HomeMy WebLinkAbout001-210-025 CF ArchiveCONTRACT'OR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING Factory
Additional copies of this form are Loss Prevemion Publications - Training Resource Center Mutual
System
available to insured from: Factory Mutual Engineering and Research. 1151 Boston -Providence Turnpike, P.O. Box 9102, Norwood MA 02062
PROCEDURE:
Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative. All
defects shall be corrected and system left in service before contractor's personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor.
It is understood the owner's representatives signature in no way prejudices any claim against the contractor for faulty material, poor workmanship,
r►r faiitiro to n^mnly tx:;th nnnrnvina ;k1Ahnr;1-v'c rennin-ment¢ or lncal ordinances -
W1 144.. Yi V ..V vv...v. l .. .... -I-V. v . ...cz . . --; , . - J --------- - - - - - - -
PROPERTY NAME: ENGSTORM WAREHOUSE/PACKING SHED JOB# 05212
DATE: SEPT. 15, 2006
PROPERTY ADDRESS: 8TH STREET, BIGGS, CA
PLANS
ACCEPTED BY APPROVING AUTIHORITY'(S) NAMES: BUTTE COUNTY- BUILDING DIVISION
ADDRESS: 7 COUNTY CENTER DRIVE, OROVILLE, CA 95965
INSTALLATION CONFORMS TO ACCEPTED PLANS YES X NO
EQt'IPMENT L►'SED 1S APPROVED (IF NO, STATE DEVIATIONS BELOW) YES X NO
— -_--- -- -
INSTRUCTIONS
VIAS PERSON-,-C41ARG.E--OF FIZE Et�I,::�';',L1''I' tIEE ' INS; RL CTE D -AS TO LOCATION OF-CON-TROL_ - - AND. - - - ---
VALVES
THE CARE AND MAINTENANCE OF THIS NEW EQUIPNIENT? YES X NO
IF NO, EXPLAIN:
H. -%%*E COPIES OF APPROPRIATE INSTRLICTIONS AND CARE AND MAINTENANCE CHARTS BEEN LEFT ON YES X I NO
PREZ'IISES?
IF NO, EXPLAIN:
LOCATION OF
SYSTEM
SL:PPLIES BUILDINGS
SYSTEM #1
SPRINKLERS
MAKE
TYCO
MODEL
YEAR OF ORIFICE SIZE
MANUFACTURE I
QUANTITY TEMPERATURE
RATING
VIKING PEND.
V K500
2006 3/4"
360 2050
PENDENT
TY -FRB
2006 '/2''
4 1550
PENDENT
TY -FRB
2006 3/4"
4 2000
PIPE & FITTINGS
PIPE CONFORM` TO N FPA # 13 STANDARD
FITTINGS CONFORM TO _ NFPA # 13 STANDARD
YES X NO
YES X NO
ALARM
VALVE OR
FLOW
INDICATOR
ALARM DEVICE
MAXINIU-M TIME TO OPERATE THROUGH TEST PIPE
TYPE
MAKE MODEL
MIN. SEC.
WATERFLOW
swiTCH
POTTER VSR-F
0 60
DRY PIPE
OPERATING
TEST
DRY VALVE
Q.O.D.
MAKE
'MODEL
SERIAL NO.
MAKE
MODEL
SERIALNO.
TIME TO TRIP
THRI 1 TEST
PIPE
WATER
PRESSURE
AIR
PRESSURE
TRIP POINT
AIR PRESSURE
TIME WATER
REACHED OUT.
ALARM OPER-
ATED PROPERLY
MIN.
SEC.
PSI
PSI
PSI
MIN.
SEC.
MIN.
SEC.
WITHOUT
' Q.O.D.
WITH
Q.O.D.
IF NO, EXPLAIN:
OPERATION I PNEUMATIC J ELECTRIC HYDRAULIC
PIPING SUPERVISED
YES
I
NO
I
DETECTING MEDIA
YES
NO
SUPERVISED?
_
DOES THE VALVE OPERATE FROM THE '1IANUAL TRIP AND/OR REMOTE CONTROL?
YES
NO
DELUGE AND
PREACTION
IS THERE AN ACCESSIBLE- FACILITY IN EACH CIRCUIT FOR TESTING?
YES
NO
VALVES
IF NO, EXPLAIN:
DOES EACI4 CIRCUIT OPERATE
DOES EACH CIRCUIT
MAXIMUM TIME TO
MAKE MODEL
SLPERV ISIO`I LOSS ALARM?
OPERATE VALVE
RELEASE?
OPERATE RELEASE
YES NO
YES NO
MIN. SEC.
HYDROSTATIC: HYDROSTATIC TESTS SHALL BE MADE AT NOT LESS THAN 200 PSI (13.6 BARS) ABOVE
STATIC PRESSURE IN EXCESS OF 150 PSI (10.3 BARS) FOR TWO HOURS. -DIFFERENTIAL DRY-
TEST
PIPE, VALVE CLAPPERS SMALL BE LEFT OPEN DURING TEST TO PREVENT DAMAGE. ALL ABOVE-GROUND
PIPING LEAKAGE SHALT. BE STOPPED.
DESCRIPTION
PNEUMATIC: ES'rL ABl.1S'H 40 PSI (2.7 BARS) AIR PRESSURE AND MEASURE DROP WHICH SHALL NOT
EXCEED 1-1/2 PSI (0.1 BARS) IN PRESSURE TANKS AT NORMAL WATER LEVEL AND AIR PRESSURE
AND MEASURE AIR PRI-,SSURE DROP WHICH SHALL NOT EXCEED 1-1/2 PSI (0.1 BARS) IN 24 HRS.
ALL PIPING HYDROSTATICALLY TESTED AT 200 PSI FOR-2 HRS.
IF NO, STATE REASON:
DRQ' PIPING PNEU.NlATICALLV TESTED? YES NO
EQUIPMENT OPERATES PROPERLY? YES NO
DRAIN READING OF GAGE LOCATED NEAR WATER SUPPLY TEST
RESIDUAL PRESSURE WITH VALVE IN
TESTS
PIPE.
TES- 200 PSI
TEST PIPE OPEN WIDE 200 PSI
r UNDERGROUND MAINS AND LEADAN CONNECTIONS TO SYSTEM RISERS SHALL BE FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING.
VERIFIED BY COPY OF'I'nE FORM # 85B? YES NO OTHER EXPLAIN
FlAiSHED BY INSTALLER OF ONDERGROUND YES NO
SPRINKLER PIPING?
BLANK TESTINGNL-NIBER
L!SED
LOCATIONS
NUMBER REMOVED
GASKETS
WELDED PIPING`' x YES NO
IF YES...
DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING YES x NO
PROCEDURES
COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS D10.9. LEVEL AR-3?
WELDINGDO YOU CERTIFY THAT T HE WELDING WAS PERFORMED BY WELDERS QUALIFIED YES X NO
IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST AWS D10"9, LEVEL AR-3?
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A YES x NO
13�)C'L�MEN"I-ED QC:ALITY CONTROL. PROCEDURE TO INSURE THAT ALL DISCS ARE
RFTI'<IEVED. THAT OPE NC_:S IN PIPING ARE SMOOTH. THAT SLAG AND OTHER
WE7LDING RESIDUE ARE RF%iOVED. AND THAT INTERNAL DIAMETERS OF PIPING
ARE NOT PENETRATED?
HYDRAULIC
NAMEPLATE PROVIDED? YES
X
NO
DATA-NAMEPLATE
IF N'O, EXPLAIN:
DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN.-
PEN:REMARKS
REMARKS
t
N.ANIE OF INSTALLING CONTRACTOR: CEN-CAL FIRE SYSTEMS, INC.
TESTS WITNESSED BY
FOR AUTHORITl'HAVING .IIAISDICTION (Signed) TITLE DATE
SIGNATURES
I. L 'G CION 'i ed) TITLE DATE
In --"--
ADDITIONAL EXPL. f ON AN N S:
CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR ABOVEGROUND PIPING ]Factory
Additional copies of this form are Loss Prevention Publications - Training Resource Center Mutual
System
available to insured from: Factory Mutual Engineering and Research, 1151 Boston -Providence Turnpike, P.O. Box 9102, Norwood MA 02062
PROCEDURE:
Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative. All
defects shall be corrected and system left in service before contractor's personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor.
It is understood the owner's representatives signature in no way prejudices any claim against the contractor for faulty material, poor workmanship,
or failure to comply with approving authority's requirements or local ordinances.
PROPERTY NAME: ENGSTORM WAREHOUSE/PACKING SHED JOB# 05212 DATE: SEPT. 15, 2006
PROPERTY ADDRESS: 8T" STREET, BIGGS, CA
ACCEPTED BY APPROVING AUTHORITY'(S) NAMES: BUTTE COUNTY -- BUILDING DIVISION
ADDRESS: 7 COUNTY CENTER DRIVE, OROVILLE, CA 95965
PLANS INSTALLATION CONFORMS TO ACCEPTED PLANS YES X NO
EQUIPMENT USED IS APPROVED (IF NO, STATE DEVIATIONS BELOW) YES X NO
-� -`
INSTRUCTIONS
_
HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL
VALVES
THE CARE AND MAINTENANCE OF THIS NEW EQUIPMENT`'
IF NO, EXPLAIN:
AND
YES X NO
HAVE COPIES OF APPROPRIATE INSTRUCTIONS AND CARE AND MAINTENANCE CHARTS BEEN LEFT ON
PREMISES'
IF NO, EXPLAIN:
YES X NO
LOCATION OF
SYSTEM
SUPPLIES BUILDINGS
SYSTEM #2
SPRINKLERS
MAKE
TYCO
MODEL YEAR OF ORIFICE SIZE
MANUFACTURE
QUANTITY
TEMPERATURE
RATING
VIKING PEND.VK500
2006 3/4" 167
2050
VIKING UPRIG.
VK520 2006 3�4" 72
2050
UPRIGHT
TY -FRB 2006 '/z" 18
2000
PENDENT
TY -FRB 2006 '/2" 16
1550
PENDENT
TY -FRB 2006 3/4" 15
2000
PIPE & FITTINGS
PIPE CONFORMS TO NFPA #13 STANDARD
FITTINGS CONFORM TO NFPA #13 STANDARD
YES X NO
YES X NO
ALARM
VALVE OR
FLOW
INDICATOR
DRY PIPE
OPERATING
TEST
ALARM DEVICE
TYPE MAKE MODEL
WATERFLOW POTTER VSR-F
SWITCH
DRY - - — -_
MAKE I MODEL SERIAL NO.
MAXIMt1M TIME TO OPERATE THROUGH TEST PIPE
MIN. SEC.
0 1 60
MAKE MODEL SERIAL NO.
TIME TO TRIP WATER AIR TRIP POINT TIME WATER ALARA'[ OPER-
THRUT TEST PRESSURE PRESSURE AIR PRESSURE REACHED OUT. ATED PROPERLY
PIPE
MIN. SEC. PSI PSI PSI ` MIN. SEC. MIN. SJEC.
WITHOUT
Q.O.D.
WITH
Q.O.D.
l IF NO, EXPLAIN:
A
OPERATION I PNEUMATIC ELECTRIC HYDRAULIC
PIPING SUPERVISED YES NO DETECTING MEDIA YES NO
SUPERVISED?
DELUGE AND DOES THE VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROL? YES NO
PREACTION IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTING? YES NO
VALVES IF NO, EXPLAIN:
DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT MAXIMUM TIME TO
SUPERVISION LOSS ALARM? OPERATE VALVE OPERATE RELEASE
MAKE MODEL. RELEASE?
YES NO YES NO MIN. SEC.
%0.9 11J 1 1JLJ R V
HYDROSTATIC: HYDROSTATIC TESTS SHALL BE MADE AT NOT LESS THAN 200 PSI (13.6 BARS) ABOVE
X YES NO
DRY -
STATIC PRESSURE IN EXCESS OF 150 PSI (10.3 BARS) FOR TWO HOURS. DIFFERENTIAL DRY -
PIPE VALVE CLAPPERS SHALL BE LEFT OPEN DURING TEST TO PREVENT DAMAGE. ALL ABOVE -GROUND
TEST
PIPING LEAKAGE SHALL, BE STOPPED.
DESCRIPTION
PNEUMATIC: ESTABI]SM 40 PSI (2.7 BARS) AIR PRESSURE AND MEASURE DROP WHICH SHALL NOT
EXCEED 1-1/2 PSI (0.1 BARS) IN PRESSURE TANKS AT NORMAL WATER LEVEL AND AIR PRESSURE
AND MEASURE AIR PRESSURE DROP WHICH SHALL NOT EXCEED
1-1/2 PSI (0.1 BARS) IN 24 HRS.
AI.I_ PIPING HYDROSTATICALLY TESTED .4T 200 PSI FOR 2 HRS.
IF NO, STATE REASON:
YES X NO
DRY PIPING PNEUMATiC.'ALLY TESTED? YES
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A
NO
Dt�Ct-MENTED QUALITY CGNTROL PROCEDURE TO INSURE THAT ALL DISCS ARE
EQUIPMENT OPERATES PROPERLY? YES
NO
DRAIN READING OF GAGE LOCATED NEAR WATER SUPPLY TEST
RESIDUAL PRESSURE WITH VALVE IN
TESTS
PIPE-.
TEST PIPE OPEN WIDE 200 PSI
HYDRAULIC
TEST 200 PSI
YES
X
UNDERGROUND MAINS AND LEAD-IN CONNECTIONS TO SYSTEM RISERS SHALL BE FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING.
VERIFIED BY COPY OF THE FORM # 85B?
IF NO, EXPLAIN:
YES
NO
OTHER
EXPLAIN
DATE LEFT IN SERVICE NNTH ALL CONTROL VALVES OPEN: T
FLI.'SHED BY INSTALLER OF I *NDERGROUND
YES
REMARKS
NO
NAN'IE OF INSTALLING CONTRACTOR: CEN -CAL FIRE SYSTEMS, INC.
SPRINKLER PIPING?
TESTS WITNESSED BY
t
FOR AUTHORITY HAVING KRISDICTION (Signed) TITLE
DATE
BLANK TESTING
,rN • f, 7lTTC
NUMBER USED
LOCATIONS
NUMBER REMOVED
%0.9 11J 1 1JLJ R V
WELDED PIPING?
X YES NO
IF YES...
DO YOU CERTIFY AS THF SPRINKLER CONTRACTOR THAT WELDING
YES X NO
PROCEDURES
COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS D10.9, LEVEL AR -3?
WELDING
DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED
IN COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST AWS D10.9, LEVEL AR -3?
YES X NO
DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A
YESX NO
Dt�Ct-MENTED QUALITY CGNTROL PROCEDURE TO INSURE THAT ALL DISCS ARE
RETRIEVED. THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND OTHER
WELDING RESIDUE ARE REN IOVED, AND THAT INTERNAL DIAMETERS OF PIPING
ARE NOT PENETRATED?
HYDRAULIC
NAMEPLATE PROVIDED? .
YES
X
NO
DATA NAMEPLATE
IF NO, EXPLAIN:
- —
DATE LEFT IN SERVICE NNTH ALL CONTROL VALVES OPEN: T
REMARKS
NAN'IE OF INSTALLING CONTRACTOR: CEN -CAL FIRE SYSTEMS, INC.
TESTS WITNESSED BY
t
FOR AUTHORITY HAVING KRISDICTION (Signed) TITLE
DATE
SIGNATURES�--
wo-11A 10".
FOR I ' 'TAI�aG CON�'i2. R Sig d) TITLE
DATE
ADDITIONAL EXPLANATION ANMD OTkS:
rn