Technical Services: Tel: (800) 381-9312 1 Fax: (800) 791-5500
B/azemaster g
CPUC Fire Sprinkler Pipe & Fittings
Submittal Sheet
General
Description
Tyco'D CPVC; Pipe and Fittings pro-
duced by Tyco Fire & Building Prod-
ucts (TFBP) are designed exclusively
for use In wet pipe automatic fire sprin-
kler systems. The Tyco CPVC Pipe
and Fittings are produced from Blaze-
MasterO CPVC compound that is a
specially developed thermoplastic
compound. composed of post chlorin-
ated polyvinyl chloride (CPVC) resin
and state of the art additives. Tyco
CPVC Pipe and Fittings are easier to
install than traditional steel pipe sys-
tems, and at the same time, provide
superlor heat resistsnra and strength
as compared to traditional CPVC and
PVC piping materials used in the
plumbing trade. Various adapters are
available to connect CPVC, pipe to me=
tailic piping. Ali female pipe thread
adapters have brass inserts for dura-
bility. Grooved adapters connect di-
rectly to grooved end valves and me-
tallic pipe, with flexible. grooved end
couplings.
NC.ITICE
TycoO CPVC Pipe and Fittings pro-
duced with BlazeMastet® CPUC com-
pound described herein must be in-
stalled and maintained in compliance
with this document and with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards of any authorities having
jurisdiction. Failure to do so may im-
pair the performance of these devices.
The owner is responsible for maintain-
ing 'their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Page 1 of 2
Technical
Data
Sizes
3/4" to 3"
Maximum Working Pressure
1750s)
Approvals
UL, FM, C -UL, NSF, LPCB, MEA, and
the City of Los Angeles. (Refer to In-
stallation Handbook IH -1900 dated
June 2008 for exact listing/approval
information.)
Manufacture Source
U.&A.
Material
• Pipe: ASTM F442, SDR 13.5
• Fittings: ASTM F438 (Sch. 40) and
ASTM F439 (Sch. 80), ASTM F1970
Color
Orange
pith r espons e"
HOMO FIRE SORT 4iKLIft Svs'r&M
BUTTE
COUNTY
MAR 0 9 2011
DEVELOPMENT
SERVICES
PERMIT # 912- 0'39y
BUTTE COUNTY DEVELOPMENT SERVICES
REVIEVVED FOR
CODE OMPLIA CE
DATE BY C
BlazeMastety is a registered trademark
of The Lubrizol Corporation
JUNE, 2008 TFP1916
Page 2: of.2
Installation
TycoO CPUC Pipe and Fittings pro=
duced by Tyco Fire & Building Prod-
ucts (TFBP) are to be installed in
accordance with installation Hand-
book .IH -1900 dated June 2008.
t'aarle' and
%Via' illtenance
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance:with this docu-.
ment, as well as with the applicable
standards of the National Fire Protec-
tioh Association (e.g., NFPA 25), in
addition to :the standards of any
authority having jurisdiction. The in-
stalling contractor or product manufac-
turer should be contacted relative to
any questions.
Automatic sprinkler systems should be
Insp'e'cted, tested, and maintained by
qualified Inspection Service in accord-
ance, with local requirements and/or
national codes.
Galore closing.a fire.protection system
control valve for inspection or mainte-
nanca? work on the"Tire'protectiori sys-
tem that it controls, permission to shut
down the affected fire protection,sys-
tem must first be obtained from the
proper authorities and all personnel
who may be affected by :this action
must be notified.
Aftei placing a Tire p- rot `system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary andlor central sta-
tion alarms.
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and JWiiriteined
under normal use and service. This
warranty will expire ten (10) years
from date of 'shipment by TFBP. No
wiarranty is given for.prodUcts or com-
portents manufactured by companies
not affiliated by ownership with TFBP
orfor products and components which
have been subject to misuse, improper
installation; corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Pebtectiori Association, antiltor the
standards of any other .Authorities
Having, Jurisdiction. Materials .found
by TFBP to be defective shall be either
repaired or replaced, .at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it;
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability .or under
any other legal theory, for incidental,
Indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was Informed about the possibility of
§uch�darhd§6s; antl iii no event "shall
TFBP's liability exceed an amount
equal to the.sales price.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is Made in contract, t6rt, Strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not.affect the remainder.
tr7 2tItT8 T1fct3 Fl�E BUtLDIN PRt70t3C75, 451 North Gannon Avenue, Lansdale. Pennsylvania 19446
TFP19115
tqco Fire Suppression
& Fr Building �cducts
mpi d response-
Technical Services $00-381-93121+1-401-781-8220 NOME FiRE SP91NKLER SvsTEM
www.tyco-fire.com
Serie LF11 Residential SprYnlrlers
Flat -Plate Concealed Pendent
4.9 K -Factor
General
Description
The TYCO RAPID RESPONSE Series
LFII Residential Flat -Plate Concealed.
Pendent Sprinklers (TY2524) are decora-
tive, fast response, fusible solder sprin-
klers designed for use in residential oc-
cupancies such: as homes, apartments,
dormitories, and hotels.
The Cover Plate/Retainer Assembly con-
ceals the sprinkler operating compo-
nents above the ceiling. The fiat profile
of the Cover Plate provides the optimum
aesthetlealiyappealing sprinkler design.
Additionally, the concealeddesignof the
Series LFII Residential Flat -Plate Con-
cealed Pendent Sprinklers provides 1/2
inch (12,8 mm) vertical adjustment. This
adjustment provides a measure of fiex-
ibility'when cutting fixed sprinkler drops.
The Series LFII Residential Flat -Plate
Concealed Pend_ ent Sprinklers are in-
tended for use in the following systems,
Wet and dry pipe residential sprin-
kler systems for one- and two•fam-
ity dwellings and mobile homes per
NFPA 13D
• wet and dry pipe residential sprin-
kler systems for residential occu-
pancies up to and including four.sto-
ries in helght,per NFPA 13R
• wet and dry pipe sprinkler systems
for the residential portions of any
occupancy per NFPA 13:
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the 'INSTALLER
WARNING" that provides cautions
with.respect to handling and irwal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a. sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 6'
Historically, residential sprinklers, based
on their Listing, have been limited to
wet pipe sprinkler systems to assure
speed of water delivery for a given pre-
scribed design area (number of design
sprinklers).
The Listing for the Series LFII Residen-
tial Flat -Plate Concealed Pendent Sprin-
kler now offers the laboratory approved
option of designing dry pipe residential
sprinkler systems.
For dry systems, as described in U:S.
Patent 7,712;543, through extensive
testing it has been determinedthat the
number of design sprinklers (hydrau-
lic design area) for the Series LFII Resi-
dential Flat -Plate Concealed Sprinklers
(TY2524) need not be increased over the
number of design sprinklers (hydrau�
lic design area) specified for wet pipe
sprinkler systems, as is customary for
density/area sprinkler systems designed
per NFPA 13,13D, or 138.
Consequently, the Series LFII Residen-
tial Fiat -Plate Concealed Sprinklers
(TY2524) offer the features of non -wa-
ter filled pipe in addition to not having to
Increase the number of design sprinklers
(hydraulic design area) for systems de-
signed to NFPA 13,13D, or 13R. Non -
water filled pipe will permit options for
areas sensitive to freezing,
The Series LFII Residential Flat -Plate
Concealed Pendent Sprinkler has a 4.9
(70,8) K -factor that provides the required
residential flow rates at reduced pres-
sures, enabling smaller pipe sizes and
water supply requirements.
This sprinkler has been designed with
heat sensitivity and waiter distribution
characteristics proven 1614p in the con-
trol of residential fires and to improve
the chance for occupants to escape or
be evacuated.
The Series LFII Residential Fiat -Plate
Concealed Pendent Sprinklers are
shipped with a Disposable Protective
Cap. The Protective Cap protects the
sprinkler during ceiling installation or
finish. After ceiling installation is com-
plete, the Protective Cap is removed
AUGUST 2011
and the Cover Plate/Retainer Assem-
bly is Installed. Removing the Protec-
tive Cap is required for proper sprinkler
performance:
wo—TICE
The Series LFII Residential Flat -Plate
Concealed Pendent Sprinklers (TY2524)
described herein must be installed and
maintained in compliance with this doc-
ument and with the applicable standards
of the National l=ire Protection Associa-
tion, In addition to the standards of any
authorities having Jurisdiction. Failure
to do so may impair the performance
of these devices.'
Owners are responsible for maintaining
their fire protection system and devices
in proper operating condition. The In-
stalling contractor or sprinkler manu-
facturer should be contacted with any
questions.
ModellSprinkler
1dentification
Number (S/IN)
TY2524
TFP443
TFP443
Page 2 of 6
(a) For coverage area dimensions less than or between those indicated; use the minimum required flow for the next highest coverage area for which
Hydraulic Design aaction under the Design Criteria are, stated.
(b) The Minimum Flora requirement is based on minimum flow in GPM (LPM) from each spunkier, The associatedresidual pressures are calculated using
the nominal K -factor. Refer to 'Hydraulic Design' in'the Design Cutena.sectionfor details.
(c) For NFPA i30 2010 applications; Horizontal Ceiling criteria shall be used for certain sloped ceiling configurations up to 8:12 pitch.
Refer to TIA 16288 for allowed sloped ceiling limitations when using iwrizontaf ceiling criteria.
(d) For NFPA 138 applications, Horizontal Ceiling criteria may be used for sloped ceiling configurations up to 8:12 pitch when acceptable to
the Local Authority Having Jurisdiction.
(e) For NFPA 13 residential applications, the greater of 0.1 GPM/FL' over the design area or the flow in accordance with the criteria in
Table A must be used,
TABLE A
SERIES LFII RESIDENTIAL, FLAT -PLATE CONCEALED PENDENT SPRINKLER (TY2524)
NFPA 13,13D AND 13R HYDRAULIC DESIGN CRITERIA.
W-wET PIPE SYSTEMS -
WET PIPE SYSTEM N
Maximum
Minimum Flow and Residual Pressure
Horizontal Ceiling taa>;l
g
Sloped Ceiling tan,°i
Sloped Cellingt°-"-)
Maximum
Covera�e
Maximum
Spacing
Area
(Maximum 2 -inch rise
(Greater than 2 -inch rise
(Greater than, 4 -inch rise
Ft, x Ft.
Ft.
for 12=inch run)
up to maximum 4 -inch
up to maximum 8 -inch
(m x m)
(m)
9.4 psi 0,65 bar)
rise for 12 -Inch run)
rise for 12 -inch run)
15 GPM (56,8 LPM)
(4,3 x 4,3)
160-F (71-C)
760°F(TVC)
160°F (71°C)
16
16 GPM (80;6 LPM)
Sprinkler
Sprinkler
Sprinkler
12 x 12
12
13 GPM (49,2,LPM)
17 GPM (64,3 LPM)
17 GPM (64,3 LPM)
(3,7 x 3,7)
(3;7)
7.0 psi (0;48 bar)
12.0 psi (0,83 bar)
12.0 psi (0,83 bar)
14 x 14
14
13 GPM (49,2 LPM)
17 GPM (64;3 LPM)
17 GPM (64,3 LPM)
(4,3 x 4,3)
(4,3)
7.0 psi (0,48 bar)
12,0 psi (0,83 bar)
12.0 psi (0,83. bar)
16 x 16
16
13 GPM (49,2 LPM)
17 GPM (64,3 LPM)
17 GPM (64,3 LPM)
(4,9 x 4,9)
(4,9)
7,0 psi (0,48 bar)
12.0 psi (0,83 bar)
12.0 psi (0,83 bar)
i8 x 18
18
17 GPM (64,3 LPM)
22 GPM (83,3 LPM)
22 GPM (83,3 LPM)
(5,5 x 5,5)
(515)
'12.0 psi (0,83 bar)
20.2 psi (1,39 bas)
20.2 psi (1,39 bar)
20 x 20
20
20 GPM (75,7 LPM)
24 GPM (90,8 LPM)
24 GPM (90,8 LPM)
(6;1 x 6,i)
(6,1)
16:7 psi (1,15 bar)
24.0 psi (1,65.bar)
24,0 psi (1,65 bar)
(a) For coverage area dimensions less than or between those indicated; use the minimum required flow for the next highest coverage area for which
Hydraulic Design aaction under the Design Criteria are, stated.
(b) The Minimum Flora requirement is based on minimum flow in GPM (LPM) from each spunkier, The associatedresidual pressures are calculated using
the nominal K -factor. Refer to 'Hydraulic Design' in'the Design Cutena.sectionfor details.
(c) For NFPA i30 2010 applications; Horizontal Ceiling criteria shall be used for certain sloped ceiling configurations up to 8:12 pitch.
Refer to TIA 16288 for allowed sloped ceiling limitations when using iwrizontaf ceiling criteria.
(d) For NFPA 138 applications, Horizontal Ceiling criteria may be used for sloped ceiling configurations up to 8:12 pitch when acceptable to
the Local Authority Having Jurisdiction.
(e) For NFPA 13 residential applications, the greater of 0.1 GPM/FL' over the design area or the flow in accordance with the criteria in
Table A must be used,
TABLE A
SERIES LFII RESIDENTIAL, FLAT -PLATE CONCEALED PENDENT SPRINKLER (TY2524)
NFPA 13,13D AND 13R HYDRAULIC DESIGN CRITERIA.
W-wET PIPE SYSTEMS -
(a) For coverage area dimensions less than or between those Indicated; use the minimum required flaw for the n"t highest
coverage area for which Hydraulic Design section under the Design Criteria are stated.
(b) The Minimum Flow requirement is based on minimum flow.ln GPM (LPM) from each sprinkler rhe associated residual pressures
are calculated using the nominal K -factor. Refer to 'Hydraulic Design' in the Design Criteria section fru details,
(c) For NFPA 136 2010 applications, Horizontal Ceiling criteria shall be used for certain sloped ceiling configuratloris up to 8:12 pitch.
Refer to TIA tU2811 for allowed:sloped ceiling limitations when using horizontal ceiling criteria.
TABLE B
SERIES LFII.RESIDEN17AL FLAT -PLATE CONCEALED PENDENT SPRINKLER (TY2524)
NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA
- DRY PIPE SYSTEMS --
DRY PIPE SYSTEM n')
Maximum
Minimum Flow and Residual Pressure
Coverage.Area
Maximum Spacing
Horizontal Ceiling Minimum Flow and Residual Pressure al
Ft. x
(m)
(Maximum 2 -Inch Rise for 12 -Inch Run)
(m x mm)
)
160°F (71°C) Sprinkler
12 x 12
122
15 GPM 56,8 LPM)
(3,7 x 3,7)
(3,7)
9.4 psi 0,65 bar)
14 x 14
14
15 GPM (56,8 LPM)
(4,3 x 4,3)
(413)
9.4 psi (0,65 bar)
16 x 16
16
16 GPM (80;6 LPM)
(4,9 x 4,9)
(419)
10,7 psi (0,74 bar)
18 x 18
18
17 GPM (64,3 LPM)
(515)
12:0 psi (0,83' bar)
20 x 20
20'
21 GPM (79,5 LPM)
(6,1 x 8,1)
(6;1)
18,4 psi (1,27 bar)
(a) For coverage area dimensions less than or between those Indicated; use the minimum required flaw for the n"t highest
coverage area for which Hydraulic Design section under the Design Criteria are stated.
(b) The Minimum Flow requirement is based on minimum flow.ln GPM (LPM) from each sprinkler rhe associated residual pressures
are calculated using the nominal K -factor. Refer to 'Hydraulic Design' in the Design Criteria section fru details,
(c) For NFPA 136 2010 applications, Horizontal Ceiling criteria shall be used for certain sloped ceiling configuratloris up to 8:12 pitch.
Refer to TIA tU2811 for allowed:sloped ceiling limitations when using horizontal ceiling criteria.
TABLE B
SERIES LFII.RESIDEN17AL FLAT -PLATE CONCEALED PENDENT SPRINKLER (TY2524)
NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA
- DRY PIPE SYSTEMS --
BODY
SEALING
(1/2° NPT) �^---_`_ _--M
_ ASSEMBLY
CAP
FACE OF
SPRINKLER
1/2°
THREADED
SPRINKLER
ASSEMBLY
WRENCHING
SADDLE " y
FITTING
AREA
SUPPORT
SPRINKLER
COMPRESSION
CUP WITH
W
- COVER
(47,6 mm �r _ -�-
SCREW
ROLL FORMED
1/8° GAP
t3,2 mm)
RETAINER
(3,2 mm)
THREADS
(27,2 mm)
COVER- SPRINKLER -7/8`
LEVER
GUIDE
RETAINER SUPPORT CUP
PIN
y 1/8' (28,6 mm)
ASSEMBLY ASSEMBLY
MW
(4,8 mm)
SOLDER LINK
3-3/16° DIA.
ELEMENT
GUIDE PIN
TIP
PROTECTIVE CAP OPERATED POSITION
HOUSING
FIGURE 3
r i
DEFLECTOR
iir -- -`-
r_�-"'�
{. (OPERATED
DEFLECTOR
--� -%�
POSITION]
SPRINKLER/SUPPORT OUP
ASSEMBLY
Th1.READINTO
RETAINER
SUPPORT CUP
WITH THREAD.
UNTIL MOUNTING"
DIMPLES
SURFACEIS
FLUSH WITH
EJECTION
COILING
SPRING
SOLDER COVER_PLATE/RIETAINER COVER
T/6 ASSEMBLY PLATE
FIGURE 1
FLAT -PLATE CONCEALED. PENDENT SPRINKLER (71!2824)
— ASSEMBLY —
TFP443
Page 3 of 6
WRENCH
RECESS
PUSH WRENCH
IN TO. ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 2
W -TYPE 18
-- SPRINKLER WRENCH —
2-i/2° DIA.
SPRINKLER -
(63,5 mm)
1/2° (12,7 mm)
FACE OF
SUPPORT CUP
1/2°
THREADED
SPRINKLER
ASSEMBLY
NPT
ADJUSTMENT
FITTING
OPERATED
SPRINKLER
1-718°ty/8"
W
- COVER
(47,6 mm �r _ -�-
-,.�- PLATE
1/8° GAP
t3,2 mm)
RETAINER
(3,2 mm)
(27,2 mm)
COVER- SPRINKLER -7/8`
MOUNTING
RETAINER SUPPORT CUP
SURFACE
y 1/8' (28,6 mm)
ASSEMBLY ASSEMBLY
MW
(4,8 mm)
3-3/16° DIA.
DISPOSABLE DEFLECTOR IN
(8i ,O mm);
TIP
PROTECTIVE CAP OPERATED POSITION
FIGURE 3
PROTECTIVE CAP AND AC77VATED DEFLECTOR
-� 'INSTALLATION DIMENSIONS —
TFP443
Page 4 of 6
Technical
Data
Approvals
UL and C -UL Listed
NSF -61 Certified
The Series LFII Residential Flat -Plate
Concealed Pendent Sprinklers are only
listed with the'Series LFII Concealed.
Cover Plates having a factory -applied
.finish'.
Maximum Working Pressure
175 psi (12,1 bar)
Dischargge Coefficient
K=4.9 GPMJpsi"2 (70,6 LPMJbar'-)
Temperature Ratin
Sprinkler: 160°F (71°C�
Cover Platt+: 139"F (59°C)
Vertical Adjustment
1/2 inch (12,7 mm)
Finishes
Refer to .the Ordering Procedure
section.
Physical Characteristics
• Cover Plate/Retainer Assembly:
Cover Plate ............. Copper
Ejection Spring .... Stainless_ Steel
Retainer ... :..... ....... Brass
'OS prinkler/Support Cup Assembly:
Body . ................ Brass
Cap ..................Bronze
Saddle ................... Brass
Sealing Assembly ..... ; .Beryllium
Nicked w/Teflon'
Soldered. Link Halves Nickel
Lever . Bronze
Compression Screw .. , Brass
Deflector . .........
.... Bronze
Guide Pin Housing...... . `Bronze
Guide Pins ............. Bronze
Support Cup ....... ..... Steel
'%!(eration
When exposed to heat from a fire, the
Cover Plate, which is normally soldered
to the Retainer at three points, fails away
to expose the Sprinkler/Support Cup As,
sembly. At this point, the Deflector, sup-
ported by the Guide Pins, drops down
to its operated position.
The Solder Link Element of the Sprinkler/
Support Cup Assembly is comprised of
two link halves that are soldered togeth-
er with a thin layer of solder, when the
rated temperature Is reached, the sol-
der melts and the two link halves sepa-
rate, allowing the sprinkler to activate
and flow water.
t Registered trademark of DuPont.
Design
Criteria
The TYCO RAPID RESPONSE Series
LFII Residential Flat -Plate Concealed
Pendent Sprinklers (TY2524) are UL
and C -UL Listed for installation in ac-
cordance
with the following criteria.
IBM
When conditions exist'thatare outside
the scope of the provided criteria, re-
fer to the Residential Sprinkler Design
Guide TFP490 for the manufacturer's
recommendations that may accept-
able to the Authority Having Jurisdiction.
The Series LFII Residential Flat -Plate
Concealed Pendent Sprinklers must
not be used in applications where the
air pressure above the ceiling is greater
than That below. Down drafts through
the Support Cup can delay sprinkler op-
eration in a fire situation.
System Type
Per the UL Listing, wet pipeand dry pipe
systems may be utilized: Per the C -UL
Listing, only wet pipe systems may be
utilized.
• For dry systems not using CPVC,
corrosion -resistant or internally gal-
vanized pipe shall be utilized with
the'sprinkiers described in this date
sheet
• For dry systems, pendent sprinklers
shall be installed on return bends,
where the sprinklers, return bends,
and branch line piping (that is, po-
tential areas for trapped water) are in
areas at or above 40°F(4"C)
Refer to technical data sheet TFP466
about the use of Residential Sprinklers
.in:residentiai dry pipe systems.
IL NOTICE
When corrosion -resistant or internally
galvanized pipe and fittings with a po-
table water supply are utilized, return
bends need not be installed. However,
any portion of the piping that has the
potential to trap water must be main-
tained at or above 40°F (4'C) unless pro-
vision to drain such areas Is provided
and maintained dry.
Water Delivery
Men using the Series LFII Residential
Flat -Plate Concealed Pendent Sprinklers
(TY2524) in dry pipe sprinkler systems,
the requirements for "Dry System Water
Delivery" per Section 8.3.4.3 of the 2010
edition of NFPA 13D apply. For a resi-
dential hazard, in no case shall the time
of water -delivery exceed 15 seconds for
the most remote operating sprinkler.
Hydraulic Design
(NFPA 13D and 13R)
The minimum required sprinkler flow rate
for systems designed to NFPA 13D or
NFPA 13R are given in Tables A and B
as a function of temperature rating and
the maximum allowable coverage areas.
The sprinkler flow rate Is the minimum
required discharge from each of the total
number of "design sprinklers" as speci-
fied in NFPA 130 or NFPA 13R.
NOT/E
The number of "design sprinklers" spec-
ified in NFPA 130 and 13R for wet pipe
systems is to be applied when design-
ing -dry pipe systems. There is no need
to increase the design area, as is the
case for density/area systems, in ac-
cordance with U.S. Patent 7,7.12,543.
Refer to technical data sheet TFP485
for details.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
Is to be the greater of the following:
• The...flow rates given in Tables A and B
for NFPA 130 and 13R as a function of
temperature rating and the maximum
allowable coverage area.
• A minimum discharge of 0.1 GPM/
sq. ft. over the "design area" com-
prised of the four most hydraulically
demanding sprinklers for the -actual
coverage areas being protected by
the four sprinklers.
NOTICE
The number of "design sprinklers"
specified in NFPA 13 for wet pipe sys-
tems is to be applied when designing
dry pipe systems. There is no need to
increase the design area, as is the case
for densitjvarea systems, in accordance
with U.S. Patent 7,712,543. Refer to
technical data sheet TFP485 for details.
Obstruction to Water
Distribution.
Sprinklers are to be located in accor-
dance with the obstruction rules of
NFPA 13D, 13R, and 13 as applicable
for residential sprinklers as well as with
the obstruction criteria described within
the TYCO technical data sheetTFP490.
Operational Sensitivity
Install sprinklers relative to the ceiling
mounting surface as shown in Figure 3.
Sprinkler Spacing
The minimum spacing between sprin-
klers is 8 feet (2,4 m).
The maximum spacing between sprin-
klers cannot exceed the length of the
coverage area (Table A) being hydrau-
lically calculated; for example, a maxi-
mum of 12 feet for a 12 % x:12 ft. cov-
erage area or.20:feet for a 20 ft. x:20 ft.
coverage area..
Installation
The TYCO RAPID RESPONSE Series
LFII Residential Flat -Plate Concealed
Pendent Sprinklers must be.instailed
in accordance with the following
instructions:
NOTICE
Damage to the Solder Link Element dur-
ing installation can be avoided byhah-
dling the sprinkler by the Support Cup
only; that is, do not apply pressure to the
Solder Link Element (Figure 1).
Obtains leak -tight 1/2.inch NPT sprinkler
joint by applying a minimum -to -maxi-
mum torque of 7 to 14 ft. -lbs. (9;5 to 19,0
Nm)..Higher levels of torque can distort
the sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient ad. fustment in the Cover Patel
Retainer Assembly by under or over -
tightening the sprinkler. Re -adjust the
positimof the sprinkler fitting to suit.
1. Install pendent sprinklers in the
pendent position, with the center-
line 'of the sprinkler perpendicular
to the mounting surface.
2. Remove the Protective Cap.
3. With pipe -thread sealant applied
to the pipe threads, and using the
W Type 18 Wrench shown in Figure
2, install and tighten the Sprinkler/
Support Cup Assembly into the fit-
ting. The W -Type 18 Wrench ac-
cepts 81/2 inch ratchet.drive.
4. Replace the Protective Cap by
pushing it upwards until it bottoms
out against the Support Cup. The
Protective against,
prevent dam-
age to the Deflector and Guide.
Pins during ceiling installation and/
or during application of the finish
coating of the ceiling.
As.long as the protective Cap.re-
mains in place, the system is con-
sidered "Out Of Service
After the ceiling has been complet-
ed with the 2-1/2 inch (63 mm) dt-
ameter hole and in preparation liar
installing the Cover Plate/Retain-
er Assembly, remove and discard
the Protective Cap, and verify that
the Deflector moves up and down
freely.
If the Sprinkler has been damaged
and the Deflector does not move up
and down freely, replace the entire
Sprinkler assembly. Do not attempt to
modify or repair a damaged sprinkler.
6. Screw on the Cover Plate/Retainer
Assembly until its flange contacts
the ceiling.
Do not continue to screw on the
Cover Plate/Retainer Assembly such
that. it lifts a ceiling panel out of Its
normal position.
If the Cover. Plate/Retainer Assembly
cannot be engaged with the Mounting
Cup or the Cover Plate/Retainer As
sembly cannot be engaged sufficiently
to contact the ceiling, the Sprinkler
Fitting must be repositioned.
Carrs and
Maintenance
'The TYCO RAPID RESPONSE Series
LFI Residential Flat -Plate Concealed
Pendent Sprinkler (TY2524) must be
maintained and serviced in accordance
with the following instructions.
NOTICE
Before closing a fire protection system
main control valve for maintenance work
on the fire protection system that. it con-
trols, obtain permission to shutdown the
affected fire protection system from the
proper authodfles and notify all person -
.net who may be affected by this action.
When properly installed, there is a nomi-
nal 118 Inch (3,2 mm) air gap between
the lip of the Cover Plate and the ceil-
Ing, as shown in Figure 3. This air gap
is necessary for proper operation of the
sprinkler by allowing heat flow from a
fire to pass below and above the Cover
Plate to help assure appropriate release
of the Cover Plate in a fire situation. If the
ceiling needs. repainting after sprinkler
installation, exercise care to ensure that
the new paint does NOT seal off any of
the air gap. Failure to do so may impair
sprinkler operation.
TFP443
Page 6 of 6
Absence of a Cover Plate can delay the
sprinkler operation in a fire situation.
Do not pull the Cover Plate relative to the
Retainer. Separation may result,
Exercise care to avoid damage to sprin-
klers before, during, and after installa-
tion. Never paint, plate, coat, or other-
wise atter automatic sprinklers after they
leave the factory,
Never repaint factory -painted Cover
Plates. When necessary,.replace cover
plates with factory -painted units. Non -
factory applied paint can adversely de-
lay or prevent sprinkler operation in the
event of a fire and is not permitted by
NEPA.
Replace sprinklers that:
• were damaged by dropping, striking,
wrench twisting, wrench slippage, or
the like.
• were modified or over -heated.
• are leaking or exhibiting visible signs
of corrosion,
Responsibility lies With owners for the
Inspection, testing, and maintenance of
their fire protection system and devices
In compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(for example, NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or sprinkler manufacturer
regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
TFP44S
Page 6 of 6
'Limited
Warranty
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the orig-
Inal Buyer for ten (10) years against de-
fects in material and workmanship when
paid for and properly installed and main-
tained under normal use and service.
This warranty will expire ten (10) years.
from date of shipment by TFSBP. No
warranty is given for products or com4
ponents manufactured by companies
not affiliated by ownership with TFSBP
or for products and components which
have been subject to misuse, Improper
installation; corrosion, or which have not
been installed, maintained, modified or
repaired in.accordance with applicable
Standards of the National Fire Protection
Association, andlor the standards of any
other Authorities Having Jurisdiction.
Materials found by TFS13P'to be defec-
tive shall be either repaired or replaced,
at TFSBP's sole option. TFSBP neither
assumes, nor authorizes any person to
assume for It, any other obligation In
connection with the sale of products or
parts of products. TFSBP shall, not be
responsible for sprinkler system design
errors or inaccurate or incomplete in-
formation supplied by Buyer or Buyer's
representatives.
In no event shall TFSBP be liable, in con-
tract, tort, strict liability or under any oth-
er legal theory, for incidental, indirect,
special or consequential damages, in-
cluding but not limited to labor charg-
es, regardless of whether TFSBP was
informed about the possibility of such
damages, and in no event shall TFSBP's
liability exceed an amount equal to the
sales price.
The fateaoi g warranty is made1_,.1r Jjau
of aoy and.•all other wArranties. ex resss
or implied. includingwarranties of mer-
chantability and fitness for a particular
purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on fail-
ure of or detect in products, materials or
components, whether the claim is made
in contract, tort, strict liability or any oth-
er legal theory.
This warranty will apply to the full extent
permitted bylaw. The invalidity, in whole
or part, of'any portion of this warranty
will not affect the remainder.
Ordering
Procedure
Contact your local distributor for avail-
ability.. When placing an order, indicate
the full product description and Part
Number (PIN).
Sprinkler/Support Cup Assembly
Specify Series LFII Residential Fiat -Plate
Concealed Pendent Sprinkler (TY2524),
K=4.9 (70,6), without Cover Plate/Retain-
er Assembly, PIN 51-114-1-160.
Cover Pilate/detainer Assembly
Specify Cover Plate/Retainer Assem-
bly with finish (below) for the Series LFII
Residential Flat -Plate Concealed Pen-
dent Sprinkler (TY2524), K=4.9 (70,6),
P/N (below):
Ziff white .................. PIN 58=201-0-135
Pura White'
(RAL9010) ......:........ PIN 66-201.3-135
Signal White—
(RAL9003) .............. PIN 66-201-4-135
Standard White ("Grey White)
(RAL9002) .............. PIN 56-201-5-135
Custom_.. ..............PIN 56-201-K-135
Eastern Hemisphere sales only
" Previously known asBrightWhite
Mote -Ali Custom Cover Plates are painted us-
ing Sherwin Williams interior Latex Paint. Contact
TYCO Customer Service with any questions related
tocustom orders.
Optional Cover Plate/Retainer
Assembly for Horizontal d=rat)
Coiling Applications Only
Specify Cover Plate/Retainer Assem-
bly with finish (below) for the Series LFII
Residential Fiat -Plate Concealed Pen-
dent Sprinkler (TY2524), K=4.9 (70,6),
PIN (below):
Off White ............ . .....PIN 56-122-0.135
Pure White'
(RAL9010) .:.... ......... PIN 66122.3-135
Signal White"
(RAL9003) ............... ... PIN 56-122-4-196
Custom .......... . .......... PIN 56.122-x-185
Eastern Hemisphere sales only
Previously known as Bright White
Note: All Custom Cover plates are painted us-
ing Sherwin Williams interior Latex paint. Contact
TYCO Customer Service with any questions rotated
to custom orders.
Sprinkler Wrench
Specify W Type 18 Sprinkler Wrench,
PIN 56-000-1-265,
Copyright 0 2010,.2011 Tyco Fire Suppression & Building Products. All rights reserved.
§Z/D
P.O. Box 3365 South. El Monte, CA 91733 '626.44460541 Fax 626.444.3887 www. Afcon.org
51.4
OFFSET CPVC HANGER
SIZE- 3/4" thru 3"pipe.
MATERIAL - Carbon Steel.
FINISH - Mil..Galvanize'&
LISTINGIAPPROVAL-
263 - EX 4231, FX 2551
PATENT - No. 6,649,2 ' 78.
FUNCTION - 3/411-210 Hanger/restrainer for horizontal CPVC, Copper or Steel pipe..
Listed hanger/restrainer in all 3 mounting positions, i.e. vertical surface and both top and.
bottom of horizontal surface. Provides listed verticaUlateral restraint and prevents upward
movement of pipe that supplies a pendent sprinkler below a, ceiling,
Size 2 %4' Hanger f6r hdrizontai CPVC pipe. Listed hanger in all 3m.ounting positions..
i 'e, vertical surface and both top and bottom of horizontal surface.
Size 311 Hanger for horizontal CPVC pipe in two mounting posifionsi side and bottom.
i.e. vertical surface and bottom of horizontal surface.
Stabilizcsvertical piping by providing horizontal -restraint..
TNSTA:LLATION - Per NFPA. 13, 1311 and 13D.
Space by pipe type. Install on 'wood, concrete or steel - See Drawings.
Snap over pipe then squeeze strap back allowing pipe to slide freely. Listed
When #905 threads are exposed in wood, install 9906 barking nut 3/4'
.MaiLNOTE:
Vetify that all assembly components are dialled of any surface oil.
FASTENERS - Uftisfed, perNFPA 13
WOOD - 31/4" - 3` CPVC pipe - #905 screw- no pre -drill.
3/4" -- 2" Copper pipe - *905 screw- no,pre-drill.
31411- 21, Steel pipe -.1/4"x.1 1/2" lag screw - no pre -drill.
Thru i/8" gypsum board- 114" x 2" tag screw.
STEEL-inin.18GA.- 3/4"-3"CPUC pipe- 1/4" or#14Tek Screw.
3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Steel pipe 1/4" or #14 Tek Screw.
CONCRkTE:Required minimum load each, fastener= 5AA10+2501bs.
2
FEATURES
* .1 1/2" Ciffict - loose fit allows pipe to slide.
* 3/4" and I " pipe size made with common center -line.
'`Patented design for superior strength.
• Offset edge eliminates abrasion.
• .AFCON#905 screw hAs.5/16" hex head - included.
ORDERING - Part # and:pipe size.
AF, CON #906 backing nut sold separately.
'l -t-0
Listed Restraint
314" thrtj 2*
SixY.ifie i1 FCON produ.'1; a�c ezclusivEly daignod tube nx:q#tr�ik t3\R;Y witb ntieer A£CfI:V prcduris im:lipling parte anti fasteners, tc.�ilting in a listod snvyttac, resitniner ur tautgcr tts;zmbly.
DISCLAIMER- AMON Will INM%watit ag.hinm the Whim of it% pfadwb; wbcn tkwd in combination with ather ptYAWs, pam tit systems
not n1lm6clumder sold by AAff0XArCO3Vehal) NVIT be liable wKki any cl=mstnnees whatsa,,vtu for any, dirma m inditcd, inc;dcjnui (a canxqu-niihi &irum ar:tnyund, including but nin
lindled to loss oftmsims numfit, m.,,tiafi nvnAPC0jVPn%1=s baw been, or am used.
6108
P.O. BOX 3365 SOUTH EL MONTE, CA 91733 626.444.01541 FAx626.444.3887 wwwafcon.org
lu
PIPE / C -P -V -C- HANGER
SIZE - 43/4" duu i" C ' P.V.C. and Copper.
V thru 211 �Steel'.
NWERIAL.- Carbon Steel,
F TISH, - *Ivlil. Galvanized, G 90 Spec.
IN,
LISTING - UL in US and CANADA.
VUN&ION - Hariger,'.support and restrainer for use on C.P.V. C., Copper
or Steel piping installed per N.F.P.A. 13,,13R and 13D.
INSTALLATION -.Install on top, bottom,or side atbeava.
Hanger spacing by pipe type - per NIFPA 13.
UlAisted fusteners tested perNFPA 13, as follows.
IN WOOD
CPUC and Coppqr:- listed hex head screw ffiniished Nvith product.
Steel - 1/4"xI.1/2" lag screw -.needs no prc-drilling.
IN CONICRtTE or fIEAVYSTEEL:
Shot:type fasteners, "On - ly when instAlledprior to pipe insertion '.
FEATURES
* Offset edge for abrasion 6.1millihation and superior strength.
* Retainer dimples secure hanger topipe during installation.
Required fastener furnished with 5116 head, needs no pre -drilling:
ORDERING -.Part #.and pipe size.
NOTE: On copper - insulate pipe,_
8,129/01
RO. BOX 3365 SOUTH EL MONTE, 'CA 91733 626.444.0541 FAX 626.444.3887 www.afdon.org
511
PIPE/ C.P.V.C. HANGER
SIDE'MOUNT
SIZE - 3/4" thru 2" C.P.VC. and Copper.
MATERIAL - Carbon Steel.
RMSH - Mil, Galvanized,. G-90 Spec,
LISTING - UL in US and CANADA
PUNCTION- Hanger, support and restrainer for use on C.P.V.C. of Copper
piping installed per M F.P.A 13,13R aftd, 13D. D.
p g
IN- , STALLAMON - Install on top; bot I bottom or side of.bemn.
'Hanger spacing by pipe type - per N.FPA- 13.
UL listed fasteners tested per NEPA 13, as follows,
IN NVOOD..
CPVC: and Copper_ li.stedhex ]lead screw furnished with product,
IN CONCRETTor HEAVY STEEL:
Shot type fasteners,, "Only when installed prior to pipe insertion"._
U ATURES
*et, Offsedge for abrasion elimination and superiorstrength.
* Ret, a . iner, diniples:sec6re hdh
, ger to pipe durtrig installation.
Required fastener, furnished with 5i'16 head, needs no pre -
ORDERING - Part # and CY.VC. or Copper pipe size.
NOTE: On copper - insulatepipe.
8/2.9/01
FOR SMALL PIPE V,SR—,5
POTTER VANE TYPE WATERFLOW
The Symbol of Protection ALARM SWITCH WITH RETARD
Stock No. 1144440
Installation must be perfomed b qualified personnel and in
and l
accordance with alt national ocal codes and ordinances.
Shock hazard. Disconnectower source before servicing:
Serious injury or death could result.
Risk of explosion. Not for use in hazardous locations. Serious
injury ordeath could result..
The Model VSR-S is a vane type waterflow switch for use on wet
sprinkler systems that use i" (25mm),11/o" (32mm); 1 rh" (38min) or 2"
(50min) pipe size. The unit may also be used as a sectional waterflow
detector on large systems.
The unit contains two single pole double throw snap action switches and
an adjustable, instantly recycling pneumatic retard. The switches are
actuated when a flow of 10 gallons per minute (38 LPM) or more occurs
downstream of the device. The flow condition must exist for a period of
time necessary to overcome the selected retard period.
Enclosure.
The V SR -S switches and retard device'areenclosed in a general purpose,
die-cast housing The cover is held in-place with two tamper resistant
screws which require a special key for removal. A fie ld.installable cover
tamper switch is available as an option which may be used to indicate
unauthorized removal. of the cover. See bulletin number 5401.103 for
installation instructions of this switch.
UL, ULC, CSFINI Listed and NYNtEA Accepted
Service Pressure: Up to 300 PSi (20,7 BAR)
Flow Sensitivity Range for Signal: 4-1.0 CPM (I.5-38 LPM) UL
Maximurn Surge: 18 FPS (5.5 m/s)
Enclosure: Die-cast. red enamel finish
Cover held in place with tamper resistant: screws
Contact Ratings: Two sets of SPDT (Form C)
10:0 Amps at 7251250 VAC
2.0 Amps at 30 VDC Resistive
10mArnps.min. at 24 VDC
Conduit Entrances: Two openings provided for 1/2" conduit.
Individual switch compartments suitable for
dissimilar voltages.
Usage: Listed plastic, copper and schedule 40 iron pipe.
Fits pipe sizes - I" (25mm), 1 1/4" (32mm), 1 1/2" (38mm)
and 2" (50mm)
Note: 12 paddles are fumished with each unit, one far each pipe
size of threaded and sweat TEE, one for I " (25mm) CPVC.
one for I"(25mm) CPVC (Ce.ntral), one for V threaded Nibco
CPVC, and one: for i 1/2" (38ntm) threaded (Japan).
Environmental. Specifications:
• NEMA-4/IP54 Rated enclosure suitable for indoor or outdoor
use with factory installed gasket and die-cast housing when used
with appropriate conduit fitting.
• Temperature range: 40° F to 120° F. (4.5° C to 49° C) UL
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Ri.ictc�iei�.l eccuira d r Grp to four star°ii s NFPA, 133
:National Fire Alarm Code NFPA-72
Optional: Cover Tamper Switch Kit, Stock No. 0090148
(See Fig. 7 for terminations)
Replaceable. Components: Retard/Switch Assembly, stock no.1029030
Installation
These devices may be mounted iti horizontal or vertical pipe. On
horizontal pipe they.shoaid be installed on the top side of the pipe where
they will he accessible.The units shouldnot beinstalled within6" (15cm)
of a valve. drain or fitting which changes the direction of the waterflow.
Select the proper paddle for the pipe;size and type of TEE used see Fig.
I for instructions on changing paddle. The unit has a I " NPT bushing
for threading into a non -corrosive TEE. See Fig. 2 for proper TEL size,
type and installation. Use no more ththree wraps of teflon tape:.
Ian
Screw the device into the TEE fitting as shown in Fig. 2. Care must be
taken to properly orient the device for the direction of waterflow.
i
The vane must not rub the inside of the'1-EE or bind in any way. The
stem should move freely when operiated by hand.
The device can also be used in copper or plastic pipe installations with
the proper adapters so that the specified TEE fitting may be installed
on the pipe run.
;'Vote: Do not leave cover off for an l xtended period of time.
j
Poiter Electric Signal Company, L.LC • 2081 Cruig Road, St..Louis,1v10, 63146-4161 • Phone: 800-325-3936/Canada 838-882-1833 • www.pottersignni.com
PRINTED IN USA
iclFG. 05401206 - REV G
12108
PAGE 1 Or, 3
Up� POTTER. BELLS
The Symbol of Protection PBA -AC & MBA -AC
i lh 1 (0c <�CCC
'these vibrating type lulls are designed for use as :fire; burglar or general
signaling devices. They have loco power consumption and high decibel
ratings. `ilio unit mounts on a standard 4" (101min) Square electrical box
for indoor use or on a modcl'BB.K-I weatherproof backbox or 138X-1
deep weatherproof. backbox .for outdoor applications. Weatherproof
baekbox model BBK-1, Stock No. 1500001.
UL, VtC, and FNf Approved
SizxsAvaitable: 6" (150mm), 8" (200mm)and 30" (250mm)
Voltages Available: 24VAC
120VAC
12V'DC (10.2 trt 'I 5.6) .Polarized
24VDC (20.4 to 31.2) Polarized
Service Ilse: FircAlarm
General Signaling
Burglar Alann
Environment: Indoor or outdoor use (See Note 1)
40° to .150- (40- to 66°C)
(Outdoor use requires weatherproof backbox.)
Termination: AC Bells - 4 No. 18 AVG stranded wires
DC Bells -Terminal strip
Finish. Red powder coating
Optional: Model BBK-1 weatherproofbackbox
Model BBX- 1 deep weatherproof backbox
'Notts:
I_ Minimum dB ratings are calculated from integrated sound pressure
measurements made tit Underwriters Laboratories as specified in UL
Standard 464. U.L. temperature range is -30° to 150°.1 (340 to 660C).
2. Typical dB ratings arc calculated imm measurerninits made witit a
conventional sound level meter and. tine indicative of output levels in
an actual installation.
3. ULC only applies to MBA DC bells.
Size inures
(mm)
Voltage
Model
Number
Stock
:Number
Current
(Max.)'
Typical dB at
1011. (3m).(2)
Minimum dB at
IOft (3m) (1)
6(150)
12VI?C
MI3A126
1756070
.12A
85
76
8 (200)
12VDC
MBA128
1750080
.12A
90
77
10 (250)
12V.fIC
M13A.1210
1750060
.12A
92
78
6(150)
24VDC
MBA246
t750100
.06A
87
77
8 (200)
24VDC
MBA248
175011.0
.06A
91
79
10 (250)
24V1)C
MRA2410
1750090
.06x1
94
80
6 (.150)
24VAC
PBA246
1806024°
17A
91.
78
8 (200)
24VAC
PBA248
1808024'
.17A
94
77
10 (250)
24VAC
PBA2410
18100241
.17A
94
78
6 (150)
I20VAC.
PBA1206
1806120-
.05A
92
83
8 (200)
120VAC
P13A.12011
1808120•
.05A
99
84
--10 (250)
120VAC
PBA12010 1
18 10 120-
.05A
99
86
All DC bells are polarized and have built-in transient proiection.
• Does not have ULC listing.
In outdoor or wet installations, bell must be mounted with
weatherproof backbox, "BH.K.-i or BBX-1. Standard electrical boxes
will riot provide a v<etaherprcof enclosure:. If thL bell and/or assembly
is exposW w moisture:, it may fail or create an electrical hazard.
Patter Electric Signal Company, LLC - 2081 Craig Road, St. Louis, MO. 6314&4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersVal.com
PRINTED Ihf USA MFG. #5400776- REV Y PAGE I OF
31,08
AGGREGATE FLOW ANALYSIS:
TOTAL
N
31.1
GPM
TOTAL
HOSE STREAM ALLOWANCE AT SOURCE
5.0
�
OTHER
SPRINKLER
SYSTEM
HYDRAULIC
ANALYSIS
Page 1
26.1
GP
9.5
13
C:\HASS74\KONYN RESIDENCE.SDF
JOB TITLE:
KONYN RESIDENCE
21
12.5
22
12.5
WATER SUPPLY DATA
9.5
24
11.8
30
11.8
SOURCE
STATIC
RESID.,
FLOW
AVAIL.
TOTAL
REQ'D
NODE
PRESS.
PRESS. @
BOR
PRESS.-
@ DEMAND
PRESS.
TAG
(PSI)
(PSI)
(GPM)
(PSI)
(GPM)
(PSI)
SOURCE
50.0
40.0
38.5
43.3
31.1
20.1
AGGREGATE FLOW ANALYSIS:
TOTAL
FLOW AT SOURCE
31.1
GPM
TOTAL
HOSE STREAM ALLOWANCE AT SOURCE
5.0
GP
OTHER
HOSE STREAM ALLOWANCES
0.0
GPM
TOTAL
DISCHARGE FROM ACTIVE SPRINKLERS
26.1
GP
NODE ANALYSIS DATA
NODE TAG
ELEVATION
(FT)
1
9.0
2
9.0
10
9.5
10A
9.5
11
9.5
12
9.5
13
9.5
20.
9.5
21
12.5
22
12.5
23
9.5
24
11.8
30
11.8
31
11.8
32
11.8
33
13.0
34
1.1.8
TOR
9.5
BOR
1.0
SOURCE
NODE TYPE
K= 4.90
K=-4_90
SOURCE
PRESSURE
(PSI)
7.1
7.0
7:3
7.2
7.4
8.3
9.1
7.9
6.9
7.5
9.3
8.8
7.4
8.0
8:4
8.2
9.0
10.9
15.9
20.1
BUTTE
CO.UNTy
M MAR 0,9'2017
M DEVELOPMENT
SERVICES
9)7-339
PERMIT #
DISCHARGE COUNTY D/E�VELOPMENT SER
®VICES
(GPM) �����WED FOR
13 ODE C PLIANCj
DAlE3-0��BY j�
- - -I'
26.1
r,
SPRINKLER
SYSTEM
HYDRAULIC ANALYSIS
Page 2
C:\HASS74\KONYN
RESIDENCE.SDF
JOB
TITLE:.KONYN
RESIDENCE
PIPE
DATA
PIPE
TAG
Q(GPM)J
DIA(IN) LENGTH
PRESS.
END
ELEV.
NOZ.
PT
DISC. VEL(FPS)
HW(C)
(FT)
SUM.
NODES
(FT)
(K)
(PSI)
(GPM)
FL/FT
(PSI)
Pipe:
1
-13.1
1.101
PL
1.50
PF
0.4
1
9.0
4.9
7.1
13.1
4.4
150
FTG
ET
PE
-0.2
10
9.5
0.0
7.3
0.0
0.031
TL
11.50
PV
Pipe:
2
3.7
1.101
PL
7.00
PF
0.0
10
9.5
0.0
7.3
0.0
1.3
150
FTG
T
PE
0.0
10A
9.5
0.0
7.2
0.0
0.003
TL
12.00
PV
Pipe:
3
13.0
1.101
PL
3.00
PF
0.4
10A
9.5
0.0
7.2
0.0
4.4
150
FTG
2E
PE
0.2
2
9.0
4.9
7.0
13.0
0.031
TL
13.00
PV
Pipe:
4
-9.3
1.101
PL
8.00
PF
0.2
10A
9.5
0.0
7.2
0..0
3.1
150
FTG
T
PE
0.0
11
9.5
0.0
7.4
0.0
0.016
TL
13.00
PV
Pipe:
5
-9.3
1.101
PL
42.50
PF
0.9
11
9.5
0.0
7.4
0.0
3.1
. 150
FTG
ET
PE
0.0
12
9.5
0.0
8.3
0.0
0.016
TL
52.50
PV
Pipe:
6
-9.3
1.101
PL
39.00
PF
0.8
12
9.5
0.0
8.3
0.0
3.1
150
FTG
2E
PE
0.0
13
9.,5
0.0
9.1
0.0
0.016
TL
49.00
PV
Pipe:
7
-9.3
1.394
PL
34.75
PF
0.2
13
9.5
0.0
9.1
0.0
2.0
150
FTG
----
PE
0.0
23
9.5
0.0
9.3
0.0
0.005
TL
34.75
PV
Pipe:
8
-16.8
1.101
PL
14.00
PF
0.7
10
9.5
0.0
7.3
0.0
5.7
150
FTG
----
PE
0.0
20
9.5
0.0
7.9
0.0
0.049
TL
14.00
PV
Pipe:
9
-8.4
1.101
PL
8.50
PF
0.3
20
9.5
0.0
7.9
0.0
2.8
150
FTG
ET
PE
-1.3
21
12.5
0.0
6.9
0.0
0.014
TL
18.50
PV
-Pipe:
10
-8.4
1.101
PL
31.50
PF
0.6
21
12.5
0.0
6.9
0.0
2.8
150
FTG
2E
PE
0.0
22
12.5
0.0
7.5
0.0
0.014
TL
41.50
PV
Pipe:
11
=8.4
1.101
PL
22.50
PF
0.5
22
12.5
0.0
7.5
0.0
2.8
150
FTG
2ET
PE
1.3
23
9.5
0.0
9.3
0'.0
0.014
TL
37.50
PV
Pipe:
12
-17.7
1.394
PL
14.75
PF
0.5
23
9.5
0.0
9.3
0.0
3.7
150
FTG
2E
PE
-1.0
24
11.8
0.0
8.8
0.0
0.017
TL
26.75
PV
Pipe:
13
-17.7
1.394
PL
5.75
PF
0.2
24
11.8
0.0
8.8
0.0
3.7
150
FTG
E
PE
0.0
34
11.8
0.0
9.0
0.0
0.017
TL
11.75
PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
C:\HASS74\KONYN RESIDENCE.SDF
JOB TITLE: KONYN RESIDENCE
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 14 -8.4 1.101 PL 19.25 PF 0.4
20 9.5 0.0 7.9 0.0 2.8 150 FTG 2E PE -1.0
30 11.8 0.0 7.4 0.0 0.014 TL 29.25 PV
Pipe: 15 -8..4 1.101 PL 33.50 PF 0.6
30 11.8 0.0 7.4 0.0 '2.8 150 FTG 2E PE 0.0
31 11.8 0.0. 8.0 0.0 0.014 TL 43.50 PV
Pipe: 16 -8.4 1.101 PL 11.25 PF 0.4
31 11.8 0.0 8:0 0.0 2.8 150 FTG 4E PE 0.0
32 11.8 0.0 8.4 0.0 0.014 TL 31.25 PV
Pipe: 17 -8.4 1.101 PL 13.25 PF 0.3
32 11.8 0.0 8.4 0.0 2.8 150 FTG 2E PE -0.5
33 13.0 0.0 8.2 0.0 0.014 TL 23.25 PV
Pipe: 18 -8.4 1.101 PL 9.50 PF 0.3
33 13.0 0.0 8.2 0.0 2.8 150 FTG ET PE 0.5
34 11.8 0.0 9.0 0.0 0.014 TL 19.50 PV
Pipe: 19 -26.1 1.394 PL 10.00 PF 1.0
34 11.8 0.0 9.0 0.0 5.5 150 FTG 3E PE 1.0
TOR. 9.5 0.0 10.9 0.0 0.035 TL 28.00 PV
Pipe: 20 -26.1 1.394 PL 8.50 PF 1.3
TOR 9.5 0.0 10.9 0.0 5.5 150 FTG 3ETC PE 3.7
BOR 1.0 10.01 15.9 0.0 0.035 TL 37.50 PV
Pipe: 21 -26.1 1.394 PL 68.00 PF 3.3
BOR 1'.0 0.0 15.9 0.0 5.5 150 FTG 3ETG PE 0.9
SOURCE -1.0 SRCE 20.1 (N/A) 0.035 TL 94.00 PV
NOTES:
(1) Calculations were performed by the HASS 7.4 computer program
under license no. 27060373 granted by
'HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
(2) The system has been calculated to provide an average
imbalance at each node of 0.004 gpm and a maximum
imbalance.at any node of 0.077 gpm.
(3) Total pressure at each node is used in balancing the system.
Maximum water velocity is 5.7 ft/sec at pipe 8.
(4) PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
" SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 ,
C:\HASS74\KONYN RESIDENCE.SDF
JOB TITLE: KONYN RESIDENCE
PAGE: P MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L P R C G
Ell Tee 45-e1L couP teeRun Ckvle Gvlve
1.101 5.00 5.00 1.00` 1.00 1.00 4.00 1.00
1.394 6.00 6.00 2.00 1.00 1.00 5.00 2.00.
c
s
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
- C:\HASS74\KONYN RESIDENCE.SDF
JOB TITLE: KONYN RESIDENCE o
0
0
O
O
O R
o a4
r 0
0
a
w
Co
0
�I
N
0
D
''. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
C:\HASS74\KONYN RESIDENCE.SDF
JOB TITLE: KONYN RESIDENCE
WATER SUPPLY CURVE
60+
I
1
i
I
50*
y \
45\
0
P 40* <-40.0 psi @ 38 gpm '
R f Flow Test Point `
E
S 1
S 35+ „
U
R
E I +
30+
P f
S
I 25+
I
20x
I
15+
10+ LEGEND -------n ;
I X = Required Water Supply
1 20.11 psi @ 31.1 gpm 8
5+
I 0 = Available Water Supply
1 43.28 psi @ 31.1 gpm
I n
0++-+---+----+-----+------+--------+--------+---------+-----------+
.200 300 400 500 600 .700 800 900 1000
` FLOW (GPM)
t