12.0 beam (5,5 x 5,5) (5,5) (64,3) (0,83) 7/8 to 1-1/8 inches below 20 21 18.4 bottom of 20 x 20 20 20 16.7 bottom of (6,1 x 6,1) (6,1) (75,7) (1,15) beam (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K -factor. Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL 4.9 K -FACTOR FLAT -PLATE CONCEALED PENDENT SPRINKLER (TY3596) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K -factor. Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ftz over the design area of the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM RAPID RESPONSE SERIES LFII RESIDENTIAL 4.9 K -FACTOR FLAT -PLATE CONCEALED PENDENT (TY3596) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEM Maximum Minimum Flow and Residual Pressure (b, C) Coverage Maximum Spacing g Ordinary Temp. Rating Area(,) Ft. 160°F (71°C) Minimum Ft. x Ft. (m) Deflector to Installation Spacing (m x m) Flow Pressure Ceiling Type Ft. GPM PSI (m) L/min bar 12 x 12 12 13 7.0 Smooth (3,7 x 3,7) (3,7) (49,2) (0,48) Ceilings 7/8 to 1-1/8 14 x 14 14 14 8.2 inches (4,3 x 4,3) (4,3) (53,0) (0,57) Beamed Ceilings per 8 16 x 16 16 15 9,4 (4,9 x 4,9) (4,9) (56,8) (0,65) NFPA 13D or Concealed (2 4) 13R, or 13. Installed in 18 x 18 18 18 13.5 beam (5,5 x 5,5) (5,5) (68,1) (0,93) 7/8 to 1-1/8 inches below 20 x 20 20 21 18.4 bottom of (6,1 x 6,1) (6,1) (79,5) (1,27) beam (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K -factor. Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ftz over the design area of the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM RAPID RESPONSE SERIES LFII RESIDENTIAL 4.9 K -FACTOR FLAT -PLATE CONCEALED PENDENT (TY3596) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA Installation The TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprinklers (TY3596) must be installed in accordance with this section. General Instructions Damage to the fusible Link Assembly during installation can be avoided by handling the sprinkler by the support cup only (i.e., do not apply pressure to the fusible Link Assembly). A 1/2 inch NPT sprinkler joint should be obtained with a minimum to maxi- mum torque of 7 to 14 ft.-Ibs. (9,5 to 19,0 Nm). Higher levels of torque may distort the sprinkler inlet with conse- quent leakage or impairment of the sprinkler. Do not attempt to compensate for in- sufficient adjustment in the Cover Plate/Retainer Assembly by under -or over -tightening the Sprinkler. Readjust the position of the sprinkler fitting to suit. Step 1. The sprinkler must only be in- stalled in the pendent position and with the centerline of the sprinkler per- pendicular to the mounting surface. Step 2. Remove the Protective Cap. Step 3. With pipe thread sealant ap- plied to the pipe threads, and using the W Type 18 Wrench shown in Figure 2, install and tighten the Sprinkler/Sup- port Cup Assembly into the fitting. The W -Type 18 Wrench will accept a 1/2 inch ratchet drive. Step 4. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. The Protec- tive Cap helps prevent damage to the Deflector and Guide Pins during ceil- ing installation and/or during applica- tion of the finish coating of the ceil- ing. It may also be used to locate the center of the clearance hole by gen- tly pushing the ceiling material against the center point of the Cap. Note: As long as the protective Cap remains in place, the system is consid- ered to be "Out Of Service". Step 5. After the ceiling has been completed with the 2-1/2 inch (63 mm) diameter clearance hole and in prep- aration for installing the Cover Plate Assembly, remove and discard the Protective Cap, and verify that the De- flector moves up and down freely. If the Sprinkler has been damaged and the Deflector does not move up and down freely, replace the ,entire Sprin- kler assembly. Do not attempt to modi- fy or repair a damaged sprinkler. Step 6. Screw on the Cover Plate As- sembly until its flange comes in con- tact with the ceiling. Do not continue to screw on the Cover Plate Assembly such that it lifts a ceil- ing panel out of its normal position. If the Cover Plate Assembly cannot be engaged with the Mounting Cup or the Cover Plate Assembly cannot be engaged sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. Care and Maintenance. The TYCO RAPID RESPONSE Se- ries LFII Residential Concealed Pen- dent Sprinklers (TY3596) must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system which it controls, permission to shut down the affected fire protection sys- tem must be obtained from the prop- er authorities and all personnel who may be affected by this action must be notified. Absence of a Cover Plate may de- lay the sprinkler operation in a fire situation. When properly installed, there is a nominal 1/8 inch (3,2 mm) air gap be- tween the lip of the Cover Plate and the ceiling, as shown in Figure 3. This air gap is necessary for proper op- eration of the sprinkler by allowing heat flow from a fire. to pass below and above the Cover Plate to help as- sure appropriate release of the Cover Plate in a fire situation. If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint does not seal off any of the air gap. Factory painted Cover Plates must not be repainted. They should be re- placed, if necessary, by factory paint- ed units. Non -factory applied paint may adversely delay or prevent sprin- kler operation in the event of a fire. Do not pull the Cover Plate relative to the Enclosure. Separation may result. Sprinklers which are found to be leak- ing or exhibiting visible signs of corro- sion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi- fied or over heated sprinklers must be replaced. TFP442 Page 5 of 6 Care must be exercised to avoid dam- age -before, during, and after installa- tion. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and devic- es in compliance with this document, as well as with the applicable stan- dards of the National Fire Protection Association (e.g., NFPA 25), in addition to the standards of any other authori- ties having jurisdiction. The installing contractor or sprinkler manufacturer should be contacted relative to any questions. The owner must assure that the sprin- klers are not used for hanging any ob- jects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non- operation in the event of a fire or inad- vertent operation may result. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor- dance with local requirements and/or national codes. TFP442 Page 6 of 6 Ordering Procedure When placing an order, indicate the full product name. Contact your local distributor for availability. Sprinkler Assembly: Series LFII (TY3596), K=4.9, Resi- dential Concealed Pendent Sprin- kler without Cover Plate Assembly, P/N 51-112-1-160 , Cover Plate Assembly: Cover Plate Assembly having a (spec- ify) finish for the Series LFII (TY3596), K=4.9, Residential Concealed Pendent Sprinkler, P/N (specify) ' M Ivory (RAL1015) ....... :... P/N 56-202-0-135 Beige (RAL1001)........... P/N 56-202-2-135 Pure White (b) (RAL9010) ... P/N 56-202-3-135 Signal White (a) (RAL9003) .. P/N 56-202-4-135 Grey White (RAL9002) ...... P/N 56-202-5-135 Brown (RAL8028).......... P/N 56-202-6-135 Black (RAL9005) .......... P/N 56-202-7-135 Brushed Brass............ P/N 56-202-8-135 Brushed Chrome .... '..... P/N 56-202-9-135 Custom Paint .............. P/N 56-202-X-135 (a) Previously known as Bright White. (b) Eastern Hemisphere sales only. Note: All Custom Cover Plates are painted us - Ing Sherwin Williams Interior Latex Paint. Contact TYCO Customer Service with any questions re- lated to custom orders. Sprinkler Wrench: Specify: W -Type 18 Sprinkler Wrench, P/N 56-000-1-265 n GLOBAL HEADQUARTERS 1400 Pennbrook Parkway, Lansdale, PA 19446 Telephone +1-215-362-0700 Copyright © 2012 Tyco Fire Products, LP. All rights reserved. TEFLON is trademark of The DuPont Corporation. tqrtection Products WorldwideI www tyco-fire.com Contacts RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K -factor Pendent Wet Pipe and Dry Pipe Systems General Description The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) are decorative, fast response, frangible bulb sprinklers designed for use in residential occu- pancies such as homes, apart- ments, dormitories, and hotels. When aesthetics and optimized flow charac- teristics are the major consideration, the Series LFII Residential Sprinklers (TY2234) should be the first choice. The Series LFII Residential Sprinklers are intended for use in the following scenarios: • wet and dry pipe residential sprin- kler systems for one- and two-family dwellings and mobile homes per NFPA 13D • wet and dry pipe residential sprin- kler systems for residential occu- pancies up to and including four stories in height per NFPA 13R • wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13 The recessed version of the Series LFII Residential Sprinklers is intended for use in areas with finished ceilings. It employs a two-piece Style 20 Recessed Escutcheon. The Recessed Escutcheon provides 1/4 inch (6,4 mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjustment from the flush ceiling position. The adjustment provided by the Recessed IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING' that provides cautions with respect to handling and instal- lation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 Escutcheon reduces the accuracy to which the pipe drops to the sprinklers must be cut. The Series LFII Residential Sprinklers have been designed with heat sensi- tivity and water distribution charac- teristics proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application The Series LFII Residential Pendent and Recessed Pendent Sprinklers offers a laboratory approved option for designing dry pipe residential sprinkler systems, whereas, most residential sprinklers are laboratory approved for wet systems only. Through extensive testing, it has been determined that the number of design sprinklers (hydraulic design area) for the Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) need not be increased over the number of design sprinklers (hydraulic design area) as specified for wet pipe sprinkler systems, as is accustomed for density/area sprinkler systems designed per NFPA 13. Consequently, the Series LFII Residential Sprinklers offer the features of non -water filled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems designed to NFPA 13, 13D, or 13R. ESM The Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) described herein must be installed and maintained in compliance with this document and the applicable stan- dards of the National Fire Protection Association, in addition to the stan- dards of any authorities having jurisdic- tion. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating condi- tion. Contact the installing contractor or sprinkler manufacturer with any questions. FEBRUARY 2014 Sprinkler Identification Number (SIN) TY2234 Technical Data Approvals LIL Listed for use with wet pipe and dry'pipe systems C -UL Listed for use only with wet pipe systems NSF Certified to NSF/ANSI 61 For details on these approvals, refer to the Design Criteria section. Maximum Working Pressure 175 psi (12,1 bar) Discharge Coefficient K = 4.9 GPM/psis/2 (70,6 LPM/bars/2) Temperature Rating 155°F (68°C) or 175°F (79°C) Finishes Natural Brass Pure or Signal White Chrome Plated Physical Characteristics Frame ............................. Brass Button ......... ..................Copper Sealing Assembly ................ Beryllium Nickel w/TEFLON Bulb (3 mm) ........................ Glass Compression Screw ................ Bronze Deflector .......................... Bronze Ejection Spring .... :.......... Stainless Steel TFP400 TFP400 Page 2 of 6 7/16" (11,1 mm) 1/2„ ESCUTCHEON Components: NOMINAL NPT PLATE SEATING 2-7/8" DIA. 1 - Frame MAKE -IN SURFACE (73,0 mm) 2- Button 3- Sealing Assembly 1 4- Bulb 5- Compression 2 Screw 2-1/4" 6-- Deflector* 3 A Q (57,2 mm) 4 1-5/8" (41,3 mm) WRENCH STYLE 20 RECESSED * Temperature 5 FLATS ESCUTCHEON rating is indicated on 6 Deflector. CROSS SECTION PENDENT RECESSED PENDENT FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) 2-7/8" DIA. " 12,7 mm 7/1611/8" (73,0 mm) 1/2 ( ) (11,1±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF SPRINKLER MOUNTING FITTING PLATE A MOUNTING SURFACE 1/8" (3,2 mm) CLOSURE TY2234 1-3/8" (34,9 mm) 1-1/8" (28,6 mm) FIGURE 2 STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER (TY2234) Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and flow water. Design Criteria The • TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) are UL and C -UL Listed for installation in accordance with this section. Residential Sprinkler Design Guide When conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufacturer's recommendations that may be acceptable to the local authority having jurisdiction. System Types Per the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C -UL Listing, only wet pipe systems may be utilized. Refer to Technical Data Sheet TFP485 for the use of residential sprinklers in residential dry pipe systems. / WRENCH RECESS (END "A" USED FOR TY2234) FIGURE 3 W -TYPE 6 SPRINKLER WRENCH WRENCH RECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 4 W -TYPE 7 RECESSED SPRINKLER WRENCH Ceiling Types Smooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R, or 13 as applicable. Hydraulic Design (NFPA 13D and 13R) For systems designed to . NFPA 13D or NFPA 13R, the minimum required sprinkler flow rates are given in Tables A and B as a func- tion of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of "design sprinklers" as specified in NFPA 13D or NFPA 13R. The number of "design sprinklers" specified in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems. Hydraulic Design (NFPA 13) For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Tables A or B as a function of temperature rating and the maximum allowable coverage area. • A minimum discharge of 0.1 gpm/ft2 over the "design area" comprised of the four most hydraulically demanding sprinklers for actual coverage areas protected by the four sprinklers. The number of "design. sprinklers" specified in NFPA 13 for wet pipe systems is to be applied when designing dry pipe systems. Dry Pipe System Water Delivery When using the Series LFII Residential Sprinklers (TY2234) in dry pipe sprin- kler systems, the time for water delivery must not exceed 15 seconds for the most remote operating sprinkler. , Obstruction to Water Distribution Sprinklers are to be located in accor- dance with the obstruction rules of NFPA 13D, 13R, and 13 as appli- cable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490. Operational Sensitivity Sprinklers are to be installed with a deflector -to -ceiling distance of 1-1/4 to 4 inches. Sprinkler Spacing The minimum spacing between sprin- klers is 8 feet (2,4 m). The maximum spacing between sprinklers cannot exceed the length of the coverage area (Table A or B) being hydraulically calculated (e.g., maximum 12 feet for a 12 ft. x 12 ft. coverage area, or 20 feet for a 20 ft. x 20 ft. coverage area). Installation The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) must be installed in accor- dance with this section: General Instructions Do not install any bulb type sprin- kler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diam- eter of the air bubble is approximately 1/16 inch (1,6 mm). A leak -tight 1/2 inch NPT sprinkler joint should be obtained by applying a minimum -to -maximum torque of 7 to 14 ft.-Ibs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprin- kler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in an Escutcheon Plate by under- or over - tightening the sprinkler. Re -adjust the position of the sprinkler fitting to suit. Series LFII Residential Pendent Sprinklers The Series LFII Residential Pendent Sprinklers must be installed in accor- dance with the following instructions. Step 1. Install pendent sprinklers in the pendent position with the deflector parallel to the ceiling'. Step 2. With pipe thread sealant applied to the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. Step 3. Tighten the sprinkler into the sprinkler fitting using only the W -Type 6 Sprinkler Wrench (Figure 3). With reference to Figure 1, apply the W -Type 6 Sprinkler Wrench to the wrench flats. 41 Series LFII Residential Recessed Pendent Sprinklers The Series LFII Residential Recessed Pendent Sprinklers must be installed in accordance with the following instructions. Step A. Install recessed pendent sprinklers in the pendent position with the deflector parallel to the ceiling. Step B. After installing the Style 20 Mounting Plate over the sprinkler threads and with pipe thread sealant applied to the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. TFP4OO Page 3 of 6 Step C. Tighten the sprinkler into the sprinkler fitting using only the W Type 7 Recessed Sprinkler Wrench (Figure 4). With reference to Figure 1, apply the W -Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Step D. After the ceiling has been installed or the finish coat has been applied, slide on the Style 20 Closure over the Series LFII Residential Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. TFP400 Page 4 of 6 (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K -factor. Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEM Maximum Minimum Flow and Residual Pressure(b, c) Max. Ordinary Temp. Rating Intermediate Temp. Rating Coverage Area (9 Coverage Area (aa 155°F (68°C) 175°F (79°C) Minimum Minimum Deflector to Deflector to Installation Spacing Flow Pressure Flow Pressure Ft. x Ft. Ceiling Type Ft. (m x m) GPM PSI GPM PSI (m) (m) (L/min) (L/min) (bar) (L/min) (bar) 12 x 12 12 x 12 13 7.0 13 7.0 Smooth (3,7 x 3,7) (3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings 1-1/4 to 4 inches 14 x 14 14 x 14 13 7.0 13 7.0 (4,3.x 4,3) (49,2) (0,48) (49,2) (0,48) Beamed Recessed using Style 20 Escutcheon or 8 16 x 16 9.4 7A 13 7.0 (4,9 x 4,9) 9, (49,2) (0,48) (49,2) (0,48) Ceilings per NFPA 13D or13R non -recessed per NFPA 13D, 13R,or13 (2,4) 18x18 17 12.0 17 12.0 (5,5 x 5,5) (64,3) (0,83) (64,3) (0,83) 1-1/4 to 1-3/4 inches below bottom of 20 x 20 20 x 20 20 16.7 20 16.7 (6,1 x 6,1) (75,7) (1,15) (75,7) (1,15) beam. (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K -factor. Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K -factor. Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEM Maximum Minimum Flow and Residual Pressurelb, c) Ordinary Temp. Rating Intermediate Temp. Rating Coverage Area (9 155°F (68°C) 175°F (79°C) Minimum Ft.x Ft. Deflector to Installation Spacing Flow Pressure Flow Pressure (m x m) Ceiling Type Ft. GPM PSI GPM PSI (m) (L/min) (bar) (L/min) (bar) 12 x 12 13 7.0 13 7.0 Smooth (3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings Z 4 to 4 incnchee s 14 x 14 14 8.2 14 8.2 (4,3 x 4,3) (53,0) (0,57). (53,0) (0,57) BeamedEscutcheon Recessed using Style 20 or 8 16 x 16 15 9.4 15 9.4 (4,9 x 4,9) (56,8) (0,65) (56,8) (0,65) Ceilings per NFPA 13D or13R non -recessed per NFPA 13D, 13R,or13 (2,4) 18x18 18 13.5 18 13.5 (5,5 x 5,5) (68,1) (0,93) (68,1) (0,93) 1 1-1/4 to 1-3/4 inches below bottom of 20 x 20 21 18.4 21 18.4 (6,1 x 6,1) (79,5) (1,27) (79,5) (1,27) 1 beam. (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K -factor. Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA Care and Maintenance The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) must be maintained and serviced in accordance with this section: Before closing afire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and notify all personnel who may be affected by this action. Absence of . the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. The owner must assure that the sprinklers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; other- wise, non -operation in the event of a fire or inadvertent operation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers - before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section.) The owner is responsible for the inspection, testing, and mainte- nance of their fire protection system and devices in compliance with this document, as well as with the appli- cable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assembly Specify: Series LFII (TY2234), K = 4.9, Residential Pendent Sprinkler, (specify) temperature rating, (specify) finish, P/N (specify): 155°F(68°C) Natural Brass .............. P/N 51-201-1-155 Pure White (RAL 9010)' ......P/N 51-201-3-155 Signal White (RAL 9003) .....P/N 51-201-4-155 Chrome Plated.............P/N 51-201-9-155 175 -F,(79 -C) Natural Brass..............P/N 51-201-1-175 Pure White (RAL 9010)' ...... P/N 51-201-3-175 Signal White (RAL 9003) ..... P/N 51-201-4-175 Chrome Plated.............P/N 51-201-9-175 'Eastern Hemisphere sales only Recessed Escutcheon Specify: Style 20 Recessed Escutcheon with (specify') finish, P/N (specify') 'Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W -Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W -Type 7 Sprinkler Wrench, P/N 56-850-4-001 TFP400 Page 5of6 GLOBAL HEADQUARTERS 1400 Pennbrook Parkway, Lansdale, PA 19446 Telephone +1-215-362-0700 Copyright © 2014 Tyco Fire Products, LP. All rights reserved. TEFLON is trademark of The DuPont Corporation. Fire Protection Products • C'Q Fire & BWldfng► Pro - ducts ,; rapid response = HOME:FIRE SPRIN,KLER,SYSTEM., Technical Services: Tel: (800) 381-9312 / Fex; (800) 791-5500- t 91-5500 r- a .r. BlazeMaster, Y C CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet a ` General t Description - Technical Tyco® CPVC Pipe and fittings pro- Data duced by Tyco Fire & Building Prod-. +° ucts (TFBP) are designed exclusively Sizes i ' T for use in wet pipe automatic fire sprin- 3/4" to 3" _ kler systems. ,The Tyco CPVC Pipe Maximum Working Pressure 4 and Fittings are produced from Blaze- 175 psi F Master® CPVC compound that is a specially developed thermoplastic Approvals - compound composed of post chlorin- UL, FM, C -UL, NSF, LPCB, MEA, and ated polyvinyl chloride (CPVC) resin the City of Los Angeles. (Refer to In-. _ and state 'of `the art additives. Tyco stallation Handbook IH -1900 dated. . CPVC, Pipe and Fittings are easier to June 2008 for exact listing/approval' , install than ,traditionaI steel pipe sys-, information:) - terns, and at the same time, provide Manufacture Source superior heat resistance and strength U.S.A. ' as compared'to traditional CPVC and - PVC piping !.materials used in the Material • , _ •' , .: Page 2 of 2 TFP1915 Installation Tyco® CPVC Pipe and Fittings pro- duced by Tyco Fire & Building Prod- ucts (TFBP) are to be installed in accordance . with Installation Hand- book IH -1900 dated June 2008. Care and Maintenance The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and de- vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction. The in- stalling contractor or product manufac- turer should be contacted relative to any questions. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accord- ance with local requirements and/or national codes. NOTICE Before closing a fire protection system control valve for inspection or mainte- nance work on the fire protection sys- tem that it controls, permission to shut down the affected fire protection sys- tem must first be obtained from the proper authorities and all personnel who may be affected by this action must be notified. After placing a fire protection system in service, notify the proper authorities and advise those responsible formoni- toring proprietary and/or central sta- tion alarms. Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war- ranted solely to the original Buyer for ten (10) years against defects in mate- rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warranty is given for products or com- ponents manufactured by companies not affiliated by ownership with TFBP or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, *maintained, modi- fied or repaired in accordance with ap- plicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall be either repaired or replaced, at TFBP's sole option. TFBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of prod- ucts. TFBP shall not be responsible for sprinkler system design errors or inac- curate or incomplete information sup- plied by Buyer or Buyer's repre- sentatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental,, indirect, special or consequential dam- ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, ex- press or implied, including warranties of merchantability and fitness for a par- ticular purer This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. © 2008 NCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 - l Pipe Clamps Fig. 22 - Hanger for CPVC Plastic Pipe & IPS Steel Pipe** Single Fastener Strap (B -Line 83181) 3 'x - Size Range: ,3/4' (20mm) thru 2° (50mm) CPVC pipe • F • USiEp3'-a ,. Material: Pre -Galvanized Steel ,, ,r` c -«: �- Function: Intended to perform as a hanger to support CPVC piping used ` in automatic fire sprinkler systems. The product acts as•a hanger when tab t is upward and the fastener screw is in the horizontal position. Fig. 22 can - - ' be installed on the top of a beam, but in this situation acts as a guide to the -piping which is supported by the beam itself. It isnot intended to support - r - CPVC pipe from under a flat horizontal surface, such as'a ceiling. �' '• �' Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada.'._ �� r (cUL) to support fire sprinkler piping. May be installed in wood using fasteners supplied with product, or into minimum 20 gauge (0.9mm) steel using • - = (1) 1/4° x 1° tek type screw. Meets and exceeds the requirements of NFPA 13, 13R and 13D. A ... • Features:. Fig'22 incorporates features which protect the'pipe and ease installation. The flared edge design protects CPVC pipe from any rough surface. It is easily attached to the building structure using the special_UL, Listed hex head self threading screw* furnished with the product. It is ' recommended that rechargeable electric drills fitted with a hex socket attachment to be used as installation tools. No impact tools (such as a hammer) are allowed. Damage has been known to result from installations using impact type tools. No pre -drilling of a pilot hole in wood is' t. ,. ' { . •°. . required - Finish: Pre -Galvanized V..- . ' Order. By: Figure`number and pipe size. . " * Hardened hex head self threading screw is furnished with t the .� ` • product and;is the minimum fastener size acceptable. r a • ** With reduced spacing, consult factory. '4 r CPVC ,; Max. Hanger Fastener Hex Approx. _ a Pipe Size • A B ,. C Spacing Head Size wt./100 - ' • Part No. in. (mm) in. , (mm) in. (mm) in. (mm) R. W ` in. (mm) ~ Lbs. -(kg) • x'22=3I4�... 3l4 �I20) 37 ,16 X61 9 ..��s .,1.. 16 � 33 3 � 1 j ��s. � �«� � ���� •` g�� ' � � . ~ ��ca �• c ./ I r •,;:5/ ( /�[30.21�5%2(167,)' 5/:16�I7 91 sz�9 4.1�� Mme: " 221 1" (25) 211/16 (683) 17/16" (36.5) 13/16' (30.2) 6 (1,83) 5/16 (7.9). 9 (4.1) E ; s �c0 ' F %` 'si�,Y'�-'>�n,V&u2�n 'Z'3[y�.,'�, ,. •f?%:: "si3.:iF's. :s�?i"¢""S £ .j� .,..ad'S�'c..^xa H ��:: �1?/��, € � 11/9. ,1321 "' ';31I16y(77 8)� F15/e i429) � 13/16 �30 2)� 61/2,=1198 ''' =1 5/El6 �Y(7 9► ','�' `�j5 01,`� � s °22-11/2 [ 11/2" (40) 35/16" (84.1) 13/4 (44 4) 13/16 (30 21 7 (213) 5/16 (7.9)' 12 (5.4) i 1'i�:,,`�� 1 y oe 3/ 1 1 �° 1/ �F( 3 3 (su 1 g 3 e ( ) � • 222' ,r 2r (50) �3 a 952 ,x,2.8 546 1� t6 302�81244j, s 5]t6 79: 15� .. �I'.�-w • 4 i • .• . _ ♦� i e — - " • r- ` •':' ` +.� ,j ..� �,. vim... ., '^Y., _ 1. ,. - All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. �� 9 �• Fire Protection Solutions 35 1! • Pipe Clampsr. Fig., 23 - Hanger for CPVC Plastic Pipe & IPS rSteel, Pipe** y R VTQLCC3� Double_ Fastener Strap (B -Line B3182) F a •r rc..L us ly. . Size Flange: X3/4° (20mm) thru 3° (80mm) CPVC pipe Material: Pre -Galvanized Steel Function: intended to perform as a hanger to support CPVC piping • F. used in automatic fire sprinkler systems. Fig. 23 can be installed r t, on the top, bottom or side of a beam. Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL) sizes 3/4° (20mm) thru 2° (50mm) to support fire sprinkler piping'. May be installed in wood using fasteners supplied t with product, or into minimum 20 gauge (0.9mm)`steel using (2) 1/4',x 1_° tek type screw. Meets and exceeds the requirements of NFPA a 13, 13R and Features. - Fig. 23 incorporates features which protect the,pipe \� \ , '' B " • _ t, i and ease installation. The flared edge design protects the CPVC + • . , "pipe from any rough surface. It also incorporates snap restrainers 8 "' allowing easier and faster installation. Easily attaches to the building B n structure using the two UL Listed hex head self threading screws* c • .•, furnished with the product. It is recommended that rechargeable , electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer) are allowed. _ - + . Damage has been known to result from installations using impact \ _ type tools. No pre -drilling of a pilot hole in wood is required. " Finish: Pre -Galvanized` r� r ` Order By: Figure number and pipe size` k * Hardened hex head self threading screw is furnished with the 4 t, • product and is the minimum fastener size acceptable. �• 1 h \ . ,R�71 3 f s 7 ** With reduced spacing, consult factory. e +, µ . ; 4. A . s ? - CPVC Max. Hanger 1 Fastener Hex Approx., Pipe Size A B ,< C Spacing _ Head Size : W000 Part No m (mm) m (mm) m (mm) m (mm) k Win. "(mm) Lbs ft) E ' ,+� � x«23 3/4 •� ' ,,3(4��1201�?s"" 31 8 S (794 19 16 397:r "" 13 16�' 30? . "'"51 2 1 67, �€ 5 t6 „�?���.�'`��� `� � r � e ` 23-1 1 (25) 33/6 (657) 111/16' .1429) 13/16 (302) 6 (1 83) 5/16' 17.91 9. (41)1�:..:< - \ ' � :._;� 1� 4v:�=Y ;s: 1 � 4.:uS 2 �'°N',.:fa 3 ,n , 5 ��'�"`3 . ( "nii.""3 "3.n:µ <,. �, °s�'" 1 � .•a...,�s'^r � ,�-7 s,��,X•++r.�., .. It I _. ='m"%".`": � � i� .' : - • /. ,. �/ ..(3 I �.�, 16 (]06.41 �x2; �' � �-•is ��r�;. ..., u4�:� :µf••?2./32�,:15311 ,iµ;;; t /t6�3021,.�_�..����r�1;98) "kz,�/16,y�17.91i %;��,�y,,�,'11 150) >?, s���,��1 23 11/2 11/2" 1401 42/16" (112.7) ' 2/32" (56.3) 13/16' (30.2) 7 (2.13) 5/16" (7.9) 12 '(5.4)!! ` , 2� 23 2•� q ��"� 21501 4? 8123 8 �`� ���27 16�»�� 6 `•9 �"` 13 t s° " 0 2�� 8�2 44 �x�'5�',�- j""��� �'� -23-2/21 21/2" (65) - 53/8" (136.5) 211/16" (68.3) 13/16" 130.21 ConsultFactory h . 5/ts" 17.91 , 22 110.01 i n. `3�I801 6 (52�4l 3°17621 2 1 h6 (3021"Consutt4Factory5/ts�(1:9) �25(1i1311 ' All dimensions in charts and on drawings are in inches.` Dimensions shown in parentheses are in millimeters unless otherwise specified. B Line `. Fire Protection Solutions - 37 ^� p&� Q '+F• Pipe Clamps Fig. 24 - Hanger for CPVC Plastic Pipe &IPS Steel Pipe** Double Fastener Strap Side Mounted '(6 -Line B3183) fpm Material: Pre -Galvanized thru 2° 15omm1 CPVC pip Size 9 e € 4 3//4' alvanized Steel t Function: Intended to perform as a hanger to support CPVC piping used in automatic fire sprinkler systems. Can be installed on the top or on the bottom e „ c _ of a beam. •'- Approvals:' Underwriters Laboratories Listed in the USA (UL) and. ' � 'r . � ,'-, . , • Canada (cUL) to support, fire sprinkler piping. May be installed in wood using , fasteners supplied with product, or into minimum 20 gauge (0.912mm) steel,'_' ' using (2) 1/4° x 1� tek type screws.. Meets and exceeds the requirements of �- ;4 , .�'•. NFPA 13,13R and 13D. Features: Fig. 24 incorporates features which protect the pipe and. ,' "• . i ease installation. The flared edge design protects the CPVC pipe from any.rough surface. Easily attaches to the building structure using the two UL Listed hex head self threading screws* furnished with the • product. It is recommended that rechargeable electric drills fitted with a hex socket attachment.be used as installation tools. No impact: '..tools (such as a hammer) are allowed. Damage has been known to result from installations using impact type tools. No, pre -drilling of a M3 pilot hole in wood is required.k; Finish: Pre -Galvanized t- e' , a Order By:: Figure number and pipe size j,)� A ' Hardened hex head self threading screw is furnished with the product and is the minimum fastener size. acceptable: F "* With reduced spacing, consult factory.. CPVC Max. Hanger,, Fastener Hex ` , Approx. Pipe Size A B- C Spacing, Head Size Wt/100 Part No. in. (mm) in. (mm) r in.: (mm) • in.' (mm) Ft. W " in. (mm) Lbs. (kg) r 'y243/4�3/420) 25/ 6(58;1) 15/32(2 81 13/16 30 21 51%211 fi7��5/1617 91 9 1411 ' 24-1 1": 1251 25/8" 166.71 15/16"`133.31 13/16" 130.21: 6 11.831 5/1s'" 17:91 914.11 24 1%g 1'1/4 1321 3,5 I76i2)1?/2'',"138x1) 13/t6 X130:21 . 6?%2 '11980 ' S/i6., :17:9) 11 r (5;0) s . 24-11/2 11/2" (40) 31/4° (82.5) 15/8" (42.3) 13/16" (30.2) 7 (2:13 i 1 5/16 ".17.9) 12 (5.4) , 29 2 2 (50) 311/1` 6��93 j)�1'27/32�j4i`i6 ��13/16 130$) 8 (244); 516 17s1IF 15I�s 81 Fig. 25 - Surge Restrainerrh A °' m, �m Size R e: — One size fits 3/4, (2omm1 thru 2° d4omml'pipe. �' USTEpg 31' Material. — P alvanized Steel , °• Function:—`Designe be .used in conjunction'with'Fig..200band .." •. hangers P { to restrict the upward movement i ing as it occurs during sprinkler ' headactivation or earthquake type active The surge restrainer is easily and efficiently installed by snapping into ocking position on the , band hanger. This'product is intended to satisfy th quirements as x i " - mdlcated.in the National Fire Protection Association. NFP , 2Niffl - edltion,'9.2.3.4.4.1 and 9.2.3.4.4.4 Can be used to restrain teel pipe or CPVC plastic Pipe. m Approvals: —Underwriters Laboratories List onlywhen used with ; . band hanger Fig. 200, in the USA (UL) anada (cUL). - °Finish: Pre Galvanized Order.By: Figure numb nd band hanger, size from z " 3/4° (20mm) thru 2' mm). l Patent #5 ,108 p 1 All B dimensions in charts and on drawings are in inches: Dimensions shown in parentheses are in millimeters unless'otherwise speci i L1nC Fire Protection Solutions 38 Pipe CI'a op§ y ' Fig, 28M - Offset Hanger & Restrainer, CPVC Plastic Pipe and IPS Steel Pipe ** T. " Size. Range: 3/41 (20mm) thru 2° (32mm) r• s s A ��pUS 'r t Material: Steel, Pre-Galvanized- 'Function: re-Galvanized 'Function: Designed to be used as a hanger and restrainerfor CPVC piping or steel'piping -where the "stand-off" design will ease installation by eliminating the need for, wood blocking. ,,, •'' I Features: y. •' Flared edge design protects CPVC pipe from any rough or abrasive surfaces �• Unique snap -on design holds pipe firmly'in place and allows retrofit type of installation The "Stand -Off design eliminates the need for wood block extension •'Can beiinstalled on horizontal or vertical piping regardless of mounting surface orientation A Attaches easilyto wood structure with two hex head self -threading screws furnished with product ' • Installs easily using rechargeable electrical driver with 5/16" 17.9mm1 extension socket• . —,eliminating impact tool damage to pipe Attaches! easily to steel, minimum 18'gauge (1.o24mm) with (2) 1/4 x 1`' tek`type self ca': .drilling tapping screws C `. cULus Listed as a .hanger and a restrainer for fire sprinkler piping Installation Note: When installed in wood structural members and threads from the #10 x T° screws are exposed, use Fig. 27B speed nut to secure, a A Approvals:,. Underwriters Laboratory Listed in the USA (UL) and Canada (cUL) •to support automatic fire sprinkler systems.., • -- r = , May be installed into wood using fasteners screws X °� n mgml�a Meets and exceeds the requirements of NFPA 13 l- v ro 13R and 13D. Fig.'28M satisfies the UL vertical restraint requirements where, needed. "Fig. 276 , Order By: Figure number and pipe size •. sx� r�a� 2 Required MOM - Patent #7,744,042. ** With reduced spacing, consult factory. IR' S k t r -- --- --- x.' y. a -T - --- ------ ------ • : b I —� - Hanger,and Restraints Application gK 'L — — — — —J r Restraint Fig,27B sWx �� t • Required cv r -- -y High Side of Hanger $� J l r I Restraint ?' i Detail A. Hanger Application', Pipe Size A� p Hole Dia. B •, C 'Max Spacing A'pproz. WtIll0' Part No: in: (mm) in.' imm) in.. (mm) in. (mm) ,, in. (mm) . lbs. (k9) • � .� --x;�;,a,sl �,„ X1508}� .�/.tsz �j481, � 3�/is 18 41) 28M-1 1" (25) 21/8" (54.0) 3/16" (a.e) 31/2" (88.9).. 6-0': (1829)•' 12 15.4) ' 28M 11/4...r11/4� y�25/ 6 a1587)i �K3� 6 ' 48 il" '889 R. rc 1 d�" _` a # t . "•m;:<a>.....0 u'M.,:,. a av °,s��zH .baa n=a�'^`La;:o6,:C«a,'a,�` ."..,x;..H:"l.�C�ai�^""�,� )".:���' ..<a:.' ��u�.�«t�:,: „za�e�:Vau�,'�,��7'T _ � iii 28M-11/2 11/2 (49) 27/16" (61.9).- 3/16" (4..8) ' 37/8" (98.4) T 0' (2133) 14 (6.3) ZBM 2r 2A�j5o) ~�.. 25/e6671r���3/ eyi48) 4/t¢It r8�S0" (2438F�' 15 x16381 3' t -'Required per NFPA,l3.for CPVC plastic pipe ' n Fire"Protection Solutions s , ,'All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unlesotherwise specified 41 tine �. r: UNITED BRASS WORKS, INC �. 714 S. Main St.. Randleman, N.C. 27317 Iso 900 Phone: 800/334-3035 Fax: 800/498-4696 Model 80 Ball Valve , Double Female , (Complies with MSS-SPI10-92) 260 lbs. WSP @ 406 6 Maxi 400 lbs. WOG * 100% Pressure Tested ' Threaded Ends * Blowout Proof Stem ' '/4" -''/2" Full Flow 4 3/4" - 2" Large Port Diameters , CRN 0007135.2 , *Contains Lead. Not Intended for Use in Potable Water Systems* F _ 1 2 MATERIAL LIST � NO. DESCRIPTION MATERIAL 1 2. 3 Lever Stem Jam Nut Plated Steel w/ vinyl grip Brass Plated Steel 4 Packing Nut Brass 5. Packing Sleeve Brass 6 Packing Graphite Non-Asb. 7 Bevel Washer Steel 8 • 9 O -Rin Tail Piece ('/a" - '/�") Tail Piece 3/4" - 2" Buna Brass Bronze 10 11 Body Ball Bronze Chrome Plated Brass 12 Nest PTFE %2" 0.50. 2.17 SIZE A B C D E F SHIP WT. (lbs.) QUAN. PER CTN. '/4", 0.38 1.86 0.92 0.94 1.58 3.31 0.52 12 3/8" 0.38 1.86 0.92 0.94 1.58 3.31 0.52 12 %2" 0.50. 2.17 1'.06 1.11 2.28 4.23 0.78 12 0.63 2.05 1.20 1.31 2.38 4.23 0.98 12 _ F, ; 0.81 3 .27 1.67 1.59 2.55 4.23 1.59 • 6 1 '/4 ' 1.00 3.48 1.72 1.77 3.19 5.47 2.47 4 1 % 1.2 5 3.97 1.95 2.02 3.38 1 " 5.47 3.50 4 2" 1.50 4.41 2.14 2.27 3.56 1 5.47 5.00 ' 2 Tel: UNITED BRASS WORKS, INC. 714 S. Main St., Randleman, NC 27317 iso9oo, 800-334-3035 Fax: 800-498-4696 www.ubw.com 015 MATERIAL LIST Model 210 Swing Check Valve 200 WOG @ 180 'Max 100% Pressure Tested • Integral Seat Threaded Ends • Metal Disc Swing Check Valve with 3/32" orifice in Clapper for use on automatic pressure switch line of fire pump installation as required by NFPA No. 20A-7-5.2.1. Not Recommended for Pulsating or Vibrating Service! Install in horizontal position only! *Contains Lead. Not for Use in Potable Water Systems* NO. DESCRIPTION MATERIAL 1 Cap (%4" — 1") Ca 1 %4" — 2") Bronze Brass 2 Washer Brass 3 Body Bronze 4 Disc Brass 5 Hinge Stainless Steel Size '/4" 3/8" 3/4" 1" 1 '/4" 1 %" 2" A 1.89 1.89 q2.14 2.51 3.03 3.45 3.81 4.44 B 1.22 1.22 1.53 2.06 2.20 2.20 2.86 Ship Wgt. (lbs.) 0:45 0.45 0.58 0.81 1.62 1.81 2.41 3.42 Qty. Unit Pack 12 12 12 12 6 6 4 2 Qty. Per Case 60 60 60 60 30 18 12 6 Dimensions include'all spacing needed to operate drain valve and ` .remove flow switch'cover _ `, * . Without check valve , �•� - :�' �, ;'. ** With or without pressure relief"valve \ 4 © National fire Products, LLC r (800)528- 7978 h 'RESI-RISERTI Size Chart ' Description National Fire Products, LLQ: ix" .` 2" • - - . RESI-RISERT"' 13" 13" 13" - The RESI-RISER. is a'pre-assembled, compact, attractive fire•sprir.'kler riser unit for residential sprinkler systems in accordance with NFPA 13, 1? -Rand 13D. 12" 12-1/2" : The RESI-RISERT"" manifold is manufactured as a one- ' S �- piece casting that isair-tested for leaks.? 3-1/2'- Raised lettering on both sides allows the RESI-RISER'" a y. 1/2". to be installed to the right or left and easily identifies • 4 , the flow direction and Test and Drain outlet: • Two mounting legs are molded onto the manifold , allowing for a secure right or left anchoring: 1 ' • The flow switch has dual SPDT switches and -a retard ' • ,M of 0-90 seconds. A i !An optional "all in one" -cost saving combination Pressure Relief Valve/Test and.Drain,Valve is available. 3' " • The RESI-RISER'" unique design gives the ability to,be }` A, installed within standard 2 x 4 frame construction. '�` • Every size RESI-RISERT"" fits within:a 2 x,4 wall framed at 16 inches on center. r \ • t 2 Technical Data+ Item. Description. f ,'• sizes: 1", 1x","1%", and 2" . 1` Manifold Body, Male Thr ead'x Style: Thread x Thread Male Thread ' - • Listing: Flow Switch and Pressure Gauge are UL , 2 '' InlinCheck Valve, Spring 'L r •. \ _Listed r •- Finish Body): Cast " -L oad I ed ; . (Riser Brass ': 3 Flow Switch with Retard ' ". • Water Pressure Gauge: 0-300 psi ' ` 4 Drain Valve, with optional° • • Optional Accessories: 175 psi Pressure Relief pressure relief valve . Valve/Test and Drain r 5 ' Pressure Gauge'psi, . .US Patent # 6,076,545 ;`• Dimensions include'all spacing needed to operate drain valve and ` .remove flow switch'cover _ `, * . Without check valve , �•� - :�' �, ;'. ** With or without pressure relief"valve \ 4 © National fire Products, LLC r (800)528- 7978 h 'RESI-RISERTI Size Chart ' Description 1" ' ix" 1%"' 2" Height* 13" 13" 13" 13" . Width** 10-3/4" 1171/2".,° 12" 12-1/2" Depth 3.1/2" 3-1/2" 3-1/2'- '3`-1/2'; Drain Size 1/2". ',1" 1" 1" Dimensions include'all spacing needed to operate drain valve and ` .remove flow switch'cover _ `, * . Without check valve , �•� - :�' �, ;'. ** With or without pressure relief"valve \ 4 © National fire Products, LLC r (800)528- 7978 h WFDTH Waterflow Detector The System Sensor WFDTH Retard T -Tap Waterflow Detector is designed for primary signaling in residential systems and fits within 2x4 stud wall construction. Features - Residential sprinkler systems Sealed retard mechanism • Visual switch activation Rugged, dual SPDT switches enclosed in a durable terminal block Easy to install and maintain design Vertical or horizontal mount Field replaceable retard mechanism and switch assembly Twelve different flexible paddles Durable, tamper resistant enclosure Two conduit openings Handy depth gauge Accommodates up to 12 AWG wire 100% synchronization fires alarm panel and local bell simultaneously Agency Listings UL u C O� ® MEA .� LISTED �' approved 5739 05169 77701653:114 - 167-93-E 3033305 The WFDTH fits any tee that has a 1 NPT branch, including: 17, t'/o", 11/2", and 2" NPT threaded ferrous and brass tees; 1-, 11/4-, 1'/2" and 2 - copper sweat tees; Central, Spears, and Victaulic' brand 1 "CPVC tees; and 1'/z" polybutylene tees. Design.The design of the WFDTH makes it easy to install and simple to maintain. It can be mounted in the vertical or horizontal position. Two conduit openings permit easy attachment to the local alarm system.The retard mechanism and switch assembly are field - replaceable. Features. Twelve different flexible paddles fit 1-, 11/4-, 11/2-, and 2" tees. Sizes are marked clearly on the paddle for ease of installation. Plastic paddles slip over the actuating lever a;)d are securely fastened with one screw. The handy depth gauge insures the proper installation depth and clearance of the detector to the tee. t Construction. The WFDTH includes a durable and tamper resistant enclosure. Its sealed retard assures that the delay mechanism is not contaminated by dust and dirt when the cover is removed. The long lasting cover completely encloses the electrical components to further keep out dust and dirt. Improved self -guiding security screws and removal tools make detectors resistant to tampering and simplify field maintenance. WFDTH Specification's Model shall be a WFDTH as manufactured by System Sensor. T-tapwaterflow detectors shall be installed on a tee that has a 1 -NPT branch including: 1-, 114-, , 11/2", or 2"threaded ferrous or brass tee; 1-2"copper sweat tees; Central, Spears*, and Vctaulic' brand 1"CPVC tees; or 11h"polybutylene tee as designated on the drawings and/or as specified herein. Detectors shall mount on any clear pipe span of the appropriate size, either a vertical or horizontal run at least 6" from any fittings or valves which may change water direction, Flow rate; or pipe diameter or no closer than 24" from a valve or drain. Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a static pressure rating of 250 psi.The retard t -tap detector shall be a sealed mechanical pneumatic unit with visual indication of actuation. The actuation mechanism shall include a polyethylene vane inserted through the tee fitting and connected by a mechanical linkage to the delay mechanism. Outputs shall consist of dual SPDT switches (Form C contacts).Two conduit entrances (one of which is a knockout type) for standard W fittings of commonly used electrical conduit shall be provided on the detectors. A grounding provision is provided. WFDTH is listed by Underwriters Laboratories ` for indoor use. ' Static Pressure Rating 250 PSI (max.) Operating Temperature Range 32°F to 120°F (O°C to 49°C) ± ' Maximum Surge 18 FPS ' Enclosure Rating UL listed for indoor use Triggering Threshold 4-10 GPM Cover Tamper Switch, Canadian models only, factory installed Bandwidth (Roma Rate) } - Installed 01.4cm H x 9cm W x 17cm L) t ' One orTwo Family Dwelling: NFPA 13D , ,- ' Residential Occupancies up to 4 Stories: NFPA 13R - - National Fire Alarm Code: NFPA 72 ,, Contact Ratingi Two sets of SPDT (Form C) Shipping Weight :v ' r ' 2.6 lbs. (1.2 kg.) 10.0 A @ 125/250 VAC 2.5A@24VDC Compatible Tee Threaded ferrous and brass tees, copper Warranty ' 3 years Fittings sweat tees, CPVC tees, and polybutylene tees + ,• z,. Conduit Entrances Two openings for 1/2"conduit. U.S. Patent Numbers 3,845,259; 4,782,333; 5,213,205 -Electrical Connections Delay Adjustment Dial = ;� UL -LISTED °. SSM24-X SSV, NOTE: COMMON AND B -NO CONNECTIONS WILL CLOSE ` Delay & o1A is APP sfco"Tr COMPATIBLE CONTROLPANEL WHEN VANE IS DEFLECTED, I.E., WHEN WATER IS FLOWING. DUAL adjustment dsa�u +, SWITCHES PERMIT dial 0 r POWER + APPLICATIONS TO BE COMBINED o o r • 24VDC OR ON A SINGLE DETECTOR. - 120VAC — Q5 ' + INITIATING SUGGESTED EOL CONTACT RATINGS 125/250VACI 10AMPS ^ 45 r LOOP RESISTOR 24VDC I 2.5AMPS " r' SCHEMATIC OF INDIVIDUAL , • `NOTE: Retard time may exceed 90 seconds. t SWITCH IN COM " Adjust and verity that time does not exceed 90 seconds. "NO WATERFLOW" IL CONDITION A 040 ` ' O 0 O BREAK WIRE AS • SWITCH 1 SWRCH 2 SHOWN FOR - - ` SETCH aoSW+a 1E�DN STATE }4iy SUPERVISION OF -CONNECTION. DO ~ • AWAY IiW NOT ALLOW -y �'"" EDGES .. �• uo�oare �°+o O STRIPPED WIRE LEADS TO EXTEND '001 BEYOND SWITCH _ HOUSING. DO NOT ' LOOP WIRES. Ordering Information , .' • . WFDTHWFDTHA WaterFlow Detector, Fits 1 ",11/4", 11/2 , 2 -ferrous and brass threaded tees; l ,11/4",11/2 , 2' copper _ sweat tees; l "CPVC tees; and Ph -polybutylene tees . - Accessories 1 t - A77-01-02 + Replacement terminal block for WFDTH S07-66002 Replacement tamper screws for covers of WFDTH .+ PRK9 •, Replacement paddle kit -12 paddles_ for WFDTH (see WFDW ` ' Replacement tamper proof wrench for cover of +� WFDTH for sizes included) WFDTH + A3008-00"- Replacement retard mechanism. ' C58-0009-000 Replacement metal cover • ♦ • + '- ` Spears' isa registered trademark of the Spears Manufacturing Company.Yaaulic• is registered trademark of the mctaulic Company of Amedca. SYSTEM • - ' ' 020105ystem Sensor. . Z• 3825 Ohio Avenue • St. Charles, IL 60174 a Phone: 800-SENSOR2 Fax:630-377-6495 Product spedfiotionssuyea todtange Wthout raticemsit systemsensoccomfa" Nrrentpaduainformation,indudingthelatestversimofthisdamsheet. „ r - • - + - A05-0941-008. 7/10-02451 r S�WTEM SENS OR SSM/SSV Series Alarm Bells 0 System Sensor's SSM and SSV series alarm bells are low current, high decibel notification appliances for use in fire and burglary systems or other signaling applications. Features Reliable Performance. The SSM and SSV series provide loud Approved for indoor and outdoor use resonant tones. The SSM series operates on 24VDC and are motor Low current draw driven, while the SSV series operates'on) 20VAC utilizing'a vibrating mechanism. High dB output Available in six-inch, eight -inch, and ten -inch sizes Simplified Installation. For indoor use, the SSM and SSV series AC and DC models mount to a standard four -inch square electrical box. For outdoor applications, weatherproof back box, model number WBB, is used. DC models polarized for use with supervision circuitry Mount directly to standard four -inch square electrical box.indoors . The SSM and SSV series come pre -wired, to reduce installation time: ' SSM and SSV series come pre -wired The SSM series incorporates a polarized electrical design for use with supervision circuitry. Agency Listings U` Cw USC FM O MEA O LISTED roved �,, �, approved - '. 54011 CSS49 300S2SS 7135-16S3:0217 331-01-E - SSM/SSV Specifications Model shall be a SSM or SSV Series alarm bell. Bells shall have underdome strikers and operating mechanisms. Gongs on said bells shall be no smaller than nominal 67/8710- (specify size) with an operating voltage of 24VDC or 120VAC (specify by part number). Bells shall be suitable for surface or semi -flush mounting. Outdoor surface mounted installations shall be weatherproof (using optional WBB weatherproof electrical box). Otherwise bells shall mount to a standard 4- square electrical box having a maximum projection of 21/2. Bells shall be located as shown on the drawings or as determined by the Authority Having Jurisdiction. Bells shall be listed for indoor/outdoor use by Underwriters Laboratories and the California State Fire Marshal, and approved by Factory • Mutual and MEA. Operating Temperature Range -31'F to 140°F Operating Voltage SSM series: 24 VDC SSV series: 120 VAC Termination Provided with 2 sets of leads for in/out wiring + Service Use Fire Alarm, General Signaling, Burglar Alarm Warranty 3 years i ` Model Gong Diameter Nominal Voltage Operating Voltage Maximum Current Sound Output WBA) _ (inches) Limit ♦.r - SSM24-6 6 Regulated 24VDC 16 to 33VDC DC -31.1 mA/ FWR-535mA .82 SSM24-8 8 Regulated 24VDC- 16 to 33VDC DC -31.1 mA/ FWR-53.5mA 80 f SSM24-10 10 Regulated 24VDC 16 to 33VDC DC -31.1 mA/ FWR-53.5mA 181 SSV720-6 6 Regulated 120VAC 96 to 132VAC 53mA 85 SSV120-8 8 Regulated 120VAC 96 to 132VAC 53mA ,, 82 SWI 20-10 10 Regulated 120VAC' 96 to 132VAC . 53mA 82 *Sound output measured at Underwriter Laboratories, as specified in UL464 ' Ordering Information SSM24-6 SSM24-6A - Bell, 6, 24VDC, Polarized, 82clBA SSM24-8 SSM24-8A Bell, 8, 24VDC, Polarized, 80dBA SSM24-10 SSM24-1 0A Bell, 10-, 24VDC, Polarized, 81 dBA SSV120-6 SSV120-6A Bell, 6-,120VAC, 85dBA SSV120-8 SSV120-8A Bell, 8 ,120VAC, 82dBA SSV120-10 SSV120-10A Bell, 10-,120VAC, 82dBA WBB Weatherproof back box for SSM and SSV series, when installed outdoors Sysmm SENSOR" , = 02011 System Sensor. 3825 Ohio Avenue - St. Charles, IL 60174 Productvedficaums subject todlange Mthom notice. Visit systemsensorcom for Phone: 800-SENSOR2 Fax: 630-377-6495 current product information, including the latest version of this data sheet. h ' • -,AOS -0260-010.08/11•02870 r •I 10 L wl • 1I 91I HS � Description FPPI pressure gauges feature an impact and corrosion:resistant case made from ABS (plastic). Features phosphor bronze bourdon tube movement with white ' enameled brass dial face with large numbers for easy reading. Dual scale to`300 PSI/2000Kpa. UL/ULc Listed (Sprinkler Gauge Model 111.1 OSP, UL Listed file' EX5232) and FM. Approved:16 ` r ti Applications r . •`fire sprinkler systems ie Suitable for -al[ media that will not obstruct the pressure system or attack copper, alloy;parts Special Features: UL -listed. (UL -393), United States and Canada (Sprinkler Gauge ' 'Model 111.1 OSP, UL Listed file " gEX5232) • FactoryMutual (FM) approved �. Reliable and economical fs 3198 LIONSHEAD AVE CARLSBAD, CA 9201.0 TEL 1 760 599-1168 + 1 800 344-1822 FAX + 1 800 344-3775' © 2012 Fire Protection Products, 4nc. Standard Features,:',, Design e. EN 837-1 & ASME B40.100 ' Sizes 4„`(100 mm) "Accuracy class ` t 32/3% of span. (ASME 840.100 Grade B) Ranges t, 0/80 psi,, retard 6250 psi (air) ' 0/300 psi (air, water, air/water) Working Pressure Steady: 3/4 of full scale value. ' Fluctuating: ,2/3 of full scale value Short time: full scale value Operating Temperature Ambient: -40T to 140°F (-40°C to 60°C) , Media: 140T (+60°C) maximum Temperature Error Additional error when temperature changes from reference temperature of 68°F (20°C) +0.4% for. every 18°F' . (10°C) rising or, falling. Percentage of span. F`PPIw ■W ■■ ■N.1 ■ I 1.vvnl Spare Sprinkler'.1 Storage Cabinet Description 1, i' Fire Protection Products, Inc. Spare Sprinkler;Head.Cabinets are designed to allow for spare sprinkler head storage as required byNFPA guidelines. The Spare Sprinkler. Head, Cabinets are ' availablesih six configurations. Three head, six head, six head,ESFR,,tweNe.head;.twenty-four °head and thirty `six head: All six styles.are manufactured with "knockouts" to'accommodate • } .',,.the most common'size sprinklers. The shelf is:located to `allow for the, storage of;a typical'`' sprinkler head. wrendh. Each cabinet is finished with.a red enamel finish. Each Yspare head L cabinet comes with a`hinged door which remains closed to protect 'the spare sprinklers from"the elements andJeatures two holes on the'back"panelao allow for attachment to most y FqqwOF I' surfaces utilizing the appropriate fasteners Not intended for exposed or harsh environments. 'tiN+vk�NY«\:1.un'�`'cr."G, ��w`Dcda , F �` - ■ i � '� .fir � � � Installation Specifications ' Select the_correet'Spare.Sprinkler Head Cabinet in accordance with the f>Y , Automatic Sprinkler Systems Handbook As per the 1989 Edition the correct,,:,,` Material\ [ ,.Painted Plaint Steel number of spare sprinkler is as follows f E \ z t 0-300 sprinklers,,not less`tFiI Al 17 an 6; 300=1000;; not less;than 12;.1000 ormore; t „�� llmed enamel a � r„� not,less- than 24':Stock;of'spare sprinklers shall include all types and ratings F fl � �ago e Styles installed.' _ ;: ; r • fF�&M y j . ezy3Spare sprinklers /zoo/�� i 16 Spare sprinklers a`,�s:��?ra.� 6 Spare NESFR /, or 1 l Once the correct Spare, Sprinkler Head Cabinet has`been selected; installation �. WWW � � a ' _ 1�2 Spare sprinklers?/zor 3/a�: PAC by inserting the correct fastener in.each of the two holes inside ' 24 Sp �e spr nklers ` the�cabinet securing the cabinet securely to the wall; The insert the correct. 36 Spare spr nklers_ � E ` number and type,;of sprinklers,in accordance with the•"handbook .'.:, - 'Final determination is subject to'approval by the AHJ: 3198.LIONSHEAD AVE I I" CARLSBAD, CA, 92010 TEL + 1 760 599=.1168 v ” 1 800 344-1822 ,. FAX +.1.8003443775 © 2012 Fire Protection Products Inc.`