Loading...
HomeMy WebLinkAboutB17-2358 047-430-065Loyd W. Martin Professional Engineer, Inc. 2510 W. 237th St. #206 Torrance, CA 90505 Tel: 1.310.464.1804 Email: loydwmartin@gmail.com www.loydwmartin.com Structural Calculations for a Ground Mounted Solar Electric System for: �oQROFESS/0 Robert Residence a! No. C58724 85 Roberts Ct., PERMIT Exp. 3-31-19 # Chico, CA 95973 BUTTE COUNTY REVIEWED FOR SERVICE � ��9rFOFi�vAv F°�c CODE COMPLIANCE Applicable Codes: DATE =fig. - -BY-- 2016 California Building Code, 2016 California Electric Code, 2016 California Mechanical Code, American Society of Civil Engineers Standard ASCE 7-10 Minimum Design Loads for Buildings and Other Structures, Local Municipal Code, and all other codes which are adopted by reference or enacted by law. - Assumed Design Parameters: Soil is Sand, Silty Sand, Clayey'Sand, Silty Gravel or Clayey Gravel. ( SW, SP, SM, SC, GM or GC ) or better. Presumptive Load -Bearing Values per Table 18.02 of 2016 CBC Contractor, Building Official or Project Engineer shall verify on-site soil parameters. Wind Design Speed is 110 mph Exposure C B17-2358 FILE/PC] Tilt Angle — 19 degrees +/- ' 047-430-065 OCTOBER =4, 201.7 { GRi`VD !VENT SOLAR Flat to Slightly Sloping Terrain �- -- - Sht # 1 of 10 2017- 3790 Join Solar Robert Residence Date: September 30, 2017 Loyd W. Martin Professional Engineer, Inc.. 2510 W. 237th St. #206 Torrance, CA 90505 Tel: 1.310.464.1804 Email: loydwmartin@gmail.com www.loydwmartin.com EO.15' 15' 16 EO. T L PIER (TYP) Solar PV ArrayLayout Plan View �oQROF ESS/p4 W. c� p I' G C� � No. C58724 * Exp.3-31-19 ��9TF 0" C 2'-6" MAX. EXPOSED ABOVE GRADE NOTE: There shall be no splice on the rails. Rails must be continuous on its entire length. 2017-3790 Join Solar Robert Residence VARIES 9' (3) CIRCUITS OF (13) Solar PV Array Section View \� 3" CROSS PIPE 1 `3" PIER PIPE 1 DIAGONAL BRACING, AS NEEDED ENGINEERED FOUNDATION Sht # 2 of 10 Date: September 30, 2017 Loyd W. Martin Professional Engineer, Inc. 2510 W. 237th St. #206 Torrance, CA 90505 Tel: 1.310.464.1804 Email: loydwmartin@gmail.com www.loydwmartin.com Loads and Load Combinations for Ground Mount System Critical Load Combinations per Section 2.4.1 Basic Combinations ASCE 7-10: Load' Case 5: D + (0.6W or 0.7E) (Wind Governs) Note: D = Dead Load = 3 psf max W = Wind Load = See Analysis for Exposure C 110 MPH S = Snow Load = 0 psf, 2017-3790 Join Solar Robert Residence �oQROF ESSIOA, W. � o � 9. c� No. C58724 Exp. 3-31-19 cPj CIVI\ Sht #'3 of 10 Date: September 30, 2017 Loyd W. Martin. Professional Engineer, Inc. 2510 W. 237th St. #206 Torrance, CA 90505 Tel: 1.310.464.1804 Email: loydwmartin@gmail.com www.loydwmartin.com Determine Wind Load per Section 6.5.13.2 ASCE 7-05: F = qh G CTAS Where F qh - G Cf = AS = QROF ESS/p\ PVNo. C58724 Exp. 3-31-19 sT CIViV 9TF OF C A\-\F�• design force velocity pressure evaluated at mean roof height h as determined in accordance with Section 29.3.2 gust- effect factor from Section 26.9 net pressure coefficient determined from Figs. 29.4-1 gross area of solar array therefore determine qZ per Section 29.3.2 qZ = 0.00256 KZ KZT Kd V2 psf z = h = 5ft. Exposure C Wind 110 mph KZ = 0.85 Velocity Pressure Exposure Coefficient ASCE 7-10 Section 29.3.1 and per Table 29.3-1 KZT = 1.0 Topographic Factor ASCE 7-10 Section 26.8.2 Kd = 0.85 Wind directionality factor as defined by ASCE 7-10 Section 26.6 and per Table 26.6-1 V 110 mph Basic Wind Speed per Section 26.5 and Fig. 26.5-1 Sht # 4 of 10 2017- 3790 Join Solar Robert Residence Date: September 30, 2017 Loyd .W. Martin Professional Engineer, Inc. 2.510 W. 237th St. #206 Torrance, CA 90505 Tel: 1.310.464.1804 . Email: loydwmartin@gmail.com . www.loydwmartin.com therefore determine qZ per Section 29.3.2: �oQROFEss/pNq� w. qZ = 0.00256 KZ KZT Kd V2 psf 2 No. C58724 qZ = 0.00256 x 0.85 x 1.0 x 0.85 x (110)` * Exp. 3-31-19 9TF OF C AQF qZ = 22.4 psf G- = 0.85. Gust Effect Factor ASCE 7-10 Section 26.9 CN _ 1.3 +/- Entire Roof Area (conservative over entire roof area) net, force 'coefficient per Fig. 29.4-1 therefore determine F per Section 29.4-1 ASCE 7-10 :. F = qh G CfAs F = .22.4 psf x 0.85 x 1.3,x As P = +/- 24.8 psf x AS Note:.Load Combinations for Allowable Stress Design per Section 24.1: 0.6 x F = 0.6 x (+/- 24.8 psf) x AS 0.6 x F. _ (+/- 14.9 psf ) x AS Sht # 5 of 10 2017- 3790 Join Solar Robert Residence Date: September 30, 2017 Loyd W. Martin Professional Engineer, Inc. 2510 W. 237th St. #206 Torrance, CA 90505 Tel: 1.310.464.1804 Email: loydwmartin@gmail.com www.loydwmartin.com Loading Diagram for Solar PV Array D=3psf �oQROF ESS/pN�l W. No. C58724 *Exp.3-31-19 * W = 14.9 psf cPj CIV 1 \P 9TF OF C ALF ti - N Angle = 19° N p p R1 I R1x R2 I R2X I I I I 11-811 91-011 11-811 Equivalent Component Force Diagram Analyze 19° Condition: Total IF Tota I Fx 6 ' N Angle = 19° io N R1 R1x R2y R2x I I I I 1'- 8" 90-01, 1'- 8" Sht # 6 of 10 2017-3790. Join Solar Robert Residence Date: September. 30, 2017 Loyd W. Martin Professional Engineer, Inc. 2510 W. 237th St. #206 Torrance, CA 90505 Tel: 1.310.464: 1804 Email: loydwmartin@gmail.com www.loydwmartin.com Determine Applied Equivalent Loads for 19° Condition: F y / Tributary Area .= 3 psf + 14.9 psf x cos 19 17.09 psf Tributary Area = 13.2 ft x 15 ft x 1/2 = 99 sq ft F y = 17.09 psf x 99 sq. ft. = 1,692 lbs F x / Tributary Area = 14.9 psf x -sin 19 Tributary Area = 13.2 ft x 15 ft x 1/2, F x = 4.85 psf x 99 sq. ft. Force Analysis in Member Elements 1,6192 # 480 # 6 4.85 psf. = 99 sq ft = 480 lbs �oQROF ESS/0 W. o LU No. C58724 Exp. 3-31-19 cPJ CIV 1V 9TF OF C AO\ 2017- 3790 Join Solar Robert Residence R2y P R2x 1 II 91-01, V-8" Sht # 7 of 10 Date: September 30, 2017 Loyd W. Martin Professional Engineer, Inc. 2510 W. 237th St. #206 Torrance, CA 90505 Tel: 1.310.464.1804 Email: loydwmartin@gmail.com- www.loydwmartin.com Force Analysis in Member Elements Continued Max Downward Vertical Load to Footing = 1,692 lbs Max Uplift Vertical Load to Footing = 1,395 lbs Lateral Load to Footing = 480 lbs �OQ?,OF ESS/pN9l W. CO p 2 No. C58724 Exp. 3-31-19 Allowable Loads for 16" Diameter x 52" Deep Pier. s�qT �ivi� F �F C A0� Uplift Capacity Weight of Foundation = Area x Depth x 150 pcf 3.14 x (0.67 ft)^2 x 4.33 ft. x 150 pcf 903 lbs Soil Friction = Surface Area x Cohesion 2016 CBC Table 1806.2 3.14 x 1.33 ft. x 4.33 ft. x 130 psf 2,353 lbs > 600 lbs (CBC Sec. 1806.3.2) Array Dead Load = (3 psf x 99 sq ft) = 297 lbs Uplift Capacity = 903 lbs + 600 lbs + 297 lbs = 1,799 lbs > 1,395 lbs OK Use (N) 16" Diameter x 52" Deep Pier as per plans at Supports of Array Sht # 8 of 10 2017- 3790 Join Solar Robert Residence Date: September 30, 2017 Loyd W. Martin Professional Engineer, Inc. 2510 W. 237th St. #206 Torrance, CA 90505 Tel: 1.310.464.1804 Email: loydwmartin@gmail.com www.loydwmartin.com Compression Capacity Compression Capacity = Area x Bearing Pressure 3.14 x (0.67 ft)^2 x 1500 psf Compression Capacity = 2,084 lbs > 1,692 lbs OK Check Soil Pressures of Pole Footing Support Check Soil Pressures per 2016 CBC Sec. 1807.3.2.1 Eq'n 18-1 d=0.5A( 1 +(1 +(4.36h/A))") A=2.34P/S1b S1=217psf x 1.33 x2=576 psf h = 5.1' b = diameter of footing = 1.33 ft. A =. 2.34 x 480 lbs / (576 x 1.33) = 1.47 �OQ�tOF ESS o � 2 No. C58724 * Exp. 3-31-19 sT Civic s 9rF Of C Al\F dReq'd=0.5x1.47(1+(1+(4.36x5.1'/1.47))05) =3.68 ft. < 4.33 ft Use (N) 16" Diameter x 52" Deep Pier as per plans at Supports of Array Note to Building Official: Based upon a review of the proposed plans I am confident that the proposed ground mounted solar PV array is capable of supporting all code required loads with the above mentioned footing. If you haver any questions or additional concerns feel free to contact me at loydwmartin@gmail.com, skype id loydwmaritn, or tel: 1-310-464-1804. Thanks. End of Calculations Sht.# 9 of 10 2017- 3790 Join Solar Robert Residence Date: September 30, 2017 Loyd .W. Martin Professional Engineer,- Inc. 2510 W. 237th St. #206 Torrance, CA 90505 Tel: 1.310.464.1804 Email: loydwmartin@gmail.com www.loydwmartin.com SUPPORT PER PLANS NATURAL GRADE X //\// 16" DIAMETER X 4.33 FT. DEEP CONCRETE.PIER; F'C.= 2500 PSI 1'A OR BETTER WRAP (2) LAYERS OF 14 -GAUGE w GALVANIZED STEEL WELDED WIRE .� . QROF ESS/p 311 o No. C58724 M• * Exp. 3-31-19 � CIV 1 \- �\P 161OF CAL\F DRAWN BY: LWM D1 PV ARRAY FOUNDATION PIER DETAIL DATE: 9-30-17 SECTION VIEW JOB: 2017-3790 Join Solar California State Fire Marshal Information Bulletin 14-011 Issued: November 25, 2014 FIRE CLASSIFICATION FOR ROOF MOUNTED SOLAR PHOTOVOLTAIC SYSTEMS AND/OR PANEL MODULES — 2013 CALIFORNIA BUILDING STANDARDS CODE SUPPLEMENT EFFECTIVE JANUARY 1, 2015 The Office of the State Fire Marshal is issuing this Information Bulletin to address the use of photovoltaic solar systems and/or panel modules in areas outside the State Responsibility Areas (SRA) and Very High Fire Hazard Severity Zones. The adoption of UL 1703 with revisions through October 25, 2013 and the Emergency Rulemaking that delayed the effective date to January 1, 2015 of the adoption were intended to focus on the areas that require Class A or Class B roofing (SRA and Very High Fire Hazard Severity Zones). Where Class A or Class B roofing is required, the photovoltaic solar system (photovoltaic panels with the rack support system) shall have a Class A or Class B rating, respectively. Areas in California that only require a minimum Class C roofing due to statutory provision contained in Health and Safety Code 13132.7 should not be impacted by the early adoption of UL 1703. Those buildings and structures requiring Class C roofing should be able to have installed one of the following and meet the intent of the 2013 California Building Standards Code: 1. Photovoltaic panels and modules having a Class C rating under the previous version of UL 1703 (2002 edition with revisions through April 2008), or 2. Photovoltaic panels and modules having a Class C rating complying with UL 790 (2004 edition with revisions through October 2008), or 3. Photovoltaic systems having a minimum Class C rating under the most recent version of UL 1703 (2002 edition with revisions through October 2013). Fire classification of photovoltaic solar systems and panels shall be marked with their fire classification rating, Class A, B, or C. Questions or comments regarding this Information Bulletin should be directed to Division Chief Kevin Reinertson, Code Development and Analysis at (916) 327-4998, or by electronic mail to kevin.reinertson@fire.ca.gov. For more information please visit our w ebsitc B17-2358 1 FILE/PC] 047-130-065 OCTOBER 4, 2017 C.RND MNT SOLAR BUTTE � DMS B�JILDIh! C • Optimized by CS6K-270 1 275 1 280M-SD sour-••: Canadian Solar's SmartDC module features an innovative integration of Canadian Solar's module technology and SolarEdge's power optimization r ' for grid-tied PV applications. t By replacing the traditional junction-,box with a ' power optimizer, the SmartDC module optimizes power output at module-level. With this feature, the SmartDC module can eliminate module- level odule level mismatch and decrease shading losses. , Furthermore, the SmartDC module provides ` module level monitoring that allows effective , system management and minimizes operational _ costs. years linear power output warranty KEY FEATURES " ft0 . product warranty on materials Harvests'up to 25% more energy years and workmanship ` from each module -:Maximizes power from each individual - .......:...'...........:.......'................................ .. ` module against potential mismatch risk MANAGEMENT SYSTEM CERTIFICATES* Decreases shading losses ISO 9001:2008 / Quality management system �•. ISO/TS 16949:2009 / The automotive industry qualit; management system Easy installation, simple system design ISO 14001:2004 / Standards for environmental man- 7-gement system, Integrated smart solution, no need to OHSAS 18001:2007 / International standards for occipational hea th & safety , add other accessories Enhances the shading tolerance PRODUCT CERTIFICATES* • +. IEC 61215 / IEC 61730: VDE/CE r Red Cites BoS Costs a, UL 1703 / IEC 61215 performance: CEC listed (US)" - Up to 11.25 kW - 12.75 kW per string UL 1703: CSA =, allows for more modules to be based on different inverters dE $P • C�US _ Free module-level monitoring system �therearedlfferentcertlilca[Ionrequlrementslndlfferentmarkets,pleasecontactyour O x Canadian Solar sales representative for the specific certificates applicable to the products. 0 Full vsbesm le y f system performance ......... ....... .. with af` artplione app CANADIAN SOLAR INC. is committed to providing' high quality `Safety solar products, solar system solutions and services to customers 4 MORE- ., Automatic drop of DC current and j around the world. As a leading manufacturer of solar modules and. , f J voltage when inverter or grid power PV project developer with over 14 GW of premium quality modules is shut down deployed around the world since 2001, Canadian Solar Inc. (NASDAQ: CSIQ) is one of the most bankable mlar companies worldwide. .. , : •.'......` ............................... .+.. .......• -.. .....c. ........... CANADIANSOLAR (USA) INC. 2420 Camino Ramon,. 125 Suite San Ramon, CA, USA 94583-4385, www.canadiansolar.com, sales.us@canadians.:)lar.com ENGINEERING DRAWING (mm) Rear View Frame Cross Section A -A 180. 645.0 / 35 Grounding ) Hole P v 11 Mounting Hole 7 . &110 --- ' oundn9 I JA Hole 40 9 44 992 ELECTRICAL DATA / STC Power Optimizer connected to a SolarEdge Inverter CS6K 270M -SD 275M -SD 28OM-SD Nom. Max. PWR(Pmax STC) 27OW 275W 28OW Nom. Max. PWR (Pmax NOCT) 195W 199W 202W Open Circuit Voltage (Voc STC) 382V 383V 38.5V Output Voltage Range (Vout) 5-60V 5-60V 5-60V Max. Output Current (Imax) 15A 15A 15A Max. Series Fuse Rating_ _ 20A 20A 20A Mo dule_Ef- ciency_�_ Output During Standby (power optimizer disconnected 16.50% 16.80% 1 V _ 17.11 % from inverter or inverter off) PV SYSTEM DESIGN Min. String Length EU& APAC 1 ph 8 3 p 16 3 ph - MV 18 US & Canada 1 ph 8 3 ph (208 V) 10 Max. String Length EU & APAC 1 ph 19 19 18 •— 3 ph 41 40 40 3 ph - MV 47 46 45 US & Canada 1 ph 19 19 18 3 ph (208 V) 22 21 21 Max. Power per String (W) EU & APAC 1 ph 5250 — 3 ph 11250— 3 ph - MV 12750 US & Canada 1 ph 5250 3 ph (208 V) 6000 Parallel Strings of Diff. Lengths Yes Parallel Strings of Diff. Orientations Yes Operating Temperature -40°C - +85°C Max. System Voltage 1000 V (IEC) / 600 V (UL) Application Classification Class A Fire Rating Type 1 (UL1703) / Class C (IEC61730) Power Tolerance 10 - +5 w CS6K-280M / I-V CURVES A Mono -crystalline, 6 inch A 60 (6 x 10) 10 ....................................................... 10 ................................................ 19.3 kg (42.5 lbs) Front Cover 9 .......................................... Frame Material ............ 9................................... J -,Box_ IP65_ _ Cable ............. g........... .......................... ...... 8 ...................................... ........... 7 ............................. _....... ....... 7 ..................................... . 6 .............. ....... .................._.... ....._ 6 ...................... .--- ..—... - ...... ...... 5 .............._........... ............... ... _ 5 ............. _.........__........... .. ... .... q................................................ ..... 4 .................... :......... ........... .. ... .. .._ .................... .... 3 ......................................... .. ......: 2 .................................................. .... 2 ................................................. .... 1 ........................................I.......... .._ 1 ................................................... _ o Vo V 5 10 15 20 25 30 35 40 5 10 15 20 25 30 35 40 0 1000w/rw 5°c a N 800w/ff)� 25°C 0 13 600 w/m, 45°C C3 0 400 Wftr� 65°C N MECHANICAL DATA OF PV MODULE Specification Data Cell Type Mono -crystalline, 6 inch Cell Arrangement 60 (6 x 10) Dimensions 1650x992x40mm(65.0x39.1x1.57in) Weight 19.3 kg (42.5 lbs) Front Cover 3.2 mm tempered glass Frame Material Anodized aluminium alloy J -,Box_ IP65_ _ Cable PV1-F 1 *6.0 mm2 / 952 mm Connectors MC4 Standard 26 pieces, 548 kg (1208 lbs) Packaging _ (quantity & weight per pallet) _ Module Pieces 728 pieces (40' HQ) - per Container TEMPERATURE CHARACTERISTICS Specification Data TemperatureCoeffcienf(Pmax)--'- -0.41oih/°C-- Temperature Coefficient (Voc) -0.31 % /°C Temperature Coefficient (Isc) 0.053 % /°C Nominal Operating Cell Temperature 45±2°C STANDARD COMPLIANCE Specification Standard EMC FCC Part15 Class B, _ v IEC61000-6-2, IEC61000-6-3_ PV Module IEC61215, IEC61730, UL1703,� _ CEC listing PV Optimizer) -Box EN50548, UL3730, IEC2109-1 (class II safety), UL1741 Fire Safety VDE-AR-E 2100-712:2013-05 PARTNER SECTION .............................................. .............................................. CANADIAN SOLAR (USA) INC. March. 2016. All rights reserved, PV Module Product Datasheet V5.4 -NA S A CSA C Group Certificate of Compliance Certificate: 2284121 Master Contract: 249143 Project: 70143782 Date Issued: 2017-06-27 Issued to: Canadian Solar Inc 545 Speedvale Ave West Guelph, Ontario NIK IE6 CANADA Attention: Wenda Zheng The products listed below are eligible to bear the CSA Mark shown with adjacent indicators 'C' and 'US' for Canada and US (indicating that products have been manufactured to the requirements of both' Canadian and US Standards) or with adjacent indicator 'US' for US only or without either indicator for Canada only. Issued by: Q`'a4(S "WV) TCa4 ' Qiang (Sean) Jiang C us PRODUCTS CLASS - C5311 10 - POWER SUPPLIES -Photovoltaic Modules and Panels CLASS - C531190 - POWER SUPPLIES -Photovoltaic Modules and Panels - Certified to US Standards Photovoltaic Modules with maximum system voltage of 600 V do or 1.000 V do and Type l and Type 2 module fire performance, Model Series CS6X-XXXP, CS6X-XXXPX where 'XXX' is the power output from 250 W to 360 W with the following electrical ratings typical at 360 W @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 46.5 V Short Circuit Current (Isc): 9.92 A Operating Voltage (Vpmax): 38.3 V Current at Operating Voltage'(Ipmax): 9.40 A Photovoltaic Modules with maximum system voltage of 600 V do or 1000 V do and Type 1 and Type 2 module fire performance, Model Series CS6X-XXXM where'XXX' is the power output from 260 W to 360 W with the following electrical ratings typical at 360 W @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 46.9 V CA S P Group Certificate: 2284121 Project: 70143782 Short Circuit Current (Isc): 9.78 A Operating Voltage (Vpmax): 38.7 V Current at Operating Voltage (lpmax): 9.31 A Master Contract: 249143 Date Issued: 2017-06-27 Photovoltaic Modules with maximum system voltage of 600 V do or 1000 V do and Type 1 and Type 2 module fire performance, Model Series CS6P-XXXP, CS6P-XXXPX where 'XXX' is the power output from 200 W to 300 W with the following electrical ratings typical at 300 W for CS6P-XXXP/ CS6P-XXXP-S, and CS6P- XXXPX series respectively @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 38.8 V Short Circuit Current (Isc): 9.92 A Operating Voltage (Vpmax): 32.0 V Current at Operating Voltage (Ipmax): 9.38 A Photovoltaic Modules with maximum system voltage of 600 V do or 1000 V do and Type 1 and Type 2 module fire performance, Model Series CS6P-XXXM and CS6P-XXXMX where'XXX' is the power output from 200 W to 300 W with the following electrical ratings typical at 300 W for CS6P-XXXM and CS6P-XXXMX series respectively @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 39.1 V Short Circuit Current (Isc): 9.78 A Operating Voltage (Vpmax): 32.4 V Current at Operating Voltage (Ipmax): 9.25 A Photovoltaic Modules with maximum system voltage of 600 V do and Type l and Type 2 module fire performance, Model Series CS6A-XXXP, where 'XXX' is the power output from 160 W to 210 W with the following electrical ratings typical at 210 W @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 30.0 V Short Circuit Current (Isc): 9.19 A Operating Voltage (Vpmax): 24.4 V Current at Operating Voltage (Ipmax): 8.63 A Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 and Type 2 module fire performance, Model Series CS6C-XXXM, CS6C-XXXMS, where 'XXX' is the power output from 120 W to 1.80 W with the following electrical ratings typical at 145 W @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 22.4V Short Circuit Current (Isc): 8.52 A Operating Voltage (Vpmax): 18.1 V Current at Operating Voltage (Ipmax): 8.01 A Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 and Type 2 module fire performance, Model Series CS6C-XXXP, where'XXX' is the power output from 120 W to 180 W with the following electrical ratings typical at 150 W @ Standard Test Condition (STC): t e CSA P Group 'Certificate: 2284121 Project: 70143782 Open Circuit Voltage (Voc): 22.3V Short Circuit Current (Isc): 8.87 A Operating Voltage (Vpmax): 18.1 V Current at Operating Voltage (Ipmax): 8.30 A Master Contract: 249143 Date Issued: 2017-06-27 Photovoltaic Modules with maximum system voltage of 600 V do or 1000 V do or 1500V do and Type l and Type 2 module fire performance, Model Series CS6K-XXXP, where 'XXX' is the power output from 220 W to 300 W with the following electrical ratings typical at 300 W for CS6K-XXXP series @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 38.8 V Short Circuit Current (Isc): 9.92 A Operating Voltage (Vpmax): 32.0 V Current at Operating Voltage (Ipmax): 9.38 A Photovoltaic Modules with maximum system voltage of 600 V do and Type 1 and Type 2 module fire performance, Model Series CS6A-XXXM, CS6A-XXXMS, where'XXX' is the power output from 160 W to 245 W with the following electrical ratings typical at 245 W @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 32.1 V Short Circuit Current (Isc): 9.84 A Operating Voltage (Vpmax): 26.2V Current at Operating Voltage (Ipmax): 9.36 A Photovoltaic Modules with maximum system voltage of 600 V do or 1000 V do or 1500V do (only for CS6K- XXXM series) and Type 1 and Type 2 module fire performance, Model Series CS6K-XXXM, CS6K-XXXMS, where 'XXX' is the power output from 240 W to.305 W with the following electrical ratings typical at 305 W @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 39.9V Short Circuit Current (Isc): 9.75 A Operating Voltage (Vpmax): 32.9V Current at Operating Voltage (Ipmax): 9.27 A Photovoltaic Modules with maximum system voltage of 1000V do or 1500 V do and Type 1 module fire performance, Model Series CS6U-XXXM, where 'XXX' is the power output from 260 W to 360 W with the following electrical ratings typical at 360 W @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 46.9 V Short Circuit Current (Isc): 9.78 A Operating Voltage (Vpmax): 38.7 V Current at Operating Voltage (Ipmax): 9.31 A Se CSA P Group Certificate: 2284121 Master Contract: 249143 Project: 70143782 Date Issued: 2017-06-27 Photovoltaic Modules with maximum system voltage of I OOOV do or 1500 V do and Type 1 fire performance, Model Series CS6U-XXXP, CS6U-XXXPN, where 'XXX' is the power output from 250 W to 360 W with the following electrical ratings typical at 360 W @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 46.5 V Short Circuit Current (Isc): 9.92 A Operating Voltage (Vpmax): 38.3 V Current at Operating Voltage (Ipmax): 9.40 A Photovoltaic Modules with maximum system voltage of 600V do or 1000 V do and Type 1 and Type 2 module fire performance, Model Series CS6P-XXXP-SD, and CS6K-XXXP-SD where'XXX' is the power output from 240 W to 300 W with the following electrical ratings typical at 250 W @ Standard Test Condition (STC): Output Voltage Range (Vout): 5-60V Maximum Output Current (Imax): 15A Photovoltaic Modules with maximum system voltage of 600V do or 1000 V do and Type 1 and Type 2 module fire performance, Model Series CS6P-XXXM-SD, CS6K-XXXMS-SD, and CS6K-XXXM-SD where'XXX' is the power output from 240 W to 305 W with the following electrical ratings typical at 250 W @ Standard Test Condition (STC): Output Voltage Range (Vout): 5 — 60 V Maximum Output Current (Imax): 15A Photovoltaic Modules with maximum system voltage of 600V or 1000 V do and Type 1 and Type 2 module fire performance, Model Series CS6P-XXXP-TD, where'XXX' is the power output from 240 W to 300-W with the following electrical ratings typical at 250.W @ Standard Test Condition (STC): Output Voltage Range (Vout): 16 — 32 V (Voc*) Maximum Output Current (Imax): 9.5 A *For modules with Smart Curve function the Voc is adjustable and is programmed only at the factory based on the PV module voltage, Photovoltaic Modules with maximum system voltage of I OOOV do or 1500 V do and Type 1 module fire performance, Model Series CS3U-XXXMS-H, where'XXX' is the power output from 350 W to -400 W with the following electrical ratings typical at 400 W @ Standard Test Condition (STC): Open Circuit Voltage (Voc); 48.6 V Short Circuit Current (Isc): 10.33 A Operating Voltage (Vpmax): 40.8 V Current at Operating Voltage (Ipmax): 9.81 A Photovoltaic Modules with maximum system voltage of 1 OOOV do or 1500 V do and Type 1 fire performance, Model Series CS3U-XXXP-H, where'XXX' is the power output from 295 W to 360 W with the following electrical ratings typical at 360 W @ Standard Test Condition (STC): S A CSA Group Certificate: 2284121 Project: 70143782 Open Circuit Voltage (Voc): 46.7 V Short Circuit Current (Isc): 9.68 A Operating Voltage (Vpmax): 39.2 V Current at Operating Voltage (Ipmax): 9.19 A Master Contract: 249143 Date Issued: 2017-06-27 Photovoltaic Modules with maximum system voltage of 1000V do or 1500 V do and Type 1 module fire performance, Model Series CS3U-XXXMS, where'XXX' is the power output from 350 W to 400 W with the following electrical ratings typical at 400 W @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 48.6 V Short Circuit Current (Isc): 10.33 A Operating Voltage (Vpmax): 40.8 V Current at Operating Voltage (Ipmax): 9.81 A Photovoltaic Modules with maximum system voltage of 1000V do and Type l module fire performance, Model Series CS3K-XXXMS, where 'XXX' is the power output from 280 W to 330 W with the following electrical ratings typical at 330 W @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 40.5 V Short Circuit Current (Isc): 10.30 A Operating Voltage (Vpmax): 33.7 V Current at Operating Voltage (Ipmax): 9.80 A Photovoltaic Modules with maximum system voltage of 1000V do or 1500 V do and Type I fire performance, Model Series CS3U-XXXP, where'XXX' is the power output from 295 W to 360 W with the following electrical ratings typical at 360 W @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 46.7 V . Short Circuit Current (Isc): 9.68 A Operating Voltage (Vpmax): 39.2 V Current at Operating Voltage (Ipmax): 9.19 A _ Photovoltaic Modules with maximum system voltage of 1000V do and Type 1 fire performance, Model Series CS3K-XXXP, where 'XXX' is the power output from 250 W to 310 W with the following electrical ratings typical at 310 W @ Standard Test Condition (STC): Open Circuit Voltage (Voc): 39.1 V Short Circuit Current (Isc): 9.96 A Operating Voltage (Vpmax): 32.4 V Current at Operating Voltage (Ipmax): 9.57 A Notes: 1. Rated electrical characteristics are within +/-10% of measured values at Standard Test Conditions of 100 mW/cm2 irradiance, AM 1.5 spectrum, and cell temperature of 25°C. SP CSA Group FF Certificate: 2284121 Master Contract: 249143 Project: 70143782 Date Issued: 2017-06-27 2. A maximum series fuse rating of 20A is only for module Model Series CS6P-XXXP=SD, CS6K-XXXP-SD, CS6P-XXXM-SD, CS6K-XXXMS-SD and CS6K-XXXM-SD 3. A maximum series fuse rating of 30A is only for module Model Series CS3U-XXXMS-H, CS3U-XXXP-H, CS3U-XXXMS, CS3U-XXXP, CS3K-XXXMS, CS3K-XXXP APPLICABLE REQUIREMENTS ULC/ORD-C]703-01 - Flat -Plate Photovoltaic Modules and Panels UL_ 1703-3`d Edition Flat -Plate Photovoltaic Modules and Panels 16-02-18 r Data Sheet Enphase Microinverters t Enphase IQ 6 and IQ 6+ Microinverters The high-powered smart grid -ready Enphase IQ 6 Micro'" and Enphase IQ 6+ Micro'" dramatically simplify the installation process while achieving the highest efficiency for module -level power electronics. Part of the Enphase IQ System, the IQ,6 and IQ 6+ Micro integrate seamlessly with the Enphase . IQ Envoy'", Enphase Q Aggregator'", Enphase IQ Battery", and the Enphase Enlighten'" monitoring and analysis software. The IQ 6 and IQ 6+ Micro extend the reliability standards set forth by previous generations and undergo over a million hours of power -on testing. Enabling Enphase to provide an industry-leading warranty of up to 25 years. Easy to Install Lightweight and simple Faster installation with improved two -wire cabling Built-in rapidshutdown compliant (NEC 2014) Productive and Reliable Optimized for high powered 60 -cell and 72 - cell* modules More than a million hours of testing Class II double -insulated enclosure Smart Grid Ready Complies with fixed power factor, voltage and frequency ride -through requirements Remotely updates to respond to changing grid requirements Configurable for varying grid profiles * The IQ 6+ Micro is required to support 72 -cell modules 1 ENPHASE. To learn more about Enphase offerings, visit enphase.com �./ Enphase IQ 6 and IQ 6+ Microinverters • - INPUT DATA (DC) LCommonly used module pairings' . ___._-_ -_ Module compatibility Maximum input DC voltage Peak power tracking voltage Operating range Min/Max start voltage Max DC short circuit current (modulelsc) IQ6-60-2-US AND IQ6-60-5-US 195W -330W+ 60 -cell PV modules only 48V 27V -37V 16V -48V 22V/48V �15A 235W -400W+ J 60 -cell and 72 -cell PV modules 62V 27V -45V 16V -62V ^� 22V/62V tse ' Overvoltage class DC port II N II DC port backfeed'under single fault �I ^�0 A_ _6A PV array configuration _ _ 1 x 1 ungrounded array; No additional DC side protection required; AC side protection requires max 20A per branch circuit OUTPUT DATA (AC) IQ6-60-2-US AND IQ6-60-5-US IQ6PLUS-72-2-US AND IQ6PLUS-72-5-US L Peak output power 240 VA 290 VA Maximum continuous output power 230 VA 280 VA Nominal voltage/range2 240 V / 211 264 V 208 V (1 m) / 183-229 V 240 V % 211-264 V 208V(10)/183 -2_29V Nominal output current 0.96 A� 1.11 A 1.17 A 1.35 A Nominalfrequency 60 Hz 60 Hz Extended frequency range 47 - 68 Hz �. 47 68 Hz Power factor at rated power r r 1.0 F _ ' " ' N' _ 1.0 Maximum units per 20 A branch circuit 16 (240 VAC) 13 (240 VAC) ~ 14 (single-phase 208 VAC) 11 (single-phase 208 VAC) } OvervoltI a class AC port AC port backfeed under single fault 0 A T 0 A Powerfactor(adjustable) v _ __ .. 0.7 leading... 0.7 lagg-ing 0.7 I'e'adi.ng... -0.7 legging t EFFICIENCY @240 V @208 V (10) @240 V @208V(14)) CEC weighted efficiency 97.0 V 96.5% 97.0% 96.5% MECHANICAL DATA Ambient temperature range -40°C to +65°C Relative humidity range 4% to 100% (condensing) � - Connector type MC4 or Amphenol H4 UTX _ Dimensions (WxHxD) 219 mm x 191 mm x 37.9 mm (without bracket) Weight _ 1.5 kg (3.3 lbs) Cooling Natural convection - No fans Approved for wet locations Yes Pollution degree _ PD3 Environmental category / UV exposure rating Outdoor - NEMA 250, type 6 (11667) FEATURES Communication Power line Monitoring M - Enlighten Manager and MyEnlighten monitoring options _ Compatible with Enphase IQ Envoy Compliance _ J UL 62109-1, U1_1741/IEEE1547, FCC Part 15 Class B, ICES -0003 Class -B, ' CAN/CSA-C22.2 NO. 107.1-01 This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC -2014 and NEC -2017 section 690.12 and C22.1-2015 Rule 6.4-218 Rapid Shutdown of PV Systems, for AC and DC conductors, when installed according manufacturer's instructions. i 4 1. No enforced DC%AC ratio. See the compatibility calculator at enphase.com/en-us/support/module-compatibility. 2. Nominal voltage range can be extended beyond nominal if required by the utility. To learn more about Enphase offerings, visit enphase.com 2017 Enphase Energy. All rights reserved. All trademarks or brands used are the property of Enphase Energy, Inc. ` E N P H A S E. 2017-05-01 , ®fid IRONRIDGE Roof' Mount System. • - • ice- _ - -• - . Built for solar's toughest roofs. IronRidge builds the strongest roof mounting system in solar. Every component has been tested to the limit - and proven in extreme environments. r� , Our rigorous approach has led to unique structural features, such as curved rails and reinforced flashings, and is also why our products are fully certified, code compliant and backed by a 207year warranty: ` Strength Tested • . PE Certified ; M ' - All components evaluated for superior, ` ® Pre -stamped engineering letters structural performance. - - available in most states: Class A Fire Rating' - - Design Software - Certified to maintain the fire resistance Online tool generates a complete bill of rating of the existing roof. s materials in minutes.' Integrated Grounding y 20 Year Warranty' ' UL 2703 system eliminates separate Twice the protection offered by module grounding components. competitors. XR Rails XR10 Rail XR100 Rail XR1000 Rail H Datasheet Internal Splices Q A low -profile mounting rail for regions with light snow. • 6' spanning capability • Moderate load capability • Clear & black anod. finish Attachments FlashFoot Anchor, flash, and mount with all -in -one attachments. • Ships with all hardware • IBC & IRC compliant • Certified with XR Rails Clamps & Grounding End Clamps The ultimate residential solar mounting rail. 8' spanning capability • Heavy load capability • Clear & black anod. finish Slotted L -Feet Drop-in design for rapid rail attachment. • High -friction serrated face • Heavy-duty profile shape • Clear & black anod. finish A heavyweight mounting rail for commercial projects. • 12' spanning capability • Extreme load capability • Clear anodized finish Standoffs All rails use internal splices for seamless connections. • Self -tapping screws • Varying versions for rails • Grounding Straps offered Tilt Legs Raise flush or tilted r systems to various heights. • Works with vent flashing • Ships pre -assembled • 4" and 7" Lengths Grounding Mid Clamps Q T Bolt Grounding Lugs Q Tilt assembly to desired angle, up to 45 degrees. • Attaches directly to rail • Ships with all hardware • Fixed and adjustable Accessories Slide in clamps and secure modules at ends of rails. • Mill finish & black anod. • Sizes from 1.22" to 2.3" • Optional Under Clamps Free Resources Attach and ground modules in the middle of the rail. • Parallel bonding T -bolt • Reusable up to 10 times • Mill & black stainless Design Assistant =_'• Go from rough layout to fully - - engineered system. For free Go to IronRidge.com/rm - -- --- --- 1 Ground system using the rail's top slot. • Easy top -slot mounting • Eliminates pre -drilling • Swivels in any direction Provide a finished and organized look for rails. • Snap -in Wire Clips • Perfected End Caps •. UV -protected polymer A d NABCEP Certified Training VO Earn free continuing education credits, AQ44 s while learning more about our systems. V Go to IronRidgexom/training © 2014 IronRidge, Inc. All rights reserved. Visit www.ironridgeX or call 1-800-227-9523 for more information. Version 1.42 /��_ LOCATION MAP 01 C, Q?,OFESS/Oyk �N- '2 No. C58724 Exp. 3-31-19 DATE: 9/29/2017 ,271' OF APPLICABLE CODES / NOTES: THIS SOLAR PHOTOVOLTAIC, SYSTEM SHALL BE INSTALLED IN September 30, 2017 ACCORDANCE WITH THE REQUIREMENTS SPECIFIED IN THE 2016 CBC, 2016 CRC, 2016 CFC, 2016 CALIFORNIA GREEN BUILDING www. Loyd W Martin .c6m STANDARDS CODES, AND ARTICLE 690 OF THE 2016 CEC, AND ALL Solar Structures Engineering' ADDITIONAL APPLICABLE BUILDING CODES'- (REFER TO PAGE 6) #2017-3790 Structural Only 41. SYSTEM SPECIFICATIONS: MODULE: CANADIAN SOLAR CS6K-270P.(39 MODULES) STRING - INVERTER: ENPHASEIQ6+ AZIMUTH(S): 180* TI LT(S) 19* BUSBAR RATING: 400A 380 ORANGE ST. MAIN BREAKER: 200A CHICO, CA 95928 ATTACHMENT, TYPE: IRONRDIGE GROUNUIVIUUNI 1(855)360 -JOIN LIC #: 1021484 280' PROPERTY LINE 85 ROBERTS CT TABLE OF CONTENTS DRAWN BY: CHICO, CA 95973 P.1 COVER SHEET CLIENT PHONE # P.2 SITE PLAN - JBH 530-519-7896 P.3 MODULE LAYOUT REV. JURISDICTION: PA --MOUNTING DETAILS BUTTE COUNTY P.5 ELETRICAL SCHEMATIC UTILITY: P.6 -ELETRICAL NOTES PG&E P.7 STICKER / PLACECARDS (E) UTILITY METER/PANELBOARD r - & INTERCONNECTION -0 m DRIVEWAY _ - (E) SEPTIC SYSTEM,. PROPERTY LINE - - (N) PV AC DISCONNECT. (N) UNDERGROUND CONDUIT —25 FT (N) COMBINER BOX (N) PV AC DISCONNECT 27' (E) PROPOSED RESIDENCE 199' - ;' / �OQROFESS/pN9l W, { s I cCO Z i No. C58724 * Exp. 3-31-19 105' s�q C i v i` R100 lF OF C (N) PV MODULE ARRAY. i September 30, 2017 REFER TO PAGE 3 FOR _ www. Loyd W Martin .com RACKING & STRINGING Solar Structures Engineering 4/ INFORMATION. - #2017-3790 Structural Only _ 1 SITE PLAN PV2 SCALE 1 : 10 J 1 85 ROBERTS CT TABLE OF CONTENTS y y y y y # OF MODULES: a CHICO, CA 95973 P.1 COVER SHEET y 39 : (10.530 kW) AZIMUTH(S): �"_' CLIENT PHONE # P.2 SITE. PLAN 530-519-7896 NOTABLE LANDSCAPE 180° P.3 MODULE LAYOUT MODULE.TYPE: JURISDICTION: , /l// , 1/./, , 380 ORANGE sr. P.4 .MOUNTING DETAILS CANADIAN SOLAR TILT(S): CHICO, CA 95928 BUTTE COUNTY. P.5 ELETRICAL SCHEMATIC 19° 1(855)360 -JOIN UTILITY: P.6 ELETRICAL NOTES )'BRUSH CLEARANCE CS6K-270P - LIC #: 1021484 PG&E P.7 STICKER / PLACECARDS 7'-6„ QROF ESS/p— �CO W IV9l I I I I I I I I C9 d No. C58724� bo`�® * Exp. 3-31-19 * �V �53 TF OF C A\ -\F �Q September 30, 2017 www.'Loyd W Martin .com DRILLED FOUNDATION MODULE CLAMP PV MODULE (3) CIRCUITS OF (13) Solar Structures Engineering PIER (TYP) #2017-3790 Structural Only 1 MODULE PLAN PV3 SCALE 1 : 10 - - VERIFY ALL OBSTRUCTIONS IN THE FIELD 85 ROBERTS CT TABLE OF CONTENTS - VERIFY ALL DIMENSIONS IN THE FIELD. CHICO, CA 95973 P.1 COVER SHEET - WHERE INDICATED ON PLAN MIN. DIMENSIONS ARE REQUIRED PER THE CLIENT PHONE # P.2 SITE PLAN "SOLAR PV INSTALLATION GUIDELINE° 530-519-7896 P.3 MODULE LAYOUT - PROVIDE RAIL SPLICES AS REQUIRED BY 380 ORANGE ST. JURISDICTION: PA MOUNTING DETAILS MANUFACTURE'S GUIDELINES BUTTE COUNTY - PV MODULE CANNOT BE INSTALLED OVER, 3' FIRE CODE OFFEST CHICO, CA 95928 P.5 ELETRICAL SCHEMATIC OR BLOCK ATTIC VENTS, PLUMING VENTS, 1(855)360 -JOIN UTILITY: P.6 ELETRICAL NOTES FURNACE OR WATER HEATER VENTS ETC. LIC #: 1021484 PG&E P.7 STICKER / PLACECARDS CANTILEVER. NOT S -UP - PV SYSTEM PLAN DETAIL Scale: 1/2"=1'-0" CANTILEVER. NOT 3" CROSS PIPE 1 3" PIER PIPE 1 DIAGONAL BRACING, AS NEEDED ENGINEERED FOUNDATION 2'-6" MAX. EXPOSED �— 9'47 ABOVE GRADE B S -UP - PV SYSTEM SIDE SECTION Scale: 3/4"=1'-0" 1. SCHEDULE 40 PIPE OR ALLIED MECHANICAL TUBING (8GA WALL THICKNESS) 85 ROBERTS CT CHICO, CA 95973 CLIENT PHONE # 530-519-7896 380 ORANGE ST. JURISDICTION: CHICO, CA 95928 BUTTE COUNTY 1611 1(855)360 -JOIN UTILITY: LIC #: 1021484 PG&E TABLE OF CONTENTS P.1 COVER SHEET P.2 SITE PLAN P.3 MODULE LAYOUT P.4 MOUNTING DETAILS . P.5 ELETRICAL SCHEMATIC P.6 ELETRICAL NOTES P.7 STICKER/ PLACECARDS PIPE FITTINGS DETAIL 3"=1'-0" Im PV MODULE, BY OTHERS XR1000 RAIL IRONRIDGE 3" RAIL CONNECTOR 'PIPE 1 IRONRIDGE 3" TOP CAP SUPPORT PER PLANS NATURAL GRADE "'✓ MODULE, Y OTHERS R1000 RAIL tONRIDGE 'RAIL ONNECTOR :ONRIDGE 'TOP CAP 'PIPE 1 . [W V Z 0 a D PIPE FITTINGS DETAIL IRONRIDGE MID CLAMP PV MODULE FRAME IRONRIDGE RAIL \ LL L In a m m Q rn p �\ DETAIL, MID CLAMP FRONT 6"=1'-0" x LL v a a U F U w a w IRONRIDGE END CLAMP W it L, " vV- w PV MODULE FRAME3 z 0 R w o f Z w y w� . FX, : \ IRONRIDGE RAIL ; ti n DETAIL, END CLAMP FRONT iiaj�® 16" DIAMETER X 4.33 FT. DEEP PV MODULE FRAME CONCRETE PIER; F'C = 2500 PSI OR BETTER '-n„ IRONRIDGE MID CLAMPROFESS/p WRAP (2) LAYERS OF 14 -GAUGE GALVANIZED STEEL WELDED WIRE E DETAIL MID CLAMP PLAN IRONRIDGE RAIL PV MODULE FRAME IRONRIDGE END CLAMP Q I/ I 411 7FC September 30, 2017 G DETAIL END CLAMP PLAN 6"=1'-0" www. Loyd W Martin .com PV ARRAY FOUNDATION PIER DETAIL Solar Structures Engineering SECTION VIEW #2017-3790 Structural Only TO UTILITY GRID lJ 120/240V SINGLE PHASE BI-DIRECTIONAL UTILITY METER (N) 45A 2 -POLE BREAKER SHALL BE INSTALLED OPPOSITE MAIN BREAKER 4T MAIN RESIDENCE NOT CENTER FED PANEL MAIN ELECTRICAL PANEL (E) 400 AMP 120/240 • I L7 J_I MOUNTS AND EQUIPMENT ENCLOSURES GROUNDED' TO MAIN PANEL GROUND �° 0 EATON 60A AC DISCONNECT MANUFACTURER ENPHASE MODEL IQ 6+ ELECTRICAL SPECIFICATIONS RATED AC VOLTAGE 240V PV TDULE$ - 11L APPROVED MAN FACTUURLW CANADIAN SOLAR MODEL CS6K-270M ELECTRICAL.SPECIFICATIONS RATED POWER OUTPUT @ STC 270 ' 290W OPEN CIRCUIT VOLTAGE (Voc) 38.2V MAX INPUT VOLTAGE MAX POWER VOLTAGE (Vmp) 31.3V SHORT CIRCUIT CURRENT (Isc) 9.31A + MAX POWER CURRENT (Imp) 8.80A MPPT VOLTAGE RANGE Voc CORRECTION FACTOR (%/deg C) -0.31 % Vmp/Pmp CORRECTION FACTOR .-0.41% TO UTILITY GRID lJ 120/240V SINGLE PHASE BI-DIRECTIONAL UTILITY METER (N) 45A 2 -POLE BREAKER SHALL BE INSTALLED OPPOSITE MAIN BREAKER 4T MAIN RESIDENCE NOT CENTER FED PANEL MAIN ELECTRICAL PANEL (E) 400 AMP 120/240 • I L7 J_I MOUNTS AND EQUIPMENT ENCLOSURES GROUNDED' TO MAIN PANEL GROUND �° 0 EATON 60A AC DISCONNECT MANUFACTURER ENPHASE MODEL IQ 6+ ELECTRICAL SPECIFICATIONS RATED AC VOLTAGE 240V J- BOX UNDER ARRAY SEALED TIGHT NON-FUSED -NEMA TYPE3 MIN. 3OX 0 EATON 60A AC DISCONNECT UNDERGROUND 2" PV AC CONDUIT (3) #4 CU THWN-2 QROFESS/0\ (1) #8 CU GROUND �O 9� 90°C WET & DRY i No. C58724 Exp. 3-31-19 CIVIC �Q 9TF OF C September 30, 2017 www. Loyd W Martin .com Solar Structures Engineering #2017-3790 Structural Only 85 ROBERTS CT CHICO, CA 95973 CLIENT PHONE # 530-519-7896 JURISDICTION: BUTTE COUNTY UTILITY: PG&E IYSTEM OVERVIEW OF MODULES IN SERIES (CIRCUIT SIZE) 13 OF MODULES IN PARALLEL (# CIRCUITS) 3 - IUMBER OF MODULES PER INVERTER 1 ,RRAY RATED DC POWER OUTPUT @ STC 10.530 kW ,* #6 CU AWG BARE WIRE (TYP) - BOUNDING MODULES & RAILS OR WEEBS BONDING & 4 GROUNDING WASHERS . 'J- BOX UNDER ARRAY SEALED TIGHT NON-FUSED -NEMA TYPE3 MIN. ENVOY S XAM1-120M COMBINER BOX o - COMPONENT CONNECTIONS WILL BE MADE WITH: (UNLESS OTHERWISE SPECIFIED) ' EXTERIOR 4° EMT AC CONDUIT OR INTERIOR ROMEX 10-3 (3) #4 CU THWN-2 ; (1) #8 CU GROUND = €t 900C WET & DRY BUSBAR RATING: 400A MAIN BREAKER: 200A # OF MODULES: 39 380 ORANGE ST. SYSTEM SIZE: 10.530 kW cHlco, CA 95928 1(855)360 -JOIN LIC #: 1021484 J -BOX TERMINATOR CAP ON LAST CABLE CONNECTOR OF AC TRUNK CABLE (TYP) 13 PANELS- BRANCH CIRCUIT #1-3 MICROA ERMRNI MICR° WCMRQ MIGRPI ERT 12 MICR0.R ERME 13 ICRO - INVERTER (TVP.) + MICRO -INVERTER TRUNK CABLE, 1 PHASE 90°c, 600V, WET/DRY, WITH MICRO -INVERTER PRE-INSTALLED CONNECTORS OPEN AIR CONDUCTORS, NOT IN A CONDUIT BLACK -L1 – RED-L2,WITH-NEUTRAL GREEN -GROUND UL1741, UL 746 C,F1, IEC 60529 IP67 (TYP) t EXTERIOR 2" EMT AC CONDUIT (3) #10 CU THWN-2® (1) #8 CU GROUND 90°C WET &DRY TABLE OF CONTENTS P.1 COVER SHEET P.2 SITE PLAN P.3 MODULE LAYOUT PA MOUNTING DETAILS P.5 ELETRICAL SCHEMATIC P.6 - ELETRICAL- NOTES P.7 STICKER / PLACECARDS CEC EFFICIENCY - 1 11 97.0% MAX POWER OUTPUT @ STC 290W MAX INPUT VOLTAGE .62V MAX INPUT CURRENT 15A MPPT VOLTAGE RANGE 211V - 264V MAX OUTPUT CURRENT _• 1.17A J- BOX UNDER ARRAY SEALED TIGHT NON-FUSED -NEMA TYPE3 MIN. 3OX 0 EATON 60A AC DISCONNECT UNDERGROUND 2" PV AC CONDUIT (3) #4 CU THWN-2 QROFESS/0\ (1) #8 CU GROUND �O 9� 90°C WET & DRY i No. C58724 Exp. 3-31-19 CIVIC �Q 9TF OF C September 30, 2017 www. Loyd W Martin .com Solar Structures Engineering #2017-3790 Structural Only 85 ROBERTS CT CHICO, CA 95973 CLIENT PHONE # 530-519-7896 JURISDICTION: BUTTE COUNTY UTILITY: PG&E IYSTEM OVERVIEW OF MODULES IN SERIES (CIRCUIT SIZE) 13 OF MODULES IN PARALLEL (# CIRCUITS) 3 - IUMBER OF MODULES PER INVERTER 1 ,RRAY RATED DC POWER OUTPUT @ STC 10.530 kW ,* #6 CU AWG BARE WIRE (TYP) - BOUNDING MODULES & RAILS OR WEEBS BONDING & 4 GROUNDING WASHERS . 'J- BOX UNDER ARRAY SEALED TIGHT NON-FUSED -NEMA TYPE3 MIN. ENVOY S XAM1-120M COMBINER BOX o - COMPONENT CONNECTIONS WILL BE MADE WITH: (UNLESS OTHERWISE SPECIFIED) ' EXTERIOR 4° EMT AC CONDUIT OR INTERIOR ROMEX 10-3 (3) #4 CU THWN-2 ; (1) #8 CU GROUND = €t 900C WET & DRY BUSBAR RATING: 400A MAIN BREAKER: 200A # OF MODULES: 39 380 ORANGE ST. SYSTEM SIZE: 10.530 kW cHlco, CA 95928 1(855)360 -JOIN LIC #: 1021484 J -BOX TERMINATOR CAP ON LAST CABLE CONNECTOR OF AC TRUNK CABLE (TYP) 13 PANELS- BRANCH CIRCUIT #1-3 MICROA ERMRNI MICR° WCMRQ MIGRPI ERT 12 MICR0.R ERME 13 ICRO - INVERTER (TVP.) + MICRO -INVERTER TRUNK CABLE, 1 PHASE 90°c, 600V, WET/DRY, WITH MICRO -INVERTER PRE-INSTALLED CONNECTORS OPEN AIR CONDUCTORS, NOT IN A CONDUIT BLACK -L1 – RED-L2,WITH-NEUTRAL GREEN -GROUND UL1741, UL 746 C,F1, IEC 60529 IP67 (TYP) t EXTERIOR 2" EMT AC CONDUIT (3) #10 CU THWN-2® (1) #8 CU GROUND 90°C WET &DRY TABLE OF CONTENTS P.1 COVER SHEET P.2 SITE PLAN P.3 MODULE LAYOUT PA MOUNTING DETAILS P.5 ELETRICAL SCHEMATIC P.6 - ELETRICAL- NOTES P.7 STICKER / PLACECARDS EACH MODULE TO BE GROUNDED USING THE SUPPLIED CONNECTION POINT - THIS SOLAR PHOTOVOLTAIC SYSTEM SHALL BE INSTALLED .INPm6 PER MANUFACTURE'S REQUIREMENTS. ALL SOLAR MODULES EQUIPMENT, AND ACCORDANCE -WITH THE REQUIREMENTS SPECIFIED IN ARTICLE 690 THE METALLIC COMPONENTS ARE TO BE BONDED. IF THE EXISTING OF THE 2016 CEC AND ALL APPLICABLE BUILDING CODES. GROUNDING ELECTRODE SYSTEM CAN NOT BE VERIFIED OR IS ONLY METALLIC , WATER PIPING, IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A ACCESS TO THE ELECTRICAL WIRE SHALL BE.RESTRICTED TO - SUPPLEMENTAL GROUNDING ELECTRODE. - QUALIFIED PERSONAL ONLY AS REQUIRED BY ARTICLE 690 OF THE 2016 CEC. -'ALL PLAGUES AND SINGAGE REQUIRED BY THE LATESTEDITION.OF NATIONAL = ELECTRICAL CODE. REFER TO SHEET 7 (STICKERS AND PLACECARDS). LABEL - THE PHOTOVOLTAIC ARRAY(S) SHALL BE PROVIDED WITH DC Y SHALL BE METALLIC OR PLASTIC, ENGRAVED OR MACHINED PRINTED IN A GROUND -FAULT PROTECTION. (CEC 690.5) CONTRASTING COLOR TO THE PLAQUE. PLAQUE SHALL BE UV RESISTANT IF EXPOSED TO SUNLIGHT: ALL CONDUCTORS SHALL BE TYPE 90 DEGREE C RATED. 690.318) - DC CONDUCTORS SHALL BE RUN IN EMT AND/OR MC (METAL CALD CABLE) AND r SHALL BE LABELED, "CAUTION DC CIRCUIT" OR EQUIV. EVERY 5 FT. - ALL EXPOSED PHOTOVOLTAIC SYSTEM CONDUCTORS SHALL BE TYPE USE -2 OR PV WIRE. (CEC 690.31 B) - EXPOSED NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH 250.134 OR 250.136 (A) - ALL CONDUCTORS SHALL BE TYPE -90 DEGREE C RATED (CEC 690.318) - CONFIRM LINE SIDE VOLTAGE AT ELECTRICAL UTILITY SERVICE PRIOR TO - - CONNECTING INVERTER. VERIFY SERVICE VOLTAGE IS WITHIN INVERTER -THE INSTALLATION OF EQUIPMENT AND ALL ASSOCIATED WIRING VOLTAGE_ OPERATIONAL RANGE. AND INTERCONNECTIONS SHALL BE PERFORMED ONLY BY QUALIFIED PERSONS (CEC 690.4) . - OUTDOOR EQUIPMENT SHALL BE NEMA -3R RATED OR BETTER- ELECTRICAL , CONTRACTOR TREQUIPER NEC. PROVIDE RED CONDUIT EXPANSION JOINTS AND � �oQROWESS ANCHOR CONDUITRUNSAS ioN�l - ALL WIRING MUST BE PROPERLY SUPPOTED BY DEVICES OR MECHANICAL a No. 058724 MEANS DESIGNED AND LISTED FOR SUCH USE, AND FOR ROOF -MOUNTED * Exp. 3-31-19 SYSTEMS, WIRING MUST BE PERMANENTLY AND COMPLETELY HELD OFF OF THE ROOF SURFACE. NEC 110.2 - 110.4 / 300.4 OF CP,0F t September 30. 2017 •-ALL PV METERS TO BE WITHIN 5 FT OF ANOTHER. � � ' www. Loyd W Martin .com - PV METERS TO BE INSTALLED CORRECTLY, SUPPLIED FROM THE TOP JAWS. Solar Structures Engineering . #2017-3790 Structural' Only - ALL ROOF PENETRATIONS MUST BE FLASHED. SIMPLY CAULKING DOES NOT SUFFICE. 85 ROBERTS CT TABLE OF CONTENTS CHICO, CA 95973 P.1 COVER SHEET CLIENT PHONE # P.2 SITE PLAN 530-519-7896 P.3 MODULE LAYOUT 380 ORANGE ST. JURISDICTION: PA MOUNTING DETAILS CHICO, CA 95928 BUTTE COUNTY P.5 ELETRICAL SCHEMATIC 1(855)360 -JOIN UTILITY: P.6 ELETRICAL NOTES LIC # : 1021484 PG&E P.7 STICKER / PLACECARDS - 41' 2" PLACED ON OR ADJACENT TO THE PLACED ON THE INVERTER, OR PLACED P.m 71 WARNING MAIN PHOTOVOLTAIC ELECTRIC SHOCK HAZARD SYSTEM AC DISCONNECT IF GROUNDED FAULT IS INDICATED ... ,; = � ; � � pig211 LOCATED ON THE GROUNDED CONDUCTORS AC DISCONNECT'! MAY BE UNGROUNDED AND ENERGIZED M h 1 M V IJIDLC Ll k-otA I IVIV' 4" I SWITCH FOR SiOLARi PV SYSTEM • •' ' '111061 fPLACED NEXT TO THE SOLAR BREAKER 5.711. _ �r r DISCONNECTING MEANS LOCATED ON THE DC DISCONNECT PORTION OF THE INVERTER , 4" , f T, v%m QESS/pamn - �o ,w, q� .95 2 - _ � No. C58724 � � p0 0 " 0 o 2 Exp. 3-31-19 * - e�' ►�i �wu wwl :51' s` - - rq @M%7m Mum OF 2" L 21' September 30, 2017 www. Loyd W Martin .com r ° e • ° , ° Q -' ° _ __. LOCATED ON MAIN SERVICE PANEL .,Solar Structures Engineering . - #2017-3790 Structural Only NOTE: STICKERS ARE WHITE LET_ TERS ON RED BACKGROUND - 4 85 ROBERTS CT • TABLE OF CONTENTS CHICO, CA 95973 P.1 COVER SHEET - CLIENT PHONE # P.2 SITE PLAN 530-519-7896 P.3 MODULE LAYOUT STICKERS AND PLACEC/�RDS , . S 380 ORANGE ST. JURISDICTION: PA MOUNTING DETAILS CHICO, CA 95928 BUTTE COUNTY P.5 ELETRICAL SCHEMATIC t 1(855)360 -JOIN UTILITY: P.6 ELETRICAL NOTES • - ._ _ LIC #: 1021484 PG&E - P.7 STICKER / PLACECARDS S 2" PLACED ON OR ADJACENT TO THE PLACED ON THE INVERTER, OR PLACED P.m 71 WARNING MAIN PHOTOVOLTAIC ELECTRIC SHOCK HAZARD SYSTEM AC DISCONNECT IF GROUNDED FAULT IS INDICATED ... ,; = � ; � � pig211 LOCATED ON THE GROUNDED CONDUCTORS AC DISCONNECT'! MAY BE UNGROUNDED AND ENERGIZED M h 1 M V IJIDLC Ll k-otA I IVIV' 4" I SWITCH FOR SiOLARi PV SYSTEM • •' ' '111061 fPLACED NEXT TO THE SOLAR BREAKER 5.711. _ �r r DISCONNECTING MEANS LOCATED ON THE DC DISCONNECT PORTION OF THE INVERTER , 4" , f T, v%m QESS/pamn - �o ,w, q� .95 2 - _ � No. C58724 � � p0 0 " 0 o 2 Exp. 3-31-19 * - e�' ►�i �wu wwl :51' s` - - rq @M%7m Mum OF 2" L 21' September 30, 2017 www. Loyd W Martin .com r ° e • ° , ° Q -' ° _ __. LOCATED ON MAIN SERVICE PANEL .,Solar Structures Engineering . - #2017-3790 Structural Only NOTE: STICKERS ARE WHITE LET_ TERS ON RED BACKGROUND - 4 85 ROBERTS CT • TABLE OF CONTENTS CHICO, CA 95973 P.1 COVER SHEET - CLIENT PHONE # P.2 SITE PLAN 530-519-7896 P.3 MODULE LAYOUT STICKERS AND PLACEC/�RDS , . S 380 ORANGE ST. JURISDICTION: PA MOUNTING DETAILS CHICO, CA 95928 BUTTE COUNTY P.5 ELETRICAL SCHEMATIC t 1(855)360 -JOIN UTILITY: P.6 ELETRICAL NOTES • - ._ _ LIC #: 1021484 PG&E - P.7 STICKER / PLACECARDS S