HomeMy WebLinkAboutB17-1544 000-000-000FCX Compa4y
3995 Olive Highway, OraviIICa Ca_ 95966
530-533-2730-. / 530-534-=-1608 ( Fax }
Ca_Lic_ 305365 C-10, C-16, C-36
Residential Fire Sprinkler
System Component List`
wo
4 _ WATER TEST GUAGE.
5 _ 2 PULE FLOW SW I TCH
BUTTE
COUNTY
JUL 27.:2017 6.- ALARM ,BELL
DEVELOPMENT
SERVICES
R17- )S yL)
PERMIT #
BUTTE COUNTY DEVELOPMENT SERVICES
REVIEWED FOR
COD C MPLIA E .
DATE BY
GOMp,�
.�O Y
* G16 CALIFORNIA
LI' NSE N
5
CTIMA ��
` RESIDENTIAL FIRE SPRINKLER
SYSTEM DESIGN BY FOX COMPANY C-16. LIC. # 305365',;�
PER REQUIREMENTS OF NFPA 13D-2016 EDITION s
w------ -_ __--_ _ _ __--_ ______________
JIM BLACK CONST. BLACK HOME .'
P.O.BOX 636 MARSH CT. AP039-460-082
DURHAM CA. 95938 DURHAM
PLAN NUMBER 3129 7/26/17
WATER SOURCE IS PUBLIC UTILITY
WATER PRESSURE IN STREET 60
DEDUCT METER LOSS FOR SIZE 1'' — 3 57
DEDUCT PRESSURE LOSS FROM SOURCE
TO SPRINKLER CONTROL VALVE
MAIN SECTION EQUIV.FT.
1--1/4"
PIPE
= 35
FT.
1
GATE VALVE
= 2
FT.
1
CHECK VALVE
— 5.
FT.
3
90 ELBOWS
— 18
FT.
2
COUPLINGS
= 2
FT.
1
TEES (RUN)
= 1
FT.
0
TEES (BRANCH)
= 0
FT..
TOTALS
= 63
FT. X .0343 — 2.16
DEDUCT HEAD LOSS FOR ELEVATION
. ( 14 FT. X 0-434 . ) . -- 6.08
DEDUCT PRESSURE LOSS FOR PIPING FROM
CONTROL VALVE TO FARTHEST SPRINKLER
54.84
48. 7.6
PIPE SECTION ONE EQUIV.FT.
1'' PIPE = 165 FT..
9'0�"ELBO:W:a.^
1 CROSSES = 1 FT.
17 TEE(RUN) & 45 ELL = 17 FT.
1 TEES (BRANCH) — 5 FT.
TOTALS = 218 FT. X .1067 -23.26 25.50
BRAND OF HEADS.= GLOBE 4906
K FACTOR OF HEADS USED = 4.9
EQUIVALENT FEET CALCULATED @ 2 HEAD
2 HEAD = 26 G.P.M. FLOW ( 13 G.P.M. EA.)
FRICTION LOSS `C' FACTOR = .150
G.P.M. — P.S.I. CONVERSION FORMULA.
MINIMUM PRESSURE REQ'D. FOR SPRINKLER HEAD(S)
DOMESTIC LOAD OF 5 G.P.M.
1.25 IN. PIPE = 35 FT. @ 5 G.P.M.
(G.P.M./ K.FACTOR)2 = P.S.I.
7.04 P.S.I.
— 0.06 P.S.I.
TOTAL.PRESSURE REQ'D. 7.09 P.S.I.
PRESSURE AVAILABLE IN SYSTEM = 25.50 P.S.I.
3995 Olive Highway
Oroville,.CA 95966
�
Phone (530) 533-2730
FOX COMPANY''.
Lic. No. 305365
"OW THE I=rRL SF)'RXNKLE7R SYSTEiN c7F�'E7RA-r S
UTILITY DISTRICT WATER SUPPLY:
The zy.a.tem activa.te.-a the 4.ine .apn.inkten.a whenever:
A) The FLOW SWITCH .aen.ae.a wate.n 6tow .in the .ay.atem e..ithen by
a head '6i4.ing' o44, on .the INSPECTOR TEST VALVE being
opened to ztmu.tate a head 4.in.ing o44.
The .ayatem can be SHUT DOWN by .tunn.ing OFF the CONTROL VALVE at
the bate o4 the FIRE RISER.
TEST & FLUSH -SYSTEM:
---- -- The �napee on teak vatve .ahoutd be opened .MONTHLY' to t.e-6t and .6tu-zh
the .ay-a.tem, ' activate a.e:anm belt and .smoke a.tanm.a.
A .two to three minute water 4tow ,tee t
.ahoutd be .au44.ic.ient .to teat att openat ions . o4 the zy4 tem
"THE INCH"
GL6.)
RESIDENTIAL
' •AUTOMATIC SPRINKLERS
FIRE SPRIN c ER CORPORATION MODEL GL4906'
ONE INCH ADJUSTABLE
FLAT PLATE CONCEALED PENDENT
DESCRIPTION AND OPERATION.
The Globe Model GL4906 Residential One Inch Adjustable Concealed Pendent Sprinkler has a
` flat plate profile that utilizes a 3mm frangible glass ampule as the thermosensitive element. Itfeatures
economy, aesthetics and the lowest allowable water flow with a nominal 1"of adjustment for easier
installation. The combination of the 3mm frangible glass ampule and specially designed deflector
make the Model GL4906 the ultimate in life safety and fire control. It has met the strict requirements
of Underwriters Laboratories Inc. as described in UL Standard, 1626; for Residential Sprinklers for
Fire Protection Service, and should be used accordingly. This sprinkler should also be installed in
accordance with the appropriate NFPA Standard 13, 13D or 13R and under the direction of the
i approving authorities having jurisdiction.
' - All that is seen at the ceiling is the 3 5/16" diameter flat ceiling plate color finished to match the
• specifier's exact requirements. The ceiling plate is soldered to the sprinkler's special uppersupport
assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing
the residential pendent spray sprinkler. At the prescribed temperature the internal pressure within the
ampule exceeds the strength of the glass causing the glass bulb to shatter. This results in water
discharge which is distributed in an approved pattern.
TECHNICAL DATA
• See reverse side for Approvals and Specifications.
• Temperature Rating: 155°F (68°C)
. Water Working Pressure Rating: 175 psi (12 Bars)
• Factory tested hydrostatically to 500 psi (34 Bars)
• Maximum lowtemperature glass bulb rating: -67°F (-55°C)
• Frame = bronze • Deflector -'brass Screw - brass
• Bulb seat - copper • Spring - nickel alloy • Seal - teflon
• Bulb - glass with alcohol based solution, 3mm size
• Cover Plate - brass `
• Upper Escutcheon Assembly- steel
RESIDENTIAL
FLAT PLATE
CONCEALEDPENDENT
• SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR
TEMPERATURES
N.F.P.A. MAXIMUM
CEILING TEMPERATURE
ORDINARY 1;5 68C RED,
.� 'ti, Od
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
t
SEPTEMBER 2011 A-10
,. ."V . . 4
989-846-4583 FAX 989-846-9231
' BULLETIN GL4906, REV. #1 .
RESIDENTIAL
AUTOMATIC SPRINKLERS
MODEL GL4906 ONE INCH ADJUSTABLE
FLAT PLATE CONCEALED PENDENT
SPECIFICATIONS AND- APPROVALS
SIN
NOMINAL
GL4906
12'x 12' 13 G.P.M. - 7 P.S.I.
14'x 14' 13 G.P.M. - 7 P.S.I.
155°F (68°C)
18'x 18' 17 G.P.M. - 12 P.S.I.
20'x 20' 20 G.P.M. - 16.7 P.S.I.
THREAD SIZE
LENGTH
FINISHES
SPRINKLER WITH
cULus
MODEL.
"K" FACTOR
135°F 57°C PLATE
Bright Chrome
White Painted
GL4906
4.9 (68 metric)
1/2" NPT
3" (7.6 cm)
Bright Brass'
X
X
Satin Chrome.'
Other Painted Finishes'
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'FINISHES AVAILABLE ON SPECIAL ORDER. FOR
PAINTED PLATES OTHER THAN WHITE, CONTACT
GLOBE FOR ORDERING SPECIFICATIONS.
INSTALLATION DATA FOR FLAT AND SLOPED CEILINGS"
ONE INCH ADJUSTABLE FLAT PLATE CONCEALED PENDENT
MODEL
MAXIMUM AREA OF IMINIMUM WATER DISCHARGE &
COVERAGE PRESSURES NEEDED PER SPRINKLER*
GL4906
12'x 12' 13 G.P.M. - 7 P.S.I.
14'x 14' 13 G.P.M. - 7 P.S.I.
16'x 16' 13 G.P.M. - 7 P.S.I.
18'x 18' 17 G.P.M. - 12 P.S.I.
20'x 20' 20 G.P.M. - 16.7 P.S.I.
NOTE: MINIMUM 9' SPRINKLER SPACING.
'WHEN THESE SPRINKLERS ARE USED IN NFPA 13 SYSTEMS, A 0.1 DESIGN DENSITY MINIMUM SHALL BE UTILIZED.
"REFER TO PAGE 2 OF THE GLOBE RESIDENTIAL SPRINKLER INSTALLATION GUIDE FOR NFPA 13D and 13R REQUIREMENTS.
ORDERING INFORMATION
CROSS SECTION SPECIFY
2 3/4" DIA. MIN. • Quantity • Model Number • Style
HOLE IN CEILING ._ •Orifice • Temperature • Finishes desired
—2 3/8" DIa--.{ . Quantity - Concealed Wrenches - P/N 332765
• Quantity - Protective Caps - P/N 332868
DEFLECTOR
DROP PIN 2 3/4' MAX.
® ® 1 7/8" MIN.
SUPPORT SHELLS I
CEILING COVER PLATES
FLATPLATE
CONCEALEDPENDENT
GL698Z,
FIR.ESPRINKLER CORPORATION
SEPTEMBER 2011
COVER PLATE
SIZE
WHITE 135'F
PART #
CHROME 135°F
PART #
3 5/16"
332892
332891
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manu-
factured products found to be defective in material or
workmanship for a period of one year from date of ship-
ment.
For specific details of our warranty please refer to Price
List Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.globesprinkler.com
PRINTED U.S.A.
BULLETIN GL4906, REV.#1
FIRE SPRINKLER CORPOR T10N
DESCRIPTION AND OPERATION
A/--/ -iC. �
QUICK RESPONSE
A_ UTOMATIC SPRINKLERS
GL SERIES
UPRIGHT • PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE
The Globe Quick Response GL Series Sprinklers are a low
profile yet durable design which utilizes a 3mm frangible glass
ampule as the'thermosensitive element. This provides sprinkler
operation approximately six times faster than ordinary sprinklers.
While the Quick Response Sprinkler provides an aesthetically
pleasing appearance, it can be installed wherever standard spray
sprinklers are specified when allowed by the applicable standards.
It offersthe additional feature of greatly increased safety to life and
is available in various styles, orifices, temperature ratings and
finishes to meet many varying design requirements. Quick
Response Sprinklers should be used advisedly and under the
direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that
contains a precisely measured amount of fluid. When heat is
absorbed, the liquid within the bulb expands increasing the internal
pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distributed
in an approved pattern depending upon the deflector style used.
TECHNICAL DATA
QUICK RESPONSE
PENDENT VERTICAL
•See reverse side for Approvals and Specifications. SIDEWALL
•Temperature Ratings - 135°F (570C), 155°F (680C),
175°F (790C), 200°F (93°C), 286°F (141-C)
• Water Working Pressure Rating - 175 psi (12 Bars)
• Factory tested hydrostatically to 500 psi (34 Bars) �nk
• Maximum low temperature glass bulb rating is -67°F (-55°C) QUICK RESPONSE
• Frame - bronze • Deflector - brass • Screw - brass HORIZONTAL LPC/CE
• Lodgement Wire - stainless steel • SIDEWALL HORIZONTAL
• Bulb seat - copper • Spring - nickel alloy • Seal - teflon SIDEWALL
• Bulb - glass with alcohol based solution, 3mm size
•SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
4077AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 • FAX 989-846-9231
JULY 2012 A-20 BULLETIN GI -5615, REV. #9
CLASSIFICATION
AVAILABLE SPRINKLER
BULB COLOR
N.F.P.A. MAXIMUM
TEMPERATURES
CEILING TEMPERATURE
ORDINARY
135°F1(55°F+ `' '57°C/6$°C
ORANGE/RED
10p°F 38°C'.
INTERMEDIATE
:175°F'1200°F 79°C/63°C
YELLOW/GREEN
150°F
HIGH
,;. v286°F' ... >; 141°C_: <'
BLUEi
4077AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 • FAX 989-846-9231
JULY 2012 A-20 BULLETIN GI -5615, REV. #9
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT. PENDENT o VERTICAL SIDEWALL
HORIZONTAL SIDEWALL • CONVENTIONAL (OLD STYLE
SPECIFICATIONS
NOMINAL "K" FACTOR
THREAD SIZE
LENGTH'
FINISHES
2.8 (39 metric)
1/2" NPT
2 1/4" (5.7cm)
200T
286°F
cUlus
FM
Factory Bronze
4.2 (59 metric)
1/2" NPT
2 1/4" (5.7cm)
MODEL
FACTOR
57°C
Chrome
5.6 (80 metric)
1/2" NPT
2 1/4" (5.7cm)
White Polyester 3
7.8 (111 metric)
1/2" NPT
2 1/4" (5.7cm)
LH
X
X
X
Black Polyester 23
8.1 (116 metric)
3/4" NPT
2 7/16" (6.2cm)
—
METRIC CONVERSIONS ARE APPROXIMATE.
'HORIZONTAL SIDEWALL IS 2 9/16".
'FINISHES AVAILABLE ON SPECIAL ORDER.
3 AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
STYLE
SIN
K
HAZARD'
135T
155T
175T
200T
286°F
cUlus
FM
LPC
CE
NYC - DOB
MODEL
FACTOR
57°C
68°C
79°C
93°C
141°C
MEA 101-92-E
GL2815
2.8
LH
X
X
X
X
X
X
—
—
—
X
QL4215
4.2
LH
X
X
X
X
X
X
—
—
—
X
GL5615
5.6
UPRIGHT
LH/OH
X
X
X
X
X
X
X
X
X
X
GL8115
7.8•
LH/OH
X
X
X
X
X
X
—
—
—
X
GL8118
8.1
LH/OH
X
X
X
X
X
X
X
X
X
X
GL2801
2.8
LH
X
X
X
X
X
X
—
—
—
X
GI -420i
4.2
LH
X
X
X
X
X
X
—
—
—
X
PENDENT
GL5601
5.6
LH/OH
X
X
X
X
X
X
X
X
X
X
GL8101
7.8•
LH/OH
X
X
X
X
X
X
X
—
—
X
GL8106
8.1
LH/OH
X
X
X
X
X
X
X
X
X
X
VERTICAL
GL5632
5.6
LH
X
X
X
X
X
X
X
—
—
—
SIDEWALLt
GL8133
8.1
LH
X
X
X
X
X
X
—
—
—
—
GL2826 §
2.8
LH
X
X
X
X
X
X
—
—
—
X
GL4226 §
4.2
LH
X
X
X
X
X
X
—
—
—
X
HORIZONTAL
GL5626 §
5.6
LH/OH
X
X
X
X
X
X
X
—
—
X
SIDEWALL
GL562713
5.6
LH/OH
X
X
X
X
X
—
—
X
X
—
GL8127 §
8.1
LH/OH
X
X
X
X
X
X
—
—
—
—
CONVENTIONAL-
GL5624
5.6
LH/OH
X
X
X
X
X
—
—
X
X
—
(OLD STYLE)
61-8125
8.1
LHIOH
X
X
X
X
X
—
-
X
X
— •
1SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6" BELOW THE CEILING.
°INSTALL IN ACCORDANCE TO BS5306 AND ANY OTHER RELATED DOCUMENTS.
?PENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING.
tUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR T MIN. SPACING.
OR ORDINARY HAZARD
LH: LIGHT HAZARD
•1/2" NPT
ORDERING INFORMATION GLOBE° PRODUCT WARRANTY
SPECIFY -
• Quantity • Model Number • Style Globe agrees to repair or replace any of its own manufactured
• Orifice • Thread Sizes Temperature products found to be defective in material or workmanship for a
• Finishes desired period of one year from date of shipment.
• Quantity - Wrenches - P/N 325390 (1/2"); For specific details of our warranty please refer to, Price List
P/N 312366 (L.O.) Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
av,.. 989-846-4583 FAX 989-846-9231
�RJE ���`ER � ORNPATION
1-800-248-0278 www.globesprinkler.com
JUNE2012 PRINTED U.S.A. BULLETIN GL5615, REV. #9
a } smell
f
W
J
Q
N
Z
O
M
M
Bronze Spring Loaded Check Valve %"-2"
Figure No. 3600 w/Teflon Disc.
Figure No. 3600SJ w/Teflon Disc
Figure No. 3615 w/Buna-N Disc
Figure No. 361'5SJ w/Buna-N Disc
125 PSI Saturated Steam, with TFE Disc Buna-N Disc Rated at 250 PSI
250 PSI Non -Shock Cold Water, 011, or Gas Fluid Pressure, Non -Shock W.O.G.
lure No. 3600
lure No. 3615
Threaded
Grinnell check valves may be Installed in vertical lines with
upward flow or In any intermediate position.
Do Not Use For Reciprocating Air Compressor Service.
Do Not Use as a Footvalve.
Q)
Figure No. 3600SJ
Figure No."3615SJ
Copper to.Copper
M Met I Ad
25
!r'n.;�yt3h:w.}E`,�a�. ��i'�•'�;+: K�. �r4��yy`..���.j1 '• L��./Mr{Ya�CY.� I.,JC,•'-�.. .'� �4Y _ _ �. � ....
�k.Sf\�";1N::� � -iv � .. .�� t � `hni �.. +'b��Ld'��•Ya;" �.,'1:i; t:%� .�'.. ..
t)IFnen§toils — Weights
Nominal
Size
Part
Speciilcation
1.
Body
-Bronze ASTM B-584
Alloy C84400
2.
Stem
Stainless Steel ASTM
A-582 Alloy S30300 .
3.
Spring
316 Stainless Steel
4.
Disc Holder
Stainless Steel Type 301
S.
Disc
Teflon, Fig. 3600
5A. Disc
Buna-N, Fig. 3615
6.
Seat Ring
Teflon
7.
8.
Seat Screw
Body End
Stainless Steel ASTM A-276
Alloy S43000
Bronze ASTM B-584
Alloy C84400
Nominal
Size
DimensionsApprox.
wt.
Fig.
Approx.
Net
Fig.et
q
g
C
2b
2
11/8
17/16,
.4
4
1/2
21116
13/e
13/16
.4
.4
2/4
21/4
15/s
15/16
.5
.5
1
25/6
2
11/2
.8
.9
11/4
215/16
2'/6
111/t6
1.2
1.3
1112
35h r,
23/4
2
1.6
1.9
2
33/4
33/6
25/16
2.4
2.7
no
��1°iCflr.T#W1MmL1NE,, cant dw
1 800 854-1015
FIRE SPRINKLER pRESSURE-GAUGES
U.S. GUAG 8, AMETEK
• Use on wet or dry sprinkler systems!
• Solid brass backed!
tioo 2Qo ,
'/," A .NTP -LM brass fitting; 31/2 diameter YS ''i M
• 300 lb./sq. In. Capacity 25 0 ins
qua'
Sao
&OSTED
r
APPROVE
VS -SF
(0)POTTER VANE TYPE WATERFLOW
e POR SMALL PIPE ALARM SWITCH WITH RETARD
Potter EleatNa signal Company potter Electric Signal & Mfg. LTD
2081 Craig Road • P.O. Box 28480 1967 Leslie Street
St. Louis, MO 63146.4161 Don Mills, Ontario, Canada M362116113
(314) 8784321 • (800) 325.3936 (416) 441-1833
STK. NO'. 1113000
U.S. PAT. NO. 3921989, CANADIAN PAT, NO -j009680
UL, ULC, CSFM LISTED and NYMEA ACCEPTED
Service Pressure: Up to 250 PSI
Minimum Flow Rab for Alarm: 10 OPM
Maximum Surge: 18 FPS
Enclosure: DI"ast, red enamel finish.
Cover hell In piece wtM tamper resistant screws
Contact Ratings: Two seta of SPDT (Form C)
16.0 Amps at 123/250 VAC
2.0 Amps at 0.30 VDC
Conduit Entrances: Two Knockoute provided for 112' condult
U409s. Listed Plastic, Copper and Schedule 40 Iron Pipe
Fits pipe sizes- 1', 1 1/41, and 1 1/2'
Note: a paddles are furnished with each unit one for each pipe
size of threaded or sweat TEE, one for i' CPVC, and one for
1 1/2' polybutylene (CTS -Copper tubing size)
Environnwrttal Specifications: -
Suitable for Indoor or outdoor use with factory metalled gasket
and die-oW housing : =
NEMA 4 Rated Enclosure • use with appropriate conduit. Ailing
Temperature Range: 400 F/120° F (4.54 C/4W C) :- _
Caution: This device Is not Intended for applicall" In exploetve
environments
Service Use: -
Automatic Sprinkler NFPA-13
One of two family dwelling NFPA-13D
Resldentlal occupancy up to four stories - NFPA-13R
Nstionat Fire Alarm Code NFPA42
r ::...;
OTHER PATENTS PENDING. Y~. ; I,:. optional: Cover Temper Swt6eh, order Suc. No. 000o
91B
The Model VSFI.SF is a vane type waterflow switch for use on waf sprinkler The vane must not rub the Inside of the TEE or bind In any way. The stern
systems that use 11,J 1/4', or 1 1/2' pipe size. The unit may also be used should move treaty When operated by hand.
as a sectional watidlow detector on large systems.
The unit contains two single pole double throw anap aollon switches and
an adfustabke pneumatic retard. The switches are actuated when a HOW Of
_t O.pellone per minute or. more occurs downstream of the doviat. The }IoW
condition must exist for a pariod of time necessary to' overoome the
selected retard period. I t
INSTALLATION: These devices may be mounted In hcrtzontsl or veftW
pipe. On horizontal pipe they should be Installed on the top side of the pipe"
where they vAl be accessible. The units should not be Installed within fl'
of a valve, draln or fthing which changes the direction of the wsterflow. The
unit has a 1' NPT bushing for threading Into a noncorrosive TEE. gee Fig,
2 for proper TEE size, type and Installation.
Screwthe device Into the TEE fitting as shown In FIg.2. Cars mustbetaken
to properly orient the device for the direction of waterflow.
The dsvtoe can also be used In copper or plastic pipe InstWtlons with the
proper adapters so that the specified TEE Atttnp may be Installed on the
pipe run.
INSPECTION AND TESTINO: Check the operation of the unit by opening
the Inapeetor' teat valve at the end of the sprinkler fine or the drain and test
oonneetlon, ti an Inspector's test valve Is not provided.
If there are no provisions for testing the operation of the flow detection
device on the system, appiklatton of the VSR-9F Is not recomr wride8 or
'advisable
The frequancy, of the Inspection and testing and tts associated protective
mon{tor" eyatam should be In nccardanoe With the applicable NFPA
Codec and Standards and/or authortty having jurisdiction (rWufaoturer
recommends quarterly or more frequently).
CAUTION: There are 8 paddles fumished with each unit. These paddles have raised lettering that shows the pipe
size and type of TEE that they are to be used with. The proper paddle MUEf be used, The screw that holds the paddle
must be securely tightened.
MKT. !l8000QJ • REV I PAt3E 1 CV 2
PRINTED IN USA MFG. #9400M , 3/06
BELLS
®PTT PBA -AC &PB
D_
DC
Potter Electric Signal Company Potter Electric Signal 8t Mfg. LTD
2081 Craig Rd.,/P.O. Box 28480 1967 Leslie Street
St. Louis, MO 63146 Don Mills, Ontario, Canada M31B2M3
(314)878-4321 / (800) 325-3936 (416) 441-1833
UL LISTED, FM APPROVED -
Sizes Available: 6", 8", and 10" •
Voltages Available: 24VAC
120VAC
12VDC (10.2 to 15.6) Polarized
24VDC (20.4 to 31:2) Polarized
-'Service Use: Fire Alarm
General Signaling
Burglar Alarm
Environment: Indoor or Outdoor Use (See Note 1)
-400 to 150°F (outdoor use require
-,weatherproof backbox)
Termination: 4 No. 18 AWG stranded wires
Finish: Red powder coating
6" BELL SHOWN Optional: 'Model BBK-1 weatherproof backbox
These vibrating type bells are designed for use as fire, burglar, or general signaling devices. They have low power
consumption and high decibel ratings. The unit mounts on a standard 4". square electrical box for,indoor use, or on a model
BBK-1 weatherproof backbox for outdoor -applications.. =`
ALL DC BELLS ARE POLARIZED AND HAVE BUILT-IN TRANSIENT PROTECTION:
SIZE
VOLTAGE
MODEL NO.
STOCK NO.
CURRENT (MAX)
TYPICAL dB
10 FT.
MINIMUM dB
. ®10 FT.'
6
12VDC
PBD126
1706012
.12A
85
75
8
12VDC
PBD128
1708012
.12A
90
75
10
12VDC
PBD1210
1710012
.12A
92
75 '
6
24VDC
PBD246
1706024
.06A
87
75
8
24VDC
PBD248
1708024
MA
91
79
10
24VDC
PBD2410
1710024
MA
94
79
6
24VAC
PBA246
1806024
.17A
91
75
8
24VAC
PBA248
1808024
.17A
94
75
10
24VAC
PBA2410
1810024
.17A
94
75
6
120VAC
PBA1206
1806120
.05A
92
82
8
120VAC
PBA1208
1808120
.05A
99
82
10
120VAC
PBA12010
1810120
.05A
99
85
Weatherproof backbox model BBK-1 Stk. No. 1500001.
Notes:
1. Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified in UL Standard 464. UL
temperature range is •30° to 150°F.
2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation.
PRINTED IN USA MKT. #8850001- REV K PAGE 1 OF 2
MFG. #5400776 - 4/94
9600 KLINGERMAN STREET * P.O. BOX 3365
O SOUTH EL MONTE, CA 91733 * USA
TEL: 626.444.0541 * FAX: 626.444.3887
i
E-MAIL: info@afcon.org * www.afcon.org
)us
CPUC - STEEL - COPPER '
#510 #511 #514
0
o 10 Patented
0
1 s
- Installation Instructions
Install on CPUC pipe as a hanger and/or restrainer
-. -- per thea- encyineerino.sheets. Some are additionally
" listed for use for use with steel and copper pipe.
#510 & #514 install on top, bottom or side
' of beam.
#511 install on top or bottom of beam.
-
#513 install on top or side of beam.
#515 & 519 install on side of beam.
' Required fasteners furnished: #904 for #515
CAV.C. - Max. Hanger #905 for #510 thru #514
Pipe Size Spacing
3/4 ------ ------- 5 1/2
-------------- - 6 '
1 1/4 ------------- 6 1/2
1 1!2 ------- ------ 7
2 --------- ---- 8
z -------------- 10