HomeMy WebLinkAboutB17-1548 000-000-000�t
FOX Company
3995 01 I Him zway, Oz-ovi. 1 1� Ca_ 95966
530-533-2730_/ 530-534-1608 (1Fax)
Ca._Lic_ 305365 C -1O, C-16, C-36
Residential Fire Sprinkler
System Component List`
ow
1 C,AL'CL7L-AT I ON S
2 SPR I NKLER HEADS
3. _ SPRING LOADED CHECK VALVE
4 _ WATER ZEST GUAGE .
5 _ 2 POLE FLOW SW I TCH
BUTTE 6_ A L A. R M ]5'E T- L
COUNTY
JUL 2 7.:2011 0� coM
DEVELOPACHM !�
SERVICES.
Q
01. ` �Sy� * 16 C FORNIA
PERMIT # L EN BUTTE
N
BUTTE COUNTY DEVELOPMENT SERVICES 305
REVIEWED FOR A
CODE COMPLIANCE �CnON�
DATE ��-71- B t i
%-� L �,�
RESIDENTIAL. FIRE SPRINKLER
SYSTEM DESIGN BY FOX COMPANY C•-1.6 LIC. ## 305365
PER REQUIREMENTS OF NF PA 13D„ 2016 EDITION
BRETT GARRITY CONST. GA RR.ITY CUSTOM HOME
P.O. BOX 6007 57 LAVA ROCK DR,. LOT 41.
CHICO CA. 95927 C CICO
PLAN NUMBER 2755 7/27/17
WATER SOURCE IS PUBLIC UTILITY
WATER PRESSURE IN STREET
DEDUCT METER LOSS FOR SIZE 1'' - 3
DEDUCT PRESSURE LOSS FROM SOURCE
TO SPRINKLER CONTROL VALVE
MAIN SECTION EQUIV.FT.
--------
1-1/2'" PIPE = 100 FT.
1 GATE VALVE 2 FT.
1 CHECK VALVE =• 6 FT.
90 ELBOWS = 21 FT.
5 COUPLINGS = 5 FT..
I TEES (RUN) = 1 FT.
0 TEES (BRANCH) = 0 FT.
TOTALS 135 FT. X .0178 2.40
DEDUCT HEAD LOSS FOR ELEVATION
( 13 FT. X 0.434 ) 5.64
DEDUCT PRESSURE LOSS FOR PIPING FROM
CONTROL VALVE TO FARTHEST SPRINKLER
PIPE SECTION ONE EQUIV.FT.
_---_ 1" .PIPE = 130 FT.
1.1. -90 ELBOWS = 55 FT.
2 CROSSES 2 FT,.
12 TEE(RUN) & 45 ELL = 1.2 FT.
0 TEES (BRANCH) - 0 FT..
TOTALS = 1.99 FT. X .1067 -21..23
60
57
54.60
48.96
27.72
L3RAND'OF HEADS - GLOBE 4906 G.P.M. -- P.S.I. PONVERSION FORMULA. -
K FACTOR OF HEADS USED = 4.9 (G.P.M./, K FACTOR)2. =. P.S,.T..
EQUIVALENT FEET CALCULATED @ 2 HEAD
2 HEAD = 26 G.P.M. FLOW ( 13 G.P.W EA.)
FRICTION i....OSS `C' FACTOR = 1.50
MINIMUM PRESSURE REQ'D.. FOR SPRINKLER HEAD(S) = 7.04 P.S.I.
DOMESTIC LOAD OF 5 G,.P,.M,
1.5 IN. PIPE = 100 FT,. @ 5 G.P.M. = 0..08 P.S,I.
TOTAL PRESSURE REQ'D,.
- 7.12
P.S.I.
PRESSURE AVAILABLE IN SYSTEM
= 27,.72
P.S.T.
3995 Olive Highway Phone (530) 533-2730
Oroville,.CA 95966
FOX COMPLALNY'.
Lic. No. 305365
Ht�W THL F.£RL SpRINKLUR SYSTEM O—RErRATErS
.UTILITY DISTRICT WATER SUPPLY:
The zyztem ac.tivat.ez .the 4i4e zptink.R.en.a wheneven:
A) The FLOW SWITCH zen.aez wat. _A 6tow in ,.the .ay.atem e4then by
a head '6i4Zn9' o44, on .the INSPECTOR TEST VALVE ' be-i,ng
opened to zZmutate a head 4t44ng o44.
The zyztem can be SHUT DOWN by .tu4ntng OFF the CONTROL VALVE at
the bate o4 the FIRE RISER.
TEST & FLUSH SYSTEM:
The Znzpecton .test vakve zhoutd be opened .MONTHLY to te.d.t and 4ku dh
the 6y6tem,' acttvate atanm belt and 4mok.e atanmz.
A .two to thnee minute waten -6tow test
bhoutd be zu4j6ic.Lent .to tezt ak2 operation s o4 the zy4tem
Parra"
...rA
FIRE SPRINKLER CORPOkATION
"THE INCH"
RESIDENTIAL
AUTOMATIC SPRINKLERS
MODEL GL4906
ONE INCH ADJUSTABLE
FLAT PLATE CONCEALED PENDENT
DESCRIPTION AND OPERATION
The Globe Model GL4906 Residential One Inch Adjustable Concealed Pendent Sprinkler has a
flat plate profile that utilizes a 3mm frangible glass ampule as the thermosensitive element. Itfeatures
economy, aesthetics and the lowest allowable water flow with a nominal 1"of adjustment for easier
installation.. The combination of the 3mm frangible glass ampule and specially designed deflector
make the Model GL4906 the ultimate in life safety and fire control. It has met the strict requirements
of Underwriters Laboratories Inc. as described in UL Standard, 1626, for Residential Sprinklers for
Fire Protection Service, and should be used accordingly. This sprinkler should also be installed in
accordance with the appropriate NFPA Standard 13, 13D or 13R and under the direction of the
approving authorities having jurisdiction.
All that is seen at the ceiling is the 3 5/16" diameter flat ceiling plate color finished to match the
specifier's exact requirements. The ceiling plate is soldered to the sprinkler's special upper support
assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing
the residential pendent spray sprinkler. Atthe prescribed temperature the internal pressure within the
ampule exceeds the strength of the glass causing the glass bulb to shatter. This results in water
discharge which is distributed in an approved pattern.
TECHNICAL DATA
• See reverse side for Approvals and Specifications.
• Temperature Rating: 155°F (68°C)
• Water Working Pressure Rating: 175 psi (12 Bars)
• Factory. tested hydrostatically to 500 psi (34 Bars)
• Maximum lowtemperature glass bulb rating: -67°F (-55°C)
• Frame - bronze • Deflector - brass • Screw - brass
• Bulb seat - copper • Spring - nickel alloy • Seal - teflon .
• Bulb - glass with alcohol based solution, 3mm size
• Cover Plate - brass
• Upper Escutcheon Assembly - steel
RESIDENTIAL
FLAT PLATE
CONCEALEDPENDENT
• SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR N.F.P.A. MAXIMUM
TEMPERATURES CEILING TEMPERATURE
ORDINARY 155° "68°C REDi:QEJ°E 382
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 • FAX 989-846-9231
SEPTEMBER 2011 A-10 BULLETIN GL4906, REV. #1
RESIDENTIAL
AUTOMATIC SPRINKLERS
MODEL GL4906 ONE INCH ADJUSTABLE
FLAT PLATE CONCEALED PENDENT
SPECIFICATIONS AND APPROVALS
SIN
NOMINAL
GL4906
12'x 12' 13 G.P.M. - 7 P.S.I.
14'x 14' 13 G.P.M. - 7 P.S.I.
155°F (68°C)
18' x 18' 17 G.P.M. - 12 P.S.I.
MODEL
''K" FACTOR
THREAD SIZE
LENGTH
FINISHES
SPRINKLER WITH
cULus
135°F 57°C PLATE
Bright Chrome
White Painted
GL4906
4.9 (68 metric)
1/2" NPT
3" (7.6 cm)
Bright Brass*
X
X
Satin Chrome,*
Other Painted Finishes*
�• ..�. ..w ..r�oviva'+r« nrrrcvnuvih i �. _hNI5HtS AVAILAULE ON SPECIAL ORDER. FOR
PAINTED PLATES OTHER THAN WHITE, CONTACT
GLOBE FOR ORDERING SPECIFICATIONS.
INSTALLATION DATA FOR FLAT AND SLOPED CEILINGS**
ONE INCH Af .m.RTARI F FI AT PI ATF r^nNPPAI Pn GPNnPkIT
MODEL
MAXIMUM AREA OF MINIMUM WATER DISCHARGE &
COVERAGE PRESSURES NEEDED PER SPRINKLER*
GL4906
12'x 12' 13 G.P.M. - 7 P.S.I.
14'x 14' 13 G.P.M. - 7 P.S.I.
16'x 16' 13 G.P.M. - 7 P.S.I.
18' x 18' 17 G.P.M. - 12 P.S.I.
20'x 20' 20 G.P.M. - 16.7 P.S.I.
,. n urr��.uv�i.
'WHEN THESE SPRINKLERS ARE USED IN NFPA 13 SYSTEMS, A 0.1 DESIGN DENSITY MINIMUM SHALL BE UTILIZED.
**REFER TO PAGE 2 OF THE GLOBE RESIDENTIAL SPRINKLER INSTALLATION GUIDE FOR NFPA 13D and 13R REQUIREMENTS.
ORDERING INFORMATION
CROSS SECTION SPECIFY
2 3/4" DIA. MIN. • Quantity • Model Number • Style
HOLE IN CEILING -Orifice • Temperature • Finishes desired
—2 3/8" DIA.—may . Quantity - Concealed Wrenches - P/N 332765
• Quantity - Protective Caps - P/N 332868
.. __.._. 1"x1/2"
.-. .. - REDUCER
CUP
O
DEFLECTOR
DROP PIN ® 2 3/4 MAX.
SUPPORT SHELL ® 17/8" MIN.
35/16"
CEILING COVER PLATE '
FLATPLATE
CONCEALED PENDENT
FIR.I: SPIRlN�i1�4� iCQIRII?i!E$i�TIiQNI
SEPTEMBER 2011
COVER PLATE
SIZE
WHITE 135°F
PART #
CHROME 135°F
PART #
3 5/16"
332892
332891
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manu-
factured products found to be defective in material or
workmanship for a period of one year from date of ship-
ment.
For specific details of our warranty please refer to Price
List Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583
1-800-248-0278
PRINTED U.S.A.
FAX 989-846-9231
www.globesorinkler.com
BULLETIN GL4906, REV. #1
Arm
QUICK RESPONSE
AUTOMATIC SPRINKLERS `
` GL SERIES `
UPRIGHT • PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE '
DESCRIPTION AND OPERATION
-The Globe Quick Response GL Series Sprinklers are a low
profile yet durable .design which utilizes a 3mm frangible glass
ampule as the thermosensitive element. This provides sprinkler
operation approximately six times faster than ordinary sprinklers.
While the Quick Response Sprinkler provides an aesthetically
.i .
pleasing appearance, it can be installed wherever standard spray +
sprinklers are specified when allowed by the applicable standards.
It offers'the additional feature of greatly increased safety to life and
is available in various styles, orifices, temperature ratings and
- ' finishes to. meet many varying design requirements. Quick QUICK SPONSE
:_. Response Sprinklers should be used advisedly. and under the UPRIGHT CONVENTIONAL
direction of approving authorities having jurisdiction. GL4215 1 '
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that
' contains 'a precisely measured amount of fluid. When heat is
absorbed, the liquid within the bulb expands increasing the internal
pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distributed
in an approved pattern depending upon the deflector style used. QUICK RESPONSE
r TECHNICAL DATA PENDENT VERTICAL
• See reverse side for Approvals and Specifications. SIDEWALL
_•_ •Temperature Ratings - 135°F (57°C), 155°F (68°C),
175°F (79°C), 200°F (93°C), 286°F (141 °C)
• Water Working Pressure Rating - 175 psi (12 Bars)
• Factory tested hydrostatically to 500 psi (34 Bars)
• Maximum low temperature glass bulb rating is -67°F (-55°C) QUICK RESPONSE
• Frame - bronze • Deflector -brass • Screw -brass HORIZONTAL LPC/CE
• Lodgement Wire -stainless steel • SIDEWALL HORIZONTAL
• Bulb seat - copper • Spring - nickel alloy • Seal -teflon SIDEWALL
• Bulb - glass with alcohol based solution, 3mm size
. '
*SPRINKLER TEMPERATURE RATING/CLASSIFMATMAI and r-ni nQ rnnimr_
CLASSIFICATION
AVAILABLE SPRINKLER
BULB COLOR
N.F.P.A. MAXIMUM -
TEMPERATURES
CEILING TEMPERATURE
ORDINARY
INTERMEDIATEt75°
F�2EKi 79kE193QG :
ORANGE/REIDT1,38•.0
YELLOW/GREEN
�15(hzF; 66 C,
HIGH
BLUE
225°F r' �07s,C.
4077AIRPARKDRIVE, STANDISH,MICHIGAN 48658 989-846-4583 • FAX989-846-9231
JULY 2012 A-20 BULLETIN GL5615, REV. #9
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT* PENDENT* VERTICAL SIDEWALL
HORIZONTAL SIDEWALL • CONVENTIONAL (OLD STYLE
SPECIFICATIONS
NOMINAL "K" FACTOR
THREAD SIZE
LENGTH'
FINISHES
2.8 (39 metric)
1/2" NPT
2 1'/4" (5.7cm)
200T
286°F
cULus
FM
Factory Bronze
4.2 (59 metric)
1/2" NPT
2 1/4" (5.7cm)
MODEL
FACTOR
57°C
Chrome
5.6 (80 metric)
1/2" NPT
2 1/4" (5.7cm)
White Polyester 3
7.8 (111 metric)
1/2" NPT
2 1/4" (5.7cm)
LH
X
X
X
Black Polyester z.3
8.1 (116 metric)
3/4" NPT
2 7/16" (6.2cm)
—
METRIC CONVERSIONS ARE APPROXIMATE.
' HORIZONTAL SIDEWALL IS 2 9/16".
' FINISHES AVAILABLE ON SPECIAL ORDER.
' AVAILABLE AS cULus LISTED. CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
STYLE
SIN
K
HAZARD'
135T
155T
175T
200T
286°F
cULus
FM
LPC
CE
NYC - DOB
MODEL
FACTOR
57°C
68°C
79°C
93°C
141°C
MEA 101-92-E
GL2815
2.8
LH
X
X
X
X
X
X
—
—
—
X
GL4215
42
LH
X
X
X
X
X
X
—
—
—
X
GL5615
5.6
UPRIGHT
LH/OH
X
X
X
X
X
X
X
X
X
X
GL8115
7.8•
LH/OH
X
X
X
X
X
X
—
—
—
X
GL8118
8.1
LH/OH
X
X
X
X
X
X
X
X
X
X
GL2801
2.8
LH
X
X
X
X
X.
X
—
—
—
X
GL4201
4.2
LH
X
X
X
X
X
X
—
—
—
X
PENDENT
GL5601
5.6
LH/OH
X
X
X
X
X
X
X
X
X
X
GL8101
7.8•
LH/OH
X
X
X
X
X
X
X
—
—
X
GL8106
8.1
LH/OH
X
X
X
X
X
X
X
X
X
X
VERTICAL
GL5632
5.6
LH
X
X
X
X
X
X
X
—
—
—
SIDEWALL'
GL8133
8.1
LH
X
X
X
X
X
X
—
—
—
—
GL2826 §
2.8
LH
X
X
X
X
X
X
—
—
—
X
HORIZONTAL
GL4226 §
4.2
LH
X
X
X
X
X
X
—
—
—
X
SIDEWALL
GL5626 §
5.6
LH/OH
X
X
X
X
X
X
X
—
-
X
GI -5627a
5.6
LH/OH
X
X
X
X
X
—
—
X
X
—
GL8127 §
8.1
LH/OH
X
X
X
X
X
X
—
—
—
—
CONVENTIONAL
GL5624
5.6
LH/OH
X
X
X
X
X
—
—
X
X
—
(OLD STYIE)
GL8125
8.1
1 LH/OH
X
X
X
X
X
—
—
X
X
—
1SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6" BELOW THE CEILING.
°INSTALL IN ACCORDANCE TO BS5306 AND ANY OTHER RELATED DOCUMENTS.
TENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING.
tUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9' MIN. SPACING.
OR ORDINARY HAZARD
LH: LIGHT HAZARD
'1/2" NPT
ORDERING INFORMATION
SPECIFY GLOBE® PRODUCT WARRANTY
• Quantity • 'Model Number Style Globe agrees to repair or replace any of its own manufactured
• Orifice • Thread Sizes • Temperature products found to be defective in material or workmanship for a
• Finishes desired period of one year from date of shipment.
• Quantity - Wrenches - P/N 325390 (1/2"); For specific details of our warranty please refer to Price List
P/N 312366 (L.O.) Terms and Conditions of Sale (Our Price List).
GL
6013E
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658' 989-846-4583 FAX 989-846-9231
FIRE SPRINKLER Ct9#iP'1RA,V.00 1-800-248-0278 www.globesprinkler.com
JUNE2012 PRINTED U.S.A. BULLETIN GL5615, REV.#9
�Y,rmnel
Bronze Spring Loaded Check Valve %"-2rr
Figure No. 3600 w/Tetlon Disc.
Figure No. 3600SJ w/Teiion Disc
Figure No. 3615 w/Buna-N Disc
Figure No. 3615SJ w/Buna-N Disc.
125 PSI Saturated Steam, with TFE Disc Buna-N Disc Rated at 250 PSI
250 PSI Non -Shock Cold Water, OII, or Gas Fluid Pressure, Non -Shock W.O.G.
lure No. 3600
lure No. 3615
Threaded
Grinnell check.valves may be installed In vertical lines with
upward flow or In any intermediate position.
Do Not Use For Reciprocating Air Compressor Service.
Do Not Use as a Footvalve.
.•.t•7Y. nr•� - .. .. .... .. .
Q)
Figure No: 3600SJ �N
Figure No"3615SJ
Copper to Copper
�Kal 'Ifrig
Dkt 61' sloils —'Weights
Nominal
Size
Part
Specification
1.
Body
-Bronze ASTM B-584
Alloy C84400
2.
Stem
Stainless Steel ASTM
A-582 Alloy S30300
3.
Spring
316 Stainless Steel
4.
Disc Holder
Stainless Steel Type 301
S.
Disc
Teflon. Fig. 3600
SA. Disc
Buna-N, Fig. 3615
6.
Seat Ring
Teflon
7.
8.
Seat Screw
Body End
Stainless Steel ASTM A-276
Alloy S43000
Bronze ASTM B-584
Alloy C84400
Nominal
Size
Dimensions
Approx.
Net Wt.
Fig. 3600
Approx.
Net Wt.
Fig.36WSJ
A
B
C
3/a
2
13/6
17/1 C,
.4
.4
'/:
2'/16
13/6
13/16
.4
.4
3/4
21/4
15/6
15/16
.5
.5
1
25/6
2
1'/z
..8
.9
VM6
23/6
111/16
1.2
1.3
35/16
2314
2
1.6
1.9
2
33/4
1 33/6
25/16
2.4
27
It
• � � � � , � .1 800 854-1015
HHOICSTRIMmLINE, cont` dw.
FIRE SPRINKLER -PRESSURE GAUGES..
U.S. GUAGL, AMETEK
• Use on wet or dry sprinkler systems
• 1
Solld brass backed!
roo 2Qo
• '/, n A .NTP -LM brass fitting; 31/2" diameter ys !'i .17s
so. 2so
300 1b./sq. 1n. Capacity
Sao
• fwL�i�lG T�NIlSyS7�/�7,5 �.GB 6t�A6F � ` -,..•;
SLISTED
FM
APPROvE�
VSR-SF
POTTER VANE TYPE WATERFLOW
e POR SMALL PIPE ALARM SWITCH WITH RETARD
Potter Efecttle Signal Company potter Electric Signal &. Mfg. LTD
2081 Craig Road • P.O. Box 28480 1987 Leslie Street
St. Louis, MO 83146-4161 Don Mills, Ontario, Cana& M3132M3
(314) 8784321,1(800) 325.3936 (416) 441-1833
UL. ULC, CSFM LISTED and NYMEA ACCEPTED
Service Pressure: Up to 250 PSI
Minimum Flow Rate for Alarm: 10 GPM
Maximum Surge 18 FPS
Enclosure: Die-cast, red enamel flnleh.
Cover held In place with tamper resistant screws
Contact Ratings: : Two sets of SPDT (Form C)
16.0 Amps at 125/250 VAC
2.0 Amps at 0-30 VDC
Omdult Entrenoas: Two Knockouts provided for tri' conduct
Usage. Listed Plastic, Copper and S>chsdule 40 Iron Pipe
Fits pipe sizes - 1', 1 1/4', and 1 1/2'
Note: 8 paddles are furnished with each unR. one for each pipe
size of threaded or sweat TEE, one for 1' CPVC, and one for
1 1/2' polybutylene (CTS -Copper tubing size)
Environnnntal Specifications:
Suitable for Indoor or outdoor use with factory Installed Casket
and die -asst housing
NEMA 4 Rated Enclosure - use with appropriate conduit fitting
Temperature Ranga: 40° F/120° F (4.5° C/49° C)
Caution: This device Is not Intended for applk:abone In expbW#
environments
service Use: : ="
Automatic Sprinkier NFPA-13
one or two family dwelling NFPA-130
STK. NO. 1113000 " ' Resldentiat occupancy up to four atones NFPA-13R
U.S. PAT. NO. 3921989, CANADIAN PAT. NO..,.1009680 National Flee Alarm Code NFPA-r2
PA -
OTHER PATENTS PENDING. _< !. : ,'. optional: Cover Tamper 8wl", order Stk. No. 0090018
W Th et t rub the Inside of the TEE or bind In env way. The stern
The Model VBA -8F la a vane type waterflaw switch for use on wet sprfn of
systems that use 1 `;;1 1/4', or 1 1/2" pipe size. The unit may also be used
as a seodonal wats'rflow detector on large systems.
The unit contains two single pole double throw snap action switches end
r! adiusteble.pneumstic retard. The switches are actuated %ban a flow of
10 gallons per minute or more occurs downstream of the ..- . Tits AoW
condition must exist for a period of time necessary to overcome the
selected retard period.
INSTALLATION: These devices may be mounted In horizontal or vertical
pipe. On horizontal pipe they should be Installed on the top side of the pipe
where they will be accessible. The units should not be Installed Within 8'
of avalve, drain or fitting w Jch changes the direction of the weterflow. The
unit has a 1' NPT bushing for threading Into a noncorrosive TEE. See Fig,
2 for proper TEE size, type and installation.
Screwthe device Into the TEE fitting as shown In Flg.2. Cara mustbetaken
to property orient the device for the direction of waterflow. .
e vane mu no
should move Ireely when operated by hand.
The devloa can also be used In copper or plask pipe Instaallaations with the
proper adapters so that the specified TEE ft" may be installed an the
pipe run.
INBPECTiON AND TESTINQ: Check the operation of the ur* by opening
the inspeelor test valve at the end of tho sprtnlder line or the drab+ and test
connection, H an Inspector's teal valve is not provided.
It there ars no provisions for testing the operation of the flow detection
devtce on the system, application of the VSR-SF Is not recommended or
'advisable
The kagwnoy of the Inspection and testing and its anwilkled protective
mcriltorhnq system should be In accordance Wtth the applicable NFPA
Codes and Standards and/or authority having )urfadlctton (manufacturer
recommends quarterly or more frequently).
CAUTION: There =tpare Theseused, ethat shows the de
size and type that they t be used with. The proper muM be .The screw that hods the
must be securely tightened.
MKT. /E8o000,7 • REV I PADS 1 OF.2
PRINTED IN USA mro. #s400804.3109
BELLS
(0),POTTER.PBA-AC & PBD -DC
DC
Potter Electric Signal Company Potter Electric Signal & Mfg. LTD
2081 Craig Rd.,/P.O. Box 28480 1967 Leslie Street
St. Louis, MO 63146 Don Mills, Ontario, Canada M3132M3
(314)878-4321 / (800) 325-3936 (416) 441-1833
UL LISTED, FM APPROVED
Sizes Available: 6", 8", and 10"
Voltages Available: 24VAC
120VAC
12VDC (10.2 to 15.6) Polarized
24VDC (20.4 to 31:2) Polarized
Service Use: Fire Alarm
General Signaling
'.Burglar Alarm
Environment: Indoor or Outdoor Use (See Note 1)
-400 to 150°F (outdoor use require
-weatherproof backbox)
Termination: 4 No. 18 AWG stranded wires
Finish: Red powder coating
6" BELL SHOWN Optional: Model BBK-1 weatherproof. backbox
These vibrating type bells are designed for.use as fire, burglar, or general signaling devices. -...They have low power
consumption and high decibel ratings. The unit mounts on a standard 4". square electrical boz for;indoor use, or on a model
BBK-1 weatherproof backbox for outdoor applications.
ALL DC BELLS ARE POLARIZED AND HAVE BUILT-IN TRANSIENT PROTECTION: • —,
SIZE
VOLTAGE
MODEL NO.'
STOCK NO.
CURRENT (MAX)
TYPICAL d6
lo FT.
MINIMUM d8
@ 10 FT.
6
12VDC
PBD126
1706012
.12A
85
75
8
12VDC
PBD128
1708012
.12A
90,
75
10
12VDC
PBD1210
1710012'
.12A
92
75 '.
6
24VDC
PBD246
1706024
.06A
87 '
75
8
24VDC
PBD248
1708024
.06A
91
79
10
24VDC
PBD2410
1710024
.06A
94
79
6
24VAC
PBA246
1806024
.17A
91
75
8
24VAC
PBA248
1808024
.17A
94
75
10
24VAC
PBA2410 .
1810024
.17A
94
75
6
120VAC
PBA1206
1806120
.05A
92
82
8
120VAC
PBA1208
1808120
.05A
99
82
10
120VAC
PBA12010
1810120
.05A
99
85
Weatherproof backbox model BBK-1 Stk. No. 1500001.
Notes:
1. Minimum d6 ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified in UL Standard 464. UL
temperature range is -30° to 150°F.
2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation.
PRINTED IN USA MKT. #8850001- REV K PAGE 1 OF 2
MFG. #5400776 - 4/94
9600 KLINGERMAN STREET * P.O. BOX 3365
O
SOUTH 'ELMONTE, CA 91733 * USA
TEL: 626.444.0541 * FAX: 626.444.3887
E-MAIL: info@afcon.org * www.afcon.org
G L�yUS
CPUC -.STEEL - COPPER
#510 #511 #514
0
o 0 kFatented
0
0
Installation Instructions
Install on CPUC pipe as a hanker and/or restrainer
- per their engineering sheets. Some are additionally
listed for use for use with steel and copper pipe.
#510A #514 install on top, bottom or side
of beam.
:r• #511 install on top or bottom of beam-.
#513 install on top or side of beam.
#515 & 519 install on side of beam.
Required fasteners furnished: #904 for #515
CYN.C. Max. Hanger #905 for #510 thru #514
Pipe Size Spacing
3/4 ----- -------- 1/2
1 -------------- 6
1 1 /d------------ 6 1 /�
1 1"- — — 7
2 . --------------8
2 1/2 ------- ------ 9