Loading...
HomeMy WebLinkAboutB17-0394 000-000-000tqC0Fire &Building Products Technical Services: Tel: (800) 381-9312 1 Fax: (800) 791-5500 B/azemaster g CPUC Fire Sprinkler Pipe & Fittings Submittal Sheet General Description Tyco'D CPVC; Pipe and Fittings pro- duced by Tyco Fire & Building Prod- ucts (TFBP) are designed exclusively for use In wet pipe automatic fire sprin- kler systems. The Tyco CPVC Pipe and Fittings are produced from Blaze- MasterO CPVC compound that is a specially developed thermoplastic compound. composed of post chlorin- ated polyvinyl chloride (CPVC) resin and state of the art additives. Tyco CPVC Pipe and Fittings are easier to install than traditional steel pipe sys- tems, and at the same time, provide superlor heat resistsnra and strength as compared to traditional CPVC and PVC piping materials used in the plumbing trade. Various adapters are available to connect CPVC, pipe to me= tailic piping. Ali female pipe thread adapters have brass inserts for dura- bility. Grooved adapters connect di- rectly to grooved end valves and me- tallic pipe, with flexible. grooved end couplings. NC.ITICE TycoO CPVC Pipe and Fittings pro- duced with BlazeMastet® CPUC com- pound described herein must be in- stalled and maintained in compliance with this document and with the appli- cable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may im- pair the performance of these devices. The owner is responsible for maintain- ing 'their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Page 1 of 2 Technical Data Sizes 3/4" to 3" Maximum Working Pressure 1750s) Approvals UL, FM, C -UL, NSF, LPCB, MEA, and the City of Los Angeles. (Refer to In- stallation Handbook IH -1900 dated June 2008 for exact listing/approval information.) Manufacture Source U.&A. Material • Pipe: ASTM F442, SDR 13.5 • Fittings: ASTM F438 (Sch. 40) and ASTM F439 (Sch. 80), ASTM F1970 Color Orange pith r espons e" HOMO FIRE SORT 4iKLIft Svs'r&M BUTTE COUNTY MAR 0 9 2011 DEVELOPMENT SERVICES PERMIT # 912- 0'39y BUTTE COUNTY DEVELOPMENT SERVICES REVIEVVED FOR CODE OMPLIA CE DATE BY C BlazeMastety is a registered trademark of The Lubrizol Corporation JUNE, 2008 TFP1916 Page 2: of.2 Installation TycoO CPUC Pipe and Fittings pro= duced by Tyco Fire & Building Prod- ucts (TFBP) are to be installed in accordance with installation Hand- book .IH -1900 dated June 2008. t'aarle' and %Via' illtenance The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and de- vices in compliance:with this docu-. ment, as well as with the applicable standards of the National Fire Protec- tioh Association (e.g., NFPA 25), in addition to :the standards of any authority having jurisdiction. The in- stalling contractor or product manufac- turer should be contacted relative to any questions. Automatic sprinkler systems should be Insp'e'cted, tested, and maintained by qualified Inspection Service in accord- ance, with local requirements and/or national codes. Galore closing.a fire.protection system control valve for inspection or mainte- nanca? work on the"Tire'protectiori sys- tem that it controls, permission to shut down the affected fire protection,sys- tem must first be obtained from the proper authorities and all personnel who may be affected by :this action must be notified. Aftei placing a Tire p- rot `system in service, notify the proper authorities and advise those responsible for moni- toring proprietary andlor central sta- tion alarms. Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war- ranted solely to the original Buyer for ten (10) years against defects in mate- rial and workmanship when paid for and properly installed and JWiiriteined under normal use and service. This warranty will expire ten (10) years from date of 'shipment by TFBP. No wiarranty is given for.prodUcts or com- portents manufactured by companies not affiliated by ownership with TFBP orfor products and components which have been subject to misuse, improper installation; corrosion, or which have not been installed, maintained, modi- fied or repaired in accordance with ap- plicable Standards of the National Fire Pebtectiori Association, antiltor the standards of any other .Authorities Having, Jurisdiction. Materials .found by TFBP to be defective shall be either repaired or replaced, .at TFBP's sole option. TFBP neither assumes, nor authorizes any person to assume for it; any other obligation in connection with the sale of products or parts of prod- ucts. TFBP shall not be responsible for sprinkler system design errors or inac- curate or incomplete information sup- plied by Buyer or Buyer's repre- sentatives. In no event shall TFBP be liable, in contract, tort, strict liability .or under any other legal theory, for incidental, Indirect, special or consequential dam- ages, including but not limited to labor charges, regardless of whether TFBP was Informed about the possibility of §uch�darhd§6s; antl iii no event "shall TFBP's liability exceed an amount equal to the.sales price. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is Made in contract, t6rt, Strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not.affect the remainder. tr7 2tItT8 T1fct3 Fl�E BUtLDIN PRt70t3C75, 451 North Gannon Avenue, Lansdale. Pennsylvania 19446 TFP19115 tqco Fire Suppression & Fr Building �cducts mpi d response- Technical Services $00-381-93121+1-401-781-8220 NOME FiRE SP91NKLER SvsTEM www.tyco-fire.com Serie LF11 Residential SprYnlrlers Flat -Plate Concealed Pendent 4.9 K -Factor General Description The TYCO RAPID RESPONSE Series LFII Residential Flat -Plate Concealed. Pendent Sprinklers (TY2524) are decora- tive, fast response, fusible solder sprin- klers designed for use in residential oc- cupancies such: as homes, apartments, dormitories, and hotels. The Cover Plate/Retainer Assembly con- ceals the sprinkler operating compo- nents above the ceiling. The fiat profile of the Cover Plate provides the optimum aesthetlealiyappealing sprinkler design. Additionally, the concealeddesignof the Series LFII Residential Flat -Plate Con- cealed Pendent Sprinklers provides 1/2 inch (12,8 mm) vertical adjustment. This adjustment provides a measure of fiex- ibility'when cutting fixed sprinkler drops. The Series LFII Residential Flat -Plate Concealed Pend_ ent Sprinklers are in- tended for use in the following systems, Wet and dry pipe residential sprin- kler systems for one- and two•fam- ity dwellings and mobile homes per NFPA 13D • wet and dry pipe residential sprin- kler systems for residential occu- pancies up to and including four.sto- ries in helght,per NFPA 13R • wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13: IMPORTANT Always refer to Technical Data Sheet TFP700 for the 'INSTALLER WARNING" that provides cautions with.respect to handling and irwal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a. sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6' Historically, residential sprinklers, based on their Listing, have been limited to wet pipe sprinkler systems to assure speed of water delivery for a given pre- scribed design area (number of design sprinklers). The Listing for the Series LFII Residen- tial Flat -Plate Concealed Pendent Sprin- kler now offers the laboratory approved option of designing dry pipe residential sprinkler systems. For dry systems, as described in U:S. Patent 7,712;543, through extensive testing it has been determinedthat the number of design sprinklers (hydrau- lic design area) for the Series LFII Resi- dential Flat -Plate Concealed Sprinklers (TY2524) need not be increased over the number of design sprinklers (hydrau� lic design area) specified for wet pipe sprinkler systems, as is customary for density/area sprinkler systems designed per NFPA 13,13D, or 138. Consequently, the Series LFII Residen- tial Fiat -Plate Concealed Sprinklers (TY2524) offer the features of non -wa- ter filled pipe in addition to not having to Increase the number of design sprinklers (hydraulic design area) for systems de- signed to NFPA 13,13D, or 13R. Non - water filled pipe will permit options for areas sensitive to freezing, The Series LFII Residential Flat -Plate Concealed Pendent Sprinkler has a 4.9 (70,8) K -factor that provides the required residential flow rates at reduced pres- sures, enabling smaller pipe sizes and water supply requirements. This sprinkler has been designed with heat sensitivity and waiter distribution characteristics proven 1614p in the con- trol of residential fires and to improve the chance for occupants to escape or be evacuated. The Series LFII Residential Fiat -Plate Concealed Pendent Sprinklers are shipped with a Disposable Protective Cap. The Protective Cap protects the sprinkler during ceiling installation or finish. After ceiling installation is com- plete, the Protective Cap is removed AUGUST 2011 and the Cover Plate/Retainer Assem- bly is Installed. Removing the Protec- tive Cap is required for proper sprinkler performance: wo—TICE The Series LFII Residential Flat -Plate Concealed Pendent Sprinklers (TY2524) described herein must be installed and maintained in compliance with this doc- ument and with the applicable standards of the National l=ire Protection Associa- tion, In addition to the standards of any authorities having Jurisdiction. Failure to do so may impair the performance of these devices.' Owners are responsible for maintaining their fire protection system and devices in proper operating condition. The In- stalling contractor or sprinkler manu- facturer should be contacted with any questions. ModellSprinkler 1dentification Number (S/IN) TY2524 TFP443 TFP443 Page 2 of 6 (a) For coverage area dimensions less than or between those indicated; use the minimum required flow for the next highest coverage area for which Hydraulic Design aaction under the Design Criteria are, stated. (b) The Minimum Flora requirement is based on minimum flow in GPM (LPM) from each spunkier, The associatedresidual pressures are calculated using the nominal K -factor. Refer to 'Hydraulic Design' in'the Design Cutena.sectionfor details. (c) For NFPA i30 2010 applications; Horizontal Ceiling criteria shall be used for certain sloped ceiling configurations up to 8:12 pitch. Refer to TIA 16288 for allowed sloped ceiling limitations when using iwrizontaf ceiling criteria. (d) For NFPA 138 applications, Horizontal Ceiling criteria may be used for sloped ceiling configurations up to 8:12 pitch when acceptable to the Local Authority Having Jurisdiction. (e) For NFPA 13 residential applications, the greater of 0.1 GPM/FL' over the design area or the flow in accordance with the criteria in Table A must be used, TABLE A SERIES LFII RESIDENTIAL, FLAT -PLATE CONCEALED PENDENT SPRINKLER (TY2524) NFPA 13,13D AND 13R HYDRAULIC DESIGN CRITERIA. W-wET PIPE SYSTEMS - WET PIPE SYSTEM N Maximum Minimum Flow and Residual Pressure Horizontal Ceiling taa>;l g Sloped Ceiling tan,°i Sloped Cellingt°-"-) Maximum Covera�e Maximum Spacing Area (Maximum 2 -inch rise (Greater than 2 -inch rise (Greater than, 4 -inch rise Ft, x Ft. Ft. for 12=inch run) up to maximum 4 -inch up to maximum 8 -inch (m x m) (m) 9.4 psi 0,65 bar) rise for 12 -Inch run) rise for 12 -inch run) 15 GPM (56,8 LPM) (4,3 x 4,3) 160-F (71-C) 760°F(TVC) 160°F (71°C) 16 16 GPM (80;6 LPM) Sprinkler Sprinkler Sprinkler 12 x 12 12 13 GPM (49,2,LPM) 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) (3,7 x 3,7) (3;7) 7.0 psi (0;48 bar) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar) 14 x 14 14 13 GPM (49,2 LPM) 17 GPM (64;3 LPM) 17 GPM (64,3 LPM) (4,3 x 4,3) (4,3) 7.0 psi (0,48 bar) 12,0 psi (0,83 bar) 12.0 psi (0,83. bar) 16 x 16 16 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) (4,9 x 4,9) (4,9) 7,0 psi (0,48 bar) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar) i8 x 18 18 17 GPM (64,3 LPM) 22 GPM (83,3 LPM) 22 GPM (83,3 LPM) (5,5 x 5,5) (515) '12.0 psi (0,83 bar) 20.2 psi (1,39 bas) 20.2 psi (1,39 bar) 20 x 20 20 20 GPM (75,7 LPM) 24 GPM (90,8 LPM) 24 GPM (90,8 LPM) (6;1 x 6,i) (6,1) 16:7 psi (1,15 bar) 24.0 psi (1,65.bar) 24,0 psi (1,65 bar) (a) For coverage area dimensions less than or between those indicated; use the minimum required flow for the next highest coverage area for which Hydraulic Design aaction under the Design Criteria are, stated. (b) The Minimum Flora requirement is based on minimum flow in GPM (LPM) from each spunkier, The associatedresidual pressures are calculated using the nominal K -factor. Refer to 'Hydraulic Design' in'the Design Cutena.sectionfor details. (c) For NFPA i30 2010 applications; Horizontal Ceiling criteria shall be used for certain sloped ceiling configurations up to 8:12 pitch. Refer to TIA 16288 for allowed sloped ceiling limitations when using iwrizontaf ceiling criteria. (d) For NFPA 138 applications, Horizontal Ceiling criteria may be used for sloped ceiling configurations up to 8:12 pitch when acceptable to the Local Authority Having Jurisdiction. (e) For NFPA 13 residential applications, the greater of 0.1 GPM/FL' over the design area or the flow in accordance with the criteria in Table A must be used, TABLE A SERIES LFII RESIDENTIAL, FLAT -PLATE CONCEALED PENDENT SPRINKLER (TY2524) NFPA 13,13D AND 13R HYDRAULIC DESIGN CRITERIA. W-wET PIPE SYSTEMS - (a) For coverage area dimensions less than or between those Indicated; use the minimum required flaw for the n"t highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b) The Minimum Flow requirement is based on minimum flow.ln GPM (LPM) from each sprinkler rhe associated residual pressures are calculated using the nominal K -factor. Refer to 'Hydraulic Design' in the Design Criteria section fru details, (c) For NFPA 136 2010 applications, Horizontal Ceiling criteria shall be used for certain sloped ceiling configuratloris up to 8:12 pitch. Refer to TIA tU2811 for allowed:sloped ceiling limitations when using horizontal ceiling criteria. TABLE B SERIES LFII.RESIDEN17AL FLAT -PLATE CONCEALED PENDENT SPRINKLER (TY2524) NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA - DRY PIPE SYSTEMS -- DRY PIPE SYSTEM n') Maximum Minimum Flow and Residual Pressure Coverage.Area Maximum Spacing Horizontal Ceiling Minimum Flow and Residual Pressure al Ft. x (m) (Maximum 2 -Inch Rise for 12 -Inch Run) (m x mm) ) 160°F (71°C) Sprinkler 12 x 12 122 15 GPM 56,8 LPM) (3,7 x 3,7) (3,7) 9.4 psi 0,65 bar) 14 x 14 14 15 GPM (56,8 LPM) (4,3 x 4,3) (413) 9.4 psi (0,65 bar) 16 x 16 16 16 GPM (80;6 LPM) (4,9 x 4,9) (419) 10,7 psi (0,74 bar) 18 x 18 18 17 GPM (64,3 LPM) (515) 12:0 psi (0,83' bar) 20 x 20 20' 21 GPM (79,5 LPM) (6,1 x 8,1) (6;1) 18,4 psi (1,27 bar) (a) For coverage area dimensions less than or between those Indicated; use the minimum required flaw for the n"t highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b) The Minimum Flow requirement is based on minimum flow.ln GPM (LPM) from each sprinkler rhe associated residual pressures are calculated using the nominal K -factor. Refer to 'Hydraulic Design' in the Design Criteria section fru details, (c) For NFPA 136 2010 applications, Horizontal Ceiling criteria shall be used for certain sloped ceiling configuratloris up to 8:12 pitch. Refer to TIA tU2811 for allowed:sloped ceiling limitations when using horizontal ceiling criteria. TABLE B SERIES LFII.RESIDEN17AL FLAT -PLATE CONCEALED PENDENT SPRINKLER (TY2524) NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA - DRY PIPE SYSTEMS -- BODY SEALING (1/2° NPT) �^---_`_ _--M _ ASSEMBLY CAP FACE OF SPRINKLER 1/2° THREADED SPRINKLER ASSEMBLY WRENCHING SADDLE " y FITTING AREA SUPPORT SPRINKLER COMPRESSION CUP WITH W - COVER (47,6 mm �r _ -�- SCREW ROLL FORMED 1/8° GAP t3,2 mm) RETAINER (3,2 mm) THREADS (27,2 mm) COVER- SPRINKLER -7/8` LEVER GUIDE RETAINER SUPPORT CUP PIN y 1/8' (28,6 mm) ASSEMBLY ASSEMBLY MW (4,8 mm) SOLDER LINK 3-3/16° DIA. ELEMENT GUIDE PIN TIP PROTECTIVE CAP OPERATED POSITION HOUSING FIGURE 3 r i DEFLECTOR iir -- -`- r_�-"'� {. (OPERATED DEFLECTOR --� -%� POSITION] SPRINKLER/SUPPORT OUP ASSEMBLY Th1.READINTO RETAINER SUPPORT CUP WITH THREAD. UNTIL MOUNTING" DIMPLES SURFACEIS FLUSH WITH EJECTION COILING SPRING SOLDER COVER_PLATE/RIETAINER COVER T/6 ASSEMBLY PLATE FIGURE 1 FLAT -PLATE CONCEALED. PENDENT SPRINKLER (71!2824) — ASSEMBLY — TFP443 Page 3 of 6 WRENCH RECESS PUSH WRENCH IN TO. ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 2 W -TYPE 18 -- SPRINKLER WRENCH — 2-i/2° DIA. SPRINKLER - (63,5 mm) 1/2° (12,7 mm) FACE OF SUPPORT CUP 1/2° THREADED SPRINKLER ASSEMBLY NPT ADJUSTMENT FITTING OPERATED SPRINKLER 1-718°ty/8" W - COVER (47,6 mm �r _ -�- -,.�- PLATE 1/8° GAP t3,2 mm) RETAINER (3,2 mm) (27,2 mm) COVER- SPRINKLER -7/8` MOUNTING RETAINER SUPPORT CUP SURFACE y 1/8' (28,6 mm) ASSEMBLY ASSEMBLY MW (4,8 mm) 3-3/16° DIA. DISPOSABLE DEFLECTOR IN (8i ,O mm); TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 PROTECTIVE CAP AND AC77VATED DEFLECTOR -� 'INSTALLATION DIMENSIONS — TFP443 Page 4 of 6 Technical Data Approvals UL and C -UL Listed NSF -61 Certified The Series LFII Residential Flat -Plate Concealed Pendent Sprinklers are only listed with the'Series LFII Concealed. Cover Plates having a factory -applied .finish'. Maximum Working Pressure 175 psi (12,1 bar) Dischargge Coefficient K=4.9 GPMJpsi"2 (70,6 LPMJbar'-) Temperature Ratin Sprinkler: 160°F (71°C� Cover Platt+: 139"F (59°C) Vertical Adjustment 1/2 inch (12,7 mm) Finishes Refer to .the Ordering Procedure section. Physical Characteristics • Cover Plate/Retainer Assembly: Cover Plate ............. Copper Ejection Spring .... Stainless_ Steel Retainer ... :..... ....... Brass 'OS prinkler/Support Cup Assembly: Body . ................ Brass Cap ..................Bronze Saddle ................... Brass Sealing Assembly ..... ; .Beryllium Nicked w/Teflon' Soldered. Link Halves Nickel Lever . Bronze Compression Screw .. , Brass Deflector . ......... .... Bronze Guide Pin Housing...... . `Bronze Guide Pins ............. Bronze Support Cup ....... ..... Steel '%!(eration When exposed to heat from a fire, the Cover Plate, which is normally soldered to the Retainer at three points, fails away to expose the Sprinkler/Support Cup As, sembly. At this point, the Deflector, sup- ported by the Guide Pins, drops down to its operated position. The Solder Link Element of the Sprinkler/ Support Cup Assembly is comprised of two link halves that are soldered togeth- er with a thin layer of solder, when the rated temperature Is reached, the sol- der melts and the two link halves sepa- rate, allowing the sprinkler to activate and flow water. t Registered trademark of DuPont. Design Criteria The TYCO RAPID RESPONSE Series LFII Residential Flat -Plate Concealed Pendent Sprinklers (TY2524) are UL and C -UL Listed for installation in ac- cordance with the following criteria. IBM When conditions exist'thatare outside the scope of the provided criteria, re- fer to the Residential Sprinkler Design Guide TFP490 for the manufacturer's recommendations that may accept- able to the Authority Having Jurisdiction. The Series LFII Residential Flat -Plate Concealed Pendent Sprinklers must not be used in applications where the air pressure above the ceiling is greater than That below. Down drafts through the Support Cup can delay sprinkler op- eration in a fire situation. System Type Per the UL Listing, wet pipeand dry pipe systems may be utilized: Per the C -UL Listing, only wet pipe systems may be utilized. • For dry systems not using CPVC, corrosion -resistant or internally gal- vanized pipe shall be utilized with the'sprinkiers described in this date sheet • For dry systems, pendent sprinklers shall be installed on return bends, where the sprinklers, return bends, and branch line piping (that is, po- tential areas for trapped water) are in areas at or above 40°F(4"C) Refer to technical data sheet TFP466 about the use of Residential Sprinklers .in:residentiai dry pipe systems. IL NOTICE When corrosion -resistant or internally galvanized pipe and fittings with a po- table water supply are utilized, return bends need not be installed. However, any portion of the piping that has the potential to trap water must be main- tained at or above 40°F (4'C) unless pro- vision to drain such areas Is provided and maintained dry. Water Delivery Men using the Series LFII Residential Flat -Plate Concealed Pendent Sprinklers (TY2524) in dry pipe sprinkler systems, the requirements for "Dry System Water Delivery" per Section 8.3.4.3 of the 2010 edition of NFPA 13D apply. For a resi- dential hazard, in no case shall the time of water -delivery exceed 15 seconds for the most remote operating sprinkler. Hydraulic Design (NFPA 13D and 13R) The minimum required sprinkler flow rate for systems designed to NFPA 13D or NFPA 13R are given in Tables A and B as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate Is the minimum required discharge from each of the total number of "design sprinklers" as speci- fied in NFPA 130 or NFPA 13R. NOT/E The number of "design sprinklers" spec- ified in NFPA 130 and 13R for wet pipe systems is to be applied when design- ing -dry pipe systems. There is no need to increase the design area, as is the case for density/area systems, in ac- cordance with U.S. Patent 7,7.12,543. Refer to technical data sheet TFP485 for details. Hydraulic Design (NFPA 13) For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis- charge from each of the four sprinklers Is to be the greater of the following: • The...flow rates given in Tables A and B for NFPA 130 and 13R as a function of temperature rating and the maximum allowable coverage area. • A minimum discharge of 0.1 GPM/ sq. ft. over the "design area" com- prised of the four most hydraulically demanding sprinklers for the -actual coverage areas being protected by the four sprinklers. NOTICE The number of "design sprinklers" specified in NFPA 13 for wet pipe sys- tems is to be applied when designing dry pipe systems. There is no need to increase the design area, as is the case for densitjvarea systems, in accordance with U.S. Patent 7,712,543. Refer to technical data sheet TFP485 for details. Obstruction to Water Distribution. Sprinklers are to be located in accor- dance with the obstruction rules of NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the TYCO technical data sheetTFP490. Operational Sensitivity Install sprinklers relative to the ceiling mounting surface as shown in Figure 3. Sprinkler Spacing The minimum spacing between sprin- klers is 8 feet (2,4 m). The maximum spacing between sprin- klers cannot exceed the length of the coverage area (Table A) being hydrau- lically calculated; for example, a maxi- mum of 12 feet for a 12 % x:12 ft. cov- erage area or.20:feet for a 20 ft. x:20 ft. coverage area.. Installation The TYCO RAPID RESPONSE Series LFII Residential Flat -Plate Concealed Pendent Sprinklers must be.instailed in accordance with the following instructions: NOTICE Damage to the Solder Link Element dur- ing installation can be avoided byhah- dling the sprinkler by the Support Cup only; that is, do not apply pressure to the Solder Link Element (Figure 1). Obtains leak -tight 1/2.inch NPT sprinkler joint by applying a minimum -to -maxi- mum torque of 7 to 14 ft. -lbs. (9;5 to 19,0 Nm)..Higher levels of torque can distort the sprinkler inlet with consequent leak- age or impairment of the sprinkler. Do not attempt to compensate for in- sufficient ad. fustment in the Cover Patel Retainer Assembly by under or over - tightening the sprinkler. Re -adjust the positimof the sprinkler fitting to suit. 1. Install pendent sprinklers in the pendent position, with the center- line 'of the sprinkler perpendicular to the mounting surface. 2. Remove the Protective Cap. 3. With pipe -thread sealant applied to the pipe threads, and using the W Type 18 Wrench shown in Figure 2, install and tighten the Sprinkler/ Support Cup Assembly into the fit- ting. The W -Type 18 Wrench ac- cepts 81/2 inch ratchet.drive. 4. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. The Protective against, prevent dam- age to the Deflector and Guide. Pins during ceiling installation and/ or during application of the finish coating of the ceiling. As.long as the protective Cap.re- mains in place, the system is con- sidered "Out Of Service After the ceiling has been complet- ed with the 2-1/2 inch (63 mm) dt- ameter hole and in preparation liar installing the Cover Plate/Retain- er Assembly, remove and discard the Protective Cap, and verify that the Deflector moves up and down freely. If the Sprinkler has been damaged and the Deflector does not move up and down freely, replace the entire Sprinkler assembly. Do not attempt to modify or repair a damaged sprinkler. 6. Screw on the Cover Plate/Retainer Assembly until its flange contacts the ceiling. Do not continue to screw on the Cover Plate/Retainer Assembly such that. it lifts a ceiling panel out of Its normal position. If the Cover. Plate/Retainer Assembly cannot be engaged with the Mounting Cup or the Cover Plate/Retainer As sembly cannot be engaged sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. Carrs and Maintenance 'The TYCO RAPID RESPONSE Series LFI Residential Flat -Plate Concealed Pendent Sprinkler (TY2524) must be maintained and serviced in accordance with the following instructions. NOTICE Before closing a fire protection system main control valve for maintenance work on the fire protection system that. it con- trols, obtain permission to shutdown the affected fire protection system from the proper authodfles and notify all person - .net who may be affected by this action. When properly installed, there is a nomi- nal 118 Inch (3,2 mm) air gap between the lip of the Cover Plate and the ceil- Ing, as shown in Figure 3. This air gap is necessary for proper operation of the sprinkler by allowing heat flow from a fire to pass below and above the Cover Plate to help assure appropriate release of the Cover Plate in a fire situation. If the ceiling needs. repainting after sprinkler installation, exercise care to ensure that the new paint does NOT seal off any of the air gap. Failure to do so may impair sprinkler operation. TFP443 Page 6 of 6 Absence of a Cover Plate can delay the sprinkler operation in a fire situation. Do not pull the Cover Plate relative to the Retainer. Separation may result, Exercise care to avoid damage to sprin- klers before, during, and after installa- tion. Never paint, plate, coat, or other- wise atter automatic sprinklers after they leave the factory, Never repaint factory -painted Cover Plates. When necessary,.replace cover plates with factory -painted units. Non - factory applied paint can adversely de- lay or prevent sprinkler operation in the event of a fire and is not permitted by NEPA. Replace sprinklers that: • were damaged by dropping, striking, wrench twisting, wrench slippage, or the like. • were modified or over -heated. • are leaking or exhibiting visible signs of corrosion, Responsibility lies With owners for the Inspection, testing, and maintenance of their fire protection system and devices In compliance with this document, as well as with the applicable standards of the National Fire Protection Association (for example, NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install- ing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. TFP44S Page 6 of 6 'Limited Warranty Products manufactured by Tyco Fire Suppression & Building Products (TFSBP) are warranted solely to the orig- Inal Buyer for ten (10) years against de- fects in material and workmanship when paid for and properly installed and main- tained under normal use and service. This warranty will expire ten (10) years. from date of shipment by TFSBP. No warranty is given for products or com4 ponents manufactured by companies not affiliated by ownership with TFSBP or for products and components which have been subject to misuse, Improper installation; corrosion, or which have not been installed, maintained, modified or repaired in.accordance with applicable Standards of the National Fire Protection Association, andlor the standards of any other Authorities Having Jurisdiction. Materials found by TFS13P'to be defec- tive shall be either repaired or replaced, at TFSBP's sole option. TFSBP neither assumes, nor authorizes any person to assume for It, any other obligation In connection with the sale of products or parts of products. TFSBP shall, not be responsible for sprinkler system design errors or inaccurate or incomplete in- formation supplied by Buyer or Buyer's representatives. In no event shall TFSBP be liable, in con- tract, tort, strict liability or under any oth- er legal theory, for incidental, indirect, special or consequential damages, in- cluding but not limited to labor charg- es, regardless of whether TFSBP was informed about the possibility of such damages, and in no event shall TFSBP's liability exceed an amount equal to the sales price. The fateaoi g warranty is made1_,.1r Jjau of aoy and.•all other wArranties. ex resss or implied. includingwarranties of mer- chantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on fail- ure of or detect in products, materials or components, whether the claim is made in contract, tort, strict liability or any oth- er legal theory. This warranty will apply to the full extent permitted bylaw. The invalidity, in whole or part, of'any portion of this warranty will not affect the remainder. Ordering Procedure Contact your local distributor for avail- ability.. When placing an order, indicate the full product description and Part Number (PIN). Sprinkler/Support Cup Assembly Specify Series LFII Residential Fiat -Plate Concealed Pendent Sprinkler (TY2524), K=4.9 (70,6), without Cover Plate/Retain- er Assembly, PIN 51-114-1-160. Cover Pilate/detainer Assembly Specify Cover Plate/Retainer Assem- bly with finish (below) for the Series LFII Residential Flat -Plate Concealed Pen- dent Sprinkler (TY2524), K=4.9 (70,6), P/N (below): Ziff white .................. PIN 58=201-0-135 Pura White' (RAL9010) ......:........ PIN 66-201.3-135 Signal White— (RAL9003) .............. PIN 66-201-4-135 Standard White ("Grey White) (RAL9002) .............. PIN 56-201-5-135 Custom_.. ..............PIN 56-201-K-135 Eastern Hemisphere sales only " Previously known asBrightWhite Mote -Ali Custom Cover Plates are painted us- ing Sherwin Williams interior Latex Paint. Contact TYCO Customer Service with any questions related tocustom orders. Optional Cover Plate/Retainer Assembly for Horizontal d=rat) Coiling Applications Only Specify Cover Plate/Retainer Assem- bly with finish (below) for the Series LFII Residential Fiat -Plate Concealed Pen- dent Sprinkler (TY2524), K=4.9 (70,6), PIN (below): Off White ............ . .....PIN 56-122-0.135 Pure White' (RAL9010) .:.... ......... PIN 66122.3-135 Signal White" (RAL9003) ............... ... PIN 56-122-4-196 Custom .......... . .......... PIN 56.122-x-185 Eastern Hemisphere sales only Previously known as Bright White Note: All Custom Cover plates are painted us- ing Sherwin Williams interior Latex paint. Contact TYCO Customer Service with any questions rotated to custom orders. Sprinkler Wrench Specify W Type 18 Sprinkler Wrench, PIN 56-000-1-265, Copyright 0 2010,.2011 Tyco Fire Suppression & Building Products. All rights reserved. §Z/D P.O. Box 3365 South. El Monte, CA 91733 '626.44460541 Fax 626.444.3887 www. Afcon.org 51.4 OFFSET CPVC HANGER SIZE- 3/4" thru 3"pipe. MATERIAL - Carbon Steel. FINISH - Mil..Galvanize'& LISTINGIAPPROVAL- 263 - EX 4231, FX 2551 PATENT - No. 6,649,2 ' 78. FUNCTION - 3/411-210 Hanger/restrainer for horizontal CPVC, Copper or Steel pipe.. Listed hanger/restrainer in all 3 mounting positions, i.e. vertical surface and both top and. bottom of horizontal surface. Provides listed verticaUlateral restraint and prevents upward movement of pipe that supplies a pendent sprinkler below a, ceiling, Size 2 %4' Hanger f6r hdrizontai CPVC pipe. Listed hanger in all 3m.ounting positions.. i 'e, vertical surface and both top and bottom of horizontal surface. Size 311 Hanger for horizontal CPVC pipe in two mounting posifionsi side and bottom. i.e. vertical surface and bottom of horizontal surface. Stabilizcsvertical piping by providing horizontal -restraint.. TNSTA:LLATION - Per NFPA. 13, 1311 and 13D. Space by pipe type. Install on 'wood, concrete or steel - See Drawings. Snap over pipe then squeeze strap back allowing pipe to slide freely. Listed When #905 threads are exposed in wood, install 9906 barking nut 3/4' .MaiLNOTE: Vetify that all assembly components are dialled of any surface oil. FASTENERS - Uftisfed, perNFPA 13 WOOD - 31/4" - 3` CPVC pipe - #905 screw- no pre -drill. 3/4" -- 2" Copper pipe - *905 screw- no,pre-drill. 31411- 21, Steel pipe -.1/4"x.1 1/2" lag screw - no pre -drill. Thru i/8" gypsum board- 114" x 2" tag screw. STEEL-inin.18GA.- 3/4"-3"CPUC pipe- 1/4" or#14Tek Screw. 3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw. 3/4" - 2" Steel pipe 1/4" or #14 Tek Screw. CONCRkTE:Required minimum load each, fastener= 5AA10+2501bs. 2 FEATURES * .1 1/2" Ciffict - loose fit allows pipe to slide. * 3/4" and I " pipe size made with common center -line. '`Patented design for superior strength. • Offset edge eliminates abrasion. • .AFCON#905 screw hAs.5/16" hex head - included. ORDERING - Part # and:pipe size. AF, CON #906 backing nut sold separately. 'l -t-0 Listed Restraint 314" thrtj 2* SixY.ifie i1 FCON produ.'1; a�c ezclusivEly daignod tube nx:q#tr�ik t3\R;Y witb ntieer A£CfI:V prcduris im:lipling parte anti fasteners, tc.�ilting in a listod snvyttac, resitniner ur tautgcr tts;zmbly. DISCLAIMER- AMON Will INM%watit ag.hinm the Whim of it% pfadwb; wbcn tkwd in combination with ather ptYAWs, pam tit systems not n1lm6clumder sold by AAff0XArCO3Vehal) NVIT be liable wKki any cl=mstnnees whatsa,,vtu for any, dirma m inditcd, inc;dcjnui (a canxqu-niihi &irum ar:tnyund, including but nin lindled to loss oftmsims numfit, m.,,tiafi nvnAPC0jVPn%1=s baw been, or am used. 6108 P.O. BOX 3365 SOUTH EL MONTE, CA 91733 626.444.01541 FAx626.444.3887 wwwafcon.org lu PIPE / C -P -V -C- HANGER SIZE - 43/4" duu i" C ' P.V.C. and Copper. V thru 211 �Steel'. NWERIAL.- Carbon Steel, F TISH, - *Ivlil. Galvanized, G 90 Spec. IN, LISTING - UL in US and CANADA. VUN&ION - Hariger,'.support and restrainer for use on C.P.V. C., Copper or Steel piping installed per N.F.P.A. 13,,13R and 13D. INSTALLATION -.Install on top, bottom,or side atbeava. Hanger spacing by pipe type - per NIFPA 13. UlAisted fusteners tested perNFPA 13, as follows. IN WOOD CPUC and Coppqr:- listed hex head screw ffiniished Nvith product. Steel - 1/4"xI.1/2" lag screw -.needs no prc-drilling. IN CONICRtTE or fIEAVYSTEEL: Shot:type fasteners, "On - ly when instAlledprior to pipe insertion '. FEATURES * Offset edge for abrasion 6.1millihation and superior strength. * Retainer dimples secure hanger topipe during installation. Required fastener furnished with 5116 head, needs no pre -drilling: ORDERING -.Part #.and pipe size. NOTE: On copper - insulate pipe,_ 8,129/01 RO. BOX 3365 SOUTH EL MONTE, 'CA 91733 626.444.0541 FAX 626.444.3887 www.afdon.org 511 PIPE/ C.P.V.C. HANGER SIDE'MOUNT SIZE - 3/4" thru 2" C.P.VC. and Copper. MATERIAL - Carbon Steel. RMSH - Mil, Galvanized,. G-90 Spec, LISTING - UL in US and CANADA PUNCTION- Hanger, support and restrainer for use on C.P.V.C. of Copper piping installed per M F.P.A 13,13R aftd, 13D. D. p g IN- , STALLAMON - Install on top; bot I bottom or side of.bemn. 'Hanger spacing by pipe type - per N.FPA- 13. UL listed fasteners tested per NEPA 13, as follows, IN NVOOD.. CPVC: and Copper_ li.stedhex ]lead screw furnished with product, IN CONCRETTor HEAVY STEEL: Shot type fasteners,, "Only when installed prior to pipe insertion"._ U ATURES *et, Offsedge for abrasion elimination and superiorstrength. * Ret, a . iner, diniples:sec6re hdh , ger to pipe durtrig installation. Required fastener, furnished with 5i'16 head, needs no pre - ORDERING - Part # and CY.VC. or Copper pipe size. NOTE: On copper - insulatepipe. 8/2.9/01 FOR SMALL PIPE V,SR—,5 POTTER VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD Stock No. 1144440 Installation must be perfomed b qualified personnel and in and l accordance with alt national ocal codes and ordinances. Shock hazard. Disconnectower source before servicing: Serious injury or death could result. Risk of explosion. Not for use in hazardous locations. Serious injury ordeath could result.. The Model VSR-S is a vane type waterflow switch for use on wet sprinkler systems that use i" (25mm),11/o" (32mm); 1 rh" (38min) or 2" (50min) pipe size. The unit may also be used as a sectional waterflow detector on large systems. The unit contains two single pole double throw snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 gallons per minute (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. Enclosure. The V SR -S switches and retard device'areenclosed in a general purpose, die-cast housing The cover is held in-place with two tamper resistant screws which require a special key for removal. A fie ld.installable cover tamper switch is available as an option which may be used to indicate unauthorized removal. of the cover. See bulletin number 5401.103 for installation instructions of this switch. UL, ULC, CSFINI Listed and NYNtEA Accepted Service Pressure: Up to 300 PSi (20,7 BAR) Flow Sensitivity Range for Signal: 4-1.0 CPM (I.5-38 LPM) UL Maximurn Surge: 18 FPS (5.5 m/s) Enclosure: Die-cast. red enamel finish Cover held in place with tamper resistant: screws Contact Ratings: Two sets of SPDT (Form C) 10:0 Amps at 7251250 VAC 2.0 Amps at 30 VDC Resistive 10mArnps.min. at 24 VDC Conduit Entrances: Two openings provided for 1/2" conduit. Individual switch compartments suitable for dissimilar voltages. Usage: Listed plastic, copper and schedule 40 iron pipe. Fits pipe sizes - I" (25mm), 1 1/4" (32mm), 1 1/2" (38mm) and 2" (50mm) Note: 12 paddles are fumished with each unit, one far each pipe size of threaded and sweat TEE, one for I " (25mm) CPVC. one for I"(25mm) CPVC (Ce.ntral), one for V threaded Nibco CPVC, and one: for i 1/2" (38ntm) threaded (Japan). Environmental. Specifications: • NEMA-4/IP54 Rated enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting. • Temperature range: 40° F to 120° F. (4.5° C to 49° C) UL Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Ri.ictc�iei�.l eccuira d r Grp to four star°ii s NFPA, 133 :National Fire Alarm Code NFPA-72 Optional: Cover Tamper Switch Kit, Stock No. 0090148 (See Fig. 7 for terminations) Replaceable. Components: Retard/Switch Assembly, stock no.1029030 Installation These devices may be mounted iti horizontal or vertical pipe. On horizontal pipe they.shoaid be installed on the top side of the pipe where they will he accessible.The units shouldnot beinstalled within6" (15cm) of a valve. drain or fitting which changes the direction of the waterflow. Select the proper paddle for the pipe;size and type of TEE used see Fig. I for instructions on changing paddle. The unit has a I " NPT bushing for threading into a non -corrosive TEE. See Fig. 2 for proper TEL size, type and installation. Use no more ththree wraps of teflon tape:. Ian Screw the device into the TEE fitting as shown in Fig. 2. Care must be taken to properly orient the device for the direction of waterflow. i The vane must not rub the inside of the'1-EE or bind in any way. The stem should move freely when operiated by hand. The device can also be used in copper or plastic pipe installations with the proper adapters so that the specified TEE fitting may be installed on the pipe run. ;'Vote: Do not leave cover off for an l xtended period of time. j Poiter Electric Signal Company, L.LC • 2081 Cruig Road, St..Louis,1v10, 63146-4161 • Phone: 800-325-3936/Canada 838-882-1833 • www.pottersignni.com PRINTED IN USA iclFG. 05401206 - REV G 12108 PAGE 1 Or, 3 Up� POTTER. BELLS The Symbol of Protection PBA -AC & MBA -AC i lh 1 (0c <�CCC 'these vibrating type lulls are designed for use as :fire; burglar or general signaling devices. They have loco power consumption and high decibel ratings. `ilio unit mounts on a standard 4" (101min) Square electrical box for indoor use or on a modcl'BB.K-I weatherproof backbox or 138X-1 deep weatherproof. backbox .for outdoor applications. Weatherproof baekbox model BBK-1, Stock No. 1500001. UL, VtC, and FNf Approved SizxsAvaitable: 6" (150mm), 8" (200mm)and 30" (250mm) Voltages Available: 24VAC 120VAC 12V'DC (10.2 trt 'I 5.6) .Polarized 24VDC (20.4 to 31.2) Polarized Service Ilse: FircAlarm General Signaling Burglar Alann Environment: Indoor or outdoor use (See Note 1) 40° to .150- (40- to 66°C) (Outdoor use requires weatherproof backbox.) Termination: AC Bells - 4 No. 18 AVG stranded wires DC Bells -Terminal strip Finish. Red powder coating Optional: Model BBK-1 weatherproofbackbox Model BBX- 1 deep weatherproof backbox 'Notts: I_ Minimum dB ratings are calculated from integrated sound pressure measurements made tit Underwriters Laboratories as specified in UL Standard 464. U.L. temperature range is -30° to 150°.1 (340 to 660C). 2. Typical dB ratings arc calculated imm measurerninits made witit a conventional sound level meter and. tine indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. Size inures (mm) Voltage Model Number Stock :Number Current (Max.)' Typical dB at 1011. (3m).(2) Minimum dB at IOft (3m) (1) 6(150) 12VI?C MI3A126 1756070 .12A 85 76 8 (200) 12VDC MBA128 1750080 .12A 90 77 10 (250) 12V.fIC M13A.1210 1750060 .12A 92 78 6(150) 24VDC MBA246 t750100 .06A 87 77 8 (200) 24VDC MBA248 175011.0 .06A 91 79 10 (250) 24V1)C MRA2410 1750090 .06x1 94 80 6 (.150) 24VAC PBA246 1806024° 17A 91. 78 8 (200) 24VAC PBA248 1808024' .17A 94 77 10 (250) 24VAC PBA2410 18100241 .17A 94 78 6 (150) I20VAC. PBA1206 1806120- .05A 92 83 8 (200) 120VAC P13A.12011 1808120• .05A 99 84 --10 (250) 120VAC PBA12010 1 18 10 120- .05A 99 86 All DC bells are polarized and have built-in transient proiection. • Does not have ULC listing. In outdoor or wet installations, bell must be mounted with weatherproof backbox, "BH.K.-i or BBX-1. Standard electrical boxes will riot provide a v<etaherprcof enclosure:. If thL bell and/or assembly is exposW w moisture:, it may fail or create an electrical hazard. Patter Electric Signal Company, LLC - 2081 Craig Road, St. Louis, MO. 6314&4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersVal.com PRINTED Ihf USA MFG. #5400776- REV Y PAGE I OF 31,08 AGGREGATE FLOW ANALYSIS: TOTAL N 31.1 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 5.0 � OTHER SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 26.1 GP 9.5 13 C:\HASS74\KONYN RESIDENCE.SDF JOB TITLE: KONYN RESIDENCE 21 12.5 22 12.5 WATER SUPPLY DATA 9.5 24 11.8 30 11.8 SOURCE STATIC RESID., FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ BOR PRESS.- @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SOURCE 50.0 40.0 38.5 43.3 31.1 20.1 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 31.1 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 5.0 GP OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.1 GP NODE ANALYSIS DATA NODE TAG ELEVATION (FT) 1 9.0 2 9.0 10 9.5 10A 9.5 11 9.5 12 9.5 13 9.5 20. 9.5 21 12.5 22 12.5 23 9.5 24 11.8 30 11.8 31 11.8 32 11.8 33 13.0 34 1.1.8 TOR 9.5 BOR 1.0 SOURCE NODE TYPE K= 4.90 K=-4_90 SOURCE PRESSURE (PSI) 7.1 7.0 7:3 7.2 7.4 8.3 9.1 7.9 6.9 7.5 9.3 8.8 7.4 8.0 8:4 8.2 9.0 10.9 15.9 20.1 BUTTE CO.UNTy M MAR 0,9'2017 M DEVELOPMENT SERVICES 9)7-339 PERMIT # DISCHARGE COUNTY D/E�VELOPMENT SER ®VICES (GPM) �����WED FOR 13 ODE C PLIANCj DAlE3-0��BY j� - - -I' 26.1 r, SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 C:\HASS74\KONYN RESIDENCE.SDF JOB TITLE:.KONYN RESIDENCE PIPE DATA PIPE TAG Q(GPM)J DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -13.1 1.101 PL 1.50 PF 0.4 1 9.0 4.9 7.1 13.1 4.4 150 FTG ET PE -0.2 10 9.5 0.0 7.3 0.0 0.031 TL 11.50 PV Pipe: 2 3.7 1.101 PL 7.00 PF 0.0 10 9.5 0.0 7.3 0.0 1.3 150 FTG T PE 0.0 10A 9.5 0.0 7.2 0.0 0.003 TL 12.00 PV Pipe: 3 13.0 1.101 PL 3.00 PF 0.4 10A 9.5 0.0 7.2 0.0 4.4 150 FTG 2E PE 0.2 2 9.0 4.9 7.0 13.0 0.031 TL 13.00 PV Pipe: 4 -9.3 1.101 PL 8.00 PF 0.2 10A 9.5 0.0 7.2 0..0 3.1 150 FTG T PE 0.0 11 9.5 0.0 7.4 0.0 0.016 TL 13.00 PV Pipe: 5 -9.3 1.101 PL 42.50 PF 0.9 11 9.5 0.0 7.4 0.0 3.1 . 150 FTG ET PE 0.0 12 9.5 0.0 8.3 0.0 0.016 TL 52.50 PV Pipe: 6 -9.3 1.101 PL 39.00 PF 0.8 12 9.5 0.0 8.3 0.0 3.1 150 FTG 2E PE 0.0 13 9.,5 0.0 9.1 0.0 0.016 TL 49.00 PV Pipe: 7 -9.3 1.394 PL 34.75 PF 0.2 13 9.5 0.0 9.1 0.0 2.0 150 FTG ---- PE 0.0 23 9.5 0.0 9.3 0.0 0.005 TL 34.75 PV Pipe: 8 -16.8 1.101 PL 14.00 PF 0.7 10 9.5 0.0 7.3 0.0 5.7 150 FTG ---- PE 0.0 20 9.5 0.0 7.9 0.0 0.049 TL 14.00 PV Pipe: 9 -8.4 1.101 PL 8.50 PF 0.3 20 9.5 0.0 7.9 0.0 2.8 150 FTG ET PE -1.3 21 12.5 0.0 6.9 0.0 0.014 TL 18.50 PV -Pipe: 10 -8.4 1.101 PL 31.50 PF 0.6 21 12.5 0.0 6.9 0.0 2.8 150 FTG 2E PE 0.0 22 12.5 0.0 7.5 0.0 0.014 TL 41.50 PV Pipe: 11 =8.4 1.101 PL 22.50 PF 0.5 22 12.5 0.0 7.5 0.0 2.8 150 FTG 2ET PE 1.3 23 9.5 0.0 9.3 0'.0 0.014 TL 37.50 PV Pipe: 12 -17.7 1.394 PL 14.75 PF 0.5 23 9.5 0.0 9.3 0.0 3.7 150 FTG 2E PE -1.0 24 11.8 0.0 8.8 0.0 0.017 TL 26.75 PV Pipe: 13 -17.7 1.394 PL 5.75 PF 0.2 24 11.8 0.0 8.8 0.0 3.7 150 FTG E PE 0.0 34 11.8 0.0 9.0 0.0 0.017 TL 11.75 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 C:\HASS74\KONYN RESIDENCE.SDF JOB TITLE: KONYN RESIDENCE PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 14 -8.4 1.101 PL 19.25 PF 0.4 20 9.5 0.0 7.9 0.0 2.8 150 FTG 2E PE -1.0 30 11.8 0.0 7.4 0.0 0.014 TL 29.25 PV Pipe: 15 -8..4 1.101 PL 33.50 PF 0.6 30 11.8 0.0 7.4 0.0 '2.8 150 FTG 2E PE 0.0 31 11.8 0.0. 8.0 0.0 0.014 TL 43.50 PV Pipe: 16 -8.4 1.101 PL 11.25 PF 0.4 31 11.8 0.0 8:0 0.0 2.8 150 FTG 4E PE 0.0 32 11.8 0.0 8.4 0.0 0.014 TL 31.25 PV Pipe: 17 -8.4 1.101 PL 13.25 PF 0.3 32 11.8 0.0 8.4 0.0 2.8 150 FTG 2E PE -0.5 33 13.0 0.0 8.2 0.0 0.014 TL 23.25 PV Pipe: 18 -8.4 1.101 PL 9.50 PF 0.3 33 13.0 0.0 8.2 0.0 2.8 150 FTG ET PE 0.5 34 11.8 0.0 9.0 0.0 0.014 TL 19.50 PV Pipe: 19 -26.1 1.394 PL 10.00 PF 1.0 34 11.8 0.0 9.0 0.0 5.5 150 FTG 3E PE 1.0 TOR. 9.5 0.0 10.9 0.0 0.035 TL 28.00 PV Pipe: 20 -26.1 1.394 PL 8.50 PF 1.3 TOR 9.5 0.0 10.9 0.0 5.5 150 FTG 3ETC PE 3.7 BOR 1.0 10.01 15.9 0.0 0.035 TL 37.50 PV Pipe: 21 -26.1 1.394 PL 68.00 PF 3.3 BOR 1'.0 0.0 15.9 0.0 5.5 150 FTG 3ETG PE 0.9 SOURCE -1.0 SRCE 20.1 (N/A) 0.035 TL 94.00 PV NOTES: (1) Calculations were performed by the HASS 7.4 computer program under license no. 27060373 granted by 'HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.004 gpm and a maximum imbalance.at any node of 0.077 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 5.7 ft/sec at pipe 8. (4) PIPE FITTINGS TABLE Pipe Table Name: STANDARD.PIP " SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 , C:\HASS74\KONYN RESIDENCE.SDF JOB TITLE: KONYN RESIDENCE PAGE: P MATERIAL: CPVC HWC: 150 Diameter Equivalent Fitting Lengths in Feet (in) E T L P R C G Ell Tee 45-e1L couP teeRun Ckvle Gvlve 1.101 5.00 5.00 1.00` 1.00 1.00 4.00 1.00 1.394 6.00 6.00 2.00 1.00 1.00 5.00 2.00. c s SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 - C:\HASS74\KONYN RESIDENCE.SDF JOB TITLE: KONYN RESIDENCE o 0 0 O O O R o a4 r 0 0 a w Co 0 �I N 0 D ''. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 C:\HASS74\KONYN RESIDENCE.SDF JOB TITLE: KONYN RESIDENCE WATER SUPPLY CURVE 60+ I 1 i I 50* y \ 45\ 0 P 40* <-40.0 psi @ 38 gpm ' R f Flow Test Point ` E S 1 S 35+ „ U R E I + 30+ P f S I 25+ I 20x I 15+ 10+ LEGEND -------n ; I X = Required Water Supply 1 20.11 psi @ 31.1 gpm 8 5+ I 0 = Available Water Supply 1 43.28 psi @ 31.1 gpm I n 0++-+---+----+-----+------+--------+--------+---------+-----------+ .200 300 400 500 600 .700 800 900 1000 ` FLOW (GPM) t