Loading...
HomeMy WebLinkAboutB17-1993 033-110-0572016 CALGreen Residential Mandatory Measures '. ,This checklist applies to newly constructed bungs, additions or alterations of existing residential buildings where the addition or alteration increases the building's conditioned area, volume, orsize. The requirements shall only apply to and or within the specific area of the addition or alteration. (2016 CGBSC 301.1.1) - ***Note 2016 CGBSC 301.1.1: On and after 11112014, residential buildings undergoing permitted alterations, additions or improvements shall replace noncompliant plumbing fixtures with water - conserving plumbing fixtures. Plumbing fixture replacement is required prior to issuance of a certificate of final completion, -certificate of occupancy or final permit approval by'the local building department." - Feature or Measure Required MaiA IN plan is developed and implemented to manage storm water drainage during - construction. CGBSC 4.106.2.• ' Construction plans shall indicate how the site grading or drainage system will manage all surface water flows to keep water from entering buildings CGBSC 4.106.3. Provide capability for electric vehicle charging in one and two-family dwellings and in townhouses with attached private garages; and 3 percent of total parking spaces, as specified, for multifamily dwellings. - Building meets or exceeds the requirements of the California Building Energy Standards. CGBSC 4.201.1. Water closets. closets. The effective flush volume of all water closets shall not exceed 1.28 ;� gpf. Tank -type water closets shall be certified to the performance criteria of the U.S. EPA WaterSense Specification for Tank -type Toilets. -Note: The effective flush volume of dual flush toilets is defined as the composite,' . average flush volume of two "reduced flushes and one full flush. Urinals. The effective flush volume of wall mounted urinals shall not exceed 0.125gpf , and floor mounted or other urinals shall not exceed 0.5 gpf:. Single showerheads: Showerheads shall have a max. flow rate of not more than 2.0 gpm at 80 psi. Showerheads shall be certified to the performance criteria of the U.S. EPA WaterSense Specification for Showerheads. ,1 Multiple showerheads serving one shower. When a shower is served by more than ;-- one showerhead, the combined flow rate of all the showerheads and/or other shower �" } outlets controlled by a single valve shall not exceed 2.0 gpm at 80 psi, or the shower shall be designed to allow only one shower outlet to be in operation at a time. Residential lavatory faucets. The max. flow rate of residential lavatory faucets shall ` not exceed 1.2,gpm at 60 psi. The min. flow rate of residential lavatory faucets shall ' not be less than 0.8 gpm at 20 psi. Metering faucets. Metering faucets when installed in residential buildings shall not ` deliver more than 0.25 gallons per cycle. ' Kitchen faucets. The max. flow rate of kitchen faucets shall not exceed 1.8gpm at 60 ' psi. - Checklists\Green Building J Page 1 of 3, t � 02/10/2017', 2016 CALGreen Residential Mandatory Measures Checklist (Cont'd) Feature or Measure Required �• 5`'xLL' a fC -� _. •• :i — r: �:>_' •t JF. ... �.0 _ . • rs .. _. Y iti. � ._ ' _-�rc�i`.�.^•.,.,r : ,!c '" � � :;4_ �t - � : •'�+L�•iij•:. �. •r�•, }-�-. c r: 'L r r::.-:cac::: s Y•; :+... .11�� �. is rT:iL ti?''F f _ i�4T: New residential developments with an aggregate landscape area equal to or greater than 500 sq ft shall comply with one of the following options: I. A local water efficient landscape ordinance or the current California Department of Water Resources Model Water Efficient Landscape Ordinance (MWELO), whichever more stringent; or 2. Projects with aggregate landscape areas less than 2,500 sq ft may comply with the MWELO Appendix D Prescriptive Compliance Option. Rodent proofing. Annular spaces around pipes, electric cables, conduits, or other openings in sole/bottom plates at exterior walls shall be protected against the passage of rodents by closing such openings with cement mortar, concrete masonry or similar method acceptable to the enforcing agency. Recycle and/or salvage for reuse a minimum of 65 percent of the nonhazardous construction and demolition waste in accordance with one of the following: ---1-Comply-with-a-more-stringent- local--construction-and demolition-waste--------- -- - management management ordinance; or ' 2. A construction waste management plan, per Section 4.408.2; or 3. A waste management company, per Section 4.408.3; or 4. The waste stream reduction alternative, per Section 4.408.4. O&M Manual: An operation and maintenance manual shall be available in the building- at the time of final inspection. Recycling by Occupants: Where 5 or more multifamily dwelling units are constructedy on a building site, provide readily accessible area(s) that serves all buildings on the site and is identified for the depositing, storage and collection of non-hazardous materials for recycling, including (at a minimum) paper, corrugated cardboard, glass, plastics, organic waste, and metals, or meet a lawfully enacted local recycling ordinance, if more restrictive. See exception for rural jurisdictions. ti. .fBill 150 Nola=_I _ :c.� Lam•,PANKIS Any installed gas fireplace shall be direct-vent sealed-combustion type. Any installed woodstove or pellet stove shall comply with U.S EPA New Source Performance Standards (NSPS) emission limits as applicable, and shall have a permanent label indicating they are certified to meet the emission limits. Woodstoves, pellet stoves and fireplaces shall also comply with applicable local ordinances. =:��- - ^ ?ucF::.:m: tr--. • _ _ _;:L' ^+.ri: `•"-:_.ia:'__3-i£':• w:•s. .Q. 'I� ��nt::C4� :r9� -, :3` ' : .�L�:. _r.. - � - •-:� �:>:r:... .L .. �_.,._, ;:�:-•,-� . T II Fr • n� - _ «,__ F • c - _ Duct openings and other related air distribution component openings shall be covered during construction. Adhesives, sealants and caulks shall ,be compliant,with VOC and other toxic compound limits Aerosol adhesives-and smaller unit sizes of adhesives and sealant or caulking compounds shall comply with statewide VOC standards and other requirements. Paints, stains and other coatings shall be compliant with VOC limits. 4.504.2.2 Check Iists\Green Building t Page 2 of 3 . 02/10/2017 2016 CALGreen Residential Mandatory Measures Checklist-(cont'd) i Feature or Measure Required Aerosol paints and coatings shall be compliant with product weighted MIR limits for ROC and other toxic comr)ounds. Carpet and carpet systems shall be compliant with VOC limits. 4.504.3 At least 80% of floor area receiving resilient flooring shall comply with specific VOC criteria. 'Hardwood plywood, particleboard and medium density fiberboard (MDF) used on interior or exterior of the building shall comply with formaldehyde emission standards. Documentation shall be provided to the City building inspector verifying that compliant . materials have been used. , •r Concrete Slab Foundations: Vapor retarder and capillary break is installed at slab - on -grade foundations. Moisture content of building materials used in wall and floor framing shall not exceed 19% before enclosure. Moisture content shall be verified in compliance with -. CGBSC 4.505.3. Indoor Air Quality and Exhaust (4.506) Bathroom exhaust fans shall be ENERGY STAR rated and ducted to terminate outside. -Unless functioning,as a component of a whole house ventilation system, bathroom exhaust fans must be controlled by.a humidity control adjustable between a relative humidity range of 50% - 80%. ;a F Duct systems are sized, designed, and equipment is selected using the following methods: I. Establish heat loss and heat gain values according to ANSI/ACCA 2 Manual t J-2011 or equivalent. 2. Size duct systems according to ANSI/ACCA 1 Manual D-2014 or equivalent. 3.Select heating and cooling equipment according to ANSI/ACCA 3 Manual S- " 2014 or equivalent. `rvr..IN-Mr.t�F •Cig!ti F= iTt.' r.�'it. r -•-•c-_' z HVAC system installers are trained and certified in the proper installation of HVAC systems. Special inspectors employed by the enforcing agency must be qualified and able to demonstrate competence in the discipline they are inspecting. - = ! .' %r` •Li,. °+ ass: :-' t�z r _,i rn•R �,°4E ::: . ^�qK :•,:•_.,::,:_:,: ........_:::,•:.:—:d. .�.;_. :'�__: +�. .c.:�. ... = __�_ •� ..� 4 :r„= �a1LL•6��' ...tLl.t.,ar�.ec . Verification of compliance with this code may include construction documents, plans specifications builder or installer certification, inspection reports, or other methods acceptable to the enforcing agency, which show substantial conformance. • ChecklistslGreen Building Page 3 of 3 02/10/2017 Butte County Department of Development Services PERM, IT CENTER 7 County Center Drifte, Oroville, CA 95965 Main Phone 530.538.7601 Fax 530.538.7785 • �ilttit'.hll[tLCOUnlS'.I1�IJC1d� SITE [ALAN Assessor's Farce Number. I E I FT I F 0 I n o on ® 0 )FORM NO SID Q.o �" - _ Owner Name: Scope of Work — -- —. _ _ _ �- �- L , _ �. ` mSite Location: CA,rJ 4 ors H—( f-f1A-AD5 (�lZ c Contact name: sArmE-- Phone:5-3t, -- 6C -ISQ6 5 )P7— o� Flood Zone: % Scale 1"= - A KABUILDING\Aluira Revised forms for review 11-17-141Fully revised forms and documents 12-01-140BP-O3_Site—Plan_Paper_REV'D-8.13.14—AKM.doc Page I of 1 ` CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD ' , CFS 1R -PRF -01 Project Name: Residential Building Calculation DateITirre: 15:23, Fri,, Aug 25, 2017- - j y" F, Page 1 of 8' Calculation Description: Title 24 Analysis.` • Input File Name: perkins addition.ribd16x GENERAL INFORMATION ENERGY USE SUMMARY 01 Project Name Residential Building 04 - 02 Calculation Description Title 24 Analysis 08 - 03 Project Location 495 Canyon Highlands Drive . Compliance Margin Percent Improvement. 04 : ' .. City Oroville 05%. Standards Version Compliance 2017 06 Zip Code 95966 ' 07' ; Compliance Manager Version BEMCmpMgr 2016.2.1 (695) '08 _ Climate Zone CZ11 - 09 . ' Software Version EnergyPro 7.1 10 —Building Type Single Family 11 - Front Orientation (deg/Cardinal) 315- 12 Project Scope Addition and/or Alteration 13 Number of Dwelling Units 1 14- Total Cond. Floor Area (ft2) 2443 15 Number of Zones 2 . 16 Slab Area (ft2) 440 17. ' Number of Stories 1 18 Addition Cond. Floor Area 440 19 ' .. Natural Gas Avallable Yes 20 Addition Slab Area (ftt2)440 21 Glazing Percentage ("/o) 13.9% COMPLIANCE RESULTS 01 Building Complies with Computer Performance 02 This building DOES NOT require HERS Verification 03 This building Incorporates one or more Special Features shown below This compliance analysis Is valid only for permit applications through October 24, 2017 . ENERGY USE SUMMARY 04 05 06 07 08 Energy Use (kTDV/ft2-yr) _ Standard. Design' Proposed Design Compliance Margin Percent Improvement. Space Heating 37.35 39.69 ' -2.34 -6.3% Space Cooling IAQ Ventilation -115.26 0.00 112.83 0.00-. 2.A3 0.00 2.1 0.0% Water Heating 10.86. 10.86 . 0.00. 0.0%0 Photovoltaic Offset 0.00. 0.00 Compliance Energy Total 163.47, 163.38 0.09 0.1% CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD • • .. . CF1 R -PRF -01: Project Name: Residential Building Calculation Date/Time: 15:23, Fri, Aug 25;•2017• ' Page 2 of 8 Calculation Description: Title 24 Analysis Input File Name: perkins addition.ribdl6x REQUIRED SPECIAL FEATURES ' The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis. • Whole house fan * ` • Window overhangs and/or fins New ductwork added is less than '40 ft: In length, HERS FEATURE SUMMARY The following is a summary of the features that must be field -verified by a certified.HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is provided in the building components tables below. Building -level Verifications- -None-- Cooling erifications:—None- Cooling System Verifications: - None — . . HVAC Distribution System Verifications: — None — Domestic Hot Water System Verifications: — None BUILDING - FEATURES INFORMATION 01 02 03 04 05 06 07 Project Name Conditioned Floor Area (ft2) Number of Dwelling Units Number of Bedrooms Number of Zones Number of Ventilation Cooling Systems 'Number of Water , • Heating Systems Residential Building 2443-'1 .06 . .3 2 1 1 ZONE INFORMATION 01 02 03 04 05 .06 . 07 Zone Floor Area. Avg. Ceiling' Zone Name Zone Type • HVAC System Name (ft2) Height Water Heating. System 1 Water Heating System 2. First Floor Existing Conditioned HVAC Systeml 2003.. 8 DHW Sys 1 n/a First Floor Addition Conditioned HVAC Systeml 440. 8 DHW Sys 1 n/a ; :Registration Number: Registration Date/Time: :HERS Provider. - - CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-07312017-695. • .. Report Generated at: 2017-08-25 15:24:12 CERTIFICATE OF COMPLIANCE - RESIDENTIAL- PERFORMANCE COMPLIANCE METHOD ' • `, ' a ' - CF1R-PRF-01 Project Name: Residential Building ' ,- ` 3 ' "Calculation DatelTime: 15:23; Fri; Aug 25, 201 T • Page 3 of 8 , Calculation Description: Title 24 Analysis.* - Input File Name: perkins addition.ribd16x OPAQUE SURFACES 01 .._ 03 04 05 06 07 08 09 01. 02 03 • . 04 05... 06 07 08 09 10 'Name' ` f Zone Construction Azimuth Orientation Gross Area (ft2) Window&'Door Area (ft2) Tilt (deg) Status Verified Existing Condition. Front Wall First Floor Existing 'Default Wall 1978 to 1991" 315 Front 152. 41 90 Existing. No Left Wall • First Floor Existing Default Wall 1978 to 1991. 45 Left 152' 6.25 90 Existing No Rear Wall . First Floor Existing .. Default Wall 1978 to 1991 135 Back 360.. 113.3 '- . - :90 Existing No Right Wall First Floor Existing Default Wall 1978. to 1991 225 Right • 80 0 90 Existing No Front Left Wall First Floor Existing Default Wall 1978 to 1991 0 45 368 28 90 Existing No Rear Left Wall First Floor Existing Default Wall 1978 to 1991 90 135 120 24 90 Existing No Rear Right Wall First Floor Existing Default Wall 1978 to 1991 180 225 352 58.5 90 Existing No . Front Right Wall First Floor Existing Default Wall 1978 to 1991 270 315 •260 28 90 Existing No Roof First Floor Existing Default Roof 1978 to Pres 2003 Existing No . Raised Floor First Floor Existing Default Floor Crawlspace 2003 Existing No Front Wall 2 First Floor Addition R-13 Wall 315 Front 176 48 90 New N/A Left Wall 2 First Floor Addition R-13 Wall 45 Left 176 28.7 90 New N/A. Right Wall 2 First Floor Addition R-13 Wall 225 Right 88 • • 0 90 - New N/A Roof 2 First Floor Addition R-38.Roof Attic 440 New N/A ATTIC 01 02 03 04 05 06 07 08 09 10 Name Construction Type - Roof Rise ':Roof Reflectance Roof Emittance . Radiant Barrier Cool Roof Status -Verified Existing Condition. Attic First Floor Existing Attic RoofFirst Floor Existing Ventilated 4 0.1 • 0.85 No No Existing No Attic First Floor Addition Attic RoofFirst Floor Addition Ventilated 4 0.1 0.85 No No Ne 11 w No= 1. CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF701' Project Name: Residential Building ' ' Calculation DateITime: 15:23, Fri,, Aug 25, 2017: Page 4 of 8 Calculation Description: Title 24 Analysis Input File Name: perkins addition.hbdl6x ' FENESTRATION / GLAZING, 01 1 03. 01" �� -02 03 04 05 06 07 08 09 10 11 • Name �' ' Surface (Orientation -Azimuth) .: - Width(ft) Height (ft) . Multiplier Area (ft): U -factor SHGC' Exterior Shading- Status ' : - Verified Existing ' ' Condition Wiridow Front Wall (Fr6nt-315) Bot Up Depth Z21.0 0.58 0.65 1nsect Screen (default). Existing No Window 2. - Left Wall.(Left-45) - -- 1 6.21 j 0.58 '0.65 Insect Screen (default) Existing No Window 3 Rear Wall (Back -135) -- -- 1- .. 13.3'-) ,0.58. 0.65 Insect Screen (default) Existing, No Window 4 Front Left Wall (- specify --0) -- -- 1. " 28.0 0.58 0.65 Insect Screen (default) Existing No = Window 5 Rear Left Wall (- specify --90) -- -- 1 j24.0 0.58 0.65 Insect Screen (default) Existing No Window 6 Rear Right Wall (-specify 180 -- -- 1 58.5 _ 0.58 0.65 Insect Screen default Existing No Window 7 Front Right Wall (- specify -270) -- -- 1 428.0- 0.58 0.65 Insect Screen (default) Existing No Window 8 Front Wall 2 (Front -315) - -- 1 ! 48.0 _ 0.32 0.23 Insect Screen (default) New N/A Window 9 Left Wall 2 (Left -45) 3.0 4.0 1 -412.0 0.32 0.23 Insect Screen (default) L New N/A OPAQUE DOORS 01 02 03. 04 05 ' -06 Name Side of Building Area (ft2) . U -factor' Status Verified Existing Condition Door Front Wall X20.0 0.50 Existing No Door 2 ' Left Wall 2 (16.7 0.50 New. No OVERHANGS AND FINS 01 02 03 04 05 ., 06 07 08 09. 10 11 12 13 14 Overhang - Left Fin Right Fin Window Depth Dist Up Left Extent Right ExtentFlap Ht. DepthTop Up DIstL Bot Up Depth Top Up ', Dist R' Bot Up. Window 2 0.1 2 2 0 0 0 ;0 0 0 0 0 U CERTIFICATE OF. COMPLIANCE RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01 Project Name: Residential Building Calculation Date/Time: 15:23, Fri; Aug 25, 2017 : Page 5 of 8 . Calculation Description: Title 24 Analysis Input File Name: perkins addition.ribd 1 6x OPAQUE SURFACE CONSTRUCTIONS ' 01 02 ... 03 .. 04 . 05 06 07 08 09 N3mo gone Total Cavity Winter Design Edge Insul. R -value Construction Name, Surface Type Construction Type Framing R -value U -value Assembly Layers 88 None . 0.8 No New No Cavity/ Frame: no insul.-/2x4 Top Chid 2x4 Top -Chord of Roof Truss @ 24. Roof Deck: Wood Siding/sheathing/decking Attic RoofFirst Floor.Existing Attic Roofs Wood Framed Ceiling in. O.C. none 0.644 Roofing: Light Roof (Asphalt Shingle) • Floor Surface: Carpeted Floors Over Floor Deck: Wood Siding/sheathing/decking ' Default Floor Crawlspace Crawlspace Wood Framed Floor 2x12 @16 in. O.C. none 0.216 Cavity/Frame: no insul. /2x12 • Inside Finish: Gypsum Board • Cavity/Frame: R-11 /2x4 • Exterior Finish: Wood Default Wall 1978 to 1991 Exterior Walls Wood Framed Wall 2x4 @ 16 in. O.C: R11 0.103 Siding/sheathing/decking • Inside Finish: Gypsum Board Ceilings (below Cavity/Frame: R-9.1 /2x4 Default Roof 1978 to Pres attic) Wood Framed Ceiling 2x4 @ 16 in. O.C. R 19 0.049 Over Ceiling Joists: R-9.9 insula • Cavity/ Frame: no insul. / 2x4 Top Chrd .2x4 Top Chord of Roof Truss @ 24 Roof Deck: Wood siding1sheathing1decking Attic RoofFirst Floor Addition Attic Roofs Wood Framed Ceiling in. O.C. none 0.644 Roofing. Light Roof (Asphalt Shingle) Inside Finish: Gypsum Board • Cavity/Frame: R -13/2x4 • Exterior finish: Wood R-13 Wall Exterior Walls, Wood Framed Wall 2x4.@,16 in. O.C. R 13 0.095 Siding/sheathing/decking Inside Finish: Gypsum Board Ceilings (below Cavity/Frame: R-9.1 /2x4 R-38 Roof Attic attic) Wood Framed Ceiling 2x4 @ 24 in. O.C. R 38 0:025 Over Ceiling Joists: R-28.9 insul. SLAB FLOORS 01 02 03 04 05 06 07 08 09 N3mo gone Area (ftp) Perirgeter (ft) Edge Insul. R -value Carpeted Fraction . Heated. Status Verified LkIsting Condition Slab First Floor Addition 440, 88 None . 0.8 No New No BUILDING ENVELOPE —HERS VERIFICATION 01 02. 03 04 Quality Insulation Installation (QII). Quality Installation of Spray Foam Insulation Building. Envelope Air Leakage CFM50 Not Required Not.Required• Not Required -- Registration Number. Registration DateTme: CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-07312017-695. CERTIFICATE OF COMPLIANCE =RESIDENTIAL PERFORMANCE COMPLIANCE METHOD , CF1 R-PRF=01: Project Name: Residential Building Calculation Dateffime: 15:23, Fri, Aug 25, 2017: = - Page 6 of 8 Calculation Description: Title 24 Analysis Input File Name: perkins additionAbd 1 6x ' WATER HEATING SYSTEMS - = 01 02 0304 04 05 OS O6 07 08 System Type 01 Efficiency EER SEER ..02, 03 ' Solar 05 06 ."07 08 09 Not Zonal Number of Fraction Name Verified Existing 'Name `_ System Type' Distribution Type ` 'Water Heater Heaters (%) Status Condition DHW Sys 1 DHW Standard DHW Heater 1 - -1 Annual, Existing No WATER HEATERS 01 02 03 04 05 06 07 08 .. System Type 01 Efficiency EER SEER ..02, 03 ' 04 05 06 ."07 08 09 Not Zonal 10 11 Name Heater Element Type Tank type -'of Number Units Tank • Volume. (gal), Energy Factor or Efficiency Input .. Rating/Pilot Tank Insulation R -value (Int/Ext) -Standby Loss/ Recovery Eff NEEA Heat Pump Type Tank Location.or Ambient Condition DHW Heater 1 Gas Small Storage '1 50 0.6 EF 40000 Btu/hr. n/a n/a n/a n/a SPACE CONDITIONING SYSTEMS 01 02 03 04 05 06 07 08 09 Heating System Cooling System Name System Type' Name Ducted Name Ducted Distribution . System Fan . System Floor Area Served Status Verified Existing. Condition HVAC Systeml Other Heating and Cooling System Heating Component 1 Yes Cooling Component 1: Yes . Air Distribution . System 1 HVAC Fan 1 2443 Existing No HVAC - HEATING UNIT TYPES 01 02 03 04 Name System Type Number of Units Efficiency Heating Component 1 CntrlFumace 1 78 AFUE HVAC - COOLING UNIT TYPES 01 02 03 04 05 06 07 08 Name _ __ System Type Number of Units Efficiency EER SEER Zonally Controlled Compressor Type HERS Verification. Cooling Component 1 SplitAirCond 1 9.6 11 Not Zonal Single Speed Cooling Component 1=hers-cool CERTIFICATE OF COMPLIANCE RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1 R -PRF -01 : Project Name: Residential BuildingCalculation DatelTime: 15:23; Fri; Aug 25, 2017 Page 7 of 8 . Calculation Description: Title 24 Analysis_ Input File Name: perkins addition.ribdl6x ' HVAC COOLING - HERS VERIFICATIONx' 01 02 _ 03 04 .. 05 06 NameVerified Alrflow AlrflowTarget Verified EER Verified SEER Verified Refrigerant Charge Cooling.Component 1 -hers -cool Not Required n/a Not Required Not Required Not Required HVAC - DISTRIBUTION SYSTEMS 01 02 03 04 05 06 07 08' 09 , -10 Name Type Duct Leakage Insulation R -value Supply Duct: Location Retum Duct Location 'Bypass Duct Status Verified Existing Condition HERS Verification. Air Distribution System 1 Ducts located in attic (Ventilated and Unventilated) Existing (not specified) 6.0 Attic Attic None Existing + New No N/A IAQ (Indoor Air Quality) FANS 01 02 03. 04 05 Name IAQ CFM IAQ Fan Type IAQ Recovery Effectiveness(%) HERS Verification SFam IAQVentRpt 0 Default 0 Not Required COOLING VENTILATION 01 02 03 04 05 .. 06 Name Airflow Rate (CFM/ft2) Cooling Vent CFM Cooling Vent Watts/CFM Total Watts Number of Fans WH Fan 1 2.046663937781416 5000 0.1 500 1 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Residential Building Calculation Date/Time: 15:23, Fri, Aug 25, 2017 Calculation Description: Title 24 Analysis Input File Name: perkins addition. ribd 1 6x DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. I certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Documentation Author Signature: Rick Rocklewitz , 1687 Company: Signature Date: NRG Compliance, LP. :8/25/2017 Address: " PO Box 3777, CEA/HERS Certification Identification (If applicable): City/Stateggr to Rosa, California 95402 Phone: 707-237-6957 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance. 2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with thi uilding permit application. Responsible Desi ner Name: Glen duigley Res I e ' n r Signature: Company: Glen Quigley Date Signed: Address: 2689 Forest View Drive License: City/State/Zip: Oroville, California95966 Phone: 530-864-1520 Registration Number. Registration DateTme: CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-07312017-695 RESIDENTIAL MEASURES SUMMARY RMS4 Project Name SCOP Perkins Building Type m Single Family ❑ Addition Alone ❑ Multi Family m Existing+ Additon/Alteration 1812512017 Date Project Address 495 Canyon Highlands Drive Oroville California Energy Climate Zone CA Climate Zone 11 Total Cond. Floor Area 2,443 Addition .440 # of Units 1 INSULATION Construction Type Cavity Area (ft) Special Features Status Floor Wood Framed w/Crawl Space no insulation 2,003 Existing Wall Wood Framed R11 1,673 Existing Door Opaque Door - no insulation 20 Existing Roof Wood Framed Attic R 19 2,003 Existing Wall Wood Framed R 13 363 New Door Opaque Door no insulation 17 New Roof Wood Framed Attic R38 440 New Slab Unheated Slab -on -Grade - no insulation 440 Perim = 88' New FENESTRATION I Total Area: 3391 Glazing Percenta e: 13.9 % New/Altered Average U -Factor. 0.32 Orientation Area(ft) U -Fac SHGC Overhang Sidefins Exterior Shades Status Front (NKK 21.0 0.580 0.65 none none Bug Screen Existing Left (NE) 6.3 0.580 0.65 none none Bug Screen Existing Rear (SE) 113.3 0.580 0.65 none none Bug Screen Existing Front (N) 28.0 0.580 0.65 none none Bug Screen Existing Left (E) 24.0 0.580 0.65 none none Bug Screen Existing Rear (S) 58.5 0.580 0.65 none none Bug Screen Existing Right (Kq 28.0 0.580 0.65 none none Bug Screen Existing Front (NW) 48.0 0.320 0.23 none none Bug Screen New. Left (NE) 12.0 0.320 0.23 2.0 none Bug Screen New HVAC SYSTEMS Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status 1 Central Furnace 78% AFUE Split Air Conditioner 11.0 SEER Setback Existing HVAC DISTRIBUTION Location I Heating Cooling Duct Duct Location R -Value Status HVAC System Ducted Ducted Attic 6.0 Altered WATER HEATING Qty. Type Gallons Min. Eff Distribution Status EneigyPro.7.1 by EnerovSoft User Number. 5581 0: 0825170 Pae 11 of 15 2016 Low -Rise Residential Mandatory Measures Summary NOTE. Low-rise residential buildings subject to the Energy Standards must comply with all applicable mandatory measures, re:Iardless'of the compliance approach used. Review the respective'section for more information. 'Exceptions may apply. (Oriainsl 118/20161 . Building Envelope Measures: § 110:6(a)1` Air Leakage.' Manufactured fenestration, exterior doors, and exterior pet doors must limit air leakage to 0.� cfm/ft' or less when tested per NFRC400 or ASTM E283 or AAMA/WDMAICSA 101/I.S.2/A440-2011 ' § 110.6(a)5: - Labeling. Fenestration products must have a label meeting the.requirements of § 10-111(a). ' § 110.6(b): Field fabricated exterior doors and fenestration products must use U -factors and solar heat gain coeffiient (SHGC) values from TABLES - 110.6-A and 110.6-13 for compliance and must be caulked and/or weatherstn ed.' 10 7 ," § 110.7-- Air Leakage. All joints, penetrations, and other openings in the building envelope that are potential sources of air leakage must be _caulked, ' asketed, or weather stripped: §.110.8(a): Insulation Certification by Manufacturers. Insulation specified or installed'must meet Standards for Insilating Material. " § 110.8(g): Insulation Requirements for Heated Slab Floors. Heated slab floors must be insulated per the requirements of § 110.8(g). § 110.8(i): Roofing Products Solar Reflectance and Thermal Emittance. The thermal emittance and aged solar reflectance values of the roofing material must meet the requirements of§ 110.8(i) when the installation of a cool roof is specified on the CFI R. § 110.80): Radiant Barrier. A radiant barrier must have an emittance of 0.05 or less and be certified to the Department of Consumer Affairs. . Ceiling and Rafter Roof Insulation. Minimum R-22 insulation in wood -frame ceiling; or the weighted average U -factor must not exceed 0.043. Minimum R-19 or weighted average U -factor of 0.054 or less in a rafter roof alteration. Attic access doors must have permanently attached § 150.0(a): insulation using adhesive or mechanical fasteners. The attic access must be gasketed to prevent air leakage. Insulation must be installed in direct contact with a continuous roof or ceiling which is sealed to limit infiltration and exfiltration as specified in § 110.7, including but not limited to placing insulation either above or below the roof deck or on of a drywall ceiling.* § 150.0(b): ' Loose -fill Insulation. Loose fill insulation must meet the manufacturer's required density for the labeled R -value. Wall Insulation. Minimum R-13 insulation in 2x4 inch wood framing wall or have a U -factor of 0.102 or less (R-19 in 2x6 or U -factor of 0.074 or § 150.0(c):'. • • less). Opaque non -framed assemblies must have an overall assembly U -factor not exceeding 0.102, equivalent to an installed value of R-13 in a • wood framed assembly.* § 150.0(d): Raised -floor Insulation. Minimum R-19 insulation in raised wood framed floor or 0.037 maximum U -factor.` ` § 150.0(f)-' Slab Edge Insulation. Slab edge insulation must meet all of the following: have a water absorption rate, for the insulation material alone without . facings, no greater than 0.3%; have a water vapor permeance no greater than 2.0 perm/inch; be protecbd from physical damage and UV light deterioration; and, when installed as pad of a heated slab floor, meet the requirements of § 11 0.8 . § 150.0(8)1: Vapor Retarder. In Climate Zones 1-16, the earth floor of unvented crawl space must be covered with a Class I or Class Il vapor retarder. This requirement also applies to controlled ventilation crawls ace for buildings complying with the excetion,to § 150.0(d). § 150.0(g)2-: " Vapor Retarder. In Climate Zones 14 and 16, a Class I or Class II vapor retarder must be installed on t)e conditioned space side of all insulation in all exteriorwalls, vented attics, and unvented attics with air -permeable insulation. , 150.0 § (q)' Fenestration Products. Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors must have a maximum U -factor of 0.58; or the weighted average U -factor of all fenestration must not exceed 0.58.* Fireplaces, Decorative. Gas Appliances, and Gas Log Measures: ' § 150.0(e)lA: Closable Doors. Masonry or factory -built fireplaces must have a closable metal or glass door covering the entire opening of the firebox. . § 150.0(e)1 B: Combustion Intake. Masonry or factory -built fireplaces must have a combustion outside air intake, whjch is at least six square inches in area ' and is equipped with a readily accessible; operable, and tight -fitting damper or combustion -air controLcevice * § 150.0(e)1C: " Flue Damper. Masonry or factory -built fireplaces must have a flue damper with a readily accessible control.' § 150.0(e)2:. Pilot Light. Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of the building, are prohibited. _ Space Conditioning, Water Heating, and Plumbing System Measures: § 110.0-§ 110.3: ; Certification. Heating, ventilation and air conditioning (HVAC) equipment,' water heaters, showerheack faucets, and all other regulated appliances must be certified by the manufacturer to the Energy Commission' . § 110.2(a): HVAC Efficiency. Equipment must meet the applicable efficiency requirements in TABLE 110.2-A through TABLE 110.2-K.' " " • Controls for Heat Pumps with Supplementary Electric Resistance Heaters. Heat pumps with supplementary electric resistance heaters § 110.2(b):' must have controls that prevent supplementary heater operation when the heating load can be met by the heat pump alone; and in which the cut -on temperature for compression heating is higher than the cut -on temperature for supplementary heating, and the cut-off temperature for compression heating is higher than the cut-off temperature for supplementary heating.* § 110.2(c): Thermostats. All unitary heating or cooling systems not controlled by a central energy management control system (EMCS) must.have a setback thermostat' Water Heating Recirculation Loops Serving Multiple Dwelling Units. Water heating recirculation (bops serving multiple dwelling units must § 110.3(c)5: meet the air release valve, backflow prevention, pump priming, pump isolation valve, and recirculatior loop connection requirements of § 1 10.3 c 5. § 110.3(c)7: Isolation Valves. Instantaneous water heaters with an input rating greater than 6.8 kBTU/hr (2 kW) must have isolation valves with hose bibbs or otherfittin s on both cold water and hot water lines of water heating systems to allow for water tanK flushing when the valves are closed. § 110.5: Pilot Lights. Continuously burning pilot lights are prohibited for rnatural gas: fan -type central fumace:; household cooking appliances (appli- ances without an electrical supply voltage connection with pilot lights that consume less than 150 BtLthr are exempt); and pool and spa heaters' Building Cooling and Heating Loads. Heating and/or cooling loads are calculated in accordance with ASHRAE Handbook, Equipment F150.0(h)l: Volume, Applica_ tions Volume, and Fundamentals Volume; SMACNA Residential Comfort System Installation Standards Manual; or ACCA Manual J usin desi n conditions specified in § 150.0(h)2. 2016 Low -Rise Residential MandatoryMeasures Summary § 150.0(h)3A-� Clearances. Installed air conditioner and heat pump outdoor condensing units must have a clearance of atileast 5 feet from the outlet of any • . dryer vent. 150.0(h)3B: Liquid Line Drier. Installed air conditioner and heat pump systems must be equipped with liquid line filter driers if required, as specified by _§ manufacturer's instructions. § 150.00)1: Storage Tank Insulation. Unfired hot water tanks, such as storage tanks and backup storage tanks for soar water -heating systems, must have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the. exterior of the tank. Water piping and cooling system line insulation. For domestic hot water system piping, whether buried or unburied, all of the following must be insulated according to the requirements of TABLE 120.3-A: the first 5 feet of hot and cold water pipes from the storage tank; all piping with a § 150.00)2A: • ," nominal diameter of 3/4 inch or larger; all piping associated with a domestic hot water recirculation systemsegardless of the pipe diameter; piping from the heating source to storage tank or between tanks; piping buried below grade; and all hot weer pipes from the heating source to kitchen fixtures' § 150.00)26: Water piping and cooling system line insulation. All domestic water pipes that are buried below grede must be installed in a waterproof and non -crushable casing or sleeve' § 150.00)X: ' Water piping and cooling system line insulation. Pipe for cooling system lines must be insulated as specified in § 150.00)2A. Distribution piping for steam and h dronic heating systems or hot waters stems must meet the requirements in TABLE 120.3-A.• § 150.00)3: Insulation Protection. Insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Insulation Protection. Insulation exposed to weather must be installed with a cover suitable for outdoor service. For example, protected by § 150.00)3A: aluminum, sheet metal, painted canvas, or plastic cover. The cover must be water retardant and provide shielding from solar radiation that can cause degradation of the material. § 150.00)36: Insulation Protection. Insulation covering chilled water piping and refrigerant suction piping located outs,de the conditioned space must have a Class l or Class II vapor retarder. Gas or Propane Systems. Systems using gas or propane water heaters to serve individual dwelling units must include all of the following: a § 150.0(n)l: 120V electrical receptacle within 3 feet of the water heater; a Category III or. IV vent, or a Type B vent wits straight pipe between the outside termination and the space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the water heater, and allows natural draining without pump assistance; and a g as supply line with a capacity of at least 200,000 Btu/hr. , § 15.0.0(n)2: Recirculating Loops. Recirculating loops serving multiple dwelling units must meet the requirements of § 1.10.3(c)5. §,150.0(n)3: Solar Water -heating Systems. Solar water -heating systems and collectors must be certified and rated Ley the Solar. Rating and Certification Corporation SRCC or by a listing agency that is approved by the Executive Director. -Ducts and Fans Measures: § 110.8(d)3: Ducts. Insulation installed on an existing space -conditioning duct must comply with § 604.0 of the California Mechanical Code (CMC). If a contractor installs, the insulation, the contractor must certify to the customer, in writing, that the insulatior meets this requirement. ' CMC Compliance.'All air -distribution system ducts and plenums must be installed, sealed, and insulated to meet the requirements of CMC §§ 601.0, 602.0, 603.0, 604.0, 605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition. Portions' : of supply -air and retum-air ducts and plenums must be insulated to a minimum installed level of R-6.0 (cr higher if required by CMC § 605.0) or a minimum installed level of R4.2 when entirely in conditioned space as confirmed through field verification and diagnostic testing § 150.0(m)1 ' (RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts must be mechanically fastened. Openings must be sealed with . mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL 181A, Dr UL 181B or aerosol sealant that meets the requirements of UL.723. If mastic or tape is used to seal openings greater than ''% inch, the combination of mastic and either mesh or : tape must be used. Building cavities, support platforms for air handlers, and plenums designed or const acted with materials other than sealed sheet metal, duct board or flexible duct must not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support plafforms must not be compressed to cause reductions in the cross-sectional area of the ducts.' . Factory -Fabricated Duct Systems. Factory -fabricated duct systems must comply with applicable regtirements for duct construction, § 150.0(m)2: connections, and closures; joints and seams of duct systems and their components must not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and draw bands. § 150.0(m)3: Field -Fabricated Duct Systems. Field -fabricated duct systems must comply with applicable requirements for: pressure -sensitive tapes, mastics, sealants, -and other requirements specified for duct construction. § 150.0(m)7: Backdraft Dampers. All fan systems that exchange air between the conditioned space and the outside: of the building must have backdraft or automatic dampers. § •150.0(m)8: Gravity Ventilation Dampers. Gravity ventilating systems serving conditioned space must have either automatic or readily accessible, manually operated dampers in all openings to the outside, except combustion inlet and outlet air o enih s and elevator shaft vents. ' - Protection of Insulation. Insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance, and § 150.0(m)g: • wind. Insulation exposed to weather must be suitable for outdoor service. For example, protected by a.uminum, sheet metal, painted canvas, or . • plastic cover. Cellular foam insulation must be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation. - § 150.0(m)10: Porous Inner Core Flex Duct. Porous inner core flex duct must have a non -porous layer between the inner core and outer vapor barrier. Duct System Sealing and Leakage Test. When space conditioning systems use forced air duct systems to supply conditioned air to an § 150.0(m)l 1: occupiable space, the ducts must be sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in accordance with § 150.0 m l land Reference Residential Appendix RA3. Air Filtration. Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal § 150.0(m)12- conditioning component, except evaporative coolers, must be provided with air filter devices that mees. the design, installation efficiency, pressure drop, and labeling requirements of § 150.0(m)12. IN 2016 Low -Rise Residential Mandatory Measures Summary Duct System Sizing and Air Filter Grille Sizing. Space conditioning systems that use forced air ducts to supply cooling to an occupiable space must have a hole for the placement of a static pressure probe (HSPP), or a permanently installed stetic pressure probe (PSPP) in the § 150.0(m)13: supply plenum. The space conditioning system must also demonstrate airflow z 350 CFM per ton of nominal cooling capacity through the return grilles, and an air -handling unit fan efficacy:5 0.58 W/CFM as confirmed by field verification and diagnostic-xesting, in accordance with Reference Residential Appendix RAU. This applies to both single zone central forced air systems and every zone for zonally controlled central forced airs stems' Ventilation for Indoor Air Quality. All dwelling units must meet the requirements of ASHRAE Standard 62.2. Neither window operation nor §150.0(0): continuous operation of central forced air system air handlers used in central fan integrated ventilation sys gems are permissible methods of providing whole -building ventilation. § 150.0(o)1A: Field Verification and Diagnostic Testing. Whole -building ventilation airflow must be confirmed through field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3.7. Pool and Spa Systems and Equipment Measures: Certification by Manufacturers. Any pool or spa heating system or equipment must be certified to have MI of the following: a thermal efficiency § 110.4(a): that complies with the Appliance Efficiency Regulations; an on-off switch mounted outside of the heater that allows shutting off the heater without adjusting the thermostat setting; a permanent weatherproof plate or card with operating instructions; and must not use electric resistance heating! § 110.4(b)l: Piping. Any pool or spa heating equipment must be installed with at least 36 inches of pipe between the #Iter and the heater, or dedicated suction and return lines, or built-in or built-up connections to allow for future solar heating. § 110.4(b)2: Covers. Outdoor pools or spas that have a heat pump or gas heater must have a cover. § 110.4(b)3: Directional inlets and time switches for pools. Pools must have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or programmed to run only during off-peak electric demand periods. § 110.5: Pilot Light. Natural gas pool and spa heaters must not have a continuously burning pilot light. 150.0 § (p)' Pool Systems and Equipment Installation. Residential pool systems or equipment must meet the specified requirements for pump sizing, flow rate, piping, filters, and valves' Lighting Measures: § 110.9: Lighting Controls and Components. All lighting control devices and systems, ballasts, and luminaires must meet the applicable requirements of § 110.9. § 110.9(e): JAB High Efficacy Light Sources. To qualify as a JAB high efficacy light source for compliance with § ':50.0(k), a residential light source must be certified to the Energy Commission according to Reference Joint Appendix JAB. § 150.0(k)1A: Luminaire Efficacy. All installed luminaires must be high efficacy in accordance with TABLE 150.0-A. Blank Electrical Boxes. The number of electrical boxes that are more than 5 feet above the finished floor and do not contain a luminaire or § 150.0(k)l B: other device must be no greater than the number of bedrooms. These electrical boxes must be served 1 y a dimmer, vacancy sensor control, or fan speed control. Recessed Downlight Luminaires in Ceilings. Luminaires recessed into ceilings must meet all of the equirements for: insulation contact (IC) § 150.0(k)l C: labeling; air leakage; sealing; maintenance; and socket and light source as described in § 150.0(k)l C. A JA8-2016-E light source rated for elevated temperature must be installed by final inspection in all recessed downli ht luminaires in ceilincs. § 150.0(k)l D: Electronic Ballasts. Ballasts for fluorescent lamps rated 13 wafts or greater must be electronic and most have an output frequency no less than 20 kHz. Night Lights. Permanently installed night lights and night lights integral to installed luminaires or exhaust fans must be rated to consume no § 150.0(k)l E: more than 5 wafts of power per luminaire or exhaust fan as determined in accordance with § 130.0(c). +light lights do not need to be controlled by vacancy sensors. § 150.0(k)1F: Lighting Integral to Exhaust Fans. Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) must meet the applicable requirements of § 150.0(k).* Screw based luminaires. Screw based luminaires must not be recessed downlight luminaires in ceilirgs and must contain lamps that comply § 150.0(k)l G: with Reference Joint Appendix JAB. Installed lamps must be marked with "JA8-2016" or "JA8-2016-E" as specified in Reference Joint Appendix JAB.* § 150.0(k)1 H: Enclosed Luminaires. Light sources installed in enclosed luminaires must be JAB compliant and must be marked with "JA8-2016-E." § 150.0(k)2A: Interior Switches and Controls. All forward phase cut dimmers used with LED light sources must comply with NEMA SSL 7A. § 150.0(k)2B: Interior Switches and Controls. Exhaust fans must be switched separately from lighting systems § 150.0(k)2C: Interior Switches and Controls. Luminaires must be switched with readily accessible controls that permit the luminaires to be manually switched ON and OFF. § 150.0(k)2D: Interior Switches and Controls. Controls and equipment must be installed in accordance with manufacturer's instructions. § 150.0(k)2E: Interior Switches and Controls. No control must bypass a dimmer or vacancy sensor function if the=control is installed to comply with 150.0(k). § 150.0(k)2F: Interior Switches and Controls. Lighting controls must comply with the applicable requirements of F• 110.9. Interior Switches and Controls. An energy management control system (EMCS) may be used to comply with dimmer requirements if it: § 150.0(k)2G: functions as a dimmer according to § 110.9; meets the Installation Certificate requirements of § 130A; meets the EMCS requirements of § 130.5(0; and meets all other requirements in § 150.0(k)2. Interior Switches and Controls. An EMCS may be used to comply with vacancy sensor requiremerts in § 150.0(k) if it meets all of the § 150.0(k)2H: following: it functions as a vacancy sensor according to § 110.9; the Installation Certificate requirements of § 130.4; the EMCS requirements of § 130.5(0; and all other requirements in § 150.0(k)2. § 150.0(k)21: Interior Switches and Controls. A multiscene programmable controller may be used to comply with dimmer requirements in § 150.0(k) if it provides the functionality of a dimmer according to § 110.9, and complies with all other applicable requirements in § 150.0(k)2. 2016 Low -Rise Residential Mandatory Measures Summary § 150.0(k)2J: Interior Switches and Controls. In bathrooms, garages, laundry rooms, and utility rooms, at least one luminaire in each of these spaces must be controlled by a vacancy sensor. § 150.0(k)2K: Interior Switches and Controls. Dimmers or vacancy sensors must control all luminaires required to have light sources compliant with Reference Joint Appendix JAB, except luminaires in closets less than 70 square feet and luminaires in hallways.' § 150.0(k)2L: Interior Switches and Controls. Undercabinet lighting must be switched separately from other lighting systems. Residential Outdoor Lighting. For single-family residential buildings, outdoor lighting permanently mounted to a residential building, or to other § 150.0(k)3A: buildings on the same lot, must meet the requirement in item § 150.0(k)3Ai (ON and OFF switch) and the requirements in either item § 150.0(k)3Aii (photocell and motion sensor) or item § 150.0(k)3Aiii (photo control and automatic time switch control, astronomical time clock, or EMCS. Residential Outdoor Lighting. For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, § 150.0(k)3B: and porches; and outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site must comply with either § 150.0(k)3A or with the applicable requirements in §§ 110.9,130.0,130.2,130.4,140.7 and 141.0. § 150.0(k)3C: Residential Outdoor Lighting. For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by 150.0(k)3B or § 150.0(k)3D must comply with the applicable requirements in §§ 110.9, 130.0, 130.2, 130.4, 140.7 and 141.0. § 150.0(k)3D: Residential Outdoor Lighting. Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site must comply with the applicable requirements in §§ 110.9,130.0, 130.2,130.4,140.7, and 141.0. § 150.0(k)4: Internally illuminated address signs. Internally illuminated address signs must comply with § 140.8; or must consume no more than 5 watts of ower as determined according to § 130.0(c). § 150.0(k)5: Residential Garages for Eight or More Vehicles. Lighting for residential parking garages for eight or more vehicles must comply with the applicable requirements for nonresidential garages in §§ 110.9, 130.0, 130.1, 130.4, 140.6, and 141.0. Interior Common Areas of Low-rise Multi -Family Residential Buildings. In a low-rise multifamily residential building where the total interior § 150.0(k)6A: common area in a single building equals 20 percent or less of the floor area, permanently installed lighting for the interior common areas in that building must be high efficacy luminaires and controlled by an occupant sensor. Interior Common Areas of Low-rise Multi -Family Residential Buildings. In a low-rise multifamily residential building where the total interior common area in a single building equals more than 20 percent of the floor area, permanently installed lighting in that building must: § 150.0(k)6B: i. Comply with the applicable requirements in §§ 110.9,130.0,130.1, 140.6 and 141.0; and ii. Lighting installed in corridors and stairwells must be controlled by occupant sensors that reduce the lighting power in each space by at least 50 percent. The occupant sensors must be capable of turning the light fully on and off from all designed paths of ingress and egress. Solar Ready Buildings: Single Family Residences. Single family residences located in subdivisions with ten or more single family residences and where the § 110.10(a)1: application for a tentative subdivision map for the residences has been deemed complete by the enforcement agency must comply with the requirements of § 110.10 b through § 110.10 e . § 110.10(a)2: Low-rise Muiti-family Buildings. Low-rise multi -family buildings must comply with the requirements of § 110.10(b) through § 110.10(d). Minimum Area. The solar zone must have a minimum total area as described below. The solar zone must comply with access, pathway, smoke ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a local jurisdiction. The solar zone total area must be comprised of areas that have no dimension less than 5 feet and are no less than 80 square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for buildings with roof areas § 110.10(b)1: greater than 10,000 square feet. For single family residences the solar zone must be located on the roof or overhang of the building and have a total area no less than 250 square feet. For low-rise multi -family buildings the solar zone must be located on the roof or overhang of the building, or on the roof or overhang of another structure located within 250 feet of the building, or on covered parking installed with the building project, and have a total area no less than 15 percent of the total roof area of the building excluding any skylight area ' § 110.10(b)2: Orientation. All sections of the solar zone located on steep -sloped roofs must be oriented between 110 degrees and 270 degrees of true north. § 110.10(b)3A: Shading. The solar zone must not contain any obstructions, including but not limited to: vents, chimneys, architectural features, and roof mounted equipment.' Shading. Any obstruction located on the roof or any other part of the building that projects above a solar zone must be located at least twice the § 110.10(b)3B: distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the horizontal projection of the nearest point of the solar zone, measured in the vertical plane.' § 110.10(b)4: Structural Design Loads on Construction Documents. For areas of the roof designated as solar zone, the structural design loads for roof dead load and roof live load must be clearly indicated on the construction documents. Interconnection Pathways. The construction documents must indicate: a location for inverters and metering equipment and a pathway for § 110.10(c): routing of conduit from the solar zone to the point of interconnection with the electrical service (for single family residences the point of interconnection will be the main service panel); and a pathway for routing of plumbing from the solar zone to the water -heating system. § 110.10(d): Documentation. A copy of the construction documents ora comparable document indicating the information from § 110.10(b) through 110.10(c) must be provided to the occu ant. § 110.10(e)1: Main Electrical Service Panel. The main electrical service panel must have a minimum busbar rating of 200 amps. Main Electrical Service Panel. The main electrical service panel must have a reserved space to allow for the installation of a double pole circuit § 110.10(e)2: breaker for a future solar electric installation. The reserved space must be: positioned at the opposite (load) end from the input feeder location or main circuit location; and permanently marked as 'For Future Solar Electric".