Loading...
HomeMy WebLinkAboutFAI15-0083 CALFIRE FIRE PUMP TEST 201425-88 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS Inspection, Testing, and Maintenance Fire Pumps Page 1 of 8 NFPA 25, Chapter 8 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: 4/10/14 Pump ID: Aurora pF Cqt� ; ct 1 ,Opy dx f , 1 ori � i k�, , M��� Instructions Property Information: Name: Gold Country Casino Serial Number: r 04-1110521 Address: 4020 Olive HiwayAbbreviation Key: I = Inspection T = Test M = Maintenance A -O = After Operation MI = Per Manufacturer's separate form for each pump City: Oroville, CA Nameplate Data Annual Fire Pump Test Results Date of Pump Test: Shaft Orientation: ✓ Horizontal Vertical 4/10/14 Number of pumps If multiple pumps: Series arrangement Parallel arrangement NOTE: Submit a at this location: 1 Type of Driver: ✓ Electric Diesel Gasoline Steam Gas separate form for each pump Nameplate Data Test Results Shutoff Pressure 212 psi Flow (gpm) Net Pump Pressure (psi) RPM Volts Amps 100% Rated Capacity 1000 gpm 0 203-3=200 3575 460 76 100% Rated Pressure 180 psi 1000 180-0=180 3568 460 150 150% Rated Capacity 1500 gpm 1500 150-0=150 3560 460 165 65% Rated Pressure 155Psi - - - Rated RPM 3560 rpm - -- - - Type of Test: Discharge to Atmosphere v Recirculation Test EquipmentController: Flow Meter / Play pipe (1-1/8") Play pipe (1-3/4") Diffuser / Size: Size: 6" Manufacturer: Cutler Hammer Serial Number: 16B6791 E State Fire Marshal AES 5 March 21, 2006 ANNEX B 25-89 Inspection, Testing, and Maintenance Fire Pumps Page 2 of 8 NFPA 25, Chapter 8 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: Property Information: Name: Gold Country Casino 4/10/14 Pump ID: Aurora -m. h•c*",'gC14. 4 \t �iV jj,I 9..� p. Instructions NFPA 25 Reference Serial Number: 04-1110521t Address: 4020 Olive Hiway Pass Abbreviation Key: I = Inspection T = Test M = Maintenance A -O = After Operation MI = Per Manufacturer's I Weekl y City: Oroville, CA 2 2 1 8O ' FIRE PUMP INSPECTIONS Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.1 I Weekl y Pump House heating and ventilating louvers 2 2 1 8O ' ;/� 1.2 1 Weekly Circulation Relief Valve 12.5.6.1X' 1.3 1 Weekly Pressure Relief Valve 12.5.6.2 j X 1.4 1 Quarterly Control Valves 12.3.2.1 X Fire Pump System: 8.2.2(2) 1.5 I Weekly a. Pump Suction, discharge, and bypass valves are open. 8.2.2(2)(a) X 1.6 1 Weekly b. Piping is free of leaks. 8.2.2(2)(b) X" 1.7 I Weekly normal c. Suction pressure gauge reading is 8.2.2(2)(c)iX 4 1.8 1 Weekly d. System line pressure gauge reading is normal 8.2.2(2)(d) X 1.9 1 Weekly e. Suction reservoir is full. 8.2.2(2)(e) X 1.10 I Weekly f. Wet pit suction screens are unobstructed and in place. 8.2.2(2)(f) Electrical System Conditions: 8.2.2(3) 1.11 1 Weekly a. Controller pilot light is illuminated. 8.2.2(3)(a) X 1.12 I Weekly b. Transfer switch normal pilot light is illuminated. 8.2.2(3)(b) ; 'X 1.13 I Weekly c. Isolating switch is closed — standby (emergency) source. 8.2.2(3)(c) X 1.14 1 Weekly d. Reverse phase alarm pilot light is off or normal phase rotation pilot Tight is on. 8.2.2(3)(d) _._. ( X 1.15 I Weekly Oil level in vertical motor sight glass is normal. 8 2 2(3)(e) X Diesel Engine System Conditions: 8.2.2(4) 1.16 1 Weekly a. Fuel tank is two-thirds full. 8.2.2(4)(a) [)< { State Fire Marshal AES 5 March 21, 2006 25-90 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS Inspection, Testing, and Maintenance Fire Pumps Page 3 of 8 NFPA 25, Chapter 8 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: 4/10/14 Pump ID: Aurora oF,_C4 /s.. Q h kiiiiirl' Instructions Property Information: Name: Gold Country Casino Serial Number: i4r 04-1110521 Address: 4020 Olive Hiway Abbreviation Key: 1= Inspection T = Test M = Maintenance A -O = After Operation MI = Per Manufacturer's 1.17 City: Oroville, CA Weekly Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.17 I Weekly b. Controller selector switch is in “auto" position. 8.2.2(4)(b) X ;--_ 1.18 1 Weekly c. Batteries (2) voltage readings are normal 8 2 2(4)(c) X 1.19 I Weekly d. Batteries (2) charging current readings are normal 8.2.2(4)(d) i_"` X ! e. Batteries (2) pilot lights are on or l 1.20 I Weekly battery failure (2) lights are off. 8.2.2(4)(e) iX 1.21 1 Weekly f. All alarm pilot lights are off. 8.2.2(4)(f) ; , X 1.22 I Weekly g. Engine running time meter is reading. 8.2.2(4)(g) i�� =X 1.23 I Weekly h. Oil level in right angle gear drive is normal. 8.2.2(4)(h) X 1.24 I Weekly i. Crankcase oil level is normal. 8.2.2(4)(i) i X 1.25 1 Weekly j. Cooling water level is normal. 8.2.2(4)0),5<-- 1.26 I Weekly k. Electrolyte level in batteries is normal. 8.2.2(4)(k) I� �X 1.27 1 Weekly I. battery terminals are free from corrosion. 8 2 2(4)(I),m_X ._ 1.28 1 Weekly m. Water -jacket heater is operating. 8.2.2(4)(m) Xc Steam System Conditions: 8.2.2(5) Steam pressure gauge reading is t-- 1.29 I Weekly normal. 8.2.2(5) X Pump System: Table 8.5.3(A) 1.30 I A-0 Wet pit suction screens Table 8.5.3(A)(5) X _..� Electrical System: Table 8.5.3(C) Inspect emergency manual starting Table ± 1.31 I Annually means 8.5.3(C)(4) jX' Diesel Engine System: Table 8.5.3(D) 1.32 1 Weekly Fuel: Tank Level. Table rX 8.5.3(D)(1)(a) State Fire Marshal AES 5 March 21, 2006 ANNEX B 25-91 Inspection, Testing, and Maintenance Fire Pumps Page 4 of 8 NFPA 25, Chapter 8 as amended by CCR, Title 19 4/10/14Aurora Date of Inspection, Testing, Maintenance: Pump ID: •., ��'pF A(/O i „Q;ass j giii D0 9jIQi F �-`''' MP:" Instructions Property Information: Name: Gold Country Casino Serial Number: 04-1110521 Address: 4020 Olive HiwayI Abbreviation Key: = Inspection p T = Test M = Maintenance A -O = After Operation MI = Per Manufacturer's City: Oroville, CA y 1 Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.33 1 Weekly Fuel: Tank Float Switch Table 8.5.3(D)(1)(b) j �/ iX 1.34 1 Weekly Fuel: Solenoid valve operation Table 8.5.3(D)(1)(c) 1.35 I Weekly Fuel: Flexible hoses and connectors Table 8.5.3(D)(1)(g)Table I _ X /� ' 1.36 1 Weekly Lubrication System: Oil level. 8,5.3(D)(2)(a) , X..__. 1.37 1 Weekly Cooling System: Level Table 8.5.3(D)(3)(a) I X 1.38 I Weeklyto Cooling System: Adequate cooling water heat exchanger. Table.__. 8.5.3(D)(3)(d) i X 1.39 1 Weekly Cooling System: Water pumps. Table 8.5.3(D)(3)(� ;" — 1.40 I Weekly Cooling System: Condition of flexible hoses and connections. Table 8.5.3(D)(3)(g)Table `— X 3.. 1.41 1 Weekly Cooling System: Jacket water heater g 5.3(D)(3)(h) 1.42 1 Weekly Battery System: Electrolyte level. Table 8.5.3(D)(5)(a)Table '-`... 1.43 1 Weekly Exhaust System: Leakage 8.5.3(D)(4)(a) X I Weekly Electrical System: General inspection Table 8.5.3(D)(6)(a) 7 5‹1.44 1.45 1 Monthly Battery System: Charger and charge rate. Table 8.5.3(D)(50) I-" $X 1.46 I Monthly Battery System: Equalize charge. Table 8.5.3(o)(5)(f) I�` ^ 1.47 1 Monthly Electrical System: Circuit breakers or fuses. Table 8.5.3(D)(6)(f) 1 r" IX 1.48 I Quarterly Lubrication System: Crankcase breather Table 8.5.3(D)(2)(e) iX 1.49 I Quarterly Exhaust System: Insulation and fire hazards. Table 8.5.3(D)(4)(c) 'X 1.50I Quarterly Battery System: Terminals clean and tight. able g 5.3(D)(5)(b) 1 IX ` 1.51 I Quarterly Electrical System: Wire chafing where subject to moving. Table 8.5.3(D)(6)(c) IX 1.52 1 Semiannually Cooling System: Antifreeze protection level Table 8.5.3(D)(3)(b) I lX State Fire Marshal AES 5 March 21, 2006 25-92 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS Inspection, Testing, and Maintenance Fire Pumps Page 5 of 8 NFPA 25, Chapter 8 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: Property Information: Name: Gold Country Casino 4/10/14 Pump ID: Aurora y, NFPA 25 Reference pFC4 tif � ..'``'t4 1 ti Serial Number: meq= t11P 1 9z.i. 04-1110521 ?� Address: 4020 Olive Hiway Pass Abbreviation Key: v,�`¢'�`° -'�i I = Inspection h nP� T = Test M = Maintenance A -O = After Operation = Per Manufacturer's Instructions I Semiannually Oroville, CA City:MI Table 8.5.3(D)(4)(f) I_ ._ _ E._' [X Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.53 I Semiannually Exhaust System: Flexible exhaust section. Table 8.5.3(D)(4)(f) I_ ._ _ E._' [X •-. 1.54 I Annually Fuel: Tank vents and overflow piping is unobstructed. Table 8.5.3(D)(1)(h) 'mm– """"" X 1.55 I Annually Fuel: Piping. Table 8.5.3(D)(1)(i) =— lX "__. 1.56 I Annually Cooling System: Inspect ductwork Table 8.5.3(D)(3)(i) X I Annually Exhaust System: Hangers and supports. Table1.57 ;%8.5.3(D)(4)(e) _.. FIRE PUMP TESTS 2.1 T Weekly Pump Operation – No Flow condition 8.3.1 IX' 2.2 T Monthly Engine Generator Sets NFPA 110 IX 2.3 T Annually Control Valve – Position 12.3.3.1 I X 2.4 T Annually Control Valve – Operation 12.3.3.1 j :X 2.5 T Annually Supervisory 12.3.3.5 ! X 2.6 T Annually Pump Operation – Flow condition 8.3.3.1 X' 2.7 T 5 Year Pressure Reducing Valve 12.5.1.2 iX, 2.8 T Automatic Transfer Switches NFPA 110 ., X Pump System: Table 8.5.3(A) 2.9 T Annually Play. P System: Check Pump shaft end 8.5.3(A)(2) -- FX 2.10 T Annually Pump System: Check accuracy of pressure gauges and sensors. Table 8.5.3(A)(3) X 2.11 T Annually Pump System: Check pump coupling alignment. Table 8.5.3(A)(4) 'mmY – a X 2.12 T Annually Pressure Relief Valve 12.5.6.2.2X 2.13 T Annually Circulation Relief Valve 12.5.6.1.2 E ,X State Fire Marshal AES 5 March 21, 2006 ANNEX B 25-93 Inspection, Testing, and Maintenance Fire Pumps Page 6 of 8 NFPA 25, Chapter 8 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: 4/10/14 Pump ID: Aurora - _ Q,�9 9 p r 4 V �� yC --- '.. '\Fp Instructions Property Information: Name: Gold Country Casino Serial Number: 04-1110521 f Address: 4020 Olive Hiway Abbreviation Key: I = Inspection T = Test M = Maintenance A -O = After Operation = Per Manufacturer's Oroville, CA City:MI Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass Electrical System: Table 8.5.3(C) 2.14 T Monthly Electrical System: Exercise isolating switch and circuit breaker. Table 8.5.3(C)(1) X 2.15 T Semiannually Electrical System: Operate manual starting means (electrical). Table 8.5.3(C)(3) X 2.16 T Annually Electrical System: Trip circuit breaker (if mechanism provided). Table 8.5.3(C)(2) 2.17 T Annually Electrical System: Operate emergency manual starting means (without power). Table 8.5.3(C)(4) i ;X Diesel Engine System: Table 8.5.3(D) 2.18 T Monthly Battery System: Specific Gravity or state of charge Table 8.5.3(D)(5)(d) - X 2.19 T Semiannually Electrical System: Operation of safeties and alarms. Table 8.5.3(D)(6)(d) X 2.20 T Annually Exhaust System: Excessive back pressure Table 8.5.3(D)(4)(d) X 'm Fire Pump Maintenance (NFPA 25: 8.5.1) 3.1 M Annually Control valves 12.3.4 X' Pump System: Table 8.5.3(A) 3.2 M Annually Lubricate pump bearings Table 8.5.3(A)(1) X Mechanical Transmission: Table 8.5.3(B) 3.3 M Annually Lubricate Coupling Table 8.5.3(6)(1) r- i. - 1X 3.4 M Annually Lubricate right-angle gear drive Table 8.3(B)(2) X - Electrical System: Table 8.5.3(C) 3.5 M Annually Tighten electrical connections Table 8.5.3(C)(5) - X 3.6 M Annually Lubricate mechanical moving parts (excluding starters and relays) Table 8.5.3(C)(6) iX State Fire Marshal AES 5 March 21, 2006 25-94 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS Inspection, Testing, and Maintenance Fire Pumps Page 7 of 8 NFPA 25, Chapter 8 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: 4/10/14 Pump ID: Aurora ca4 Property Information: Name: Gold Country Casino of Serial Number: ZQ t f -A 1, 04-1110521 ' CO'' 'Tr- ce Address: 4020 Olive Hiway Abbreviation Key: 'u ,, Tr I = Inspection hEIA T = Test M = Maintenance A-0 = After Operation = Per Manufacturer's Instructions Pass Oroville, CA City:MI M Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 3.7 M Annually Calibrate pressure switch settings. Table 8.5.3(C)(7) i IX 3.8 M Annually Grease motor bearings Table 8.5.3(C)(8) X Diesel Engine System: Table 8.5.3(D) 3.9 M Weekly Fuel: Water in system. Table 8.5.3(D)(1)(f) X 3.10 M Quarterly Fuel: Strainer, filter, or dirt leg, or combination thereof. Table 8.5.3(D)(1)(d) X 3.11 M Annually Fuel: Water or foreign material in tank. Table 8.5.3(D)(1)(e) FX 3.12 M Annually Cooling System: Antifreeze Table 8.5.3(D)(3)(c) X Lubrication System: Table 8.5.3(D)(2) 3.13 M Weekly Lube oil heater Table 8.5.3(D)(2)(d) a. X 3.14 M Quarterly Crankcase breather Table 8.5.3(D)(2)(e) X 3.15 M Annually/50 Hours Oil change Table 8.5.3(D)(2)(b) r,X 3.16 M Annually/50 Hours Oil Filter(s)X Table 8.5.3(D)(2)(c) ._ Cooling System: Table 8.5.3(D)(3) 3.17 M Quarterly Water Strainer Table 8.5.3(D)(3)(j) X 3.18 M Semiannually Antifreeze protection level. Table 8.5.3(D)(3)b) ; 1X 3.19 M Annually Rod out heat exchanger. Table 8.5.3(D)(3)(e) X 3.20 M Annually Clean louvers. Table 8.5.3(D)(3)(i) X Exhaust System: Table 8.5.3(D)(4) 3.21 M Weekly Drain condensate trap. Table 8.5.3(D)(4)(b) State Fire Marshal AES 5 March 21, 2006 ANNEX B 25-95 Inspection, Testing, and Maintenance Fire Pumps Page 8 of 8 NFPA 25, Chapter 8 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: 4/10/14 Pump ID: Aurora ---;--'7- tiof 4r/ tI 6 0l �'O9At -�?� ` 'Q gip" Property Information: Name: Gold Country Casino Serial Number: 04-1110521 Address: 4020 Olive Hiway Abbreviation Key: I = Inspection T = Test M = Maintenance A -O = After Operation = Per Manufacturer's Instructions Oroville,CA City:MI Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass Battery System: 3.22 M Monthly Remove corrosion, case exterior clean and dry. Table 8.5.3(D)(5)(c) f i __. t X Electrical System: Table 8.5.3(D)(6) 3.23 M Semiannually Boxes, panels, and cabinets. Table 8.5.3(D1(6)(e) of continuation pages) ° """°°'cka, MIS nnSugo.em�%ien.wen®mnutw. ,0,. o,,. ,.,,.° NW X, PASS John Swett FAILD 3.24 M Annually Tighten control and power wiring connections. Table 8.5. JD)(6)(b)Table i X, 3.25 M Biannually Circuit breakers and fuses 8.5.3(D)(6)(g) , Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the Activity listed above: See Continuation Page(s) (Indicate the number of continuation pages) ° """°°'cka, MIS nnSugo.em�%ien.wen®mnutw. ,0,. o,,. ,.,,.° NW 4/14/14 PASS John Swett FAILD Signature Date State Fire Marshal AES 5 March 21, 2006 FAI15-0083 068-160-076