HomeMy WebLinkAboutB17-1781 047-770-042l
tit_r4 .1
FOX Company..
3995 Olive Hi�Yiway, Orocri 1 lc Ca_ 95966
530-533-2730../ 530-534-1608 (Fax)
Ca_Lic_ 305365 C-1.0, C-16, C-36
Residential Fire Sprinkler
System Component List'
aw
4 _ WA'TER TE S T C3uAGE.
5 _ 2 PULE FLOW SW I TCH
PERMIT'# tsh I7��
BUTTE COUNTY DEVELOPMENTSERVICES
REVIEWED FOR
6 _ AL A.riM EET- 1-- CODE COMPLIANCE
DATE BY ke
O� COMA,�y
8/xap
r-* C-16 CALIFORNIA
B1:7-1761 F11,E/('.C;'1 L E 5FN.
047-770-042 s
�O
AIJGUSrr 1.0, 2017 Pv
rt ': F/S FOR B 17-1399 o �C110N C�
RESIDENTIAL FIRE SPRINKLER
SYSTEM DESIGN BY FOX COMPANY C-16 LIC:. ## 305365
PER REQUIREMENTS OF NEPA 13D, 2016 EDITION
RICK PAYNE CONSTRUCTION PAYNE SPEC NOME
:.1.19 SPANISH GARDENS DR. 3880 ST. LUCIA CT.
CHICO CA. 95928 CHICO
PLAN NUMBER 3219 6/6/17
WATER SOURCE IS PUBLIC UTILITY
WATER PRESSURE IN STREET 60
DEDUCT METER LOSS FOR SIZE 1" " - 3 57
DEDUCT PRESSURE LOSS FROM SOURCE
TO SPRINKLER CONTROL VALVE
MAIN SECTION EQUIV.FT,.
I'' PIPE = 50 FT,
1 GATE VALVE -• 1 FT.
1 CHECK VALVE 4 FT..
3 90 ELBOWS = 15 FT.
3 COUPLINGS - 3 FT..
I TEES (RUN) = 1 FT.
0 TEES -(BRANCH) - 0 FT..
TOTALS = 74 FT. X .1067 - 7`.50 49.10.
DEDUCT HEAD LOSS FOR ELEVATION
( 15 FT, X 0.434 ) 6.51 42.59
DEDUCT PRESSURE LOSS FOR PIPING FROM
CONTROL VALVE TO FARTHEST SPRINKLER
PIPE SECTION ONE EQUIV.FT.
1'' PIPE = 145 FT.
5 90 ELBOWS = 25 FT.
2 CROSSES = 2 FT...
11 TEE(RUN) & 45 ELL = 11 FT.
3 TEES (BRANCH) = 15 FT..
TOTALS 198 FT. X ,.1067 -21..13 21.47
BRAND OF HEADS = GLOBE 4906 G.P.M. - P.S.I. CONVERSION FORMULA::
K FACTOR OF HEADS USED = 4.9 (G.P.M./ K FACTOR)2 = P.S.I.
EQUIVALENT FEET CALCULATED @ 2 HEAD
.> HEAD = 26 G.P.M. FLOW ( 13 G.P.M. EA:)
FRICTION LOSS `C' FACTOR = .150
MINIMUM PRESSURE REQ'D. FOR SPRINKLER HEAD(S) _ '7.04 P.S.I.
DOMESTIC LOAD OF S G.P.M.
1.5 IN. PIPE -:: 50, FT, @ 5 G.R.M. = 0.04 P. S.I.
TOTAL PRESSURE•REQ'D. = 7.08 P.S.I.
PRESSURE AVAILABLE IN SYSTEM. = 21.47 P.S.I.
ry
3995 Olive Highway Phone (530) 533-2730
Oroville,.CA 95966
FOX.'COMPANY'i
Lic. No. 305365
"OW 7 HE7 F-rRE7 SpRXNKLUR SYSTLM 0T>L=_RAWES
.UTILITY DISTRICT WATER SUPPLY:
The .6.y.6tem activatez the 44.ne zp4ink.te4z whenever:
A) The FLOW -SWITCH denze-6 waters 4kow .in the .ayetem e.L.ther by
a head '6i4Zng' o44, on. the INSPECTOR TEST VALVE being
opened to zZmuta#e a head 4i4ing o44.
The zyztem can be SHUT DOWN by .tunntng OFF the CONTROL VALVE at
the bate o4 the FIRE RISER.
TEST & FLUSH SYSTEM:
-The Znzpector..tezt va.tve dhoutd be opened .MONTHLY to te-6t and 4tuah
'the .ay tem, ' activate atarm belt and. emoke atanmz.
A .two to three minute water 4tow ,teat
.dhoutd be zu44.icZent .to tezt att ope.ria.tion.d o4 .the zy4tem:
,Nos
NITO
FIRE SPRINKLER CORPORATION
"THE INCH"
RESIDENTIAL
AUTOMATIC SPRINKLERS
MODEL GL4906
ONE INCH ADJUSTABLE
FLAT PLATE CONCEALED PENDENT
DESCRIPTION AND OPERATION
The Globe Model GL4906 Residential One Inch Adjustable Concealed Pendent Sprinkler has a
flat plate profile that utilizes a 3mm frangible glass ampule as the thermosensitive element. Itfeatures
economy, aesthetics and the lowest allowable water flow with a nominal 1" of adjustment for easier
installation. The combination of the 3mm frangible glass ampule and specially designed deflector
make the Model GL4906 the ultimate in life safety and fire control. It has met the strict requirements
of Underwriters Laboratories Inc. as described in UL Standard, 1626, for Residential Sprinklers for
Fire Protection Service, and should be used accordingly. This sprinkler should also be installed in
accordance with the appropriate NFPA Standard 13, 13D or 13R and under the direction of the
approving authorities having jurisdiction.
All that is seen at the ceiling is the 3 5/16" diameter flat ceiling plate color finished to match the
specifier's exact requirements. The ceiling plate is soldered to the sprinkler's special upper support
assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing
the residential pendent spray sprinkler. At the prescribed temperature the internal pressure within the
ampule exceeds the strength of the glass causing the glass bulb to shatter. This results in water
discharge which is distributed in an approved pattern.
TECHNICAL DATA
• See reverse side for Approvals and Specifications.
• Temperature Rating: 155°F (68°C)
• Water Working Pressure Rating: 175 psi (12 Bars)
• Factory. tested hydrostatically to 500 psi (34 Bars)
• Maximum lowtemperature glass bulb rating: -67°F (-55°C)
• Frame - bronze • Deflector - brass • Screw - brass
• Bulb seat - copper • Spring - nickel alloy • Seal - teflon
• Bulb - glass with alcohol based solution, 3mm size
• Cover Plate - brass
• Upper Escutcheon Assembly - steel
RESIDENTIAL
FLATPLATE
CONCEALEDPENDENT
• SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR N.F.P.A. MAXIMUM
TEMPERATURES CEILING TEMPERATURE
ORDINARYW
' 0=8-181
RED 10088'C'
rt
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 • FAX 989-846-9231
SEPTEMBER 2011 A-10 BULLETIN GL4906, REV. #1
,-
r
RESIDENTIAL
AUTOMATIC SPRINKLERS
MODEL GL4906 ONE INCH ADJUSTABLE
FLAT PLATE CONCEALED PENDENT
SPECIFICATIONS AND APPROVALS
SIN
NOMINAL
GL4906
12'x 12' 13 G.P.M. - 7 P.S.I.
14'x 14' 13 G.P.M. - 7. P.S.I.
155°F (68°C)
18'x 18' 17 G.P.M. - 12 P.S.I.
20'x 20' 20 G.P.M. - 16.7 P.S.I.
THREAD SIZE
LENGTH
FINISHES
SPRINKLER WITH
cULus
MODEL
"K" FACTOR
135°F 57°C PLATE
Bright Chrome
White Painted
GL4906
4.9 (68 metric)
1/2" NPT
3" (7.6 cm)
Bright Brass'
X
X
Satin Chrome"
Other Painted Finishes`
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'FINISHES AVAILABLE ON SPECIAL ORDER. FOR
PAINTED PLATES OTHER THAN WHITE, CONTACT
GLOBE FOR ORDERING SPECIFICATIONS.
INSTALLATION DATA FOR FLAT AND SLOPED CEILINGS**
ONE INCH ADJUSTABLE FLAT PLATE CONCEALED PENDENT
MODEL
MAXIMUM AREA OF MINIMUM WATER DISCHARGE &
COVERAGE PRESSURES NEEDED PER SPRINKLER"
GL4906
12'x 12' 13 G.P.M. - 7 P.S.I.
14'x 14' 13 G.P.M. - 7. P.S.I.
16'x 16' 13 G.P.M. - 7 P.S.I.
18'x 18' 17 G.P.M. - 12 P.S.I.
20'x 20' 20 G.P.M. - 16.7 P.S.I.
NOTE: MINIMUM 9' SPRINKLER SPACING.
'WHEN THESE SPRINKLERS ARE USED IN NFPA 13 SYSTEMS, A 0.1 DESIGN DENSITY MINIMUM SHALL BE UTILIZED.
"REFER TO PAGE 2 OF THE GLOBE RESIDENTIAL SPRINKLER INSTALLATION GUIDE FOR NFPA 13D and 13R REQUIREMENTS.
ORDERING INFORMATION
CROSS SECTION SPECIFY
23/4 "
3/4" DIA. MIN. • Quantity • Model Number Style
HOLE IN CEILING . Orifice • Temperature • Finishes desired
F__ . Quantity -Concealed Wrenches - 332765
•Quantity -Protective Caps - P/N 332828 68
VXI/2m
REDUCER
CUP
O
DEFLECTOR
DROP PIN 2 3/4 MAX.
® ® 1 7/8" MIN.
SUPPORT SHELL
CEILING COVER PLATE 3;;5/16"
FLAT PLATE
CONCEALEDPENDENT
GL6)BE
FIR:FSPRINKLIERCOR1 RATIipM
SEPTEMBER 2011
'COVER PLATE
SIZE
WHITE 135°F
PART #
CHROME 135°F
PART #
3 5/16"
332892
332891
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manu-
factured products found to be defective in material or
workmanship for a period of one year from date of ship-
ment.
For specific details of our warranty please refer to Price
List Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.globesprinkler.com
PRINTED U.S.A. BULLETIN GL4906, REV.#1
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT, PENDENT a VERTICAL SIDEWALL
HORIZONTAL SIDEWALL • CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR
THREAD SIZE
LENGTH'
FINISHES
2.8 (39 metric)
1/2" NPT
2 1/4" (5.7cm)
200T
286•F
cULus
FM
Factory Bronze
4.2 (59 metric)
1/2" NPT
2 1/4" (5.7cm)
MODEL
FACTOR
5TC
Chrome
5.6 (80 metric)
1/2" NPT
2 1/4" (5.7cm)
White Polyester
7.8 (111 metric)
1/2" NPT
2 1/4" (5.7cm)
LH
X
X
X
Black Polyester 2.3
8.1 (116 metric)
3/4" NPT
2 7/16" (6.2cm)
—
METRIC CONVERSIONS ARE APPROXIMATE.
HORIZONTAL SIDEWALL IS 2 9/16".
: FINISHES AVAILABLE ON SPECIAL ORDER.
AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
STYLE
SIN
K
135T
155•F
175T
200T
286•F
cULus
FM
LPC.
CE
NYC - DOB
MODEL
FACTOR
5TC
68•C
79•C
93•C
141•C
MEA 101-92-E
GL2815
2.8
LH
X
X
X
X
X
X
—
—
—
X
4.2
LH
X
X
X
X
X
X
—
—
—
X
GL5615
5.6
UPRIGHT
LH/OH
X
X
X
X
X
X
X
X
X
X
GL8115
7.8'
LH/OH
X
X
X
X
X
X
—
—
—
X
GL8118
8.1
LH/OH
X
X
X
X
X
X
X
X
X
X
GL2801
2.8
LH
X
X
X
X
X
X
—
—
—
X
GL4201
4.2
LH
X
X
X
X
X
X
—
—
—
X
PENDENT
GL5601
5.6
LH/OH
X
X
X
X
X
X
X
X
X
X
GL8101
7.8•
LH/OH
X
X
X
X
X
X
X
—
—
X
GL8106
8.1
LH/OH
X
X
X
X
X
X
X
X
X
X
VERTICAL
GL5632
5.6
LH
X
X
X
X
X
X
X
—
—
—
SIDEWALLt
GL8133
8.1
LH
X
X
X
X
X
X
—
—
—
—
GL2826 §
2.8
LH
X
X
X
X
X
X
—
—
—
X
GL4226 §
4.2
LH
X
X
X
X
X
X
—
—
—
X
HORIZONTAL
GL5626 §
5.6
LH/OH
X
X
X
X
X
X
X
—
—
X
SIDEWALL
GL5627o
5.6
LH/OH
X
X
X
X
X
—
—
X
X
—
GL8127 §
8.1
LHIOH
X
X
X
X
X
X
—
—
—
—
CONVENTIONAL
GL5624
5.6
LH/OH
X
XX
X
X
—
—
X
X
(OLD STYLE)
-GL812 1
8.1
1 -LH/OH
X
I X
I X
X
X
1SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6" BELOW THE CEILING.
-INSTALL IN ACCORDANCE TO BS5306 AND ANY OTHER RELATED DOCUMENTS.
tPENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING.
tUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9' MIN. SPACING.
OH: ORDINARY HAZARD
LH: LIGHT HAZARD
•1/2" NPT
ORDERING INFORMATION'
SPECIFY
• Quantity • Model Number • Style
• Orifice • Thread Sizes • Temperature
• Finishes desired
• Quantity - Wrenches - P/N 325390 (1/2");
P/N 312366 (L.O.)
GTL 6DRE
mmm
FIRES PRI KUR 000Rf ATION
JUNE2012
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price, List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583
1-800-248-0278
PRINTED U.S.A.
FAX 989-846-9231
www.globesprinkler.com
BULLETIN GL5615, REV49
a F: s s is t.1.e: '�
DESCRIPTION AND OPERATION
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT*- PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
The Globe Quick Response GL Series Sprinklers are a low
profile yet durable design which utilizes a 3mm frangible glass
ampule as the thermosensitive element. This provides sprinkler
operation approximately six times faster than ordinary sprinklers.
While the Quick Response Sprinkler provides an aesthetically
pleasing appearance, it can be installed wherever standard spray
sprinklers are specified when allowed by the applicable standards.
It offers'the additional feature of greatly increased safety to life and
is available in various styles, orifices, temperature ratings and
finishes to meet many varying design requirements. Quick
Response Sprinklers should be used advisedly and under the
direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that
contains a precisely measured amount of fluid. When heat is
absorbed, the liquid within the bulb expands increasing the internal
pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distributed
in an approved pattern depending upon the deflector style used.
TECHNICAL DATA
QUICK RESPONSE
PENDENT VERTICAL
*See reverse side for Approvals and Specifications. sIDEwALL
•Temperature Ratings - 135°F (57C), 155°F (680C),
175°F (79°C), 200°F (93°C), 286°F (141 °C) AdM6
• Water Working Pressure Rating - 175 psi (12 Bars)
• Factory tested hydrostatically to 500 psi (34 Bars)
iob-
*Maximum low temperature glass bulb rating is -67°F (-55°C) QUICK RESPONSE
• Frame - bronze • Deflector - brass • Screw - brass HORIZONTAL LPC/CE
• Lodgement Wire - stainless steel • SIDEWALL HORIZONTAL
• Bulb seat - copper • Spring - nickel alloy • Seal - teflon SIDEWALL
• Bulb - glass with alcohol based solution, 3mm size
*SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
4077AIRPARKDRIVE, STANDISH, MICHIGAN 48658 989-846-4583 • FAX989-846-9231
JULY 2012 A-20 BULLETIN GI -5615, REV. #9
AVAILABLE SPRINKLER
N.F.P.A. MAXIMUM
CLASSIFICATION
BULB COLOR
TEMPERATURES
CEILING TEMPERATURE
ORDINARY
13S°F�1'SS°F STIG8°C,
ORANGE/RED
INTERMEDIATE
79°C/93°C
YELLOW/GREEN
HIGH
286°F 1d1°C `_
BLUE
x: 225°F. 107°C
> ,.t
4077AIRPARKDRIVE, STANDISH, MICHIGAN 48658 989-846-4583 • FAX989-846-9231
JULY 2012 A-20 BULLETIN GI -5615, REV. #9
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT* PENDENT e VERTICAL SIDEWALL
HORIZONTAL SIDEWALL • CONVENTIONAL (OLD STYLE
SPECIFICATIONS
NOMINAL "K" FACTOR
THREAD SIZE
LENGTH'
FINISHES
2.8 (39 metric)
1/2" NPT
2 1/4" (5.7cm)
200T
286°F
cULus
FM
Bronze
4 2Factory
(59 metric)
1/2" NPT
2 1/4" (5.7cm)
MODEL
FACTOR
57°C
Chrome
5.6, (80. metric)
1/2" NPT
2 1/4" (5.7cm)
. White Polyester'
7.8 (111 metric)
1/2" NPT
2 1/4" (5.7cm)
LH
X
X
X
Black Polyester 2.3
8.1 (116 metric)
3/4" NPT
2 7/16" (6.2cm)
—
METRIC CONVERSIONS ARE APPROXIMATE.
'HORIZONTAL SIDEWALL IS 2 9/16".
2 FINISHES AVAILABLE ON SPECIAL ORDER.
' AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
STYLE
SIN
K
HAZARD'
135•F
155°F
175T
200T
286°F
cULus
FM
LPC
CE
NYC - DOB
MODEL
FACTOR
57°C
68•C
79•C
93•C
141•C
MEA 101-92-E
GL2815
2.8
LH
X
X
X
X
X
X
—
—
—
X
LH
X
X
X
X
X
X
—
—
—
X
GL5615
5.6
UPRIGHT
LH/OH
X
X
X
X
X
X
X
X
X
X
GL8115
7.8•
LH/OH
X
X
X
X
X
X
—
—
—
X'
GL8118
8.1
LH/OH
X
X
X
X
X
X
X
X
X
X
GL2801
2.8
LH
X
X
X
X
X
X
—
—
—
X
GL4201
4.2
LH
X
X
X
X
X
X
—
—
—
X
PENDENT
GL5601
5.6
LH/OH
X
X
X
X
X
X
X
X
X
X
GL8101
7.8•
LH/OH
X
X
X
X
X
X
X
—
—
X
GL8106
8.1
LH/OH
X
X
X
X
X
X
X
X
X
X
VERTICAL
GL5632
5.6
LH
X
X
X
X
X
X
X
—
—
—
SIDEWALLt
GL8133
8.1
LH
X
X
X
X
X
X
—
—
—
—
GL2826 §
2.8
LH
X
X
X
X
X
X
—
—
—
X
HORIZONTAL
GL4226 §
4.2
LH
X
X
X
X
X
X
—
—
—
X
SIDEWALL
GL5626 §
5.6
LH/OH
X
X
X
X
X
X
X
—
—
X
GL5627o
5.6
LH/OH
X
X
X
X
X
—
—
X
X
—
GL8127 §
8.1
LH/OH
X
X
X
X
X
X
—
—
—
—
CONVENTIONAL
GL5624
5.6
LH/OH
X
X
X
X
X
—
—
X
X
-
- -(OLD-STYLE)
GL8125
8:1
-1-'LH/OH
-X-
X
I X-
I X 'I
X
-
_
X
I X
1SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6" BELOW THE CEILING.
oINSTALL IN ACCORDANCE TO BS5306 AND ANY OTHER RELATED DOCUMENTS.
1PENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING.
tUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR T MIN. SPACING.
OH: ORDINARY HAZARD
LH: LIGHT HAZARD
•1/2" NPT
ORDERING INFORMATION
SPECIFY
• Quantity • Model Number • Style
• Orifice • Thread Sizes • Temperature
• Finishes desired
• Quantity - Wrenches - P/N 325390 (1/2");
P/N 312366 (L.O.)
GL613
FIRE $PRDN KLER CORPORATION
JUNE2012
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583
1-800-248-0278
PRINTED U.S.A.
FAX 989-846-9231
www.globesprinkler.com
BULLETIN GL5615, REV.#9
Jl'llll��z
W
J
Q
N
Z
Q
Bronze Spring Loaded Check Valve %"-2"
Figure No. 3600 w/Teflon Disc.
Figure No. 36O0SJ w/Teflon Disc
Figure No. 3615 w/Buna-N Disc
Figure No. 3615SJ w/Buna-N Disc
125 PSI Saturated Steam, with TFE Disc Buna-N Disc Rated at 250 PSI
250 PSI Non -Shock Cold Water, OII, or Gas Fluid Pressure, Non -Shock W.O.G.
lure No. 3600
lure No. 3615
Threaded:
Grinnell check.valves may be installed in vertical lines with
upward flow or In any intermediate position.
Do Not Use For Reciprocating Air Compressor Service.
Do Not Use as a Footvalve.
M
Figure No: 3600SJ
Figure No:•3615SJ
Copper to Copper
1r;�'.a:
01thensi6hs = Weights
Nominal
Size
Part
Specification
1.
Body
.Bronze ASTM B-584
Alloy C84400
2.
Stem
Stainless Steel ASTM
A-582 Alloy S30300.
3.
Spring
316 Stainless Steel
4.
Disc Holder
Stainless Steel Type 301
5.
Disc
Teflon, Rg.3600
SA. Disc
Buna-N, Fig. 3615
6.
Seat Ring
Teflon
7.
8.
Seat Screw
Body End
Stainless Steel ASTM A-276
Alloy S43000
Bronze ASTM B-584
Alloy C84400
M
Figure No: 3600SJ
Figure No:•3615SJ
Copper to Copper
1r;�'.a:
01thensi6hs = Weights
Nominal
Size
Dimensions
Approx.
Net Wt.
Fig. 3600
Approx.
et Wt.
Fig.3600SJ
A
B
C
3/4
2
11/8
17/16
.4
.4
'/2
21hr.
13/e
13/16
.4
.4
314
21/4
15/e
15/16
.5
.5
1
25/e
2
1'/s
8
.9
2'sh6
23/6
111/+6
1.2
1.3
1'/2
35/i4
23/4
2
1.6
1:9
2
33/4
3%
25hr,
2.4
2.7
FIRE SPRINKLER PRESSURE GA
U.S. GUAGL, AMETEK
Use on wet or dry sprinkler systems!
• Solld brass backed!
• 114 A -NTP-LM brass fitting; 3'/2" diameter
• -300 !b./sq. In. Capacity
• , f�iaGDinlG Ti�NII� S ySi�/�9 SD.�:B 6t�A6F
UGES.
ns10ns
goo xQo
rs 21s
io. 250
no
&USTED
FM
APPROVEC
VSR-SF
VANE TYPE WATERPLOW
(0),POTTER FOR SMALL PIPE ALARM SWITCH WITH RETARD
Pottet Elwtrie Signal Company potter Electric Signal & Mfg. LTD
2081 Craig Road • P.O. Box 28480 1987 Leslie Street
St. Louis, MO 63146.4161 Don Mills, Ontario, Canada M392M3
(314) 878.4321 6 (800) 325.3936 (416) 441.1833
UL. ULC, CSFM LIMED and NYMEA ACCEPTED
Service Pressure: Up to 250 PSI
Minimum Flow Rate for Alarm: 10 OPM
Maximum Sura: 18 FPS
Enclesurs: Die-cast, red enamel finish.
Cover. held In puce wMi tamper resistant wawa
Contact Ratings: Two seta of SPOT (Form C)
16.0 Anila at 123250 VAC
2.0 Amps at 0.30 VDC
Condult Entraneas: Two Knockouts provided for 12' oondutt
Usage. Listed Plastic, Copper and Schedule 40 Iron Pipe
Fits pipe sizes - 1', 1 1/4', and 1 12'
Note: 9 paddies are furnished wfth each unit one for each pipe
size of threaded or sweat TEE, one for 1' CPVC, and one for
1 1/2' polybutylene (CTS -Copper tubing size)
Environnsentbl speotflcatlons:
8ultable for Indoor or outdoor use with factory Installed gasket
and die-cast housing
NEMA 4 Rated Enclosure • use with appropriate eondufi. Meng
Temperature Range: 40• F/120- F (4.5° C/4ir C)
Caution: This device Is not Intended for applk:attons In exploolve
onvlronments
service Use*
Automate Sprinkler NFPA-13
One or two family dwelling NFPA-130
STK. NO. 1113000 "-' "" '° Resldentiat ooeupaM up to four stories NFPA-13R
U.S. PAT. NO. 3921989. CANADIAN PAT, NO. 4009680 National Flee Alarm Code NFPA-72
OTHER PATENTS PENDING. ;.; : Optloml: Cover Tamper Switch, order Stk. No. 009mill '
f rtnW r The vane meet not rub the Inside of the TEE or blvd In anyway. The stern
The Model VSA -SF Is a vane type waterflow switch for use on we w e
systems that use 1%, J 1/4', or 1 1/2' pipe size. The unit may also be used
as a sectional wate flow detector on large systems.
The unit contains two single pole double throw $nap eoban switches and
en adjustable: pneumatic retard. The ewltchea are actuated when a Now of
w10 gallons per.minute.or more occurs downstream of the devtoi. The flow
condition must exist for a perlod of time necessary to overcome the
selected retard period. I
INSTALLATION: These devices may be mounted In her tontsl or vertical
pipe. On horizontal pipe they should be Installed on the top side of the pipe
where they will be ncceaalble. The units should not be Installed within ti'
of a valve, drain or fhting »filch changes the direction of the waterflow. The
unft has a 14 NPT tushing for threading Into a noncomoslve TEE. See Fig,
2 for proper TEE size, type and Installation.
8crewthe device into the TEE toting as shown In Fig: 2. Care muatbe taken
to property orient the device for the direction of waterflow. .
should move freely when operated by hand.
The device can also be used In copper or plastic pipe InetAUtions wfth the
proper adapters so that the specified TEE fftttnq may be installed on the
pipe run.
INSPECTION AND TESTINO: Check the operation of the unit by opening
the Inspector' teat valve at the end of the eprinWer Me or the drain and test
bonttaetion, N an Inspector's test valve to not provided.
If then are no prcMglons for testing the operation of the Now detection
device on the system, spplleaBon of the VSR-SF in not recerrxnended or
'advisable
The kequency of the Inspection and testing and Its 686001111ted protective
nnonitorhtg system should be In 600"nce with the applicable NFPA
Codes and Standards and/or authority havN lurisdictlon (manufacturer
recommends quarterly or more frequently).
ese
les have raised
CAUTION: There EEre 8 thatpthedles fumlshed with each unit. art be used with. The propertpaddleddiaLW be used.I The screw that holds he Paddle
l-ing that shows the pipe
size and type o Y
must be securely tightened.
MKT. i03000Q2 • REV I PAGE 1 CW.2
PRINTED IN USA Mira. 09400M - 3/06
(e),BELLS
POTTER.
PBA-AC &PBD -DC
Potter Electric Signal Company Potter Electric Signal & Mfg. LTD
2081 Craig Rd.,/P.O. Box 28480 1967 Leslie Street
St. Louis, MO 63146 Don Mills, Ontarlo, Canada M3B2M3
(314)878-4321 / (800) 325-3936 (416) 441-1833
UL LISTED, FM APPROVED
Sizes Available: 6", 8", and 10"
Voltages Available: 24VAC
120VAC
12VDC (10.2 to 15.6) Polarized
24VDC (20.4 to 31:2) Polarized
Service Use: Fire Alarm
General Signaling
-Burglar Alarm
Environment: Indoor or Outdoor Use (See Note 1)•
-40° to 150°F (outdoor use require'
'-weatherproof backb6x)
Termination: 4 No. 18 AWG stranded wires ..` -
Finish: Red powder coating
6" BELL SHOWN Optional: Model BBK-1 weatherproof backbox
These vibrating type bells are designed for use as fire, burglar, or -general signaling devices. They_have low power
consumption and high decibel ratings. The unit mounts on a standard 4" square electrical b6z_for,indoor use, or on a model
BBK-1 weatherproof backbox for outdoor applications..
ALL DC -BELLS ARE POLARIZED AND HAVE BUILT-IN TRANSIENT PROTECTION:
SIZE
VOLTAGE
MODEL NO.'
STOCK NO.
CURRENT (MA)O
TYPICAL 010FT.
.
MINIMUM dB
.®LOFT. -
6
12VDC
PBD126
1706012
.UA
85
75
8
12VDC
PBO128
1708012
.12A
90
75
10
12VDC
PBD1210
1710012
.12A
92
75
6
24VDC
PBD246
1706024
.06A
87 '
75
8
24VDC
PBD248
.1708024
.06A
91
79
.10
24VDC
PBD2410
1710024
.06A
94
79
6
24VAC
PBA246
1806024
.17A
91
75
8
24VAC
PBA248
1808024
.17A
94
75
10
24VAC
PBA2410
1810024
.17A
94
75
6
120VAC
PBA1206
1806120
.05A
92
82
8
120VAC
PBA1208
1808120
.05A
99
82
10
120VAC
PBA12010
1810120
.05A
99
85
Weatherproof backbox model BBK-1 Stk. No. 1500001.
Notes:
1. Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified in UL Standard 464. UL
temperature range is -30° to 150°F.
2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation.
PRINTED IN USA MKT. #8850001- REV K PAGE 1 OF 2
MFG. #5400776 - 4/94
9600 KLINGERMAN STREET * P.O. BOX 3365 ,
` O SOUTH EL MONTE, CA 91733 * USA
TEL: 626.444.0541 * FAX: 626.444.3887
odd E-MAIL: info@afcon.org * www.afcon.org
C(S)US
CPUC - STEEL, - COPPER
#510 #511 #514
0
o 10 Patented
o
0
Installation Instructions
Install on CPUC pipe as a hanger and/or restrainer
._-...__.__.....__.....�__.._.___ .pe.i-._their_e.nbineering.sh.e.ets.:Some.are..additi6nAlly. _ ....
listed for use for use with steel and copper pipe.
#510 & #514 install on top, bottom or side
of beam.
#511 install on top or bottom of beam.
#513 install on top or side of beam.
r
r #515 & 519 install on side of beam.
Required fasteners furnished: #904 for #515
T c.P.Vc. Max. Hanger #905 for #510 thru #514
Pipe `izc . Spacing
♦ 3/4 ----- -------- 5 11
I
1/4 -------- 6 1/2
2 -------------- S
3 1 /' -------------- 1