HomeMy WebLinkAboutFAI15-0078 Fire Annual Inspection 2017FIRE
Butte County Fire Department
California Department of Forestry and Fire Protection
Fire Prevention Bureau
176 Nelson Avenue, Oroville, CA 95965
530-538-7888/530-538-2105(fax)
Fire Safety Inspection
Business Address: z ti op, t- v. -LIa Air i
Business Name: OP h 2, k t-to'oO.
Owner/Manager: R :.,—,F} (`0S�►t
Bus: 53.2-- 3t
Other:
Other Contact:
Bus:
Other:
Building Owner: OQ.0.;�l.L iZ, or. t Fr:a:5
Bus:
Other:
Address:
Occ. Class: e
N INSPECTION OF YOUR FACILITY REVEALED THE FOLLOWING:
TAILED EXPLANATION AND CORRECTIONS:
RRECTED:
extinguishers: required, service due
/10. Exit(s): obstructed, inadequate
AFire
. Extension cords: Excessive use, defective
V
11. Exit sign(s): required, illumination, photo luminescent
1\,
3. Excessive rubbish, trash, debris
IN w L t-srfci)
12. Exit sign lights: obstructed, defective
4. Fire alarm system defective
13. Exit lighting: required, defective
5. Sprinkler system: service required, defective
14. Heating system: defective appliance, flue combustibles
6. Kitchen hood ext. system: service due
15. Wiring: exposed, damaged connectors, etc.
7. Fire walls, ceilings, fire doors, draft stopsA6.
Address posted and visible from road
8. Smoke detectors: required, defective
17. Other
9. Fire drill log checked Yes Vlo u
18. Other type of inspection — State below
TAILED EXPLANATION AND CORRECTIONS:
RRECTED:
y order of the Fire Chief: You are hereby notified t c rrect all violaton immediately or show cause why you should not be
required to do so. A re -inspection will be conducted on Z c, 17 °`^ 3 2 /7 . Willful failure to comply with this notice is a
misdemeanor. Violations that are not corrected immediately 'dn /or remain a the re -inspection may be processed as a criminal
offense. Thank you for your assistance and cooperation in minimizing the fire and life loss in our community. (H & S sec. 13112)
White Copy — Station File Yellow Copy — Re-inspect/business
Pink Copy — Business ❑ Check when sent to prevention
4777, \
1\,
i'
IN w L t-srfci)
Date:
I � 2.-co1 0
Discuss
(Print)
with:
yr y A,."
S.
d:
attalion 1 2 3 4
5)
7
Station:
r
(04 FPB
Ins
cting Officer:
0 i1"ilO fi.:rz1.
y order of the Fire Chief: You are hereby notified t c rrect all violaton immediately or show cause why you should not be
required to do so. A re -inspection will be conducted on Z c, 17 °`^ 3 2 /7 . Willful failure to comply with this notice is a
misdemeanor. Violations that are not corrected immediately 'dn /or remain a the re -inspection may be processed as a criminal
offense. Thank you for your assistance and cooperation in minimizing the fire and life loss in our community. (H & S sec. 13112)
White Copy — Station File Yellow Copy — Re-inspect/business
Pink Copy — Business ❑ Check when sent to prevention
Ophir School
210 Oakvale Ave
Oroville, CA 95966
Attn: Rita Costa
Attn: Brian Holmes
Butte County /CALFIRE
176 Nelson Ave
Oroville, CA 95966
Chad Porter: Captain
January 26, 2017
On January 26, 2017 we conducted a Title 19 (Fire & Life Safety Inspection) at the Ophir
School and found the following issues in need of repair. Please feel free to contact the
station with any question. A Re -inspection is scheduled for February 9th 2017 at 3:00 pm.
If this time doesn't fit with your schedule please contact us as we will be happy to work
with you.
• Kitchen door in between the kitchen and cafeteria is a fire rated door and needs to
be self-closing. This was an issue in our last inspection
• Exit signs (CFC 1011.3 & 1011.6.3) shall be internally or externally illuminated
at all times; signs shall be connected to an emergency power system that provides
power for not less than 90 minutes in case of primary power failure. If the sign is
externally illuminated it will be stamped with a date good for 10 years.
o All class rooms must have an exit sign posted.
• The 5th & 6th grade classroom area
o Both double doors hang up and don't swing freely.
• Room 24
o Remove the extension cord that goes to a power strip
o We need to research a different method to secure students. I realize that
this class services severely disabled students, but with gate and locking
mechanism located at the 6' mark can prevent exit to a safe location and
needs to be removed immediately.
• Extinguishers need to be marked
o Room 17
o Library
o Room 24
• All storage rooms need to maintain the following.
o 36" of clearance around (electrical panels, water heaters, and appliances)
o Any room in use needs to maintain free ingress and egress paths.
• The school has 2 different sprinkler systems (Furnace / AC room over in the
second grade wing and janitor's room off of the gym/ cafeteria). The school needs
to verify and show proof of service or that they have been allowed to become
decommissioned systems.
I talked to Jim Galloway on our last inspection about the sprinkler system and it was my
understanding that he has a letter that is allowing the school district to abandon the
current partial sprinkler system. I would like to include a copy of the approval in your
file.
Please let me know if you have any question or concerns.
Chad Porter
Captain
(530) 538-7228
Wet Pipe California
Fire Sprinkler System Inspection,
Property Information
Code of Regulations
Testing, and Maintenance
- Title 19 Quarterly and 1 of 3
Annual Report
Contractor or Licensed Owner Information
' F �A�(As / Y,J
4z-, es, i -A ,,
�( `D
li, "CS • P
MP
Building Name Ophir School
Name Voltage Specialists
ess
Address 5031 Foster Road
210 oakvale Ave
City Paradise St. CA Zip 95969
City Oroville
License #
Phone 530-362-2609
Contact Person
fl SFM
Job #
Jim Galloway
Ig CSLB 880862
Misc.
= Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Main Drain
Diameter
Main Drain
Initial Static
Pressure
Test (Annual)
Residual
Pressure
NFPA 25 CA ed.
Reference
Date _
Riser
No.
Location
Riser
Diameter
Final Static
Pressure
p F,N/A
1
MP boiler room
1 1/4
N/A
N/A
N/A
N/A
N/A
2
Primary building boiler room
1 1/4
N/A
N/A
N/A
N/A
N/A
Waterflow Alarm Devices
5.2.5
N/A
1.4
1
Supervisory Devices
5.2.5
N/A
1.5
1
Gauges (Wet Pipe Systems)
5.2.4.1
N/A
1.6
1
n This building has more than 5 risers. See additional AES 2.9 form attached
Number of AES 2.9 forms attached j I
= Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item
Description
NFPA 25 CA ed.
Reference
Date _
•Date Date
Date
Date_ _�_
1.1
1
Control Valves - Identification Sign
13.3.1
N/A
. 2
1
Control Valves - Inspection
13.3.2
P
-r.3
I
Waterflow Alarm Devices
5.2.5
N/A
1.4
1
Supervisory Devices
5.2.5
N/A
1.5
1
Gauges (Wet Pipe Systems)
5.2.4.1
N/A
1.6
1
Enter Water Supply Pressure Below Riser Check
5.2.4.1
psi
psi
psi
psi
1.7
1
Enter Water Supply Pressure Above Riser Check
5.2.4.1
psi
psi
psi
psi
1.8
1
Pressure Readings Acceptable
5.2.4.1
N/A
1 9
1
Hydraulic Design Information Sign
(for hydraulically designed systems)
5.2.6
N/A
1.10
I
General Information Sign
(not required for system prior to 2007 edition of NFPA 13)
5.2.8
N/A
1.11
1
Heat Tape
5.2.7
N/A
1.12
I
Spare Sprinklers
5.2.1.4
P
1.13
1
Fire Department Connections
13.7
N/A
1.14
1
Alarm Valves - Exterior Inspection
13.4.1
N/A
1.15
1
Pressure Reducing Valves
13.5.1.1
N/A
1.16
1
Backflow Preventers
13.6.1
N/A
1.17
1
Small Hose Connections - Hose Valve
5.1.6, 13.5.2
13.5.5.1
N/A
9
1
PRV - Fire Sprinkler Systems
13.5.1.1
N/A
'Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or 111
standpipe systems.
I
Wet Pipe
Fire Sprinkler System
California Code of Regulations - Title 19
Inspection, Testing, and Maintenance
Quarterly and
Annual Report
2 of 3
Property Information
Building NameOphir School
'ess
210 oakvale Ave
City Oroville
Contractor or Licensed Owner Information
Name
Voltage Specialists
Job #
ANNUAL INSPECTION, TESTING, AND MAINTENANCE
gid,. Include ALL Quarterly Inspections
1 = Inspection T = Test M = Maintenance P = Pass F = Fail N/A = Not Applicable
Item
Description
NFPA 25 CA ed.
Reference
Date
Comments Only
P,F,N/A
1.19
I
Sprinklers
5.2.1
3/2/17
2.3
P
1.20
1
Buildings (Freeze Protection)
4.1.1.1
3/2/17
Owner's Responsibility
P
1.21
I
Pipe and Fittings
5.2.2
3/2/17
1,2
P
1.22
I
Hangers
5.2.3
3/2/17
P
1.23
I
Seismic Braces
5.2.3
N/A
2.1
T
Field Service Test Required
(Send Report to Fire Code Official)
5.3.1
If REQUIRED, Enter 'F until
results are returned from Lab
N/A
2 2
T
Recalled Sprinklers
If not present = Pass; If present = Fail
Title 19
904.1(c)
N/A
2.3
T
Water Flow Alarm Devices
90 sec. maximum - (Enter Time)
5.3.3
13.2.6
sec.
N/A
2.4
T
Main Drain Test
(Enter data on Page 1 of this form)
13.2.5
13.3.3.4
N/A
2.5
T
Control Valve - Position
13.3.3.2
3/2/17
P
^ 6
T
Control Valve – Operation
13.3.3.1
3/2/17
P
z.7
T
Supervisory Devices
13.3.3.5
N/A
2.8
T
Backflow Preventer Assemblies
13.6.2
N/A
2.9
T
Small Hose Connections*
w/PRV Hose Valves – Partial Flow Test
13.5.2.3
13.5.3.3
N/A
2.10
T
PRV – Fire Sprinkler Systems
13.5.1.3
N/A
3.1
M
Control Valves
13.3.4
N/A
3.2
M
Small Hose Connections*
13.5.6.3
N/A
3.3
M
Obstruction Investigation required
(If "Yes", see Deficiencies and Comments Section
for Results.)
14.3
_—
,/
Yes
No
3.4
M
System Returned to Service
4.5.3
Yes
No
* Small
standpipe
hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II, or III
systems.
D = Deficiency C = Comment
Indicate pe)
e 6,en tesand om trients
laceci
3/2/17
1,2
✓
Fire systems do not meet NFPA 13 requirements.
2.3
3/2/17
1,2
No water flow switch installed
2.4
3/2/17
1,2
No main drain installed
3
3/2/17
1,2
No inspectors test valve installed
3/2/17
1
Covers only boiler room and old storage room 3 sprinkler heads on system
Wet Pipe
Fire Sprinkler System
California Code of Regulations - Title 19 Quarterly and
Inspection, Testing, and Maintenance Annual Report
3 of 3
Property Information
Building Name Ophir School
ess
210 oakvale Ave
City Oroville
Contractor or Licensed Owner Information
Name
Voltage Specialists
Job #
D = Deficiency
Item
C
Date
= Comment
Riser
(Indicate pe)
D G Deficiencies and Comments (cont.)
„ .,, irate all equipment, devices and 3arts that were �,a{rel or replaced
03/02/17
2
Sprinkler system only covers boiler room and two storage rooms. 4 heads installed
03/02/17
1,2
No gauges installed on fire sprinkler systems
s.�
a.;
mi
nu
1
an
Check here if additional Deficiencies and Comments are listed on Form AES9 Number attached:
See Correction Form AES 10 for corrected deficiencies. Number attached:
I hereby certify that the fire protection equipment listed above has been fully inspected, tested, and maintained on this date by
the company indicated above, in accordance with CCR, Title 19, Sections 901 to 906 and that the equipment is fully operable
except as noted in the "Deficiencies and Comments" section of this form.
L
Check box if Annual Inspection, Testing & Maintenance Items are Completed in the Indicated Quarter
Quarter 1st - j7 Annual 2nd - fl Annual
Date 03/02/17
Print Name Don Cantrell
Signature
L
Don Cantrell
3rd - f Annual 4th - 0 Annual