HomeMy WebLinkAboutB17-2755 041-030-152SPRINKLER SYSTEM HYDRAULIC ANALYSISPage 1
C:\HASS74\ RESIDENCE.SDF
JOB TITLE w_ -RESIDENCE
WATER SUPPLY DATA
SOURCE
STATIC
RESID. FLOW
NODE
PRESS._
PRESS. @
TAG
(PSI)
(PSI) (GPM)
.SOURCE
$0.0
40.0 42.0
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE
TOTAL HOSE STREAM ALLOWANCE AT SOURCE
OTHER HOSE STREAM ALLOWANCES
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS
NODE ANALYSIS DATA
NODE TAG ELEVATION
(FT)
1
2
10
11
12
13
14
20
21
22
30
31
32
40
41
TOR
'AOR
SOURCE
9.0
9.0
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
1.0
-3.0
NODE TYPE
K= 4.90
K= 4.90
F � F
SOURCE
AVAIL. TOTAL REQ'D
PRESS. @ DEMAND PRESS.
(PSI) (GPM) (PSI)'
43.1
34.4 GPM
5.0 GPM
0.0 GPM
29.4 GPM
PRESSURE
(PSI)
9.0
8.9
9.5
9.8
10.0
10.4
10.9
9.3
10.8
10.9
8.8
9.3
10.6
8.8
9.1
11.8
17.1
20.0
34.4 20.0
DISCHARGE
(GPM)
14.7
14.6
a � -
29.4
PERMIT #
BUTTE COUNTY DEVELOPMENT SERVICES
REVIEWED FOR
CODE COMPLIANCE
DATE BY L�
PC1/FILE
B17-2755
0:11-030-152
NOVEMBER 16, 2017
F/S FOR B1.7-1090
C -1b
STA E --LICENSE M
9w7t.
REP k*
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
C:\HASS74\ENGLEKING RE$IDENCE.SDF
JO$ TI2'LE: ENGLEKING RESIDENCE
PIPE DATA
PIPE TAG
END ELEV. NOZ.
NODES (FT) (K)
Pipe: 1
1 9.0 4.9
20 9.5 0.0
Pipe: 2
1 9.0 4.9
30 9.5 0.0
Pipe: 3
30 9.5 0.0
2 9.0 4.9
Pipe: 4
2 9.0 4.9
40 9.5 0.0
Pipe: 5
20 9.5 0.0
10 9.5 0.0
Pipe: 6
10 9.5 0.0
11 9.5 0.0
Pipe: 7
11 9.5 0.0
12 9.5 0.0
Pipe: 8
12 9.5 0.0
13 9.5 0.0
13
14
14
22
30
31
40
41
41
31
Pipe: 9
9.5
9.5
Pipe: 10
9.5
9.5
Pipe: 11
9.5
9.5
Pipe: 12
9.5
9.5
Pipe: 13
9.5
9.5
t t
t t
t t
t t
t t�
t
t t
t t�
LENGTH PRESS.
(FT) SUM.
(PSI)
6.50 PF 0.5
T PE -0.2
11.50 PV
7.25 PF 0.0
-- PE -0.2
7.25 PV
2.75 PF 0.1
T PE 0.2
7.75 PV
8.00 PF 0.1
T PE -0.2
13.00 PV
12.00 PF 0.2
E PE 0.0
17.00 PV
26.25 PF 0.2
---- PE 0.0
26.25 PV
16.00 PF 0.2
2T PE 0.0
26.00 PV
35.00 PF 0.4
ET PE 0.0
45.00 PV
34.50 PF 0.5
3E PE 0.0
49.50 PV
6.50 PF 0.0
-- - PE 0.0
6.50 PV
40.00 PF 0.5
G T PE 0.0
45.00 PV
40.50 PF 0.3
G ---- PE 0.0
40.50 PV
10.75 PF 0.2
G 2T PE 0.0
20.75 PV
Q(GPM)
DIA (IN)
PT
DISC. VEL(FPS)
HW(C)
(PSI)
(GPM)
FL/FT
-16.1
1.101
PL
9.0
14.7
5.4
150
FTG
9.3
0.0
0.046
TL
1.4
1.101
PL
9.0
14.7
0.5
150
FTG
8.8
0.0
0.000
TL
8.5
1.101
PL
8.8
0.0
2.9
150
FTG
8.9
14.6
0.014
TL
-6.1
1.101
PL
8.9
14.6
2.1
150
FTG
8.8
0.0
0.008
TL
-6.9
1.101
PL
9.3
0.0
2.3
150
FTG
9.5
0.0
0.009
TL
-6.9
1.101
PL
9.5
0.0
2.3
150
FTG
9.8
0.0
0.009
TL
-6.9
1.101
PL
9.8
0.0
2.3
150
FTG
10.0
0.0
0.009
TL
-6.9
1.101
PL
10.0
0.0
2.3
150
FTG
10.4
0.0
0.009
TL
-6.9
1.101
PL
10.4
0.0
2.3
150
FTG
10.9
0.0
0.009
TL
-6.9
1.394
PL
10.9
0.0
1.4
150
FTG
10.9
0.0
0.003
TL
-7.1
1.101
PL
8.8
0.0
2.4
150
FT
9.3
0.0
0.010
TL
-6.1
1.101
PL
8.8
0.0
2.1
150
FT
9.1
0.0
0.008
TL
-6.1
1.. 101
PL
9.1
0.0
2.1
150
FT
9.3
0.0
0.008
TL
LENGTH PRESS.
(FT) SUM.
(PSI)
6.50 PF 0.5
T PE -0.2
11.50 PV
7.25 PF 0.0
-- PE -0.2
7.25 PV
2.75 PF 0.1
T PE 0.2
7.75 PV
8.00 PF 0.1
T PE -0.2
13.00 PV
12.00 PF 0.2
E PE 0.0
17.00 PV
26.25 PF 0.2
---- PE 0.0
26.25 PV
16.00 PF 0.2
2T PE 0.0
26.00 PV
35.00 PF 0.4
ET PE 0.0
45.00 PV
34.50 PF 0.5
3E PE 0.0
49.50 PV
6.50 PF 0.0
-- - PE 0.0
6.50 PV
40.00 PF 0.5
G T PE 0.0
45.00 PV
40.50 PF 0.3
G ---- PE 0.0
40.50 PV
10.75 PF 0.2
G 2T PE 0.0
20.75 PV
NOTES:
1.101
Pipe:
SPRINKLER
SYSTEM HYDRAULIC ANALYSIS
Page 3
150
_
21
PE
9.5
C:\HASS74\ENGLEKING
RESIDENCE.SDF
1O9"TITLE:
ENGLEKING
RESIDENCE
1.394
9.5
0.0
9.3
PIPE TAG
150
FTG
Pipe:
17
Q(GPM)
DIA(IN) LENGTH
PRESS.
END
ELEV.
NOZ.
PT
DISC.
VEL(FPS)
HW(C) (FT)
SUM.
NODES
(FT)
(K)
(PSI)
(GPM)
0.0
FL/FT
(PSI)
Pipe:
14
1.394
PL
8.50
-13.2
1.101 PL 38.25
PF 1.4
31
9.5
0.0
9.3
0.0'
4.5
150 FTG E
PE 0.0
32
9.5
0.0
10.6
0.0
Pipe:
0.032 TL 43.25
PV
Pipe:
15
-29.4
TOR
TL 150.0
=13.2
1.394 PL 14.00
PF 0.1
32
9.5
0.0
10.6
0.0
2.8
150 FTG -- --
PE 0.0
21
9.5
0.0
10.8
0.0
0.010 TL 14.00
PV
NOTES:
1.101
Pipe:
16
PF,
1.4
150
9.2
21
PE
9.5
0.0
10.8
0.0
3.1
20
1.394
9.5
0.0
9.3
0.0
150
FTG
Pipe:
17
0.0
0.027
TL
-22.5
21
9.5
0.0
10.8
0.0
4.1
22
FTG
9.5
0.0
10.9
0.0
TL
20.50
Pipe:
18
1.394
PL
8.50
-29.4
22
150
9.5
0.0
10.9
0.0
6.2
TOR
37.50
9.5
0.0
11.8
0.0
110.00
PF
Pipe:
19'
FTG
3ETG
PE
-29.4
TOR
TL 150.0
9.5
0.0
11.8
0.0
6.2
BOR
1.0
0.0
17.1
0.0
Pipe:
20
-29.4
BOR
1.0
0.0
17.1
0.0
3.0
SOURCE
-3.0
SRCE
20.0
(N/A)
NOTES:
1.101
PL
78.50
PF,
1.4
150
FTG
2T
PE
0.0
0.016
TL
88.50
PV
1.394
PL
5.00
PF
0.1
150
FTG
----
PE
0.0
0.027
TL
5.00
PV
1.394
PL
2.50
PF
0.9
150
FTG
2ET
PE
0.0
0.044
TL
20.50
PV
1.394
PL
8.50
PF
1.6
150
FTG
3ETC
PE
3.7
0.044
TL
37.50
PV
2.003
PL
110.00
PF
1.1
150
FTG
3ETG
PE
1.7
0.008
TL 150.0
PV
1
7
ve_-,,
y
(1) Calculations were performed by the HASS 7.4 computer program
under license no. 27060373 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker-, GA 30084
(2) The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.006 gpm.
(3) Total pressure at each node is used in balancing the system.
Maximum water velocity is 6.2 ft/sec at pipe 18.
(4) PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
C:\HASS74\ENGLEKING RESIDENCE.SDF
JOB -TITLE: ENGLEKING RESIDENCE
PAGE: P
MATERIAL: CPVC HWC:
150
Diameter
Equivalent Fitting
Lengths
in Feet
(in)
E
T L
P R
C
G
Ell
Tee 45-e1L
couP teeRun
Ckvle
Gvlve
1.101
5.00
5.00 1.00
1.00 1.00
4.00
1.00
1.394
6.00
6.00 2.00
1.00 1.00
5.00
2.00
2.003
9.00
10.00 2.00
1.00 1.00
7.00
3.00
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
C:\HASS74\ENGLEKING RESIDENCE.SDF
JOB TITLE: ENGLEKING RESIDENCE o0
0
9
o -i N r
O O O O O O O cr
O O O
l0 LA C' M C4 .-=1
�Q:D0 aawcnv�axw - t�.�n �+--
I
0
0
0
O
a
0
0
m
0
0
N
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
_ C:\HASS74\ENGLEKING RESIDENCE.SDF
JOB TITLE: ENGLEKING RESIDENCE
WATER SUPPLY CURVE
60+
1
I
i
55+
l
50*
45\
0
P
40*
<-40.0 psi @ 42 gpm
R
(
Flow Test Point
E
I
S
S
35+
U
R
E
i
30+
P
S
I
I
25+
I
i
20X
1
,
I
I
15+
I
'
I
10+
"
" .
LEGEND
I
I
X = Required Water
Supply
"
f
20.00 psi @ 34.4
gpm
"
5+
"
I
0 = Available Water
Supply
"
(
I
43.10 psi @ 34.4
gpm
"
"
0 ------------------------------------------------------------------
200 3.00 400 500
600
700 800 900 1000
FLOW (GPM)
r
M
tqCCFire &Building
Products
Technical Services: Tei: (800) 381-93121 Fax:.(800) 791-5500
niazemaster w
CPVC Fire Winkler Pipe & Fittings
Submittal Street
General
Description
Tyrxrr" CPVC Pipe and Fittings pro-
du�d by Tyco Fire & building Prod-
ucts (TF P) are designed exclusively
for use In wet pipe automatic tire sprin-
kler systems. The Tyco CPUC Pipe
and Fittings are produced from Bliaze-
MasterO. CPVC compound that is a
specially developed thermoplastic
compound composed of post chlorin -
Wed polyvinyl chloride (CPVC) resin
and state of the art additives. Tyco
CPVC Pipe and Fittings are easier to
Install than traditional steel pipe sys-
tems, and at the Berne time, provide
superior heat resistance and strength
esred to traditional CPVC and
PVC ping materials used in the
plum trade. Various adapters are
available to oonned CPVC pipe to me=
tallic 'piping. All female pipe thread
adapters halm brass Inserts for dura-
bility. Grooved adapters conned di-
rectly to grooved end valves and me-
tallic pipe, with flexible grooved rand
owpitrW.
TYWO CPUC Pipe And Fittings pro -
duo d with BiazahiastetO CPUC com-
pound describers herein must be in-
stallsd end MAMtelned In wmpliance
with this document and with the appli-
cable standards of the National Fire
Protection Associollon, in addition to
the standards ofanyeuthorities Craving
jurisdiction, Falluie to do so may Im-
pair the p&*rmance of thetas daviaes.
The owner is responsible for rnaintain-
Ing,ftt9lr fire proteellon system and d8 -
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
*11tr any questions.
Page 1 of Z
Technical
Data
Sizes
314' to 3"
Maximum Working Pressure
V5 psi
Approvals
UL.TM, C -UL, NSF, LPCB, MEA, and
the City of Los Angeles. (Refer to in-
stallation Handbook iHA900 dated
June 2008 for exact iistinglapprovai
Information.)
Manufacture Source
U.S.A.
Material
. Pipe: ASTM F442, SDR 13.5
• Fittings: ASTM F438 ($ch. 40) and
ASTM F439 (Sch. 80), ASTM F1970
Color
Orange
JUNE, 2008
mp1d ryespnnse
i4011A. ftff$ S0i1101111,61t SrffVIA
B17-27» PCI/FILE
041-030-152
NOVEMBER I C, 2017
F/S FOR B17-1090
918z6M?SW& to a replatered budetmark
of The Lubrtzot CoM"Hon
T>=P1815
Page 2of2
Installation
Tyco# CPvC PI and Fittings pro,
duced by T co rt 8 Building Prod-
ucts �rI art; 16. be installed in
accordance with installation 44(and-
book 114»f 900 dated June 2008.
C06 and
Maintenance,
'Me owner :is roponsiblb for the in-
spetditon, testings and maIrrionance of
their, fire protedilon system, and de=
viol=s in compliance 1with :this 40cu-
ment, as well as With this epplibable
ztanoorda of the,National Fire Protec»
iltsl'a aftlatlon "(e.g., NFPA 29). in
addition _10 the Standards of any
authority 'having .jurisdiction. The in-
stalling contractor v produdrfionufac-
iuMr should be contacted -re ietive Yo
any quesiipns"
Automailc sprinkler systems ahould he
Inspeoted,-teated, and maintalo ad by a
qualified Inspection Samoa in accord -
once with fowl requirermonts and/or
at�tirtrtal codt;s::
8et0re t;tosirrg a fire protap#ion spstQr)l
Control valva for inspe0oh or main
Bance wink on`t, .rpro protectlon sys-
tem that It ,rnrols, permission to shut
down 1ho a7iectod .ilr9 protection sys-
tern must first ba obtained from the
proper authorities and aff paisonnel
Who may be effected by this action
rntfst tie notified.. :
After Oh#"' a fire pwiike ion s- tein
in servtce, nobly the proper authi dfia$
anOodvise thosaposponsiblafor moni-
torfrtt9 proprietary andlor ntret sta-
tiorr alarms.
Liknito
'arrant
Products manOiactured byTyco Fire
Building Products (TF13P) are war-
ranted
arrantedsolely ki lite originattuypr for
ten (10) years igalrtst defects in mate-
eist and workmanship whan paid for
atilt properly i 461led'and, maintained:
under notrraal,use and t4rvice. Thl s..
v3arranty will ,bxpire ten; (,1.0) ars
from data of shipment 6y', i=$i No
w.arra'nty. s givers for pt`odttcts orcoin,
no fit fnanufacturad, by companies
not atfillaW. by ownership with `fF8P
of, for pro
t: r'3 andrf pi0nents vvhir ft
have been subiecttomiause, improper
installation, .corroston, or which have
not been installed, thalntolned,'madi-
Nd or repaired in accordance with ap-
plicable Standards of the National Fire
Prbteabh Assoclatfbh, andibi the
standb ds of any "other Authorities
Having Jurisdibilbn. Materials fount;
by TFBP to ba defective hahlt.be either;
m osired or repla`Ced, of rpap's sols
option. T'F8P neither bssumes,' nor
authoYzes any person;toassume for it,
any tether obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shail'not be responsible for
sprinklerayat®m deal -9n errors orinat-
ctjratti ter incomplete Information sup.
plied, by Buyor or Buyer's repre-
5ei3tatittAB. .
In no =event shall TFBP be liable; In
wntrai:t, tori, sulci liabiitty or unMc
2other legal, theory, for incidentals .
indrect, spacial or conaectUendal dom-
ages, including but noit.Il tlted to labor
charges; regardlest of whether TF13P
wee informedabout the possibility of
such damages, and In no evt nt shall, .
TFaP's tiabliity, exceed an "emp`urtt:
equal to t116,189 price.,
The f•orarinlLnrs wrrrarty;e made fns#
o iY-mss! If 141ti�ti terra ;sex-
bresa ,tit If 14 ifi,dir3a warrents
iCtiiSgllihdnarrr g par-
;.
This limited wwrrarity,sats forth the ex-
clusivo;asnrtzdy for claims based �n
faiittte of or defadtin produtxts, maters-
sis or comporiantS, whether' the Claire
is foodo In contract, tort; strict liabiiit i.
or any outer legal theory.
his warranty will appxl" to the full ex-
tent permitted bylaw. I rte invalidity, in
whole or pari of''any portion of this.
warranty wail not affect 'the::reMafnder.
+ i3tr8 T'1i231`I3tL' {� titLt3lliC i�W2iti3utw ia; A51 't mita
0ennon Avenue, iaosdai6. P6nmsyivanla 1 8
: 1 of a
SENJU Si RIWLER CO.,,LTO.
fts. Wft fia i -Lead F EIX QaMpiLd
.adakin
Pendent
fik&I.- RC -RES,, K -Factor 4.9SIN. -SS8464
j
GENERAL
The Model RC -RES Residential Flat Concealed Spdrilders are automatic spr*Ws of the compressed fusibie solder type. These
are decorative mid fast response. The Cover Plate Assembly hides the Deflector, Heat Responsive Element etc. which is in turn
concealed above the ceiling. The cover plate has a flat profile and its diameter is extremely small (2-538 inch, 68mm). The
push -on and/or thread -on, thread -off design of ft concealed cover plate assembly allows easy instagation of the cover plate.
Therefore, the Model RC41ES should be your first choice when aesthetics is the mW consideration for ultimate appeal and
unbeatable performance is desired. The Model RC -RES is designed for the residential occuparides and it is perfect for use in
homes, hotels and other " quarters.
The Model RC -RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and
Manufactured Homes per NFPA 130; wet pipe residential sprftW systems for Residential Occulxxxxz up to and Including
Four Stones in Height per NFFA 13R; or, wet pipe spnnklef systems for the residential portions of any occupancies per NEPA 13.
The Model RC -RES has a 4.9 (70.6 LPM/barn K-4actor fiat meets the required residential flow rates with minimal residual
pressure, vhTx;h allows for smaller pipe saw and water supply requirements
For extended installation flexibility, the Model RCAES provides 1!2 inch (128mm) vertical adjustment. This adjustrnent in
installation deaeaSeS the reed for precise cutting of the pipe that drops to the sprinider and allows for a perfect fit with a range of
pipe lengths.
The heat sensitivity and water distribution design of Model RC41ES akwa for an increased chance of residents' escape or
evacuation in case of fire. However, residential fee sprinkler systems are not a substitute for fire safety awareness or fire safety
construction required by building codes.
'Lead Free is defined in the Reducoon of Lead in Drinking Water Act (S.3874) endorsed by A~s Vftter LUty Council. and
California Assembly BID #1953 as having less than or equal to a weighted average of 0.25% lead in welted surface of pipes,
plumbing fittings and 5duras.
WABAMVGS
The Atoclef RC -RES MUSt be kjstWW and n3ainta%ed in accerdmice with the rales snood herein as wed as in
conwHance Wr the Wgificabie 5ftwovis of the ill donal Arti Pniftedon Assoctatlon MqWatkins and the sftmlards of
any 00*w audwrides havbV ftnftdktfon.
In the went Of dim VINMI1000, COMA 620 NAWOOS fOAVfflffAS&W for WAtafte and qVroval.
FaMare to do so may ln*efr the h1tW* of ftse devAce&
It is the rOSPOMAtOMW of the insUffing con rotor to provider a copy of this docuntent to We owiw or his rqproserjta&%
and in &M, if is the Obfigafim of the own&r to Prov** a ropy of dds d=nnent to a succeedkV owner The owneir is
'OsPOnsfide fm ln3ftftkft &Wr fim praftefta systain and devkas in pmpw Operas" OWA&dm. Tft kneofthm
conftaor orspdhkkrmwwftc1ww-qhmW be cmnwftdwft &Vmkftd qsmsdorm
Dow nxint NO. U085162 Date : FebIO912017
D
TECHNICAL DATA
Approvals: An.,,, Listed, NSF -61-G
Sprinkler ldert fitation Number (SIN): SSSW
Maximum Woe4V Pressure: 176W (12.1bar)
Discharge Coeifircent (Nominal K -f=actor):
00=4.9 GPt owta (i`9.,8 Lp#i w/2)
Temperature RatinT
162E (7=) Spr***r Wft 149F (Wt) Coves Plato
175E (79°C) Sprbdder vdlh 148F (W90) Cover plate
1751F (7'9°C) Sp*#Sw wft 1aT (7210) *herr Elate
Color Code (Sprinkler)
162E (72`C): WIDOW"
1175: (79V): White
Color Code (Cover Plate)
MOT (Wt): W Mark
162T (720ey i hke-Coloread Nark
Vertices AdM tment 112 !much (12.8 mm)
Cover Plate Fid:
Standard Fhshes.
Whft Ivory , Brown, Obck, MAW,
Wood
Custom Finishes.
Custom color arhd custom pattern cover pkibm ase
avail" on special order. ContMA a 5enju
MW"" h,lrlth any custom order&
Please see chart on Page 8 for more detail.
Physical Chaff: Ref. Mgum 1
OPERATMN
Page : 2 of 8
Mwki'ql Oeflactm)
I
is
or ,nC
COVER PLATE SPRUCLER
Crop viva) Mlottom view)
In case of fire, the solder- component that holds togetther the Cover Date and the Retainer mom. Then, the Cover Plate is
released at once. As a .result, the Deflector drops down to the Intended posklon. Two keep Collectors are end to fire, and
when suffiaernt heat horn the fire is recorded, intend components of the spfinkter to fall apart This leads to slow the water flow
to be distributed on the affected by fire area (Ref. F►gure 2)
Document No. U085162 Date : FebIO912017
tot No.
Yes of Marw%ctwe
-am; S58482
9 i _
K-fas{a : M.0
182'F; r2b
or IWFT79'0
---UL
MaA
-- -_
camd ria.: WW
NSF : NSF -m -s
!S: Hadi tcoppar Apay)
2-W(4s68008
104; Gashet(PrFP)
a 3-h1�` t m
� Fusbls 1R W (Solder;
Heat CO&Wtor (OOW r)
t.owa Plate Anw-Aly
Mwki'ql Oeflactm)
I
is
or ,nC
COVER PLATE SPRUCLER
Crop viva) Mlottom view)
In case of fire, the solder- component that holds togetther the Cover Date and the Retainer mom. Then, the Cover Plate is
released at once. As a .result, the Deflector drops down to the Intended posklon. Two keep Collectors are end to fire, and
when suffiaernt heat horn the fire is recorded, intend components of the spfinkter to fall apart This leads to slow the water flow
to be distributed on the affected by fire area (Ref. F►gure 2)
Document No. U085162 Date : FebIO912017
DESIGN CRITERIA
Page :3 of 8
The herein stated rules for use and installation of Model RC -RES are provided by the manufacturer and must be strictly
implemented for safe and full results.
11ftY1'E,5'
Residential Eire Sprinkler Systems should only be designed and Installed by individuals who are completely familiar
with automatic sprinkler system design, installation procedures, and techniques.
Several criteria may apply to the installation and usage of each sprinkler: Consequently, it is recommended that the
Sprinkler system designer review and develop a working understanding of the complete list of criteria prior to initiating
the design of the sprinkler system.
Questions concerning sprinkler Installation and usage criteria, which are not coverage by the following instructions,
should be submitted to Contact Company. Include sketches and technical details as appropriate.
In some instances, the requirements of this document may concern specifications which are more stringent and which
take precedence over time specified In NEPA 13, 13D, 131y "by the authority having Jurisdiction.
The Model RC -RES must not be used in applications where the air pressure above the ceiling is greater than that below.
Inspect all sprinklers after Installation to ensure that both the gap between the cover plate, ceiling and the 6 slots in the
cup are open and free from any air flow impediment
The spray from the sprinkler is distributed radically outward and downward from the sprinkler deflector. Consequently,
the sprinklers must be located such that there will be no blind spaces shielded from spray by pardtions, room drlriders,
overhangs or otherparts of the dwelling structure.
rhe number of sprinklers within each compartment (as defined by NEPA 13, 13D, or 13R) must be kept as small as
possible. Do NOT use more sprinklers than necessary to cover a particular space.
Use only the Cover Plate provided with the Model RC -RFS. The sprinkler must be secured in place by firmly fastening
the sprinkler system piping to the structure. if the sprinkler is not properly secured In position, reaction farces
resulting from sprinkler operation could alter its orientation and its water distribution pattern.
Obstrucdon to Water Distribution
Locations of sprinklers must follow the obstruction rules of NFPA 13 for Residential Sprinklers.
General Service Conditions
The Model RC -RES must only be utilized in WET PIPE sprinkler systems.
Neat Source Criteria
Refer to NFPA 13D or 13R for the requirements relisting to the prevention of possible activation of the Heat Responsive
Element of Model RC -RES, due to exposure to a heat sources other than an actual fire.
Available Sprinkler Temperature Ratings
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating
j Maximum Ambient Ceiling
Temperature
Temperature Rating of the
Cover Plate Assembly
Ordinary
1627 (72°C)
100T (38°C)
140T (60'C)
Intermediate
17ST (7!?C)
150°F (66"C)
140`F (600C)'i
Intermediate
175T (7'9°C)
150T (660C)
182T (72°C)
l maximum ambient temperature for the cover Plate Assembly is 1DOT (38�C).
Precautionary Warnings for Corrosive Environments
The Model RC -RES should not be installed where they may be subjected to a Corrosive environment including the following:
(1) Chlorine ion and Chloride environment
Stress corrosion Cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this
environment may result in sprinklers operating under Non -Fire conditions or Not Operating when exposed to an actual fire.
(2) Sprinkler system piping with Copper.
Sprinkler systems should be constructed in Compliance with the applicable standards and the requirements for the copper
piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM 8813, 8828, and CDA
(Copper Development Association) — Solder Joint)
All residual flux must be removed from the interior and exterior of copper piping by thoroughly flushing before installation of
the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and leakage in the sprinkler system.
Document NO. U085162 Date : Feb109120' 7
fi
,
n
I
Hydraulic Design Crileria
Page :4 of 8
The minimum required sprinkler flow rates for system designed to NFPA 13D or 13R are given in Table A as a function of
temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge
from the most hydraulically demanding sprinkler from each of the total number of "design sprinklers" as specified in NFPA 13D
or 13R.
For systems designed to NFPA 13, the number of de -signed sprinklers is to be the four most hydraulically demanding
sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the followings;
• The flow rates given in Table A for NFPA 13D and 13R as a function of temperature rating and maximum allowable
coverage area
• A minimum discharge 0.1GPM/sq.ft. (4.071.PM/sq.m) over the "design area' comprised of the four most hydraulically
demanding sprinklers for the actual coverage areas being protected by the four sprinklers.
TABLE A. NFPA 13D & 13R WET PIPE HYDRAULIC DESIGN CRITERIA for Model SS8dSd
Maximum
Ordinary
Intermediate
Covera a
Maximum
Temperature Rating
Temperature Rating
Deflector
Minimum
Areas
Spacing
162`F (72°C)
175°f t73°C)
installation
Spacing
Flo
Pressure
Flo
Pressure
Ft x Ft
Ft
t0
Ceiling
Type
Ft.
(m Xm)
(m)
GPM
PSI
GPM
PSI
(m)
LPM
bar)
(LPM)
(bar
12x12
12
13
7.0
13
7.0
Smooth
C li
Ceilings
ngs
(3.7x3.7)
(3.7)
(43.2)
(0.48)
(49.2)
(0.48)
7/8
Inches.
14x14
14
13
7.0
13
7.0
(4.3%4.3)
(4.3)
(49.2)
(0.48)
(49.2)
(0.48)
Beamed
Ceilings
per NFPA
16x16
16
13
7.0
14
8.2
113D, 3R
8
(4.9x4.9)
(4.9)
(49.2)
(0.48)
(53.0)
(0.57)
or 13
Concealed
(2.4)
Installed
18x"!8
18
17
12.0
18
13.5
in beam
3/8 to
(6.5x6.5)
(5:5)
(64.3)
(0.83)
(68.1)
(0.93)
7/8
inches
20X20
20
21
18.4
below
(79.5)
(1.27)
—
—
bottom of
Cream.
(a) For coverage area dimensions less than the above mentioned, it needs to use the minimum required flow for the
Next Higher Coverage Area listed.
(b) Requirement is based on minimum flow In GPM/t.PM from each sprinkler. The associated residual pressures are
calculated using the nominal K -Factor. Refer to Hydraulic Design Criteria Section for details.
(c) For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of
NFPA 130,13R or 13 as applicable.
p nkler Spacing +wrileria
The minimum spacing between sprinklers is 8 feet (2.4m). The maximum spacing between sprinklers cannot go beyond the
coverage area calculated by using the specific hydraulic factors. (Ref. Table A)
Document No. 0085152 Hate : Febl09/2017
1N3T"!f Page : 5 of 8
The Model RC RES must be in bWd in accordance with the foilnwing instructions.
Do nWtMeaffYAPAkddemwhkhhw&meer, SubjwW f POW10Wh da� DO not use any spdrA6RM whir
shot~ det'w tks or in e&ier tie SpAnitter or oe.iProtecWe Cap
P for tib irk, -*#Vvddem should be, n"dntatbed in t0 orfglrW Qwtwrs aWPOCMWA9 WW mod to the
POMWW ftwVie. to W*d*m dW MON CaUSe ftpWwopieratit n or nou ns.
The Proftedve Cap MLW regoam ors the W"NerdWft&=WJfiMend ""W the 40OW h"0432km is o=Weftd The
Prole eWO COP rrtt M be +wed to pian dresp&Mar in saWm
tlste 8 tcuagete of to tl ftAs jS.S to 19,M") to a M L'K* NOT sPrhWwAirlt #you arceed to girded
twgL, t; iws CMMresuft in dame to tyle spdriaw hgK %rkh any load go i &OW tO
In, case ,ofhav0 it, to +coveriIte M409016m do nW &y to am* fthtM mjw ghe VArider,too low
ar stacks awry r VOIC2160a of the cover pW9 assenWy. Jteacgag the apdrAder rfftg tbra beater fi'iL
Do rot kwft to ri We die CAP Rgamw RC to the iletAt whw pbdag Oe fto hook an" kft pbm The kaMed
seri dder terry berme bossned, ~ my cause hakogm
Instal#ice► hue
step
i The instaKabon reTikements for the sprinkler are as foilowv. to be installed only in the pendent position with the waterway
PeVPMOWt8r to the Wig. !nisi the Ww4der fitting so lust the distance from ft fake of the Ming tD ft mourning surf
will be nomi4ratiy 2 inch (50.8mm) as shun+ n in Figure 3.
Step
With pipe thread seatant applied to the threads, hand tighten the sprinktitr into the sprinider fitting. Then fightert it vmh the
Spanider Socket or Wrench & Socket Curnbinabon (Ref. FMure 4). The grooves of tate Socket must fit perfeGt#y with the
a grooves on the Sprinkler for proper installation (Ref. Figure 4).
Step
K if desi W the Protective Cap may also be used to locate the center of the deal3f1w We by Witty pustft the cebV rnatetial
r against the venter point of the Protective Gap: Before the MSWWM of the ce&K, the sprinkler install oon can be started with
the 2-318 inch (60mm) diameter clearance hole (fief. Figure 3). Use the'Tolerance Limit of CeWng LeyeP indcator on the
Protective Cap to check for proper installation hem (Rei. Fgwe 3).
Make a. Specs live On Nal
Ave. Y L6Armd Oyer 7
! W TO t l
Tokrar�ce Ladt zt zz
Of CLard
1 %
N
\_ p
vswf ce
Mwmtiry� 2318' !lbaimm: OaxTem
Obifirs tide Obmour
CORRECT (tori
kon t3�e Sa�i�tar
omavc Cao
F�V 1-1 °'�° en TAC seaet
Sodmt
sup
Use the Cap Remover RC to remove the Protective Cap (Rud. Figure 5), and then push or screw a Cover Plate AsswnNyr on
the Cup of the Spraider by hand until its tkartge Just comes in cwftd with the ceiTehg (Ref, Fore S and Figure T)., Stop
tightening the Cover Plate Assembly once the flange has come in c iontad with the ceibv& If the ceing has been iced from its
normal position in the process of lightentiV of the Cover Plate Assemblyr, readAisi the cover plate assembly as necessary If
Document NMU085162 Date : FebIl19M17
Lass than
1-3/4- (44.4m)
i
II�III `i
f;E�'�ff�
lit
t
/4' (50.8 ±6.4mm)
Mora then
2-1/4' (SMw)_
.........
If
CARE AND MAINTENANCE Page " 7 of 8
The following instructions must be implemented for the maintenance and service of the Model RG -RES.
M
Wet pipe sprinkler systems must be maintained at a minimum temperature of AO F14 i to prevent freezing and bursting
of the pipe and/or sprinklers.
Automatic sprinklers are not to be tested with a heat source. operation of the heat responsive element can result
Absence of a Cover Plate Assembly may delay the response time of the sprinkler in case of fire.
Install the cover plate assembly properly, as shown in Figure 6. Improper installation of the cover plate assembly may
cause improper operation or non -operation.
If the ceiling is to be repainted after the Installation of the Sprinkler, care must be exercised to ensure that the new paint
does not seal off any of the air gap,
Factory painted Cover Plates must not be repainted, They should be replace4 N necessary, by factory painted cover
plates. 111011 -factory applied paint may adversely delay or prevent sprinkler operation in case of fire.
Do not pull the Cover Plate. Separation may result
In preparation for maintenance of the fire protection system, permission to close the main control valve must be
obtained from the proper authorities and all affected by this action parties must be informed before the maintenance
session can commence.
Do NOT enclose any sprinklers within drapes, curtains, or valances.
Do NOT hang anything from the sprinklers.
Do NOT clean the sprinklers with soap and water, detergents, ammonia, cleaning fluids, or other chemicals. Remove
dust, lint, cobwebs, cocoons, Insects, and larvae by gently brushing with a feather duster or gently vacuuming with a
soft bristle (Le., dusting) brush attachment
Exercise suitable safety precautions in the use and storage of highly flammable materials. The rapid rate of fire
development and spread of these matmrials can reduce the ability of the sprinkler systems to aid in the control of a fire
involving such hazards.
Leaking or corroded sprinklers must be replaced.
Automatic Sprinklers must never be shipped or stored where the temperature exceeds IOOT 138°C.
Automatic sprinkler must never be physically altered, such as painted, plated, or coated, once shipped from the factory. If the
sprinklers have been in any way modified. they must be replaced.
Great caution must be applied to prevent damage to the sprinklers at all stages - before, during, and after installation. Damaged
units, as a result of dropping, hitting, over -tightening, or wrench slippage, must be replaced.
The Model RC -RES must only be replaced with pendent sprinklers which are listed for residential fire protection service and
which have the same nominal K -Factor, the same coverage area, and the same or lower flow ratings (as indicated under Table A
`Hydraulic Design Criteria').
When remodeling, such as by adding false beams or light fixtures or changing the location of compartment walls, first verity that
the new construction will not violate the installation requirements of the applicable standards of NFPA. After the new construction
and/or the sprinkler system to suit the requirements of this document and the applicable NFPA regulations.
The owner Is responsible for the maintenance of the sprinkler system, including inspection and testing, its compliance with this
documents, as well as the standards of the National Fire Protection Association (e.g., NFPA 25), and the regulations of any other
authorities having jurisdiction. The owner should direct any questions regarding the above rules and regulations to the installing
contractors or the sprinkler manufacturer. It is recommended that automatic sprinkler systems be inspected, tested, and
maintained by a qualified Inspection Service in accordance with NFPA 25.
UOctlrnent No.U085162 Date FebIO912017
ORDER PROCEDURE
Page : 8 of 8
When placing an order, please contact a local distributor with the following information (Model Name, Specify, Temp. and Finish).
Sprinlder:
Model: RC -RES
(SIN: SS8464, Residential Fiat Concealed Sprinkler; Pendent, K4.9, Temperature: 162`F (72°C) or 175`F (79°C) )
Cover Plate Assembly:
2-518 inch (068mm) or 3-1/4 inch (083mm) or 2-518 inch square (068mm), Order Separately from Sprinkler
Please refer to the dart below for available sires, temperature, and finishes.
Toots for Installation of Model': RC -RLS
• Socket for Model RC -RES
Wrench & Socket for Model RC -RES
Cap Remover RC
V
Document No. U085162 Date : FeblMO17
Standard Finishes
Custom Finishes
White
Ivory
Beige
Brown
Black
Nickel
Wood grain
Custom Color
Custom Pattern
2-5/8" Round, 140OF
O
O
-
-
-
O
-
O
O
3-114" Round, 140°F
O
O
O
O
O
O
O
O
O
2-518" Square, 140OF
O
-
-
-
_
_
_
O
O
2-519" Round, 16rF
O
-
-
-
-
O
O
3-114" Round,_ 162°F
O
-
-
-
-
-
-
O
O
Toots for Installation of Model': RC -RLS
• Socket for Model RC -RES
Wrench & Socket for Model RC -RES
Cap Remover RC
V
Document No. U085162 Date : FeblMO17
PA Box 3365 Soluttl El Monte, Ck91733 626-444,.0541 Fax 626, .3837
www. Afoon,org
514'
�FSE GER
SIZE - V4" Niru 3"p'i�_
MATll;iill i., - Carbtso -steel
T TNi W - Mil. Galvanized,.
USTING7APP;:tOVAL -
203 Y 4231, EX -1551
PATENT -:No.6;t48,278.
rUNCTION - 37.1"—V, Hangerlreitrainer for iadxi7'nntal !i✓I)VC, C'olyper oa steel pipe.
,
L sxeni bangerlrewainer in al13 inoftting positions, i& vertical, surhoe".and both iop and
%ttorn ofborizontal surface. 'provides listed verticaviateral restraint,andprevenisupward` ,
mgvement tib pipe that supplies latnzlitlt slirinklcr below a ceila`ng
sig 2'h" Ringer 3or hzoratal CPVC pipe. Guteii hanger itz x113 r»ourttrg'pc� itoos
I.C. vertical surface and both top �turdbottom of.�4 titonta! surface.
y
Size Hangs .for, hnrizoMat CT VC pi 'in two iptatattting positions, ®de and bottom.
it. vertical:; &ce, and bottom of horizontal surface.
Sbabiliacs, vertical piping by providin rharizontal,; a traiiit.
tS�i3.a��i3� PCipPJ�, Banti 1:317,
p
Space.by pipe tylx, .Tnstwl on wood, cotactetvor steel < &-eDrawinp.
_a
Snap over pip; then .scluetrc sirrap ffiTlcrrtng pipe t9 slide frly. t meted ar+,ni
when 'Ads threads are expaied iij wood, it s l 4906Ucktng nut. Sts" itu 2e'
Sr'ffitirJir:'dti`rt' SYiKs ir++rrritg a� Ca°1*t iyPfnk�Cr aygbeni plDe
Verify thal40 Awmbty wmpa mU artttiated oiuryti: t>$1,
'AS°l 1" N It;RS -UA,,W.0 per XFPA 13
WOOD- - W _ 3" C VC Vice - #905 screw- no:p7+�=driiT.
374° _ 2" Copper pipe - 4008 screw- tto pre -civil.
374'' - 2" -Steel pipe -1144 1 192" lag screw - no pre -drill.
{,k ' ku 518" gypsum board .-.R74" x.2" lag screw,
�
S`rE i,- anur: T8 GA: 3/4"- 3" CPUC pipe -"i jd" or # ld I'ek Screw:
q
�
374" -2� Copperpipe-14',or_#14 Tek Screw..
al
i 3/411 -t Steet pipe -114" or M4 Tek Screw.
CONCRET'T ° `R squired minimum ioaOoo tiasteilef *r 3 wt)+25011is.
4,
FEATURFS
1 172" Oftt - loose fit allows pipe ata slide.
y 374" tenet 1" pipe siye inane with eonYmon centdr�ine; .,
irn
.°
* ftzp rated &,5ign ft superior strength.3W
tTuii a'
. 3ifsat edge elite .6mcs abrasion.
AFCON #9p5 screw has;56611 hex .brad - included. =:
ORHEMNi r°- 'Part. 4 and pipe size.
A7"t" N #911iS backing tint sn'JA iitparately.
BgegPkRYC(7Npn/t�3s.slrcoYriasvdyhaeigpi$06, pgsied)F1tYwri�Liikrawi MrM 3oelukikG mdfaRsa ?a}�iis Arai§ ad n9d+aa, r*i eitir}� tt .
Sati�fsal9rfoiMw6+�S�aEyrarnktimw{3�iippiy Oi�G1,�U'.�a�'•AiGU3vW�lKL1a?�t+satn�ix3aM�aRF+fhrtanf;Yi��kr�e4ua�a6�a5vKl��tlril�(4+k�
stllmtri�fw7'desdorlohidVita5iarxM., rcAnl9s�wefo=or�ey$0bitlAl
. �$d9 biGNt ati:arren?x.1}bea MOMN�•CtiiVim�f}asi hiw DEpU�cM L'L nwd„ .. _ _ �
00
SIZE 314" tlUU 2" C.P.V.C. and Copper,
r l,• thru 2" .steel,
INIAT-IRTUAL - Carbon Steel,
FMSU-','Mit 0,9..0 Spec.
LISTING -'LiL in US and CANADA,
` .'CTION Hauges, su )ort and rastraiiier #sir use on,C.P.V.C., Coppet
or Sie61 piping installed;per.NTS P.A. 13,;1311 and.13b.
�'STALLATi0N, - .Install'on top, bottgrn or Me of beans
Hanger spacingby pipe type- ,per N44-PA 13.
U1. listen fasteners tested per NFPA L3, as follows.
IN WOOD:
CPVC and Copper - fisted hex 4.gati scree furnished tit+i -product.
Steel - 114"x 11/2" lag screw -needs no pmdrilling,
N CONCIRE-M or HEAVY STEEL;
Shot type fasteners, "Only when installed prior topipc insertion .,
* OM-et edge for abrasion eiiminai on and,superior strength. .
*Retainer 1 1tples secure liangar to pipe during rgstailation.
Requited. AL916ner fmisheri with 5/16 head, needs no pts -drilling.
O WBMG - Part #i and pipe si70,
NOTE' On copper - insulate pipe.
y,
:8129101
P.O. Box 3365'SOUTH EI, MOTE CA 91733 `626.444:6541 FAX 626-444.3887 W..ww,afcon,org
51
PIPE/ C.P-Yf,. HANGER
SIDEMOUNT:
SIZE - 314" ihru 2" C.P.V:C,and CO�aper.
11 ATERIAI - Carbon'Steel.
NNW( Mil, Galvanized, 0, 40 Spec.
(STING - Min US and CANNA—DA
,FUNCTION - Hangrt, support and mtiainer for use on C.P,VQ.-tsr Copper
piphig,installed per N.F.T.A. 13,13R and 131: �
V SEAL LATIOr1 - Install ort top, bottom or side of beasts.
Hauser spacing b pipepe - per:iFP.A 13,
i.?'L listed fasteners tested per NPi'A,13, as follows,
INI WOOD:
CPUC and Colsprr - listed hex 1=4 screw £untss}re(i with product.
IN CONCRETE or 14EAVY STEEL
Shot typo fasteners, "truly: when installed prior to pipe inrtirtion". .
* Offset edge for ribrasion climination and superior strength.'
Retainer dimples sectut hanger to pipe durit g installation.
* Required fastener furnished with 5116 head.. uee no pre-
drilling.
0),W .RIS G - Part # and CTVC. or Copper pipe Size.
NOTES: On tapper -insulate pipe,
'SSR -SG
VANE TYPE WATERFLOW
fc"PO"ffER FOR CPVC PIPE ALARM SWITCH WITH RETARD
The Symbol of Protection AND GLUE -IN UNION
UL, CUL and CSFM Listed, CE Marked
Specifications subject to change without notice.
Stock Number: 1144460
Optional: Cover Tamper Switch Kit, stock no. 0090148
Replaceable Components: Retard/SwitchAssembly, stock no. 1029030
CAUTION
Waterflow switches that are monitoring wet pipe sprinkler systems shall
not be used as rite sole initiating switch to discharge AFFF, deluge,
or chemical suppression systems. Waterfiow switches used VIM,
application may result in unintended discharges caused by surges,
Dapped air, or short retard times.
General Information
The Model VSR-SG is a vane type waterfiow switch for use on wet
sprinkler systems using CPVC plastic fittings (manufactured by Tyco,
Nibco, Victaulic, Ipex, and Spears Manufacturing Company) that use 1'",
1 14", .1 %z", or 2" pipe sizes. It is equipped with a union to accommodate
installation in confiner] spares.
The VSR-SG contains two single pole, double throw, snap action
switches and an adjustable, instantly recycling pneumatic retard. The
switches are actuated when a flow of 10 GPM (38 LPM) or more
occurs downstream of the switch. The flow condition must exist for a
period of time necessary to overcome the selected retard period
e Enclosure
The VSR SG switches and retard switch are enclosed in a general
s purpose, die-cast housing. The cover is held in place with two tamper
• resistant screws which require a special key for removal. A field
installable cover tamper switch is available as an option which may
be used to indicate unauthorized removal of the cover. See bulletin
t number 5401103 for installation instructions of this switch.
Installation (see Fig. 1, 3, and 5)
These switches may be mounted on horizontal or vertical pipe. On
horizontal pipe they shall be installed on the top side of the pipe where
4 they will be accessible. The switch should not be installed within 6"
t (15 cm) of a fitting which changes the direction of the waterflow or
CAUTION
Do not trim the paddle. Failure to follow these instructions may prevent the
switch from operatin and will void the warranty.
ServicePressure: Up to 175 PSI (12,07 BAR)
Flow Sensitivity Range for Signal: 4-10 GPM (15-38 LPM) -'CIL
Maximum Surge: I S FPS (5.5 m/s)
Contact Ratings: Two sets of SPDT (Form C)
10.0Amps at 125/250VAC
2.0Amps at 30VDC Resistive
10 mAntps min. at 24VDC
CondaitEntrances: Two openingsprovidedforl/2°conduit.
Individual switch compartments suitable
for dissimilar voltages.
Environmental Specifications:
• NEMA 4/IP54 Rated Enclosure suitable for indoor or
outdoor use with factory installed gasket and die-cast housing
when used with appropriate conduit fitting.
• Temperature Range: 40°F -120°F, (4.5°C - 49°G) - UL
Service Use:
.British Standard
B59251
Automatic Sprinkler
NFPA-13
One or two family dwelling
NFPA-13D
Residential occupancy up to four stories
NEPA-ISR
National Fire Alarm Code
NFPA-72
• Installation must be performed by qualified personnel and in
accordance with all national and local codes and ordinances.
• Shock hazard .Disconnect power source before servicing. Serious
injury or death could result.
• Risk of explosion. Not for use in hazardous locations. Serious
iniury or death could result.
within 24" (60 cm) of a valve or drain. The unit has a V male fitting
for gluing into a CPVC plastic 'tee.
NOTE: Do not leave cover off for an extended period of time.
Loosen the union nut and separate the 1" male fitting from the VSR.SG.
Glue the I" male fitting into the TEE following the TEE manufacturer's
instructions for preparation and gluing of CPVC piping systems. (Note:
The 1 " male fitting must bottom out on the stop of the TEE for proper
operation of the VSR-SG. See Fig. 1.) Wait 2 to 4 hours to allow the
glue to dry before attaching the VSR-SG to the I" male fitting. Select
the proper paddle for the pipe size and type of TEE used.. See Fig. 3
for instructions on how to change paddle. Verify that the o-nng is
properly positioned in its groove. Hand tighten the nut on the union
after orienting the switch in the appropriate direction to detect waterliow
as shown in Fig. 5 8t Fig. 7.
The vane must not rub the inside of the TEE or bind in any way. The
stem should move freely when operated by hand
A CAUTION
Do not over -tighten the union nut, hand tighten only. Use of a wrench
may a the union nut.
PotterrElectricSi alCo ,LLC•St.Louis,MO•CustService:866-572-3005•TechSu ort 866-956-0988,,"Canada88M82-1833 - www.pottersignal.cm
PRINT'E'D IN USA MFG. -#3401205 - REV H PAGE 1 OF 4
01/12
VSRY-SG
E)POTTER VANE TYPE WATERFLOW
R CP'l'C PIPE ALARM SWITCH WITH RETARD?
The Symbol of Protection .AND GLUE -IN UNION
Testing
The frequency of inspection and testing for the Model VSR-SG and its associated protective. monitoring system shall be in accordance with applicable
NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
A method of testing the VSR SG must be provided. The valve used for testing shall be easily reached and shall produce a minimum flow of 10
GPM to activate the switch. The discharge orifice shall be equal to the smallest sprinkler used in the system.
-Advise the person responsible for testing of the fire protection system that this system must be tested in accordance
with the testing instructions.
F4 1
Glue the 1 "male fitting into the ME following
the TEE manufacturer's instructions for
preparation and gluing of CP VC piping
systems. Wait 2 to 4 hours to allow the glue
to dry before attaching the VSR-SG to the 7"
male fitting.
9'
(uw"Suu CLEARA14CE 1- �1s1E FITT NC
REWIRED FOR j'''� �M� our
REMOVALinEVVII--) 1 8N STOP
I
NO SUS»iNO5,
INSERTS OR Ogg p1O62-r
ADAPTERS
ARE PMIMO
Fig. 3
!s
-< • . jjj
r
important:
11 paddles are furnished with each unit
to accommodate the various sizes and
manufacturers of TEES. The paddles have
raised tettering that show the pipe size and
the TEE manufacturer they are to be used
with. The proper paddle must be used. The
paddle must be properly attached (see Fig, 3)
and the screw that holds the paddle must be
securely tightened.
Fig..2
Break out thin section of cover when wiring both switches from one
conduit entrance. A
Fig. 4 Typical Electrical Connections
Notes:
1. The Model VSR SG has two switches, one can be used to operate a
central station, proprietary or remote signaling unit, while tate other
contact is used to operate a local audible or viaW annunciator.
2. For supervised circuits, see "Switch Terminal Connections"
drawing and warning note (Fig. 6).
WMA.LFROMMMAM N"VMALFDiOMMU
IMAM
WLWr1d OPD.icRfttWd
NOM.
When connnecti V to a Ut. fisted
control panel, use the panel's
resistor value for urcuit supervision.
PRINTED TN USA WG. #5401205 - REV K PAGE 2 OF d
01112
SASH SEREES
opSPRIN
ALARM STROBE�E.R
The Symbol of Prt�te�tion HORN/SIGN COMBINATION
UL lasted Strobe Haan
Dimemslons:.9-114" h x 10" w x 4" d
VotiagesAvaiiable: SASE -24 (24VDC)
SASH -120 (120VAC)
Envirottment: Indoor or Outdoor use
W-fietproof backim is ittciuded with
both modals
Termination: Sepal tem=ais for horn and strobe
Fittisb: Red with while lettering
SASE 24 Stock No. 1000555
SASH -120 Stock No. 1000560
The SASH series is 2 multitone homistrobe oombivatioa designed for use as an m idio visual indication for arrlomatic sprinkler systems. It cart be
installed in c0Uju c`d0a with or in place of water motor gomp..
Strome Intensity, dBA, and Omerent'Ratirgs
Mom
SASH 24 �itttGtorreat
SASH-i20.irapatCnaeat
TYDt�A>�nied3Aa4'lOft.
Tone
Axnps at 24V DC
Amps at 115V AC
At Nominal Inpat %mge
Ea
STD
H1
STD
Hl
STD
Ham
0.038
0.024
0.0.0
0.040
99
93
Bell
0.019
0.012
0.040
0.038
92
87
March Time lion
0.038
0.024
0.050
0.040
99
93
Coit -3 noL°
0.038
0.024
0.050
0.040
99
93
Co& -3 Tone
0.027
10.016
0.042
0.038
95
90
Slow Whoop
0.047
0.025
0.050
0.040
99
94
Siren
0,034
0.022
0.033
0.040
98
93
Hxn'o
0.020
0.013
0.041
0.039
93
88
Strobe CznsdeIla
75
is
Strobe Current (If the strobe and andiNe aperffie on the same
0.102
enmit. &H the strobe catYCIIt to the tom Current)
0.060
Wtrbtg.Ldbrmmtion
SASH -+e -
S=W AM OMS
tOWea"n BYiLi&
SAt,&CmCtSr ♦ * - - MZ -
• sLs - + ALv -
&AS"
SSROW AM WORN
POWiiltS:OftEWii SSL1;y a
RAnCWCW
C&Nt., ScLam
C ALAad
1AS84-V MfA16Bftd1V
opot V,W aY
WAM3Ut.aWSWr.r" V 578
N
W401 v i
PotterMe at'c Signet Cvmpany> LLC • 2081 Craig- Road, S L Lords, MO, 6314,1>4161 -Phone. 800.325-3936/Cnada 888-8$2-1833• w ww.pott agttd.
nom
MINTED INUSA WG.;5401016-REV H PAGE Of 1
5