ALARM AND DETECTION REPORT Page 1 of 4
obs—i2D—oyb 2c
VOLTAGE' iPECIAuSTs
530-624-4514
c+0/neuo«r...e801162 www.v.n.esp«i.n.n.cmn Inspection#
ALARM&DETECTION EQUIPMENT TEST REPORT
Type of Inspection:Annual Date: 4/15/2019
Customer Paradise Unified School District
Site: Cedarwood School
Street: 6400 Columbine Road Contact: Jake
City/State: Paradise Ca Phone#: 530-872-6487
Fax#:
1. Before Test Notify Proper Authorities: Name Phone#
A. Owner or Owner's Rep Jake 530-872-6487
B. Fire Department Cal fire 533-6363
C. Central Station CSM 800-722-0364
D. Central Station Acct# 2002-1331
2. Control Panel Status Yes No Note#
A. Is the system monitored by Central Station? X
On Test Time:8:50 Return to Service Time:
B. Is the Power Light on? X
C. Does the Panel indicate Normal conditions? X
D. Are all indicating Lamp Bulbs in Operator order? X
E. Does the Trouble Light operate? x
F. Does the Silence Switch Operate? X
G. Battery A.H.8 Date Batteries Installed: 4/1/19
H. Does the Panel have Non-Operational Zones? X
I. Does the Panel have Battery Backup? X
J. Do the batteries indicate they are Properly Charged? X
Condition of Batteries:Good Note#
Battery Voltage with AC Power:27.19 Battery Voltage without AC Power:27.98
K. List any trouble conditions on panel before test: Note#
Note#
Comments: Note#
Note# •
-
3.FACP Manufacturer: Silent Knight Model#5208 System Type: hard wire
Location of Annunciators:Office
Location of Primary Power Source:Outside of office Panel#MS 10 Breaker 14
Comments: Note#
Note#
FCPS: Manufacturer: Booster Power Supply Model#BPS6 PaneVBreaker# Location:Library Jan.Clc
Battery Voltage with A/C Power: w/o NC Power Date: Out dated
FCPS: Manufacturer: Silent Knight Model#5495 Panel/Breaker# Location:Next to FACP
Battery Voltage with NC Power: 27.14 w/o NC Power 26.86 Date: 4/1/19
FCPS: Manufacturer: Model# PaneVBreaker# Location:
Battery Voltage with NC Power: w/o NC Power Date:
Owner/Rep: Phone#: Date:
Inspector: Don Cantrell ��./ ���� Phone#:530-362-2609 Date:4/155/r1y9t L
Owners Rep Sign: �Irusaa a Date:4/15/2019 Inspector Sign: �L/r r"��
ALARM AND DETECTION REPORT Page 2 of 4
Property Site: Cedarwood School
l Operational I
#Tested
This
Equipment Total# Report Yes N/A Note#
4. Remote Annunciators 1 1 X
5. Zones 20 20 X
6, Manual Stations (Pull)
Hardwire 31 31 X
Addressable
7. Detectors
Photoelectric 1 1 X
Ionization
Heats/ Fixed or R of R
Flame
Duct(See#15) 1
8. Horn/Strobe 6 6 X 1
Strobe Only 10 10 X
Bell 1
Speakers
Horn 20 20 X
9.
10. Automatic Door Release
11. Water Flow switches 3 3 X
Did W/F Ring Outside Bell?
Did W/F Activate Alarm Panel?
12. Tamper Switches 3 3 X
13. PIV
OS&Y
14.
15. Did test of Duct Detectors shut down air handling units? X
16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line)receive signal? X
17. Is system reset for normal conditions? X
18. Is system restored to operational service? X
19. Have Proper Authorities (see#1)been notified system is back in service? X
List Proper Authorities:
20. Indicate%of equipment tested this report 25% 50% 75% ✓ 100%
21. Indicate%of equipment tested YTD 25% 50% 75% ✓ 100%
Comments for any"no"answers or explanations(Note#):
Owners Rep Sign: i/'��'�+ Date: 4/15/2019 #01.1
Ins ector Si n:
p g
ALARM AND DETECTION REPORT Cedarwood School Page 3 of 4
Zone or
DEVICE sLc DEVICE#
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
PS ADMIN X 1 1
PS ADMIN X 1 2
PS ADMIN X 1 3
PS ROOM 7 X 3 1
PS ROOM 8 X 3 2
PS ROOM 9 X 3 3
PS ROOM 10 X 3 4
PS LIBRARY X 4 1
PS LIBRARY X 4 2
PS ROOM 13 X 5 1
PS ROOM 14 X 5 2
PS CAFETERIA SE X 7 2
PS CAFETERIA SW X 7 3
PS GYM NE X 7 4
PS GYM NW X 7 5
PS ROOM 15 X 9 1
PS ROOM 16 X 9 2
PS ROOM 17 X 9 3
PS ROOM 18 X 9 4
PS ROOM 11 X 11 1
PS ROOM 12 X 11 2
PS ROOM 3 X 15 1
PS ROOM 4 X 15 3
PS ROOM 5 X 15 4
PS ROOM 6 X 15 5
PS ROOM 1 X 17 1
PS ROOM 1 X 17 2
PS ROOM 2 X 17 3
PS ROOM 2 X 17 4
PS Admin X 1 4
PS Kitchen X 4 1
DEVICE COUNT:31
Owners Rep Sign: otaltd..14 Date: 4/15/2019 Inspector Sign: �✓ 41
4 of 4AND DETECTION REPORT Cedarwood School
ALARMPage
Zone or DEVICE
DEVICE SLC
TYPE DEVICE LOCATION PASS FAIL NOTE # CHANNEL #
PSD ABOVE FACP X 2 1
TS Rooms 15-18 X 9 7
TS Rooms 9-10 X 19 1
TS Rooms 5-6 X
WF Rooms 5-6 X 16 1
WF Rooms 15-18 X 9 6
WF Rooms 9-10 X 3 5
KH Kitchen Hood X 6 1
LEGEND
PSD — Photc'elec:tric Smoke Detector BD — Beam Detector H — Horn V —Visual
ISC — Ionizatjon Smoke Detector PS— Pull Station WPH — Weather Proof Horn TS—Tamper Switch
PD D — Photo Du it '=7rnoke Detector- RR — Rate of Rise Heat Detector C — Chime WF — Water Flow Switch
IC:'L) — 1 on DUct Smoke Detector HT — Fixed Temp Heat Detector CV — Lihirne Visual DH — Door Holder
DH'_ — Door Holder & Smoke Detector- FC Flame Detector S— Speaker OSY — Outside Stern & Yoke Tamper Valve
SSD — S[R nal Station Em oft e Detector P — RelI AV —Audible Visual PIV — Pci t InHicator Valve
Cur - Elevator Curtains FRD - Fire Rolldown Door SDC Smoke Detector & Door Holder Combo
CO - Carbon Monoxide Detector - - -
NOTE # COMMENT
2 Tamper switches failed to supervise fire alarm panel
77104d-
4/15/2019
Owners Rep Sign: A Date: Inspector Sign: /49bil ‘47.06