FAI18-0013 CF Overhead Sprinkler Hydro Test
6 (17- 12o-013\ • 1/ 1 • , A , , r 41,,k ir 0 fr- II ,414 DESIGN a INSTALLATION • INSPECTION • REPAIR • EXTINGUISHERS Rocklin Office:4000 Alvis Ct.,Rocklin,CA 95677• Phone:(916)663-3532 Chico Office: 170 Enna Ct,Chico,CA 95928•Phone:(530)826-3013 Greater Bay Area Office:2280 Bates Aye,Ste_A.Concord,CA 94520•(925)209-6164 Redding Office:3092 Crossroads Dr.Ste. 1,Redding,CA 96003 •Phone:(530)223-2492 C.L.C16#783132&C10#998129 August 7, 2017 Butte County Fire-CALFIRE Administrative Office 176 Nelson Avenue Oroville, CA 95965 To Whom to May Concern; Enclosed is a copy of the Title 19 5-year Fire Sprinkler Inspection Report for Berberian Nut located at 6100 Wilson Landing Rd. in Chico CA that was recently preform by Rick Zimmerman of Foothill Fire Protection. This property did not pass the inspection so we have given them a quote for corrections. After we have performed these corrections we will send you an updated inspection report. Please keep this copy for your records. If you have any questions or would like to speak to Rick regarding this report and its findings, please feel free to call our office at(530) 826-3013. Thank you Darci Peck Administrative Assistant dpeck@ffprotection.com Inspection, Testing, and Maintenance Cover Sheet NFPA25 as amended by CCR, Title 19 ,,,,,ic.--,--. ,::..,./&., Property Information: Name: Berberian Nut Company Occupancy/Use: Office/Processing Plant 6100 Wilson Landing Steel ' O `A Address: Construction Type: k*, C1,cQ i# City: Chico No. Stories: 1 �� � 4 �qtl,, ZIP: 95927 Year Constructed: 2007 �t'9.\\�� •r, Contact: Taylor Bean ' + jp. �� Telephone: (530) 343-5365 i/; ir0 % Vii,;, �,, Contra r Information: um r of System Risers Name: Foothill Fire Protection; Inc. Copy sent to: Address: 170 Erma Ct E3 Owner Date: 07/31/17 City: Chico ZFire AHJ Date: 07/31/17 State: CA ❑Contractor Date: (530)826-3013 NOTES: Telephone: 1) For specific inspection,testing,and maintenance 783132 requirements and information,see NFPA 25, 2011 CA License#: edition as amended by California Code of Regulations, Title 19, §901 to§906. Job#: 6100WIL 2) Inspection items may be performed by the owner in Performed by: Rick Zimmerman accordance with California Code of Regulations, Title 19, §904.1(a) Check box f*eadkaYstein inspected and enter tie number of forms used for inspec on- ; CheclC;boxe's(Fai1 or Pass)to indicate status of inspected system at end of inspe�, _ .w Forms Included with this Report NFPA 25 p Number of Forms N/A Fail* Pass Chapter m Automatic Sprinkler System 5 4 ❑ ❑✓ E D Standpipe and Hose System 6 0 0 ❑ ❑ ❑ Private Water Supply System 7 0 El ❑ ❑ ❑ Fire Pump 8 0 ❑ ❑ O Water Storage Tank 9 0 ❑ ❑ O Water Spray System 10 0 ❑ ❑ O Foam Water Sprinkler System 11 0 ✓ ❑ ❑ O Water Mist System 12 0 ❑ ❑ ❑Concerns that are Not Deficiencies(i.e. Non-Sprinklered Areas) 0 Yes 0 No *See"Deficiencies and Comments"section at end of each resp?ctf've form. AES 1 September 3,2013 ' ° " Wet Pipe California Code of Regulations-Title 19 5-Year Fire Sprinkler System Inspection,'Testing, and Maintenance Report 1 of 3 Property Information Tt.a �o�i Contractor or Licensed Owner Information //II. IF -41\11,io Building Name Berberian Nut Company } �' "" ��'�--"���e Name Foothill Fire Protection, Inc. '%' .. i,4i% Address 170 Erma Ct r �tl tp `-^fy �} Address 6100 Wilson Landing � N!` City Chico St. CA Zip 95928 License# 783132 Phone (530)826-3013 City Chico El SFM Job# 6100WIL Contact Person Taylor Bean © CSLB C-16 Misc. Riser informrr AN AL Riser , .,;,,,,,,44, '//�,„/ Riser\ DAL-1-'6;7;k; Initial Static Residual . Final Static �� ;_` ,� � '� _ ; :, ' Diameter Diameter ” Pressure L Pressure Pressure 1 Left 3 2 109 8 ........t 45 P I 2 Left Middle 4 2 113 20 45 P 2 Right Middle 6 2 113 25 45 P 4 Right 6 2 120 30 45 P 0 This building has more than 5 risers. See additional AES 2.9 form attached. Number of AES 2.9 forms attached: 5-Year INSPECTION,TOTING,AND MAINTENANCE Itdes ALL ice. nd Annual Inspections,Tests,and Maintenance items =Inspection T=Test M=Maintenance P=Pass F=Fail N/A=Not Applicable �r/�'11 4 INFPA 25 CA I ��/ Description a Date Comments Only P,F'N/A 1.1 I Control Valves—Identification Sign 13.3.1 07/21/17 P 1.2 'I I Control Valves—Inspection 13.3.2 07/21/17 P 1.3 I Waterflow Alarm Devices 5.2.5 07/21/17 P 1.4 I Supervisory Devices 5.2.5 07/21/17 P 1.5 I Gauges(Wet Pipe Systems) 5.2.4.1 07/21/17 P 1.6 I Hydraulic Design Information Sign 5.2.6 07/21/17 P (For Hydraulically Designed Systems) 1.7 I Enter Water Supply Pressure Below Riser Check 5.2.4.1 07/21/17 psi P I 1.8 I Enter Water Supply Pressure Above Riser Check 5.2.4.1 07/21/17 psi P 1.9 I Pressure Readings Acceptable 5.2.4.1 07/21/17 P 1.10 ! I General Information Sign 5.2.8 07/21/17 NA (Not Required for System Prior to 2007 Edition NFPA 13) 1.11 I Heat Tape 5.2.7 07/21/17 NA 1.12 I Spare Sprinklers 5.2.1.4 07/21/17 P 1.13 I Fire Department Connections 13.7 07/21/17 P 1.14 I Alarm Valves—Exterior Inspection 13.4.1 07/21/17 P 1.15 I Pressure Reducing Valves 13.5.1.1 07/21/17 NA 1.16 i I Backflow Preventers 13.6.1 07/21/17 P Form AES 2.2 Sept.3,2013 • ' ' Wet Pipe California Code of Regulations-Title 19 5 Year Fire,Sprinkler System inspection,;Testing, and Maintenance , Report 2 of 3 Property Information Cq�''� Contractor or Licensed Owner Information ,,,...,,75,--fO #1 'xQ"l es'i -4►, - it Building Name Berberian Nut Company u� `�, ' in i Name Foothill Fire Protection, Inc. Address 6100 Wilson Landing Itt\.�1`' "k 1'R, Job# 6100WIL City Chico �k\,., ANN ICK STINGyy �y Iff1 ri � Inspection T Test M Maintenance (See P Pass F Fail N/A=NotApplicabie /y" G/I r 'i ril � �" , ., r�;4�/a✓Vj�, ; o°i w » ,'r N rr %� ��/��;-i �,, �,,///.'/ aid r �� r µ% ��"�,,. ///,1Y „��r/r t ", 1.17 I Small Hose Connections-Hose Valve* 5.1.6, 13.5.2 13.5.5.1 7/21/2017 N/A 1.18 I PRV—Fire Sprinkler Systems 13.5.1.1 7/21/2017 N/A 1.19 I Buildings(Freeze Protection) 4.1.1.1 7/21/2017 Owner's Responsibility P 1.20 I Sprinklers 5.2.1 7/21/2017 F 1.21 I Sprinklers-Accessible Concealed Space 5.2.1.1.6 7/21/2017 N/A 1.22 I Pipe and Fittings 5.2.2 7/21/2017 P 1.23 I Pipe and Fittings-Accessible Concealed Space 5.2.2.3 7/21/2017 N/A 1.24 I Hangers 5.2.3 7/21/2017 F 1.25 I Hangers-Accessible Concealed Space 5.2.3.3 7/21/2017 N/A 1.26 I Seismic Braces 5.2.3 7/21/2017 P 1.27 I Seismic Braces-Accessible Concealed Space 5.2.3.3 7/21/2017 N/A 1.28 I Unsprinklered Areas CFC 901.4 7/21/2017 EYes El No 2.1 T Field Service Test Required 5.3.1 7/21/2017 If REQUIRED,Enter'F'until N/A Send Report to Fire Code Official results are returned from Lab 2 2 T Recalled Sprinklers Title 19 7/21/2017 P If not present=Pass; If present=Fail 904.1(c) 2.3 T Water Flow Alarm Devices 5.3.3 7/21/2017 1)37sec.2)45sec,3)46sec sec. F 90 secs max. Enter time 13.2.6 2.4 T Main Drain Test 13.2.5 7/21/2017 P (Enter data on Page 1 of this form) 13.3.3.4 2.5 T Control Valve-Position 13.3.3.2 7/21/2017 P 2.6 T Control Valve—Operation 13.3.3.1 7/21/2017 P 2.7 T Supervisory Devices 13.3.3.5 7/21/2017 F 2.8 T Backflow Preventer Assemblies 13.6.2 7/21/2017 P Small Hose Connections* 13.5.2.3 2.9 T 7/21/2017 N/A w/PRV Hose Valves—Partial Flow Test 13.5.3.3 2.10 T PRV—Fire Sprinkler Systems 13.5.1.3 7/21/2017 N/A 2.11 T Pressure Gauges-Calibration 5.3.2 7/21/2017 New Gauges on risers 1, 2, &3 P 2.12 T Small Hose Connections* 13.5.6.2.2 7/21/2017 N/A *Small hose connections are hose valves and optional hose supplied by the fire sprinkler system. They do not include Class I, II,or III standpipe systems. Form AES 2.2 Sept.3,2013 .3 Wet Pipe California Code of Regulations -Title 19 5 Year Fire Sprinkler System Inspection,Testing, andMaintenance Report 3 of 3 Property Information a ;l+, Contractor or Licensed Owner Information Building Name Berberian Nut Company 01 N f Name Foothill Fire Protection, Inc. 00 Address 6100 Wilson Landing + � Cavy Job# 6100WIL City Chico MPS / / ��/��, '. I =Inspection T =Test M=Maintenance P=Pass F=Fail N/A=Not Applicable ;,,r it », 25 C! %r,// 'r% Withr r ✓ / 1 twon % r/p60,1 er �`� .1€ i fT �,l•:,I�l/A 3.1 M Check Valves- Internal inspection 13.4.2 07/21/17 P 3.2 M Control Valves 13.3.4 07/21/17 P 3.3 M FDC-Backflush 14.3.2.3 07/21/17 P 14.3.2.4 3.4 M Internal Pipe Inspection-See Deficiencies and 14.2 07/21/17 Nos No Comments Section for Results. 3.5 M Obstruction Investigation Required. If"Yes", See 14.3 07/21/17 N/A Deficiencies and Comments Section for Results 3.6 M System Returned to Service 4.5.3 07/21/17 Nos D=Deficiency C=Comment (Indicate type) /, %� r r i' \c fi *ies a� ycrotfit77Mr'/'1 \ '' ' ' �/r �?� RfSEt1 3 C/P/� Indfcatl ui devk*s and at were* rrr� c X Owner maintains system, item 3.4 & 3.5 excluded. X Performed Five year Inspection in Accordance with CA NFPA 25 2.3 7-21-2017 4 X No alarm coverage on riser 4.System is not currently monitored.No alarm will sound/notify during the event of a fire 2.7 7-21-2017 4 X Control valve is not monitored. No signal will be received/reported of system valve is shut off 1.20 7-21-2017 1 X Sprinklers in break room bathrooms are corroded(x6). 1 sprinkler between bathroom entries corroded 1 sprinkler in bathroom in new office area painted 1.24 7-21-2017 2 X Two hangers on the 3"floater main have been disconnected from structure and are hanging from pipe El Check here if additional Deficiencies and Comments are listed on Form AES 9. Number attached: Eli See Correction Form AES 10 for corrected deficiencies. Number attached. I hereby certify that the fire protection equipment listed above has been fully inspected, tested,and maintained on this date by the company indicated above,in accordance with CCR, Title 19,Sections 901 to 906 and that the equipment is fully operable except as noted in the"Deficiencies and Comments"section of this form. Print Name Rick Zimmerman Signature Date 07/31/17 Form AES 2.2 Sept.3,2013