Inspection, Testing, and Maintenance Fire Sprinkler System Page 1 of 4
NFPA 25, Chapter 5 as amended by CCR. Title 19
Date of Inspection, Testing, Maintenance: 05/21/2009
Property Information:
Name: Sun West (Warehouse / Office)
Address: 507 Bannock Street
City: Biggs, CA 95917
System Riser ID: #1
Type of System:
® Wet Pipe
❑ Dry Pipe
❑ Preaction
❑ Deluge
Main Drain Test Results:
Abbreviation Key:
I = Inspection
Initial Static Pressure: 165 (psi)
T = Test
M = Maintenance
Residual Pressure: 150 (psi)
A -O = After Operation
Restored Static Pressure: 171 (psi)
MI = Per Manufacture's Instructions
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.1
1
Daily
Preaction/Deluge Valves — Enclosure
12.4.3.1
X
Weekly
temperature
1.2
1
Daily
Dry Pipe Valves — Enclosure
12.4.4.1.1
X
Weekly
temperature
1.3
1
Quarterly
Gauges (Dry, Preaction, Deluge
5.2.4.2
X
Systems)
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves — Exterior Inspection
12.4.1.1
X
1.13
1
QuarterlPreaction/Deulge
y
Valves — Exterior
12.4.3.1.6
X
Inspection
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves — Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annually
Buildings
5.2.5
X
State Fire Marshal AES 2 March 21, 2006
25-80 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System Page 2 of 4
NEPA 25, Chapter 5 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: 05/21/2009
Property Information:
Name: Sun West (Warehouse / Office)
Address: 507 Bannock Street
City:
Biggs, CA 95917
System Riser ID: #1
Type of System:
®Wet Pipe
[]Dry Pipe
[]Preaction
❑Deluge
Item:
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed
spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves — Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves — Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction/Deluge Valves — Interior
Inspection
12.4.3.1.7
X
1.28
I
5 Years
Preaction/Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves -- Interior Inspection
12.4.4.1.5
X
1.30
T
5 Years
Dry Pipe Valves - Strainers, filters,
orifices
12.4.4.1.6
x
2.1
T
Annually
Alarm Devices (90 Sec) 32 Sec.
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6.
12.2.6.1.
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve — Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve — Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve — Low Air Pressure
Alarm
12.4.3.2.10
X
2.9
T
Annually
Preaction Valve — Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshall AES 2
March 21, 2006
ANNEX B
25-81
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25, Chapter 5 as amended b CCR, Title 19
Activity
Page 3 of 4
Date of Inspection, Testing, Maintenance: 05/21/2009
System Riser ID: #1
Fail
Property Information:
Pass
2.10
Name: Sun West (Warehouse / Office)
Type of System:
®Wet Pipe
of CA4/
Address: 507 Bannock Street
❑Dry Pipe
X
City: Biggs, CA 95917
❑Preaction,
9
Annually
❑Deluge
F� p�
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve — Priming water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve — Low Air Pressure
Alarm
12.4.4.2.6
X
2.12
T
Annually
Dry Pipe Valve — Quick -Opening
Device
12.4.4.2.4
X
2.13
T
Annually
Dry Pipe Valve — Trip Test
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventer Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve — Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers — Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers — Corrosive environment or
corrosive water
5.3.1.1.2
X
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
— Re I ace
5.3.1.1.1.1
X
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction/Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves/Quick-Opening
Devices
12.4.4.3.2
X
3.4
M
Annually
Dry Pipe Valve — Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2 March 21, 2006
25-82 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System Page 4 of 4
NEPA 25, Chapter 5 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: 05/21/2009 System Riser ID: #1
Property Information:
Name:
Address:
City:
Sun West (Warehouse /Office)
507 Bannock Street
Biggs, CA 95917
Type of System:
Wet Pipe
spry pipe � 2
v
❑Preaction
Q
[]Deluge
Deficiencies and Comments:
Item Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
1.10 5.2.1.3 Missing upright heads.
*Added 8 Viking Y 200° ssu BR to spare head box.
Zone 1 & 2 share spare head box. *06/17/2009
o See Continuation Page(s) (Indicate the number of continuation pages)
® PASS
❑ FAIL Scott Reed
ionature
State Fire Marshal AES 2
05/21/2009
Date
March 21, 2006
ANNEX B
25-79
Inspection, Testing, and Maintenance Fire Sprinkler System Page 1 of 4
NFPA 25. Chanter 5 as amended by CCR. Title 19
Date of Inspection, Testing, Maintenance: 05/21/2009
Property Information:
i Name: Sun West (Warehouse /Loading)
Address: 507 Bannock Street
City: Biggs, CA 95917
System Riser I D: #2
Type of System:
OF Cq���o
� Wet Pipe
9�
a pry Pipe
�
44
a
❑ Preaction
A -O = After Operation
E] Deluge
� MAp�
Main Drain Test Results:
Abbreviation Key:
I = Inspection
Initial Static Pressure: 165 (psi)
T = Test
M = Maintenance
Residual Pressure: 150 (psi)
A -O = After Operation
Restored Static Pressure: 171 (psi)
MI = Per Manufacture's Instructions
EActivity
Item
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.1
I
Daily
Preaction/Deluge Valves — Enclosure
12.4.3.1
X
Weekly
temperature
1.2
I
Daily
Dry Pipe Valves — Enclosure
12.4.4.1.1
X
Weeklytemperature
1.3
1
Quarterly
Gauges (Dry, Preaction, Deluge
5.2.4.2
X
Systems)
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
I
Quarterly
Alarm Valves — Exterior Inspection
12.4.1.1
X
1.13
I
Quarterly
Preaction/Deulge Valves — Exterior
12.4.3.1.6
X
Inspect on
1.14
I
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
I
Quarterly
Dry Pipe Valves — Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annually
Buildings
5.2.5
X
State Fire Marshal AES 2 March 21, 2006
25-80 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System Page 2 of 4
NEPA 25, Chapter 5 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: 05/21/2009
Property Information:
Name: Sun West (Warehouse / Loading)
Address: 507 Bannock Street
City: Biggs, CA 95917
System Riser ID: #2
Type of System:
®Wet Pipe
F] Dry Pipe
[]Preaction
[]Deluge
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed
spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves — Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
x
1.26
1
5 Years
Check Valves — Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction/Deluge Valves — Interior
Ins ection
12.4.3.1.7
X
1.28
1
5 Years
Preaction/Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves — Interior Inspection
12.4.4.1.5
X
1.30
T
5 Years
Dry Pipe Valves - Strainers, filters,
orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec) 30 Sec.
12 2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6.
12.2.6.1.
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve — Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve — Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve — Low Air Pressure
Alarm
12.4.3.2.10
X
2.9
T
Annually
Preaction Valve — Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshall AES 2 March 21, 2006
ANNEX B
25-81
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25, Chapter 5 as amended by CCR, Title 19
Page 3 of 4
Date of Inspection, Testing, Maintenance: 05/21/2009
System Riser ID: ##2
Property Information:
Fail
Name: Sun West (Warehouse / Loading}
Type of System:
®Wet Pipe of Cq4/�
Address: 507 Bannock Street
[]Dry Pipe m
City: Biggs, CA 95917
❑Preaction
9
12.4.4.2.1
❑Deluge
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve — Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve — Low Air Pressure
Alarm
12.4.4.2.6
X
2.12
T
Annually
Dry Pipe Valve — Quick -Opening
Device
12.4.4.2.4
X
2.13
T
Annually
Dry Pipe Valve — Trip Test
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventer Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve — Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers — Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers — Corrosive environment or
corrosive water.
5.3.1.1.2
X
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
— Replace
5.3.1.1.1.1
X
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction/Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves/Quick-Opening
Devices
12.4.4.3.2
X
3.4
M
Annually
Dry Pipe Valve — Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2 March 21, 2006
25-82 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System
NEPA 25, Chapter 5 as amended by CCR, Title 19
Page 4 of 4
Date of Inspection, Testing, Maintenance: 05/21/2009
System Riser ID: #2
Property Information:
Name: Sun West (Warehouse / Loading)
Type of System:
®Wet Pipe
�o� ��`���
Address: 507 Bannock Street
❑Dry Pipe
City: Biggs, CA 95917
❑Preaction
❑Deluge-----����
�'RE Nip`
Deficiencies and Comments:
Item Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
1 1.10 15.2.1.3 Missing heads.
*Added (8) Y22000 ssu to box. Zone 1 & 2 share head box. 06/16/2009.
o See Continuation Page(s) (Indicate the number of continuation pages)
® PASS
❑ FAIL Scott Reed 06/17/2009
Signature Date
State Fire Marshal AES 2 March 21, 2006
ANNEX B
25-79
Inspection, Testing, and Maintenance Fire Sprinkler System Page 1 of 4
NFPA 25, Chapter 5 as amended by CCR. Title 19
Date of Inspection, Testing, Maintenance: 05/21/2009
Property Information:
Name: Sun West (Tank Farm)
Address: 507 Bannock Street
� city: Biggs, CA 95917
System Riser ID: #5
Type of System:
� Wet Pipe 0� CA(��O
❑ Dry Pipe
a
❑ Preaction
❑ Deluge`lM
Main Drain Test Results:
Initial Static Pressure: 172 (psi)
Residual Pressure: 151 (psi)
Restored Static Pressure: 172 (psi)
Abbreviation Key:
I = Inspection
T = Test
M = Maintenance
A -O = After Operation
MI = Per Manufacture's Instructions
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.1
1
Daily
Weekly
Preaction/Deluge Valves — Enclosure
temperature
12.4.3.1
X
1.2
1
Daily
Weekly
Dry Pipe Valves — Enclosure
temperature
12.4.4.1.1
X
1.3
1
Quarterly
Gauges (Dry, Preaction, Deluge
Systems)
5.2.4.2
5.2.4.3
X
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves — Exterior Inspection
12.4.1.1
X
1.13
1
Quarterly
Preaction/Deulge Valves — Exterior
Inspection
12.4.3.1.6
X
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves — Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annually
Buildings
5.2.5
X
State Fire Marshal AES 2 March 21, 2006
25-80 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System Page 2 of 4
NFPA 25. Chapter 5 as amended by CCR. Title 19
Date of Inspection, Testing, Maintenance:
Property Information:
Name:
Address:
City:
05/21/2009
Sun West (Tank Farm)
507 Bannock Street
Biggs, CA 95917
System Riser ID: #5
Type of System:
®Wet Pipe
[-]Dry Pipe
❑Preaction
❑Deluge
Item
Activit
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
I
Annually
Hangers
5.2.3
X
1.19
!
Annually
Seismic Braces
5.2.3
X
1.20
I
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
I
5 Years
Seismic Braces (Accessible concealed
5.2.3.3
X
spaces)
1.22
I
5 Years
Pipe and Fittings (Accessible concealed
5.2.2.3
X
spaces)
1.23
1
5 Years
Sprinklers (Accessible concealed
5.2.1.1.4
X
spaces)
1.24
1
5 Years
Alarm Valves — Interior Inspection
12.4.1.2
x
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves — Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction/Deluge Valves — Interior
12.4.3.1.7
X
Inspection
1.28
1
5 Years
Preaction/Deluge Valves - Strainers,
12.4.3.1.8
X
filters, orifices
1.29
1
5 Years
Dry Pipe Valves — Interior Inspection
12.4.4.1.5
X
1.30
T
5 Years
Dry Pipe Valves - Strainers, filters,
12.4.4.1.6
X
orifices
2.1
T
Annually
Alarm Devices (90 Sec) 43 Sec.
12.2 .7
X
12.2.6.
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6.1.
X
12.3.3.4
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve — Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve — Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve — Low Air Pressure
12.4.3.2.10
X
Alarm
2.9
T
Annually
Preaction Valve — Full Flow Trip Test
12.4.3.2.2
x
State Fire Marshall AES 2 March 21, 2006
ANNEX B
25-81
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25, Chapter 5 as amended by CCR, Title 19
Activity
Page 3 of 4
Date of Inspection, Testing, Maintenance: 05/21/2009
System Riser ID: #5
Fail
Property Information:
Pass
2.10
T
Type of System:
OF ca,�,
Name: Sun Vilest (Tank Farm)
®Wet Pipe
�
o
Address: 507 Bannock Street
[:]Dry Pipetwo
T
City: Biggs, CA 95917
❑Preaction
12.4.4.2.6
_
❑Deluge
E t�P►
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve — Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve — Low Air Pressure
Alarm
12.4.4.2.6
X
2.12
T
Annually
Dry Pipe Valve — Quick -Opening
Device
12.4.4.2.4
X
2.13
T
Annually
Dry Pipe Valve — Trip Test
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventer Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve — Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers — Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers — Corrosive environment or
corrosive water
5.3.1.1.2
X
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
— Replace
5.3,1.1.1.1
X
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction/Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves/Quick-Opening
Devices
12.4.4.3.2
X
3.4
M
Annually
Dry Pipe Valve — Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2 March 21, 2006
25-82 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System
NEPA 25, Chapter 5 as amended by CCR, Title 19
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
Page 4 of 4
Date of Inspection, Testing, Maintenance: 05/21/2009
System Riser ID: ##5
*Repaired 0611812009.
Property Information:
Type of System:
c���
Name: Sun West(Tank Farm
®Wet Pipe
tial
Address: 507 Bannock Street
❑Dry Pipe
Preaction
a,t
City: Biggs, CA 95917
❑
�
❑Deluge
�E NtP►
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
1.18
5.2.3 8 line hangers above Rice Equi ment are off 40'— 48' AFF.
*Repaired 0611812009.
o See Continuation Page(s) (Indicate the number of continuation pages)
® PASS
❑ FAIL Scott Reed 05/21/2009
Signature Date
State Fire Marshal AES 2 March 21, 2006
r
ANNEX B
25-79
Inspection, Testing, and Maintenance Fire Sprinkler System Pagel of 4
NFPA 25. Chapter 5 as amended by CCR. Title 19
Date of Inspection, Testing, Maintenance: 05/22/2009
Property Information:
Name: Sun West /Specialty Warehouse
Address: 2875 A 8th Street
City: Biggs, CA 95917
System Riser ID: 11 Zone #5
Type of System:
� Wet Pipe 0� Cq���o�
Dry pipe �, 2
n
❑ Preaction
❑ Deluge 9�1� MPQ''��
Main Drain Test Results:
Abbreviation Key:
I = Inspection
Initial Static Pressure: 172 (psi)
T = Test
M = Maintenance
Residual Pressure: 148 (psi)
A -O = After Operation
Restored Static Pressure: 168 (psi)
MI = Per Manufacture's Instructions
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
NIA
Pass
1.1
1
Daily
Preaction/Deluge Valves — Enclosure
12.4.3.1
X
Weekly
temperature
1.2
I
Daily
Dry Pipe Valves — Enclosure
12.4.4.1.1
X
Weekly
temperature
1.3
I
Quarterly
Gauges (Dry, Preaction, Deluge
5.2.4.2
X
Systems)
5.2.4.3
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves — Exterior Inspection
12.4.1.1
X
1.13
1
Quarterly
Preaction/Deulge Valves — Exterior
12.4.3.1.6
X
Inspection
1.14
l
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves — Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annually
Buildings
5.2.5
X
State Fire Marshal AES 2
March 21, 2006
25-80 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System Page 2 of 4
NEPA 25, Chapter 5 as amended by CCR. Title 19
Date of Inspection, Testing, Maintenance: 05/22/2009
Property Information:
Name: Sun West / Specialty Warehouse
Address: 2875 A 8th Street
City:
Biggs, CA 95917
System Riser ID: #1 Zone ##5
Type of System:
®Wet Pipe
❑Dry Pipe
❑Preaction
[]Deluge
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed
spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves — Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves — Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction/Deluge Valves — Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction/Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves — Interior Inspection
12.4.4.1.5
X
1.30
T
5 Years
Dry Pipe Valves - Strainers, filters,
orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec) 67 Sec.
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6.
12.2.6.1.
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve — Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve — Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve — Low Air Pressure
Alarm
12.4.3.2.10
X
2.9
T
Annually
Preaction Valve — Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshall AES 2 March 21, 2006
ANNEX B
25-81
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25, Cha ter 5 as amended by CCR, Title 19
Activity
Page 3 of 4
Date of Inspection, Testing, Maintenance: 05/22/2009
System Riser ID: #1 Zone #5
Property Information:
N/A
Pass
Name: Sun West / Specialty Warehouse
Type of System:
®Wet Pipe
0.a[�
Address: 2875 A 8th Street
[-]Dry Pipe
?
City: Biggs, CA 95917
❑Preaction
f
T
[:]Deluge
--''
MA
Item
Activity
Frequency
Description
NEPA 25
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve — Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve — Low Air Pressure
Alarm
12.4.4.2.6
X
2.12
T
Annually
Dry Pipe Valve — Quick -Opening
Device
12.4.4.2.4
X
2.13
T
Annually
Dry Pipe Valve — Trip Test
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventer Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve — Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers — Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers — Corrosive environment or
corrosive water
5.3.1.1.2
X
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
— Replace
5.3.1.1.1.1
X
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction/Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves/Quick-Opening
Devices
12.4.4.3.2
X
3.4
M
Annually
Dry Pipe Valve — Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2 March 21, 2006
v
25-82 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System
NEPA 25, Chapter 5 as amended by CCR, Title 19
Page 4 of 4
Date of Inspection, Testing, Maintenance: 05/22/2009
System Riser ID: #1 Zone #5
Property Information:
Name: Sun West / Specialty Warehouse
Type of System:
®Wet Pipe
of CA ��
o
Address: 2875 A 8th Street
❑Dry Pipe
City: Biggs, CA 95917
❑Preaction
[]DelugeRE
VA
Deficiencies and Comments:
Item Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
2.14 12.6.2 Backflow preventer tested by others.
1.19 5.2.3 8" braces at top of riser are below flexible coupling. Need to relocate
4-wa braces.
*Re -braced top of riser. 06/18/2009.
o See Continuation Page(s) (Indicate the number of continuation pages)
® PASS
❑ FAIL Scott Reed 05/22/2009
State Fire Marshal AES 2
Sianature
Date
March 21, 2006
ANNEX B
25-79
Inspection, Testing, and Maintenance Fire Sprinkler System Page 1 of 4
NFPA 25. Chanter 5 as amended by CCR. Title 19
Date of Inspection, Testing, Maintenance: 05/22/2009
Property Information:
Name: Sun West /Sp6(iakyWarehouse -0�102
Address: 2$75 A 8th $tf@2t
� city: Biggs, CA 95917
System Riser ID: #2 Zone #6
Type of System:
❑ Wet Pipe
�� �����
❑ Dry Pipe
❑ Preaction
❑ Deluge � M
Main Drain Test Results:
Initial Static Pressure: 171 (psi)
Residual Pressure: 148 (psi)
Restored Static Pressure: 168 (psi)
Abbreviation Key:
I = Inspection
T = Test
M = Maintenance
A -O = After Operation
MI = Per Manufacture's Instructions
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.1
1
Daily
Weekly
Preaction/Deluge Valves — Enclosure
temperature
12.4.3.1
X
1.2
1
Daily
Weekly
Dry Pipe Valves -- Enclosure
temperature
12.4.4.1.1
X
1.3
1
Quarterly
Gauges (Dry, Preaction, Deluge
Systems)
5.2.4.2
5.2.4.3
X
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves — Exterior Inspection
12.4.1.1
X
1.13
1
Quarterly
Preaction/Deulge Valves — Exterior
Inspection
12.4.3.1.6
X
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves — Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annually
Buildings
5.2.5
X
State Fire Marshal AES 2 March 21, 2006
25-80 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System Page 2 of 4
NFPA 25, Chapter 5 as amended by CCR. Title 19
Date of Inspection, Testing, Maintenance: 05/22/2009
Property Information:
Name: Sun West/Spec afty Warehouse —Office
Address: 2875 A 8t' Street
city:
Biggs, CA 95917
System Riser I D : #2 Zone #6
Type of System:
[-]Wet Pipe
[]Dry Pipe
[]Preaction
[]Deluge
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
ces
5.2.3.3
X
1.22
1
,---spa
5 Years
Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed
spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves - Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves - Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction/Deluge Valves - Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction/Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
X
1.29
1
5 Years
Dry Pipe Valves - Interior Inspection
12.4.4.1.5
X
1.30
T
5 Years
Dry Pipe Valves - Strainers, filters,
orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec) 60 Sec.
12.2 .7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6.
12.2.6.1.
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve - Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve - Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve - Low Air Pressure
Alarm
12.4.3.2.10
X
2.9
T
Annually
Preaction Valve - Full Flow Trip Test
12.4.3.2.2
x
State Fire Marshall AES 2 March 21, 2006
ANNEX B
25-81
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25, Chapter 5 as amended by CCR, Title 19
Page 3 of 4
Date of Inspection, Testing, Maintenance: 05/22/2009
System Riser ID: #2 Zone #6
Property Information:
Fail
Name: Sun West/ fly Warehouse --Office
Type of System:
❑Wet Pipe°� cA���
Address: 2875 A 8t" Street
❑Dry Pipe a,
City: Biggs, CA 95917
❑ Preaction
12.4.4.2.1
❑Deluge
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve — Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve — Low Air Pressure
Alarm
12.4.4.2.6
X
2.12
T
Annually
Dry Pipe Valve — Quick -Opening
Device
12.4.4.2.4
X
2.13
T
Annually
Dry Pipe Valve — Trip Test
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventer Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve — Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers — Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers — Corrosive environment or
corrosive water
5.3.1.1.2
X
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
— Replace
5.3,1.1.1.1
X
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction/Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves/Quick-Opening
Devices
12.4.4.3.2
X
3.4
M
Annually
Dry Pipe Valve — Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2 March 21, 2006
25-82 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System
NEPA 25, Chapter 5 as amended by CCR, Title 19
Page 4 of 4
Date of Inspection, Testing, Maintenance: 05/22/2009
System Riser ID: #2 Zone #6
Property Information:
relocate 8" 4 -ways.
Name: Sun West/ S Warehouse --Office❑Wet
Type of System:
Pipe �o� C����
Address: 2875 A 8th Street
❑Dry Pipe
City: Biggs, CA 95917
❑ Preaction
Delu e
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
1.19
5.2.3 4 -Way braces at top riser are on wrong side of flex couplings. Need to
relocate 8" 4 -ways.
*Re -braced top of riser. 06/18/2009.
1.8
5.2.2 Heavy gauge electrical wire needs to be removed from sprinkler system
at outside Office / Stairs. Robert to re -hang wires.
o See Continuation Page(s) (Indicate the number of continuation pages)
® PASS
❑ FAIL Scott Reed 05/22/2009
Signature Date
State Fire Marshal AES 2 March 21, 2006
ANNEX B
25-79
Inspection, Testing, and Maintenance Fire Sprinkler System Page 1 of 4
NFPA 25, Chapter 5 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: 05/21/2009 System Riser ID: #7
Property Information:
Type of System:
Name: Sun West (Hull House) ® Wet Pipe �
DPipe
Address: 507 Bannock Street ❑ Dry x�
❑ Preaction
City: Biggs, CA 95917 Deluge - .U.
--'r�'r�
Main Drain Test Results:
Initial Static Pressure: 165 (psi)
Residual Pressure: 150 (psi)
Restored Static Pressure: 171 (psi)
Restoration Time: 3 Sec.
Abbreviation Key:
I = Inspection
T = Test
M = Maintenance
A -O = After Operation
MI = Per Manufacture's Instructions
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.1
I
Daily
Weekly
Preaction/Deluge Valves — Enclosure
temperature
12.4.3.1
X
1.2
1
Daily
Weekly
Dry Pipe Valves — Enclosure
tem erature
12.4.4.1.1
X
1.3
1
QuarterlyGauges
(Dry, Preaction, Deluge
Systems)
5.2.4.2
5.2.4.3
X
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
I
Quarterly
Alarm Devices
5.2.6
X
1.6
I
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
I
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
I
Quarterly
Pipe and Fittings
5.2.2
X
1.9
I
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
I
Quarterly
Alarm Valves — Exterior Inspection
12.4.1.1
X
1.13
I
Quarterly
Preaction/Deulge Valves — Exterior
Inspection
12.4.3.1.6
X
1.14
I
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
I
Quarterly
Dry Pipe Valves — Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annually
Buildings
5.2.5
X
State Fire Marshal AES 2 March 21, 2006
25-80 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System Page 2 of 4
NEPA 25, Chapter 5 as amended by CCR. Title 19
Date of Inspection, Testing, Maintenance: 05/21/2009
Property Information:
Name: Sun West (Hull House)
Address: 507 Bannock Street
City:
Biggs, CA 95917
System Riser ID: #7
Type of System:
®Wet Pipe
[]Dry Pipe
❑Preaction
[]Deluge
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
X
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
5.2.3.3
X
spaces)__
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
5.2.2.3
x
spaces)_
1.23
1
5 Years
Sprinklers (Accessible concealed
5.2.1.1.4
X
spaces)
1.24
1
5 Years
Alarm Valves — Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years
Check Valves — Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction/Deluge Valves — Interior
12.4.3.1.7
X
Inspection
1.28
1
5 Years
Preaction/Deluge Valves - Strainers,
12.4.3.1.8
X
filters, orifices
1.29
1
5 Years
Dry Pipe Valves — Interior Inspection
12.4.4.1.5
X
1.30
T
5 Years
Dry Pipe Valves - Strainers, filters,
12.4.4.1.6
X
orifices
2.1
T
Annually
Alarm Devices (90 Sec) 30 Sec.
12.2.7
X
12.2.6.
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6.1.
X
12.3.3.4
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve — Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve — Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve — Low Air Pressure
12.4.3.2.10
X
Alarm
2.9
T
Annually
Preaction Valve — Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshall AES 2 March 21, 2006
ANNEX B
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25, Chapter 5 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: 05/21/2009 System Riser ID: ##7
Property Information:
Name: Sun West (Hull House)
Address: 507 Bannock Street
City: Biggs, CA 95917
25-81
Page 3 of 4
Type of System:
E �A���o
Wet Pipe
Description
[]Dry Pipe
a
❑Preaction
Q
❑Deluge
�� M
Item
Activity
Frequency
q
Description
NFPA 25
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve — Priming Water
12.4.4.2.1
X
2.11
T
Annually
Annuals
Dry Pipe Valve — Low Air Pressure
Alarm
12.4.4.2.6
X
2.12
T
AnnuallyDry
Pipe Valve — Quick -Opening
Device
12.4.4.2.4
X
2.13
T
Annually
Dry Pipe Valve — Trip Test
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventer Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve — Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers — Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers — Corrosive environment or
corrosive water
5.3.1.1.2
X
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
— Replace
5.3.1.1.1.1
X
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction/Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves/Quick-Opening
Devices
12.4.4.3.2
X
3.4
M
Annually
Dry Pipe Valve — Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2 March 21, 2006
25-82 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System
NEPA 25, Chapter 5 as amended by CCR, Title 19
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
Page 4 of 4
Date of Inspection, Testing, Maintenance: 05/21/2009
System Riser ID: ##7
Property Information:
Type of System:
Name: Sun West (Hull House)
®Wet Pipe
c�Of C& �
V,
Address: 507 Bannock Street
❑Dry Pipe
.
: BI s
Cit , CA 95917
Biggs, v
E] Preaction
'
�•------` '�
a
❑Deluge
E MAP►
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
1.10
5.2.1.3 Spare head box located in Storage Room Zone #5 Mill/ Office).
o See Continuation Page(s) (Indicate the number of continuation pages)
® PASS
❑ FAIL Scott Reed 05/21/2009
Signature Date
State Fire Marshal AES 2 March 21, 2006
ANNEX B
25-79
Inspection, Testing, and Maintenance Fire Sprinkler System Page 1 of 4
NFPA 25, Chapter 5 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: 05/21/2009
Property Information:
Name: Sun Vilest Fire Pump Room
Address: 507 Bannock Street
city: Biggs, CA 95917
System Riser ID: #9
Type of System:
� Wet Pipe 0� Cq���o9
� pry pipe �, 2
a
❑ Preaction �
❑ Deluge
MP
Main Drain Test Results:
Initial Static Pressure: 168 (psi)
Residual Pressure: 150 (psi)
Restored Static Pressure: 171 (psi)
Abbreviation Key:
I = Inspection
T = Test
=
M Maintenance
A -O = After Operation
MI = Per Manufacture's Instructions
LItem
Activity
Frequency
Description
NEPA 25
Reference
Fail
N/A
Pass
1.1
1
Daily
Weekly
Preaction/Deluge Valves — Enclosure
temperature
12.4.3.1
X
1.2
1
Daily
Weekly
Dry Pipe Valves — Enclosure
temperature
12.4.4.1.1
X
1.3
1
Quarterly
Gauges (Dry, Preaction, Deluge
Systems)
5.2.4.2
5.2.4.3
X
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
I
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves — Exterior Inspection
12.4.1.1
X
1.13
1
Quarterly
Preaction/Deulge Valves — Exterior
Inspection
12.4.3.1.6
X
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves — Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annually
Buildings
5.2.5
X
State Fire Marshal AES 2 March 21, 2006
25-80 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System Page 2 of 4
NEPA 25, Chapter 5 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: 05/21/2009
Property Information:
Name: Sun West Fire Pump Room
Address: 507 Bannock Street
City:
Biggs, CA 95917
System Riser ID: #9
Type of System:
®Wet Pipe
❑Dry Pipe
❑Preaction
❑Deluge
Item
Activity
Frequency Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually Hangers
5.2.3
X
1.19
1
Annually Seismic Braces
5.2.3
X
1.20
1
5 Years Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
1
5 Years Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
x
1.23
1
5 Years Sprinklers (Accessible concealed
spaces)
5.2.1.1.4
X
1.24
1
5 Years Alarm Valves — Interior Inspection
12.4.1.2
X
1.25
1
5 Years Alarm Valves - Strainers, filters, orifices
12.4.1.2
X
1.26
1
5 Years Check Valves — Interior Inspection
12.4.2.1
X
1.27
1
5 Years Preaction/Deluge Valves — Interior
Ins ection
12.4.3.1.7
X
1.28
1
5 Years Preaction/Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
x
1.29
1
5 Years Dry Pipe Valves — Interior Inspection
12.4.4.1.5
X
1.30
T
5 Years Dry Pipe Valves - Strainers, filters,
orifices
12.4.4.1.6
X
2.1
T
Annually Alarm Devices (90 Sec)
12.2 .7
X
2.2
T
Annually Main Drain Test (Enter data on Page 1)
12.2.6.
12.2.6.1.
12.3.3.4
X
2.3
T
Annually Antifreeze Test
5.3.4
X
2.4
T
Annually Control Valve - Position
12.3.3.1
X
2.5
T
Annually Control Valve — Operation
12.3.3.1
X
2.6
T
Annually Supervisory
12.3.3.5
X
2.7
T
Annually Preaction Valve — Priming Water
12.4.3.2.1
X
2.8
T
Annually Preaction Valve — Low Air Pressure
Alarm
12.4.3.2.10
X
2.9
T
Annually Preaction Valve — Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshall AES 2 March 21, 2006
ANNEX B
25-81
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25, Chapter 5 as amended by CCR, Title 19
Activity
Page 3 of 4
Date of Inspection, Testing, Maintenance: 05/21/2009
System Riser ID: #9
Fail
Property Information:
Pass
2.10
Name: Sun Vilest Fire Pump Room
Type of System:
Wet Pie
® p
�oF �A%4z
Address: 507 Bannock Street
[]Dry Pipe
�. o
.
City: Beggs, CA 95917
❑Preaction
9
Annually
❑Deluge�.
12.4.4.2.6
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
2.10
T
Annually
Dry Pipe Valve — Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve — Low Air Pressure
Alarm
12.4.4.2.6
X
2.12
T
Annually
Dry Pipe Valve — Quick -Opening Device
2.4.4.2.4
X
2.13
T
Annually
Dry Pipe Valve — Trip Test
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventer Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve — Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers — Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers — Corrosive environment or
corrosive water
5.3.1.1.2
X
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
— Replace
5.3.1.1.1.1
X
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction/Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves/Quick-Opening
Devices
12.4.4.3.2
X
3.4
M
Annually
Dry Pipe Valve — Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2 March 21, 2006
25-82 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System
NEPA 25, Chapter 5 as amended by CCR, Title 19
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
Page 4 of 4
Date of Inspection, Testing, Maintenance: 05/21/2009
System Riser I D: #9
*Replaced by Alarm Tech 06116/2009.
Property Information:
2.6
Name: Sun Vilest Fire Pump Room
Type of System:
®Wet Pipe
�F ����o
Address: 507 Bannock Street
❑Dry Pipe
v,
City: Biggs, CA 95917
❑Preaction
❑Deluge
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
2.1
12.2.7 Water flow switch does not send any signal to alarm panel or bell.
*Replaced by Alarm Tech 06116/2009.
2.6
12.3.3.5 Tamper switch does not send signal to alarm panel.
*Repaired by Alarm Tech. 06/16/2009.
2.14
12.6.2 Backflow tested b others.
o See Continuation Page(s) (Indicate the number of continuation pages)
® PASS
❑ FAIL Scott Reed 05/21/2009
Signature Date
State Fire Marshal AES 2 March 21,•2006
ANNEX B
25-79
Inspection, Testing, and Maintenance Fire Sprinkler System Page 1 of 41
NFPA 25. Chapter 5 as amended by CCR. Title 19 �
Date of Inspection, Testing, Maintenance: 05/22/2009
Property Information:
Name: Sun West / Wild Rice
Address: 28758 th Street
� cry: Biggs, CA 95917
System Riser ID: ##1
Type of System:
OF cA���O
� Wet Pipe
92
❑ Dry Pipe
0
NFPA 25
Reference
Fail
N/A
a
❑ Preaction
c3,,
❑ Deluge
�E MPS
Main Drain Test Results:
Initial Static Pressure: 174 (psi)
Residual Pressure: 142 (psi)
Restored Static Pressure: 169 (psi)
Abbreviation Key:
I = Inspection
T = Test
M = Maintenance
A -O = After Operation
MI = Per Manufacture's Instructions
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.1
1
Daily
Weekl
Preaction/Deluge Valves — Enclosure
temperature
12.4.3.1
X
1.2
1
Daily
Weeklv
Dry Pipe Valves — Enclosure
temperature
12.4.4.1.1
X
1.3
1
Quarterly
Gauges (Dry, Preaction, Deluge
Systems)
5.2.4.2
5.2.4.3
X
1.4
1
Quarterly
Control Valves
12.3.2.1
X
1.5
1
Quarterly
Alarm Devices
5.2.6
X
1.6
1
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
X
1.7
1
Quarterly
Hydraulic nameplate
5.2.7
X
1.8
1
Quarterly
Pipe and Fittings
5.2.2
X
1.9
1
Quarterly
Sprinklers
5.2.1
X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
X
1.11
1
Quarterly
Fire Department Connections
12.7.1
X
1.12
1
Quarterly
Alarm Valves — Exterior Inspection
12.4.1.1
X
1.13
1
Quarterly
Preaction/Deulge Valves — Exterior
Inspection
12.4.3.1.6
X
1.14
1
Quarterly
Pressure Reducing Valves
12.5.1.1
X
1.15
1
Quarterly
Dry Pipe Valves — Exterior Inspection
12.4.4.1.4
X
1.16
1
Quarterly
Backflow Preventers
12.6.1
X
1.17
1
Annually
Buildings
5.2.5
X
State Fire Marshal AES 2 March 21, 2006
25-80 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System Page 2 of 4
NEPA 25. Chapter 5 as amended by CCR. Title 19
Date of Inspection, Testing, Maintenance: 05/22/2009
Property Information:
Name: Sun West / Wild Rice
Address:
City.
2875 Stn Street
Biggs, CA 95917
System Riser ID: ##1
Type of System:
®Wet Pipe
[]Dry Pipe
❑Preaction
❑Deluge
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
X
1.19
1
Annually
Seismic Braces
5.2.3
x
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
X
1.21
1
5 Years
Seismic Braces (Accessible concealed
spa es
5.2.3.3
x
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
X
1.23
1
5 Years
Sprinklers (Accessible concealed
spaces)
5.2.1.1.4
X
1.24
1
5 Years
Alarm Valves — Interior Inspection
12.4.1.2
X
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
x
1.26
1
5 Years
Check Valves — Interior Inspection
12.4.2.1
X
1.27
1
5 Years
Preaction/Deluge Valves — Interior
Inspection
12.4.3.1.7
X
1.28
1
5 Years
Preaction/Deluge Valves - Strainers,
filters, orifices
12.4.3.1.8
x
1.29
1
5 Years
Dry Pipe Valves — Interior Inspection
12.4.4.1.5
X
1.30
T
5 Years
Dry Pipe Valves - Strainers, filters,
orifices
12.4.4.1.6
X
2.1
T
Annually
Alarm Devices (90 Sec) 65 Sec.
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6.
12.2.6.1.
12.3.3.4
X
2.3
T
Annually
Antifreeze Test
5.3.4
X
2.4
T
Annually
Control Valve - Position
12.3.3.1
X
2.5
T
Annually
Control Valve — Operation
12.3.3.1
X
2.6
T
Annually
Supervisory
12.3.3.5
X
2.7
T
Annually
Preaction Valve — Priming Water
12.4.3.2.1
X
2.8
T
Annually
Preaction Valve — Low Air Pressure
Alarm
12.4.3.2.10
X
2.9
T
Annually
Preaction Valve — Full Flow Trip Test
12.4.3.2.2
X
State Fire Marshall AES 2 March 21, 2006
ANNEX B
25-81
Inspection, Testing, and Maintenance Fire Sprinkler System
NFPA 25, Chapter 5 as amended by CCR, Title 19
Activity
Page 3 of 4
Date of Inspection, Testing, Maintenance: 05/2212009
System Riser ID: ##1
Fail
Property Information:
Pass
2.10
Name: Sun West / Wild Rice
Type of System:
®Wet Pipe
c��, cq��fi.
Address: 2875 8th Street
[]Dry Pipe
X
.
City: BI s, CA 95917
❑Preaction
T
Annually
❑Deluge
Q
MP
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
NIA
Pass
2.10
T
Annually
Dry Pipe Valve — Priming Water
12.4.4.2.1
X
2.11
T
Annually
Dry Pipe Valve — Low Air Pressure
Alarm
12.4.4.2.6
X
2.12
T
Annually
Dry Pipe Valve — Quick -Opening
Device
12.4.4.2.4
X
2.13
T
Annually
Dry Pipe Valve — Trip Test
12.4.4.2.2
X
2.14
T
Annually
Backflow Preventer Assemblies
12.6.2
X
2.15
T
3 Years
Dry Pipe Valve — Full Flow Trip Test
12.4.4.2.2.2
X
2.16
T
5 Years
Gauges
5.3.2
X
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
X
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
X
2.19
T
5 Years
Sprinklers — Extra High Temperature
5.3.1.1.1.3
X
2.20
T
5 Years
Sprinklers — Corrosive environment or
corrosive water
5.3.1.1.2
X
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
X
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
X
2.23
T
50 Years
Sprinklers
5.3.1.1.1
X
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
X
2.25
T
Sprinklers manufactured prior to 1920
— Replace
5.3.1.1.1.1
X
3.1
M
Annually
Control Valves
12.3.4
X
3.2
M
Annually
Preaction/Deluge Valves
12.4.3.3.2
X
3.3
M
Annually
Dry Pipe Valves/Quick-Opening
Devices
12.4.4.3.2
X
3.4
M
Annually
Dry Pipe Valve — Low Point Drains
12.4.4.3.3
X
3.5
M
5 Years
Obstruction Investigation
Chapter 13
X
State Fire Marshal AES 2 March 21, 2006
25-82 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System
NEPA 25, Chapter 5 as amended by CCR, Title 19
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
Page 4 of 4
Date of Inspection, Testing, Maintenance: 05/22/2009
System Riser ID: #1
Property Information:
5.2.1 2 heads need to be changed out in 6" Riser Room, Line #1 from QR to
std response heads, need 1 head under stairs in Electrical Room. Need to
Type of System:
lower 3 heads in Brine Room & install s/r cp escutcheons.
Name: Sun West / Wild Rice
®Wet Pipe°�
��`���
14W °
Address: 28758 th Street
❑Dry Pipe
City: Biggs, CA 95917
❑ Preaction
Delu a------!
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
2.14
12.6.2 Backflow preventer tested by others.
1.9
5.2.1 2 heads need to be changed out in 6" Riser Room, Line #1 from QR to
std response heads, need 1 head under stairs in Electrical Room. Need to
lower 3 heads in Brine Room & install s/r cp escutcheons.
*All corrections completed 06/16/2009.
o See Continuation Page(s) (Indicate the number of continuation pages)
® PASS
❑ FAIL Scott Reed 05/22/2009
Signature Date
State Fire Marshal AES 2 March 21, 2006