TRB+ Associates r Agency: County of Butte
a. TRB+ Project Number. PC 17.054.107. 1
Initial Plan Review
Page 1 of 6
Date: April 14, 2017
To: Elodio Salas
Email: Salasl478@gmail.com
(via email)
Cc: Philo Hunt, Nancy Springer, Deborah DeBrunner, Jordan DeBrunner, Curtis Johnson, Carrie Gomez
Email: Phuntabuttecounty.net; nspringer(a)_buttecountv.net; ddebrunneraC-buttecountv.net;
idebrunneraC-buttecounty.net; cjohnsona-buttecountv.net; cgomez(ED-buttecountv.net
(via email)
RE: Plan Review for: Salas Residence — New SFD
Project Address: 0 Hogan Road, Cohasset
Agency App. No.: B17-0528
TRB+ Project No.: PC17.054.107.1
At the County of Butte's request, TRB + Associates has completed its plan review for the project
listed above. Please see the section entitled "FOREWORD" on the following page for information on
the scope of the review, instructions on how to resubmit, and contact information for your project.
The following documents were received for review:
Plans: (2 sets) Sheets dated 03/21/17: C, Al to A3, S1 to S5, El, D1, D2
Structural Calcs: (1 copy) L. Wentland, dated 03/21/17
Truss Calcs: (2 copies) E. Teodosescu, dated 03/20/17
Energy Calcs: (1 copy) M. Martin, dated 03/15/17
Other. (1 copy) Square Footage Verification Form, dated 03/27/17
(1 copy) Permit Application, dated 03/27/17
Plan review comments are listed on the following pages.
Sincerely,
TRB + ASSOCIATES, INC.
Dan McLaughlin, P.E.
ICC Certified Plans Examiner
c�
BUILDING SOLUTIONS
TRB + Associates, Inc.
3180 Crow Canyon Place +Suite 216
+San Ramon, CA 94583
for MUNICIPALITIES
- T 925 866.2633
F 925 790.0011
av _
www.TRBp/us.com
FOREWORD
■ This plan review is only for the purpose of evaluating compliance with the provisions contained in the
2016 CBC, 2016 CPC, 2016 CMC, 2016 CEC, 2016 CRC, 2016 Green Building Standards Code,
2016 Energy Code, and County of Butte Ordinances. Please note that our review does not encompass
provisions regulated and enforced by Planning, Engineering, Public Works, Health Departments; or other
authorities outside the jurisdiction of the Building Department.
■ Please address all of the following items and return a copy of this list, along with a response sheet,
indicating the location of all required changes to the plans, specifications and/or calculations. Be as
specific as possible in your responses so that we may expedite your recheck-
■ If any changes have been made to the plan documents unrelated to those items identified in this
comment list, please list the changes on a separate sheet and include in your resubmittal documentation.
■ Please submit two (2) complete revised sets of plans and plan documents, wet stamped and signed by
the Architect and/or Engineer of Record, to:
County of Butte
Department of Development Services "
7 County Center Drive
Oroville, CA 95965
OR-
TRB + Associates, Inc.
Attention: Todd Bailey
3180 Crow Canyon Place, Suite 216
San Ramon, CA 94583
ARCHITECTURAL COMMENTS Complete review by: Dan McLaughlin, P.E.
Al. Please provide a section identified as deferred submittals and indicate the fire sprinklers
and any other deferred submittal items. CRC section 313.2
A2. Please indicate if natural gas or propane is to be used to service the structure. If propane,
show location, size, and anchorage. The anchorage may be a deferred item but please
identify it as such on the cover sheet.
A3. Please correct general note 19 on the cover sheet to indicate that the structure is in a State
Responsibility Area as indicated by Butte County. Indicate that the structure is required to
comply with the Wildland Urban Interface (WUI) provisions as given in CRC section R337
per Butte County.
A4. Please indicate that the new exterior stucco is to be applied in no less than three coats over
two layers of grade D paper. CRC sections R703.6.2 & R703.6.3
- - - +
Page 2of6 TRQ
Agency: County of Butte ,
TRB+ Project Number. PC17.054.107.1
PROJECT DATA
Occupancy Group:
R3/U
Type of Construction:
VB
Number of Stories:
1
Conditioned Floor Area:
2950 SF
Garage:
905 SF
Fire Sprinklered:
Yes
Valuation:
$200,000
FOREWORD
■ This plan review is only for the purpose of evaluating compliance with the provisions contained in the
2016 CBC, 2016 CPC, 2016 CMC, 2016 CEC, 2016 CRC, 2016 Green Building Standards Code,
2016 Energy Code, and County of Butte Ordinances. Please note that our review does not encompass
provisions regulated and enforced by Planning, Engineering, Public Works, Health Departments; or other
authorities outside the jurisdiction of the Building Department.
■ Please address all of the following items and return a copy of this list, along with a response sheet,
indicating the location of all required changes to the plans, specifications and/or calculations. Be as
specific as possible in your responses so that we may expedite your recheck-
■ If any changes have been made to the plan documents unrelated to those items identified in this
comment list, please list the changes on a separate sheet and include in your resubmittal documentation.
■ Please submit two (2) complete revised sets of plans and plan documents, wet stamped and signed by
the Architect and/or Engineer of Record, to:
County of Butte
Department of Development Services "
7 County Center Drive
Oroville, CA 95965
OR-
TRB + Associates, Inc.
Attention: Todd Bailey
3180 Crow Canyon Place, Suite 216
San Ramon, CA 94583
ARCHITECTURAL COMMENTS Complete review by: Dan McLaughlin, P.E.
Al. Please provide a section identified as deferred submittals and indicate the fire sprinklers
and any other deferred submittal items. CRC section 313.2
A2. Please indicate if natural gas or propane is to be used to service the structure. If propane,
show location, size, and anchorage. The anchorage may be a deferred item but please
identify it as such on the cover sheet.
A3. Please correct general note 19 on the cover sheet to indicate that the structure is in a State
Responsibility Area as indicated by Butte County. Indicate that the structure is required to
comply with the Wildland Urban Interface (WUI) provisions as given in CRC section R337
per Butte County.
A4. Please indicate that the new exterior stucco is to be applied in no less than three coats over
two layers of grade D paper. CRC sections R703.6.2 & R703.6.3
- - - +
Page 2of6 TRQ
r
A5.
Agency. County of Butte
TRB+ project Number. PCI 7.054.107.1
Please indicate that stucco weep screeds shall be.installed no less than 2" above paved
areas and 4" above soil. CRC section R703.6.2.1
A6. Please indicate the location of the crawl space access to all portions of the building and
ensure the access opening is no less than 18° by 24°. CRC section R408.4
A7. Please indicate that the window adjacent to the sliding door in the great room is to have
safety glazing. CRC section R308.4
A8. Please indicate on the plans that the windows located in each bathroom is to be safety
glass as per CRC section R308.4.5 or indicate that the bottom exposed edge of the glazing
is no less than 60 inches above the adjacent standing surface.
A9. Please indicate the egress component in each bedroom and provide a note indicating the
bottom of the new egress window openings shall not be higher than 44inches measured
from the floor. CRC section R310.1
A10. Indicate a non-absorbent surface to extend not less than 72 inches above the floor in the
shower. CRC section R307.2
A11. Please indicate that the garage ceiling is to have 1/2" gypsum board applied to the underside
for fire protection and to the garage side of the walls which separate the garage from the
dwelling space. CRC section R302.6
GREEN BUILDING COMMENTS
GB1. Please incorporate the CALGreen checklist into the drawings. Green Building Compliance
measures in addition to checklist shall be incorporated into the project drawings. A checklist
can be obtained at the building department counter.
G132. Please indicate that a listed raceway shall be installed to accommodate a dedicated
208/240 -volt branch circuit which shall originate at the main service or sub panel and shall
terminate into a listed cabinet, box or other enclosure to facilitate the future installation and
use of Electric Vehicle (EV) chargers. The raceway shall not be less than 1 inch inside
diameter and shall be continuous at enclosed, inaccessible, or concealed areas and
spaces. The service panel and/or subpanel shall provide capacity to install a 40 -ampere
minimum branch circuit. The raceway termination location shall be permanently and visibly
marked as "EV CAPABLE". CALGreen section 4.106.4
ENERGY COMMENTS
EN1. Please correct the lighting notes in "Permanent Int. Luminaires" section shown on sheet E1
to indicate the following 2016 energy code requirements for residential lighting:
a. All installed lighting shall be high -efficacy CA Energy Code section 150.0(k)1A
b. In bathrooms, garages, laundry rooms, and utility/storage rooms, at least one luminaire
in each of these spaces is to be controlled by a vacancy sensor. CA Energy Code
section 150.0(k)2J
c. Outdoor lighting is to be high efficacy that is controlled one of the following per CA
Energy Code section 150.0(k)3A:
a.• Photocontrol and motion sensor
b. Photocontrol and automatic time switch control
Page 3 of 6 TRD+
Agency: County of Butte
TRB+ Project Number. PC 17.054.107.1
c. Astronomical time switch control
d. Energy management control system
EN2. Please show on the plans next to the water heater as per California Energy Code section
150.0(n), water heating systems installed in new homes using gas or propane shall include
the following components:
a. 120V electrical receptacle that is within 3 feet from the water heater and accessible to
the water heater with no obstructions
b. A Category III or IV vent, or a Type B vent with straight pipe between the outside
termination and the space where the water heater is installed
c. A condensate drain that is no more than 2 inches higher than the base of the installed
water heater, and allows natural draining without pump assistance
d. A gas supply line with a capacity of at least 200,000 Btu/hr.
EN3. Please show on the plans how the Indoor Air Quality (IAQ) requirement determined in the
energy calculations is met. Show flow rate (59.5 cfm per page 8 of CF1 R -PRF -01 form) and
show location of mechanism which will fulfill the IAQ requirement.
MECHANICAL COMMENTS
M1. Please indicate that a passage way shall be constructed from attic opening to the appliance
in the attic. The passageway shall not have less than 30 inches high clearance and not
more than 20 feet in length measured along the centerline of the passageway from the attic
opening to the front of appliance. The passageway shall have continuous solid flooring not
less than 24 inches wide. A level service space not less than 30 inches deep and 30 inches
wide shall be present at the front or service side of the appliance. CMC section 904.10
M2. Please indicate the make and model of the fireplace to be installed. Provide the
manufacture cut sheet showing that prefabricated metal fireplace units shall be listed and
vented. Units shall be installed and terminated in accordance with the manufacturer's
installation instructions. Units shall be equipped with an outside air supply. CMC section
908
PLUMBING COMMENTS
P1. Please indicate that the water heater located in the garage is to be placed on an 18 inch
high platform. CPC section 507.13
P2. Since the water heater is installed in the garage, please provide a means to protect the
equipment from being damaged by vehicles. Perhaps provide protective bollards. CPC
section 507.13.1
P3. Please indicate that the new tank style water heater shall be provided with an approved,
listed, adequately sized combination pressure and temperature relief valve. The relief valve
shall be provided with a drain that extends from the valve to the outside of the building, with
the end drain pipe not more than 2 feet nor less than 6 inches above ground and pointing
downward. No part of the drain pipe shall be threaded. CPC sections 608.3 & 608.5
P4. Please indicate that all new showers and tub/shower combinations shall be provided with
individual control valves of the thermostatic mixing, pressure balance or combination valve
type. CPC section 408.3
Page 4 of 6 1 R B+
ELECTRICAL COMMENTS
No comments noted: -
FLOOD ZONE COMMENTS
Not in a flood zone; therefore, no comments. '
Agency. County of Butte
TRB+ Project Number. PC17.054.107.1
WILDFIRE EXPOSURE CONSTRUCTION REQ.
W1. Specify exterior glazing in accordance with CRC Section R337.8. One pane of window shall
also be tempered.
W2. Specify ignition resistant or non-combustible eaves and soffits in accordance with CRC
Section R337.7.5. Open Roof Eaves require. noncombustible or ignition -resistant materials
such as fire-resistant plywood or OSB. Refer to SFM web site above for approved
materials.
W3. Please specify that gable attic vents and foundation vents shall be fully covered with metal
wire mesh or noncombustible materials with minimum openings of 1/16" and shall not
exceed 1/8" openings in compliance with CRC section R337.6.2.
W4. Specify the approved eave vents that resist the intrusion of flame and burning embers per
CBC Section R337.6.3 Exception #1 (E.g. Vulcan Vents or tested equivalent)
W5. Specify that the Roof Gutters shall be provided with means to prevent the accumulation of
leaves and debris in the gutter. CRC section R337.5.4.
W6. Specify decking material in accordance with CRC section R337.9.
W7. Specify fire resistive exterior doors in accordance with CRC section R337.8. (The door
exterior surface shall be of noncombustible or ignition -resistant materials or be constructed
of solid core wood 1-3/8" thick or have a fire -resistive rating of not less than 20 -minutes.)
STRUCTURAL COMMENTS
S1. Please verify that the redundancy factor of 1.0 is applicable to this project. Per ASCE7-10
section 12.3.4.2, for Seismic Design Category D, which this projected is assigned to, the
redundancy factor should be 1.3. Please verify and revise calculations or provide
calculations which demonstrate either of the two applicable exceptions.
S2. Along shearwall line C, 2'-6" length shearwalls are shown in the garage which has a ceiling
height of 10'-4". These shearwalls have a height to length ratio greater than 3.5 which is not
permitted per AWC SDPWS-2015 section 4.3.4.1 and table 4.3.4. Please correct.
S3. Please provide a letter from the Engineer of Record stating that the roof truss calculations
and plans have been fully reviewed and found to be in compliance with the applicable
building codes and requirements specified in the plans.
S4. Please provide foundation calculations showing that the bearing capacity of the soil does
not exceed 1500 psf at any of the spread footings or continuous footings. Please provide
calculations demonstrating that the bearing capacity at the worst case shearwall boundary
element does not exceed the allowable given in CBC table 1806.2
S5. A note on sheet S3 indicates that the girder trusses are to be supported by 2x studs directly
underneath each girder and will have the same number of studs as there are number of
Page 5 of 6 1 RB+
S6.
S7.
S8.
S9.
S10.
[END]
.; Agency: County of Butte
TRB+ Project Number. PCI 7.054,107.1
plies in the girder truss. Provide calculations for the larger reaction loads showing the studs
have adequate capacity. Please indicate the size of studs at the interior bearing walls.
Please show how each truss will be supported that has a reaction greater than 2.5 kips. Will
a stud be directly under each of those trusses? Please clarify how each truss will be
supported and provide calculations showing the following:
a. The capacity of a double top plate when a truss is not placed directly over the stud
b. The capacity of the stud to support the trusses
c. The crushing capacity of the top plate when the load is perpendicular to the grain
d. The crushing capacity of the sill plate when the load is perpendicular to the grain
and the incising factor from AWC NDS -2015 section 4.3.8 is used for pressure
treated wood.
e. The bearing capacity of the foundation including spread footings that support a
beam which supports an interior bearing wall.
Along each shear wall, the assumption has been made that all lateral loads are equally
distributed to each of the shear wall segments. The basis of this assumption is founded on
premise that there is continuity in the roof diaphragm. As such, provide justification and/or
verification that there are adequate collectors, straps or ties between the shear walls. Drag
trusses and truss blocking could not be located on the plans at the shearwalls. Please
show how the load is transferred from the roof sheathing to each shearwall. ASCE 7-10,
Sec. 12.10.2
Please provide a detail showing the connection of the roof truss over a non-bearing wall
that is both parallel and perpendicular to the truss. Ensure to indicate a gap between the
wall and the truss and provide a fastener that is for a positive connection.
Please provide a detail showing a typical hold down installation at the foundation.
Provide a detail showing the grade beam at the garage door entrance as called out on
sheet S1.
Page 6 of 6 TRB