HomeMy WebLinkAboutB17-0881 000-000-000GENEF,AL NOTES
1. S-YSTEM DESIGN AND INSTALLATION SHALL COMPLY WITH NFPA 13D-2016 EDITION,
ALL LOCAL CODES AND THE CITY OF CHICO FIRE DEPARTMENT REQUIREMENTS.
2. SYSTEM DESIGN BASIS:
HYDRAULICALLY MOST DEMANDING 2 SPRINIG>_ERS.
3. WATER TO SUPPLY INFORMATION:
STATIC - 83 PSI RESIDUAL - 57 PSI RESIDUAL FLOW - 2307 GPM
SOURCE: CAL. WATER SERVICE CO.
TEST DATE - 1/27/2010 LOCATION - 5W CORNER OF SKWAY HEGAN LANE
4, ALL PIPE SHALL BE:
UNDERGROUND - SCHEDULE 40 PVC
ABOVE GROUND EXPOSED - COPPER -L
OVERHEAD IN ATTIC - CPVC
5. MANUFACTURERS OF RESIDENTIAL Sf=,RINKLERS PUBLISH INFORMATION
REGARDING THE SPACING OF THEIR SPRINKLERS WITH RESPECT TO HEAT
PRODUCING DEVICES (FIREPLACES, RANGES, OVENS, HEATING VENTS,
WATER HEATERS, FURNACES, ETC.) WHETHER OR NOT ALL HEAT
PRODUCING DEVICES ARE SHOWN ON THE PLAN PROPER MINIMUM
DISTANCES MUST BE MAINTAINED. SEE HEAT SOURCE CHART.
(o. THE MINIMUM DISTANCE BETWEEN ANY 2 RESIDENTIAL SPRINKLERS
SHALL NOT BE LESS THAN 8 FEET.
7. THE MAXIMUM DISTANCE BETWEEN ANY 2 RESIDENTIAL SPRINKLERS ON
THIS PROJECT IS HYDRAULICALLY LIMITED TO leo FEET. SPRINKLERS
SHALL NOT EXCEED 8 FEET FROM ANY WALL.
8. THE MINIMUM DISTANCE A SPRINKLER CAN BE LOCATED FROM A WALL IS
4 INCHES.
S. INSTALLATION OF ALL RESIDENTIAL SPRINKLERS WILL BE IN STRICT
COMPLIANCE WITH THE MANUFACTURERS INSTALLATION GUIDE.
10. PROVIDE PROPER SIGNAGE PER CRC 313.3.1 AND NFPA 131D
AND ALL APPLIGABLE LOCAL CODES.
01 CONCEALED RESiC,-)ENTIAL PENDENT SPRINKLER
RECESSED RESIDENTIAL PENDENT SPRINKLER
QR UPRIGHT SPRINKLER
NEW 5pRIN :LER PIPE
® SYSTEM RISER
�— CHANGE IN PIPE ELEVATION
12 HYDRAULIC REFERENCE POINT
--�� PIPE HANGER
OCR SPACING OF VARIOU5 PIPING MATERIAL5
PIPING
PIPE KE
ORDINARY
3/4
if
'/4/4
TEMP.
12:�4/
liMATE-RIAL5
3 it
COPPER
ro
8
8
10
10
10
12
GPVG
LATERAL DISTANCE FROM THE 51DE6 OF A
WOOD OR COAL BURNING STOVE
31-611
1'-0"
9
10
1000
5
1'-6"
0'-9"
LATERAL DISTANCE FROM A
WALL OVEN
120°
01_C3II
5
55
-1
13
03
SCHEDULE 40 $ 10
5TEEL
*
12
12
15
15
15
1 E�
THREADA13LE
THNWALL
*
12
12
12
12
12
12
POLYBUTYLENE
(GIST
3
3
.4
4.5
E�'5
2'-0"
1'-0"
POLYBUTYLENE
(IP5)
*
4
-,,5
5
1f -e"
LATERAL DISTANCE FROM THE SUFAC-E OF
ISSUES AND REVISIONS:
No. DATE I DESCRIPTION
,pROTECT/'O \
FIRE
�p �pt�
W� p~ CLASSIFlCAMN �p
C-16 Z o
J LICENSE N0,
6
�'4
F OF C AL`F�
Hill$ lim
�I�IV�II�VtlII I VVV U110
1 Qi
uuEm iuuuuul 11MIluumumul� u
JuMu li�uu uliuuuuu
�du�ud �u�uuu��uou MMIdu
all MUM
'k T I m
ka ne er Spa c ine Ncte5
1. ALL LENGTHS SHOWN ARE THE MAXIMUM RECOMMENDED
DISTANCE BETWEEN HANGERS EXPRESSED IN FEET.
2. PROVIDE A HANGER WITHIN ro INCHES OF ALL DROPS TO
SPRINGLER HEADS WHEN USING CPVC PIPE.
3. STEEL PIPE 15 NOT ALLOWED IN SIZES LESS THAN 1 INCH,
4. INDICATE INFORMATION THAT IS NOT AVAILABLE.
5. CTS = COPPER TUBE SIZE.
6. IPS IRON PIPE SIZE.
7. DENOTES LOCATION OF PIPE HANGER.
HARDENED PEX HEAD SELF
THREADING SCREW 15 FURNISHED
HARDENED HEX HEAD SELF WITH THE HANGER AND 15 THE
THREADING SCREW IS FURNISHED MINIMUM FASTENER 51ZE
®I I® WITH THE HANGER AND IS THE ACCEPTABLE T'I'P.
.MINIMUM FASTENER SIZE
ACCEPTABLE TYP.
CPUC DOUBLE FASTENER PLAN SYMBOL PLAN SYMBOL
STRAP TYPE HANGER CPVC STAND-OFF HANGER
1=1GUR 24 CPVC HANGER FIGURE 20 - CPVC HANGER
o
�Toa�O `�oa�0
HANGER IDETAIL�
P WATER METER
V 10201 I E'JTTE COUNTY DEVELOPMENT SERVICES
REVIEWED FOR
CODE COMPLIANCE
A
�F\VkE
F''oT
� o
UALIFORbiIA 2
f,',-?
n
x 1 �
1/4" = 1'-0,.
4 0 4 8
NOTE: THIS PLAN IS FOR HYDROLIC REFERENCE ONLY. ALL UNDERGROUND NO SCALE
INSTALLATION IS BY OTHERS. SCALE IN FEET
PENDENT HEADS TO HAVE CHROME ESCUTCHEONS 0 1' 2' 4' CARTWRIGHT RESIDENCE JOB # 1272
SPRINKLERS SYM, FINISH TEMP. QTY, SCALEGWH ,.. DIAMOND M FIRE PROTECTION 710 SKYWAY AVE. DATE: 5-4-17
SCALE: AS NOTED
", CHICO, CA
DRAWN PYi EDC
TOTAL SPRINKLERS THIS DRAWING
PROJECT SUPERINTENDENTi
2400 CATTLE DRIVE ROAD APPROVALSI ■ CITY HEAD COUNT = 31
❑ INSURER
CORNING, CA 960:21 ❑ OWNER DRAWING NO,
LIC. # C-16 463104 LSP _ �I
TELEPHONE I (530) 824-3456 FAX , (530) 824-3456 COVER SHEET 11�' 1
SHEET 1- [IF 2
PROX11"IIT1' OF= SPRINKLERS TO 14E ,4T SOURCES
ORDINARY
INTERMED.
TEMP.
TEMP.
LATERAI, DISTANCE FROM THE SIDES OF
AN OPEN OR RECESSED HEARTH FIREPLACE
31-0"
1'-0"
RADIAL D I STANCE FROM A
RECESSED HEARTH FIREPLACE
B, -01I
3'-0"
LATERAL DISTANCE FROM THE 51DE6 OF A
WOOD OR COAL BURNING STOVE
31-611
1'-0"
LATERAL DISTANCE FROM THE
SURFACE OF A KITCHEN RANGE
1'-6"
0'-9"
LATERAL DISTANCE FROM A
WALL OVEN
11_611
01_C3II
LATERAL DISTANCE FROM THE
SURFACE OF NOT AIR FLUES
LATERAL DISTANCE FROM
UNINSL'L ATED HEATING DUCTS
LATERAL DISTANCE FROM
UNINSULATED WATER PIPES
LATERAL DISTANCE FROM THE EDGES OF
A CEILING MOUNTED HOT AIR DIFFUSER
2'-0"
1'-0"
LATERAL DISTANCE FROM T;�E SIDES OF A
WALL MOUNTED HOT AIR DIFFUSER
2'-0"
1'-0"
LATERAL DISTANCE FROM THE FRONT OF A
WALL MOUNTED HOT AIR DIFFUSER
31-011
1f -e"
LATERAL DISTANCE FROM THE SUFAC-E OF
A WATER HEATER OR FURNACE
01_oll
0'-3"
LATERAL DISTANCE FROM A 250 WATT, OR
LESS, LIGHT FIXTURE
014011
0'-3"
LATERAL DISTANCE FROM A 250 WATT TO
499 WATT LIGHT FIXTURE
1'-0"
0140"
ka ne er Spa c ine Ncte5
1. ALL LENGTHS SHOWN ARE THE MAXIMUM RECOMMENDED
DISTANCE BETWEEN HANGERS EXPRESSED IN FEET.
2. PROVIDE A HANGER WITHIN ro INCHES OF ALL DROPS TO
SPRINGLER HEADS WHEN USING CPVC PIPE.
3. STEEL PIPE 15 NOT ALLOWED IN SIZES LESS THAN 1 INCH,
4. INDICATE INFORMATION THAT IS NOT AVAILABLE.
5. CTS = COPPER TUBE SIZE.
6. IPS IRON PIPE SIZE.
7. DENOTES LOCATION OF PIPE HANGER.
HARDENED PEX HEAD SELF
THREADING SCREW 15 FURNISHED
HARDENED HEX HEAD SELF WITH THE HANGER AND 15 THE
THREADING SCREW IS FURNISHED MINIMUM FASTENER 51ZE
®I I® WITH THE HANGER AND IS THE ACCEPTABLE T'I'P.
.MINIMUM FASTENER SIZE
ACCEPTABLE TYP.
CPUC DOUBLE FASTENER PLAN SYMBOL PLAN SYMBOL
STRAP TYPE HANGER CPVC STAND-OFF HANGER
1=1GUR 24 CPVC HANGER FIGURE 20 - CPVC HANGER
o
�Toa�O `�oa�0
HANGER IDETAIL�
P WATER METER
V 10201 I E'JTTE COUNTY DEVELOPMENT SERVICES
REVIEWED FOR
CODE COMPLIANCE
A
�F\VkE
F''oT
� o
UALIFORbiIA 2
f,',-?
n
x 1 �
1/4" = 1'-0,.
4 0 4 8
NOTE: THIS PLAN IS FOR HYDROLIC REFERENCE ONLY. ALL UNDERGROUND NO SCALE
INSTALLATION IS BY OTHERS. SCALE IN FEET
PENDENT HEADS TO HAVE CHROME ESCUTCHEONS 0 1' 2' 4' CARTWRIGHT RESIDENCE JOB # 1272
SPRINKLERS SYM, FINISH TEMP. QTY, SCALEGWH ,.. DIAMOND M FIRE PROTECTION 710 SKYWAY AVE. DATE: 5-4-17
SCALE: AS NOTED
", CHICO, CA
DRAWN PYi EDC
TOTAL SPRINKLERS THIS DRAWING
PROJECT SUPERINTENDENTi
2400 CATTLE DRIVE ROAD APPROVALSI ■ CITY HEAD COUNT = 31
❑ INSURER
CORNING, CA 960:21 ❑ OWNER DRAWING NO,
LIC. # C-16 463104 LSP _ �I
TELEPHONE I (530) 824-3456 FAX , (530) 824-3456 COVER SHEET 11�' 1
SHEET 1- [IF 2
SYSTEM DESIGN DATA
5EDROOMS 2 8 3
HAZARD
CLASSWICATIDN 2 MOST HI-DRAULICALLY DEMANDING 5PR(NKLERS
HYDRAULIC /
DESIGN DENSITY N/A GPM/SQ FT 2 A. S. @ 25rJ SQ/FT HEAD ALLLOVANCES 5 GPM
AREA OF APPLICATION 2 HEADS REQUIREMENTS REMENTS 312-19 GPM AT 39.-139 PSI AT GITl'
TYGO "TYFRB" 5RA55 UPRIGHT
WATER SUPPLY INFORMATI❑N; STATIC PRESSURE. 83 PSI, RESIDUAL PRESSURE: 51 PSI WITH 2307 GPM FLOWING
TEST
TAKEN AT, SW CORNER OF SKWAY E PECAN LANE
TEST TEST
TAKEN BY. CAL. WATER SERVICE CO. DATE, 1/21/2010
APPROVALS REQUIRED, CITY OF CNICO FIRE DISTRICT
1' CPVC TO
PVC UNDERGROUND
R«R DETAIL
NO SCALE
f.:
i
LED
LED LEDD .. .,
f h SD In
Jz;2 4,
L , € 4 .t rcd
.... ...... ........
f
1
1 HE -ADS
Cr
I
fl -
10 - 9 .:........................
4i
•
t
\"•
"'•. \ , `BKYLIGH I j fl40!
.� SGHT
{,SD HATCHED AREAS
INDICATE HEAT
SOURCES - SEE CHART
NO A/S ALLOWED
O o
.-, of c)
V
2-7 6-t 4-9 10-3
CD C—
C)
j.:_ ...... ...........
1 1
0-5 15-3
0-6 8-2'
$Y 3 s
+ ff[
.< l
NOTE:
NO A/S REQ, IN CLOSETS THAT D❑
NOT EXCEED 24 SQ, FT, PER NF"PA
13D 8.3.3 OR BATHROOMS LESS
THAN 55 SQ. FT, PER NF -PA 8.3.2
C-16 z
LEL . 60104
_.
_„
-?JTtE COUNTY DEVELOPMENT SERVICES
REVIEWED FOR
_ CODE COMPLIANCE
OF;T-� f BY �.
UND R ROUND AND R
Ov HE AD F I F I N LAN
1. SEE SHEET Fi=-i FOR GENERAL NOTES 4 DETAILS.
2. ALL CEILING HEIGHTS A5 NOTED ON KLAN, 4 0 4 8
3. ALL FIFING 16 Gl=Vc U.O.N.
SCALE IN FEET
ISSUES AND REVISIONS:
PENDENT HEADS T❑ HAVE CHROME ESCUTCHEONS No. DATE DESCRIPTION 0 1' 2' 4' �❑B # 1272
P�aTEcro� �-0» ,.'-�� ���' CARTWRIGHT RESIDENCE
0
M FIREPpOjn SPRINKLERS SYM, FINISH TEMP, QTY. SCALE GRAPH
""'' DIAMOND M FIRE PROTECTION 710 SKYWAY AVE. DATE: 5-4-17
U� p~ CLASSIFICATION Z
,Y�i CHICO, CA SCALE AS NOTED
'S
J C-16 0
T � DRAWN BY, EDC
* ucsE No. *
463104 2400 CATTLE DRIVE ROAD
y: 1t APPROVALS: ■ CITY HEAD COUNT = 31
Sj4T O���tr PROJECT SUPERINTENDENT:
"" CORNING, ❑INSURER
£ ALF _ •�...� ' ,,.. FAQ
CA 96021 o OWNER DRAWING NO.
OF C
LIC. # C-16 463104 FP -2
TOTAL SPRINKLERS THIS DRAWING — TELEPHONE ; (530) 824-3456 FAX I (530) 824-3456 FIRE SPRINKLER PLAN
SHEET 2— OF 2
30 TYCO Lr --ii CONCEALED RESIDENTIAL SSP
15r�o 1/2" ORIFICE 1/2" NFT K=4,9O S.I.N. TY2524
TYGO "TYFRB" 5RA55 UPRIGHT
200" 1/2" ORIFICE 1/2" Nf=T K=5.60 6.1.N. TY3131
PRE—FABBED TRUSSES
1' CPVC TO
,. FIRE SPRINKLER SYSTEM
O6' ELEC. BELL
U
d
U
11 SPARE CHB, w/ WRENCH
1' FLOW SWITCH
I ACCESS PANEL BY G.C.
I j 1' SWING CK, VA,
Z
u RISER LOCATED IN
A > EXTERIOR WALL
��N U
--~COPPER / CPVC TRANS COUP.
1' CONTROL VALVE TO DOMESTIC
I I ®
SERVICE BY PLUMBER
1' CONTROL VALVE
0
1', x 60-0 PVC / COPPER TRANS COUP,
PVC UNDERGROUND
R«R DETAIL
NO SCALE
f.:
i
LED
LED LEDD .. .,
f h SD In
Jz;2 4,
L , € 4 .t rcd
.... ...... ........
f
1
1 HE -ADS
Cr
I
fl -
10 - 9 .:........................
4i
•
t
\"•
"'•. \ , `BKYLIGH I j fl40!
.� SGHT
{,SD HATCHED AREAS
INDICATE HEAT
SOURCES - SEE CHART
NO A/S ALLOWED
O o
.-, of c)
V
2-7 6-t 4-9 10-3
CD C—
C)
j.:_ ...... ...........
1 1
0-5 15-3
0-6 8-2'
$Y 3 s
+ ff[
.< l
NOTE:
NO A/S REQ, IN CLOSETS THAT D❑
NOT EXCEED 24 SQ, FT, PER NF"PA
13D 8.3.3 OR BATHROOMS LESS
THAN 55 SQ. FT, PER NF -PA 8.3.2
C-16 z
LEL . 60104
_.
_„
-?JTtE COUNTY DEVELOPMENT SERVICES
REVIEWED FOR
_ CODE COMPLIANCE
OF;T-� f BY �.
UND R ROUND AND R
Ov HE AD F I F I N LAN
1. SEE SHEET Fi=-i FOR GENERAL NOTES 4 DETAILS.
2. ALL CEILING HEIGHTS A5 NOTED ON KLAN, 4 0 4 8
3. ALL FIFING 16 Gl=Vc U.O.N.
SCALE IN FEET
ISSUES AND REVISIONS:
PENDENT HEADS T❑ HAVE CHROME ESCUTCHEONS No. DATE DESCRIPTION 0 1' 2' 4' �❑B # 1272
P�aTEcro� �-0» ,.'-�� ���' CARTWRIGHT RESIDENCE
0
M FIREPpOjn SPRINKLERS SYM, FINISH TEMP, QTY. SCALE GRAPH
""'' DIAMOND M FIRE PROTECTION 710 SKYWAY AVE. DATE: 5-4-17
U� p~ CLASSIFICATION Z
,Y�i CHICO, CA SCALE AS NOTED
'S
J C-16 0
T � DRAWN BY, EDC
* ucsE No. *
463104 2400 CATTLE DRIVE ROAD
y: 1t APPROVALS: ■ CITY HEAD COUNT = 31
Sj4T O���tr PROJECT SUPERINTENDENT:
"" CORNING, ❑INSURER
£ ALF _ •�...� ' ,,.. FAQ
CA 96021 o OWNER DRAWING NO.
OF C
LIC. # C-16 463104 FP -2
TOTAL SPRINKLERS THIS DRAWING — TELEPHONE ; (530) 824-3456 FAX I (530) 824-3456 FIRE SPRINKLER PLAN
SHEET 2— OF 2