B17-2180 041-470-062
t,9VLOTECpT� Q � F Pi"Ja O—.0000Vj �Y y U CLASSIFLU 1 j C-�O LICEN#78OFCALIFO E�o�s D Foohill Fire Protection Inc. 170 Erma Ct. Chico, CA 95928 530-826-3013 Job Name PepplerRes_FP_9-6-17 Building FP -1 Location 5280 Pioneer Trail, Paradise, CA 95969 System 2 Contract 17-26-0093 Data File PepplerRes_FP_9-6-17 Area 2.WXF B17-21 80 FILE/PCI 041-470-062 SEPTEMBER 14, 2017 F/S .FOR B-1 6-2915 Computer Programs by Hydratec Inc. Revision: 50.52.1 Foohill Fire Protection Inc. Page 1 w PepplerRes_FP_9-6-17 Date HYDRAULIC CALCULATIONS for Project name: PepplerRes_FP_9-6-17 Location: 5280 Pioneer Trail, Paradise, CA 95969 Drawing no: FP -1 Date: 09/06/17 Design Remote area number. 2 Remote area location: Studio Occupancy classification: Residential Density: 0.05 - Gpm/SgFt Area of application: 324 - SgFt Coverage per sprinkler.: 324 - Sq Ft Type of sprinklers calculated: 4.9K 165° SSP No. of sprinklers calculated: 1 In -rack demand: N/A - GPM Hose streams: 5 - GPM Total water required (including hose streams): 22.0094 -GPM @ 39.398 - Psi Type of system: Wet Volume of dry or preaction system: N/A - Gal Water supply information Date: N/A Location: N/A ' Source: N/A Name of contractor: Foohill Fire Protection Inc. Address: 170 Erma Ct. / / Chico, CA 95928 Phone number: 530-826-3013 Name of designer: Colby Cram Authority having jurisdiction: Butte County Notes: (Include peaking information or gridded systems here.) Computer Programs by Hydratec Inc. Revision: 50.52.1 Water Supply Curve C Foohill Fire Protection Inc. Page 2 PepplerRes_FP_9-6-17 Date Demand: D1 - Elevation : 3.933 D2 - System Flow : 17.009 D2 --System Pressure 39.398 - Hose ( Demand) : 5 D3 - System Demand : 22.009 Safety Margin 150 140 130 P 120 R 110 E 100 S 90 S 80 U 70 R 60 E 50 D2 40 30 20 10 10 20 30 40 50 60 70 80 90 FLOW (N-1.85) Computer Programs by Hydratec Inc. Revision: 50.52.1 Fittings Used Summary Foohill Fire Protection Inc. PepplerRes_FP_9-6-17 Page 3 Date Fitting Legend Abbrev. Name '/2 % 1 1'/< 1'/z 2 2Yz 3 3'/2 4 5 6 8 10 12 14 16 18 20 24 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N* CPVC 90'EII Harvel -Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O; CPVC Tee - Branch 3 3 5 6 8 10 12 15 0. 0 0 0 0 0 0 0 0 0 0 0 R- CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0. 0 0 0 0 0 0 0 S NFPA 13 Swing Check 0' 0 5 7 9 11 14 16 19 22 27 32 45 55 65 Unit Summary Diameter Units Length Units Flow Units Pressure Units Inches Feet US Gallons per Minute Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with ". The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a " will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Revision: 50.52.1 w Pressure / Flow Summary - STANDARD Foohill Fire Protection Inc. PepplerRes_FP_9-6-17 Page 4 - Date Node Elevation K -Fact Pt Pn Flow Density Area Press No. Actual Actual Req. 1 9.08 4.9 12.05 na 17.01 0.05 324 12.05 2 10.08 12.02 na 3 10.08 12.42 na 4 9.08 16.24 na TOR 9.08 27.33 na BOR -2.0 37.23 na 5.0 TEST 0.0 39.4 na The maximum velocity is 5.73 and it occurs in the pipe between nodes 1 and 2 Computer Programs by Hydratec Inc. Revision: 50.52.1 Final Calculations - Hazen -Williams - 2007 w Foohill Fire Protection Inc. Page 5 PepplerRes_FP_9-6-17 Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv "*"'* Notes Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 1 17.01 1.101 N 7.0 1.000 12.050 K Factor = 4.90 to 150.0 0.0 7.000 -0.433 2 17.01 0.0504 0.0 8.000. 0.403 Vel = 5.73 2 0.0 1.101 0.0 7.990 12.020 to 150.0 0.0 0.0 0.0 3 17.01 0.0504 0.0 7.990 0.403 Vel = 5.73 3 0.0 1.101 4N 28.0 25.090 12.423 to 150.0 20 10.0 42.000 0.433 4 17.01 0.0504 4R 4.0 67.090 3.383 Vel = 5.73 4 0.0 1.101 50 25.0 86.930 16.239 to 150.0 14N 98.0 133.000 0.0 TOR 17.01 0.0504 10R 10.0 219.930 11.089 Vel = 5.73 TOR 0.0 1.101 3N 21.0 11.080 27.328 to 150.0, Fsp 0.0 30.562 7.799 ' Fixed Loss = 3 BOR 17.01 0.0504 S 9.563 41.642 2.100 Vel = 5.73 BOR 5.00 1.394 N 28.0 110.000 37.227 Qa = 5 to 150.0 0.0 8.000 -0.866 TEST 22.01 0.0257 0.0 118.000 3.037 Vel = 4.63 0.0 22.01 39.398 K Factor = 3.51 Computer Programs by Hydratec Inc. Revision: 50.52.1 Foohill Fire Protection Inc. 170 Erma Ct. Chico, CA 95928 530-826-3013 Job Name PepplerRes_FP_9-6-17 Building FP -1 Location 5280 Pioneer Trail, Paradise, CA 95969 System 1 Contract 17-26-0093 Data File PepplerRes_FP_9-6-17 Area 1.WXF B l 7-21 til) FCL,E/PC 1. 041-4711-462 SEPTEMBER 14,20-1.7 F/S FOR Bl <►-2'):l Computer Programs by Hydratec Inc. Revision: 50.52.1 A- �c y �S/j Foohill Fire Protection Inc. Page 1 PepplerRes_FP_9-6-17 Date HYDRAULIC CALCULATIONS for Project name: PepplerRes_FP_9-6-17 Location: 5280 Pioneer Trail, Paradise, CA 95969 Drawing no: FP -1 Date: 09/06/17 Design Remote area number: 1 Remote area location: Studio Occupancy classification: Residential Density: 0.05 - Gpm/SgFt Area of application: 512 - SgFt Coverage per sprinkler: 256 - Sq Ft Type of sprinklers calculated: 4.9K 1650 SSP No. of sprinklers calculated: 2 In -rack demand: N/A - GPM Hose streams: 5 - GPM Total water required (including hose streams): 31.2943 - GPM @ 56.903 -Psi Type of system: Wet Volume of dry or preaction system: N/A - Gal Water supply information Date: N/A r Location: N/A Source: N/A Name of contractor: Foohill Fire Protection Inc. Address: 170 Erma Ct. / / Chico, CA 95928 Phone number. 530-826-3013 Name of designer. Colby Cram Authority having jurisdiction: Butte County Notes: (Include peaking information or gridded systems here.) Computer Programs by Hydratec Inc. Revision: 50.52.1 Water Supply Curve C i All Foohill Fire Protection Inc. Page 2 PepplerRes_FP_9-6-17 Date Demand: D1 - Elevation 3.933 D2-- System Flow : 26.294 D2 - System Pressure 56.903 Hose ( Demand ) : 5 D3 - System Demand : 31.294 Safety Margin 150 140 130 P 120 R 110 E 100 , S 90 S 80 U 70 R 60 E 50 D 40 30 20 10 10 20 30 40 50 60 70 80 90 FLOW ( N ^ 1.85 ) Computer Programs by Hydratec Inc. Revision: 50.52.1 Fittings Used Summary Foohill Fire Protection Inc. Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Page 3 PepplerRes_FP_9-6-17 Date Fitting Legend Abbrev. Name Y2 '/< 1 1% 1'/z 2 2'/2 3 3'/2 4 5 6 8 10 12 14 16 18 20 24 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N- CPVC 90'EII Harvel -Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 01 0 0 O' CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 R' CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0 S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65 Unit Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a " show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a " will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Revision: 50.52.1 "Pressure / Flow Summary - STANDARD Foohill Fire Protection Inc. Page 4 PepplerRes_FP_9-6-17 Date Node Elevation K -Fact Pt Pn Flow Density Area Press No. Actual Actual . Req. 1 9.08 4.9 7.05 na 13.01 0.05 256 7.05 2 10.08 6.86 na 3 10.08 7.11 na 4 9.08 15.11 na TOR 9.08 39.94 na BOR -2.0 52.44 na 5.0 TEST 0.0 56.9 na 5 9.08 4.9 7.35 na 13.28 0.05 256 7.05 The maximum velocity is 8.86 and it occurs in the pipe between nodes 3 and 4 Computer Programs by Hydratec Inc. Revision: 50.52.1 Final Calculations - Hazen-Williams - 2007 Foohill Fire Protection Inc. Page 5 Vt PepplerRes_FP_9-6-17 Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv """ Notes Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 1 13.01 1.101 N 7.0 1.000 7.050 K Factor = 4.90 to 150.0 Fsp 0.0 7.000 -0.433 ` Fixed Loss = 3 BOR 2 13.01 0.0308 9.563 0.0 8.000 0.246 Vel = 4.38 2 0.0 1.101 100.000 0.0 7.990 6.863 150.0 to 0.0 150.0 -0.866 0.0 0.0 0.0 0.0494 3 13.01 0.0307 Vel = 6.58 0.0 7.990 0.245 Vel = 4.38 3 13.28 1.101 4N 28.0 25.090 7.108 to K Factor= 4.15 150.0 20 10.0 42.000 .0.433 1.000 7.350 4 26.29 0.1129 4R 4.0 67.090 7.573 Vel = 8.86 4 0.0 1.101 50 25.0 86.930 15.114 Vel = 4.48 to 150.0 14N 98.0 133.000 0.0 13.28 TOR 26.29 0.1129 10R 10.0 219.930 24.825 Vel = 8.86 TOR 0.0 1.101 3N 21.0 11.080 39.939 to 150.0 Fsp 0.0 30.562 7.799 ` Fixed Loss = 3 BOR 26.29 0.1129 S 9.563 41.642 4.700 Vel = 8.86 BOR 5.00 1.394 N 8.0 100.000 52.438 Qa = 5 to 150.0 0.0 8.000 -0.866 TEST 31.29 0.0494 0.0 108.000 5.331 Vel = 6.58 0.0 31.29 56.903 K Factor= 4.15 5 13.28 1.101 O 5.0 1.000 7.350 K Factor = 4.90 to 150.0 0.0 5.000 -0.433 3 13.28 0.0318 0.0 6.000 0.191 Vel = 4.48 0.0 13.28 7.108 K Factor = 4.98 Computer Programs by Hydratec Inc. Revision: 50.52.1 t �J FED } RUE DESIGN • INSTALLATION • INSPECTION • REPAIR Chico Office: 170 Erma Ct., Chico; CA 95928 • Phone: (530) 826-3013 / Fax: (530) 893-3013 Rocklin Office: 4000 Alvis Ct., Rocklin, CA 95677 • Phone: (916) 663-3582 / Fax: (916) 663-3583 Peppier Residence 5280 Pioneer Trail Paradise, CA 95696 Fire Protection Material Data Submittal 09/07/2017 Bl 7-2180 FILE/K."I 041.470-062 SEPTEMBER 14, 211.17 F/S FOR B1.6-291.5 A Residential Flat. Concealed Sprinkler engineered for a minimum design density of 0.05 gpm/`ft2 with low GPM requirements. Features 1. Very low water flow requirements. 2. Cover plate attachment (Plain or Perforated) with 1/2" (13mm) Total adjustment, 3. Thread-On/Thread-Off or Push-On/Thread Off cover attachment option. 4. Smooth aesthetic ceiling profile. 5. Available in brass, chrome and black plated or painted finishes. Listings & Approval 1. Listed by Underwriters Laboratories, and certified by UL for Canada (cULus) . UL Listing Categories Residential Automatic Sprinklers UL Guide -Number VKKW ' Product Description Model RFC30, RFC43 and RFC49 Concealed Residen- tial Sprinklers are fast response residential fusible solder link automatic sprinklers. Residential sprinklers differ from standard sprinklers primarily in their response time and water distribution patterns. Model RFC30, RFC43 and RFC49 sprinklers discharge water in a hemispherical pattern below the sprinkler de- flector. Residential distribution patterns are higher and generally contain a finer droplet size than standard sprin- kler patterns. The combination of speed of operation and high dis- charge pattern required for residential sprinklers has demonstrated, in fire testing, an ability for controlling residential fires, and thereby providing significant evacu- ation time for occupants. The RFC30, RFC43 and RFC49 Sprinklers provide the best form of fire protection by combining an attractive ap- pearance and '/2" (13mm) of cover adjustment for ease of installation. The small diameter cover plate is easily Bulletin 006 Rev. I Model RFC30 (SIN RA0611) Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Residential Flat Concealed Sprinklers riain Lover riate PWP7 - _ �- __ --- - �.p Perforated Cover Plate and positively attached and blends into the ceiling, con- cealing the most dependable fire protection available, an automatic sprinkler system. The RFC30, RFC43 and RFC49 are LIL Listed Residen- tial Sprinklers to be installed in the residential portions of any occupancy in accordance with NFPA 13, 13R, & 13D. The RFC30, RFC43 and RFC49 can reduce the need for precise cutting of drop nipples. The threaded cover plate assembly can be adjusted without tools to fit ac- curately against the ceiling. The fire protection system need not be shut down to adjust or remove the cover plate assembly. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Application and Installation The RFC30, RFC43 and RFC49, for residential instal- lations, use a 165°F (74°C) fusible solder link in a tun- ing fork style sprinkler frame with a drop-down deflector. This assembly is recessed into the ceiling and concealed by a flat cover plate. The cover plate is attached to the skirt, using 135°F (57°C) ordinary temperature classifica- tion solder. When the ceiling temperature rises, the solder holding the cover plate releases the cover allowing the -deflector to drop into position and exposing the sprinkler inside to ceiling temperature. The subsequent operation of the solder link opens the waterway and causes the de- flector to drop into position to distribute the discharging water in a hemispherical pattern below the sprinkler de- flector. Any adjustment of thread engagement between the cover plate and cup will assure that the drop-down deflector is properly located below the ceiling. The resi- dential distribution pattern contains a finer droplet size than a standard sprinkler, and the pattern produces sig- nificantly higher wall wetting. After a 25/8 inch diameter hole is cut in the ceiling, the sprinkler is to be installed with the Model FC Wrench. When installing a sprinkler, the wrench is first positioned into the sprinkler/cup assembly and around the hexago- nal body of the sprinkler frame. The Wrench must bottom out against the cup in order to ensure proper, safe instal- lation. The sprinkler is then tightened into the pipe fitting. When inserting or removing the wrench from the sprin- kler/cup assembly, care should be taken to prevent dam- age to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS MUST BE INSTALLED ONLY WITH 135°F RATED COV- ERS. Note: A leak tight 1/2" NPT (R1/2) sprinkler joint can be ob- tained with a torque of 8-18 ft -lbs (10,8 - 24,4 N -m). Do not tighten sprinklers over maximum recommended torque. It may cause leakage or impairment of the sprinklers. Cover assemblies provide up to 1/2" (13mm) of adjust- ment. Turn the cover clockwise until the flange is in con- tact with the ceiling. For the push-on/thread-off option, the cover assembly is pushed onto the cup and final ad- justment is made by turning the cover clockwise until the skirt flange makes full contact with the ceiling. Cover re- moval requires turning in the counter -clockwise direction. In. ceilings that have a plenum space above the sprinkler, the plenum space may have neutral or neg- ative pressurization but must not be positively pres- surized. Inspect all sprinklers after installation to en- sure that the gap between the cover plate and ceiling and the 4 slots in the cup are all open and free from any air flow impediment. Model Thread Nominal Sprinkler CCP Assembly Max. Ambient K Max. (SIN) Size Orifice Temp Rating Temp. Rating Temp. Factor Pressure Spacing Ft (m) Inch (mm) Inch (mm) psi (bar) GPM (Umin) PSI (bar) 12 x 12 (3,6 x 3,6) 12(3.6) 9(34,1) 9.0 (0,62) OF °C OF °C OF Oc 14 x 14 (4,3 x 4,3) RFC 30 10 (37,8) 11.0 (0,76) 13 installed in beams 1/2 to 1 (13 to 25.4) (RA0611) '/z (15) 21/64 (8,2) 165 74 135 57 100 38 3.0 (43.2) 175 (12) RFC (RA0612) 1/2" (15) 3/6 (10) 165 74 135 57 . 100 38 4.3(62) 175 (12) RFC 49 RFC 4 6) '/Z (15) '/,6 (11) 165 74 135 57 100 38 4.9 (70.6) T 175 (12) Note: 1 bar = 100 Kpa RFC 30 For Ceiling types refer to NFPA 13, 13R or 13D 2. Ordinary Temp. Rating Max. Coverage Max.. acing (165°Fl74°C) To p of Deflector Installation Minimum area Ft x Ft (m x m) Ft (m) to Ceiling Inch (mm) Type Spacing Ft (m) Flow Pressure GPM (Umin) PSI (bar) 12 x 12 (3,6 x 3,6) 12(3.6) 9(34,1) 9.0 (0,62) Smooth Ceilings 1/2 to 1(13 to 25.4) Beamed Ceilings per NFPA 13D, 13R or Concealed 8(2,4) 14 x 14 (4,3 x 4,3) 14(4.3) 10 (37,8) 11.0 (0,76) 13 installed in beams 1/2 to 1 (13 to 25.4) For Ceiling types refer to NFPA 13, 13R or 13D 2. RFC 43 For Ceiling types refer to NFPA 13, 13R or 13D RFC 49 Max. Coverage Ordinary Temp. Rating Top of Deflector Minimum Max. Coverage Max. Spacing (165°F/74°C) T op of Deflector Installation Minimum area Ft x Ft (m x m) Ft (m) to Ceiling Inch (mm) Type Spacing Ft (m) Flow Pressure GPM (Umin) PSI (bar) 12 x 12 (3,6 x 3,6) 12(3,6) 12(4.5) 7.8 (0,54) Smooth Ceilings 1/2 to 1 (13 to 25.4) 14 x 14 (4,3 x 4,3) 14(4.3) 13 (49) 9.1 (0,63) 16 x 16 (4,9 x 4,9) 16(4,9) 13 (49) 9.1 (0,63) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 1/2 to 1(13 to 25.4) Concealed 8(2,4) 18 x 18 (5,5 x 5,5) 18(5,5) 18 (68) 17.5 (1,21) 20x20(6,1 x6,1) 20(6,1) 21 (79) 23.8(1,64) For Ceiling types refer to NFPA 13, 13R or 13D RFC 49 Max. Coverage Ordinary Temp. Rating Top of Deflector Minimum area Max. Spacing (165' 4-C) to Ceiling Installation Spacing Flow Pressure Ft x Ft (m x m) Ft (m) (mm) Type Ft (m) GPM Umin PSI(bar)Inch 12 x 12 (3,6 x 3,6) 12(3,6) 13 (49) 7.0 (0,48) Smooth Ceilings 1/2 to 1 (13 to 25.4) 14 x 14 (4,3 x 4,3) 14(4,3) .13(49) 7.0 (0,48) 16 x 16 (4,9 x 4,9) 16(4,9) 13 (49) 7.0 (0,48) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 1/2 to 1 (13 to 25.4) Concealed 8(2,4) 18 x 18 (5,5 x 5,5) 18(5,5) 17 (64,3) 12.0 (0,83) 20x20(6,1 x6,1) 20(6,1) 20(75,73) 16.7(1,14) For Ceiling types refer to NFPA 13, 13R or 13D Maintenance Model RFC30, RFC43 and RFC49 Concealed Sprin- klers should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler cover plate as- sembly which has been painted (other than factory ap- plied) or damaged in any way. A stock of spare sprin- klers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper opera- tion or non -operation. Model RFC30, RFC43 and RFC49 Residential Concealed Sprinkler Specification Sprinklers shall be cULus Listed low flow residential con- cealed sprinklers with drop-down deflector and adjust- able flat cover plate engineered for a minimum design density of 0.05 gpm/ft2. Sprinkler frame and deflector shall be of bronze frame construction having a 1/2" NPT thread. Thermal element shall consist of an approved black -painted beryllium -nickel fusible solder link with 0 symmetric lever mechanism, maintaining a Teflon -coated Belleville spring washer and machined brass cap water seal assembly containing no plastic parts. Sprinkler K - factor shall be nominal 3.0 (43.2), 4.3 (62), and 4.9 (70.6) having a 5/16", 3/6" and 7/,6" orifice. Temperature rating shall be Ordinary 165°F (74°C); cover plate temperature rating to be 135°F (57C). Cover plate assembly shall consist of a brass cover plate and copper alloy retainer flange allowing a'/2" cover plate adjustment. Any secure engagement between the cover plate and the cup will assure that the drop-down deflector is properly located below the ceiling. A plastic protective cap shall be provided and factory installed inside the sprinkler cup to protect the drop-down sprinkler deflector from dam- age, Which could occur during construction before the cover plate is installed. Standard cover finish: [Chrome] [White] [Specialty — specify]. Residential concealed sprinklers shall be Reliable Model RFC30, SIN RA0611 (Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006) or Model RFC49, SIN RA0616 (Bulletin 006). Ordering Information Specify: 1. Sprinkler Model 2. Cover Plate Finish 3. Thread -On or Push -On Feature Cover Plate Finishes0) Standard Finishes Chrome White Paint Special Application Finishes(2) Bright Brass Finished Bronze Black Plating Black Paint Off White Satin Chrome (') Other finishes and colors are available on special order. Consult factory for details. Coverplate custom paint is semi -gloss, unless specified otherwise. tet For the perforated style cover - plate, consult factory for avail- ability on these and other cus- tom finishes. 1' x 1/2' REDUCING TEE OR ELBOW `T-- .............. �-- --- -- „l 2 [66.SSmm] 2' [58.42mm]DIA Ill HOLE IN CEILING CUP 0A 300 I 2' [50.8mm] MAX. FACE OF f177ING ' [12.70mm] MAX. ♦ TO FACE OF CEILING COVER ADJUSTMENT DIMENSION ♦������ 1/2' [12.70mm] MIN. TO I' [25.4mm] MAX. CEYUNC DROPPED DEFLECTOR 70 CEILINGCE/UNC FLAT COVER PLATE ASSEMBLY Jj- [84.21mm] DIA ' [4.96mm] COVER PLATE. • 112" [ 12.7mmZ ADJUSTMENT 00ffW,C The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by Reliable Automatic Sprinkler Co., Inc. � Recycled ® (800) 431-1588 Sales Offices Paper iab (800) 848-6051 Sales Fax Revision lines indicate updated or new data. Relle (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 11/14 P/N 9999970261 Bulletin 135 Rev. M Model F1 Residential Sprinklers for Design Density of .05 gpmfft2 Model F1 Res Sprinklers engineered for the lowest flows to meet the minimum design density of .05 gpnV t2 Types: 1. F1 Res 30 Pendent 2. F1 Res 30 Recessed Pendent/F2 3. F1 Res 30 Recessed Pendent/FP 4. F1 Res 49 Pendent 5. F1 Res 49 Recessed Pendent/F1 6. F1 Res 49 Recessed Pendent/FP 7. F1 Res 58 Pendent 8. F1 Res 58 Recessed PendenVF1 9. F1 Res 58 Recessed Pendent/FP 10. F1 Res 76 Pendent 11. F1 Res 76 Recessed Pendent/F1 12. F1 Res 76 Recessed Pendent/FP 13. F1 Res 30 CCP Pendent 14. F1 Res 49 CCP Pendent 15. F1 Res 58 CCP Pendent 16. F1 Res 76 CCP Pendent 17. F1 Res 44 HSW 18. F1 Res 44 Recessed HSW/F2 19. F1 Res 58 HSW 20. F1 Res 58 HSWX 21. KRes58 HSWX 22. F1 Res 58 HSW Recessed HSW/F2 23. F1 Res 44 SWC Listings & Approvals 1. Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus) EN F1 Res 30, 49, 58 & 76 F1 Res 30, 49, 58 & 76 Recessed- Pendent/ F1 Recessed Pendent/ FP 10010 3. 7204y"M F1 Res 30, 49, 58 & 76 CCP Pendent Sprinklers for .10 Density: Refer to Bulletin 176 UL Listing Category Residential Automatic Sprinkler UL Guide Number VKKW Patents US Patent No. 6,516,893 applies to the Model F1 Res 49 & 58 Pendent Sprinklers US Patent No. 7,353,882 applies to Model F1 Res 44 & 58 HSW Sprinklers US Patent No. 7,784,555 applies to Model F1 Res 44 SWC Sprinklers Product Description Model F1 Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are fast response sprinklers combining excellent durability, high sensitiv- ity glass -bulb and low profile decorative design. The F1 Res F1 Res 44 & 58 F1 Res 44 SWC Recessed HSW/F2 Horizontal Sidewall sprinklers (Figs. 5, 6 & 7) are equally attrac- tive when above ceiling piping cannot be used. The 3mm glass -bulb pendent sprinklers permit the efficient use of residential water supplies for sprinkler coverage in residential fire protection design. The low flow F1 Res sprinklers are specially engineered for fast thermal response to meet the sensitive fire protection applica- tion needs of the latest residential market standards (UL 1626 Standard). Upon fire conditions, rising heat causes a sprinkler's heat -sensitive element, glass bulb or link to actuate, releasing the waterway for water flow onto the deflector, evenly distributing the discharged water to control a fire. Technical Data: • Thermal Sensor: Soldered Element (Link) or Nominal 3mm glass -bulb • Sprinkler Frame : Brass Casting • Sprinklers' Pressure Rating : 175 psi Factory Hydrostatically Tested to 500 psi • Thread Size: '/2" NPT (R'/2) • K -Factor: 3.0 (43.2) (Actual) - F1 Res 30 Pendent Sprinkler 4.9 (70.6) (Actual) - F1 Res 49 Pendent Sprinkler 5.8 (83.5) (Actual) - F1 Res 58 Pendent & HSW Sprinkler 7.6 (109)(Actual) - F1 Res 76 Pendent Sprinkler 4.4 (63) (Actual) - F1 Res 44 HSW Sprinkler • Density: Minimum 0.05 gpm/ft2 Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 c CO Cn DD CD Application Model F1 Res Sprinklers are used for Residential Fire Pro- tection according to UL 1626 Standard". For ceiling types: Smooth Flat Horizontal, or beamed, or sloped, in accordance with NFPA 13D, 13R, or 13 2013 editions. Be sure that orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest published standards of The Na- tional Fire Protection Association or the approving authority having jurisdiction. Installation Models F1 Res sprinklers are to be installed as shown. Model F1, F2 and FP Escutcheons, illustrated herewith, are Escutcheon*, F1 or F2, Data: the only recessed escutcheons to be used with Model F1 Res sprinklers. Use of any other recessed escutcheon will void all approvals and warranties. For installing Model F1 Res Pen- dent sprinklers use only the Model D sprinkler Wrench; for installing Models F1 Res Recessed Pendent, CCP & SWC sprinklers use only the Model GFR2 sprinkler wrench; for in- stalling Model F1 Res Recessed HSW sprinklers use only the Model GFR2 Sprinkler Wrench. Use of wrenches other than those specified may damage these sprinklers. Install F1 Res 44 with a ceiling to deflector distance of 4" - 12". Flow arrow on deflector must point away from near wall and "Top" mark- ing must face ceiling. Type Adjustment "A" Face of fitting to ceiling B Deflector Distance below bottom of beam Sprinkler Length Inch mm Inch (mm) Inch (mm) Inch (mm) Inch mm F1 3/4(19.0) Min. Recessed = 15/8 (41.3) 3/8 (9.5) 13/4(44.4) 7.0 (0,48) Smooth Ceilings 1'/4 to 4 (31.7 to 102) using F2 escutcheon. Max. Recessed = N 22.2 11/8(28.6) 1 25.4 F2 Yz (12.7) Min. Recessed = 15/8 (41.3) 3/e (9.5) 13/4(44.4) 14(4,3) 10 (37,8) Max. Recessed =1'/8 28.6 7/e 22.2 1'/a 31.7 . Note: Escutcheons F1 or F2 may be used with Model F1 Res 49, 58 & 76 Recessed Pendent Sprinkler iviooeI Irl KeS 3U, 4% ots & /b F'enae 1J5FG0J • Model F1 Res 30 Recessed Pendent / F2 nt • Modt TURN COLLAR UNTIL 77GHT AGAINST SPRINKLER WRENCH BOSS. J 02 ADJUSTMENT !I fl Kes 49, 5S & 16 mecessea Pent F1 escutcheon, 3/4" (19mm) adjustment 1/9" HOLE DIA. t (57.2-1 — 1 15/16" DIA. (49.2mm) r—� a DIA. 1" X 1/2" REDUCER Fig. 1 'Fig. 2 Technical Data: F1 Res 30 Pendent and Recessed Pendent (SIN R3511) lent / F1 AC£ OF FITTING TO CEILING DIMENSION: 3/8"-1 1/8" (F1 ESCUTCHEON) 3/8"-7/8" (F2 ESCUTCHEON) Thread Size Nominal Orifice Inch mm Max. Pressure si bar S rinkler Temp. Ratincil Max. Ambient Temp. I Actual K Factor Sprinkler Length Inch mm OF °C OF °C '/z" NPT R1/2 2i/64" (8.2) 175 (12) 155 68 100 175 79 38 3.0 (43.2) 2.25 (57) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating 155°F/68°C Intermediate Temp. Rating 175°F/790C Top of Deflector to Ceiling Inch (mm) Minimum Spacing Ft (m) Flow GPM Umin Pressure PSI bar Flow GPM Umin Pressure PSI bar 12 x 12 (3,6 x 3,6) 12(3,6) 8(30,3) 7.0 (0,48) 8(30,3) 7.0 (0,48) Smooth Ceilings 1'/4 to 4 (31.7 to 102) using F2 escutcheon. 14 x 14 (4,3 x 4,3) 14(4,3) 10 (37,8) 11 (0,76) 10 (37,8) 11 (0,76) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 1'/4 to 13/4 31.7 to 44.4 using F2 escutcheon 8(2,4) 16 x 16 (4,9 x 4,9) 16(4.9) 13 (49) 18.8 (1,3) 13 (49) 18.8(l.3) For Ceiling types refer to NFPA 13, 13R or 13D 2. Technical Data: F1 Res 49 Pendent and Recessed Pendent (SIN R3516) Thread Nominal Orifice Max. Sprinkler Max. Actual Sprinkler Size Inch (mm) Pressure emD. atin Ambient TemD. K Length OF °C OF °C Pressure Ft x Ft (m x m) psi bar Factor Inch mm '/z" NPT 7/16" (11) 175 (12) 155 68 100 38 1 4.9 (70.6) 2.25 (57) (R 1/2) 12(3.6) 13 (49) 175 79 150 66 Smooth Ceilings 1'/4 to 4 (31.7 to 102) using F2 escutcheon. For Ceiling types refer to NFPA 13, 13R or 13D Nominal Orifice Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector Minimum Max. Coverage area Max. Spacing 1550F/680C 175°F/799C to Ceiling Spacing Flow Pressure Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) '/2" NPT '/2" (13) GPM (Urn n) PSI bar GPM L/min PSI bar Inch (mm) Ft (m) 12 x 12 (3,6 x 3,6) 12(3.6) 13 (49) 7.0 (0,48) 13 (49) 7.0 (0,48) Smooth Ceilings 1'/4 to 4 (31.7 to 102) using F2 escutcheon. 14 x 14 (4,3 x 4,3) 14(4.3) 13 (49) 7.0 (0,48) 13 (49) 7.0 (0,48) 1 to 4 (25.4 to 102) using F1 escutcheon. Beamed Ceilings per NFPA 13D, 13R or 13 installed in 8(2,4) 16 x 16 (4,9 x 4,9) 16(4,9) 13 (49) 7.0 (0,48) 13 (49) 7.0 (0,48) 18 x 18 (5,5 x 5,5) 18(5,5) 17 (64,3) 12 (0,83) 17 (64,3) 12 (0,83) beams 1'/a to 13/4 (31.7 to 44.4) using F2 escutcheon, 1 20(6,1) 20 x 20 (6,1 x 6, 1) 20(6,1) 20(75,7) 16.7(1,14) 20(75,7) 16,7(1,14) to 13/4(25.4 to 44.4) using F1 escutcheon For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: F1 Res 58 Pendent and Recessed Pendent (SIN R3513) Thread Nominal Orifice Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector Minimum Max. Coverage area Max. Spacing 155°F/ti8°C 175°F/790C to Ceiling Spacing Flow Pressure Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) '/2" NPT '/2" (13) GPM(L/min) PSI bar GPM Wmin PSI bar 5.8 (83.5) 2.25 (57) 12 x 12 (3,6 x 3,6) 12(3,6) 15 (57) 9.4 (0,65) 15 (57) 9.4 (0,65) Smooth Ceilings 4 to 8 (100 to 203) using F2 escutcheon. 14 x 14 (4,3 x 4,3) 14(4,3) 16 (60,5) 10.6 (0,73) 16 (60,5) 10.6 (0,73) 4 to 8 (100 to 203) using F1 escutcheon. 16 x 16 (4,9 x 4,9) 16(4,9) 17 (64,3) 12.0 (0,83) 17 (64,3) 12.0 (0,83) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 8(2,4) 18 x 18 (5,5 x 5,5) 18(5,5) 19 (72) 15.0 (1,0) 19 (72) 15.0 (1,0) 41/4 to 8 (108 to 203) using F2 escutcheon, 4 to 8 (100 to 203) 20 x 20 (6,1 x 6,1) 20(6,1) 22 (83,2) 20.2 (1,4) 22 (83,2) 20.2(l.4) using F1 escutcheon Technical Data: F1 Res 58 Pendent and Recessed Pendent (SIN R3513) Thread Nominal Orifice Max. Sprinkler Max. Actual Sprinkler Size Inch (mm) Pressure emp. Ratin Ambient Tem K Factor Length OF °C OF °C Pressure Ft x Ft (m x m) psi (bar) Inch (mm) Inch mm '/2" NPT '/2" (13) 175 (12) 155 68 100 38 5.8 (83.5) 2.25 (57) (R 1/2) 12(3,6) 16 (61) 175 79 150 66 Smooth Ceilings 1'/4 to 4 (31.7 to 102) using F2 escutcheon. For Ceiling types refer to NFPA 13, 13R or 13D 3. Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector Minimum Max. Coverage area Max. Spacing 155°F/G8°C 175°F/79°C Ceiling Spacing Flow Pressure Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM Umin PSI bar GPM Umin PSI(bar) 12 x 12 (3,6 x 3,6) 12(3,6) 16 (61) 7.6 (0,53) 16 (61) 7.6 (0,53) Smooth Ceilings 1'/4 to 4 (31.7 to 102) using F2 escutcheon. 14 x 14 (4,3 x 4,3) 14(4,3) 16 (61) 7.6 (0,53) 16 (61) 7.6 (0,53) 1 to 4 (25.4 to 102) using F1 escutcheon. 16 x 16 (4,9 x 4,9) 16(4.9) 16 (61) 7.6 (0,53) 16 (61) 7.6 (0,53) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 8(2,4) 18 x 18 (5,5 x 5,5) 18(5,5) 19 (72) 10.8 (0,75) 19 (72) 10.8 (0,75) 11/4 to 13/4 (31.7 to 44.4) using F2 escutcheon, 1 to 13/4 (25.4 to 20 x 20 (6,1 x 6,1) 20(6,1) 22 (83,3) 1 14.4(l.0) 22 (83,3) 14.4 (1,0) 44.4) using F1 escutcheon For Ceiling types refer to NFPA 13, 13R or 13D 3. Technical Data: F1 Res 76 Pendent and Recessed Pendent (SIN R7618) Thread Nominal Orifice Max. Sprinkler Max. K Sprinkler Size Inch (mm) Pressure TemD. Ratina Ambient Temp. Factor Length OF °C °F OC Pressure Ft x Ft (m x m) psi bar Inch (mm) Inch mm 3/4" NPT (RI/4) "/32" (13.5) 175 (12) 155 175 68 100 79 150 38 66 7.6(109) 2.25 (57) For Ceiling types refer to NFPA 13, 13R or 13D • Mi ots & /b "r tier * Not listed for corrosion resistance. dent* Model F1 Res 30, 49, 58 & 76 Rpeascarl Panriant / FP "B„ Ordinary Temp. Rating Intermediate Temp. Rating Minimum Max. Coverage area Max. Spacing 1550F/680C(1750F/790c)Top CUP of Deflector to Ceiling Spacing Spa g Flow. Pressure • Flow GPM Pressure Ft x Ft (m x m) Ft (m) Inch (mm) GPM L/min PSI bar L/min PSI bar MAX. FACE OF FITTING TO FACE OF CEILING Ft 12 x 12 (3,6 x 3,6) 12(3,6) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53) Smooth Ceilings 41/4 to 8 (108 to 203) using F2 escutcheon. B COVER ADJUSTMENT � HEIGHT J 5/16'" DIA. 14 x 14 (4,3 x 4,3) 14(4,3) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53) 4 to 8 (100 to 203) using F1 escutcheon. 16 x 16 (4,9 x 4,9) 16(4,9) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53) Beamed Ceilings per NFPA 13D, 13R or 13 installed in 8(2,4) 18 x 18 (5,5 x 5,5) 18(5,5) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53) beams 4'/4 to 8 (108 to 203) us- ing F2 escutcheon, 4 to 8 (100 20 x 20 (6,1 x 6,1) 20(6,1) 23 (87,1) 9.2 (0,63) 1 23 (87,1) 9.2 (0,63) Ito 203) using F1 escutcheon For Ceiling types refer to NFPA 13, 13R or 13D • Mi ots & /b "r tier * Not listed for corrosion resistance. dent* Model F1 Res 30, 49, 58 & 76 Rpeascarl Panriant / FP rr pusn-arianreaa-orr escuicneon CEILING 112" [ 13mm] MA. FP ADJUSTMENT 2 5/8" DIA. [66.7mm] HOLE IN CEILING — 2 5/16" DIA. [58.7mm] C P 1 ' X 1/2 " REDUCER 1 1 /2 ""[38.1 mm] MAX. FACE OF FITTING TO FACE OF CEILING F1 RES 49 PENDENT/FP rlg. d Fig. 4 Note: The F1 Res 76 will use a 1"x %" reducer. CCP Cover Plate Data: FP Escutcheon Data: Cover Adjustment CCP Height Deflector Distance below bottom Inch (mm) Inch (mm) of beam Inch (mm) 1/2 (12.7) 15/16 24 '/z 13 - 1 25.4 5h6 7.9 3/4 19 Yz 13 - 1 25.4 "B„ 2 5/8'" [66.7mm] DIA. 2 5/16" DIA. HOLE IN CEILING [58.7mm] Inch mm Max. Recessed CUP - `— 75/16 24 1(25.4) i 1'x112- REDUCER CUP I j CEILING 1 1/4'" [31.5mm] MAX. FACE OF FITTING TO FACE OF CEILING LTi �?j DIMENSION I f�,A, � B COVER ADJUSTMENT � HEIGHT J 5/16'" DIA. 135FG04E [84.1 mm] F1 RES 30, 49, 58 & 76 CCP PEND. rr pusn-arianreaa-orr escuicneon CEILING 112" [ 13mm] MA. FP ADJUSTMENT 2 5/8" DIA. [66.7mm] HOLE IN CEILING — 2 5/16" DIA. [58.7mm] C P 1 ' X 1/2 " REDUCER 1 1 /2 ""[38.1 mm] MAX. FACE OF FITTING TO FACE OF CEILING F1 RES 49 PENDENT/FP rlg. d Fig. 4 Note: The F1 Res 76 will use a 1"x %" reducer. CCP Cover Plate Data: FP Escutcheon Data: Cover Adjustment CCP Height Deflector Distance below bottom Inch (mm) Inch (mm) of beam Inch (mm) 1/2 (12.7) 15/16 24 '/z 13 - 1 25.4 5h6 7.9 3/4 19 Yz 13 - 1 25.4 Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in the space above. 4. "B„ FP Position "A" Deflector Distance below bottom Inch (mm) of beam Inch mm Max. Recessed 7/16 11 1/z 12.7 Min. Recessed 75/16 24 1(25.4) Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in the space above. 4. Technical Data: F1 Res 30 CCP Pendent and Recessed PendenVFP (SIN R3511) For Ceiling,types refer to NFPA 13, 13R or 13D Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/FP (SIN 3516) Nominal Max. CCP Assembly Max. Minimum Sprinkler Thread Orifice Pressure TemD. atin Ambient Temp. K Length Size Inch mmpsi bar Factor Inch mm OF °C OF °C '/z" NPT (R 1/2) 21/64" (8.2) 175 (12) 135 57 100 38 3.0 (43.2) 2.25 (57) For Ceiling,types refer to NFPA 13, 13R or 13D Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/FP (SIN 3516) Nominal Ordinary Temp. Rating CCP Max. Minimum Max. Coverage area Max. Spacing 1550F/680C Top of Deflector to Ceiling Spacing Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Temp. Temp. Factor Length GPM Umin PSI(bar)Ft psi (bar) (m) 12 x 12 (3,6 x 3,6) (mm) OF °C OF °C Smooth Ceilings 1/2 to 1 (13 to 25.4) using CCP. 175 (12) 12 x 12 (3,6 x 3,6) 12 (3,6) 8 (30,3) 7.0 (0,48) /z to 1 (13 to 25.4) using FP escutcheon. 175 (12) 135 57 100 38 4.9 (70.6) 2.25 (57) Beamed Ceilings per NFPA 13D, 13R or 13 installed in 8(2.4) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams Yz to 1 (13 to 25.4) using CCP. 8(2.4) 16 x 16 (4,9 x 4,9) 16(4,9) 14 x 14 (4,3 x 4,3) 14(4,3) 11 (37,8) 13.4 (0,92) beams 1/2 to 1 (13 to 25.4) using CCP. 10.8 (0,75) '/z to 1 (13 to 25.4) using FP escutcheon. 18 x 18 (5,5 x 5,5) 18(5,5) '/z to 1 (13 to 25.4) using FP escutcheon. 13.5 (0,93) For Ceiling,types refer to NFPA 13, 13R or 13D Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/FP (SIN 3516) Max. Coverage Nominal Ordinary Temp. Rating CCP Max. Minimum area Thread Orifice Max. Assembly Ambient K Sprinkler Size Inch Pressure Temp. Temp. Factor Length GPM (Umin) (mm) psi (bar) RatingInch 12 x 12 (3,6 x 3,6) (mm) OF °C OF °C Smooth Ceilings Yz to 1 (13 to 25.4) using 175 (12) 135 57 100 38 Yz" NPT (R 1/2) '/,s„ (11) 175 (12) 135 57 100 38 4.9 (70.6) 2.25 (57) Max. Coverage Nominal Ordinary Temp. Rating CCP Assembly Max. . Minimum area Max. Spacing (155- 80C) Top of Deflector to Ceiling Spacing Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) OF GPM (Umin) PSI bar Inch mm 12 x 12 (3,6 x 3,6) 12(3,6) 13 (49) 7.0 (0,48) Smooth Ceilings Yz to 1 (13 to 25.4) using 175 (12) 135 57 100 38 5.8 (83.5) 14 x 14 (4,3 x 4,3) 14(4,3) 13 (49) 7.0 (0,48) CCP. '/z to 1 (13 to 25.4) using FP escutcheon. 16(4,9) 16 (61) 7.6 (0,53) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams Yz to 1 (13 to 25.4) using CCP. 8(2.4) 16 x 16 (4,9 x 4,9) 16(4,9) 14 (53) 8.2 (0,56) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams Yz to 1 (13 to 25.4) using 8(2,4) 19 (72) 10.8 (0,75) '/z to 1 (13 to 25.4) using FP escutcheon. 18 x 18 (5,5 x 5,5) 18(5,5) 18 (68,1) 13.5 (0,93) CCP. Yz to 1 (13 to 25.4) using FP escutcheon. 20 x 20 (6,1 x 6,1) 20(6,1) 20 (75,7) 1 16.7 (1,14) For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP (SIN R3513) Max. Coverage Nominal Max. CCP Assembly Max. . Minimum Sprinkler Thread Orifice Pressure Temo. Ratin . Ambient Tem K Length Size Ft (m) Inch (mm) Factor OF °C OF °C Inch mm psi bar 12(3,6) Inch mm '/z" NPT (R 1/2) '/z (13) 175 (12) 135 57 100 38 5.8 (83.5) 2.25 (57) Max. Coverage Ordinary Temp. Rating Minimum area Max. Spacing 155°F/68°C Top of Deflector to Ceiling Spacing Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM (Umin PSI bar 12 x 12 (3,6 x 3,6) 12(3,6) 16 (61) 7.6 (0,53) Smooth Ceilings Yz to 1 (13 to 25.4) using CCP '/z to 1 (13 to 25.4) using FP escutcheon. 14 x 14 (4,3 x 4,3) 14(4,3) 16 (61) 7.6 (0,53) 16 x 16 (4,9 x 4,9) 16(4,9) 16 (61) 7.6 (0,53) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams Yz to 1 (13 to 25.4) using CCP. 8(2.4) 18 x 18 (5,5 x 5,5) 18(5,5) 19 (72) 10.8 (0,75) '/z to 1 (13 to 25.4) using FP escutcheon. 20 x 20 (6,1 x 6,1) 20(6,1) 22 (83,3) 14.4 (1,0) For Ceiling types refer to NFPA 13, 13R or 13D 5. Technical Data: F1 Res 76. CCP Pendent and Recessed Pendent/FP (SIN R7618) Thread Nominal Max. CCP Assembly Max. K Sprinkler Size Orifice Pressure Temp. Ratin Ambient Tem Factor Length OF °C OF OC GPM L/min Inch (mm) psi bar Inch mm 3/a" NPT R /4 »/az" (13.5) 175 (12) 135 57 0 ::150 38 66 7.6(109) 2.25 (57) Max. Coverage Z Ordinary Temp. Rating 1 1/4" MIN. Minimum area Max. Spacing 155°F/68°C Top of Deflector to Ceiling SFt pacing Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) I 2 27132 -'DIA. { [72.2mm] GPM L/min PSI bar 12 x 12 (3,6 x 3,6) 12(3.6) 21 (79,5) 7.6 (0,53) Smooth Ceilings 1/2 to 1 (13 to 25.4) using CCP. '/z to 1 (13 to 25.4) using FP escutcheon. ADJUSTMENT 14 x 14 (4,3 x 4,3) 14(4,3) 21 (79,5) , 7.6 (0,53) 2.45 (62) 16 x 16 (4,9 x 4,9) 16(4,9) 21 (79,5) 7.6 (0,53) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 1/2 to 1 (13 to 25.4) using CCP. 8(2.4) 18 x 18 (5,5 x 5,5) 18(5,5) 22 (83,3) 8.4 (0,58) '/z to 1 (13 to 25.4) using FP escutcheon. 20 x 20 (6,1 x 6,1) 20(6.1) 25 (94,6) 10.8 (0,74) For Ceiling types refer to NFPA 13, 13R or 13D FACE OF FITTING TO WALL DIMENSION 2 1/4" HOLE DIA. [57.2mm] 1" X 1/2" REDUCER —7 7 15/16' DIA. (49.2mm] ' �i"--- i mo � i TURN COLLAR UNTIL J TIGHT AGAINST SPRINKLER WRENCH BOSS. IJ5FG06—D F1 RES 58 & 44 HSW/F2 Fig. 5 Technical Data: F1 Res 44 HSW & HSW/F2 (SIN R3531) • Model F1 Res 44 & 58 HSW • Model F1 Res 44 & 58 Recessed HSW/F2 Thread Z Max. 1 1/4" MIN. K [31.8m,ri] Size 1/8 ,A„ [3.2mm] CEILING TO Pressure DEFLECTOR Factor DIMENSION i �-T psi (bar) I 2 27132 -'DIA. { [72.2mm] °C OF °C —; r— 1/2" [13mm] 3/8" (10) ADJUSTMENT F1 RES 58 & 44 HSW/F2 Fig. 5 Technical Data: F1 Res 44 HSW & HSW/F2 (SIN R3531) • Model F1 Res 44 & 58 HSW • Model F1 Res 44 & 58 Recessed HSW/F2 Thread Nominal Max. Sprinkler Ambient K Sprinkler Size Orifice Pressure Temp. Rating Tem . Factor Length Inch (mm) psi (bar) Inch (mm) OF °C OF °C '/z" NPT R''/z 3/8" (10) 175 (12) 155 175 68 100 79 150 38 66 4.4 (63) 2.45 (62) N F2 escutcheon, 1/2" (13mm) adjustment Escutcheon, F2, Data: Face of Type Adjustment to wall Inch (mm) Inch (mm) F2 1/2(13) 3/16 -11/16 (4.7 - 17.4) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating 155°F/680C) Intermediate Temp. Rating (175'F/790c)Top of Deflector to Ceiling Inch (mm) Minimum Spacing Ft (m) Flow GPM Umin Pressure PSI bar Flow GPM Umin) Pressure PSI bar 12 x 12 (3,6 x 3,6) 12(3,6) 12 (45,4) 7.5 (0,52) 12 (45,4) 7.5 (0,52) 4 to 6 (100 to 152); '/z (13) recessed using F2 escutcheon 8(2,4) 14 x 14 (4,3 x 4,3) 14(4,3) 14 (53,0) 10.2 (0,71) 14 (53,0) 10.2 (0,71) 16 x 16 (4,9 x 4,9) 16(4.9) 16 (60,6) 13.3 (0,92) 16 (60,6) 13.3 (0,92) 16 x 18 (4,9 x 5,5) 16(4.9) 18 (68,1) . 16.8 (0,53) 18 (68,1) 16.8 (0,53) 18 x 18 (5,5 x 5,5) 18(5.5) 19 (72,0) 18.7 (1,29) 19 (72,0) 18.7 (1,29) 16 x 20 (4,9 x 6,1) 16(4,9) 23 (87,1) 27.4 (1,89) 23 (87,1) 27.4 (1,89) 12 x 12 (3,6 x 3,6) 12(3,6) 14 (53,0) 10.2 (0,71) . 14 (53,0) 10.2 (0,71) 6 to 12 (152 to 305); Yz (13) recessed using F2 escutcheon 14 x 14 (4,3 x 4,3) 14(4,3) 16 (60,6) 13.3 (0,92) 16 (60,6) 13.3 (0,92) 16 x 16 (4,9 x 4,9) 16(4,9) 17 (64,4) 15.0 (1,04) 17 (64,4) 15.0 (1,04) 16 x 18 (4,9 x 5,5) 16(4,9) 20 (75,7) 20.7 (1,43) 20 (75,7) 20.7 (1,43) 16 x 20 (4,9 x 6,1) 16(4,9) 23 (87,1) 27.4 (1,89) 23 (87,1) 27.4 (1,89) For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: F1 Res 58 HSW & HSW F2 SIN R3533 Escutcheon, F2, Data: Nominal Max. Sprinkler Face of Fitting Thread Orifice Type Pressure Temp. Rating Ambient K Length T to wall Inch mm Size Inch Tem Factor Inch ( ) Inch mm Psi (bar) ( ) mm OF °C OF °C mm ''/z" NPT 155 68 100 38 F2 1/2(13) 3/16-11/16. R'/z /z (13) 175 (12) 5.8 (83.5) 2.45 (62) (4.77 - 17.4) 175 79 150 66 Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector to Minimum Max. Coverage area Max. Spacing 155°F/68°C 175°F/79°C Ft x Ft (m x m) Ft (m) Ceiling Spacing Flow Pressure Flow Pressure GPM (Umin) PSI bar GPM Umin) PSI (bar) Inch (mm) Ft (m) 12 x 12 (3,6 x 3,6) 12(3,6) 16 (60,6) 7.6 (0,53) 16 (60,6) 7.6 (0,53) 4 to 6 (100 to 152); 14 x 14 (4,3 x 4,3) 14(4,3) 18 (68,2) 9.7 (0,69) 18 (68,2) 9.7 (0,69) 16 x 16 (4,9 x 4,9) 16(4,9) 21 (79,5) 13.2 (0,91) 21 (79,5) 13.2 (0,91) '/z (13) recessed using F2 escutcheon 16 x 18 (4,9 x 5,5) 16(4.9) 25 (94,7) 18.6 (1,28) 25 (94,7) 18.6(l.28) 8(2,4) 16 x 20 (4,9 x 6,1) 16(4.9) 29 (109,8) 25.0 (1,73) 29 (109,8) 25.0 (1,73) 12 x 12 (3,6 x 3,6) 12(3,6) 22 (83,3) 14.4(l.0) 22 (83,3) 14.4(l.0) 6 to 12 (152 to 305); '/z (13) recessed 14 x 14 (4,3 x 4,3) 14(4,3) 22 (83,3) 14.4 (1,0) 22 (83,3) 14.4(l.0) 16 x 16 (4,9 x 4,9) 16(4,9) 26 (98,4) 20.1 (1,39) 26 (98,4) 20.1 (1,39) using F2 escutcheon 16 x 18 (4,9 x 5,5) 16(4,9) 31 (117,4) 28.6 (1,97) 31 (117,4) 28.6 (1,97) For Ceiling types refer to NFPA 13, 13R or 13D • Model F1 Res 44 SWC"' " Not listed for corrosion resistance. Fig. 6 Technical Data- F1 nes 44 SWC (SIN R35311 Nominal Max. Cover Max. Minimum Spacing Ft (m) Sprinkler Thread Orifice Pressure Temp. Ambient K 4' to 12' Size Inch (mm) psi (bar) [I01.60mm io 1 1/4' [31.75mm] At. 16(4,9) J04.80mm] 15.0 (1,1) Foce Of Fitting To Wall Dimension 16(4,9) PUSH ON COVER, THEN TURN TO ADJUST UNTIL 18.7 (1,13) 16 x 20 (4,9 x 6,1) 1/2" NPT TIGHT AGAINST WALL. 175 (12) 1' X 1/2• Reducer 1 i- Recommended 2.45 (62) Wall Hole 2 5/i6' �m--- _ i- 2 5/8' (58.74mmJ -- --- —F•-- 3 5/16' [66.68mmJ Di.. i - 16(4,9) , [84.14m.1 Die. Dia. TURN COLLAR UNTIL r' 1 OGHT AGAINST SPRINKLER 1 2I/J2' WRENCH DOSS. [42.07mmJ [12. Adjustmeentnt F1 RES 44 SWC Fig. 6 Technical Data- F1 nes 44 SWC (SIN R35311 Max. Coverage area Ft x Ft (m x m) Nominal Max. Cover Max. Minimum Spacing Ft (m) Sprinkler Thread Orifice Pressure Temp. Ambient K Length Size Inch (mm) psi (bar) Ratin Tem Factor Inch (mm) 16(4,9) 17 (64,3) 15.0 (1,1) 16 x 18 (4,9 x 5,5) 16(4,9) 19 (71,8) 18.7 (1,13) 16 x 20 (4,9 x 6,1) 1/2" NPT 3/8" (10) 175 (12) 135 57 100 38 4.4(63) 2.45 (62) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (1 55-17/68-C) Top of Deflector to Ceiling (mm) Minimum Spacing Ft (m) Flow GPM L/min Pressure PSI(bar)Inch 12 x 12 (3,6 x 3,6) 12(3,6) 13 (49,2) 8.7 (0,60) 4 to 6 (100 to 152); /2 (13) recessed using F2 escutcheon 8(2.4) 14 x 14(4,3 x 4,3) 14(4,3) 14 (53,0) 10.2 (0,71) 16 x 16 (4,9 x 4,9) 16(4,9) 17 (64,3) 15.0 (1,1) 16 x 18 (4,9 x 5,5) 16(4,9) 19 (71,8) 18.7 (1,13) 16 x 20 (4,9 x 6,1) 16(4.9) 23(87,1)- 27.4 (1,89) 12 x 12 (3,6 x 3,6) 12(3.6) 14 (52,9) 10.2 (0,71) 6 to 12 (152 to 305); /2 (13) recessed using F2 escutcheon 14 x 14 (4,3 x 4,3) 14(4.3) 15 (56,7) 11.7 (0,81) 16 x 16 (4,9 x 4,9) 16(4.9) 18 (68,1) 16.8 (1,16) 16 x 18 (4,9 x 5,5) 16(4,9) 20 (75,6) 20.7 (1,43) For Ceiling types refer to NFPA 13, 13R or 13D 3 Technical Data: F1 Res 58 HSWX (SIN RA3533) Max. Coverage area Ft x Ft (m x m) Thread Nominal Max. Sprinkler Max. Ambient K'. ', Sprinkler Sprinkler Flow GPM L/min Size Orifice Pressure Temp. Rating Tem Factor Length Identification 4 to 6 (100 to 152); '/z (13) recessed using F2 escutcheon 8(2.4) Inch (mm) psi (bar) 30(114) Inch (mm) Number (SIN) 0F C 0 0F aC 16(4,9) 33 (125) 32.4 (2,23) 33 (125) 32.4 (2,23) 16 x 24 (4,9 x 7,3) 16(4,9) Bulb /z" NPT 1/2" (13) 175 (12) 155 68 100 38 5.8 (83.5) 2.45 (62) RA3533 52.4 (3,75) R /z 18(5,5) 35 (133) 175 79 150 66 36.4 (2,5) 6 to 12 (152 to 305); 1/2 (13) recessed using F2 escutcheon Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating 1550F/680C Intermediate Temp. Rating 1750F/790C Top of Deflector to Ceiling Inch (mm) Minimum Spacing Ft (m) Flow GPM L/min Pressure PSI bar Flow GPM L/min Pressure PSI (bar) 18 x 20 (5,5 x 6, 1) 18(5,5) 30(114) 26.8 (1,85). 30(114)- 26.8(1,85) 4 to 6 (100 to 152); '/z (13) recessed using F2 escutcheon 8(2.4) 20x20(6,1 x6,1) 20(6,1) 30(114) 26.8(1,85) 30(11 4) 26.8(1,85) 16 x 22 (4,9 x 7,3) 16(4,9) 33 (125) 32.4 (2,23) 33 (125) 32.4 (2,23) 16 x 24 (4,9 x 7,3) 16(4,9) 38 (144) 42.9 (2,96) 38 (144) 42.9 (2,96) 14 x 26 (4,3 x 7,9) 14(4.3) 42 (160) 52.4 (3,75) .42(160) 52.4 (3,75) 18 x 20 (5,5 x 6,1) 18(5,5) 35 (133) 36.4 (2,5) 35 (133) 36.4 (2,5) 6 to 12 (152 to 305); 1/2 (13) recessed using F2 escutcheon 16 x 22 (4,9 x 6,7) 16(4,9) 38 (144) 42.9 (2,96) 38 (144) 42.9 (2,96) 16 x 24 (4,9 x 7,3) 16(4,9) 42 (160) 52.4 (3,6) 42 (160) 52.4 (3,6) 14 x 26 (4,3 x 7,9) 14 (413) 46 (174) 62.9 (4,34) 46 (174) 62.9 (4,34) For Ceiling types refer to NFPA 13, 13R or 13D • Model KRes58 HSWX (Link) Fig. 7 } Technical Data: KRes58 HSWX.(RA3593) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Nominal Max. Max. Flow GPM Umin Sprinkler Sprinkler 18(5,5) Thread Orifice Pressure Ambient K Length Identification 26.8(1,85) Size Inch (mm) psi (bar) 32.4 (2,23) Factor Inch (mm) Number (SIN) oTemp- C 14(4,3) 42 (160) 52.4 (3,75) 18 x 20 (5,5 x 6,1) 18(5.5) 35 (133) 36.4 (2,5) Link 1/2" NPT '/2 (13) 175 (12) 100 38 5.8 (83.5) 2.45 (62) RA3593 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (1165- VC) Top of Deflector to Ceiling (mm) Minimum Spacing Ft (m) Flow GPM Umin Pressure PSI(bar)Inch 18 x 20 (5,5 x 6,1) 18(5,5) 29 (109) 25 (1,72) 4 to 6 (100 to 152); 1/2 (13) recessed using F2 escutcheon 8(2,4) 20x20(6,1 x6,1) 20(6,1) 30(114) 26.8(1,85) 16 x 22 (4,9 x 7,3) 16(4,9) 33 (125) 32.4 (2,23) 16 x 24 (4,9 x 7,3) 16(4,9) 38 (144) 42.9 (2,96) 14 x 26 (4,3 x 7,9) 14(4,3) 42 (160) 52.4 (3,75) 18 x 20 (5,5 x 6,1) 18(5.5) 35 (133) 36.4 (2,5) 6 to 12 (152 to 305); '/2 (13) Recessed using F2 escutcheon 16 x 22 (4,9 x 6,7) 16(4.9) 38 (144) 42.9 (2,96) 16 x 24 (4,9 x 7,3) 16(4,9) 42 (160) 52.4 (3,6) 14 x 26 (4,3 x 7,9) 14(4,3) 46 (174) For Ceiling types refer to NFPA 13, 13R or 13D Maintenance Model F1 Res 30, 49, F1 Res 58, F1 Res 76 and F1 Res 44 Sprinklers should be inspected and the sprinkler sys- tem maintained in accordance with NFPA 25, 13, 13D, and 13R. Do not clean sprinkler with soap and water, Am- monia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should remain in the original cartons and packaging until used. This will minimize the potential for damage to sprinklers that could cause improper operation or non -operation. Model F1 Res 30, 49 & 58 Pendent Sprinkler Specifications Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential pendent.sprin- klers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer's technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer's installation guide- lines and the applicable installation standard. Deflector - to -ceiling distance listing shall be 1" to 8" maximum, only for F1Res 49. Sprinkler frame and deflector shall be of bronze frame construction having a 1/2" NPT thread. Wa- 'DuPont Registered Trademark 10 ter seal assembly shall consist of a Teflon* coated Bel- leville spring washer with top -loaded extruded or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a nominal K -factor of 3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome - plated] [White Polyester] [Special finish- specify]. Resi- dential pendent sprinklers shall be Reliable Model F1 Res 30, 49 & 58, SIN R3511, R3516 & R3513 (Bulletin 135). Model F1 Res 49 & 58 Recessed Pendent/171, Model 171 Res 30, 49 & 58 Recessed Pendent/ F2, Model F1 Res 30,49 & 58 Recessed Pendent/ FP Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential recessed pen- dent sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer's technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer's in- stallation guidelines and the applicable installation stan- dard. Deflector -to -ceiling distance listing shall be 1" to 8" maximum, only for F1 Res 49. Sprinkler frame and deflec- tor shall be of bronze frame construction having a'/2" NPT thread. Water seal assembly shall consist of a Teflon* coated Belleville spring washer with top -loaded extruded or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a nomi- nal K -factor of 3.0, 4.9 & 5.8. Standard finish: [Bronze] [Chrome -plated] [White Polyester] [Special finish- spec- ify]. Recessed escutcheon assembly shall be a steel, two-piece escutcheon [with 1/2" adjustment (Model F2)] [with 3/a" adjustment (Model F1)] [of push -on and thread off design with 1/2" adjustment (Model FP)]. Standard fin- ish shall be [brass][bright chrome] [white painted]. Resi- dential recessed pendent sprinklers shall be Reliable [Model F1 Res 30, 49& 58 Recessed Pendent/F1] [Model F1 Res 30, 49 & 58 Recessed Pendent/F2] [Model F1 Res 30, 49 & 58 Recessed Pendent/FP] SIN R3511, R3516 & R3513 (Bulletin 135). Model F1 Res 30, 49 & 58 CCP Pendent (Concealed) Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential concealed sprinklers engineered to provide a minimum design den- sity of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer's technical data sheets are to be used. Residential sprinklers shall be in- stalled in conformance with the manufacturer's installa- tion guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a 1/2" NPT thread. Water seal as- sembly shall consist of a Teflon* coated Belleville spring washer with top -loaded extruded or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of 155°F (68°C). Cover plate assem- bly shall consist of a brass cover plate and copper alloy retainer flange. Method of attaching the cover plate to the sprinkler cup shall be a push -on and thread -off design allowing a '/2" cover plate adjustment. Cover plate tem- perature rating shall be 135°F (57'C). A plastic protec- tive cap shall be provided and factory installed inside the sprinkler cup to protect the sprinkler from damage, which could occur during construction before the cover plate is installed. Standard cover plate finish: [White] [Custom Color- specify]. ]. Concealed pendent sprinklers shall be Reliable Model F1 Res 30, 49 & 58 CCP, SIN R3511, R3516 & R3513 (Bulletin 135). Model F1 Res 44, .F1 Res 58 Horizontal Sidewall, F1 Res 58 HSWX & KRes58 HSWX Residential Sprinkler Specifications Sprinklers shall be [cULus Listed] low flow residential horizontal sidewall sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manu- facturer's technical data sheets are to be used. Residen- tial sprinklers shall be installed in conformance with the manufacturer's installation guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a'/2" NPT thread. Water seal assembly shall consist of a Teflon* coated Bel - *DuPont Registered Trademark leville spring washer with top -loaded extruded or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. The solder element (Link) version, the water seal consist of a cap with a bellville spring washer and a temperature rating of 165°F (74°C). The recessed assembly forthe HSWX (Bulb & Link) should be a steel two pieces escutcheon with 1/2" adjustment (Model F2) standard finish should be Bright Chrome and white paint- ed. The F1 Res 58 HSW is also available with low lead- frame. F1 Res 58 HSW and HSWX sprinklers shall have a nominal K Factor of 5.8 and F1 Res 44 a nominal K factor of 4.4. Standard finish: [Bronze] [Chrome -plated] [White' Polyester] [Special finish- specify]. Residential horizontal sidewall sprinklers shall be Reliable Model F1 Res 44, F1 Res 58, F1 Res 58 HSWX & Model KRes58 HSWX, SIN R3531, RA3533 & RA3593 (Bulletin 135). Model F1 Res 44 Recessed Horizontal Sidewall Sprinkler Use description for the Model F1 Res 44 horizontal side- wall sprinkler with the following modifications: Replace "horizontal sidewall sprinkler" with "recessed horizontal sprinkler." Add: Recessed escutcheon assembly shall be a steel, two-piece escutcheon with 1/2" adjustment (Model F2). Standard finish shall be [brass][bright chrome] [white painted] [Special finish- specify]. Residential recessed horizontal sidewall sprinklers shall be Reliable Model F1 Res 44/F2, SIN 93531 (Bulletin 135). Model 171 Res 76 Pendent Sprinklers shall be [cULus Listed] low flow residential pendent sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer's technical data sheets are to be used. Residential sprin- klers shall be installed in conformance with the manufac- turer's installation guidelines and the applicable installa- tion standard. Sprinkler frame and deflector shall be of bronze frame construction having a 3/a" NPT thread. Wa- ter seal assembly shall consist of a Teflon* coated Bel- leville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a nominal K -factor of 7.6. Standard finish: [Bronze] [Chrome -plated] [White Polyester] [Spe- cial finish- specify]. Residential pendent sprinklers shall be Reliable Model F1 Res 76, SIN R7618 (Bulletin 135). Model F1 Res 76 Recessed Pendent/F1, Model F1 Res 76 Recessed Pendent/F2, Model F1 Res 76 Recessed Pendent/FP Sprinklers shall be [cULus Listed] low flow residential recessed pendent sprinklers engineered to provide a minimum design density of 0.05 gpm/ftz over the listed coverage area. Listed flows as specified by the manu- facturer's technical data sheets are to be used. Residen- tial sprinklers shall be installed in conformance with the manufacturer's installation guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a 3/a" NPT thread. Water seal assembly shall consist of a Teflon* coated Bel- leville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and hav- ing a temperature rating of [155°F (680C)] [175°F (79°C)]. Sprinklers shall have a nominal K -factor of 7.6. Standard finish: [Bronze] [Chrome -plated] [White Polyester] [Spe- cial finish— specify]. Recessed escutcheon assembly shall be a steel, two-piece escutcheon [with 1/2" adjust- ment (Model F2)] [with 3/" adjustment (Model F1)] [of push -on and thread off design with 1/2" adjustment (Mod- el FP)]. Standard finish shall be [brass][bright chrome] [white painted]. Residential recessed pendent sprinklers shall be Reliable [Model F1 Res 76 Recessed Pendent/ F1] [Model F1 Res 76 Recessed Pendent/F2] [Model F1 Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135). Model F1 Res 76 CCP Pendent (Concealed) Sprinklers shall be [cULus Listed] low flow residential concealed sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer's technical data sheets are to be used. Residential sprin- klers shall be installed in conformance with the manufac- turer's installation guidelines and the applicable installa- tion standard. Sprinkler frame and deflector shall be of bronze frame construction having a 3/a" NPT thread. Wa- ter seal assembly shall consist of a Teflon* coated Bel- leville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and having "DuPont Registered Trademark a temperature rating of 155°F (68°C). Cover plate assem- bly shall consist of a brass cover plate and copper alloy retainer flange. Method of attaching the cover plate to the sprinkler cup shall be a push -on and thread -off design allowing a 1/2" cover plate adjustment. Cover plate tem- perature rating shall be 135°F (57C). A plastic protec- tive cap shall be provided and factory installed inside the sprinkler cup to protect the sprinkler from damage, which could occur during construction before the cover plate is installed. Standard cover plate finish: [White] [Custom Color— specify]. ]. Concealed pendent sprinklers shall be Reliable Model F1 Res 76 CCP, SIN R7618 (Bulletin 135). Finishes ft> (') Other finishes and colors are available on special order. Consult factory for details. (') cULus listed Corrosion Resistant Note: Paint or any other coating applied over the factory finish will void all approvals and warranties. Ordering Information Specify: 1. Sprinkler Model 2. Sprinkler Type 3. Temperature Rating 4. Sprinkler Finish 5. Escutcheon Finish 6. Cover Plate Finish The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by Reliable Automatic Sprinkler Co., Inc. Recycled ® (800) 431-1588 Sales Offices Paper iab (800) 848-6051 Sales Fax Revision lines indicate updated or new data. RelIQ (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 07/14 P/N 9999970235 Standard Finishes Sprinkler F1, F2, FP Cover Plates Escutcheons Bronze Brass White Painted Chrome Plated Bright Chrome Plated Chrome White and Black White Painted Polyester(') Coated Special Application Finishes Sprinkler F1, F2, FP Escutcheons Electroless Nickel PTFE(Teflon®)(') Electroless Nickel PTFE (Teflon®) Bright Brass Bright Brass Black Plated Black Plated Black Paint Black Paint Off White Off White Chrome Dull Chrome Dull (') Other finishes and colors are available on special order. Consult factory for details. (') cULus listed Corrosion Resistant Note: Paint or any other coating applied over the factory finish will void all approvals and warranties. Ordering Information Specify: 1. Sprinkler Model 2. Sprinkler Type 3. Temperature Rating 4. Sprinkler Finish 5. Escutcheon Finish 6. Cover Plate Finish The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by Reliable Automatic Sprinkler Co., Inc. Recycled ® (800) 431-1588 Sales Offices Paper iab (800) 848-6051 Sales Fax Revision lines indicate updated or new data. RelIQ (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 07/14 P/N 9999970235 SPEARS FlameGuard° CPVC FIRE SPRINKLER PRODUCTS Complete System of Pipe, Fittings & Solvent Cement FG -2-0312 Corrosion Resistant • Superior Flow • Ease of Installation Spears° FlameGuard° CPVC Fire Sprinkler Products provide a cost effective alternative to metal systems with advantages of high corrosion resistance, improved system hydraulics, ease of installation and quick assembly with readily available tools. CPVC Fire Sprinkler Systems are based on proven products that have been in continuous service for over40 years. Spears° FlameGuard° products are approved by UL°, FMO A Global, LPCB and Certi ed by NSF International for potable water use. Check local codes for restrictions and limitations. Corrosion Resistant CPVC Material Does Not Sustain Biological Growth Unlike metal systems, FlameGuard® CPVC products never rust, scale or pit and do not sustain biological growth - a cause of Microbiologically In uenced Corrosion (MIC) which can destroy metal re sprinkler systems from the inside out. Superior Flow Characteristics for Lower Friction Losses The smooth -wall interior surfaces of FlameGuard® CPVC systems result in reduced friction loss over metal systems. The design ow characteristics remain constant throughout the life of the product because there is no interior corrosion in the system due to microbiological activity. Pressure Rated to 175 psi (1200kpa) @ 150°F (65°C) FlameGuard® CPVC Products are produced in combinations of Schedule 40 and Schedule 80 Fitting con gurations con- forming to ASTM F438 or F 439 standards and FlameGuard® SDR 13.5 CPVC Fire Sprinkler Pipe conforming to ASTM F 442 standards. UL® Rated working pressure is 175 psi (1200kpa) @ 150°F (65°C) (LPCB rated to 120°F) (49°C). ms`s Easy Installation for Lower Costs FlameGuard® CPVC system installations significantly reduce costs over conventional metal piping by virtually eliminating prefabrication. Systems can be fully installed on site using solvent cement joining methods. UL° Listed for U.S. and Canada in NFPA 13,13R & 13D Systems FlameGuard® CPVC Fire Sprinkler Products are UL® listed for U.S. and Canada applications for Light Hazard occupanciesasde ned inNFPA 13, Residential occupancies up to and including 4 -stories as defined in NFPA 13R, and Residential occupancies for one and two family dwellings and manufactured homes as de ned in NFPA 13D. Consult Spears® FlameGuard®CPVC Fire Sprinkler Products Installation Instructions and NFPA Standards for additional applications including air plenum, system risers, concealed, exposed, underground, combustable attic, garage, basement and low pressure dry piping installations. Full Limited Lifetime Warranty FlameGuard® CPVC Fire Sprinkler Products carry a limited lifetime warranty against defects in material or workmanship. Consult Spears® warranty for additional details. PROGRESSIVE PRODUCTS FROM SPEARS "� IVNO VATION & TECHNOLOGY Visit our web site: www.spearsmfg.com ON CERr,, \ 9 a LPCB o UKAS a M/.NAGWENT o� oa SYSIL's 007 } Spears° FlameGuard° ... The Leader in Innovative CPVC Fire Sprinkler System Products Pioneer in Molded -in Metal Insert Head Adapters Spears° pioneered the development of the FlameGuard° molded -in-place metal thread insert for connection of sprinkler heads to CPVC re sprinkler systems, plus Metal FIPT threaded female adapters for metal -to -plastic transitions. Developed the Special Reinforced (SR)'Head Adapters Spears° FlameGuard® continuous improvement program developed the technology to produce a superior patented plastic threaded tting - the Special Reinforced (SR) Design. This unique design incorporates a patented thermoplastic compression process that equalizes stresses generated by • tapered thread joint make-up. All CPVC plastic body and threads provide a more uniform construction and improved corrosion resistance. Now, the Revolutionary TorqueSafeTA° Gasket Sealed Head Adapter • Requires NO Thread Sealants • Eliminates Stress • Prevents Over Tightening • Provides Easy Frame Alignment Spears° revolutionary design features a special molded -in-place Brass Thread Insert tted with an elastomer gasket seal at the base of the threads. .The gasket seal allows'a modi ed thread design that eliminates radial stress and associated problems typical with tapered thread joint make up. The insert is designed to rotate for easy sprinkler frame alignment without over tightening. Patent Pending. Full Assortment of Specialty Products & Fitting Configurations Spears° FlameGuard° provides the specialty ttings needed in today's re sprinkler systems. Like the adjustable drop nipple for ne-tuning to nished ceiling height, and ringed head adapter for ease of locating .during installation. Plus, Spears° Fla meGuard' line offers a full assortment of CPVC re sprinkler tting con gurations including Tees, Elbows, Flanges, Couplings, Caps, Male Adapters, Grooved Coupling Adapters and Unions, sizes 3/4" through 3"; with new 3/4" and V Repair Couplings. Complete Size Range of CPVC Pipe - .;.3f Flarn eC3uard9 usA Spears° FlameGuard° CPVC Fire Sprinkler Pipe is available in sizes 3/4" to 3". Conforms to ASTM F 442 standard for r,lanne4Guard6 usn SDR 13.5 CPVC pipe.. Spears° Solvent Cements & Thread Sealant FlameGuard° products should be installed using Spears® FS -5 One -Step Solvent Cement. For threaded joints, use Spears' BLUE 75— Thread Sealant that has been tested for compatibility with FlameGuard° CPVC Fire Sprinkler Products. Spears° TorqueSafeTM Gasket Sealed Adapter requires no sealant. - Consult sprinkler head manufacturer prior to use. -. Installation Training Available - Contact Spears° Technical Services for Details FlameGuard® Products must be installed in accordance with Spears' CPVC Fire Sprinkler Piping Products Installation Instructions; National Fire Protection Association Standards 13, 13R, 13D, and in accordance with local codes. Code requirements and eld conditions may differ. It is the responsibility of the installing contractor to insure that the product is suitable to meet these requirements. . SPEARS° MANUFACTURING COMPANY T. CORPORATE OFFICEe rn::i 15853 Olden St., Sylmar, CA 91342 • PO Box 9203, Sylmar, CA 91392 (818).364-1611 • www.spearsmfg.com 04 © Copyright 2012 Spears® Manufacturing Company. All Rights Reserved. Printed in the United States of America 03112. FG -2-0312 --LAN A.LE INTERNATIONAL 1050 Broadway, Westville, NJ 08093 R 800-90870523 F 856-45.6-9223 www.lansdaleinternational.com BRONZE GLOBE VALVE Soft Seat - 1 N0. -MATERIAL 1 Wheel Nut Hot Rolled (SAE 10108) 2 Name Plate Aluminum (A1100) 3 Hand Wheel Cast Iron (JiS zZ2202) 4 Packing Nut Brass (ASTM-UNS B16 036000) 5 Gland Ring Brass (ASTM-UNS B16 036000) 6 Gland Packing Graphite (LK 33 NAFG) 7 Bonnet Bronze (ASTM-UNS B584 084400) - 8 Lock Nut Brass (ASTM-UNS B16 C36000) 9 Stem Bronze (ASTM-UNS B584 C84400) 10 Disc Bronze (ASTM-UNS 8584 C84400) 11 Body j Bronze (ASTM-UNS 8584 C84400) D SIZE D H i 1/4" 2.13" D SIZE D H L 1/4" 2.13" 2.90" 1.81" %71 2.13" : 2.72" 1.85" '/z" 2.13" 2.66" 1.89" %it 2.19" 2.97" 2.20" 1 " 2.76" 3.41 " 2.54" 11/4" 2.95" 4.33" 2.92" 11/2" 3.31 " 5.12" 3.31 " 2" 3,74" 6.03" 3.92" PROJECT INFORMATION APPROVAL STAMP Project: ❑ Approved Address: ❑ Approved as noted Contractor: ❑ Not approved Engineer: Submittal Data: Notes 1: '- Notes 2: - Remarks: ALE i, INTERNATIONAL ' 1050 Broadway, Westville, NJ 08093 P.800.-908-0523 F.856-456-9223 ` www.lansdal'eintern'ational.com SW/NG CHECK VALVE. Full Floating Clapper Assembly. Y Sizes: 1/2" IPS - 2" IPS, Female x Female , Rated Pressure:175psi MATERIAL LIST N0: MATERIAL 1 Cap - , Brass (ASTM-UNS B584 C85710) 2 DISC Brass (ASTM-UNS B584 C85710) Disc Holder 3 Seat Packing Rubber NBR(SAE No 1052#) 4 Lock Bolt _ BraSS(ASTM-UNS B16 C36000) 5 Pin - Brass (ASTM-UNS B16 C36000)' 6 Body Brass (ASTM-UNS 8584 C85710) s SIZE_ H L H , • 3 ` 1 PROJECT INFORMATION APPROVAL STAMP Project: r-, '_ - 1/2 :• 1.44" • 2.09" 3/4" 1.58" 2.36"- .36"' 4113 1" 1.79" 2.62" 1'/4" 2.05" 3.19" 1'/2" 2.19" 3.55" 2" • 2.74" 4.22" , • 3 ` 1 PROJECT INFORMATION APPROVAL STAMP Project: r-, '_ - ❑ Approved Address: - ❑ Approved as noted 4 Contractor: ` 4 ❑ Not approved Engineer: Submittal Data: Notes 1. Notes 2: Remarks: - - P POTTER BELLS ® The Symbol of Protection PBA -AC & MBA -DC UL, ULC, and FM Approved Sizes Available: 6" (150mm), 8" (200mm) and 10" (250mm) Voltages Available: 24VAC 120VAC 12VDC (10.2 to 15.6) Polarized 24VDC (20.4 to 31.2) Polarized Service Use: Fire Alarm ' General Signaling Burglar Alarm Environment: . Indoor or outdoor use (See Note 1) -400 to 150°F (401 to 66°C) (Outdoor use requires weatherproof t> backbox.) ' ' 'Termination: AC Bells - 4 No. 18 AWG stranded wires DC Bells - Terminal strip ^ Finish: Red powder coating U� UhC F Optional: Model BBK-1 weatherproof backbox Model BBX-1 deep weatherproof backbox These vibrating type bells are designed for use as re, burglar or general signaling devices. They have low power consumption and high decibel ratings. The unit mounts on a standard 4" (101 mm) square electrical box for indoor use or on a model BBK-1 weatherproof backbox for outdoor applications. Weatherproof backbox model BBK-1, Stock No. 1500001. ALL DC BELLS ARE POLARIZED AND HAVE BUILT-IN TRANSIENT PROTECTION: Size inches (mm) Voltage Model Number Stock Number Current (Max.) Typical dB at 10 ft. (3m) (2) Minimum dB at 10 ft. (3m) (1) 6 (150) 12VDC MBA126 1750070 .12A 85 76 8 (200) 12VDC MBA128 1750080 .12A 90 77 10 (250) 12VDC MBA1210 1750060 .12A 92 78 6 (150) " 24VDC MBA246 1750100 .06A'• 87 77 8 (200) 24VDC MBA248 " 1750110 .06A 91 79 10 (250) 24VDC MBA2410 1750090- .06A 94 80 6 (150) 24VAC PBA246 1806024 .17A 91 78 ,8(200)- 24VAC PBA248. 1808024 .17A 94 77 10(250)- 24VAC PBA2410 1810024 .17A' , 94 78 6 (150) 120VAC PBA 1206 1806120 .05A 92 83 8 (200) 120VAC PBA 1208 1808120 ,05A 99 _ 84 10 (250) 120VAC PBA12010 1810120 .05A 99 . 86 Notes: 1. Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as speci ed in UL Standard 464. UL temperature range is -30° to 150°F (-34° to 66°C). 2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation. _ Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone:•800-325-3936/Canada 888-882-1833 • www. potters ignal.corn PRINTED IN USA MKT. 98850001 - REV V PAGE I OF 2 MFG. #5400776 - 10/06 • ' �, P POTTER BELLS ® The Symbol of Protection PBA -AC & MBA -DC FIG. 1 DIMENSIONS INCHES (mm) BELLS FIG.3 DWGN 776.1 INSTALLATION FIG. 2 WEATHERPROOF BACKBOX BOX HAS ONE THREADED 1/2" CONDUIT ENTRANCE DWGN 776-2 3 3/8" 5" (86) (127) 3 3/8" (86) 41/4" (108) WIRING (REAR VIEW) A.C. BELLS WI I ITE (IN) WPI ITE (OUT) O O FROM CONTROL PANELOR PRECEDING BELL BLACK (IN) BLACK (OUT) CAUTION: WIZEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SI'IOWN. NOTES: . I. WHEN USING AC BELLS. TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL. 2. END -OF -LINE RESISTOR IS NOT REQUIRED ON AC BELLS. DWGN 776-3 1. The bell shall be installed in accordance with NFPA 13, 72, or local AHJ. The top of the device shall be no less than 90" AFF and not less than 6" below the ceiling. 2. Remove the gong. 3. Connect wiring (see Fig. 3). 4. Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing down). 5. Reinstall the gong (be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong). 6. Test all bells for proper operation and observe that they can be heard where required (bells must be heard in all areas as designated by the, authority having jurisdiction). PRINTED IN LSA MKT. 98850001 - REV V PAGE 2 OF 2 MFG. 95400776 - 10/06 10" (250) ,J 2 (68) (68) FIG.3 DWGN 776.1 INSTALLATION FIG. 2 WEATHERPROOF BACKBOX BOX HAS ONE THREADED 1/2" CONDUIT ENTRANCE DWGN 776-2 3 3/8" 5" (86) (127) 3 3/8" (86) 41/4" (108) WIRING (REAR VIEW) A.C. BELLS WI I ITE (IN) WPI ITE (OUT) O O FROM CONTROL PANELOR PRECEDING BELL BLACK (IN) BLACK (OUT) CAUTION: WIZEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SI'IOWN. NOTES: . I. WHEN USING AC BELLS. TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL. 2. END -OF -LINE RESISTOR IS NOT REQUIRED ON AC BELLS. DWGN 776-3 1. The bell shall be installed in accordance with NFPA 13, 72, or local AHJ. The top of the device shall be no less than 90" AFF and not less than 6" below the ceiling. 2. Remove the gong. 3. Connect wiring (see Fig. 3). 4. Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing down). 5. Reinstall the gong (be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong). 6. Test all bells for proper operation and observe that they can be heard where required (bells must be heard in all areas as designated by the, authority having jurisdiction). PRINTED IN LSA MKT. 98850001 - REV V PAGE 2 OF 2 MFG. 95400776 - 10/06 1i1•�.Y!' POTTER. VANE TYPE WATERFLOW FOR CPVC PIPE ALARM SWITCH WITH RETARD ® The Symbol of Protection AND GLUE -IN UNION l� UL, CUL and CSFM Listed, CE Marked Specifications subject to change without notice. Stock Number: 1144460 Optional: Cover Tamper Switch Kit, stock no. 0090148 Replaceable Components: Retard/Switch Assembly, stock no. 1029030 CAUTION Waterflow switches that are monitoring wet pipe sprinkler systems shall not be used as the sole initiating switch to discharge AFFF, deluge. or chemical suppression systems. Waterflow switches used for this application may result in unintended discharges caused by surges, trapped air; or short retard times. General Information The Model VSR-SG is a vane type waterflow switch for use on wet sprinkler systems using CPVC plastic fittings (manufactured by Tvco, Nibco. Victaulic, 1pex, and Spears Manufacturing Company) that use 1". 1 '/4', 1 V2", or 2" pipe sizes. It is equipped with a union to accommodate installation in confined spaces. The VSR-SG contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the switch. The flow condition must exist for a period of time necessary to overcome the selected retard period. Enclosure The VSR-SG switches and retard switch are enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin number 5401103 for installation instructions of this switch. Installation (see Fig. I, 3, and 5) These switches may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will be accessible. The switch should not be installed within 6" (15 cm) of a fitting which changes the direction of the watertlow or A CAUTION Do not trim the paddle. Failure to follow these instructions may prevent the switch from operating and will void the warranty. Service Pressure: Up to l75 PSI (12;07 BAR) Flow Sensitivity Range for Signal: 4-10 GPM (15-38 LPM) - UL Maximum Surge: 18 FPS (5.5 m/s) Contact Ratings: Two sets of SPDT (Form C) 10.0Ampsat 125/250VAC 2.0Amps at 30VDC Resistive 10 mAmps min. at 24VDC Conduit Entrances: Two openings provided for 1/2" conduit. Individual switch compartments suitable for dissimilar voltages. Environmental Specifications: NEMA 4/IP54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting. Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL Service Use: British Standard B59251 Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy tip to four stories NFPA-13R National Fire Alarm Code NFPA-72 • Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. • Shock hazard. Disconnect power source before servicing. Serious injury or death could result. • Risk of explosion. Not for use in hazardous locations. Serious injury or death could result. within 24" (60 cm) of a valve or drain. The unit has a 1" male fitting for gluing into a CPVC plastic tee. NOTE: Do not leave cover off for an extended period of time. Loosen the union nut and separate the 1" male fitting from the VSR-SG. Glue the I" male fitting into the TEE following the TEE manufacturer's instructions for preparation and gluing of CPVC piping systems. (Note: The V male fitting must bottom out on the stop of the TEE for proper operation of the VSR-SG. See Fig. 1.) Wait 2 to 4 hours to allow the glue to dry before attaching the VSR-SG to the I" male fitting. Select the proper paddle for the pipe size and type of TEE used. See Fig. 3 for instructions on how to change paddle. Verify that the o -ring is properly positioned in its groove. Hand tighten the nut on the union after orienting the switch in the appropriate direction to detect waterfiow as shown in Fig. 5 & Fig. 7. The vane must not rub the inside of the TEE or bind in any way. The stem should move freely when operated by hand. A CAUTION Do not over -tighten the union nut; hand tighten only. Use of a wrench may damage the union nut. Potter C• lectric Signal Company, LLC • St. Louis; MO • CustService: 866-572-3005 -Tech Support: 866-956-0988/Canada 888-882-1833• ww\\cpottersignal.com PRINTED IN USA MFG. 95401205 - REV H PAGE I OF 4 01/12 VSR-SG QF) POTTER FORCPVCPIPE ALVANE TYPE ARM SWITCH WTH RETARD The Symbol of Protection AND -GLUE -IN UNION Testing The frequency of inspection and testing for the Model VSR-SG and its associated protective monitoring system shall be in accordance with applicable NFPA Codes and Standards and/or the authority havingjurisdiction (manufacturer recommends quarterly or more frequently). A method of testing the VSR-SG must be provided. The valve used for testing shall be easily reached and shall produce a minimum flow of 10 -GPM to activate the switch. The discharge orifice shall be equal to the smallest sprinkler used in the system. I Advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. Fig. l Glue the I" male fitting into the TEE following the TEE manufacturer's instructions for preparation and gluing of CPVC piping systems. Wait 2 to 4 hours to allow the glue to dry before attaching the VSR-SG to the V male fitting. 9' (MINIMUM CLEARANCE REOUIRED FOR I" MALE FITTING INSTALLATION OR MUST BOTTOM OUT REMOVAL OF DEVICE) ON STOP NO BUSHINGS, LL_ INS -RTS OR DWG. NIDE1-1 ADAPTERS ARE PERMITTED Fig. 3 DIRECTION OtD WATERFLOW V G. O #1063-3 Important: Il paddles are furnished with each unit to accommodate the various sizes and manufacturers of TEES. The paddles have raised lettering that show the pipe size and the TEE manq acturer they are to be used with. The proper paddle must be used. The paddle must be properly attached (see Fie. 3) and the screw that holds the paddle must be securely tightened. Fig. 2 Break out thin section of cover when wiring both switches from one conduit entrance. 1h Fig. 4 Typical Electrical Connections Notes: I. The Model VSR-SG has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator. 2. For supervised circuits, see "Switch Terminal Connections` drawing and warning note (Fig. 6). coNNEcroR NEUTRAL FROM BREAKER NEUTRAL FROM BELL 1 BBEAKER J F,� LINE FROM BREAKER as EOL (End Of line Resistor) NOTE: When connecting to a LIL Listed control panel, use the panel's resistor value for circuit supervision. PRIN'rE-D IN USA MPG. 45401205 - REV 1-1 PAGE 2 OF 4 01/12 VSR-SG VANE TYPE WATERFLOW P POTTER FOR CPVC PIPE ALARM SWITCH WITH RETARD 0® The Symbol of Protection AND GLUE -IN UNION Fig. 5 Retard Adjustment The delay can be adj usted by rotating the retard adjustment knob from 0 to the max setting (60- 90 seconds). The time delay should be set at the minimum required to prevent false alarms. OFFIONALCOVIRTANIPER SWI'I'CI I / Do nor I— corer rpfor--nrled perW r f rin e RI:I'ARD . AD1U.S'I'MENT KNO13 WEJ MOUNT SOA ON OASE POMTS IN UIItI>C'1'ION OP WA'I'ERFLOW V NIALE' FITTING ON ALL SIZES D%VC.4 1205-1A Flowing water activates stitch in oneV RUN OFnui'nili direction oniv. MAV DE I I '''A I Y.. or 2" Fig. 7 Mounting Dimensions -Orientation 3.50 in2.00 in (89.0 mm) (50.9 AA PIPE ' ' PLASTIC PADDLE D0.. PIPE Fig. 6 Switch Terminal Connections Clamping Plate Terminal 001GOINU INGONING An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire become dislodged from under the terminal. Failure to sever the wire may render the device inoperable risking severe property damage and loss of life. Do not strip wire beyond 3/8" of length or expose an uninsulated conductor beyond the edge of the terminal block. When using stranded wire, capture all strands under the clamping plate. A CAUTI O N Flow switch must be properly orientated. Side of cover must be perpendicular with the pipe. I m proper orientation co u I d delay or prevent notification of waterflow. Fig. 8 GREEN GROUND DWGn 1205-15 PRINTED IN USA MFG. #5401205 - REV H PAGE 3 OF 4 01/12 VSR-SG VANE TYPE WATERFLOW P POTTER FOR CPVC PIPE ALARM SWITCH WITH RETARD ® The Symbol of Protection AND GLUE -IN UNION Maintenance Inspect the waterflow switch monthly. If leaks are found: replace the waterflow switch. The VSR-SG waterflow switch should provide years of trouble-free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock # 1029030 (see Fig. 9). There is no maintenance required, only periodic testing ,and inspection. Retard/Switch Assembly Replacement (See Fig. 9) The Retard/Switch Assembly is field -replaceable without draining the system or removing the \vatertlow switch from the pipe I. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service. 2. Disconnect the power source for local bell (if applicable). 3. Identify and remove all wires from the waterflow switch. 4. Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws. 5. Remove the retard assembly by lifting it straight up over the.tripstem. 6. Install the new retard assembly. Make sure the locating pins on the retard/s\vitch assembly fit into the locating pin bosses on the base. 7. Re -install the (2) original mounting screws. 8. Reconnect all wires. Perform a flow test and place the system back in service. Fig. 9 (2) ORIGINAL MOUNTING REMOVE (2) ORIGINAL MOUNTING BREAK OUTTHIN SECTIONOF COVER SCREWS SCREWS HOLDING RETARD/SWITCH WHEN WIRING BOTH SWITCHES ASSEMBLY TO BASE FROM ONE CONDUIT ENTRANCE. ® RETARD/SWITCH ASSEMBLY J DO NO"r REMOVE (2) RETARD HOUSING SCREWS Removal of Waterflow Switch (2) LOCATING PINS (2) LOCATING PIl BOSSES IN BASE BASE GN 1190.2 • To prevent accidental water damage, all control valves should be shut tight and .the system coinpletely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector. then disconnect wiring-. • Loosen nuts and seperate unit from the glued -in fittings • Gently lift the unit far enough to get your fingers under it. With your fingers, roll the vane so it will fit through the hole while continuing to lift the waterflow detector. • Lift detector clear of pipe. PRINTED IN USA MFG. #5401205 - REV H PAGE 4 OI' 4 01/12 P.O. Box 3365 South EI Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 514 CPVC - STEEL - COPPER OFFSET HANGER SIZE - 3/4" thru 3"pipe. MATERIAL - Carbon Steel. FINISH - Mil. Galvanized.. LISTING/APPROVAL - e@ua 203 - EX 4231, EX 2551 a PATENT - No. 6,648,278. FUNCTION - 3/4"-2" Hanger/restrainer for horizontal CPVC, Copper or Steel pipe. Listed hanger/restrainer in all 3 mounting positions, i.e. vertical surface and both top and bottom of horizontal surface. Provides listed vertical/lateral restraint and prevents upward movement of pipe that supplies a pendent sprinkler below a ceiling. Size 2'/�" Hanger for horizontal CPVC pipe. Listed hanger in all 3 mounting positions. i.e. vertical surface and both top and bottom of horizontal surface. Size 3" Hanger for horizontal CPVC pipe in two mounting positions, side and bottom. i.e. vertical surface and bottom of horizontal surface. Stabilizes vertical piping by providing horizontal restraint. INSTALLATION - Per NFPA 13, 13R, 13D and CPVC manufacturers instructions. Space by pipe type. - See Drawings. Snap over pipe then squeeze strap back allowing pipe to slide freely. Listed When #905 threads are exposed in wood, install #906 backing nut. 3/4' SPECIAL NOTE: When installing on CPVC sprinkler system pipe: Verify that all assembly components are cleaned of any surface oil. FASTENERS - UL Listed per NFPA 13 WOOD - 3/4" - 3" CPVC pipe - #905 screw- no pre -drill. 3/4" - 2" Copper pipe - #905 screw- no pre -drill. 3/4" - 2" Steel pipe - 1/4"xl 1/2" lag screw - no pre -drill. Thru 5/8" gypsum board - 1/4" x 2" lag screw. STEEL - min. 18 GA. - 3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw. 3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw. 3/4" - 2" Steel pipe - 1/4" or #14 Tek Screw. CONCRETE: Required minimum load each fastener = 5(wo+250lbs. 2 FEATURES * 1 1/2" Offset - loose fit allows pipe to slide. * 3/4" and I" pipe size made with common center -line. * Patented design for superior strength. * Offset edge eliminates abrasion. * AFCON#905 screw has 5/16" hex head - included. ORDERING - Part # and pipe size. AFCON#906 backing nut sold separately. #905 #906 t.saoo i 3.00 1 0 o D 4 � o Q I Listed Restraint 3/4" thru 2" Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, when non-AFCON products have been, or are used. 8/08 0 P.O. Box 3365 South EI Monte, CA 91733 626.444.0541 Fax 626.444.3887. www. Afcon.org 511 CPVC - COPPER SIDE MOUNT HANGER SIZE - 3/4" thru 2" pipe. MATERIAL - Carbon Steel. FINISH - Mil. Galvanized. LISTING/APPROVAL - e(&. 203 - EX 4231, EX 2551 FUNCTION - Hanger on CPVC and Copper pipe. INSTALLATION - Per NFPA 13,13R, 13D and CPVC manufacturers instructions on top or bottom of beam. Space by pipe type SPECIAL NOTE: When installing on CPVC sprinkler system pipe: Verify that all assembly components are cleaned of any surface oil. FASTENERS - UL Listed per NFPA 13. in WOOD: 3/4" - 2" CPVC pipe - #905 screw - no pre -drill. 3/4" - 2" Copper pipe - #905 screw - no pre -drill. in STEEL - min. 18 GA. 3/4" - 2" CPVC pipe - 1/4" or #14 Tek Screw. 3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw. FEATURES * Offset edge.eliminates abrasion. * Retainer dimples secure hanger to pipe during installation. * Required AFCON#905 screw has 5/16" hex head - included. ORDERING - Part # and pipe size. Hanger - Wood Stud Side View - For Drawings Below Hanger - Metal Stud Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER - AFCONwill NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of nny kind, including but not limited to loss of business or profit, when non-AFCON products have been, or arc used. ' 7/08 P.O. Box 3365 South EI Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 510 CPVC - STEEL - COPPER HANGER SIZE - 3/4" thru 3" pipe - see Function. MATERIAL - Carbon Steel. FINISH - Mil. Galvanized. LISTING/APPROVAL - '&'203 - EX 4231, EX 2551 USTIED FUNCTION - To support horizontal piping 3/4" -2" CPVC, Copper or Steel. To support horizontal piping 2 1/2" -3" CPVC and Copper. Hanger in listed mounting positions - Top, Bottom or Side. Also, provides stability on vertical piping. INSTALLATION - Per NFPA 13, 13R, 13D and CPVC manufacturers instructions_ , mount on top, bottom or side of building element. Space by pipe type. FASTENERS - UL Listed per NFPA 13 in WOOD: 3/4" - 3" CPVC pipe - #905 screw - no pre -drill. 3/4" - 2" Steel and Copper pipe - 1/4"x11/2" lag screw - no pre -drill. in STEEL - min. 18 GA. 3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw. 3/4" - 2" Steel and Copper pipe - 1/4" or #14 Tek Screw. FEATURES * Offset edge eliminates abrasion. * Retainer dimples secure hanger to pipe during installation. * Required AFC.ON#905 screw has 5/16" hex head - included. ORDERING - Part # and pipe size. *CAN ALSO BE USED TO REPLACE - #500 Pipe Strap #520 Tin Strap Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER - AFCONwill NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, when non-AFCON products have been, or are used. 10/11 510 astanar SIZE oi- 44 3/4 2.125 1 2.312 1 1/4 3.170 1 1/2 3.400 4.010 21/2 4.320 3 1 5.320 FUNCTION - To support horizontal piping 3/4" -2" CPVC, Copper or Steel. To support horizontal piping 2 1/2" -3" CPVC and Copper. Hanger in listed mounting positions - Top, Bottom or Side. Also, provides stability on vertical piping. INSTALLATION - Per NFPA 13, 13R, 13D and CPVC manufacturers instructions_ , mount on top, bottom or side of building element. Space by pipe type. FASTENERS - UL Listed per NFPA 13 in WOOD: 3/4" - 3" CPVC pipe - #905 screw - no pre -drill. 3/4" - 2" Steel and Copper pipe - 1/4"x11/2" lag screw - no pre -drill. in STEEL - min. 18 GA. 3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw. 3/4" - 2" Steel and Copper pipe - 1/4" or #14 Tek Screw. FEATURES * Offset edge eliminates abrasion. * Retainer dimples secure hanger to pipe during installation. * Required AFC.ON#905 screw has 5/16" hex head - included. ORDERING - Part # and pipe size. *CAN ALSO BE USED TO REPLACE - #500 Pipe Strap #520 Tin Strap Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER - AFCONwill NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, when non-AFCON products have been, or are used. 10/11 P.O. Box 3365 South EI Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 515 DOUBLE OFFSET C.P.V.C. HANGER SIZE - 3/4" and 1" pipe. MATERIAL - Carbon Steel. FINISH - Mil. Galvanized. LISTING/APPROVAL - . c@us 203 - EX 4231 PATENT - No. 6,702,236 FUNCTION - Hanger/restrainer for horizontal CPVC pipe. INSTALLATION - Per N.P.F.A 13, 13R and 13D.. SPECIAL NOTE: When installing on CPVC sprinkler system pipe: Verify that all assembly components are cleaned of any surface oil. FASTENERS - UL Listed per NFPA 13. WOOD: #904 screw - no pre -drill. STEEL: 1/4" or #14 Tek Screw in min. 20 GA. FEATURES * Double 1 1/2" offset - loose fit allows pipe to slide. * Center line matches AFCON#514. * 3/4"•and V pipe size have common center -line. * Offset edge eliminates abrasion. * Required AFCON #904 screw has 3/8" hex head - included. ORDERING - Part # and pipe size. Specific AFCON products arc exclusively designed to be compatible ONLY with otherAFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, when non-AFCON products have been, or are used. 8/07