Foohill Fire Protection Inc.
170 Erma Ct.
Chico, CA 95928
530-826-3013
Job Name Logan Res—FP-8-17-17
Building FP -1
Location 13572 Doe Mill Rd., Forest Ranch, CA 95942
System 1
Contract 17-26-0084
Data File LoganRes_FP-8-17-17 Area 1.WXF
'BY17 FILE/PCI
2016
063-040-117
A UGUST 3 1, 2017
F/S FOR B'13-0846
-A-
Computer Programs by Hydratec Inc. Revision: 50.52.1
Foohill Fire Protection lnc.,,,��;- Page
LoganRes FP 84��-i7� Date
114YDRAULIC CALCULATIONS
iA
for
Project name: LoganRes_FP-8-17-17
Location: 13572 Doe Mill Rd., Forest Ranch, CA 95942
Drawing no: FP -1
Date: 08/23/17
Design
Remote area number. 1
Remote area location: Sleeping Area
Occupancy classification: Residential
Density: 0.05 - Gpm/SqFt
Area of application: 512 - SqFt
Coverage per sprinkler. 256 - SqFt
Type of sprinklers calculated: 4.91K 165* SSP
No. of sprinklers calculated: 2
In -rack demand: N/A - GPM
Hose streams: 5 - GPM
Total water required (including hose streams): 31.7889 -GPM @ 38.572 -Psi
Type of system: Wet
Volume of dry or preaction system: N/A - Gal
Water supply information
Date: N/A
Location: N/A
Source: N/A
Name of contractor. Foohill Fire Protection Inc.
Address: 170 Erma Ct. / / Chico, CA 95928
Phone number: 530-826-3013
Name of designer. Colby Cram
Authority having jurisdiction: Butte County
Notes: (include peaking information or gridded systems here.)
Computer Programs by Hydratec Inc. Revision: 50.52.1
Water Supply Curve C
Foohill Fire Protection Inc.
Logan Res -FP -8-17-17
Page 2
Date
Demand:
D1 - Elevation 3.465
D2 - System Flow 26.789
D2 - System Pressure 38.572
Hose ( Demand ) 5
D3 - System Demand 31.789
Safety Margin
150
140
130
p 120
R 110
E 100
S 90
S 80
U 70
R 60
E 50
D2
40
30
U3
20
10
........
T ........
.........
7 ........
-04-
10 20 30 40 50 1 60 70 80 90
FLOW (N 11 1.85)
Computer Programs by Hydratec Inc. Revision: 50.52.1
Fittings Used Summary
Foohill Fire Protection Inc. Page 3
LoganRes—FP-8-17-17 Date
Fitting Legend
Abbrev. Name 1/2 % 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N - CPVC 90'Ell Harvel -Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0
0. CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
R - CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
Unit Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Iry.. Revision: 50.52.1
depressure / Flow Summary - STANDARD
Foohill Fire Protection Inc.
Page 4
Logan Res—FP-8-1 7-17
Date
Node Elevation K -Fact
Pt
Pn
Flow Density
Area Press
No.
Actual
Actual
Reg.
1 8.0 4.9
7.05
na
13.01 0.05
256 7.05
2 9.0
6.86
na
3 9.0,
7.68
na
4 9.0
14.45
na
TOR 9.0
22:16
na
5.0
6OR -2.0
36.59
na
TEST 0.0
38.57
na
5 8.0 4.9
7.91
na
13.78 0.05
256 7.05
The maximum velocity is 10.71 and it occurs in the pipe between nodes TOR
and BOR
Computer Programs by Hydratec Inc. Revision: 50.52.1
Final Calculations - Hazen -Williams - 2007 At
Foohill Fire Protection Inc. Page 5
Logan Res -FP -8-1 7-17 Date
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C'. or Ftng's Pe Pv Notes
Point Qt Pf/Ft Eqv. , Ln. Tota I Pf Pn
1
13.01
1.101
N
7.0
1.000
7.050
K Factor = 4.90
to
to 150.0
150.0
0.0
7.000
-0.433
0.0
2
13.01
0.0308
7.679
0.0
8.000
0.246
Vel = 4:38
2
0.0
1.101
2N
14.0
11.580
6.863
to
150.0
R
1.0
15.000
0.0
3
13.01
0.0307
0.0
26.580
0.816
Vel = 4.38
3
13.78
1.101
6N
42.0
13.930
7.679
to
150.0
2R
2.0
44.000
0.0
4
26.79
0.1168
0.0
57.930
6.768
Vel = 9.03
4
0.0
1.101
20
10.0
13.030
14.447
to
150.0 -
6N
42.0
53.000
0.0
TOR
26.79
0.1168
R
1.0
66.030
7.715
Vel = 9.03
TOR
5.00
1.101
3N
21.0
11.000
22.162
Qa = 5
to
150.0
Fsp
0.0
30.562
7.764
* Fixed Loss 3
BOR
31,79
0.1603
S
9.563
41.562
6.664
Vel = 10.71
BOR
0.0
1.598
N
9.0
100.000
36.590
to
150.0
0.0
9.000
-0.866
TEST
31.79
0.0261
0.0
109.000
2.848
Vel = 5.09
0.0
31.79
38.572
K Factor= , 5.12
5 13.78 1.101
0 5.0 1.000 7.907
K Factor = 4.90
to 150.0
0.0 5.000 -0.433
3 13.78 0.0342
0.0 6.000 0.205
Vel = 4.64
0.0
13.78
7.679
K Factor= 4.97
Computer Programs by Hydratec Inc. Revision: 50.52.1
DESIGN INSTALLATION INSPECTION e REPAIR
Chico Office: 170 Erma Ct., Chico, CA 95928 e Phone: (530) 826-3013 / Fax: (530) 893-3013
Rocklin Office: 4000 Alvis Ct., Rocklin, CA 95677 Phone: (916) 663-3582 Fax: (916) 663-3583
Logan Residence
13572 Doe Mill Rd.
Forest Ranch, CA 95942
BUT -Te 1�r"'OUNV
13Ujjj)jWC, (WISION
t4pqROVED
Fire Protection
Material Data Submittal
08/29/2017
vpc��I-
1317-7-016, FI -L
7 2�)
0631-040-1.17, -
AUGUST311, 2017
F/S FOR. B1.3-0846
®R
R411mlablia
A Residential Flat Concealed
Sprinkler engineered for a minimum
design density of 0.05 gpM/ft2 with
low GPM requirements.
Features
1. Very low water flow requirements.
2. Cover plate attachment (Plain or Perforated)
with 1/2" (1 3mm) Total adjustment.
3. Th read -O n/Th read -Off or Push-On[Thread
Off cover attachment option.
4. Smooth aesthetic ceiling profile.
5. Available in brass, chrome and black plated
or painted finishes.
Listings & Approval
1. Listed by Underwriters Laboratories, and
certified by UL for Canada (cULus)
UL Listing Categories
Residential. Aut6m atic Sprinklers
U ' L Guide Number-
VKKW
Product Description
Model RFC30, RFC43 and RFC49 Concealed Residen-
tial Sprinklers are fast response residential fusible solder
link automatic sprinklers. Residential sprinklers differ
from standard sprinklers primarily in their response time
and water distribution patterns.
Model RFC30, RIF ' C43 and RFC49 sprinklers discharge
water in a hemispherical pattern below the sprinkler de-
flector. Residential distribution patterns are higher and
generally contain a finer droplet size than standard sprin-
kler patterns.
The combination of speed of operation and high dis-
charge pattern required for residential sprinklers has
demonstrated, in fire testing,, an ability for controlling
residential fires, and thereby providing significant evacu-
ation time for occupants.
The RFC30, RFC43 and RFC49 Sprinklers provide the
best form of fire protection by combining an attractive ap-
pearance and 1/2" (13mm) of cover adjustment for ease
of installation. The small diameter cover plate is easily
Bulletin 006 Rev. I
Model RFC30 (SIN RA061 1)
Model RFC43 (SIN RA0612)
Model RFC49 (SIN RA0616)
Residential Flat Concealed
Sprinklers
I Main Uover Hate
Perforated Cover Plate
.and positively attached and blends into the ceiling, con-
cealing the most dependable fire protection available, an
automatic sprinkler system.
The RFC30, RFC43 and RFC49 are UL Listed Residen-
tial Sprinklers to be installed in the residential portions
of any occupancy in accordance with NFPA 13, 13R, &
13D. -
The RFC30, RFC43 and RFC49 can reduce the need
for precise cutting of drop nipples. The threaded cover
plate assembly can be adjusted without tools to fit ac-
curately against the ceiling. The fire protection system
need not be shut down to adjust or remove the cover
plate assembly.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
0
C)
0')
M
CD
Application and Installation
The RFC30, RFC43 and RFC49, for residential instal-
lations, use a 165'F (74'C) fusible solder link in a tun-
ing fork style sprinkler frame with a drop-down deflector.
This assembly is recessed into the ceiling and concealed
by a flat cover plate. The cover plate is attached to the
skirt, using 135"F (570C) ordinary temperature classifica-
tion solder. When the ceiling temperature rises, the solder
holding the cover plate releases the cover allowing the
deflector to drop into position and exposing the sprinkler
inside to ceiling temperature. The subsequent operation
of the solder link opens the waterway and causes the de-
fiector to drop into position to distribute the discharging
water in a hemispherical pattern below the sprinkler de-
flector. Any adjustment of thread engagement between
the cover plate and cup will assure that the drop-down
deflector is properly located below the ceiling. The resi-
dential distribution pattern contains a finer droplet size
than a standard sprinkler, and the pattern produces sig-
nificantly higher wall wetting.
After a 2 5/8 inch diameter hole is cut in the ceiling, the
sprinkler is to be installed with the Model FC Wrench.
When installing a sprinkler, the wrench is first positioned
into the sprinkler/cup assembly and around the hexago-
nal body of the sprinkler frame. The Wrench must bottom
out against the cup in order to ensure proper, safe instal-
lation. The sprinkler is then tightened into the pipe fitting.
When inserting or removing the wrench from the sprin-
kler/cup assembly, care should be taken to prevent dam-
age to the sprinkler. DO NOT WRENCH ON ANY OTHER
PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL
RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS
MUST BE INSTALLED ONLY WITH 1350F RATED COV-
ERS.
Note: A leak tight 1/2" NPT (R1/2) sprinkler joint can be ob-
tained with a torque of 8-18 ft -lbs (10,8 - 24,4 N -m). Do not
tighten sprinklers over maximum recommended torque. It
may cause leakage or impairment of the sprinklers.
Cover assemblies provide up to 1/2" (13mm) of adjust-
ment. Turn the cover clockwise until the flange is in con-
tact with the ceiling. For the push-on/thread-off option,
the cover assembly is pushed onto the cup and final ad-
justment is made by turning the cover clockwise until the
skirt flange makes full contact with the ceiling. Cover re-
moval requires turning in the counter -clockwise direction.
In ceilings that have a plenum space above the
sprinkler, the plenum space may have neutral or neg-
ative pressurization but must not be positively pres-
surized. Inspect all sprinklers after installation to en-
sure that the gap between the cover plate and ceiling
and the 4 slots in the cup are all open and free from
any air flow impediment.
Model
Thread
Nominal
Sprinkler
CCP Assembly
Max.
Ambient
K
Max.
(SIN)
Size
Orifice
Temp Rating
Temp. Rating
Temp.
Factor
Pressure
Spacing
Ft (m)
Inch (mm)
Inch (mm)
psi (bar)
GPM (Umin)
PSI (bar)
12 x 12 (3,6 x 3,6)
12(3,6)
9(34,1)
9.0(0,62)
OF
Oc
OF
Oc
OF
Oc
14 x 14 (4,3 x 4,3)
RFC 30
10(37,8)
11.0(0,76)
13 installed in beams 1/2 to 1 (13 to 25.4)
(RA061 1)
2
" " (15)
2'/64 (8,2)
165
74
135
57
100
38
3.0(43.2)
175(12)
RFC 43
(RA0612)
1/2" (15)
3/,(10)
1 165
1 74
1 135
1 57
1 100
1 38
1 4.3(62)
175(12 .
RFC 49
(RA061 6)-
'/2..(15)
/16 0 1)
165
74
135
57
100
38
4.9(70.6)
175(12)
Note: 1 bar = 100 Kpa
IRFC 30
For Ceiling types refer to NFPA 13, 13R or 13D
2.
Ordinary Temp. Rating
Max. Coverage
Max. Spacing
(11 65'Ff74-C)
Top of Deflector
Installation
Minimum
area
Ft x Ft (m x m)
Ft (m)
to Ceiling
Inch (mm)
Type
Spacing
Ft (m)
Flow
Pressure
GPM (Umin)
PSI (bar)
12 x 12 (3,6 x 3,6)
12(3,6)
9(34,1)
9.0(0,62)
Smooth Ceilings 1/2 to 1 (13 to 25.4)
Beamed Ceilings per NFPA 13D, -13R or
Concealed
8(2,4)
14 x 14 (4,3 x 4,3)
14(4,3)
10(37,8)
11.0(0,76)
13 installed in beams 1/2 to 1 (13 to 25.4)
For Ceiling types refer to NFPA 13, 13R or 13D
2.
RFC 43
For Ceiling types refer to NFPA 13, 13R or 13D
RFC 49
Max. Coverage
Ordinary Temp. Rating
Top.of Deflector
Minimum
Max. Coverage
Max. Spacing
(165'F/74 -C)
Top of Deflector
Installation
Minimum
area
Ft x Ft (m x m)
Ft (m)
to Ceiling
Inch (mm)
Type
Spacing
Ft (m)
Flow
Pressure
GPM (Umin)
PSI (bar)
12 x 12 (3,6 x 3,6)
12(3.6)
12(4,5)
7.8(0,54)
Smooth Ceilings 1/2 to 1 (13 to 25.4)
14 x 14 (4,3 x 4,3)
14(4.3)
13(49)
9.1(0,63)
16 x 16 (4,9 x 4,9)
16(4.9)
13(49)
9.1(0,63)
Beamed Ceilings per NFPA 13D, 13R or
13 installed in beams 1/2 to 1 (13 to 25.4)
Concealed
8(2,4)
18 X 18 (5,5 x 5,5)
18(5.5)
18(68)
17.5(1,21)
20 x 20 (6,1 x 6, 1)
20(6,1)
21(79)
23.8(1,64)
For Ceiling types refer to NFPA 13, 13R or 13D
RFC 49
Max. Coverage
Ordinary Temp. Rating
Top.of Deflector
Minimum
area
Max. Spacing
(1650 40C)
to Ceiling
Installation
Spacing
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Type
Ft (m)
GPM (Umin)
PSI (bar)
12 x 12 (3,6 x 3,6)
12(3,6)
13(49)
7.0(0,48)
Smooth Ceilings 1/2 to 1 (13 to 25.4)
14 x 14 (4,3 x 4,3)
14(4,3)
13(49)
7.0(0,48)
16 x 16 (4,9 x 4,9)
16(4,9)
13(49)
7.0(0,48)
Beamed Ceilings per NFPA 13D, 13R or
13 installed in beams 1/2 to 1 (13 to 25.4)
Concealed
8(2,4)
18 x 18 (5,5 x 5,5)
18(5,5)
17(64,3)
12.0(0,83)
20 x 20 (6,1 x 6, 1)
20(6,1)
20(75,73)
16.7(1,14)
For Ceiling types refer to NFPA 13, 13R or 13D
Maintenance
Model RFC30, RFC43 and RFC49 Concealed Sprin-
klers should be inspected and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or
gentle vacuuming. Remove any sprinkler cover plate as-
sembly which has been painted (other than factory ap-
plied) or damaged in any way. A stock of spare sprin-
klers should be maintained to allow quick replacement
of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons
and packaging until used to minimize the potential for
damage to sprinklers that would cause improper opera-
tion or non -operation.
Model RFC30, RFC43 and RFC49 Residential
Concealed Sprinkler Specification
Sprinklers shall be cULus Listed low flow residential con-
cealed sprinklers with drop-down deflector and adjust-
able flat cover plate engineered for a minimum design
density of 0.05 gpm/ft'. Sprinkler frame and deflector
shall be of bronze frame construction having a 1/2" NPT
thread. Thermal element shall consist of an approved
black -painted beryllium -nickel fusible solder link with
3.
symmetric lever mechanism, maintaining a Teflon -coated
Belleville spring washer and machined brass cap water
seal assembly containing no plastic parts. Sprinkler K -
factor shall be nominal 3.0 (43.2), 4.3 (62), and 4.9 (70.6)
having a 5/16", 3/8" and 7/16" orifice. Temperature rating
shall be -Ordinary 165'F (74'C); cover plate temperature
rating to be 135'F (57C). Cover plate assembly shall
consist of a brass cover plate and copper alloy retainer
flange allowing a 1/2" cover plate adjustment. Any secure
engagement between the cover plate and the cup will
assure that the drop-down deflector is properly located
below the ceiling. A plastic protective cap shall be
provided and factory installed inside the sprinkler cup
to protect the drop-down sprinkler deflector from dam-
age, which could occur during construction before the
cover plate is installed. Standard cover finish: [Chrome]
[White) [Specialty - specify]. Residential concealed
sprinklers shall be Reliable Model RFC30, SIN RA0611
(Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006)
or Model RFC49, SIN RA0616 (Bulletin 006).
Ordering Information
Specify:
1. Sprinkler Model
2. Cover Plate Finish
3. Thread -On or
Push -On Feature
Cover Plate Finishes0)
Standard Finishes
Chrome
White Paint
Special Application
FinisheS(2)
Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome
(1) Other finishes and colors are
available on special order.
Consult factory for details.
Coverplate custom paint is
semi -gloss, unless specified
otherwise.
(2) For the perforated style cover -
plate, consult factory for avail-
ability on these and other cus-
tom finishes.
I' x 112' REDUCING
TEE OR ELBOW
—JL -
2j' (66.55,,,,j
HOLE IN
[.58.42.11,111 DIA CEILING
CUP
2- [50.8mm] WX
FACE OF RMNG
[12.70mml WX
TO FACE OF CEILING
COVER ADJUSTWENT
DIMENSION
(800) 431-1588
A S
Paper
112- [12.70mml MIN. 70 Y
(800) 848-6051
I' [25.4mm] MAY. CEILING
Revision lines indicate updated or new data.
DROPPED DEFLECTOR
(914) 829-2042
TO CEILING
It
[4.96,nm] -7
FLAr COVER PLA7E_1 J;6- [84.21mml D1k
ASSEMBLr
SPRUINK
COVER PLATE 112" 02.7mmj ADJUSTMENT
00MWIC
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
®R
Reliable Automatic Sprinkler Co., Inc.
Recycled
(800) 431-1588
Sales Offices
Paper
Reliabile
(800) 848-6051
Sales Fax
Revision lines indicate updated or new data.
(914) 829-2042
Corporate Offices
blesprinkler.com
Internet Address
EG. Printed in U.S.A. 11/ 14 P/N 9999970261
R
0
Reliable
Bulletin 135 Rev. M
Model F1
Residential Sprinklers for
Design Density of .05 gpm4t2
Model F1 Res Sprinklers engineered for the lowest f lows
to meet the minimum design density of .05 gpm4t2
Types:
1 . F1 Res 30 Pendent
2. F1 Res 30 Recessed Pendent/F2
3. F1 Res 30 Recessed Pendent/FP
4. F1 Res 49 Pendent
5. F1 Res 49 Recessed Penclent/Fi
6. F1 Res 49 Recessed Penclent/FP
7. F1 Res 58 Pendent
8. F1 Res 58 Recessed Pendent/F1
9. F1 Res 58 Recessed Penclent/FP
10. F1 Res 76 Pendent
11. F1 Res 76 Recessed Penclent/Fi
12. F1 Res 76 Recessed Pendent/FP
13. F1 Res 30 CCP Pendent
14. F1 Res 49 CCP Pendent
15. F1 Res 58 CCP Pendent
16. F1 Res 76 CCP Pendent
17. F1 Res 44 HSW
18. F1 Res 44 Recessed HSW/F2
19. F1 Res 58 HSW
20. F1 Res 58 HSWX
21. KRes58 HSWX
22. F1 Res 58 HSW Recessed HSW/F2
23. F1 Res 44 SWC
Listings & Approvals
1. Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
F1 Res 30, 49, 58 & 76 F1 Res 30, 49, 58 & 76
Recessed Pendent / F1 Recessed Pendent / FP
F1 Res 30, 49, 58 & 76
CCP Pendent
Sprinklers for .10 Density: Refer to Bulletin 176
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6,516,893 applies to the Model F1 Res 49
& 58 Pendent Sprinklers
US Patent No. 7,353,882 applies to Model F1 Res 44 & 58
HSW Sprinklers
US Patent No. 7,784,555 applies to Model F1 Res 44 SWC
Sprinklers
Product Description
Model F1 Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are fas " t
response sprinklers combining excellent durability, high sensitiv-
ity glass -bulb and low profile decorative design. The F1 Res
1- 1 KeS bb HbVVY\
A
F1 Res 44 & 58 F1 Res 44 SWC
Recessed HSW/F2
Horizontal Sidewall sprinklers (Figs. 5, 6 & 7) are equally attrac-
tive when above ceiling piping cannot be used.
The 3mm glass -bulb pendent sprinklers permit the efficient use
of residential water supplies for sprinkler coverage in residential
fire protection design.
. The low flow F1 Res sprinklers are specially engineered for fast
thermal response to meet the sensitive fire protection applica-
tion needs of the latest residential market standards (UL 1626
Standard). Upon fire conditions, rising heat causes a sprinkler's
heat -sensitive element, glass bulb or link to actuate, releasing the
waterway for water flow onto the deflector, evenly distributing the
discharged water to control a fire.
Technical Data:
• Thermal Sensor: Soldered Element (Link) or Nominal
3mm glass -bulb
• Sprinkler Frame : Brass Casting
• Sprinklers' Pressure Rating -. 175 psi
Factory Hydrostatically Tested to 500 psi
• Thread Size: 112" NPT (RI/2)
• K -Factor: 3.0 (43.2) (Actual) - F1 Res 30 Pendent Sprinkler
4.9 (70.6) (Actual) - F1 Res 49 Pendent Sprinkler
5.8 (83.5) (Actual) - F1 Res 58 Pendent & HSW Sprinkler
7.6 (109)(Actual) - F1 Res 76 Pendent Sprinkler
4.4 (63) (Actual) - F1 Res 44 HSW Sprinkler
• Density: Minimum 0.05 gpM/ft2
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application
7 Model F1 Res Sprinklers are used for Residential Fire Pro-
tection according to UL 1626 Standard*. For ceiling types:
Smooth Flat Horizontal, or beamed, or sloped, in accordance
with NFPA 13D, 13R, or 13 2013 editions. Be sure that orifice
size, temperature rating, deflector style and sprinkler type are
in accordance with the latest published standards of The Na-
tional Fire Protection Association or the approving authority
having jurisdiction.
Installation
Models F1 Res sprinklers are to be installed as shown.
Model F1, F2 and FP Escutcheons, illustrated herewith, are
Escutcheon*, F1 or F2, Data:
the only recessed escutcheons to be used with Model F1 Res
sprinklers. Use of any other recessed escutcheon will void all
approvals and warranties. For installing Model F1 Res Pen-
dent sprinklers use only the Model D sprinkler Wrench; for
installing Models F1 Res Recessed Pendent, CCP & SWC
sprinklers use only the Model GFR2 sprinkler wrench; for in-
stalling Model F1 Res Recessed HSW sprinklers use only the
Model GFR2 Sprinkler Wrench. Use of wrenches other than
those specified may damage these sprinklers. Install F1 Res
44 with a ceiling to deflector distance of 4" - 12". Flow arrow
on deflector must point away from near wall and "Top" mark-
ing must face ceiling.
Type
Adjustment
"A"
Face of fitting to ceiling
Deflector Distance below bottom of beam
I Sprinkler Lencith
Inch (mm)
Inch (mm)
Inch (mm)
Inch (mm)
2'/64" (8.2)
175(12)
155 68 100
175 79
38
3.0(43.2)
Inch (mm)
F1
3/4 (19.0)
Min. Recessed = 15/8 (41.3)
3/8 (9.5)
13/� (44.4)
Max. Recessed N (22.2)
11/s(28.6)
1 (25.4)
F2
1/2(12.7)
Min. Recessed 15/8 (41.3)
3/s(9.5)
13/4(44.4)
8(30,3)
7.0(0,48)
Max. Recessed 11/8 (28.6)
7/s(22.2)
11/4(31.7)
* Note: Escutcheons F1 or F2 may be used with Model F1 Res 49, 58 & 76 Recessed Pendent Sprinkler
0
Model F1 Res 30, 49, 58 & 76 Pende
03SVN
135F003
0 Model F1 Res 30 Recessed Pendent / F2
nt 0 Mod4
�i ri Kes 4% ots & 11b Kecesseo ii-eni
Jent / F1
F1 escutcheon, '/4" (19mm) adjustment
2 114 -HOLE DIA.
� [�72mmj —
1 15116 - DIA.
[49.2mm)
r – –
I' X 112" REDUCER
TURN COLLAR UNTIL
TIGHT AGAINST SPRINKLER FACE OF FITTING TO
WRENCH BOSS. F CEILING DIMENSION
318"-1 118- (FI ESCUTCHEON)
318�-718" (F2 ESCUTCHEON)
ADJUSTMENT
2 27132- DIA.
[72.2mml—
Fig. 1 Fig. 2
Technical Data: F1 Res 30 Pendent and Recessed Pendent (SIN R351 1)
Thread
Size
Nominal Orifice
Inch (mm)
ax. Pressure
Dsl (bar)
_��Ikler Temp. Rating I Max. Ambient Temp.
Actual K
Factor
I Sprinkler Lencith
Inch (mm)
OF oc OF
oc
1/2" NPT
(R 1/2)
2'/64" (8.2)
175(12)
155 68 100
175 79
38
3.0(43.2)
2.25(57)
For Ceiling types refer to NFPA 13, 13R or 13D
2.
Max.
Ordinary Temp. Rating
Intermediate Temp. Rating
Minimum
Max. Coverage area
Spacin 9
(1550 80c)
(1750F/790c)
Top of Deflector to Ceiling
Spacing
Flow
Pressure
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
GPM (Umin)
PSI (bar)
GPM (Umin)
PSI (bar)
12 x 12 (3,6 x 3,6)
12(3,6)
8(30,3)
7.0(0,48)
8(30,3)
7.0(0,48)
Smooth Ceilings 11/4 to 4 (31.7 to 102)
1
using F2 escutcheon,
14 x 14 (4,3 x 4,3�)
14(4,3)
10(37,8)
11(0,76)
10(37.8)
11(0,76)
Beamed Ceilings per NFPA 131), 13R
or 13 installed in beams 11/4 to 134
(31.7 to 44.4) using F2 escutcheon
8(2,4)
16 x 16 (4,9 x 4,9)
16(4,9)
13(49)
18.8(1,3)
13(49)
18.8(1,3)
For Ceiling types refer to NFPA 13, 13R or 13D
2.
Technical Data: F1 Res 49 Pendent and Recessed Pendent (SIN R3516)
Thread
Nominal Orifice
Max*
Sprinkler Max.
Actual
Sprinkler
Size
Inch (mm)
Pressure
emp. atinq Ambient Temp.
K
Length
OF
OC OF
OC
Pressure
Ft x Ft (m x m)
(bar)
Factor
Inch (mm)
1/2" NPT
(R 112)
7/16"
-psi
175(12)
1 55
175
� 68 100
79 150
38
66
4.9(70.6)
2.25(57)
For Ceiling types refer to NFPA 13, 13R or 13D
Ordinary Temp. Rating
Intermediate Temp. Rating
Top of Deflector
Minimum
Max. Coverage area
Max. Spacing
(1550F/680c)
(175*F/79*C)
to Ceiling
Spacing
Flow
Pressure
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
1/2" NPT
1/2" (13)
GPM Wmin)
PSI (bar)
GPM Wrnin)
PSI (bar)
Inch (mm)
Ft (m)
12 x 12 (3,6 x 3,6)
12(3,6)
13(49)
7,0(0,48)
13(49)
7.0(0,48)
Smooth Ceilings 11/4 to 4 (31.7 to
1102) using F2 escutcheon.
14 x 14 (4,3 x 4,3)
14(4,3)
13(49)
7.0(0,48)
13(49)
7.0(0,48)
1 to 4 (25.4 to 102) using F1
lescutcheon.
Beamed Ceilings per NFPA
13D, 13R or 13 installed in
8(2,4)
16 x 16 (4,9 x 4,9)
16(4.9)
13(49)
7.0(0,48)
13(49)
7.0(0,48)
18 x 18 (5,5 x 5,5)
18(5,5)
17(64.3)
12(0,83)
17(64,3)
12(0,83)
beams 1114 to 13/4 (31.7 to
44.4) using F2 escutcheon, 1
20(6,1)
20 x 20 (6,1 x 6, 1)
20(6,1)
20(75.7)
16.7(1,14)
20(75,7)
16,7(1,14)
to 13/4 (25.4 to 44.4) using F1
escutcheon
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 58 Pendent and Recessed Pendent (SIN R3513)
Ordinary Temp. Rating
Intermediate Temp. Rating
Top of Deflector
Minimum
Max. Coverage area
Max. Spacing
(1550 OC)
(1750F/790c)
to Ceiling
Spacing
Flow
Pressure
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
1/2" NPT
1/2" (13)
GPM (Umin)
PSI (bar)
GPM Wirnin)
PSI (bar)
5.8(83.5)
2.25(57)
12 x 12 (3,6 x 3,6)
12(3.6)
15(57)
9.4(0,65)
15(57)
9.4(0,65)
Smooth Ceilings 4 to 8 (100 to
203) using F2 escutcheon.
14 x 14 (4,3 x 4,3)
14(4,3)
16(60,5)
10.6(0,73)
1 16(60.5)
10.6(0,73)
4 to 8 (100 to 203) using F1
escutcheon.
16 x 16 (4,9 x 4,9)
16(4,9)
17(64,3)
12.0(0,83)
17(64.3)
12.0(0,83)
Beamed Ceilings per NFPA 13D,
13R or 13 installed in beams
8(2,4)
18 x 18 (5,5 x 5,5)
18(5,5)
19(72)
15.0(1,0)
19(72)
15.00-0)
41/4 to 8 (108 to 203) using F2
escutcheon, 4 to 8 (100 to 203)
20 x 20 (6,1 x 6, 1)
20(6,1)
22(83,2)
1 20.2(1,4)
22(83,2)
20.2(1,4)
using F 1 escutcheon
Technical Data: F1 Res 58 Pendent and Recessed Pendent (SIN R3513)
For Ceiling types refer to NFPA 13, 13R or 13D
3.
Max.
Sprinkler Max.
Top of Deflector
Sprinkler
Thread
Nominal Orifice
Pressure
Temp. ating Amble emp.
Actual
Length
Size
Inch (mm)
psi (bar)
K Factor
Inch (mm)
OF
OC OF
OC
1/2" NPT
1/2" (13)
175(12)
155
68 100
38
5.8(83.5)
2.25(57)
(R 1/2)
12(3,6)
16(61)
175
79 150
66
Smooth Ceilings 11/4 to 4 (31.7 to
102) using F2 escutcheon.
For Ceiling types refer to NFPA 13, 13R or 13D
3.
Ordinary Temp. Rating
Intermediate Temp. Rating
Top of Deflector
Minimum
Max. Coverage area
Max. Spacing
(1550F/680C)
(1750F/790c)
to Ceiling
Spacing
Flow
Pressure
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
GPM ( in)
PSI (bar)
GPM (Umin)
PSI (bar)
12 x 12 (3,6 x 3,6)
12(3,6)
16(61)
7.6(0,53)
16(61)
7.6(0.53)
Smooth Ceilings 11/4 to 4 (31.7 to
102) using F2 escutcheon.
14 x 14 (4,3 x 4,3)
14(4,3)
16(61)
7.6(0,53)
16(61)
7.6(0,53)
1 to 4 (25.4 to 102) using F1
escutcheon.
16 x 16 (4,9 x 4,9)
16(4,9)
16(61)
7.6(0,53)
16(61)
7.6(0,53)
Beamed Ceilings per NFPA 13D,
13R or 13 installed in beams
8(2.4)
18 x 18 (5,5 x 5,5)
18(5,5)
19(72)
10.8(0,75)
19(72)
10.8(0,
11/4 to 13/4 (31.7 to 44.4) using
F2 escutcheon, 1 to 13/4 (25.4 to
20 x 20 (6,1 x 6, 1)
20(6,1)
22(83,3)
1 14.4(l.0)
22(83.3)
14.40,0)
44.4) using F1 escutcheon
For Ceiling types refer to NFPA 13, 13R or 13D
3.
Technical Data: F1 Res 76 Pendent and Recessed Pendent (SIN R7618)
Thread
Nominal Orifice
Max.
Sprinkler Max.
K
Sprinkler
Size
Inch (mm)
Pressure
Temp. Ratinq Ambient Temp.
Factor
Length
OF
OC OF
OC
Spacing
Flow
psi (bar)
Flow GPM
Inch (mm)
3/4" NPT
(193/4)
17 /32" (13.5)
175(12)
1 55
175
68 100
79 150
38
66
7.6(109)
2.25(57)
For Ceiling types refer to NFPA 13, 13R or 13D
0 Model F1 Res 30, 49, 58 & 76 CCP Pendent'
* Not listed for corrosion resistance.
"B"
Ordinary Temp. Rating
Intermediate Temp. Rating
Inch (mm)
Minimum
Max. Coverage area
Max. Spacing
(1155ORS80C)
(1750F/790c)
Top of Deflector to Ceiling
1 (25.4)
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Spacing
Flow
Pressure
Flow GPM
Pressure
GPM Wimin)
PSI (bar)
(Urnin)
PSI (bar)
MAX. FA E 0 TTING
C
TO FACE OF CEILING
Ft (m)
12 x 12 (3,6 x 3,6)
12(3,6)
21(79.5)
7.6(0,53)
21(79,5)
7.6(0,53)
Smooth Ceilings 41/4 to 8 (108
to 203) using F2 escutcheon.
COVER ADJUSTMENT
T
3 5116" DIA.
14 x .14 (4,3 x 4,3)
14(4,3)
21(79.5)
7.6(0,53)
21(7,9,5)
7.6(0,53)
4 to 8 (100 to 203) using F1
escutcheon.
16 x 16 (4,9 x 4,9)
16(4,9)
21(79.5)
7.6(0,53)
21(79,5)
7.6(0,53)
Beamed Ceilings per NFPA
13D, 13R or 13 installed in
8(2,4)
18 x 18 (5,5 x 5,5)
18(5,5)
21(79.5)
7.6(0,53)
21(79,5)
7.6(0,53)
beams 41/4 to 8 (108 to -203) us-
ing F2 escutcheon, 4 to 8 (100
20 x 20 (6,1 x 6, 1)
20(6,1)
23(87.1)
9.2(0,63)
23(87,1)
9.2(0,63)
to 203) using F1 escutcheon
For Ceiling types refer to NFPA 13, 13R or 13D
0 Model F1 Res 30, 49, 58 & 76 CCP Pendent'
* Not listed for corrosion resistance.
Fig. 3
Note: The F1 Res 76 will use a 1 " x Y4 " reducer.
CCP Cover Plate Data:
. "A" "B" "C"
Cover Adjustment CCP Height Deflector Distance below bottom
Inch (mm) Inch (mm) of beam
Inch (mm)
1/2(12.7) '5/16 (24) 1/2 (13) - 1 (25.4)
5h6 (7.9) '/4 ( 19) 1/2 (13) - 1 (25.4).
Model F1 Res 30, 49, 58 & 76
Recessed Pendent/ FP
FP push-on/thread-off escutcheon
2 518 - DIA. [66.7mml
HOLE IN CEILING
2 5116" DIA.
[58.7mml
C P
1 X 112 REDUCER
CEILING
i L F;-� 1 112 " [38. Imm] MAX.
FACE OF FITTING
TO FACE OF CEILING
112" [IJmml MAX.J " 8
FP ADJUSTMENT
F1 RES 49 PENDENT/FP
Fig. 4
FP Escutcheon Data:
"B"
2 518" [66.7mm] Db4.
2 5116" DIA
Inch (mm)
HOLE IN CEILING
[58.7mm]
Inch (mm)
Max. Recessed 7/16(l 1)
CUP
Min. Recessed , 15h6 (24)
1 (25.4)
I"xI12- REDUCER
CUP
CEILING
I "_'VFMJM'
.7
MAX. FA E 0 TTING
C
TO FACE OF CEILING
DIMENSION
COVER ADJUSTMENT
T
3 5116" DIA.
135FG04E
[84. Imm]
F1 RES 30,
49, 58 &
76 QCP PEND.
Fig. 3
Note: The F1 Res 76 will use a 1 " x Y4 " reducer.
CCP Cover Plate Data:
. "A" "B" "C"
Cover Adjustment CCP Height Deflector Distance below bottom
Inch (mm) Inch (mm) of beam
Inch (mm)
1/2(12.7) '5/16 (24) 1/2 (13) - 1 (25.4)
5h6 (7.9) '/4 ( 19) 1/2 (13) - 1 (25.4).
Model F1 Res 30, 49, 58 & 76
Recessed Pendent/ FP
FP push-on/thread-off escutcheon
2 518 - DIA. [66.7mml
HOLE IN CEILING
2 5116" DIA.
[58.7mml
C P
1 X 112 REDUCER
CEILING
i L F;-� 1 112 " [38. Imm] MAX.
FACE OF FITTING
TO FACE OF CEILING
112" [IJmml MAX.J " 8
FP ADJUSTMENT
F1 RES 49 PENDENT/FP
Fig. 4
FP Escutcheon Data:
Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in
the space above.
10
"B"
FP Position "A"
Deflector Distance below bottom
Inch (mm)
of beam
Inch (mm)
Max. Recessed 7/16(l 1)
1/2(12.7)
Min. Recessed , 15h6 (24)
1 (25.4)
Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in
the space above.
10
Technical Data: F1 Res 30 CCP Pendent and Recessed Pendent/FP (SIN R351 1)
Thread
Nominal
Max.
CCP Assembly Max.
K
Sprinkler
Max. Spacing
Orif ice
Pressure
Temp. ating Ambie Temp.
Flow
Length
Size
Inch (mm)
psi (bar)
Factor
Inch (mm)
OF
OC OF
OC
1/2" NPT
(R 1/2)
21/64" (8.2)
175(12)
135
57 100
38
3.0(43.2)
2.25(57)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/FP (SIN 351-6)
Nominail
Ordinary Temp. Rating
CCP Max.
Minimum
Max. Coverage area
Max. Spacing
(1550F/68*C)
Top of Deflector to Ceiling
Spacing
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
Factor
Length
GPM (Umin).
PSI (bar)
psi (bar)
Rating
12 x 12 (3,6 x 3,6)
Inch (mm)
OF
OC OF
Smooth Ceilings 1/2 to 1 (13 to 25.4) using CCR
57 100 �
12 x 12 (3,6 x 3,6)
12(3,6)
8(30,3)
7.0(0,48)
1/2 to 1 (13 to 25.4) using FP escutcheon.
/16" ( 11
175(12)
135
57 100
1
38
1
Beamed Ceilings per NFPA 13D, 13R or 13 installed in
8(2,4)
Max. Coverage
16 x 16 (4,9 x 4,9)
16(4,9)
14 x 14 (4,3 x 4,3)
14(4,3)
11(37.8)
13.4(0,92)
beams 1/2 to.1 (13 to 25.4) using CCP
Top of Deflector to Ceiling
Spacing
Flow
18 x 18 (5,5 x 5,5)
18(5,5)
1/2 to 1 (13 to 25.4) using FP escutcheon.
13.5(0,93)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/FP (SIN 351-6)
Max. Coverage
Nominail
Ordinary Temp. Rating
CCP Max.
Minimum
area
Thread
Orifice
Max.
Assembly Ambient
K
Sprinkler
Size
Inch
Pressure
Temp. Temp.
Factor
Length
GPM (Umin)
(mm)
psi (bar)
Rating
12 x 12 (3,6 x 3,6)
Inch (mm)
OF
OC OF
OC
57 100 �
38
5.8(83.5)
2.25(57)
1/2" NPT
'/2
/16" ( 11
175(12)
135
57 100
1
38
1
4.9(70.6)
1
2.25(57)
1 1
Max. Coverage
Nominal
Ordinary Temp. Rating
CCP Assembly Max.
Minimum
area
Max. Spacing
(155- 8-C)
Top of Deflector to Ceiling
Spacing
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
OC
GPM (Umin)
PSI (bar)
Inch (mm)
12 x 12 (3,6 x 3,6)
12(3,6)
13(49)
7.0(0,48)
Smooth Ceilings 1/2 to 1 (13 to 25.4) using
57 100 �
38
5.8(83.5)
2.25(57)
14 x 14 (4,3 x 4,3)
14(4,3)
13(49)
7.0(0,48)
CCR
1/2 to 1 (13 to 25.4) using FP escutcheon.
Max. Coverage
16 x 16 (4,9 x 4,9)
16(4,9)
14(53)
8.2(0,56)
Beamed Ceilings per NFPA 13D, 13R or 13
installed in beams 1/2 to 1 (13 to 25.4) using
8(2,4)
(155- 80C)
Top of Deflector to Ceiling
Spacing
Flow
18 x 18 (5,5 x 5,5)
18(5,5)
18(68,1)
13.5(0,93)
CCp.
1/2 to 1 (13 to 25.4) using FP escutcheon.
GPM (Umin)
PSI (bar)
20 x 20 (6,1 x 6, 1)
20(6,1)
20(75,7)
1 16.7(1,14)
7.6(0,53)
Smooth Ceilings 1/2 to 1 (13 to 25.4) using CCP
1/2 to 1 (13 to 25.4) using FP escutcheon.
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP (SIN R3513)
Thread
Nominal
Max.
CCP Assembly Max.
K
Sprinkler
Size
Orifice
Pressure
Temp. atina Ambient Temp.
Factor
Length
OF
OC OF
OC
Inch (mm)
psi (b r)
Inch (mm)
1/2 " NPT
(R 1/2)
'/2" ( 13)
175(12)
135
57 100 �
38
5.8(83.5)
2.25(57)
Max. Coverage
Ordinary Temp. Rating
Minimum
area
Max. Spacing
(155- 80C)
Top of Deflector to Ceiling
Spacing
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
GPM (Umin)
PSI (bar)
12 x 12 (3,6 x 3,6)
12(3,6)
16(61)
7.6(0,53)
Smooth Ceilings 1/2 to 1 (13 to 25.4) using CCP
1/2 to 1 (13 to 25.4) using FP escutcheon.
14 x 14 (4,3 x 4,3)
14(4,3)
16(61)
7.6(0,53)
16 x 16 (4,9 x 4,9)
16(4,9)
16(61)
7.6(0,53)
Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 1/2 to
1 (13 to 25.4) using CCP.
8(2,4)
18 x 18 (5,5 x 5,5)
18(5,5)
19(72)
10.8(0,75)
112 to 1 (13 to 25.4) using FP escutcheon.
1
1 1
20 x 20 (6,.1 x 6, 1)
20(6.1)
22(83,3)
1 14.4(1,0)
For Ceiling types refer to NFPA 13, 13R or 13D
5.
I
Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP (SIN R7618)
Thread
Nominal
Max.
CCP Assembly
Max.
K
Sprinkler
Size
Orifice
Pressure
Temp. Rating
Ambie emp.
Factor
Length
OF
OC
OF
OC
GPM (Umin)
Inch (mm)
psi (bar)
-
Inch (mm)
3/4" NPT
R
( 3/�)
"/32" ( 13.5)
175(12)
135
57
1 00
150
38
66
7.6(109)
2.25(57)
Max. Coverage
Nominal
Ordinary Temp. Rating
Sprinkler Max.
Ambient
Minimum
area
Max. Spacing
(155- 80C)
Top of Deflector to Ceiling
Spacing
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
Inch (mm)
OF
GPM (Umin)
PSI (bar)
2 114 " HOLE DIA. . .
-
12 x 12 (3,6 x 3,6)
12(3,6)
21(79,5)
7.6(0,53)
Smooth Ceilings 1/2 to 1 (13 to 25.4) using CCR
1/2 to 1 (13 to 25.4) *using FP escutcheon.
CEILING TO
14 x 14 (4,3 x 4,3)
14(4,3)
21(79,5)
7.6(0,53)
I" X 112 " REDUCER -7
.
16 x 16 (4,9 x 4,9)
16(4,9)
21(79,5)
7.6(0,53)
Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 1/2
to 1 (13 to 25.4) using CCR
8(2,4)
18 x 18 (5,5 x 5,5)
18(5,5)
22(83,3)
8.4(0,58)
1/2 to 1 (13 to 25.4) using FP escutcheon.
2 27132" DIA.
20 x 20 (6,1 x 6, 1)
20(6,1)
25(94.6)
10.8(0,74)
For Ceiling types refer to NFPA 13, 13R or 13D
Fig. 5
Technical Data: F1 Res 44 HSW & HSW/F2 (SIN R3531)
0 Model F1 Res 44 & 58 HSW
* Model -F1 Res 44 & 58 Recessed HSW/F2
Thread
Nominal
FACE OF FITTING TO
Sprinkler Max.
Ambient
K
Sprinkler
WALL DIMENSION
Orifice
Pressure
Temp. Rating
e p.
-actor
Length
----1
714 MIN.
psi (bar)
Inch (mm)
OF
OC OF
OC
2 114 " HOLE DIA. . .
-
-1/81,
[572mm]
1/2" NPT
(R )
[3.2mm]
CEILING TO
155
175
68 1 00
79 150
38
66
DEFLECTOR
I" X 112 " REDUCER -7
DIMENSION
1 15116 " D
[49.2mm]
2 27132" DIA.
[72.2mml
Y
TURN COLLAR UNTIL
TIGHT AGAINST SPRINKLER
WRENCH BOSS.
112" [13mml
135FG06-D
ADJUSTMENT
F1 RES 58
& 44 HSW/F
Fig. 5
Technical Data: F1 Res 44 HSW & HSW/F2 (SIN R3531)
0 Model F1 Res 44 & 58 HSW
* Model -F1 Res 44 & 58 Recessed HSW/F2
Thread
Nominal
Max.
Sprinkler Max.
Ambient
K
Sprinkler
Size
Orifice
Pressure
Temp. Rating
e p.
-actor
Length
Inch (mm)
psi (bar)
Inch (mm)
OF
OC OF
OC
1/2" NPT
(R )
3/8" (10)
175(12)
155
175
68 1 00
79 150
38
66
4.4(63)
2.45(62)
A
F2 escutcheon,
1/2" (1 3mm) adjustment
Escutcheon, F2, Data:
Face of Fitting
Type
Adjustment
to wall
Inch (mm)
Inch (mm)
F2
L--
'/2 (13)
3/16 - "/16
(4.7-17.4)
I —
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
. Ordinary Temp. Rating
(1 55'F/680C)
Intermediate Temp. Rating
(1750F/79 -C)
Top of Deflector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)
Flow
GPM (Umin)
Pressure
PSI (bar)
Flow
GPM ( in)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6)
12(3,6)
12(45,4)
7.5(0,52)
12(45,4)
7.5(0.52)
4 to 6 (100 to 152):
1/2 (13) recessed
using F2 escutcheon
8(2,4)
14 x 14 (4,3 x 4,3)
14(4,3)
14(53,0)
10.2(0,71)
14(53,0)
10.2(0,71)
16 x 16 (4,9 x 4,9)
16(4,9)
16(60,6)
13.3(0,92)
16(60.6)
13.3(0,92)
16 x 18 (4,9 x 5,5)
16(4,9)
18(68,1)
16.8(0,53)
18(68.1)
16.8(0,53)
18 x 18 (5,5 x 5,5)
18(5,5)
19(72,0)
18.7(1,29)
19(72.0)
18.7(1,29)
16 x 20 (4,9 x 6, 1)
16(4,9)
23(87,1)
27.4(1,89)
23(87.1)
27.4(l.89)
12 x 12 (3,6 x 3,6)
12(3,6)
14(53,0)
10.2(0,71)
14(53.0)
10.2(0,71)
6 to 12 (152 to 305);
1/2 (13) recessed
using F2 escutcheon
14 x 14 (4,3 x 4,3)
14(4,3)
16(60,6)
13.3(0,92)
16(60.6)
13.3(0,92)
16 x 16 (4,9 x 4,9)
16(4,9)
17(64,4)
15.0(1,04)
17(64.4)
15.0(1,04)
16 x 18 (4,9 x 5,S)
16(4,9)
20(75,7)
20.7(1,43)
20(75.7)
20.7(1,43)
16 x 20 (4,9 x 6, 1)
16(4,9)
23(87,1)
27.4(l.89)
23(87.1)
27.4(1,89)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 58 HSW & HSWF2 (SIN R3533)
Escutcheon, F2, Data:
Nominal Max. Sprinkler Max. Sprinkler Face of Fitting
Adjustment
Thread Orifice Pressure Temp. Ratin Ambient K Length Type to wall
9 Inch (mm)
T Factor Inch
Size Inch psi (bar) Inch (mm)
(mm) OF OC OF OC (mm)
- -
3/16 - "/16
1/2" NPT 1/2" (13) 175(12 55 68 1 00 38 5.8(83.5) 2.45(62) F2 1/2(13) (4.7-17.4)
1175
(R 1/2) 79 150 66 1 1
Ordinary Temp. Rating
Intermediate Temp. Rating
Top of Deflector to
Minimum
Max. Coverage area
Max. Spacing
(1 55'F/680C)
(1750F/790c)
Ceiling
Spacing
Flow
Pressure
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
GPM (Umin)
PSI (bar)
GPM in)
PSI (bar)
12 x 12 (3,6 x 3,6)
12(3.6)
16(60,6)
7.6(0,53)
16(60,6)
7.6(0,53)
4 to 6 (100 to 152);
14 x 14 (4,3 x 4,3)
14(4.3)
18(68.2)
9.7(0,69)
18(68,2)
9.7(0,69)
16 x 16 (4,9 x 4,9)
16(4.9)
21(79.5)
13.2(0,91)
21(79,5)
13.2(0,91)
1/2 (13) recessed
using F2 escutcheon
_
16 x 18 (4,9 x 5,5)
16(4.9)
25(94,7)
18.6(1,28)
25(94.7)
18.6(1,28)
8(2,4)
16 x 20 (4,9 x 6, 1)
16(4,9)
29(109.8)
25.0(1,73)
29(109,8)
25.0(1,73)
12 x 12 (3,6 x 3,6)
12(3,6)
22(83,3)
14.4(1,0)
22(83.3)
14.4(1,0)
6 to 12 (152 to 305):
1/2 (13) recessed
14 x 14 (4,3 x 4,3)
14(4,3)
22(83,3)
14.4(l.0)
22(83,3)
14.4(1,0)
16 x 16 (4,9 x 4,9)
16(4,9)
26(98,4)
20.1(1.39)
26(98,4)
20.1(1,39)
using F2 escutcheon
16 x 18 (4,9 x 5,5)
16(4,9)
31(117,4)
28.6(l.97)
31(117.4)
28.6(l.97)
For Ceiling types refer to NFPA 13, 13R or 13D
* ftfi^A�l C1 0- AA QlAff'*
* Not listed for corrosion resistance.
Fig. 6 �
. Terhniral r)ata- F1 Rp-, d14 -qWr 1qIN R'A-9;'Al I
Nominal
Max.
Cover Max.
Minimum
Spacing
Ft (m)
f1041.6too- T.
1
114" (J 1. 75mm] W -i- -
304.80-1
Temp. Ambient
F- Of F46�g
To Wall Di-sion
ON THEN
ITU -RN TO As�=ST UNTIL
Size
Inch (mm)
ncHr AGAINST WALL.
14(53,0)
I' X 112- R�d-e, -7
--T
Recolended
17(64,3)
.15.0(1,1)
W.11 Hol�
2 518"
2 5111
(56.74.
19(71,8)
[66.68-]
Dio.
3 5116"
(84.14mm]
Dia
175(12)
Di..
12(3,6)
TUR COL��g UNTIL
COLM UNRLN
COLM UN
N COLr
4.4(63)
2.45(62)
ncHr A. 11 11111
"",
WRENCH soss.
21IJ2*
14(4,3)
15(56,7)
/4
16 x 16 (4,9 x 4,9)
16(4,9)
'12. r,2.,Om2.O-Mj
M1
16.8(1,16)
16 x 18 K9 x 5,5)
Adj-tm-t
20(75,6)
El RES 44 SWC
Fig. 6 �
. Terhniral r)ata- F1 Rp-, d14 -qWr 1qIN R'A-9;'Al I
Max. Coverage area
Ft x Ft (m x m)
Nominal
Max.
Cover Max.
Minimum
Spacing
Ft (m)
Sprinkler
Thread
Orifice
Pressure
Temp. Ambient
K
Length
Size
Inch (mm)
psi (bar)
14(53,0)
Factor
Inch (mm)
16(4,9)
17(64,3)
.15.0(1,1)
16* x 18 (4,9 x 5,5)
16(4,9)
19(71,8)
18.7(1,13)
16 x 20 (4,9 x 6,1)
1/2" NPT
(R
10
175(12)
12 x 12 (3,6 x 3,6)
12(3,6)
14(52.9)
4.4(63)
2.45(62)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(1 55'F/680C)
Top of Deflector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)
Flow ,
GPM (Umin
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6)
12(3,6)
13(49,2)
8.7(0,60)
4 to 6 (100 to 152);
1/2 (13) recessed
using F2 escutcheon
8(2.4)
14 x 14 (4,3 x 4,3)
14(4,3)
14(53,0)
10.2(0,71)
16 x 16 (4,9 x 4,9)
16(4,9)
17(64,3)
.15.0(1,1)
16* x 18 (4,9 x 5,5)
16(4,9)
19(71,8)
18.7(1,13)
16 x 20 (4,9 x 6,1)
16(4,9)
23(87.1)
27.4(1,89)
12 x 12 (3,6 x 3,6)
12(3,6)
14(52.9)
10.2(0,71)
6 to 12 (152 to 305);
1/2 (13) recessed
using F2 escutcheon
14 x 14 (4,3 x 4,3)
14(4,3)
15(56,7)
11.7 (0;81)
16 x 16 (4,9 x 4,9)
16(4,9)
18(68.1)
16.8(1,16)
16 x 18 K9 x 5,5)
16(4,9)
20(75,6)
20.7(1,43)
For Ceiling types refer to NFPA 13, 13R or 13D
2
Technical Data: F1 Res 58 HSWX (SIN RA3533)
For Ceiling types refer to NFPA 13, 13R or 13D
V/i
Nominal
Max.
Max.
Sprinkler
Minimum
Sprinkler
Sprinkler
(1 550F/680C)
(175'F/790C) -
Thread
Orifice
Pressure
Ambient
Temp. Rating
K
Length
Identification
Ft (m)
Inch (mm)
Size
Inch (mm)
psi (bar)
emp.
Factor
Inch . (mm)
Number (SIN)
OF
Oc OF
-C
30(114)
26.8(1,85)
30(114)
26.8(1,85)
.
DIMENSION
20 x 20 (6,1 x 6, 1)
20(6,1)
Bulb
1/2" NPT
'/2" (13)
175(12)
1 6s.
68' 100
38
5r8 (83 .5)
2.45(62)
RA3533
16 x 22 (4,9 x 7,3)
16(4,9)
33(125)
32.4(2,23)
33(125)
175
79 150
66
TIGHT
WRENCH BOSS.
For Ceiling types refer to NFPA 13, 13R or 13D
V/i
Ordinary Temp. Rating
Intermediate Temp. Rating
Top of Deflector to
Minimum
Max. Coverage area
Max. Spacing
(1 550F/680C)
(175'F/790C) -
Ceiling
Spacing
Flow
Pressure
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
2 114 " HOLE DIA.
GPM (Umin)
PSI (bar)
GPM in)
PSI (bar)
[3-2mm]
18 x 20 (5,5 x 6, 1)
18(5.5)
30(114)
26.8(1,85)
30(114)
26.8(1,85)
4 to 6 (100 to 152);
DIMENSION
20 x 20 (6,1 x 6, 1)
20(6,1)
30(114),
26.8(1,85)
30 (114)
26.8(1,85)
[49.2mm]
2 27132- DIA.
16 x 22 (4,9 x 7,3)
16(4,9)
33(125)
32.4(2,23)
33(125)
32.4(2,23)
112 (13) recessed
TIGHT
WRENCH BOSS.
112" [13mm]
using F2 escutcheon
ADJUSTMENT
F1 RES
58 HSWX
16 x 24 (4,9 x 7,3)
16.(4,9)
38(144)
42.9 (2,96)
38(144)
42.9(2,96)
8(2,4)
14 x 26 (4,3 x 7,9)
14(4,3)
42(160)
52.4(3,75)
42(160)
52.4(3,75)
18 x 20 (5,5 x 6,1)
18(5,5)
35(133)
36.4(2.5)
35(133)
36.4(2.5)
6 to 12 (152 to 305);
1/2 (13) recessed
16 x 22 (4,9 x 6,7)
16(4,9)
38(144)
42.9(2,96)
(144)
42.9(2,96)
-
16 x 24 (4,9 x 7,3)
16(4,9)
42(160)
.52.4 (3,6)
42(160)
52.4(3,6)
using F2 escutcheon
14 x 26 (4,3 x 7,9)
14(4,3)
46(174)
62.9 (4.34)
46(.174)
62.9(4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
Model F1 Res 58 HSWX (Bulb)
V/i
FACE OF FITTING TO
WALL DIMENSION
1 11116" MIN.
9.
2 114 " HOLE DIA.
-118-
'A
[5Z2mm]
[3-2mm]
CEILING TO
DEFLECTOR
1 " x V2 REDUCER
-7
DIMENSION
-
1 15116 OIA.
[49.2mm]
2 27132- DIA.
[72.2mm]
r��r
L
TURN COLLAR UNTIL
AGAINST SRINKLER
TIGHT
WRENCH BOSS.
112" [13mm]
135FG68
ADJUSTMENT
F1 RES
58 HSWX
Model F1 Res 58 HSWX (Bulb)
Model KRes58 HSWX (Linki
Fig.
7
9.
Model KRes58 HSWX (Linki
Technical Data: KRes58 HSWX (RA3593)
For Ceiling types refer to NFPA 13, 13R or 13D
Maintenance
Model F1 Res 30, 49, F1 Res 58, F1 Res 76 and F1 Res
44 Sprinklers should be inspected and the sprinkler sys-
tem maintained in accordance with NFPA 25, 13, 13D,
and 13R. Do not clean sprinkler with soap and water, Am-
monia or any other cleaning fluids. Remove dust by using
a soft brush or gentle vacuuming. Remove any sprinkler
which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated. sprinklers. Prior to installation, sprinklers should
remain in the original cartons and packaging until used.
This will minimize the potential for damage to sprinklers
that could cause improper operation or non -operation.
Model F1 Res 30, 49 & 58 Pendent
Sprinkler Specifications
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential pendent sprin-
klers engineered to provide a minimum design density of
0.05 gpm/ft' over the listed coverage area. Listed flows
as specified by the manufacturer's technical data sheets
are to be used. Residential sprinklers shall be installed
in conformance with the manufacturer's installation guide-
lines and the applicable installation standard. Deflector -
to -ceiling distance listing shall be 1 " to 8" maximum, only
for FlRes 49. Sprinkler frame and deflector shall be of
bronze frame construction having a 1/2" NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with top -loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of (155'F (68'C)]
[175'F (79'C)]. Sprinklers shall have a nominal K -factor
of 3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome -
plated] [White Polyester] [Special finish- specify]. Resi-
dential pendent sprinklers shall be Reliable Model F1 Res
30, 49 & 58, SIN R351 1, R3516 & R3513 (Bulletin 135).
Model F1 Res 49 & 58 Recessed Pendent/171,
Model F1 Res 30, 49 & 58 Recessed Pendent/
F2, Model F1 Res 30,49 & 58 Recessed Pendent/
FP
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential recessed pen-
dent sprinklers engineered to provide a minimum design
density of 0.05.gpM/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer's technical
da ' ta sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer's in-
stallation guidelines and the applicable installation stan-
dard. Deflector -to -ceiling distance listing shall be 1" to 8"
maximum, only for F1 Res 49. Sprinkler frame and deflec-
tor shall be of bronze frame construction having a 1/2" NPT
thread. Water seal assembly shall consist of a Teflon*
coated Belleville spring washer with top -loaded extruded
*DuPont Registered Trademark
10.
Thread
Nominal
Max. -
. Max.
Ambient
K
Sprinkler
Sprinkler
Top of Deflector to
Size
Orifice
Pressure
Temp-
Factor
Length
Identification
Inch (mm)
psi (bar)
Inch (mm)
Inch (mm)
Number (SIN)
F
0C
Link
1/2" NPT
/2" (13)
175(12)
100
38
5.8(83.5)
2.45(62)
RA3593
For Ceiling types refer to NFPA 13, 13R or 13D
Maintenance
Model F1 Res 30, 49, F1 Res 58, F1 Res 76 and F1 Res
44 Sprinklers should be inspected and the sprinkler sys-
tem maintained in accordance with NFPA 25, 13, 13D,
and 13R. Do not clean sprinkler with soap and water, Am-
monia or any other cleaning fluids. Remove dust by using
a soft brush or gentle vacuuming. Remove any sprinkler
which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated. sprinklers. Prior to installation, sprinklers should
remain in the original cartons and packaging until used.
This will minimize the potential for damage to sprinklers
that could cause improper operation or non -operation.
Model F1 Res 30, 49 & 58 Pendent
Sprinkler Specifications
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential pendent sprin-
klers engineered to provide a minimum design density of
0.05 gpm/ft' over the listed coverage area. Listed flows
as specified by the manufacturer's technical data sheets
are to be used. Residential sprinklers shall be installed
in conformance with the manufacturer's installation guide-
lines and the applicable installation standard. Deflector -
to -ceiling distance listing shall be 1 " to 8" maximum, only
for FlRes 49. Sprinkler frame and deflector shall be of
bronze frame construction having a 1/2" NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with top -loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of (155'F (68'C)]
[175'F (79'C)]. Sprinklers shall have a nominal K -factor
of 3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome -
plated] [White Polyester] [Special finish- specify]. Resi-
dential pendent sprinklers shall be Reliable Model F1 Res
30, 49 & 58, SIN R351 1, R3516 & R3513 (Bulletin 135).
Model F1 Res 49 & 58 Recessed Pendent/171,
Model F1 Res 30, 49 & 58 Recessed Pendent/
F2, Model F1 Res 30,49 & 58 Recessed Pendent/
FP
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential recessed pen-
dent sprinklers engineered to provide a minimum design
density of 0.05.gpM/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer's technical
da ' ta sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer's in-
stallation guidelines and the applicable installation stan-
dard. Deflector -to -ceiling distance listing shall be 1" to 8"
maximum, only for F1 Res 49. Sprinkler frame and deflec-
tor shall be of bronze frame construction having a 1/2" NPT
thread. Water seal assembly shall consist of a Teflon*
coated Belleville spring washer with top -loaded extruded
*DuPont Registered Trademark
10.
Ordinary Temp. Rating
Max. Coverage area
Max. Spacing
(165- VC)
Top of Deflector to
Minimum
Ft x Ft (m x m)
Ft (m)
Ceiling
Spacing
Flow
Pressure
GPM (Umin
PSI (bar)
Inch (mm)
Ft (m)
18 x 20 (5,5 x 6, 1)
18(5,5)
29(109)
25(1,72)
4 to 6 (100 to 152):
20 x 20 (6,1 x 6, 1)
20(6,1)
30(114)
26.8(l.85)
16 x 22 (4,9 x 7,3)
16(4,9)
33(125)
32.4(2,23)
1/2 (13) recessed
using F2 escutcheon
16 x 24 (4,9 x 7,3)
16(4.9)
38(144)
42.9(2,96)
8(2,4)
14 x 26 (4,3 x 7,9)
14(4.3)
42(160)
52.4(3,75)
18 x 20 (5,5 x 6, 1)
18(5.5)
35(133)
36.4(2,5)
6 to 12 (152 to 305);
1/2 (13) Recessed
16 x 22 (4,9 x 6,7)
16(4,9)
38(144)
42,9(2,96)
16 x 24 (4,9 x 7,3)
16(4.9)
42(160)
52.4(3,6)
using F2 escutcheon
14 x 26 (4,3 x 7,9)
14(4,3)
46(174)
62.9(4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
Maintenance
Model F1 Res 30, 49, F1 Res 58, F1 Res 76 and F1 Res
44 Sprinklers should be inspected and the sprinkler sys-
tem maintained in accordance with NFPA 25, 13, 13D,
and 13R. Do not clean sprinkler with soap and water, Am-
monia or any other cleaning fluids. Remove dust by using
a soft brush or gentle vacuuming. Remove any sprinkler
which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated. sprinklers. Prior to installation, sprinklers should
remain in the original cartons and packaging until used.
This will minimize the potential for damage to sprinklers
that could cause improper operation or non -operation.
Model F1 Res 30, 49 & 58 Pendent
Sprinkler Specifications
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential pendent sprin-
klers engineered to provide a minimum design density of
0.05 gpm/ft' over the listed coverage area. Listed flows
as specified by the manufacturer's technical data sheets
are to be used. Residential sprinklers shall be installed
in conformance with the manufacturer's installation guide-
lines and the applicable installation standard. Deflector -
to -ceiling distance listing shall be 1 " to 8" maximum, only
for FlRes 49. Sprinkler frame and deflector shall be of
bronze frame construction having a 1/2" NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with top -loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of (155'F (68'C)]
[175'F (79'C)]. Sprinklers shall have a nominal K -factor
of 3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome -
plated] [White Polyester] [Special finish- specify]. Resi-
dential pendent sprinklers shall be Reliable Model F1 Res
30, 49 & 58, SIN R351 1, R3516 & R3513 (Bulletin 135).
Model F1 Res 49 & 58 Recessed Pendent/171,
Model F1 Res 30, 49 & 58 Recessed Pendent/
F2, Model F1 Res 30,49 & 58 Recessed Pendent/
FP
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential recessed pen-
dent sprinklers engineered to provide a minimum design
density of 0.05.gpM/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer's technical
da ' ta sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer's in-
stallation guidelines and the applicable installation stan-
dard. Deflector -to -ceiling distance listing shall be 1" to 8"
maximum, only for F1 Res 49. Sprinkler frame and deflec-
tor shall be of bronze frame construction having a 1/2" NPT
thread. Water seal assembly shall consist of a Teflon*
coated Belleville spring washer with top -loaded extruded
*DuPont Registered Trademark
10.
or cold head cup with 3 mm glass bulb containing no
plastic parts, and having a temperature rating of [155'F
(68-C)] (175-F (79'C)]. Sprinklers shall have a nomi-
nal K -factor of 3.0, 4.9 & 5.8. Standard finish: [Bronze]
[Chrome -plated] [White Polyester] [Special finish- spec-
ify]. Recessed escutcheon assembly shall be a steel,
two-piece escutcheon [with 112" adjustment (Model F2)]
[with 3/4" adjustment (Model F1)] [of push -on and thread
off design with 1/2" adjustment (Model FP)J. Standard fin-
ish shall be [brass][bright chrome] [white painted]. Resi-
dential recessed pendent sprinklers shall be Reliable
[Model F1 Res 30, 49 & 58 Recessed Pendent/Fl] [Model
F1 Res 30, 49 & 58 Recessed Pendent/F21 [Model F1 Res
30, 49 & 58 Recessed Pendent/FP] SIN R351 1, R3516 &
R3513 (Bulletin 135).
Model F1 Res 30, 49 & 58 CCP Pendent
(Concealed)
Sprinklers shall be [cULus Listed] (New York City MEA
Approved (258-93-E)] low flow residential concealed
sprinklers engineered to provide a minimum design den-
sity of 0.05 gpM/ft2 over the listed coverage area. Listed
flows as specified by the manufacturer's technical data
sheets are to be used. Residential sprinklers shall be in-
stalled in conformance with the manufacturer's installa-
tion guidelines and the applicable installation standard.
Sprinkler frame and deflector shall be of bronze frame
construction having a 1/2" NPT thread. Water seal as-
sembly shall consist of a Teflon* coated Belleville spring
washer with top -loaded extruded or cold head cup with 3
mm glass bulb containing no plastic parts, and having a
temperature rating of 1550F (680C). Cover plate assem-
bly shall consist of a brass cover plate and copper alloy
retainer flange. Method of attaching the cover plate to the
sprinkler cup shall be a push -on and thread -off design
allowing a 1/2" cover plate adjustment. Cover plate tem-
perature rating shall be 135'F (57C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate
is installed. Standard cover plate finish: (White] [Custom
Color- specify]. ]. Concealed pendent sprinklers shall
be Reliable Model F1 Res 30, 49 & 58 CCP, SIN R351 1,
R3516 & R3513 (Bulletin 135).
Model F1 Res 44, F1 Res 58 Horizontal
Sidewall, F1 Res 58 HSWX & KRes58 HSWX
Residential Sprinkler Specifications
Sprinklers shall be [cULus Listed] low flow residential
horizontal sidewall sprinklers engineered to provide a
minimum design density of 0.05 gpM/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturer's technical data sheets are to be usecl� Residen-
tial sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard, Sprinkler frame and deflector shall
be of bronze frame construction having a 1/2" NPT thread.
Water seal assembly shall consist of a Teflon* coated Bel -
*DuPont Registered Trademark
leville spring washer with top -loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155"F (68'C)]
[175-F (79-C)]. The solder element (Link) version, the
water seal consist of a cap with a bellville spring washer
and a temperature rating of 165'F (74'C). The recessed
assembly forthe HSWX (Bulb & Link) should be a steel
two pieces escutcheon with 1/2" adjustment (Model F2)
standard finish should be Bright Chrome and white paint-
ed. The F1 Res 58 HSW is also available with low lead
frame. F1 Res 58 HSW and HSWX sprinklers shall have a
nominal K Factor of 5.8 and F1 Res 44 a nominal K factor
of 4.4. Standard finish: [Bronze] [Chrome -plated] [White
Polyester] (Special finish- specify]. Residential horizontal
sidewall sprinklers shall be Reliable Model F1 Res 44, F1
Res 58, F1 Res 58 HSWX & Model KRes58 HSWX, SIN
R3531, RA3533 & RA3593 (Bulletin 135).
Model F1 Res 44 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model F1 Res 44 horizontal side-
wall sprinkler with the following modifications: Replace
"horizontal sidewall sprinkler" with "recessed horizontal
sprinkler." Add: Recessed escutcheon assembly shall be
a steel, two-piece escutcheon with 112" adjustment (Model
F2). Standard finish shall be [brass)[bright chrome] [white
painted] [Special finish- specify]. Residential recessed
horizontal sidewall sprinklers shall be Reliable Model F1
Res 44/F2, SIN R3531 (Bulletin 135).
Model F1 Res 76 Pendent
Sprinklers shall be [cULus Listed] low flow residential
pendent sprinklers engineered to provide a minimum
design density of 0.05 gpM/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential sprin-
klers shall be installed in conformance with the manufac-
turer's installation guidelines and the applicable installa-
tion standard. Sprinkler frame and deflector shall be of
bronze frame construction having a 3/4" NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and having
a temperature rating of [155'F (68'C)] [175'F (79'C)I.
Sprinklers shall have a nominal K -factor of 7.6. Standard
finish: [Bronze) [Chrome -plated] [White Polyester] [Spe-
cial finish- specify]. Residential pendent sprinklers shall
be Reliable Model F1 Res 76, SIN R7618'(Bulletin 135).
Model F1 Res 76 Recessed Pendent/Fl,
Model F1 Res 76 Recessed Pendent/172,
Model F1 Res 76 Recessed Pendent/FP
Sprinklers shall be [cULus Listed) low flow residential
recessed pendent sprinklers engineered to provide a
minimum design density of 0.05 gpM/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturer's technical data sheets are to be used. Residen-
tial sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall
be of bronze frame construction having a 3/4" NPT thread.
-Water. seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and hav-
ing a temperature rating of [ 1 55'F (68'C)] [ 1 750F (79'C)].
Sprinklers shall have a nominal K -factor of 7.6. Standard
finish: [Bronze] [Chrome -plated] [White Polyester] [Spe-
cial finish- specify]. Recessed escutcheon assembly
shall be a steel, two-piece escutcheon [with 1/2" adjust-
ment (Model F2)) [with 3/4" adjustment (Model Fl)) [of
push -on and thread off design with 1/2" adjustment (Mod-
el FP)]. Standard finish shall be [brass)[bright chrome]
[white painted]. Residential recessed pendent sprinklers
shall be Reliable [Model F1 Res 76 Recessed Pendent/
F1] [Model F1 Res 76 Recessed Pendent/F2] (Model F1
Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135).
Model F1 Res 76 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] low flow residential
concealed sprinklers engineered to provide a minimum
design density of 0.05 gpM/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential sprin-
klers shall be installed in conformance with the manufac-
turer's installatiop guidelines and the applicable installa-
tion standard. Sprinkler frame and deflector shall be of
bronze frame construction having a 3/4" NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with -machined or cold head cup with
3 mm glass bulb containing no plastic parts, and having
*DuPont Registered Trademark
a temperature rating of 155'F (68'C). Cover plate assem-
bly shall consist of a brass cover plate and copper alloy
retainer flange. Method of attaching the cover plate to the
sprinkler cup shall be a push -on and thread -off design
allowing a 1/2" cover plate adjustment. Cover plate tem-
perature rating shall be 135'F (57C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate
is installed. Standard cover plate finish: [White] [Custom
Color- specify]. ]. Concealed pendent sprinklers shall be
Reliable Model F1 Res 76 CCP, SIN R7618 (Bulletin 135).
Finishes (1)
(1) Other finishes and colors are available on special order.
Consult factory for details.
(2) cULus listed Corrosion Resistant
Note: Paint or any other coating applied over the factory finish will void
all approvals and warranties.
Ordering Information
Specify:
1 . Sprinkler Model
2. Sprinkler Type
3. Temperature Rating
4. Sprinkler Finish
5. Escutcheon Finish
6. Cover Plate Finish
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by Reliable Automatic Sprinkler Co., Inc. Recycled
(800) 431-1588 Sales Offices Paper
(800) 848-6051 Sales Fax Revision lines indicate updated or new data.
Reliabile (914) 829-2042 Corporate Offices
blesprinkler.corn Internet Address EG. Printed in U.S.A. 07/14 P/N 9999970235
Standard Finishes
Sprinkler
F1, F2, FP
Cover Plates
Escutcheons
Bronze
Brass
White Painted
Chrome Plated
Bright Chrome Plated
Chrome
White and Black
White Painted
Polyester(2) Coated
Special Application Finishes
Sprinkler
F1, F2, FP
Escutcheons
Electroless Nickel PTFE(TeflonO)(2)
Electroless Nickel PTFE (Teflone)
Bright Brass
Bright Brass
Black Plated
Black Plated
Black Paint
Black Paint
Off White
Off White
Chrome Dull
Chrome Dull
(1) Other finishes and colors are available on special order.
Consult factory for details.
(2) cULus listed Corrosion Resistant
Note: Paint or any other coating applied over the factory finish will void
all approvals and warranties.
Ordering Information
Specify:
1 . Sprinkler Model
2. Sprinkler Type
3. Temperature Rating
4. Sprinkler Finish
5. Escutcheon Finish
6. Cover Plate Finish
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by Reliable Automatic Sprinkler Co., Inc. Recycled
(800) 431-1588 Sales Offices Paper
(800) 848-6051 Sales Fax Revision lines indicate updated or new data.
Reliabile (914) 829-2042 Corporate Offices
blesprinkler.corn Internet Address EG. Printed in U.S.A. 07/14 P/N 9999970235
SPE
FlameGuar&
CPVC FIRE SPRINKLER PRODUCTS
FG -2-0312
Complete System of Pipe., Fittings & Solvent Cement.
Corrosion Resistant * Superior Flow * Ease ofInstallation
SpearsO FlameGuarde CPVC Fire Sprinkler Products provide a cost
effective alternative to metal systems with advantages of high corrosion
resistance, improved system hydraulics, ease of installation and quick
assembly with readily available tools. CPVC Fire Sprinkler Systems are
based on proven
products that
have been in continuous service for
over 40 years. SpearsOFlameGuardo
products are approved by ULI, FMI
Global, LPCB and Certi ed by 14SF
International for potable water use.
Check local codes for restrictions and
limitations.
Corrosion Resistant CPVC Material Does Not
Sustain Biological Growth
Unlike metal systems, FlameGuardo CPVC products never
rust, scale or pit and do not sustain biological growth - a cause
of Microbiologically In uenced Corrosion (MIC) which can
destroy metal re sprinkler systems from the inside out.
Superior Flow Characteristics for Lower
Friction Losses
The smooth -wall interior surfaces of FlameGuardo CPVC
systems result in reduced friction loss over metal systems.
The desi ' g n ow characteristics rernain constant throughout
the life of the product because there is no interior corrosion
in the system due to microbiological activity. '
Pressure Rated to 175 psi (1200kpa) @ 1501F
(65-C)
FlameGuardo CPVC Products are produ�ed in combinations
of Schedule 40 and Schedule 80 Fittincy con ourations con-
fon-nin- toASTM F 438 or F 439 standards and FlameGuardo
SDR 1 3.5 CPVC Fire Sprinkler Pipe conforming to ASTM F
442 standards. ULO Rated workinc, pressure is 175 psi
(1200kpa) @ 1507 (65'C) (LPC13 rated to 120'F) (49'C).
L 14, _"Oug'"41
VA
Easy Installation for Lower Costs
Flame'Guardo CPVC system installations significantly
reduce costs over conventional metal piping by virtually
eliminating prefabrication. Systems can be fully installed
on site using solvent cement joining methods.
ULO Listed for U.S. and Canada in
NFPA 13,13R & 13D Systems
FlameGuardo CPVC Fire Sprinkler Products are ULI
listed for U.S. and Canada applications for Light Hazard
.occupancies as de ned inNFPA 13, Residential occupancies
up to and including 4 -stories as defined in NFPA'l 3 R,
and Residential occupancies for one and two family
dwellings and manufactured homes as de ned in NFPA
131). Consult Spears' FlameGuardOCPVC Fire Sprinkler
Products Installation Instructions and NFPA Standards for
additional applications including air plenum, system risers,
concealed, exposed, underground, cornbustable attic,
CY rient and low pressure dry piping installations.
garage, basei
Full Limited Lifetime Warranty
FlameGuardo CPVC Fire Sprinkler Products carry a
limited lifetime warranty against defects in material or
workmanship. Consult SpearsO warranty for additional
details.
Tl�
PROGRESSIVE PRODUCTS FROM
R'
SPEARS' NA10VATION&
TECHWOL OG Y'
Visit our web site: www.spearsmfg.com
o CERr/,
UKAS
.4 WMC.LMF.VT
smms
007
Spears' FlameGuard'. . . The Leader in Innovative
CPVC Fire Sprinkler System Products
Pioneer in Molded -in Metal Insert Head Adapters
SpearsO pioneered the development of the FllameGuardo molded -in-place,
metal thread insert for coimection of sprinkler heads to CPVC re sprinkler
systems, plus Metal FIPT threaded female !adapters for metal -to -plastic
transitions.
Developed the Special Winforced (SR) Head Adapters
SpearsO FllameGuardo continuous improvement program developed the
technology to produce a superior patented plastic threaded tting - the
Special Reinforced (SR) Design. This unique design incorporates a patented
thermoplastic compression process that equalizes stresses generated by
tapered thread joint make-up. All CPVC plastic body and threads provide a.
more uniform construction and improved corrosion resistance.
Now, the Revolutionary TorqueSafe Tm Gasket Sealed
Head Adapter
- Requires NO Thread Sealants - Eliminates Stress
- Prevents Over Tightening - Provides Easy Frame Alignment
SpearsO revolutionary design features a special molded -in-place Brass
Thread Insert tted with an elastomer gasket seal at the base of the threads.
The gasket seal allows a modi ed thread design that eliminates radial stress
and associated problems typical with tapered thread joint make up. The insert is designed to rotate for easy
sprinkler frame alignment without over tightening. Patent Pending.
Full Assortment of Specialty Products & Fitting Configurations
SpearsO FllameGuard' provides the, specialty ttings needed in today's re sprinkler systems. Like the
adjustable drop nipple for ne-tuning to - nished ceiling height, and ringed head adapter for ease of locating
during installation. Plus, SpearsO FllameGuardo line offers a full assortment of CPVC re sprinkler tting
con gurations including Tees, Elbows, Flanges, Couplings, Caps, Male Adapters, Grooved Coupling
Adapters and Unions, sizes 3/4" through 3 "; with new 3/4" and 1 " Repair Couplings.
Complete Size Range of CPVC Pipe
SpearsO FllameGuardo CPVC Fire Sprinkler Pipe is available
in sizes 3/4" to 3". Conforms to ASTM F 442 standard for
Ca USA
SDR. 13.5 CPVC pipe. F!rn I
C:
Spears' Solvent Cements & Thread Sealant
FllameGuar& products should be installed using SpearsO FS -5 One -Step Solvent Cement. For threaded
joints, use Spears' BLUE 75— Thread Sealant that has been tested for compatibility with FllameGuar&
CPVC Fire Sprinkler Products. SpearsO TorqueSafe Tm Gasket Sealed Adapter requires no sealant.
Consult sprinkler head manufacturer prior to use.
Installation Training Available - Contact Spears' Technical Services for Details
FlameGuar& Products must be installed in accordance with Spears"'CPVC Fire Sprinkler Piping Products Installation Instructions, National
Fire Protection Association Standards 13, 13R. 131), and in accordance with local codes. Code requirements and eld conditions may diffier.
It is the responsibility of the installing contractor to insure that the product is suitable to meet these requirements.
SPEARS@ MANUFACTURING COMPANY
CORPORATE OFFICE
15853 Olden St., Sylmar, CA 91342 - PO Box 9203, Sylmar, CA 91392
(818) 364-1611 - www.spearsmfg.com
@Copyright 2012 Speare Manufacturing Company. All Rights Reserved. Printed in the United States of America 03/12.
FG -2-0312
..LAN ALE
I N T E - RNATUONAL
1050. Broadway, \�estville, NJ 08093
800-908 ' -0523 , F. 856--456-9223
www.lansdaleinternational.com
B) ?ONZE GL OBEMA L VE
.Soft Seat
NO.
MATERIAL
1
Wheel Nut
Hot Rolled (SAE 101 OR)
2
Name Plate
Aluminum (A1100)
3
Hand Wheel
Cast Iron pis zZ2202)
4
Packing Nut
Brass (ASTM-UNS B1 6 C36000)
5
Gland Ring
Brass (ASTM-UNS B16 C36000)
6
Gland Packing
Graphite (LK 33 NAFG)
7
Bonnet
Bronze (ASTM-UNS B584 C84400)
8
Lock Nut
Brass (ASTM-UNS B1 6 C36000)
9
Stem
Bronze (ASTM-UNS B584 C84400)
10 Disc
Bronze (ASTM-UNS B584 C84400)
11 Body
Bronze (ASTM-UNS B584 C84400)
D
SIZE
D
H
L
1/499
2.13
2.90"
1.81
%99
2.1399
2.72"
1.85"
1/211
2.1 T9
2.66"
1.89"
%it
2.19"
2.97"
2.209'
V
2.76"
3.41 "
2.54"
1 %19
2.95"
4.33"
2.92"
11/2"
3.3199
5.12"
3.31
2
3.74"
6.0F
3.92'9
PROJECT INFORMATION
APPROVAL STAMP
Project:
El Approved
Address:
El Approved as noted
Contractor:
0 Not approved
Engineer:
Remarks:
Submittal Data: j
Notes 1:
Notes 2:
LAN ALE
.INTERN AT I ON.AL
1050 Broadway, Westville, NJ 08093
P. 800-908-0523 F. 856-456-9223
www.lansdalei n-te.rnational.com
SWING CHECK VALVE
Full Floating Clapper Assembly
Sizes: 1/211 IPS - 211 IPS, Female x Female
Rated Pressure: 175psi
MATERIAL LIST
NO.
MATERIAL
1 Cap
Brass (ASTM-UNS B584 C85710)
2 Disc
Brass (ASTWUNS B584 C85710)
Disc Holder
.3 Seat Packing
Rubber NBR(SAE NO 1052#)
4 Lock Bolt
BraSS(ASTM-UNS B16 C36000)
5 Pin
Brass (ASTM-UNS B1 6 C36000)
6 Body
Brass (ASTM-UNSB584C85710)
SIZE
H
L
1/2
1.44yl�
2.09"
3/41Y
1.5891
2.36"
lip
1.7991
2.6299
1 1/41i
2.0599
3.1919
11/2
2.19"
'3.55"
2.7499
4.2299
H
11
PROJECT INFORMATION
APPROVAL STAMP
Project:
Approved
Address:
Approved as noted
Contractor:
El Not approved
Engineer:
Submittal Data:
Notes 1:
Notes 2:
Remarks:
Poum..
BELLS
The Symbol of Protection PBA -AC & MBA -DC
% UL, ULC, and FM Approved
7
Sizes Available: 6" (1 50mm), 8" (200mm) and 10" (250mm)
Voltages Available: 24VAC
120VAC
12VDC (10.2 to, 15.6) Polarized
24VDC (20.4 to 31.2) Polarized
Service,Use: Fire Alarm'
General Signaling
Burglar A larrn
6v�el 711-IrImp" Environment: Indoor or outdoor use (See Note 1)
lk-1
-400 to 150OF (400 to 66'C)
(Outdoor use requires weatherproof
backbox.)
lap% Termination:' -AC Bells - 4 No. 18 AWG stranded wires
DC Bells -Terminal strip
�inish: -Red powder coating
Optional: Model BBK- I weatherproof backbox
Model BBX- I deep weatherproof backbox
These vibrating type bells are designed for use as re, burglar or general signaling devices. They have low power consumption
and high decibel ratings. The unit mounts on a standard 4" (101mm) square electrical box for indoor use or on a model BBK-I
weatherproof backbo� for outdoor applications. Weatherproof backbox model BBK-1, Stock No. 1500001.
ALL DC BELLS ARE POLARIZED AND HAVE BbIL7TINTRANSIENT PROTECTION:
Sizeinches,
(m M)
Voltage
*Model Number Stock Number
Current'(Max.)
Typical dB at, Minimum dB at
10ft.(3m)(2). ]Oft.(3m)(1)
6(150)
12VDC
MBA126 ;1750070
.12A
85 76
8(200)
12VDC
MBA128 1750080
.1 2A
9.0 77
10(250)
12VDC
MBA1210. 1750060
�. 12A
92 78�
6(150)
24VDC
MBA2W- 1750100
.06A
'87 77
8(200)
24VDC
MBA248 1750110
.06A
91 79
10(250)
24VDC
MBA2410 .1750090
.06A
94 80,
6(150).
24VAC
PBA246 1806024.
17A
91 78
8(200)
24VAC
PBA248 1808024
.1 7A
94 77
10(250)
24VAC
PBA24 10 1810024
17A
94 78
6(156)
120VAC
PBA 1206 l8o6120
.05A
92 83
8(200)
120VAC
PBA 1208 1808120
.05A.
99 84
10(250)
120VAC
PBA 120 10 1810120
.-.05A
99 86
Notes:
1. Minimum dB ratings are calculated frorn integrated sound pressure measurements made at Underwriters Laboratories as speci ed
in UL Standard 464. UL temperature rancre is -30' to 150'F (-')41 to 66'C).
2. Typical dB ratings are calculated from measure�nents rnade with a conventional sound level meter and are indicative of output
levels in an actual installation.
Potter Electric Signal Company 2081 Craig Road, St. Louis, MO, 63 146-4161 * Phone: 800-325-3936/Canada 888-882-1833 * xm%v. potters i gnal. coni
PRINTED IN USA MKT. 98850001 REV V
MFG. #54007 76 - 10/06
PAGE I OF 2
BELLS
Poum
The Symbol of Protection -AC & MBA -6C
PBA
DIMENSIONS
JNCHES (mm)
�'WEATH'ER PROOFBACKBOX
FIG. 1' BELLS FIG. 2
BOX HAS ONE THREADED 1/2" CONDUIT ENTRANCE
(2 0)
5 3/4" 3 3/8" 5-
(2 0) (146) (86)- (127)
6" L,-,
(150)
/8'
J6)
11/16" (41),.
4 M
J68),
DWGH 776-1
DWG# 776-2
FIG. 3 WHUNG (REAR VIEW),
A.C. BELLS
F CP.
A
WIIITE(IN) WHITE(OUT
o
FROM CONTROL'
PANEL OR
PRECEDING BELI!
o
BLA( BLACK(OUT)
To Next
CAUTION:
beviee or' �:'
WI I.EN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS ASS[ ]OWN.
End-U-1-ine
Resistor NOTES:
1: WHEN USING AC BELLS. TEWMII�ATE EACH EXTRA WIRE SEPARATELYAFTER LAST BELL.
2. END -OF -LINE RF�IST611 IS NOT REQUIRED ONAC BELLS.
r DWG# 77�-3
INSTALLATION.*
7
-AFF.
I.. The bell shall be installed in accordance with 14FPA 11-72 'or local AHJ. The top of the deviIe shall be no less than 90"
-and not less than 6" 6elow thb ceiling.
2. 'Re�nov'e the -on-
J. �C6nnect wiring.(see Fig. 3).'
4. Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing down).
5. Reinstall the gong (be sure,that,the gong positioning pin, in the mechanism housing, is in the hole in the gong).
b n
6. Test all.bells for proper operation and observe that they can be heard where iiequired (bells must be h6rd in all areas as
desi -jurisdiction).
gnated by the authority havin
0
3/8"
8f
F -F
o
o
PRINTED IN USA MKT. 98850001 - REV V PAGE 2 OF 2
MFG. 954007 76 - 10/06,
@POTTER
The Symbol of Protection
VSR-SG
VANE TYPE WATERFLOW
FOR CPVC PIPE ALARM SWITCH WITH RETARD
AND GLUE -IN UNION
Specifications subject to change Without notice.
Stock Number: 1144460
Optional: Cover Tamper Switch Kit, stock no. 0090148
Replaceable Components: Retard/Switch Assembly, stock no. 1029030
CAUTION
Waterflow switchesthat are monitoring xvet pipe sprinkler systems shall
not be used as the sole initiating switch to discharge AFFF. deluge.
or chemical suppression systems. Waterflow switches used for &s
application may result in unintended discharges caused by surges,
,trapped air, or short retard times.
General Information
The Model VSR-SG is a vane type waterflow switch for use on xvet
sprinkler Systems using CPVC plastic fittings (manufactured by Tyco,
Nibco. Victaulic, 1pex, and Spears Manufacturing Company) that use I ".
I Y47% 1 1/2", or 2" pipe sizes. It is equipped with a union to accommodate
installation in confined. spaces.
The VSR-SG contains two single pole, double throw, snap action
switches and an adjustable, instantly recycling pneumatic retard. The
switches are actuated when a flow of 10 GPM (38 LPM) or more
occurs downstrearn of the switch. The flo\v condition must exist for a
period of time necessary to overcome the selected retard period.
Enclosure
The VSR-SG switches and retard switch are enclosed in a general
purpose, die-cast housing. The cover is held in place with two tarnper
resistant screws which require a special key for removal. A field
installable cover tamper switch is available as an option which may
be used to indicate unauthorized removal of the cover. See bulletin
number 5401103 for installation instructions of this switch. '
Installation (see Fig. 1, 3, and 5)
These switches may be mounted on horizontal or vertical pipe. On
horizontal pipe thev shall be installed on the top side of the pipe where The vane must not rub the inside of the TEE or bind in any way. The
the), will be accessible. The switch should not be installed within 6" stern should move freely when operated by hand.
(15 crn) of a fitting which changes the direction of the waterflow or
A CAUTION CAUTION
Do not trim the paddle. Failure to follow these instructions may prevent the —Fo Tnot over -tighten the union nut, hand tighten only. Use of a wrench
switch from operatin.- and will void the warranty. mav damage the union nut.
Potter Electric S i anal Company. LLC- St. Louis. MO - CLISt Service: 866-572-3005-TechSUpport: 866-956-0988 /Canada 888-882-1833 -
PRINTED IN USA MFG. 95401205 - REV H PAGE I OF 4
01/12
UL, CUL and CSFM Listed, CE Marked
Service Pressure: Up to 175 PS 1 (12,07 BAR)
Flow Sensitivity Range for Signal: 4- 10 GPM (15-38 LPM) - UL
Maximum Surge: 18 FPS (5.5 m/s)
Contact Ratings: Two sets of SPDT (Form C)
I0.0Arnps at 125/250VAC
2.0Arnpsat30VDC Resistive
10mAmpsmin.at24VDC
Conduit Entrances: Two openings provided for 1/2" conduit.
Individual switch compartments suitable
for dissimilar voltages.
Environmental Specifications:
NEMA4/IP54Rated Enclosure suitable for indoor or
outdoor use with factory installed gasket and die-cast housing
when used with appropriate conduit fitting.
Temp&atUre Range: 40'F - 120'F. (4.5'C - 49'C) - UL
Service Use:
British Standard-
B59251
Automatic Sprinkler
NFPA-13
One or two family dwelling
NFPA-13D
Residential Occupancy Lip to four stories
NFPA-13R
National Fire Alarm Code
NFPA-72
Installation must be perfon-ned by qualified personnel and in
accordance with all national and local codes and ordinances.
Shock hazard. Disconnect power source before servicing. Serious
injury or death could result.
Risk of explosion. Not for use in hazardous locations. Serious
injury or death could result.
within 24" (60 crn) of a valve or drain. The unit has a I" male fitting
for gluing into a CPVC plastic tee.
NOTE: Do not leave cover off for an extended period of time.
Loosen the union nut and separate the I " rnale fitting from the VSR-SG.
Glue the I " male fitting into the TEE following the TEE manufacturer's
instructions for preparation and gluing ofCPVC piping systems. (Note:
The I " male fitting Must bottom out on the stop of the TEE for proper
operation of the VSR-SG. See Fig. 1.) Wait 2 to 4 hours to allow the
glue to dry before attaching the VSR-SG to the I" niale fitting. Select
the proper paddle for the pipe size and type ofTEE used. See Fig. 3
for instructions on how to change paddle. Verify that the o -ring is
properly positioned in its groove. Hand tighten the nut on the union
after orienting the switch in the appropriate direction to detect waterflow
as shown in Fig. 5 & Fig. 7.
VSR-SG
Poinffm VANE TYPE WATERFLOW
The Symbol of . Protection FOR CPVC PIPE ALARM SWITCH WITH RETARD
AND GLUE -IN UNION
Testing
The frequency of inspection and testing for the Model VSR-SG and its associated protective monitoringsystern shall be in accordance with applicable
NFPA Codes and Standards and/or the authority having.jurisdiction (manufacturer recornmends quarterly or more frequently).
A method of testing the VSR-SG must be provided. The valve used for testing shall be easily reached and shall produce a nlininlUrn flow Of 10
GPM to activate the switch. The discharge orifice shall be equal to the smallest sprinkler used in the system.
Advise the person responsible for testing of the fire protection system that this system must be tested in accordance
with the testing instructions.
Fig. I
Glue tile I " male fitting into tile TEE following
the TEE manufacturer's -instructions for
preparation and gluing of CPVC piping
systems. Wait 2 to 4 hours to allow the glue
to dry before attaching the VSR-SG to the I"
male fitting.
(MINIMUM CLEARANCE
REOUIRED FOR i t� E -IN'
I NSTALLATION OR US-`L..r1Q OUT
REMOVAL OF DEVICE) ON STOP
Z,
'NO BUSHINGS. I
INSERTS OR
Z�PIER's DWG. #1062 -1 -
ARE PERMITTED
Fig. 3
C
V�
Q,O)
#1063-3
Important:
11 paddles are furnished with each unit
to accommodate the various sizes and
manu ' fact ' Urers of TEES. The podclles have
raised leuering that show the.pipe size and
the TEE nzanqfacturer the),* are to be used
with. The Proper paddle must be useaf. The
paddle Must be properly attached (see Fig. 3)
and the screw that holds tile paddle must be
se�urely tightened.
Fig. 2
Break out thin section of cover when wiring both switches from one
conduit entrance. a —
fig. 4 Typical Electrical Connections
Notes:
1. The Model VSR-SG has two switches, one can be used to operate a
central station, proprietary or remote signaling unit.. while the other
contact is used to operate a local audible or visual annunciator.
2. For supervised circuits. see "Switch Terminal Connections"
drawing and warning note (Fig. 6). CONNECTOR
I BEL
NEUTRAL FROM BREAKER NEUTRAL FROM BELL 11—
BREAKER
0
LINE FROM BREAKER
EOL (End Of Line Resistor)
NOTE:
When connecting to a LIL Listed
control panel, use the panel's
resistor value for circuit supervision.
PRINTED IN USA MFG. H5401205 - REV H PAGE 2 OF 4
01/12
VSR-SG
VANE TYPE WATERFLOW
@POTTER FOR CPVC PIPE ALARM SWITCH WITH RETARD
The Symbol of Protection AND GLUE -IN UNION
Fig. 5 Retard Adjustment
Thedelaycan beadjUsted by rotatingthe retard
adjustment knob from 0 to the max setting (60-
90 seconds). The time delay should be set at the
minimum required to prevent false alarms.
0111 IONAIXOVERTANIPER SWITC1 I
RE' r 'ARD
ADJUS1 ME, T
KNOB
WE
MOUNTSOA OWON
M.r,��JR
N DJRJ�
BASL Pol C.I.ION
01: "WrERVISM I
1"MAIX 17171NG ON
AI,I,SIZIzS
D%VO4 1205.1A
Floxving %vater activam witc7h in one RUNO1:'iiiE'rLi:
direction onl,-. MAYI)17 ", I I
,/:'*. 0, 2 -
Fig. 7 Mounting Dimensions -Orientation
3.50 i':.) 2.00 in
(99.0.. (50.9
WA
PIPE ' '
PLASTIC PADDLE
1. 1!3inrn
.. PIPE
Fig. 6 Switch Terminal Connections Clamping Plate Terminal
0 T00,
loco 0106
An uninsulated section of a single conductor should not be looped around the
terminal and serve as two separate connections. The wire must be severed,
thereby providing supervision of the connection in the event that the wire
become dislodged from Linder the terminal. Failure to sever the wire may
render the device inoperable risking severe property dania.-e and loss of I ife.
Do not strip wire beyond 3/8" of length or expose an uninsulated conductor
beyond the edge of the tenninal block. When using stranded wire, capture all
strands under the clarnping plate.
ACAUTION
Flow switch must be properly orientated. Side of cover must be
perpendicu I ar with the p i pe. I rnproper orientation cou ld de lay or prevent
notification of Nvaterflow.
Fig. 8
GREEN GROUND
DWGN 1205-15
PRINTED IN USA MFG. 95401205 - REV H PACE 3 OF 4
01/12
VSR-SG
VANE TYPE WATERFLOW
@POTTER FOR CPVC PIPE ALARM SWITCH WITH RETARD
The Symbol of Protection AND GLUE -IN UNION
Maintenance
Inspect the waterflow switch monthly. If leaks are found, replace the waterflow switch. The VSR-SG waterflow switch should provide years of
trouble-free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform
properly, please order replacement retard switch assembly stock # 1029030 (see Fig. 9). There is no maintenance required, only periodic testing
and insDection.
Retard/Switch Assembly Replacement (See Fig. 9)
The Rctard/Switch Assembly is field-replaccabic without draining the system or removing the waterflow switch from the
pipe
I . Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service.
2. Disconnect the power source for local bell (if applicable).
3. Identi fy and remove all wires from the waterflow switch.
4. Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws.
5. Remove the retard assembly by lifting it Straight up over the tripstern.
6. Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base.
7. Re -install the (2) original mounting screws.
8. Reconnect all wires. Perform a flow test and place the system back in service.
Fig. 9
DO NOT REMOVE
(2) RETARD HOUSING
SCREWS
REMOVE (2) ORIGINAL MOUNTING BREAK OUTTHIN SECTION OKOVER
SCREWS HOLDING RETARD/SWITCH WHEN WIRING BOTH SWITCHES
SEMBLY TO BASE FROM ONE CONDUIT ENTRANCE.
RETARD/SWITCH ASSENIBLY
(2) LOCATING PINS
(2) LOCATING Pli
BOSSES IN BASE
BASE
(2) ORIGINAL MOUNTING
SCREWS
G. 1 1�2
Removal of Waterflow Switch
• To prevent accidental water damage, all control valves §hould be shut tight and the system completely drained before waterflow detectors are
rem ' oved or replaced.
• Turn off electrical power to the detector. then disconnect wiring.
• Loosen nuts and seperatC unit from the glued -in fittings
• Gently lift the unit far enough to get your fingers under it. With your fingers, roll the vane so it w*ill fit throu-h the hole while continuin- to lift
the waterflo\v detector.
• Lift detector clear of pipe.
PRINTED IN USA MFG. 95401205 - REV H PAGE 4 OF 4
01/12
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
514
CPVC - STEEL - COPPER
OFFSET HANGER
SIZE - 3/4" thru 3 "pipe.
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized..
LISTING/APPROVAL -
.@us 203 EX 4231, EX 2551
PATENT No. 6,648,278.
FUNCTION - 3/4'%-2" Hanger/restrainer for horizontal CPVC, Copper or Steel pipe.
Listed hanger/restrainer in all 3 mounting positions, i.e. vertical surface and both top and
bottom of horizontal surface. Provides listed vertical/lateral restraint and prevents upward
movement of pipe that supplies a pendent sprinkler below a ceiling.
Size 2 '/2" Hanger for horizontal CPVC pipe. Listed hanger in all 3 mounting positions.
i.e. vertical surface and both top and bottom of horizontal surface.
Size 3" Hanger for horizontal CPVC pipe in two mounting positions, side and bottom.
i.e. vertical surface and bottom of horizontal surface.
Stabilizes vertical piping by providing horizontal restraint.
INSTALLATION - Per NFPA 13, 13R, 13D and CPVC manufacturers instructions.
Space by pipe type. - See Drawings.
Snap over pipe then squeeze strap back allowing pipe to slide freely. Listed
When #905 threads are exposed in wood, install #906 backing nut. 3/4"
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13
WOOD - 3/4" - 3" CPVC pipe - #905 screw- no pre -drill.
3/4" - 2" Copper pipe - #905 screw- no pre -drill.
3/4" - 2" Steel pipe - 1/4"x 1 1/2" lag screw - no pre -drill.
Thru 5/8" gypsum board - 1/4" x 2" lag screw.
STEEL - min. 18 GA. - 3/4" - 3 " CPVC pipe - 1/4" or # 14 Tek Screw.
3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Steel pipe - 1/4" or# 14 Tek Screw.
CONCRETE: Required minimum load each fastener = 5(vvt)+2501bs.
2
FEATURES
* 1 1/2" Offset - loose fit allows pipe to slide.
* 3/4" and I" pipe size made with common center -line.
* Patented design for superior strength.
* Offset edge eliminates abrasion.
* AFCON#905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
AFCON#906 backing nut sold separately.
#905
#906
1.5000-
3.00
7u,
lar
.0— t ---I>
Listed Restraint
3/4" thru 2"
Specific AFCON products arc exclusively designed to be compatible ONLV with other A FCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCLAIMER - AFCONwill NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages ofany kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or arc used.
8/08
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
511
CPVC - COPPER
SIDE MOUNT HANGER
SIZE - 3/4" thru.2" pipe.
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
" (9. 203 - EX 4231, EX 2551
FUNCTION - Hanger on CPVC and Copper pipe.
INSTALLATION - Per NFPA 13, 13R, 13D and CPVC
manufacturers instructions on top or bottom of beam.
Space by pipe type
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13.
in WOOD:
3/4" - 2" CPVC pipe - #905 screw - no pre -drill.
3/4" - 2" Copper pipe - #905 screw - no pre -drill.
in STEEL - min. 18 GA.
3/4" - 2" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Copper pipe - 1/4" or # 14 Tek Screw.
FEATURES
* Offset edge eliminates abrasion.
* Retainer dimples secure hanger to pipe during installation.
* Required AFCON #905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
0
Side Vicw - For
Drawings Below
uI nall
� I
^V�� '
Hanger - Wood Stud
6q1"
Hanger - Metal Stud
Specific AFCONproducts arc exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCLAIMER - AFCONwill NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCONshall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages ofany kind, including but not
limited to loss ofbusiiess or profit, when non-AFCON products have been, or am used.
TA Q:7
P.O. Box 3365 South El Monte, CA 91,733 626.444.0541 Fax 626.444.3887 www. Afcon.org
510
CPVC - STEEL - COPPER
HANGER
SIZE - 3/4" thru 3 11 pipe - see Function.
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
'@" 203 - EX 4231, EX 2551
USTED
FUNCTION - To support horizontal piping 3/4" -2" CPVC, Copper or Steel.
To support horizontal piping 2 1/2" -3" CPVC and Copper.
Hanger in listed mounting positions - Top, Bottom or Side.
Also, provides stability on vertical piping.
INSTALLATION - Per NFPA 13, 13R, 13D and CPVC manufacturers instructions,
mount on top, bottom or side of building element. Space by pipe type.
FASTENERS - UL Listed per NFPA 13
in WOOD:
3/4" - 3" CPVC pipe - #905 screw - no pre -drill.
3/4" - 2" Steel and Copper pipe - 1/4"x 11/2" lag screw - no pre -drill.
in STEEL - min. 18 GA.
3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Steel and Copper pipe - 1/4" or #14 Tek Screw.
FEATURES
• Offset edge eliminates abrasion.
• Retainer dimples secure hanger to pipe during installation.
• Required AFCON #905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
*CAN ALSO BE USED TO REPLACE - #500 Pipe Strap
#520 Tin Strap
510 FaDstener
SIZE L'Tk
314 2.125
1 2.312
1 1/4 3.170
1 IJ2 3.400
2 4.010
21/2 4.320
1 3 1 5.320
Specific A FCON products are exclusively designed to be compatible ONLY with other A FCON products including parts and fasteners, resulting in a I isted sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCLAIMER - AFCONwill NOT warrant against the failure ofits products when used in combination with other products. parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of3ny kind, including but not
limited to loss of business or profit, when non-A FCON products have been, or are used. .
10/11
z
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
515
DOUBLE OFFSET
C.P.V.C. HANGER
SIZE - 3/4" and I" pipe.
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
.(g.. 203 - EX 4231
PATENT - No. 6,702,236
FUNCTION - Hanger/restrainer for horizontal CPVC pipe.
INSTALLATION - Per N.P.F.A 13,13R and 13D.
SPECIAL NOTE: When installing on.CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13.
WOOD: #904 screw - no pre -drill.
STEEL: 1/4" or #14 Tek Screw in min. 20 GA.
FEATURES
Double 1 1/2" offset - loose fit allows pipe to slide.
Center I ine matches AFCON #514.
3/4" and I" pipe size have common center -line.
Offset edge eliminates abrasion.
Required AFCON#904 screw has 3/8" hex head - included.
ORDERING - Part # and pipe size.
Specific AFCON pmducts are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners. resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the follcming warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages ofany kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or am used.
8/07
0
�
1.00
_L
VO
SIZE - 3/4" and I" pipe.
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING/APPROVAL -
.(g.. 203 - EX 4231
PATENT - No. 6,702,236
FUNCTION - Hanger/restrainer for horizontal CPVC pipe.
INSTALLATION - Per N.P.F.A 13,13R and 13D.
SPECIAL NOTE: When installing on.CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13.
WOOD: #904 screw - no pre -drill.
STEEL: 1/4" or #14 Tek Screw in min. 20 GA.
FEATURES
Double 1 1/2" offset - loose fit allows pipe to slide.
Center I ine matches AFCON #514.
3/4" and I" pipe size have common center -line.
Offset edge eliminates abrasion.
Required AFCON#904 screw has 3/8" hex head - included.
ORDERING - Part # and pipe size.
Specific AFCON pmducts are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners. resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the follcming warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages ofany kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or am used.
8/07