HomeMy WebLinkAboutB17-1993 033-110-0572016 CALGreen Residential Mandatory Measures
'. ,This checklist applies to newly constructed bungs, additions or alterations of existing residential
buildings where the addition or alteration increases the building's conditioned area, volume, orsize.
The requirements shall only apply to and or within the specific area of the addition or alteration.
(2016 CGBSC 301.1.1) -
***Note 2016 CGBSC 301.1.1: On and after 11112014, residential buildings undergoing permitted
alterations, additions or improvements shall replace noncompliant plumbing fixtures with water -
conserving plumbing fixtures. Plumbing fixture replacement is required prior to issuance of a
certificate of final completion, -certificate of occupancy or final permit approval by'the local building
department." -
Feature or Measure
Required
MaiA
IN
plan is developed and implemented to manage storm water drainage during -
construction. CGBSC 4.106.2.•
'
Construction plans shall indicate how the site grading or drainage system will manage
all surface water flows to keep water from entering buildings CGBSC 4.106.3.
Provide capability for electric vehicle charging in one and two-family dwellings and in
townhouses with attached private garages; and 3 percent of total parking spaces, as
specified, for multifamily dwellings. -
Building meets or exceeds the requirements of the California Building Energy
Standards. CGBSC 4.201.1.
Water closets. closets. The effective flush volume of all water closets shall not exceed 1.28
;� gpf. Tank -type water closets shall be certified to the performance criteria of the U.S.
EPA WaterSense Specification for Tank -type Toilets.
-Note: The effective flush volume of dual flush toilets is defined as the composite,'
.
average flush volume of two "reduced flushes and one full flush.
Urinals. The effective flush volume of wall mounted urinals shall not exceed 0.125gpf
,
and floor mounted or other urinals shall not exceed 0.5 gpf:.
Single showerheads: Showerheads shall have a max. flow rate of not more than 2.0
gpm at 80 psi. Showerheads shall be certified to the performance criteria of the U.S.
EPA WaterSense Specification for Showerheads.
,1
Multiple showerheads serving one shower. When a shower is served by more than
;--
one showerhead, the combined flow rate of all the showerheads and/or other shower
�" }
outlets controlled by a single valve shall not exceed 2.0 gpm at 80 psi, or the shower
shall be designed to allow only one shower outlet to be in operation at a time.
Residential lavatory faucets. The max. flow rate of residential lavatory faucets shall
` not exceed 1.2,gpm at 60 psi. The min. flow rate of residential lavatory faucets shall
'
not be less than 0.8 gpm at 20 psi.
Metering faucets. Metering faucets when installed in residential buildings shall not
`
deliver more than 0.25 gallons per cycle.
'
Kitchen faucets. The max. flow rate of kitchen faucets shall not exceed 1.8gpm at 60
'
psi. -
Checklists\Green Building
J
Page 1 of 3,
t �
02/10/2017',
2016 CALGreen Residential Mandatory Measures Checklist (Cont'd)
Feature or Measure
Required
�• 5`'xLL' a fC -� _. •• :i — r: �:>_'
•t JF. ... �.0 _ . • rs .. _. Y iti. � ._ ' _-�rc�i`.�.^•.,.,r : ,!c '" � � :;4_ �t - � : •'�+L�•iij•:. �. •r�•, }-�-. c r:
'L r
r::.-:cac::: s Y•;
:+... .11�� �. is rT:iL ti?''F f _ i�4T:
New residential developments with an aggregate landscape area equal to or greater
than 500 sq ft shall comply with one of the following options:
I. A local water efficient landscape ordinance or the current California Department
of Water Resources Model Water Efficient Landscape Ordinance (MWELO),
whichever more stringent; or
2. Projects with aggregate landscape areas less than 2,500 sq ft may comply with
the MWELO Appendix D Prescriptive Compliance Option.
Rodent proofing. Annular spaces around pipes, electric cables, conduits, or other
openings in sole/bottom plates at exterior walls shall be protected against the passage
of rodents by closing such openings with cement mortar, concrete masonry or similar
method acceptable to the enforcing agency.
Recycle and/or salvage for reuse a minimum of 65 percent of the nonhazardous
construction and demolition waste in accordance with one of the following:
---1-Comply-with-a-more-stringent- local--construction-and demolition-waste---------
-- -
management
management ordinance; or '
2. A construction waste management plan, per Section 4.408.2; or
3. A waste management company, per Section 4.408.3; or
4. The waste stream reduction alternative, per Section 4.408.4.
O&M Manual: An operation and maintenance manual shall be available in the building-
at the time of final inspection.
Recycling by Occupants: Where 5 or more multifamily dwelling units are constructedy
on a building site, provide readily accessible area(s) that serves all buildings on the
site and is identified for the depositing, storage and collection of non-hazardous
materials for recycling, including (at a minimum) paper, corrugated cardboard, glass,
plastics, organic waste, and metals, or meet a lawfully enacted local recycling
ordinance, if more restrictive. See exception for rural jurisdictions.
ti.
.fBill
150
Nola=_I
_ :c.� Lam•,PANKIS
Any installed gas fireplace shall be direct-vent sealed-combustion type. Any installed
woodstove or pellet stove shall comply with U.S EPA New Source Performance
Standards (NSPS) emission limits as applicable, and shall have a permanent label
indicating they are certified to meet the emission limits. Woodstoves, pellet stoves and
fireplaces shall also comply with applicable local ordinances.
=:��- - ^ ?ucF::.:m: tr--. • _ _ _;:L' ^+.ri: `•"-:_.ia:'__3-i£':• w:•s.
.Q. 'I� ��nt::C4� :r9� -, :3` ' : .�L�:. _r.. - � - •-:� �:>:r:... .L .. �_.,._, ;:�:-•,-� .
T II Fr • n� -
_ «,__ F • c - _
Duct openings and other related air distribution component openings shall be covered
during construction.
Adhesives, sealants and caulks shall ,be compliant,with VOC and other toxic
compound limits
Aerosol adhesives-and smaller unit sizes of adhesives and sealant or caulking
compounds shall comply with statewide VOC standards and other requirements.
Paints, stains and other coatings shall be compliant with VOC limits. 4.504.2.2
Check Iists\Green Building
t
Page 2 of 3
. 02/10/2017
2016 CALGreen Residential Mandatory Measures Checklist-(cont'd)
i Feature or Measure
Required
Aerosol paints and coatings shall be compliant with product weighted MIR limits for
ROC and other toxic comr)ounds.
Carpet and carpet systems shall be compliant with VOC limits. 4.504.3
At least 80% of floor area receiving resilient flooring shall comply with
specific VOC criteria.
'Hardwood plywood, particleboard and medium density fiberboard (MDF) used on
interior or exterior of the building shall comply with formaldehyde emission
standards.
Documentation shall be provided to the City building inspector verifying that compliant
.
materials have been used.
, •r
Concrete Slab Foundations: Vapor retarder and capillary break is installed at slab -
on -grade foundations.
Moisture content of building materials used in wall and floor framing shall not
exceed 19% before enclosure. Moisture content shall be verified in compliance with
-.
CGBSC 4.505.3.
Indoor Air Quality and Exhaust (4.506)
Bathroom exhaust fans shall be ENERGY STAR rated and ducted to terminate
outside.
-Unless functioning,as a component of a whole house ventilation system, bathroom
exhaust fans must be controlled by.a humidity control adjustable between a relative
humidity range of 50% - 80%.
;a F
Duct systems are sized, designed, and equipment is selected using the following
methods:
I. Establish heat loss and heat gain values according to ANSI/ACCA 2 Manual
t
J-2011 or equivalent.
2. Size duct systems according to ANSI/ACCA 1 Manual D-2014 or equivalent.
3.Select heating and cooling equipment according to ANSI/ACCA 3 Manual S-
"
2014 or equivalent.
`rvr..IN-Mr.t�F
•Cig!ti F= iTt.' r.�'it. r -•-•c-_' z
HVAC system installers are trained and certified in the proper installation of HVAC
systems.
Special inspectors employed by the enforcing agency must be qualified and able to
demonstrate competence in the discipline they are inspecting.
- = ! .' %r` •Li,. °+ ass: :-' t�z r _,i rn•R
�,°4E ::: . ^�qK
:•,:•_.,::,:_:,: ........_:::,•:.:—:d. .�.;_. :'�__: +�. .c.:�. ... = __�_ •� ..� 4 :r„= �a1LL•6��' ...tLl.t.,ar�.ec
.
Verification of compliance with this code may include construction documents,
plans specifications builder or installer certification, inspection reports, or other
methods acceptable to the enforcing agency, which show substantial conformance.
• ChecklistslGreen Building Page 3 of 3 02/10/2017
Butte County Department of Development Services
PERM, IT CENTER
7 County Center Drifte, Oroville, CA 95965
Main Phone 530.538.7601 Fax 530.538.7785
• �ilttit'.hll[tLCOUnlS'.I1�IJC1d�
SITE [ALAN Assessor's Farce Number. I E I FT I F 0 I n o on ® 0
)FORM NO
SID Q.o �" - _
Owner Name: Scope of Work — -- —. _ _ _ �- �- L , _
�.
` mSite Location: CA,rJ 4 ors H—( f-f1A-AD5 (�lZ
c
Contact name: sArmE-- Phone:5-3t, -- 6C -ISQ6 5 )P7— o�
Flood Zone: % Scale 1"= - A
KABUILDING\Aluira Revised forms for review 11-17-141Fully revised forms and documents 12-01-140BP-O3_Site—Plan_Paper_REV'D-8.13.14—AKM.doc
Page I of 1 `
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD ' , CFS 1R -PRF -01
Project Name: Residential Building Calculation DateITirre: 15:23, Fri,, Aug 25, 2017- - j y" F, Page 1 of 8'
Calculation Description: Title 24 Analysis.` • Input File Name: perkins addition.ribd16x
GENERAL INFORMATION
ENERGY USE SUMMARY
01
Project Name Residential Building
04
-
02
Calculation Description Title 24 Analysis
08
-
03
Project Location 495 Canyon Highlands Drive .
Compliance Margin
Percent Improvement.
04 : '
.. City Oroville
05%.
Standards Version Compliance 2017
06
Zip Code 95966 '
07' ;
Compliance Manager Version BEMCmpMgr 2016.2.1 (695)
'08 _
Climate Zone CZ11 -
09 . '
Software Version EnergyPro 7.1
10
—Building Type Single Family
11 -
Front Orientation (deg/Cardinal) 315-
12
Project Scope Addition and/or Alteration
13
Number of Dwelling Units 1
14-
Total Cond. Floor Area (ft2) 2443
15
Number of Zones 2 .
16
Slab Area (ft2) 440
17. '
Number of Stories 1
18
Addition Cond. Floor Area 440
19 ' ..
Natural Gas Avallable Yes
20
Addition Slab Area (ftt2)440
21
Glazing Percentage ("/o) 13.9%
COMPLIANCE RESULTS
01 Building Complies with Computer Performance
02 This building DOES NOT require HERS Verification
03 This building Incorporates one or more Special Features shown below
This compliance analysis Is valid only for permit applications through October 24, 2017 .
ENERGY USE SUMMARY
04
05
06
07
08
Energy Use (kTDV/ft2-yr) _
Standard. Design'
Proposed Design
Compliance Margin
Percent Improvement.
Space Heating
37.35
39.69 '
-2.34
-6.3%
Space Cooling
IAQ Ventilation
-115.26
0.00
112.83
0.00-.
2.A3
0.00
2.1
0.0%
Water Heating
10.86.
10.86
. 0.00.
0.0%0
Photovoltaic Offset
0.00.
0.00
Compliance Energy Total
163.47,
163.38
0.09
0.1%
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD • • .. . CF1 R -PRF -01:
Project Name: Residential Building Calculation Date/Time: 15:23, Fri, Aug 25;•2017• ' Page 2 of 8
Calculation Description: Title 24 Analysis Input File Name: perkins addition.ribdl6x
REQUIRED SPECIAL FEATURES '
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
• Whole house fan * `
• Window overhangs and/or fins
New ductwork added is less than '40 ft: In length,
HERS FEATURE SUMMARY
The following is a summary of the features that must be field -verified by a certified.HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications-
-None--
Cooling
erifications:—None- Cooling System Verifications: -
None — . .
HVAC Distribution System Verifications:
— None —
Domestic Hot Water System Verifications:
— None
BUILDING - FEATURES INFORMATION
01
02
03
04
05
06
07
Project Name
Conditioned Floor Area (ft2)
Number of Dwelling
Units
Number of Bedrooms
Number of Zones
Number of Ventilation
Cooling Systems
'Number of Water ,
• Heating Systems
Residential Building
2443-'1
.06 .
.3
2
1
1
ZONE INFORMATION
01
02
03
04
05
.06 .
07
Zone Floor Area.
Avg. Ceiling'
Zone Name
Zone Type •
HVAC System Name
(ft2)
Height
Water Heating. System 1
Water Heating System 2.
First Floor Existing
Conditioned
HVAC Systeml
2003..
8
DHW Sys 1
n/a
First Floor Addition
Conditioned
HVAC Systeml
440.
8
DHW Sys 1
n/a ;
:Registration Number:
Registration Date/Time:
:HERS Provider.
- -
CA Building Energy Efficiency Standards - 2016 Residential Compliance
Report Version - CF1 R-07312017-695.
• ..
Report Generated at: 2017-08-25 15:24:12
CERTIFICATE OF COMPLIANCE - RESIDENTIAL- PERFORMANCE COMPLIANCE METHOD ' • `, ' a ' - CF1R-PRF-01
Project Name: Residential Building ' ,-
` 3 ' "Calculation DatelTime: 15:23; Fri; Aug 25, 201 T • Page 3 of 8 ,
Calculation Description: Title 24 Analysis.* - Input File Name: perkins addition.ribd16x
OPAQUE SURFACES
01
.._
03
04
05
06
07
08
09
01.
02
03 • .
04
05...
06
07
08
09
10
'Name' ` f
Zone
Construction
Azimuth
Orientation
Gross Area (ft2)
Window&'Door
Area (ft2)
Tilt
(deg)
Status
Verified
Existing
Condition.
Front Wall
First Floor Existing
'Default Wall 1978 to 1991"
315
Front
152.
41
90
Existing.
No
Left Wall •
First Floor Existing
Default Wall 1978 to 1991.
45
Left
152'
6.25
90
Existing
No
Rear Wall .
First Floor Existing ..
Default Wall 1978 to 1991
135
Back
360..
113.3 '- . -
:90
Existing
No
Right Wall
First Floor Existing
Default Wall 1978. to 1991
225
Right
• 80
0
90
Existing
No
Front Left Wall
First Floor Existing
Default Wall 1978 to 1991
0
45
368
28
90
Existing
No
Rear Left Wall
First Floor Existing
Default Wall 1978 to 1991
90
135
120
24
90
Existing
No
Rear Right Wall
First Floor Existing
Default Wall 1978 to 1991
180
225
352
58.5
90
Existing
No .
Front Right Wall
First Floor Existing
Default Wall 1978 to 1991
270
315
•260
28
90
Existing
No
Roof
First Floor Existing
Default Roof 1978 to Pres
2003
Existing
No .
Raised Floor
First Floor Existing
Default Floor Crawlspace
2003
Existing
No
Front Wall 2
First Floor Addition
R-13 Wall
315
Front
176
48
90
New
N/A
Left Wall 2
First Floor Addition
R-13 Wall
45
Left
176
28.7
90
New
N/A.
Right Wall 2
First Floor Addition
R-13 Wall
225
Right
88 •
• 0
90 -
New
N/A
Roof 2
First Floor Addition
R-38.Roof Attic
440
New
N/A
ATTIC
01
02
03
04
05
06
07
08
09
10
Name
Construction
Type
-
Roof Rise
':Roof
Reflectance
Roof
Emittance
. Radiant
Barrier
Cool
Roof
Status
-Verified Existing
Condition.
Attic First Floor Existing
Attic RoofFirst Floor Existing
Ventilated
4
0.1 •
0.85
No
No
Existing
No
Attic First Floor Addition
Attic RoofFirst Floor Addition
Ventilated
4
0.1
0.85
No
No
Ne
11
w
No=
1.
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF701'
Project Name: Residential Building ' ' Calculation DateITime: 15:23, Fri,, Aug 25, 2017: Page 4 of 8
Calculation Description: Title 24 Analysis Input File Name: perkins addition.hbdl6x '
FENESTRATION / GLAZING,
01
1
03.
01" ��
-02
03 04
05
06
07
08
09
10
11
•
Name �' '
Surface (Orientation -Azimuth) .:
-
Width(ft) Height (ft)
. Multiplier
Area (ft):
U -factor
SHGC'
Exterior Shading-
Status ' :
- Verified
Existing '
' Condition
Wiridow
Front Wall (Fr6nt-315)
Bot Up
Depth
Z21.0
0.58
0.65
1nsect Screen (default).
Existing
No
Window 2. -
Left Wall.(Left-45)
- --
1
6.21 j
0.58
'0.65
Insect Screen (default)
Existing
No
Window 3
Rear Wall (Back -135)
-- --
1- ..
13.3'-) ,0.58.
0.65
Insect Screen (default)
Existing,
No
Window 4
Front Left Wall (- specify --0)
-- --
1. "
28.0
0.58
0.65
Insect Screen (default)
Existing
No =
Window 5
Rear Left Wall (- specify --90)
-- --
1
j24.0
0.58
0.65
Insect Screen (default)
Existing
No
Window 6
Rear Right Wall (-specify 180
-- --
1
58.5 _
0.58
0.65
Insect Screen default
Existing
No
Window 7
Front Right Wall (- specify -270)
-- --
1
428.0-
0.58
0.65
Insect Screen (default)
Existing
No
Window 8
Front Wall 2 (Front -315)
- --
1
! 48.0 _
0.32
0.23
Insect Screen (default)
New
N/A
Window 9
Left Wall 2 (Left -45)
3.0 4.0
1
-412.0
0.32
0.23
Insect Screen (default)
L New
N/A
OPAQUE DOORS
01
02
03.
04
05 '
-06
Name
Side of Building
Area (ft2) .
U -factor'
Status
Verified Existing Condition
Door
Front Wall
X20.0
0.50
Existing
No
Door 2 '
Left Wall 2
(16.7
0.50
New.
No
OVERHANGS AND FINS
01
02
03
04
05 ., 06
07
08 09. 10
11 12 13 14
Overhang
- Left Fin
Right Fin
Window
Depth
Dist Up
Left
Extent
Right
ExtentFlap
Ht.
DepthTop
Up
DIstL
Bot Up
Depth
Top Up ',
Dist R'
Bot Up.
Window
2
0.1
2
2
0
0
0
;0
0
0
0
0
U
CERTIFICATE OF. COMPLIANCE RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01
Project Name: Residential Building Calculation Date/Time: 15:23, Fri; Aug 25, 2017 : Page 5 of 8 .
Calculation Description: Title 24 Analysis Input File Name: perkins addition.ribd 1 6x
OPAQUE SURFACE CONSTRUCTIONS '
01
02 ...
03 ..
04 .
05
06
07
08
09
N3mo
gone
Total Cavity
Winter Design
Edge Insul. R -value
Construction Name,
Surface Type
Construction Type
Framing
R -value
U -value
Assembly Layers
88
None .
0.8
No
New
No
Cavity/ Frame: no insul.-/2x4 Top Chid
2x4 Top -Chord of Roof Truss @ 24.
Roof Deck: Wood Siding/sheathing/decking
Attic RoofFirst Floor.Existing
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
• Floor Surface: Carpeted
Floors Over
Floor Deck: Wood Siding/sheathing/decking '
Default Floor Crawlspace
Crawlspace
Wood Framed Floor
2x12 @16 in. O.C.
none
0.216
Cavity/Frame: no insul. /2x12
• Inside Finish: Gypsum Board
• Cavity/Frame: R-11 /2x4
• Exterior Finish: Wood
Default Wall 1978 to 1991
Exterior Walls
Wood Framed Wall
2x4 @ 16 in. O.C:
R11
0.103
Siding/sheathing/decking
• Inside Finish: Gypsum Board
Ceilings (below
Cavity/Frame: R-9.1 /2x4
Default Roof 1978 to Pres
attic)
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 19
0.049
Over Ceiling Joists: R-9.9 insula
• Cavity/ Frame: no insul. / 2x4 Top Chrd
.2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood siding1sheathing1decking
Attic RoofFirst Floor Addition
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing. Light Roof (Asphalt Shingle)
Inside Finish: Gypsum Board
• Cavity/Frame: R -13/2x4
• Exterior finish: Wood
R-13 Wall
Exterior Walls,
Wood Framed Wall
2x4.@,16 in. O.C.
R 13
0.095
Siding/sheathing/decking
Inside Finish: Gypsum Board
Ceilings (below
Cavity/Frame: R-9.1 /2x4
R-38 Roof Attic
attic)
Wood Framed Ceiling
2x4 @ 24 in. O.C.
R 38
0:025
Over Ceiling Joists: R-28.9 insul.
SLAB FLOORS
01
02
03
04
05
06
07
08
09
N3mo
gone
Area (ftp)
Perirgeter
(ft)
Edge Insul. R -value
Carpeted
Fraction
. Heated.
Status
Verified
LkIsting
Condition
Slab
First Floor Addition
440,
88
None .
0.8
No
New
No
BUILDING ENVELOPE —HERS VERIFICATION
01 02. 03 04
Quality Insulation Installation (QII). Quality Installation of Spray Foam Insulation Building. Envelope Air Leakage CFM50
Not Required Not.Required• Not Required --
Registration Number. Registration DateTme:
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-07312017-695.
CERTIFICATE OF COMPLIANCE =RESIDENTIAL PERFORMANCE COMPLIANCE METHOD , CF1 R-PRF=01:
Project Name: Residential Building Calculation Dateffime: 15:23, Fri, Aug 25, 2017: = - Page 6 of 8
Calculation Description: Title 24 Analysis Input File Name: perkins additionAbd 1 6x '
WATER HEATING SYSTEMS - =
01
02
0304
04 05
OS
O6
07
08
System Type
01
Efficiency
EER SEER
..02,
03 '
Solar
05
06
."07
08
09
Not Zonal
Number of
Fraction
Name
Verified Existing
'Name `_
System Type'
Distribution Type `
'Water Heater
Heaters
(%)
Status
Condition
DHW Sys 1
DHW
Standard
DHW Heater 1 -
-1
Annual,
Existing
No
WATER HEATERS
01
02
03
04 05
06
07
08
..
System Type
01
Efficiency
EER SEER
..02,
03 '
04
05
06
."07
08
09
Not Zonal
10
11
Name
Heater
Element Type
Tank type -'of
Number
Units
Tank •
Volume.
(gal),
Energy
Factor or
Efficiency
Input ..
Rating/Pilot
Tank Insulation
R -value
(Int/Ext)
-Standby Loss/
Recovery Eff
NEEA Heat Pump Type
Tank Location.or
Ambient
Condition
DHW Heater 1
Gas
Small Storage
'1
50
0.6 EF
40000 Btu/hr.
n/a
n/a
n/a
n/a
SPACE CONDITIONING SYSTEMS
01
02
03
04
05
06
07
08
09
Heating System
Cooling System
Name
System Type'
Name
Ducted
Name
Ducted
Distribution
. System
Fan .
System
Floor Area
Served
Status
Verified Existing.
Condition
HVAC Systeml
Other Heating and
Cooling System
Heating
Component 1
Yes
Cooling
Component 1:
Yes
.
Air Distribution
. System 1
HVAC Fan
1
2443
Existing
No
HVAC - HEATING UNIT TYPES
01 02 03 04
Name System Type Number of Units Efficiency
Heating Component 1 CntrlFumace 1 78 AFUE
HVAC - COOLING UNIT TYPES
01
02
03
04 05
06
07
08
Name _ __
System Type
Number of Units
Efficiency
EER SEER
Zonally Controlled
Compressor Type
HERS Verification.
Cooling Component 1
SplitAirCond
1
9.6
11
Not Zonal
Single Speed
Cooling Component
1=hers-cool
CERTIFICATE OF COMPLIANCE RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1 R -PRF -01 :
Project Name: Residential BuildingCalculation DatelTime: 15:23; Fri; Aug 25, 2017 Page 7 of 8 .
Calculation Description: Title 24 Analysis_ Input File Name: perkins addition.ribdl6x '
HVAC COOLING - HERS VERIFICATIONx'
01
02 _
03
04 ..
05
06
NameVerified
Alrflow
AlrflowTarget
Verified EER
Verified SEER
Verified Refrigerant
Charge
Cooling.Component 1 -hers -cool
Not Required
n/a
Not Required
Not Required
Not Required
HVAC - DISTRIBUTION SYSTEMS
01
02
03
04
05
06
07
08'
09 ,
-10
Name
Type
Duct Leakage
Insulation
R -value
Supply Duct:
Location
Retum Duct
Location
'Bypass Duct
Status
Verified Existing
Condition
HERS
Verification.
Air Distribution
System 1
Ducts located in attic
(Ventilated and
Unventilated)
Existing (not
specified)
6.0
Attic
Attic
None
Existing + New
No
N/A
IAQ (Indoor Air Quality) FANS
01
02
03.
04
05
Name
IAQ CFM
IAQ Fan Type IAQ Recovery Effectiveness(%)
HERS Verification
SFam IAQVentRpt
0
Default
0
Not Required
COOLING VENTILATION
01 02 03 04 05 .. 06
Name Airflow Rate (CFM/ft2) Cooling Vent CFM Cooling Vent Watts/CFM Total Watts Number of Fans
WH Fan 1 2.046663937781416 5000 0.1 500 1
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Residential Building Calculation Date/Time: 15:23, Fri, Aug 25, 2017
Calculation Description: Title 24 Analysis Input File Name: perkins addition. ribd 1 6x
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Documentation Author Signature:
Rick Rocklewitz ,
1687
Company:
Signature Date:
NRG Compliance, LP.
:8/25/2017
Address: "
PO Box 3777,
CEA/HERS Certification Identification (If applicable):
City/Stateggr to Rosa, California 95402
Phone: 707-237-6957
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.
3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with thi uilding permit application.
Responsible Desi ner Name:
Glen duigley
Res I e ' n r Signature:
Company:
Glen Quigley
Date Signed:
Address:
2689 Forest View Drive
License:
City/State/Zip:
Oroville, California95966
Phone:
530-864-1520
Registration Number. Registration DateTme:
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-07312017-695
RESIDENTIAL MEASURES SUMMARY
RMS4
Project Name
SCOP Perkins
Building Type
m Single Family ❑ Addition Alone
❑ Multi Family m Existing+ Additon/Alteration 1812512017
Date
Project Address
495 Canyon Highlands Drive Oroville
California Energy Climate Zone
CA Climate Zone 11
Total Cond. Floor Area
2,443
Addition
.440
# of Units
1
INSULATION
Construction Type
Cavity
Area
(ft) Special Features Status
Floor Wood Framed w/Crawl Space no insulation
2,003 Existing
Wall Wood Framed R11
1,673 Existing
Door Opaque Door - no insulation
20 Existing
Roof Wood Framed Attic R 19
2,003 Existing
Wall Wood Framed R 13
363 New
Door Opaque Door no insulation
17 New
Roof Wood Framed Attic R38
440 New
Slab Unheated Slab -on -Grade - no insulation
440 Perim = 88' New
FENESTRATION I Total Area: 3391 Glazing Percenta e: 13.9 % New/Altered Average U -Factor. 0.32
Orientation Area(ft) U -Fac SHGC Overhang Sidefins Exterior Shades Status
Front (NKK 21.0 0.580
0.65 none
none Bug Screen Existing
Left (NE) 6.3 0.580
0.65 none
none Bug Screen Existing
Rear (SE) 113.3 0.580
0.65 none
none Bug Screen Existing
Front (N) 28.0 0.580
0.65 none
none Bug Screen Existing
Left (E) 24.0 0.580
0.65 none
none Bug Screen Existing
Rear (S) 58.5 0.580
0.65 none
none Bug Screen Existing
Right (Kq 28.0 0.580
0.65 none
none Bug Screen Existing
Front (NW) 48.0 0.320
0.23 none
none Bug Screen New.
Left (NE) 12.0 0.320
0.23 2.0
none Bug Screen New
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling
Min. Eff Thermostat Status
1 Central Furnace 78% AFUE
Split Air Conditioner 11.0 SEER Setback Existing
HVAC DISTRIBUTION
Location I Heating
Cooling
Duct
Duct Location R -Value Status
HVAC System Ducted
Ducted
Attic 6.0 Altered
WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
EneigyPro.7.1 by EnerovSoft User Number. 5581
0: 0825170 Pae 11 of 15
2016 Low -Rise Residential Mandatory Measures Summary
NOTE. Low-rise residential buildings subject to the Energy Standards must comply with all applicable mandatory measures, re:Iardless'of the compliance approach
used. Review the respective'section for more information. 'Exceptions may apply.
(Oriainsl 118/20161 .
Building Envelope Measures:
§ 110:6(a)1`
Air Leakage.' Manufactured fenestration, exterior doors, and exterior pet doors must limit air leakage to 0.� cfm/ft' or less when tested per
NFRC400 or ASTM E283 or AAMA/WDMAICSA 101/I.S.2/A440-2011 '
§ 110.6(a)5: -
Labeling. Fenestration products must have a label meeting the.requirements of § 10-111(a). '
§ 110.6(b):
Field fabricated exterior doors and fenestration products must use U -factors and solar heat gain coeffiient (SHGC) values from TABLES
-
110.6-A and 110.6-13 for compliance and must be caulked and/or weatherstn ed.'
10 7 ,"
§ 110.7--
Air Leakage. All joints, penetrations, and other openings in the building envelope that are potential sources of air leakage must be _caulked, '
asketed, or weather stripped:
§.110.8(a):
Insulation Certification by Manufacturers. Insulation specified or installed'must meet Standards for Insilating Material. "
§ 110.8(g):
Insulation Requirements for Heated Slab Floors. Heated slab floors must be insulated per the requirements of § 110.8(g).
§ 110.8(i):
Roofing Products Solar Reflectance and Thermal Emittance. The thermal emittance and aged solar reflectance values of the roofing
material must meet the requirements of§ 110.8(i) when the installation of a cool roof is specified on the CFI R.
§ 110.80):
Radiant Barrier. A radiant barrier must have an emittance of 0.05 or less and be certified to the Department of Consumer Affairs. .
Ceiling and Rafter Roof Insulation. Minimum R-22 insulation in wood -frame ceiling; or the weighted average U -factor must not exceed 0.043.
Minimum R-19 or weighted average U -factor of 0.054 or less in a rafter roof alteration. Attic access doors must have permanently attached
§ 150.0(a):
insulation using adhesive or mechanical fasteners. The attic access must be gasketed to prevent air leakage. Insulation must be installed in
direct contact with a continuous roof or ceiling which is sealed to limit infiltration and exfiltration as specified in § 110.7, including but not limited
to placing insulation either above or below the roof deck or on of a drywall ceiling.*
§ 150.0(b): '
Loose -fill Insulation. Loose fill insulation must meet the manufacturer's required density for the labeled R -value.
Wall Insulation. Minimum R-13 insulation in 2x4 inch wood framing wall or have a U -factor of 0.102 or less (R-19 in 2x6 or U -factor of 0.074 or
§ 150.0(c):'. • •
less). Opaque non -framed assemblies must have an overall assembly U -factor not exceeding 0.102, equivalent to an installed value of R-13 in a
•
wood framed assembly.*
§ 150.0(d):
Raised -floor Insulation. Minimum R-19 insulation in raised wood framed floor or 0.037 maximum U -factor.` `
§ 150.0(f)-'
Slab Edge Insulation. Slab edge insulation must meet all of the following: have a water absorption rate, for the insulation material alone without .
facings, no greater than 0.3%; have a water vapor permeance no greater than 2.0 perm/inch; be protecbd from physical damage and UV light
deterioration; and, when installed as pad of a heated slab floor, meet the requirements of § 11 0.8 .
§ 150.0(8)1:
Vapor Retarder. In Climate Zones 1-16, the earth floor of unvented crawl space must be covered with a Class I or Class Il vapor retarder. This
requirement also applies to controlled ventilation crawls ace for buildings complying with the excetion,to § 150.0(d).
§ 150.0(g)2-:
" Vapor Retarder. In Climate Zones 14 and 16, a Class I or Class II vapor retarder must be installed on t)e conditioned space side of all
insulation in all exteriorwalls, vented attics, and unvented attics with air -permeable insulation. ,
150.0
§ (q)'
Fenestration Products. Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors must have a
maximum U -factor of 0.58; or the weighted average U -factor of all fenestration must not exceed 0.58.*
Fireplaces, Decorative. Gas Appliances, and Gas Log Measures: '
§ 150.0(e)lA:
Closable Doors. Masonry or factory -built fireplaces must have a closable metal or glass door covering the entire opening of the firebox. .
§ 150.0(e)1 B:
Combustion Intake. Masonry or factory -built fireplaces must have a combustion outside air intake, whjch is at least six square inches in area '
and is equipped with a readily accessible; operable, and tight -fitting damper or combustion -air controLcevice *
§ 150.0(e)1C: "
Flue Damper. Masonry or factory -built fireplaces must have a flue damper with a readily accessible control.'
§ 150.0(e)2:.
Pilot Light. Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of
the building, are prohibited. _
Space Conditioning, Water Heating, and Plumbing System Measures:
§ 110.0-§ 110.3:
; Certification. Heating, ventilation and air conditioning (HVAC) equipment,' water heaters, showerheack faucets, and all other regulated
appliances must be certified by the manufacturer to the Energy Commission' .
§ 110.2(a):
HVAC Efficiency. Equipment must meet the applicable efficiency requirements in TABLE 110.2-A through TABLE 110.2-K.' "
"
• Controls for Heat Pumps with Supplementary Electric Resistance Heaters. Heat pumps with supplementary electric resistance heaters
§ 110.2(b):'
must have controls that prevent supplementary heater operation when the heating load can be met by the heat pump alone; and in which the
cut -on temperature for compression heating is higher than the cut -on temperature for supplementary heating, and the cut-off temperature for
compression heating is higher than the cut-off temperature for supplementary heating.*
§ 110.2(c):
Thermostats. All unitary heating or cooling systems not controlled by a central energy management control system (EMCS) must.have a
setback thermostat'
Water Heating Recirculation Loops Serving Multiple Dwelling Units. Water heating recirculation (bops serving multiple dwelling units must
§ 110.3(c)5:
meet the air release valve, backflow prevention, pump priming, pump isolation valve, and recirculatior loop connection requirements of §
1 10.3 c 5.
§ 110.3(c)7:
Isolation Valves. Instantaneous water heaters with an input rating greater than 6.8 kBTU/hr (2 kW) must have isolation valves with hose bibbs
or otherfittin s on both cold water and hot water lines of water heating systems to allow for water tanK flushing when the valves are closed.
§ 110.5:
Pilot Lights. Continuously burning pilot lights are prohibited for rnatural gas: fan -type central fumace:; household cooking appliances (appli-
ances without an electrical supply voltage connection with pilot lights that consume less than 150 BtLthr are exempt); and pool and spa heaters'
Building Cooling and Heating Loads. Heating and/or cooling loads are calculated in accordance with ASHRAE Handbook, Equipment
F150.0(h)l:
Volume, Applica_ tions Volume, and Fundamentals Volume; SMACNA Residential Comfort System Installation Standards Manual; or ACCA
Manual J usin desi n conditions specified in § 150.0(h)2.
2016 Low -Rise Residential MandatoryMeasures Summary
§ 150.0(h)3A-�
Clearances. Installed air conditioner and heat pump outdoor condensing units must have a clearance of atileast 5 feet from the outlet of any • .
dryer vent.
150.0(h)3B:
Liquid Line Drier. Installed air conditioner and heat pump systems must be equipped with liquid line filter driers if required, as specified by
_§
manufacturer's instructions.
§ 150.00)1:
Storage Tank Insulation. Unfired hot water tanks, such as storage tanks and backup storage tanks for soar water -heating systems, must have
R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the. exterior of the tank.
Water piping and cooling system line insulation. For domestic hot water system piping, whether buried or unburied, all of the following must
be insulated according to the requirements of TABLE 120.3-A: the first 5 feet of hot and cold water pipes from the storage tank; all piping with a
§ 150.00)2A: •
," nominal diameter of 3/4 inch or larger; all piping associated with a domestic hot water recirculation systemsegardless of the pipe diameter;
piping from the heating source to storage tank or between tanks; piping buried below grade; and all hot weer pipes from the heating source to
kitchen fixtures'
§ 150.00)26:
Water piping and cooling system line insulation. All domestic water pipes that are buried below grede must be installed in a waterproof
and non -crushable casing or sleeve'
§ 150.00)X: '
Water piping and cooling system line insulation. Pipe for cooling system lines must be insulated as specified in § 150.00)2A. Distribution
piping for steam and h dronic heating systems or hot waters stems must meet the requirements in TABLE 120.3-A.•
§ 150.00)3:
Insulation Protection. Insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Insulation Protection. Insulation exposed to weather must be installed with a cover suitable for outdoor service. For example, protected by
§ 150.00)3A:
aluminum, sheet metal, painted canvas, or plastic cover. The cover must be water retardant and provide shielding from solar radiation that can
cause degradation of the material.
§ 150.00)36:
Insulation Protection. Insulation covering chilled water piping and refrigerant suction piping located outs,de the conditioned space must have a
Class l or Class II vapor retarder.
Gas or Propane Systems. Systems using gas or propane water heaters to serve individual dwelling units must include all of the following: a
§ 150.0(n)l:
120V electrical receptacle within 3 feet of the water heater; a Category III or. IV vent, or a Type B vent wits straight pipe between the outside
termination and the space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the
water heater, and allows natural draining without pump assistance; and a g as supply line with a capacity of at least 200,000 Btu/hr. ,
§ 15.0.0(n)2:
Recirculating Loops. Recirculating loops serving multiple dwelling units must meet the requirements of § 1.10.3(c)5.
§,150.0(n)3:
Solar Water -heating Systems. Solar water -heating systems and collectors must be certified and rated Ley the Solar. Rating and Certification
Corporation SRCC or by a listing agency that is approved by the Executive Director.
-Ducts and Fans Measures:
§ 110.8(d)3:
Ducts. Insulation installed on an existing space -conditioning duct must comply with § 604.0 of the California Mechanical Code (CMC). If a
contractor installs, the insulation, the contractor must certify to the customer, in writing, that the insulatior meets this requirement. '
CMC Compliance.'All air -distribution system ducts and plenums must be installed, sealed, and insulated to meet the requirements of CMC
§§ 601.0, 602.0, 603.0, 604.0, 605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition. Portions'
:
of supply -air and retum-air ducts and plenums must be insulated to a minimum installed level of R-6.0 (cr higher if required by CMC § 605.0) or
a minimum installed level of R4.2 when entirely in conditioned space as confirmed through field verification and diagnostic testing
§ 150.0(m)1 '
(RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts must be mechanically fastened. Openings must be sealed with .
mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL 181A, Dr UL 181B or aerosol sealant that
meets the requirements of UL.723. If mastic or tape is used to seal openings greater than ''% inch, the combination of mastic and either mesh or
: tape must be used. Building cavities, support platforms for air handlers, and plenums designed or const acted with materials other than sealed
sheet metal, duct board or flexible duct must not be used for conveying conditioned air. Building cavities and support platforms may contain
ducts. Ducts installed in cavities and support plafforms must not be compressed to cause reductions in the cross-sectional area of the ducts.' .
Factory -Fabricated Duct Systems. Factory -fabricated duct systems must comply with applicable regtirements for duct construction,
§ 150.0(m)2:
connections, and closures; joints and seams of duct systems and their components must not be sealed with cloth back rubber adhesive duct
tapes unless such tape is used in combination with mastic and draw bands.
§ 150.0(m)3:
Field -Fabricated Duct Systems. Field -fabricated duct systems must comply with applicable requirements for: pressure -sensitive tapes,
mastics, sealants, -and other requirements specified for duct construction.
§ 150.0(m)7:
Backdraft Dampers. All fan systems that exchange air between the conditioned space and the outside: of the building must have backdraft or
automatic dampers.
§ •150.0(m)8:
Gravity Ventilation Dampers. Gravity ventilating systems serving conditioned space must have either automatic or readily accessible,
manually operated dampers in all openings to the outside, except combustion inlet and outlet air o enih s and elevator shaft vents.
' -
Protection of Insulation. Insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance, and
§ 150.0(m)g:
• wind. Insulation exposed to weather must be suitable for outdoor service. For example, protected by a.uminum, sheet metal, painted canvas, or
. •
plastic cover. Cellular foam insulation must be protected as above or painted with a coating that is water retardant and provides shielding from
solar radiation. -
§ 150.0(m)10:
Porous Inner Core Flex Duct. Porous inner core flex duct must have a non -porous layer between the inner core and outer vapor barrier.
Duct System Sealing and Leakage Test. When space conditioning systems use forced air duct systems to supply conditioned air to an
§ 150.0(m)l 1:
occupiable space, the ducts must be sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in
accordance with § 150.0 m l land Reference Residential Appendix RA3.
Air Filtration. Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal
§ 150.0(m)12-
conditioning component, except evaporative coolers, must be provided with air filter devices that mees. the design, installation efficiency,
pressure drop, and labeling requirements of § 150.0(m)12.
IN
2016 Low -Rise Residential Mandatory Measures Summary
Duct System Sizing and Air Filter Grille Sizing. Space conditioning systems that use forced air ducts to supply cooling to an occupiable
space must have a hole for the placement of a static pressure probe (HSPP), or a permanently installed stetic pressure probe (PSPP) in the
§ 150.0(m)13:
supply plenum. The space conditioning system must also demonstrate airflow z 350 CFM per ton of nominal cooling capacity through the return
grilles, and an air -handling unit fan efficacy:5 0.58 W/CFM as confirmed by field verification and diagnostic-xesting, in accordance with
Reference Residential Appendix RAU. This applies to both single zone central forced air systems and every zone for zonally controlled central
forced airs stems'
Ventilation for Indoor Air Quality. All dwelling units must meet the requirements of ASHRAE Standard 62.2. Neither window operation nor
§150.0(0):
continuous operation of central forced air system air handlers used in central fan integrated ventilation sys gems are permissible methods of
providing whole -building ventilation.
§ 150.0(o)1A:
Field Verification and Diagnostic Testing. Whole -building ventilation airflow must be confirmed through field verification and diagnostic
testing, in accordance with Reference Residential Appendix RA3.7.
Pool and Spa Systems and Equipment Measures:
Certification by Manufacturers. Any pool or spa heating system or equipment must be certified to have MI of the following: a thermal efficiency
§ 110.4(a):
that complies with the Appliance Efficiency Regulations; an on-off switch mounted outside of the heater that allows shutting off the heater
without adjusting the thermostat setting; a permanent weatherproof plate or card with operating instructions; and must not use electric
resistance heating!
§ 110.4(b)l:
Piping. Any pool or spa heating equipment must be installed with at least 36 inches of pipe between the #Iter and the heater, or dedicated
suction and return lines, or built-in or built-up connections to allow for future solar heating.
§ 110.4(b)2:
Covers. Outdoor pools or spas that have a heat pump or gas heater must have a cover.
§ 110.4(b)3:
Directional inlets and time switches for pools. Pools must have directional inlets that adequately mix the pool water, and a time switch that
will allow all pumps to be set or programmed to run only during off-peak electric demand periods.
§ 110.5:
Pilot Light. Natural gas pool and spa heaters must not have a continuously burning pilot light.
150.0
§ (p)'
Pool Systems and Equipment Installation. Residential pool systems or equipment must meet the specified requirements for pump sizing, flow
rate, piping, filters, and valves'
Lighting Measures:
§ 110.9:
Lighting Controls and Components. All lighting control devices and systems, ballasts, and luminaires must meet the applicable requirements
of § 110.9.
§ 110.9(e):
JAB High Efficacy Light Sources. To qualify as a JAB high efficacy light source for compliance with § ':50.0(k), a residential light source must
be certified to the Energy Commission according to Reference Joint Appendix JAB.
§ 150.0(k)1A:
Luminaire Efficacy. All installed luminaires must be high efficacy in accordance with TABLE 150.0-A.
Blank Electrical Boxes. The number of electrical boxes that are more than 5 feet above the finished floor and do not contain a luminaire or
§ 150.0(k)l B:
other device must be no greater than the number of bedrooms. These electrical boxes must be served 1 y a dimmer, vacancy sensor control, or
fan speed control.
Recessed Downlight Luminaires in Ceilings. Luminaires recessed into ceilings must meet all of the equirements for: insulation contact (IC)
§ 150.0(k)l C:
labeling; air leakage; sealing; maintenance; and socket and light source as described in § 150.0(k)l C. A JA8-2016-E light source rated for
elevated temperature must be installed by final inspection in all recessed downli ht luminaires in ceilincs.
§ 150.0(k)l D:
Electronic Ballasts. Ballasts for fluorescent lamps rated 13 wafts or greater must be electronic and most have an output frequency no less than
20 kHz.
Night Lights. Permanently installed night lights and night lights integral to installed luminaires or exhaust fans must be rated to consume no
§ 150.0(k)l E:
more than 5 wafts of power per luminaire or exhaust fan as determined in accordance with § 130.0(c). +light lights do not need to be controlled
by vacancy sensors.
§ 150.0(k)1F:
Lighting Integral to Exhaust Fans. Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods)
must meet the applicable requirements of § 150.0(k).*
Screw based luminaires. Screw based luminaires must not be recessed downlight luminaires in ceilirgs and must contain lamps that comply
§ 150.0(k)l G:
with Reference Joint Appendix JAB. Installed lamps must be marked with "JA8-2016" or "JA8-2016-E" as specified in Reference Joint Appendix
JAB.*
§ 150.0(k)1 H:
Enclosed Luminaires. Light sources installed in enclosed luminaires must be JAB compliant and must be marked with "JA8-2016-E."
§ 150.0(k)2A:
Interior Switches and Controls. All forward phase cut dimmers used with LED light sources must comply with NEMA SSL 7A.
§ 150.0(k)2B:
Interior Switches and Controls. Exhaust fans must be switched separately from lighting systems
§ 150.0(k)2C:
Interior Switches and Controls. Luminaires must be switched with readily accessible controls that permit the luminaires to be manually
switched ON and OFF.
§ 150.0(k)2D:
Interior Switches and Controls. Controls and equipment must be installed in accordance with manufacturer's instructions.
§ 150.0(k)2E:
Interior Switches and Controls. No control must bypass a dimmer or vacancy sensor function if the=control is installed to comply with
150.0(k).
§ 150.0(k)2F:
Interior Switches and Controls. Lighting controls must comply with the applicable requirements of F• 110.9.
Interior Switches and Controls. An energy management control system (EMCS) may be used to comply with dimmer requirements if it:
§ 150.0(k)2G:
functions as a dimmer according to § 110.9; meets the Installation Certificate requirements of § 130A; meets the EMCS requirements of §
130.5(0; and meets all other requirements in § 150.0(k)2.
Interior Switches and Controls. An EMCS may be used to comply with vacancy sensor requiremerts in § 150.0(k) if it meets all of the
§ 150.0(k)2H:
following: it functions as a vacancy sensor according to § 110.9; the Installation Certificate requirements of § 130.4; the EMCS requirements of §
130.5(0; and all other requirements in § 150.0(k)2.
§ 150.0(k)21:
Interior Switches and Controls. A multiscene programmable controller may be used to comply with dimmer requirements in § 150.0(k) if it
provides the functionality of a dimmer according to § 110.9, and complies with all other applicable requirements in § 150.0(k)2.
2016 Low -Rise Residential Mandatory Measures Summary
§ 150.0(k)2J:
Interior Switches and Controls. In bathrooms, garages, laundry rooms, and utility rooms, at least one luminaire in each of these spaces must
be controlled by a vacancy sensor.
§ 150.0(k)2K:
Interior Switches and Controls. Dimmers or vacancy sensors must control all luminaires required to have light sources compliant with
Reference Joint Appendix JAB, except luminaires in closets less than 70 square feet and luminaires in hallways.'
§ 150.0(k)2L:
Interior Switches and Controls. Undercabinet lighting must be switched separately from other lighting systems.
Residential Outdoor Lighting. For single-family residential buildings, outdoor lighting permanently mounted to a residential building, or to other
§ 150.0(k)3A:
buildings on the same lot, must meet the requirement in item § 150.0(k)3Ai (ON and OFF switch) and the requirements in either item
§ 150.0(k)3Aii (photocell and motion sensor) or item § 150.0(k)3Aiii (photo control and automatic time switch control, astronomical time clock, or
EMCS.
Residential Outdoor Lighting. For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies,
§ 150.0(k)3B:
and porches; and outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site must comply with
either § 150.0(k)3A or with the applicable requirements in §§ 110.9,130.0,130.2,130.4,140.7 and 141.0.
§ 150.0(k)3C:
Residential Outdoor Lighting. For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by
150.0(k)3B or § 150.0(k)3D must comply with the applicable requirements in §§ 110.9, 130.0, 130.2, 130.4, 140.7 and 141.0.
§ 150.0(k)3D:
Residential Outdoor Lighting. Outdoor lighting for residential parking lots and residential carports with a total of eight or more
vehicles per site must comply with the applicable requirements in §§ 110.9,130.0, 130.2,130.4,140.7, and 141.0.
§ 150.0(k)4:
Internally illuminated address signs. Internally illuminated address signs must comply with § 140.8; or must consume no more than 5 watts of
ower as determined according to § 130.0(c).
§ 150.0(k)5:
Residential Garages for Eight or More Vehicles. Lighting for residential parking garages for eight or more vehicles must comply with the
applicable requirements for nonresidential garages in §§ 110.9, 130.0, 130.1, 130.4, 140.6, and 141.0.
Interior Common Areas of Low-rise Multi -Family Residential Buildings. In a low-rise multifamily residential building where the total interior
§ 150.0(k)6A:
common area in a single building equals 20 percent or less of the floor area, permanently installed lighting for the interior common areas in that
building must be high efficacy luminaires and controlled by an occupant sensor.
Interior Common Areas of Low-rise Multi -Family Residential Buildings. In a low-rise multifamily residential building where the total interior
common area in a single building equals more than 20 percent of the floor area, permanently installed lighting in that building must:
§ 150.0(k)6B:
i. Comply with the applicable requirements in §§ 110.9,130.0,130.1, 140.6 and 141.0; and
ii. Lighting installed in corridors and stairwells must be controlled by occupant sensors that reduce the lighting power in each space by at least
50 percent. The occupant sensors must be capable of turning the light fully on and off from all designed paths of ingress and egress.
Solar Ready Buildings:
Single Family Residences. Single family residences located in subdivisions with ten or more single family residences and where the
§ 110.10(a)1:
application for a tentative subdivision map for the residences has been deemed complete by the enforcement agency must comply with the
requirements of § 110.10 b through § 110.10 e .
§ 110.10(a)2:
Low-rise Muiti-family Buildings. Low-rise multi -family buildings must comply with the requirements of § 110.10(b) through § 110.10(d).
Minimum Area. The solar zone must have a minimum total area as described below. The solar zone must comply with access, pathway, smoke
ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a local
jurisdiction. The solar zone total area must be comprised of areas that have no dimension less than 5 feet and are no less than 80 square feet
each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for buildings with roof areas
§ 110.10(b)1:
greater than 10,000 square feet.
For single family residences the solar zone must be located on the roof or overhang of the building and have a total area no less than 250
square feet. For low-rise multi -family buildings the solar zone must be located on the roof or overhang of the building, or on the roof or overhang
of another structure located within 250 feet of the building, or on covered parking installed with the building project, and have a total area no less
than 15 percent of the total roof area of the building excluding any skylight area '
§ 110.10(b)2:
Orientation. All sections of the solar zone located on steep -sloped roofs must be oriented between 110 degrees and 270 degrees of true north.
§ 110.10(b)3A:
Shading. The solar zone must not contain any obstructions, including but not limited to: vents, chimneys, architectural features, and roof
mounted equipment.'
Shading. Any obstruction located on the roof or any other part of the building that projects above a solar zone must be located at least twice the
§ 110.10(b)3B:
distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the horizontal projection of
the nearest point of the solar zone, measured in the vertical plane.'
§ 110.10(b)4:
Structural Design Loads on Construction Documents. For areas of the roof designated as solar zone, the structural design loads for roof
dead load and roof live load must be clearly indicated on the construction documents.
Interconnection Pathways. The construction documents must indicate: a location for inverters and metering equipment and a pathway for
§ 110.10(c):
routing of conduit from the solar zone to the point of interconnection with the electrical service (for single family residences the point of
interconnection will be the main service panel); and a pathway for routing of plumbing from the solar zone to the water -heating system.
§ 110.10(d):
Documentation. A copy of the construction documents ora comparable document indicating the information from § 110.10(b) through
110.10(c) must be provided to the occu ant.
§ 110.10(e)1:
Main Electrical Service Panel. The main electrical service panel must have a minimum busbar rating of 200 amps.
Main Electrical Service Panel. The main electrical service panel must have a reserved space to allow for the installation of a double pole circuit
§ 110.10(e)2:
breaker for a future solar electric installation. The reserved space must be: positioned at the opposite (load) end from the input feeder location or
main circuit location; and permanently marked as 'For Future Solar Electric".