2008 Butte County
Fire
Alarm/Sprinkler
Testing
Juvenile Hall Report
Tested:
Fire sprinkler system
Fire alarm system including
• 6 Pull Stations
• 10 Horn/Strobes
• 30 Strobes
• 36 Fire Dampers
• 182 Heat Detectors
• 254 Smoke Detectors
� 12 Monitoring Tamper/Supervisory Devices
During the test 8 Duct detectors were discovered, that have never
been tested, or included in the contract.
The fire sprinkler pump needs some service.
One heat detector was found missing/never installed
One smoke detector was un -testable because of location above
HVAC ducting.
4 L*C' CzUA-t F--Vtr,. Rot -5Q'
Inspection, Testing and Maintenance of Fire Alarm Systems
Fire Control,Wilgus Inc.
FIRE ALARM DIVISION
1703 Sonoma St
Redding, Ca 96001
(530)241-2465 (800)776-3046
Ca. License #462979 C-16, C-10 UL # S24291
Building Name:
Address: q
City: Postal Code:
C� ilk C-
qS
Date of Service
S '7/D6
Time p f1
Z� V
Annual Insp do
Initial Inspection
Last Service Date
U 1
1:1
Single Stage
Two Stage
ite Monitoring?
❑ yes ®no
❑
Manufacturer: •
Model # 9�00
ti c
Phone:
Contact Person:
z
L
Fax:
Owner:
Phone:
Fax:
Phone:
Central Station: _
"Yes"- Acceptable "No"- Unacceptable (Explain No answers in comments
Yes No Summa
® The Fire alarm system is now fully functional without deficiencies.
❑ The Fire alarm system has deficiencies noted on the a es attached.
® ❑ The Fire Alarm System is tested in accordance with NFPA 72
1�c1 �1 Seauence of Operation confirmed and tested.
Technicians After -test Checklist
Reconnect time limit cutouts?
Reconnect ancilln functions?
Reconnect ancillary functions off site connections)?
Reconnect signal ower?
Advise fire department the testin is completed?
Ensure that the alarm s stem is functional?
Comments
Yne a. % z - 4%,ro- 0-A &-r-Lk X 0 --
I state that the information on this form is correct at the time and place of my inspection, and that all equipment was tested in conformance with applicable codes and the
Manufacturers requirements and "-OiMe wq*left in operational condition upon completion of this inspection except as noted in comments.
5 0
Ll 30
,. ,.
T&Gician Signature
Dae
Time
I Owner or Authorized Agent
1 of 4
Inspection, Testing and Maintenance of Fire Alarm Systems
Date 5 .1 IC) $ Building Name 0-k
Yes - Tested correctly "X" No - Did not test correctly (Explain NO answers in comments) SNA" Not applicable
Control Unit Tests Annunciator Inspection & Tests
Power on visual indicator? Power on indicator?
Common visual trouble signal? Individual alarm and supervisory zone indication?
Common audible trouble signal? Individual alarm and supervisory zone indication labels?
Trouble signal silence switch? Common trouble signal?
Main Power supply failure trouble signal? Visual indicator test - Lamp test?
Ground fault tested on positive and negative trouble signal Input wiring from control unit is supervised?
Alert signal operation? Alarm signal silence visual indicator?
Alarm signal operation? Switches for ancillary function operate as intended?
Automatic transfer from Alert signal to Alarm signal? Other ancillary function visual indicators?
Acknowledge switch operation? Manual activation of alarm signal and indication?
Alarm signal silence inhibit? Power Supply Inspection
Alarm signal silence operation? Fused with mfgs marked rating of the system?
Alarm signal silence visual indication? Adequate to meet the requirements of the system?
Alarm signal when silenced automatically reinstate on Remote Trouble Unit Tests and Inspection
subsequent alarm? IA"t wiring from control unit is supervised?
Alarm signal silence automatic cut-out timer? Visu ouble signal?
Input circuit alarm and supervisory operation including _ Audible ble signal?
visual indicator? Audible trou signal silence?
Input circuit trouble operation? Battery Tests and Inspection
Output circuit alarm operation? Battery type
Output circuit trouble operation? Battery Voltage
Visual indicator test (lamp test)? AC power on Is. Vdc
V11 4 Coded signal sequence operate not less than the required AC power on 12 Vdc
number of times and the correct alarm signal thereafter.
Coded signal sequences are not interrupted by
subsequent alarms?
Input circuit to output circuit operation including
ancilliary device, for correct matrix operation
Reset operation?
Main power to emergency power supply transfer?
tilh Data communications link (DCL) supervision & operation
�J p Control unit interconnection to monitoring Station?
Control Unit Inspection
Input circuit designations, correctly identified in relation
to connected field devices
Output circuit designations correctly identified in relation
to connected field devices.
Designations for common control functions & indicators
Cabinet, plugin components and modules securely in place
Plugin cables securely in place
Record date, revision and version of Firmware & software
Date: Rev: Ver:
Cleanliness?
Fuses in accordance with MFGs specification
Control Unit lock
Termination points from wiring to field devices secure
Battery Amp Hours:
AC power on a.D, 5 Ah
AC power on Ah
Inspected for physical damage?
Terminal cleaned and lubricated?
Terminals clamped tightly?
Val_ Correct Electrolyte level?
A Specific gravity within mfg specifications?
Electrolyte leaks?
Adequately ventilated?
Within manufacturer's rated life date code?
Disconnection causes trouble signal?
Generator Power Supply
A,Qv,ides power to AC circuit serving the fire alarm?
Trou condition at the em gen shall result in an audible
common ftkle signal and a visual indication at the
required annunc or?
2 of 4
tr
Date 5/7/0
Inspection, Testing and Maintenance of Fire Alarm Systems
Name
114"Yes - Tested correctly 11X11 No - Did not test correctly (Explain NO answers in comments) "NA" Not applicable
Field Devices
Field Devices continued
Each device is free of damage, foreign substance &
Water Flow Detection devices
flow
mechanically supported independent of wiring?
a) tested by appropriate water means
Each device tested while connected to control unit?
b) time delay recorded
Manual Pull stations tested?
Two stage pullstations tested and functions confirmed?
L
_.�
Supervisory Devices
Shut-off valves tested and result in trouble signal?
Heat detectors tested
Low pressure supervisory device inspected and tested?
Smoke detectors
Low water supervisor test?
Inspected for cleanliness?
Sensitivity tested?
tJ A
Low temperature supervisor device tested
Each power loss (eg fire pump and air compressor) tested?
Systems
Tested for Operation?
Other Fixed Type Extinguishing
-- —
Remote indicator units inspected and tested?
Verify operation of the output contacts initiates the
Status change confirmation inspection and tested?
specified function at the FA control unit.
Air Duct smoke detectors tested?
Supervisory Devices Other Types
p
Beam type smoke detectors for actuation & sensitivity?
�--
Inspected and tested as per manufacturer requirements?
a
Flame detectors inspected and tested?
Combination detectors inspected and tested?
Signal Appliances
Shall be inspected and tested for operability
--
�—
detectors — other s inspected & tested
Automatic de type pe
Proper installation and tightness, tampering & obstruction?
a) initiation
b) deteZt<is oriented so as to detect hazard?
1314
Intelligibility of voice messages?
Audibility of alert, alarm and voice messages/
c) sensivity ted?
Visual signal appliance inspected and tested?
Combination devices tested?
Sequential Display Inspection and Testing
Individual alarm, supervisory and trouble inputs are
clearly indicated and separately designated?
Individual alarm and supervisory input designation
labels are properly identified?
Alarm input overrides supervisory and trouble input?
Supervisory input overrides trouble input?
Display can be manually advanced?
First alarm is clearly identified each time it is displayed
Alarm and supervisory input can be retrieved until system
is reset?
Printer Testing
Operde-tion as intended?
Zone o h alarm initiating device is correctly printed?
Rated voltage ' sent?
Printers located in Proprietary Control Centers
N" and acknowledgements are automatically printed?
Time to is recorded by the printer?
Each event is rded as they occur?
System records sta anges with loss of data?
Paper advances automati ch that print record is
visible?
Printer operates under loss of main powers 1 ?
Printer is monitored for "low paper" and "paper o 91
9
Voice Communication Inspection/Tests
ower on indicator?
C on visual trouble signal?
Co on audible trouble signal?
r
Trou a signal silence switch?
All cal voice paging including visual indicator?
output c alts for selective voice paging and visual.
Output c' its for selective voice paging trouble/visual
Microphon including press to talk switch?
Operation o VC systems does interfere with initial
inhibit time o lert and alarm signal.
All call voice p ing operates on emergency power?
Upon failure of a amplifier, system automatically
transfers to bac ku amplifier.
Circuits for emerge cy telephone call in operation
including audible an visual indication
Circuits for emergenc telephone for operation, including
two way voice comm 'cation?
Circuits for emergency t ephones trouble and visual ops.
Emergency telephone ve communication?
Emergency telephone ope le or in -use tone at handset.
Emergency telephone call-in amp?
Emergency telephone call-in a dible signal?
All telephone zone select switch s individually tested?
Individual telephone zone select ' dicators?
Operating instruction clearly vis
Lockable release mechanism is i
Ancillary Device Testing
Circuit
Circuit
Circuit
3 of 4
Inspection, Testing and Maintenance of Fire Alarm Systems
FD'ate s) ? ) o 3 Building Name 9, A F-- ra tI &NV U - S t 1 %j P W ,1 e 4 " k k
Device Testing — Legend and Notes
Device
Description T e Model No.
M
HT
Manual Pull station Rq% t• %G • 112L
Heat detector non restorable(Note 9
RHT
Heat detector, Restorable(Note 9 aftF• s
S
Smoke detector(Note 1, 2 & 9
RI
Remote indicator unit
DS
Duct smoke detector(Note 1, 3 & 9
PS
Photo electric smoke detector = S 355
SFD
Supporting Feld device monitor
FS
Sprinkler flow switch ffote 4
SS
Sprinkler supervisory device Note
LA -- Low air
PS — Pressure switch
EM
Fault isolation module
B
Bell
H
Horn
V
Visual si al appliance -%Q t
HS
Born/Strobe
SP
Cone type speaker
HSP
Horn type speaker
AD
Ancillary device(Note 8
ET
Emergency Telephone
---
Other supervisory devices Notes 6 &
---
other type of detector
Note 1. Smoke detector sensitivity measurement and cleaning date should be recorded in the remarks column.
Note 2. Status change, including time delay, should be recorded in the remarks column.
Note 3. Duct smoke detector pressure differential should be confirmed and recorded in the remarks column.
Note 4. Time delay setting of water flow switch should be recorded in the remarks column.
Note 5. Sprinkler supervisory switches cause trouble condition to be annunciated but not an alarm condition.
Note 6. Upper and lower pressure setting of supervisory devices should be recorded in the remarks column.
Note 7. Low temperature setting should be recorded in the remarks column.
Note 8. Identify the specific ancillary devices in the remarks column.
Note 9. Identify date fire detector was changed.
Caution: The tests reported on this form do not include the actual operational test of ancillary devices.
4 of 4
VA
Butte County Juvenile Hall
Fire Alarm Test 5R/2008
Devices Tested
•lypeDescription
Alarm/Device
Notification Booster Panels
Alarm Zone
Time of Test Device Address
ACTIVE SUPERVISORY
Address Batte Volts
Batte Amps__
Pass YIN
1M049
1M138
13
8.3
Y
lectrica I Room
13
5.83
Y
JB Pod
13
7
Y
PIV TAMPER
13
7
Y
D Pod
13
0.64
n
1 M 153
0
0 nmwmwwwwsmm
n
:/F Pod
13
.�•6
Y
Z000
13
7
Y
Devices Tested
•lypeDescription
Alarm/Device
Alarm Zone
Time of Test Device Address
ACTIVE SUPERVISORY
SPRINKLER TAMPER
Z000
1M049
1M138
ACTIVE SUPERVISORY
ACTIVE SUPERVISORY
JOCKEY PUMP
PUMP OPR ALARM
Z000
Z000
10*38A 050708
1 M 151
ACTIVE SUPERVISORY
JCKY FLOW SWITCH
Z000
10*39A 050708
1 M048
ACTIVE SUPERVISORY
PIV TAMPER
Z008
11 *02A 050708
1 M003
ACTIVE SUPERVISORY
PHASE FAILURE FP
Z000
10*45A 050708
1 M 153
ACTIVE TAMPER
TWIN GATE VALVE TMPR
Z000
11 *04A 050708
1 M002
ACTIVE TAMPER
TWIN GATE VALVE TMPR
Z000
11 *05A 050708
1 M002
ACTIVE TAMPER
TWIN GATE VALVE TMPR
Z000
11 *06A 050708
1 M002
ACTIVE TAMPER
TWIN GATE VALVE TMPR
Z000
11 *06A 050708
1 M002
ALARM: HEAT DETECT
E/F TOILET LET STAF F 119
Z001
09*01 A 050908
1 D 129
.
ALARM: HEA T DETECT
Z001
01 *43P 050908
1 M090
.
• T DETECT
ALARM. HEA
Z001
01 *46P 050908
1 M090
ALARM: HE. AT DETECT
2001
01 *49P 050908
1 M090
• T DETECT
ALARM. HEA
Z001
01 *52P 050908
1 M090
• T DETECT
ALARM. HEA
Z001
01 *55P 050908
1 M090
• T DETECT
ALARM. HEA
Z001
0.1 *55P 050908
1 M090
• DETECT
ALARM. HEAT
Z001
01 *56P 050908
1M090
• DETECT
ALARM. HEAT
F102 CLASSROOM
Z000
10*47A 050908
1M104
• - DETECT
ALARM. HEAT
E102 CLASSROOM
Z000
09*37A 050908
1M144
• T DETECT
ALARM. HEA
E102 CLASSROOM
Z000
09*41 A 050908
1 M 144
• HEAT DETECT
ALARM.
KITCHEN J155
Z001
09*41A 050808
2DO34
ALARM: HE. AT DETECT
A101 HIGH CLNG HEATS
Z000
10*48A 050808
2M115
• T DETECT
ALARM. HEA
B POD HIGH CEILING
Z000
11 *27A 050808
2M158
ALARM: HE. AT DETECT
STAFF TOILET/SH J142
Z001
12*47P 050708
1 DO16
• AT DETECT
ALARM. HE
TOILET -EXAM MED J136
Z001
12*42P 050708
1 D036
ALARM. HEA T DETECT
ADMIN BATH ROOM 113
Z000
12*OOP 050708
1 D060
ALARM: HEAT DETECT
PUBLIC BATHROOM 103
Z001
12*07P 050708
1 D063
• EAT DETECT
ALARM. H
TOILET LET INTAKE J 109
Z001
12*24P 050708
1 D087
ALARM: H EAT DETECT
F JANITORS CL. F 117
Z001
09*48A 050908
1 D 130
ALARM: HEAT DETECT
E JANITORS CL. E117
Z001
08*54A 050908
1 D131
ALARM: HEAT DETECT
LAUNDRY J141
Z001
12*44P 050708
1 D 133
ALARM: HEAT DETECT
J144 STAFF LOCKERS
Z000
10*51 A 050708
1 M010
ALARM: HEAT DETECT
J144 STAFF LOCKERS
Z000
10*52A 050708
1M010
ALARM: HEAT DETECT
J144 STAFF LOCKERS
Z000
10*53A 050708
1 M010
ALARM: HEAT DETECT
J131 SALLYPORT
Z000
08*11 A 050908
1 MO15
ALARM HEAT DETECT
J130 MAIN CORRIDOR
Z000
03*15P 050808
1MO18
• EAT DETECT
ALARM. H
J 130 MAIN CORRIDOR DOR
Z000
03*18P 050808
1 MO18
ALARM: H. EAT DETECT
J130 MAIN CORRIDOR
Z000
03*21 P 050808
1 M018
ALARM: HEAT DETECT
J130 MAIN CORRIDOR
Z000
03*21 P 050808
1 MO18
ALARM: HEAT DETECT
J141 LAUNDRY
Z000
11*06A 050908
1MO19
ALARM: HEAT DETECT
J141 LAUNDRY
z000
11*08A 050908
1MO19
ALARM: HEAT DETECT
J140 BREAK ROOM
z000
11*03A 050908
1M022
ALARM: HEAT DETECT
J140 BREAK ROOM
z000
11 *09A 050908
1 M022
ALARM: HEAT DETECT
F101 LOW CEILING
z000
10*50A 050908
1 M032
ALARM: HEAT DETECT
F101 LOW CEILING
z000
10*50A 050908
1 M032
ALARM: HEAT DETECT
F101 LOW CEILING
z000
10*51A 050908
1 M032
ALARM: HEAT DETECT
E POD HEATS ABOVE
z000
11 *25A 050908
1 M035
ALARM: HEAT DETECT
E POD HEATS ABOVE
z000
11 *26A 050908
1 M035
ALARM: HEAT DETECT
E POD HEATS ABOVE
z000
11 *29A 050908
1 M035
ALARM: HEAT DETECT
E POD HEATS ABOVE
z000
11 *30A 050908
1M035
ALARM: HEAT DETECT
J132 NURSES FILES FS
z001
11 *12A 050908
1 M040
ALARM: HEAT DETECT
J132 NURSES FILES FS
z001
11 *13A 050908
1 M040
ALARM: HEAT DETECT
J132 NURSES FILES FS
z001
11 *15A 050908
1 M040
ALARM: HEAT DETECT
J132 NURSES FILES FS
z001
11*19A 050908
1M040
ALARM: HEAT DETECT
J132 NURSES FILES FS
z001
11 *19A 050908
1 M040
ALARM: HEAT DETECT
E101 HIGH CEILING
z000
08*36A 050908
1 M046
ALARM: HEAT DETECT
E101 HIGH CEILING
z000
08*38A 050908
1 M046
ALARM: HEAT DETECT
E101 HIGH CEILING
z000
08*40A 050908
1 M046
ALARM: HEAT DETECT
E101 HIGH CEILING
z000
08*43A 050908
1 M046
ALARM: HEAT DETECT
E101 HIGH CEILING
z000
08*45A 050908
1 M046
ALARM: HEAT DETECT
J107 CLOTHING
z000
01 *12P 050908
1 M047
ALARM: HEAT DETECT
J107 CLOTHING
z000
01*13P 050908
1M047
ALARM: HEAT DETECT
J107 CLOTHING
z000
01 *14P 050908
1 M047
ALARM: HEAT DETECT
J107 CLOTHING
z000
12*22P 050708
1 M047
ALARM: HEAT DETECT
J105 J106 HOLDING
z000
01*06P 050908
1M051
ALARM: HEAT DETECT
J105 J106 HOLDING
z000
01 *06P 050908
1 M051
ALARM: HEAT DETECT
J105 J106 HOLDING
z000
01*07P 050908
1M051
ALARM: HEAT DETECT
J105 J106 HOLDING
z000
01*08P 050908
1M051
ALARM: HEAT DETECT
J105 J106 HOLDING
z000
01 *08P 050908
1 M051
ALARM: HEAT DETECT
J105 J106 HOLDING
z000
01 *09P 050908
1 M051
ALARM: HEAT DETECT
J105 J106 HOLDING
z000
01*09P 050908
1M051
ALARM: HEAT DETECT
J105 J106 HOLDING
z000
01 *10P 050908
1 M051
ALARM: HEAT DETECT
J105 J106 HOLDING
z000
12*15P 050708
1M051
ALARM: HEAT DETECT
J101 SALLYPORT
z000
01 *17P 050908
1 M054
ALARM: HEAT DETECT
F101 HIGH CEILING
z000
09*09A 050908
1 M056
ALARM: HEAT DETECT
F101 HIGH CEILING
z000
09*13A 050908
1 M056
ALARM: HEAT DETECT
F101 HIGH CEILING
z000
09*23A 050908
1 M056
ALARM: HEAT DETECT
F101 HIGH CEILING
z000
09*24A 050908
1 M056
ALARM: HEAT DETECT
J144 STAFF LOCKERS
z000
08*13A 050908
1 M058
ALARM: HEAT DETECT
J144 STAFF LOCKERS
z000
08*13A 050908
1M058
ALARM: HEAT DETECT
J144 STAFF LOCKERS
z000
08*15A 050908
1 M058
ALARM: HEAT DETECT
J144 STAFF LOCKERS
z000
08*16A 050908
1 M058
ALARM: HEAT DETECT
J123 VISITATION SALY
z000
02*06P 050908
1M060
ALARM: HEAT DETECT
J123 VISITATION SALY
z000
02*07P 050908
1 M060
ALARM: HEAT DETECT
z001
01 *43P 050908
1 M090
ALARM: HEAT DETECT
z001
01 *44P 050908
1 M090
ALARM: HEAT DETECT
z001
01 *45P 050908
1 M090
ALARM: HEAT DETECT
z001
01 *45P 050908
1 M090
ALARM: HEAT DETECT
z001
01 *57P 050908
1 M090
ALARM: HEAT DETECT
z001
01 *58P 050908
1 M090
ALARM: HEAT DETECT
z001
01 *59P 050908
1 M090
ALARM: HEAT DETECT
z001
02*01 P 050908
1 M090
ALARM: HEAT DETECT
z001
02*02P 050908
1 M090
ALARM: HEAT DETECT
z001
02*02P 050908
1 M090
ALARM: HEAT DETECT
z001
02*03P 050908
1 Mo90
ALARM: HEAT DETECT
z001
02*03P 050908
1 M090
ALARM: HEAT DETECT
J121 STORAGE
z000
02*09P 050908
1 MO92
ALARM: HEAT DETECT
J121 STORAGE
z000
02*12P 050908
1 M092
LARM: HEAT DETECT
J121 STORAGE
z000
02*12P 050908
1 M092
LARM: HEAT DETECT
J116 VISITING
z000
02*08P 050908
1 MO97
LARM: HEAT DETECT
J116 VISITING
z000
02*09P 050908
1 M097
LARM: HEAT DETECT
J116 VISITING
z000
02*10P 050908
1 M097
LARM: HEAT DETECT
J116 VISITING
z000
02*10P 050908
1 M097
LARM: HEAT DETECT
J116 VISITING
z000
02*11 P 050908
1 M097
LARM: HEAT DETECT
J180 CORRIDOR
z000
02*47P 050808
1 M 103
LARM: HEAT DETECT
J180 CORRIDOR
z000
02*48P 050808
1 M103
LARM: HEAT DETECT
J180 CORRIDOR
z000
02*51 P 050808
1 M103
LARM: HEAT DETECT
J180 CORRIDOR
z000
02*54P 050808
1M103
ALARM: HEAT DETECT
J180 CORRIDOR
z000
02*56P 050808
1M103
ALARM: HEAT DETECT
J180 CORRIDOR
z000
02*58P 050808
1 M 103
ALARM: HEAT DETECT
F102 CLASSROOM
z000
10*48A 050908
1 M104
ALARM: HEAT DETECT
F102 CLASSROOM
z000
10*54A 050908
1M104
ALARM: HEAT DETECT
F102 CLASSROOM
z000
10*55A 050908
1M104
ALARM: HEAT DETECT
E101 LOW CEILING
z000
08*54A 050908
1 M147
ALARM: HEAT DETECT
E101 LOW CEILING
z000
08*56A 050908
1 M147
ALARM: HEAT DETECT
E101 LOW CEILING
z000
08*58A 050908
1 M147
ALARM: HEAT DETECT
B JANITORS CL. B117
z001
10*10A 050808
2DO08
ALARM: HEAT DETECT
AIB TOILET STAF A119
z001
10*09A 050808
2DO09
ALARM: HEAT DETECT
A JANITORS CL. A117
zo01
10*08A 050808
2DO10
ALARM: HEAT DETECT
TOILET KITCHEN J158
z001
09*42A 050808
2DO35
ALARM: HEAT DETECT
KIT. SALLYPORT J153
z001
09*45A 050808
2DO40
ALARM: HEAT DETECT
C JANITORS CL. C117
z001
02*34P 050808
2DO88
ALARM: HEAT DETECT
CID TOILET STAF Cl 19
zoo 1
01 *56P 050808
2 DO89
ALARM: HEAT DETECT
D JANITORS CL. D117
z001
01 *56P 050808
2DO90
ALARM: HEAT DETECT
A102 CLASSROOM
z000
11 *11 A 050808
2MO24
ALARM: HEAT DETECT
A102 CLASSROOM
z000
11 *14A 050808
2MO24
ALARM: HEAT DETECT
A102 CLASSROOM
z000
11 *15A 050808
2MO24
ALARM: HEAT DETECT
A102 CLASSROOM
z000
11 *18A 050808
2MO24
ALARM: HEAT DETECT
A101 LWR. CEILING
z000
11*04A 050808
2MO27
ALARM: HEAT DETECT
A101 LWR. CEILING
z000
11*05A 050808
2MO27
ALARM: HEAT DETECT
BELOW KITCHEN
z001
09*39A 050808
2MO31
ALARM: HEAT DETECT
BELOW KITCHEN
z001
09*40A 050808
2MO31
ALARM: HEAT DETECT
BELOW KITCHEN
z001
09*40A 050808
2MO31
ALARM: HEAT DETECT
ABOVE KITCHEN
z000
11 *34A 050908
2MO32
ALARM: HEAT DETECT
ABOVE KITCHEN
z000
11 *34A 050908
2MO32
ALARM: HEAT DETECT
ABOVE KITCHEN
z000
11 *35A 050908
2MO32
ALARM: HEAT DETECT
ABOVE KITCHEN
z000
11 *36A 050908
2MO32
ALARM: HEAT DETECT
ABOVE KITCHEN
z000
11 *50A 050908
2MO32
ALARM: HEAT DETECT
ABOVE KITCHEN
z000
11*51A 050908
2MO32
ALARM: HEAT DETECT
ABOVE KITCHEN
z000
11 *51A 050908
2MO32
ALARM: HEAT DETECT
ABOVE KITCHEN
z000
11 *52A 050908
2MO32
ALARM: HEAT DETECT
ABOVE KITCHEN
z000
11 *55A 050908
2MO32
ALARM: HEAT DETECT
ABOVE KITCHEN
z000
11 *55A 050908
2MO32
ALARM: HEAT DETECT
OFFICE KITCHEN
z000
11 *43A 050908
2MO33
ALARM: HEAT DETECT
OFFICE KITCHEN
z000
11 *44A 050908
2MO33
ALARM: HEAT DETECT
J160 STORAGE RM
z000
11*36A 050908
2MO42
ALARM: HEAT DETECT
J160 STORAGE RM
z000
11*41A 050908
2MO42
ALARM: HEAT DETECT
J160 STORAGE RM
z000
11*45A 050908
2MO42
ALARM: HEAT DETECT
B102 HEATS ABOVE
z000
11*56A 050808
2MO54
ALARM: HEAT DETECT
B102 HEATS ABOVE
z000
11 *58A 050808
2MO54
ALARM: HEAT DETECT
B102 HEATS ABOVE
z000
11 *59A 050808
2MO54
ALARM: HEAT DETECT
B102 HEATS ABOVE
z000
12*01 P 050808
2MO54
ALARM: HEAT DETECT
B102 HEATS ABOVE
z000
12*01 P 050808
2MO54
ALARM: HEAT DETECT
B101 LOW CEILING HEAT
z000
01 *23P 050808
2MO56
ALARM: HEAT DETECT
B101 LOW CEILING HEAT
z000
01 *24P 050808
2MO56
ALARM: HEAT DETECT
C101 LOW CEILING
z000
02*38P 050808
2MO61
ALARM: HEAT DETECT
C101 LOW CEILING
z000
02*39P 050808
2MO61
ALARM: HEAT DETECT
C101 LOW CEILING
z000
02*40P 050808
2MO61
ALARM: HEAT DETECT
C102 CLASSROOM
z000
08*26A 050908
2MO64
ALARM: HEAT DETECT
C102 CLASSROOM
z000
08*26A 050908
2MO64
ALARM: HEAT DETECT
C102 CLASSROOM
z000
08*27A 050908
2MO64
ALARM: HEAT DETECT
C102 CLASSROOM
z000
08*29A 050908
2MO64
ALARM: HEAT DETECT
J170 CORRIDOR
z000
03*06P 050808
2MO65
ALARM: HEAT DETECT
J170 CORRIDOR
z000
03*08P 050808
2MO65
ALARM: HEAT DETECT
J171 SALLYPORT
z000
03*12P 050808
2MO69
ALARM: HEAT DETECT
D102 CLASSROOM
z000
01*57P 050808
2M103
ALARM: HEAT DETECT
D102 CLASSROOM
z000
01*58P 050808
2M103
ALARM: HEAT DETECT
D102 CLASSROOM
z000
01*59P 050808
2M103
ALARM: HEAT DETECT
D102 CLASSROOM
z000
02*OOP 050808
2M103
ALARM: HEAT DETECT
D101 HEATS ABOVE
z000
01 *32P 050808
2M1 14
ALARM: HEAT DETECT
D101 HEATS ABOVE
z000
01*38P 050808
2M114
ALARM: HEAT DETECT
Dl 01 H EATS ABOVE
z000
01 *42 P 050808
2M1 14
ALARM: HEAT DETECT
D101 HEATS ABOVE
z000
01*44P 050808
2M114
ALARM: HEAT DETECT
D101 HEATS ABOVE
z000
01*47P 050808
2M114
ALARM: HEAT DETECT
D101 HEATS ABOVE
z000
01*50P 050808
2M114
ALARM: HEAT DETECT
A101 HIGH CLNG HEATS
z000
10*37A 050808
2M115
ALARM: HEAT DETECT
A101 HIGH CLNG HEATS
z000
10*40A 050808
2M115
ALARM: HEAT- DETECT
A101 HIGH CLNG HEATS
z000
10*42A 050808
2M115
ALARM: HEAT DETECT
A101 HIGH CLNG HEATS
z000
10*47A 050808
2M115
ALARM: HEAT DETECT
A101 HIGH CLNG HEATS
z000
10*51A 050808
2M115
ALARM: HEAT DETECT
C101 HIGH CEILING
z000
02*19P 050808
2M147
ALARM: HEAT DETECT
C101 HIGH CEILING
z000
02*27P 050808
2M147
ALARM: HEAT DETECT
C101 HIGH CEILING
z000
02*29P 050808
2M147
ALARM: HEAT DETECT
C101 HIGH CEILING
z000
02*32P 050808
2M147
ALARM: HEAT DETECT
B POD HIGH CEILING
z000
11*32A 050808
2M158
ALARM: HEAT DETECT
B POD HIGH CEILING
z000
11*40A 050808
2M158
ALARM: HEAT DETECT
B POD HIGH CEILING
z000
11*45A 050808
2M158
ALARM: HEAT DETECT
B POD HIGH CEILING
z000
11*46A 050808
2M158
ALARM: MONITOR
D101 LOW CEILING
z000
01*52P 050808
2M106
ALARM: MONITOR
D101 LOW CEILING
z000
01 *54P 050808
2M106
ALARM: MONITOR
D101 LOW CEILING
z000
01 *55P 050808
2M106
ALARM: PULL STATION
J131 SALLYPORT
z000
12*49P 050708
1 MO13
ALARM: PULL STATION
J131 SALLYPORT
z000
12*49P 050708
1 MO13
ALARM: PULL STATION
104 HALL ADMINISTRAT
z001
12*06P 050708
1 M070
ALARM: PULL STATION
El 18 STAFF STATION
z000
08*44A 050908
1 M124
ALARM: PULL STATION
Al 18 STAFF STATION
z000
10*1OA 050808
2MO13
ALARM: PULL STATION
J151 RECEIVING SALLY
z000
09*45A 050808
2MO41
ALARM: PULL STATION
J 171 SALLY PORT
z000
09*56A 050808
2MO72
ALARM: PULL STATION
C118 STAFF STATION
z000
01 *31 P 050808
2MO93
ALARM: PULL STATION
J181 SALLYPORT
z000
09*53A 050808
2M113
ALARM: SMOKE(PHOTO)
WEST CORRIDOR 5 J130
z001
09*51A 050808
1 DO17
ALARM: SMOKE(PHOTO)
WEST CORRIDOR 2 J130
z001
09*50A 050808
1 D020
ALARM: SMOKE(PHOTO)
WEST CORRIDOR 3 J130
zo01
09*50A 050808
1 D032
ALARM: SMOKE(PHOTO)
SKYLIGHT E-POD E201
z001
08*55A 050908
1 D044
ALARM: SMOKE(PHOTO)
MECHANICAL RM. F203
z001
09*58A 050908
1 D062
ALARM: SMOKE(PHOTO)
E/F ELECT. RM. F114
z001
09*05A 050908
1D123
ALARM: SMOKE(PHOTO)
E/F STORAGE El 14
zo01
09*03A 050908
1 D134
ALARM: SMOKE(PHOTO)
E CLASS RM STR E103
zool
09*32A 050908
1 D143
ALARM: SMOKE(PHOTO)
CLASSROOM E-POD E102
zo01
09*31A 050908
1 D145
ALARM: SMOKE(PHOTO)
E/F 2ND STR. W E216
z001
09*16A 050908
1D153
ALARM: SMOKE(PHOTO)
A LOW CEIL. S A101
z001
10*07A 050808
2DO26
ALARM: SMOKE(PHOTO)
ROOF DR./STR. E J 152
z001
09*47A 050808
2DO38
ALARM: SMOKE(PHOTO)
D-12 SLEEP UNIT D208
z001
01 *38P 050808
2DO65
ALARM: SMOKE(PHOTO)
NORTH CORI DOR 1 J170
z001
09*54A 050808
2DO67
LARM: SMOKE(PHOTO)
ELECTRICAL RM.W J148
2001
10*56A 050708
1 D007
LARM: SMOKE(PHOTO)
ELECTRICAL RM.M J148
2001
10*54A 050708
1 D008
LARM: SMOKE(PHOTO)
ELECTRICAL RM.E J148
2001
10"55A 050708
1D009
LARM: SMOKE(PHOTO)
STAFF LOCKER RM J144
2001
12"48P 050708
1D011
LARM: SMOKE(PHOTO)
STAFF CHANGING J143
2001
12'48P 050708
1D012
LARM: SMOKE(PHOTO)
SALLYPORT-STAFF J131
2001
12*48P 050708
1D014
LARM: SMOKE(PHOTO)
PROPERTY RM.W J102
2001
12"13P 050708
1D015
LARM: SMOKE(PHOTO)
PROPERTY RM.M J102
2001
12"13P 050708
1D018
LARM: SMOKE(PHOTO)
PROPERTY RM.E J102
2001
12*12P 050708
1D019
�LARM: SMOKE(PHOTO)
BREAK RM. J140
2001
12*43P 050708
1D021
ALARM: SMOKE(PHOTO)
E HIGH CEIL. S E201
2001
08"35A 050908
1 D022
ALARM: SMOKE(PHOTO)
F HIGH CEIL. N F201
2001
09"06A 050908
1 D023
ALARM: SMOKE(PHOTO)
F HIGH CEIL. W F201
2001
09*10A050908
1D024
ALARM: SMOKE(PHOTO)
F HIGH CEIL. S F201
2001
09"`15A 050908
1D025
ALARM: SMOKE(PHOTO)
EDUCAT. STR. E J139
2001
12''45P 050708
1 D026
ALARM: SMOKE(PHOTO)
EpUCAT. STR. W J139
2001
12*46P 050708
1D027
ALARM: SMOKE(PHOTO)
TELEPHONE RM. J149
2001
12"01 P 050708
1 D031
ALARM: SMOKE(PHOTO)
EXAM RM WAITING J138
2001
12*41 P 050708
1 D033
ALARM: SMOKE(PHOTO)
EXAM RM. MED. J137
2001
12"40P 050708
1D034
ALARM: SMOKE(PHOTO)
E-16 SLEEP UNIT E211
2001
08"48A 050908
1 D035
ALARM: SMOKE(PHOTO)
SOILED UTILITY J135
2000
12*39P 050708
1 D038
ALARM: SMOKE(PHOTO)
NURSES FILES J132
2001
12*38P 050708
1D039
ALARM: SMOKE(PHOTO)
E-15 SLEEP UNIT E210
2001
08''49A 050908
1 D040
ALARM: SMOKE(PHOTO)
CLEAN UTILITY J134
2001
12*39P 050708
1D041
ALARM: SMOKE(PHOTO)
E HIGH CEIL. Id E201
2001
08*34A 050908
1 D043
ALARM: SMOKE(PHOTO)
E HIGH CEIL. E E201
2001
08"`35A 050908
1 D045
ALARM: SMOKE(PHOTO)
WEST CORRIDOR 2 J130
2001
09*50A 050808
1D046
ALARM: SMOKE(PHOTO)
E-14 SLEEP UNIT E209
2001
08*49A 050908
1 D047
ALARM: SMOKE(PHOTO)
CLOTHING INTAKE J107
2001
12*25P 050708
1 D048
ALARM: SMOKE(PHOTO)
HOLDING RM. J106
2001
12"`20P 050708
1D049
ALARM: SMOKE(PHOTO)
HOLDING RM. J106
2001
12*22P 050708
1D049
ALARM: SMOKE(PHOTO)
HOLDING CELL J105
2001
12"`19P 050708
1 D050
ALARM: SMOKE(PHOTO)
SALLYPORT-CAR J101
2001
11"59A 050708
1D052
ALARM: SMOKE(PHOTO)
F HIGH CEIL. E F201
2001
09"`25A050908
1D053
ALARM: SMOKE(PHOTO)
CORRIDOR ADMIN 112
2001
11*59A 050708
1 D055
ALARM: SMOKE(PHOTO)
SKYLIGHT F-POD F201
2001
09*27A 050908
1 D057
ALARM: SMOKE(PHOTO)
HOLDING WEST #2 J112
2001
12"11 P 050708
1 D058
ALARM: SMOKE(PHOTO)
HOLDING EAST #1 J111
2001
12*11 P 050708
1 D059
ALARM: SMOKE(PHOTO)
MECHANICAL RM. F203
2001
09*58A 050908
1 D062
ALARM: SMOKE(PHOTO)
F-16 SLEEP UNIT F204
2001
09*57A 050908
1 D064
ALARM: SMOKE(PHOTO)
SALLYPORT VISIT J123
2001
12*08P 050708
1 D065
ALARM: SMOKE(PHOTO)
F-15 SLEEP UNIT F205
2001
09*57A 050908
1 D066
ALARM: SMOKE(PHOTO)
E HIGH CEIL. W E201
2001
08"`35A 050908
1 D067
ALARM: SMOKE(PHOTO)
LOBBY N 100
2001
12*07P 050708
1 D068
ALARM: SMOKE(PHOTO)
HALL-FRONT ADMIN 104
2001
12"03P 050708
1D069
ALARM: SMOKE(PHOTO)
ELECTRICAL ADMIN 115
2001
12"09P 050708
1 D071
ALARM: SMOKE(PHOTO)
CLERICAL N 108
2001
12"01 P 050708
1 D072
ALARM: SMOKE(PHOTO)
CLERICALS 108
2001
12*01 P 050708
1 D073
ALARM: SMOKE(PHOTO)
SUPERVISOR NORTH 111
2001
12"03P 050708
1 D074
ALARM: SMOKE(PHOTO)
SUPERVISOR SOUTH 110
2001
12'02P 050708
1 D075
ALARM: SMOKE(PHOTO)
SUPERINTENDANT 109
2001
12*02P 050708
1D076
ALARM: SMOKE(PHOTO)
BREAK RM.ADMIN 107
2001
12"03P 050708
1D077
ALARM: SMOKE(PHOTO)
CONFERENCE ADMIN 106
2001
12*05P 050708
1D078
ALARM: SMOKE(PHOTO)
RECEPTION ADMIN 105
2001
12*05P 050708
1D079
ALARM: SMOKE(PHOTO)
LOBBY S 100
2001
12*06P 050708
1 D081
ALARM: SMOKE(PHOTO)
RECORDS ADMIN 116
2001
12*05P 050708
1D082
ALARM: SMOKE(PHOTO)
NO-CONTACT V. S J125
2001
12*28P 050708
1D083
ALARM: SMOKE(PHOTO)
NO-CONTACT V. N J116
2001
12"27P 050708
1D084
ALARM: SMOKE(PHOTO)
INTEVIEW INTAKE J110
2001
12*21 P 050708
1 D086
ALARM: SMOKE(PHOTO)
INTAKE W J104
2001
12*14P 050708
1 D090
ALARM: SMOKE(PHOTO)
INTAKE W J104
2001
12*20P 050708
1 D090
ALARM: SMOKE(PHOTO)
WEST CORRIDOR 1 J 130
2001
09*52A 050808
1 D091
ALARM: SMOKE(PHOTO)
VISITING OBSERV.J122
2001
12*29P 050708
1 D093
ALARM: SMOKE(PHOTO)
VISIT UTIL STR J121
2001
12*31 P 050708
1 D094
ALARM: SMOKE(PHOTO)
VISIT.CONTACT S J120-
2001
12*29P 050708
1 D095
ALARM: SMOKE(PHOTO)
VISIT.CONTACT N J120
2001
12*28P 050708
1 D096
ALARM: SMOKE(PHOTO)
C.C. BATHROOM J118
2001
12*33P 050708
1 D098
ALARM: SMOKE(PHOTO)
CENTRAL CONTROL J117
2001
12*33P 050708
1 D099
ALARM: SMOKE(PHOTO)
EAST CORRIDOR 2 J180
2001
09*52A 050808
1 D100
ALARM: SMOKE(PHOTO)
EAST CORRIDOR 1 J180
2001
09*57A 050808
1 D101
ALARM: SMOKE(PHOTO)
EAST SALLYPORT J 181
2001
09*53A 050808
1 D 102
ALARM: SMOKE(PHOTO)
EAST SALLYPORT J 181
2001
09*55A 050808
113102
ALARM: SMOKE(PHOTO)
E-10 SLEEP UNIT E205
2001
08*52A 050908
113103
ALARM: SMOKE(PHOTO)
E-11 S. U. DAL. E206
2001
08*51 A 050908
1 D104
ALARM: SMOKE(PHOTO)
CLASSROOM F-POD F102
2001
10*47A 050908
1D105
ALARM: SMOKE(PHOTO)
F LOW CEIL. N F101
2001
09*50A 050908
113106
ALARM: SMOKE(PHOTO)
F LOW CEIL. S F101
2001
09*49A 050908
113107
ALARM: SMOKE(PHOTO)
E-12 S.U. DBL. E207
2001
08*50A 050908
1 D108
ALARM: SMOKE(PHOTO)
EAST CORRIDOR 3 J180
2001
09*52A 050808
11)109
ALARM: SMOKE(PHOTO)
EAST CORRIDOR 4 J180
2001
09*52A 050808
11)110
ALARM: SMOKE(PHOTO)
EAST CORRIDOR 5 J180
2001
09*53A 050808
1 D111
ALARM: SMOKE(PHOTO)
E-13 SLEEP UNIT E208
2001
08*50A 050908
1 D113
ALARM: SMOKE(PHOTO)
CLASS STR. F J103
2001
10*46A 050908
1 D114
ALARM: SMOKE(PHOTO)
F-08 SLEEP UNIT F104
2001
09*53A 050908
11)115
ALARM: SMOKE(PHOTO)
F-07 SLEEP UNIT F105
2001
09*52A 050908
1 D116
ALARM: SMOKE(PHOTO)
F-06 S.U.DBL/HC F106
2001
09*52A 050908
11)117
ALARM: SMOKE(PHOTO)
F-05 S.U. DBL. F107
2001
09*52A 050908
1 D118
ALARM: SMOKE(PHOTO)
F-04 SLEEP UNIT F108
2001
09*52A 050908
1D`119
ALARM: SMOKE(PHOTO)
F-03 SLEEP UNIT F109
2001
09*51A 050908
11)120
ALARM: SMOKE(PHOTO)
F-02 SLEEP UNIT F110
2001
09*51A 050908
1 D121
ALARM: SMOKE(PHOTO)
F-01 SLEEP UNIT F111
2001
09*51A 050908
11)122
ALARM: SMOKE(PHOTO)
C.C. SALLYPORT J115
2001
12*26P 050708
1D124
ALARM: SMOKE(PHOTO)
E/F SALLYPORT E115
2001
09*04A 050908
1 D127
ALARM: SMOKE(PHOTO)
F INTERVEW RM F116
2001
09*49A 050908
11)128
ALARM: SMOKE(PHOTO)
E/F STAFF AREA E118
2001
09*01A 050908
113132
ALARM: SMOKE(PHOTO)
E-08 SLEEP UNIT E111
2001
08*45A 050908
1D135
ALARM: SMOKE(PHOTO)
E-07 SLEEP UNIT E110
2001
08*45A 050908
1 D136
ALARM: SMOKE(PHOTO)
E-06 SLEEP UNIT E109
2001
08*46A 050908
11)137
ALARM: SMOKE(PHOTO)
E-05 SLEEP UNIT E108
2001
08*46A 050908
1D138
ALARM: SMOKE(PHOTO)
E-04 S.U. DBL. E107
2001
08*47A 050908
11)139
ALARM: SMOKE(PHOTO)
E-03 S.U.DBL/HC E106
2001
08*47A 050908
1 D140
ALARM: SMOKE(PHOTO)
E-02 SLEEP UNIT E105
2001
08*47A 050908
113141
ALARM: SMOKE(PHOTO)
E-01 SLEEP UNIT E104
2001
08*48A 050908
1 D142
ALARM: SMOKE(PHOTO)
E-09 SLEEP UNIT E204
2001
08*53A 050908
1 D144
ALARM: SMOKE(PHOTO)
E LOW CEIL. N E101
2001
08*34A 050908
1 D146
ALARM: SMOKE(PHOTO)
E LOW CEIL. S E101
2001
08*34A 050908
1 D147
ALARM: SMOKE(PHOTO)
E INTERVIEW RM E116
2001
08*37A 050908
113149
ALARM: SMOKE(PHOTO)
E/F LOW VOLTAGE E215
2001
09*17A 050908
113150
ALARM: SMOKE(PHOTO)
E/F 2ND FL.PASS E214
2001
09*18A 050908
1 D151
ALARM: SMOKE(PHOTO)
E/F 2ND STR. E E216
2001
09*18A 050908
11)152
ALARM: SMOKE(PHOTO)
F-09 SLEEP UNIT F211
2001
09*54A 050908
11)154
ALARM: SMOKE(PHOTO)
F-10 SLEEP UNIT F210
2001
09*55A 050908
113155
ALARM: SMOKE(PHOTO)
F-11 SLEEP UNIT F209
2001
09*55A 050908
113156
ALARM: SMOKE(PHOTO)
F-12 SLEEP UNIT F208
2001
09*56A 050908
113157
ALARM: SMOKE(PHOTO)
F-13 S.U. DBL. E207
2001
09*55A 050908
11)158
ALARM: SMOKE(PHOTO)
F-14 S.U. DBL. F206
2001
09*56A 050908
11)159
LARM: SMOKE(PHOTO)
A/6 STORAGE 6114
2001
10*31A 050808
2D003
LARM: SMOKE(PHOTO)
A/B ELECTRICAL A114
2001
10*25A 050808
2D004
LARM: SMOKE(PHOTO)
A INTERVIEW RM A116
2001
10"11A 050808
2D006
LARM: SMOKE(PHOTO)
B INTERVIEW RM 6116
2001
11*23A 050808
2D007
LARM: SMOKE(PHOTO)
AIB STAFF ROOM A118
2001
10*10A 050808
2D011
LARM: SMOKE(PHOTO)
SKYLIGHT D-POD D201
2001
01*34P 050808
2D012
LARM: SMOKE(PHOTO)
A-08 SLEEP UNIT A111
2001
10"12A 050808
2D014
LARM: SMOKE(PHOTO)
A-07 SLEEP UNIT A110
2001
10*13A 050808
2D015
LARM: SMOKE(PHOTO)
A-06 SLEEP UNIT A109
2001
10"13A 050808
2D016
LARM: SMOKE(PHOTO)
A-05 SLEEP UNIT A108
2001
10'`14A 050808
2D017
LARM: SMOKE(PHOTO)
A-04 S.U. DBL A107
2001
10*16A 050808
2D018
LARM: SMOKE(PHOTO)
A-03 S.U.DBUHC A106
2001
10"15A 050808
2D019
ALARM: SMOKE(PHOTO)
A-02 SLEEP UNIT A105
2001
10*14A 050808
2D020
ALARM: SMOKE(PHOTO)
A-01 SLEEP UNIT A104
2001
10*15A 050808
2D021
ALARM: SMOKE(PHOTO)
A CLASS RM STR A103
2001
10"08A 050808
2D022
ALARM: SMOKE(PHOTO)
CLASSROOM A-POD A102
2001
10*09A 050808
2D025
ALARM: SMOKE(PHOTO)
D HIGH CEIL. N D201
2001
01'36P 050808
2D031
ALARM: SMOKE(PHOTO)
D HIGH CEIL. E D201
2001
01"30P 050808
2D032
ALARM: SMOKE(PHOTO)
KITHEN OFFICE J161
2001
09*44A 050808
2D033
ALARM: SMOKE(PHOTO)
KITCHEN STR. N J160
2001
09*42A 050808
2D037
ALARM: SMOKE(PHOTO)
ROOF DR./STR. W J152
2001
09'`46A 050808
2D039
ALARM: SMOKE(PHOTO)
D HIGH CEIL. S D201
2001
01*49P 050808
2D042
ALARM: SMOKE(PHOTO)
KITCHEN STR. S J160
2001
09"`44A 050808
2D043
ALARM: SMOKE(PHOTO)
B-01 SLEEP UNIT 6111
2001
11"24A 050808
2D044
ALARM: SMOKE(PHOTO)
B-02 SLEEP UNIT 6110
2001
11*24A 050808
2D045
ALARM: SMOKE(PHOTO)
B-03 SLEEP UNIT 8109
2001
11"25A 050808
2D046
ALARM: SMOKE(PHOTO)
B-04 SLEEP UNIT 6108
2001
11 *25A 050808
2D047
ALARM: SMOKE(PHOTO)
B-05 S.U. DBL 6107
2001
11*25A 050808
2D048
ALARM: SMOKE(PHOTO)
B-05 S.U. DBL 6107
2001
11'`27A 050808
2D048
ALARM: SMOKE(PHOTO)
B-06 S.U.DBUHC 6106
2001
11"'26A 050808
2D049
ALARM: SMOKE(PHOTO)
B-07 SLEEP UNIT 6105
2001
11 *26A 050808
2D050
ALARM: SMOKE(PHOTO)
B-08 SLEEP UNIT 6104
2001
11*26A 050808
2D051
ALARM: SMOKE(PHOTO)
CLASS STR. B 6103
2001
11 *53A 050808
2D052
ALARM: SMOKE(PHOTO)
CLASSROOM B-POD 8102
2001
11*47A 050808
2D053
ALARM: SMOKE(PHOTO)
BLOW CEIL. N 6101
2001
11*48A 050808
2D055
ALARM: SMOKE(PHOTO) .
BLOW CEIL. S 6101
2001
11*47A 050808
2D057
ALARM: SMOKE(PHOTO)
D-09 SLEEP UNIT D211
2001
01"36P 050808
2D059
ALARM: SMOKE(PHOTO)
CLOW CEIL. S C101
2001
02*14P 050808
2D060
ALARM: SMOKE(PHOTO)
D-10 SLEEP UNIT D210
2001
01"37P 050808
2D061
ALARM: SMOKE(PHOTO)
CLOW CEIL. N C101
2001
02*24P 050808
2D062
ALARM: SMOKE(PHOTO)
CLASSROOM C-POD C102
2001
08*24A 050908
2D063
ALARM: SMOKE(PHOTO)
D-11 SLEEP UNIT D209
2001
01 "37P 050808
2D064
ALARM: SMOKE(PHOTO)
D-12 SLEEP UNIT D208
2001
01*39P 050808
2D065
ALARM: SMOKE(PHOTO)
NORTH CORIDOR 1 J170
2001
09*57A 050808
2D067
ALARM: SMOKE(PHOTO)
CLASS RM.STR. C C103
2001
08"24A 050908
2D068
ALARM: SMOKE(PHOTO)
D-14 S.U. DBL D206
2001
01*39P 050808
2D069
ALARM: SMOKE(PHOTO)
D-15 SLEEP UNIT D205
2001
01"39P 050808
2D071
ALARM: SMOKE(PHOTO)
C-01 SLEEP UNIT C104
2001
02*22P 050808
2D072
ALARM: SMOKE(PHOTO)
C-02 SLEEP UNIT C105
2001
02*20P 050808
2D073
ALARM: SMOKE(PHOTO)
C-03 S.U.DBL/HC C106
2001
02*19P 050808
2D074
ALARM: SMOKE(PHOTO)
C-04 S.U. DBL C107
2001
02"19P 050808
2D075
ALARM: SMOKE(PHOTO)
C-05 SLEEP UNIT C108
2001
02'`19P 050808
2D076
ALARM: SMOKE(PHOTO)
C-06 SLEEP UNIT C109
2001
02"18P 050808
2D077
ALARM: SMOKE(PHOTO)
C-07 SLEEP UNIT C110
2001
02'18P 050808
2D078
ALARM: SMOKE(PHOTO)
C-08 SLEEP UNIT C111
2001
02`18P 050808
2D079
ALARM: SMOKE(PHOTO)
D-16 SLEEP UNIT D204
2001
01*40P 050808
2D080
ALARM: SMOKE(PHOTO)
C/D 2ND MECH RM D203
2001
01*41P 050808
2D081
ALARM: SMOKE(PHOTO)
C/D ELECT. RM. C114
2001
02*13P 050808
2D083
ALARM: SMOKE(PHOTO)
C/D STORAGE D114
2001
01"32P 050808
2D084
ALARM: SMOKE(PHOTO)
D INTERVIEW RM. D116
2001
01*31P 050808
2D086
ALARM: SMOKE(PHOTO)
D INTERVIEW RM. D116
2001
01*36P 050808
2D086
ALARM: SMOKE(PHOTO)
C INTERVIEW RM. C116
2001
02'12P 050808
2D087
ALARM: SMOKE(PHOTO)
C/D STAFF AREA C118
2001
01"`31P 050808
2D091
ALARM: SMOKE(PHOTO)
D HIGH CEIL. W D201
2001
01'`41 P 050808
2D092
ALARM: SMOKE(PHOTO)
D-01 SLEEP UNIT D111
2001
01"33P 050808
2D094
ALARM: SMOKE(PHOTO)
D-02 SLEEP UNIT D110
2001
01*34P 050808
2D095
ALARM: SMOKE(PHOTO)
D-03 SLEEP UNIT D109
2001
01*34P 050808
2D096
ALARM: SMOKE(PHOTO)
D-04 SLEEP UNIT D108
2001
01"34P 050808
2D097
ALARM: SMOKE(PHOTO)
D-05 S.U. DBL. D107
2001
01"34P 050808
2D098
ALARM: SMOKE(PHOTO)
D-07 SLEEP UNIT D105
2001
01*35P 050808
2D100
ALARM: SMOKE(PHOTO)
D-08 SLEEP UNIT D104
2001
01*37P 050808
2D101
ALARM: SMOKE(PHOTO)
D CLASS RM STR D103
2001
01*43P 050808
2D102
ALARM: SMOKE(PHOTO)
CLASSROOM D -POD D102
2001
01*45P 050808
2D104
ALARM: SMOKE(PHOTO)
D LOW CEIL. S D101
2001
01*30P 050808
213107
ALARM: SMOKE(PHOTO)
SKYLIGHT C -POD C201
2001
02*24P 050808
2D108
ALARM: SMOKE(PHOTO)
SKYLIGHT C -POD C201
2001
02'''25P 050808
2D108
ALARM: SMOKE(PHOTO)
C HIGH CEIL. N C201
2001
02*24P 050808
2D109
ALARM: SMOKE(PHOTO)
A/B LOW VOLTAGE A215
2001
10"23A 050808
2D110
ALARM: SMOKE(PHOTO)
A/B 2ND FL.PASS A214
2000
10*24A 050808
21)111
ALARM: SMOKE(PHOTO)
A/B 2ND STR. E A216
2001
10*25A 050808
2D112
ALARM: SMOKE(PHOTO)
A/B 2ND STR. W A216
2001
10"24A 050808
2D113
ALARM: SMOKE(PHOTO)
A HIGH CEIL. E A201
2001
10"45A 050808
2D114
ALARM: SMOKE(PHOTO)
SKYLIGHT A -POD A201
2001
10*44A 050808
213115
ALARM: SMOKE(PHOTO)
A HIGH CEIL. S A201
2001
10"`39A 050808
2D116
ALARM: SMOKE(PHOTO)
A HIGH CEIL. W A201
2001
10*35A 050808
2D117
ALARM: SMOKE(PHOTO)
A-16 SLEEP UNIT A211
2001
10*17A 050808
213118
ALARM: SMOKE(PHOTO)
A-15 SLEEP UNIT A210
2001
10*21A 050808
2D119
ALARM: SMOKE(PHOTO)
A-14 SLEEP UNIT A209
2001
10'"`21A 050808
2D120
ALARM: SMOKE(PHOTO)
A-13 SLEEP UNIT A208
2001
10"21A 050808
2D121
ALARM: SMOKE(PHOTO)
A-12 S.U. DBL. A207
2001
10*20A 050808
2D122
ALARM: SMOKE(PHOTO)
A-11 S.U. DBL. A206
2001
10"20A 050808
2D123
ALARM: SMOKE(PHOTO)
A-10 SLEEP UNIT A205
2001
10*20A 050808
2D124
ALARM: SMOKE(PHOTO)
A-09 SLEEP UNIT A204
2001
10"19A 050808
2D125
ALARM: SMOKE(PHOTO)
A HIGH CEIL. N A201
2001
10*41A 050808
2D127
ALARM: SMOKE(PHOTO)
B HIGH CEIL. W 6201
2001
11*42A050808
213128
ALARM: SMOKE(PHOTO)
B HIGH CEIL. S 8201
2001
11*38A 050808
2D129
ALARM: SMOKE(PHOTO)
B HIGH CEIL. E 6201
2001
11"`23A 050808
2D130
ALARM: SMOKE(PHOTO)
SKYLIGHTS -POD 6201
2001
11"35A050808
2D131
ALARM: SMOKE(PHOTO)
B-09 SLEEP UNIT 8211
2001
11*30A 050808
2D132
ALARM: SMOKE(PHOTO)
6-10 SLEEP UNIT 6210
2001
11*31A 050808
2D133
ALARM: SMOKE(PHOTO)
B-11 SLEEP UNIT 6209
2001
11*30A 050808
2D134
ALARM: SMOKE(PHOTO)
B-12 SLEEP UNIT 8208
2001
11*31A 050808
2D135
ALARM: SMOKE(PHOTO)
B-13 S.U. DBL. 8207
2001
11*32A 050808
2D136
ALARM: SMOKE(PHOTO)
B-14 S.U. DBL. 6206
2001
11*33A 050808
2D137
ALARM: SMOKE(PHOTO)
B-15 SLEEP UNIT 6205
2001
11`'33A 050808
213138
ALARM: SMOKE(PHOTO)
B-16 SLEEP UNIT 8204
2001
11=34A 050808
2D139
ALARM: SMOKE(PHOTO)
B HIGH CEIL. N 6201
2001
11*30A050808
2D141
ALARM: SMOKE(PHOTO)
C/D LOW VOLT RM C216
2001
02"31P 050808
2D142
ALARM: SMOKE(PHOTO)
C/D 2ND FL.PASS C214
2001
02*30P 050808
2D143
ALARM: SMOKE(PHOTO)
C/D 2ND STR. W C215
2001
02*31 P 050808
2D144
ALARM: SMOKE(PHOTO)
C/D 2ND STR. E C215
2001
02"34P 050808
2D145
ALARM: SMOKE(PHOTO)
C HIGH CEIL. E C201
2001
02*06P 050808
213146
ALARM: SMOKE(PHOTO)
SALLYPORT NORTH J171
2001
09*54A 050808
213147
ALARM: SMOKE(PHOTO)
C HIGH CEIL. S C201
2001
02""23P 050808
2D148
ALARM: SMOKE(PHOTO)
C HIGH CEIL. W C201
2001
02*23P 050808
2D149
ALARM: SMOKE(PHOTO)
C-16 SLEEP UNIT C211
2001
02'25P 050808
213150
LARM: SMOKE(PHOTO)
C-15 SLEEP UNIT C210
2001
02*25P 050808
2D151
LARM: SMOKE(PHOTO)
C-14 SLEEP UNIT C209
2001
02*25P 050808
2D152
LARM: SMOKE(PHOTO)
C-13 SLEEP UNIT C208
2001
02*26P 050808
2D153
LARM: SMOKE(PHOTO)
C-12 S.U. DBL. C207
2001
02*27P 050808
2D154
LARM: SMOKE(PHOTO)
C-11 S. U. DBL. C206
2001
02*27P 050808
2D155
,LARM: SMOKE(PHOTO)
C-10 SLEEP UNIT C205
2001
02*28P 050808
2D156
,LARM: SMOKE(PHOTO)
C-09 SLEEP UNIT C204
2001
02*28P 050808
2D157
,LARM: SMOKE(PHOTO)
C MECHANICAL RM C203
2001
02*29P 050808
21)158
,LARM: WATERFLOW
MAIN BUILDING
2000
10*42A 050708
1 MO'12
ROUBL MONITOR
E F POD BOOSTER TRBL
OPEN
09*1 OA 050908
1 M136
25-78 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Cover Sheet
NEPA 25 as amended by CCR, Title 19
Property Information:
NIA,
FAIL*
___.
M0J���
Name. �t �
Occupancy/Use: /Use: 7
panc Y
hof CAi�
o
Address: r'
Construction Type: C• % «.�i.
X
❑ Standpipe and Hose Systems
6
Cit : %-.'r . t �` a
Y
No. Stories:
,,.�,..,,
�4E Mp
ZIP: a 59 V;
Year Constructed:
7
Contact:
y(
Telephone:
[A Fire Pump
8
Contractor Information:
,_,1_.._ Number of System Risers
Name: Wilgus Fire Control, Inc.
O Water Storage Tank
Copy sent to:
Address: 1703 Sonoma St
1(
❑ Owner Date
City: Rem
❑Water Spray System
❑ Fire AHJ Date
State: California
❑ Contractor Date
Telephone: (530)241-2465
❑Foam Water Sprinkler System
NOTES:
�
1 ) For specific inspection, testing, and
CA License# 462979 C-16 C-10 C-7
maintenance requirements and information,
see NFPA 25, 2002 Edition as amended by
Job #
California Code of Regulations, Title 19, §901
Performed b : �
Perf
to §90fi.
Y .�1w+Q��
(Print)
2) Inspection Item y performed y the
s rna be b
Owner in accordance with California Code of
Note: Contractor information may be pre-printed
Regulations Title 19 904.1 a
Forms included with this report
NFPA 25
Chapter
Number of Forms
NIA,
FAIL*
PASS
;q Automatic Sprinkler System
5
�
X
❑ Standpipe and Hose Systems
6
❑ Private Water Supply System
7
y(
[A Fire Pump
8
O Water Storage Tank
9
1(
❑Water Spray System
10
❑Foam Water Sprinkler System
11
�
*See "Deficiencies and Comments" section at end of each respective form.
State Fire Marshal AES 1 March 21, 2006
e
ANNEX B
25-79
Inspection, Testing, and Maintenance Fire Sprinkler System Page 1 of 4
NFPA 25, Cha ter 5 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance:System Riser ID:
f fell WL -0 I
Property Information:
Type of System: oF CA���
Name: Wet Pipe
D D Pie `a a
L11 _ Dry
p
Address. t D Preaction �► ,,�
0 Deluge`.
Baa
City:
Main Drain Test Results:
Abbreviation Key:
I = Inspection
Initial Static Pressure: 110 (psi)
T = Test
M = Maintenance
Residual Pressure: S�S (psi)
A-0 = After Operation
t
MI = Per Manufacturer's Instructions
1 i)
Restored Static Pressure:(Ps
Item
Activity
=Freque=ncyDescription
NFPA 25
Reference
Fail
NIA
Pass
1.1
1
Daily
Preaction/Deluge Valves — Enclosure
12.4.3.1
Week)
temperature
1.2
1
Daily
Dry Pipe Valves — Enclosure
12.4.4.1.1
Week)
temperature
1.3
I
Quarter! y
Gauges (Dry, Preaction, Deluge
5.2.4.2
Systems)
5.2.4.3
1.4
I
Quarterly
Control Valves
12.3.2.1
1.5
I
Quarterly
Alarm Devices
5.2.6
1.6
!
Quarterly
Gauges (Wet Pipe Systems)
5.2.4.1
1.7
!
Quarterly
Hydraulic nameplate
5.2.7
1.8
I
Quarterly
Pipe and Fittings
5.2.2'
1.9
I
Quarterly
Sprinklers
5.2.1
'X
1.10
1
Quarterly
Spare Sprinklers
5.2.1.3
1.11
I
Quarterly
Fire Department Connections
12.7.1
1.12
I
Quarterly
Alarm Valves — Exterior Inspection
12.4.1.1
X
1.13
I
Quarter)
Quarterly
Preaction/D6uge Valves --Exterior
12.4.3.1.6
X
Ins ection
1.14
I
Quarterly
Pressure Reducing Valves
12.5.1.1
1.15
I
Quarterly
Dry Pipe Valves — Exterior Inspection
12.4.4.1.4
`
1.16
I
Quarterly
Backflow Preventers
12.6.1
1.17
I
Annually
Buildings
5.2.5
State Fire Marshal AES 2
March 21, 2006
25-80 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PR0TFC`.TT0N �V4TF.MR
Inspection, Testing, and Maintenance Fire Sprinkler System Page 2 of 4
NEPA 25, Chapter 5 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: _
System Riser ID: i
Property Information:
NEPA 25
Reference
Fail
Type of System: oT CA
Name:
CK Wet Pipe
Address:
❑ Dry Pipe �
Hangers
❑Preaction
9
❑ Deluge
ARE N1
City:c
1.19
Item
Activity
Frequency
Description
NEPA 25
Reference
Fail
N/A
Pass
1.18
1
Annually
Hangers
5.2.3
1.19
1
Annually
Seismic Braces
5.2.3
1.20
1
5 Years
Hangers (Accessible concealed spaces)
5.2.3.3
1.21
1
5 Years
Seismic Braces (Accessible concealed
spaces)
5.2.3.3
X
1.22
1
5 Years
Pipe and Fittings (Accessible concealed
spaces)
5.2.2.3
1.23
1
5 Years
Sprinklers (Accessible concealed spaces)
5.2.1.1.4
1.24
1
5 Years
Alarm Valves — Interior Inspection
12.4.1.2
1.25
1
5 Years
Alarm Valves - Strainers, filters, orifices
12.4.1.2
1.26
1
5 Years
Check Valves — Interior Inspection
12.4.2.1
•y�
1.27
I
5 Years
PreactioniDeluge Valves — Interior
Ins cfion
12.4.3.1.7
1.28
1
5 Years
Preaction/Deluge Valves - Strainers,
filters orifices
12.4.3.1.8
1.29
1
5 Years
Dry Pipe Valves — Interior Inspecfion
12.4.4.1.5
1.30
1
5 Years
Dry Pipe Valves - Strainers, filters, orifices
12.4.4.1.6
2.1
T
Annually
Alarm Devices (90 Sec)
5.3.3
12.2.7
X
2.2
T
Annually
Main Drain Test (Enter data on Page 1)
12.2.6
12.2.6.1
12.3.3.4
2.3
T
Annually
Antifreeze Test
5.3.4
2.4
T
Annually
Control Valve - Position
-12.3.3.1
2.5
T
Annually
Control Valve — Operation
12.3.3.1
2.6
T
Annually
Supervisory
12.3.3.5
2.7
T
Annually
Preaction Valve — Priming Water
12.4.3.2.1
.�
2.8
T
Annually
Preaction Valve — Low Air Pressure Alarm
12.4.3.2.10
2.9
T
Annually
Preaction Valve — Full Flow Trip Test
12.4.3.2.2
State Fire Marshal AES 2 . March 21, 2006
ANNEX B
25-81
Inspection, Testing, and Maintenance Fire Sprinkler System Page 3 of 4
NFPA 25, Cha ter 5 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: 5/7108
System Riser ID:
Property Information:
System: ca���
Fail
Type of tioF
Name: 4'
®Wet Pipe ,��� �
T
❑ Dry Pipe
Address:
❑ Preaction
❑ Deluge
E MP►
City: Dtoo--Ae- ..� 9 s3k 5
2.11
em
E
ActivityFrequency
q y
Description
NFPA 25
Reference
Fail
NIA
Pass
2.10
T
Annually
Dry Pipe Valve — Priming Water
12.4.4.2.1
2.11
T
Annually
Dry Pipe Valve — Low Air Pressure
Alarm
12.4.4.2.6
2.12
T
Annually
Dry Pipe Valve — Quick -Opening
Device
12.4.4.2.4
�.
2.13
T
Annually
Dry Pipe Valve — Trip Test
12.4.4.2.2
2.14
T
Annually
Backflow Preventer Assemblies
12.6.2
2.15
T
3 Years
Dry Pipe Valve — Full Flow Trip Test
12.4.4.2.2.2
2.16
T
5 Years
Gauges
5.3.2
2.17
T
5 Years
Pressure Reducing Valve
12.5.1.2
2.18
T
5 Years
Fire Department Connection Backflush
12.7.4
2.19
T
5 Years
Sprinklers — Extra High Temperature
5.3.1.1.1.3
.�
2.20
T
5 Years
Sprinklers — Corrosive environment or
corrosive water
....
5112
3
�
2.21
T
10 Years
Sprinklers - Dry
5.3.1.1.1.5
2.22
T
20 Years
Sprinklers - Fast Response
5.3.1.1.1.2
2.23
T
50 Years
Sprinklers
5.3.1.1.1
2.24
T
75 Years
Sprinklers 75 years in service
5.3.1.1.1.4
2.25
T
Sprinklers manufactured prior to 1920
— Re ace
5.3.1.1.1.1
3.1
M
Annually
Control Valves
12.3.4
�(
3.2
M
Annually
Preaction/Deluge Valves
12.4.3.3.2
3.3
M
Annually
Dry Pipe Valves/Quick-Opening
Devices
12.4.4.3.2
3.4
M
Annually
Dry Pipe Valve — Low Point Drains
12.4.4.3.3
3.5
M
5 Years
Obstruction Investigation
Chapter 13
State Fire Marshal AES 2 March 21, 2006
2582 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Sprinkler System Page 4 of 4
NEPA 25, Chapter 5 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: 5/7/019
System Riser ID:
Property Information:
Name: �-
Type of System: torr CAI c
% Wet Pipe
� -
Address.. 1 .. �
❑Dry Pipe �
❑ Preac ion
t y
❑ Deluge
� Ma
City:
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the Item number
of the Activity listed above:
❑ See Continuation Page(s) (Indite ;n, fj r ontinuation pages)
PASS
❑ FAI L 71,9
signature Date
State Fire Marshal AES 2 March 21, 2006
2S -RR TN.9PFC_TT0N_ TESTING_ AND MARqTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Pumps Page 1 of 8
NEPA 25, Chapter 8 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: i P,
Pump ID:
. _ ' ..011
'�'� `
•
Property Information:
Serial Number: raw-:' Y
• 1
Name.
O, ` ' �1 j l
Key:
'
Abbreviation
i �
Address: --�,.�-'
I = Inspection
T = Test
Shaft Orientation:
M = Maintenance
A-0 = After Operation
City:
MI = Per Manufacturer's Instructions
State Fire Marshal AES 5 March 21, 2006
Annual Fire Pump Test Results
Type of Driver:
Date of Pump Test: 5
Number of pumps at this location:
III Electric
If multiple pumps:
❑ Diesel
Shaft Orientation:
❑ Series arrangement
❑ Gasoline
❑ Horizontal
❑ Parallel arrangement
❑ Steam
11 Vertical
NOTE: Submit a separate form for each pump
❑ Gas
Nameplate Data
Test Results
Shutoff
psi
p
Flow C9P m )
Net Pump RPM
Pressure (psi)
Volts
Amps
Pressure
100% Rated
Capacity
OLOO gPm
100% Rated
psi
Pressure(
150% Rated
�� gpm
Capacity
65% Rated
psi
Pressure
Rated RPM ()o rpm
Type of Test:
04 Discharge to Atmosphere
❑ Recirculation
Controller:
Test Equipment
QQ Flow Meter 1 Size: �`�
y
Manufacturer:
❑ Play pipe (1-118 )
❑ Play pipe (1-3/4")
Serial Number: (o PO DS $
❑ Diffuser/ Size:
State Fire Marshal AES 5 March 21, 2006
ANNEX B
25-R9
Inspection, Testing, and Maintenance Fire Pumps
NFPA 25, Chapter 8 as amended by CCR, Title 19
Page 2 of 8
Date of Inspection, Testing, Maintenance:
Pump ID:
Description
p
Property rtYInformation'
Name: �
Serial Number:
,-'rA�
Pass
_
I
Address:
Abbreviation Key:
-•,,� --� _-'
'
I = Inspection
T =Test
louvers
M = Maintenance
City: `Q"' '' �''S�'S�
A-0 = After Operation
-
MI = Per Manufacturer's
Instructions
FIRE PUMP INSPECTIONS
Item
Activity
Frequency
q y
Description
p
NEPA 25
Reference
Fail
NIA
Pass
1.1
I
Weekly
Pump House heating and ventilating
8.2.2( 1}
louvers
x
1.2
I
Weekly
Circulation Relief Valve
12.5.6.1
1.3
I
Weekly
Pressure Relief Valve
12.5.6.2
X
1.4
I
Quarterly
Control Valves
12.3.2.1
Fire Pump System:
8.2.2(2)
1.5
!
Weekly
a• Pump Suction, discharge, and
..
822 2 a
()()
b ass valves are open.
�{
1.6
1
Weekly
b. Piping is free of leaks.
8.2.2(2)(b)
1.7
1
Weekly
C. Suction pressure gauge reading is
8.2.2(2 } (c}
normal
X'
1.8
1
Weekly
d. System line pressure gauge
8.2.2 2 d
()( }
readingis normal
1.9
1
Weekly
e. Suction reservoir is full.
8.2.2(2)(e)
1.10
1
Weekly
f. Wet pit suction screens are
8.2.2 2
()(�
unobstructed and in lace.
Electrical System Conditions:
8.2.2(3)
1.14
f
Weekly
a. Controller pilot fight is illuminated.
8.2.2(3)(a)
1.12
l
Weekly
b. Transfer switch normal pilot light is
8..2.2 3
()�}
illuminated.
1.13
1
Weekly
c. Isolating switch is closed — standby
8.2.2(3)(c)
(emergency) source.
d. Reverse phase alarm pilot light is
1.14
1
Weekly
off or normal phase rotation pilot light
8.2.2(3)(d)
is on.
1.15
1
Weekly
Oil level in vertical motor sight glass is
8.2.2 3
(}(e }
normal.
Diesel Engine System Conditions:
8.2.2(4)
1.16
1
Weekly
a. Fuel tank is iwo-thirds full.
8.2.2(4)(a)
State Fire Marshal AES 5 March 21, 2006
25.90 INSPECTION. TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Pumps Page 3 of 8
NEPA 25, Chapter 8 as amended by CCR, Tine 19
Date of Inspection, Testing, Maintenance: r
Pump ID: 11?
a �YInformation:
Serial Number:Pro �' s ''•
Name: ' �.3!'77�
fait
Abbreviation Key.
Address:
I = Ins eclion
R �E
1
T = Test
b Controller selector switch is in
M = Maintenance
A-0 = After Operation
City: Qi b%# ,fle
MI = Per Manufacturer's Instructions
Item
.
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.17
1
Weekly
b Controller selector switch is in
8'2'2 (4)(b) i
x
auto" position.
1.18
!
Week! y
c. Batteries (2) voltage readings are
8.2.2(4)(c)
normal
1.19
I
Weeklyd.
Batteries (2) charging current
8.2.2(4)(d)
•
readings are normal
1.20
I
Weeklye.
Batteries (2) pilot lights are on or
8.2.2(4)(e)
battery failure 2 Ii hts are off.
1.21
I
Weekly
f. All alarm pilot lights are off.
8.2.2(4)(f)
1.22
1
Weekly9-
Engine running time meter is
8.2.2(4)(g)
reading.
1.23
1
Weeklyh.
Oil level in right angle gear drive is
8.2.2(4)(h)
normal.
1.24
I
Weekly
i. Crankcase oil level is normal.
8.2.2(4)(1)
1.25
l
Weekly
j. Cooling water level is normal.
8.2.2(4)0)
1.26
1
Weeklyk.
Electrolyte level in batteries is
8.2.2(4)(k)
normal.
1.27
1
Weekly
1. battery terminals are free from
..
$22(4)(1)
�
corrosion.
1.28
1
Weekly
m. Water jacket heater is operating.
8.2.2(4)(m)
Steam System Conditions:
8.2.2(5)
1.29
!
Weekly
Steam pressure gauge reading is
8.2.2 5
()
normal.
Pump System:
Table 8.5.3(A)
1.30
l
A-0
Wet pit suction screens
Table
Table
5
Electrical System:
Table 8.5.3(C)
1.31
t
Annually
Inspect emergency manual starling
Table
means
8.5.3 C 4
Diesel Engine System:
Table 8.5.3(D)
1.32
I
Weekly
Fuel: Tank Level.
e
Table
1 a
State Fire Marshal AES 5 March 21, 2006
ANNEX B
25..91
Inspection, Testing, and Maintenance Fire Pumps Page 4 of 8
NFPA 25, Chapter 8 as amended by CCR, Title 19
Date of inspection, Testing, Maintenance:
Pump ID:
Description
NFPA 25
Reference
Property Information:
Serial Number: --/"• �,:i •;'y�
Name:�
117 7.2
Address: �- � u � �
Abbreviation Key:,. • ' `- r 1 .
=- '� �
Inspec�on'
`
Fuel: Tank Float Switch
T - Test
M = Maintenance
City: ' r-
A-0 = After Operation
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.33
1
Weekly
Fuel: Tank Float Switch
Table
8.5.3(D)(1)(b)
1.34
1
Weekly
Fuel: Solenoid valve operation
Table
8.5.3(D)(1)(c
1.35
1
Weekly
Fuel: Flexible hoses and connectors
Table
8.5.3(D)(1)(g)
1.36
1
Weekly
Lubrication System: Oil level.
Table
8.5.3(D)(2)(a)
1.37
1
Weekly
Cooling System: Level
Table
8.5.3(D)(3)(a)
1.38
1
Weekly
Cooling System: Adequate cooling water
Table
to heat exchanger.
8.5.3(D) 3 d
1.39
1
Weekly
Cooling System: Water pumps.
Table
8.5.3(D)(3)(
1.40
1
Weekly
Cooling System: Condition of flexible
Table
hoses and connections.
8.5.3(D)(3)(g
1.41
1
Weekly
Cooling System: Jacket water heater
Table
8.5.3(D)(3)(h)
X
1.42
1
Weekly
Battery System: Electrolyte level.
Table
8.5.3(D)(5)(a)
is
1.43
1
Weekly
Exhaust System: Leakage
Table
8.5.3(D)(4)(a)
1.44
1
Weeldy
Electrical System: General inspection
Table
8.5.3(D)(6)(a)
1.45
1
Monthly
Battery System: Charger and charge rage.
Table
8.5.3(D)(5)(e)
1.46
1
Monthly
Battery System: Equalize charge.
Table
8.5.3(D)(5)(f)
1.47
1
Monthly
Electrical System: Circuit breakers or
Table
fuses.
8.5.3(D)(6)(f)
1.48
1
Quarterly
Lubrication System: Crankcase breather
Table
8.5.3(D)(2)(e)
1.49
1
Quarterly
Exhaust System: Insulation and fire
Table
hazards.
8.5.3(D)(4)(c)
1.50
1
Quarterly
Battery System: Terminals dean and tight.
Table
8.5.3(D)(5)(b)
`
1.51
1
Quarterly
Electrical System: Wire chafing where
Table
'
subject to moving.
8.5.3(D)(6)(c)
Cooling System: Antifreeze protection
Table
1.52
1
Semiannually
level
8.5.3(D)(3)(b)
State Fire Marshal AES 5 March 21, 2006
25-92 INSPECTION. TESTING. AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Item
Inspection, Testing, and Maintenance Fine Pumps
NFPA 25, Chapter 8 as amended by CCR, Title 19
Page 5 of 8
Date of Inspection, Testing, Maintenance: 7
p
Pump ID:
Fail
•
Property Informa'�on.
Pass
Serial Number:
l�y� },
r' ; •ice .J L
Name:
Exhaust System: Flexible exhaust
section. I8.5.3(D)(4)(f)_
oa-
'
Add ess: �
r
Abbreviation Key:
I = Inspection
IV
Annually
Fuel: Tank vents and overflow piping is
unobstructed.
T =Test
..�
M = Maintenance
I
Annually
Fuel: Piping.
A-0 = After Operation
City; •,
= SGj�
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Reference
Fail
N/A
Pass
1.53
I
Semiannually
Exhaust System: Flexible exhaust
section. I8.5.3(D)(4)(f)_
Table
1.54
I
Annually
Fuel: Tank vents and overflow piping is
unobstructed.
Table
8.5.3 D 1 h
1.55
I
Annually
Fuel: Piping.
Table
8.5.3 D 1 i
`(
1.56
I
Annually
Cooling System: Inspect ductwork
Table
6.5.3 D 3 i
1.57
I
Annually
Exhaust System: Hangers and supports.
Table
8.5.3 D 4 e
%
FIRE PUMP TESTS
2.1
T
Weekly
Pump Operation — No Flow condition
8.3.1
2.2
T
Monthly
Engine Generator Sets
NFPA 110
7(
2.3
T
Annually
Control Valve —Position
12.3.3.1
X
2.4
T
Annually
Control Valve —Operation
12.3.3.1
2.5
T
Annually
Supervisory
12.3.3.5
x
2.6
T
Annually
Pump Operation —Flow condition
8.3.3.1
2.7
T
5 Year
Pressure Reducing Valve
12.5.1.2
X
2.8
T
Automatic Transfer Switches
NFPA 110
Pump System:
Table 8.5.3(A)
2.9
T
Annually
y
Pump System: Check Pump shaft end
la .
Table
8.5.3(A)(2)
2.10
T
Annually
Pump System: Check accuracy of
pressure gauges and sensors.
Table
8.5.3 A 3
2.11
T
Annually
Pump System Check pump coupling
alignment.
Table
8.5.3 A 4
x
2.12
T
Annually
Pressure Relief Valve
12.5.6.2.2
y(
2.13
T
Annually
Circulation Relief Valve
12.5.6.1.2
�
State Fire Marshal AES 5 March 21, 2006
ANNEX B
25-93
Inspection, Testing, and Maintenance Fire Pumps Page 6 of 8
N F PA 25, Chapter 8 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: S -7
Pump ID: -,
Property Information:
Name:
Serial Number:,t:,�.
'.JI 7 7�
Fail
Abbreviation Key:;-.
Address:`'
�. � t
�....... _-x-
l=Inspection
T = Test '= -
M = Maintenance
A-0 = After Operation
City: ' �� �� C1
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
N/A
Pass
Reference
Electrical System:
Table 8.5.3(C)
2.14
T
Monthly
Electrical System: Exercise isolating
Table
switch and circuit breaker.
8.5.3 C 1
2.15
T
Semiannually
Electrical System: Operate manual
Table
starting means (electrical).
8.5.3 C 3
2.16
T
AnnuallyElectrical
System: Trip circuit breaker
Table
if mechanism provided).
8.5.3(C)(2)
X
Electrical System: Operate emergency
Table
2.17
T
Annually
manual starting means (without
8,5.3 C 4
()()
power).
Diesel Engine System:
Table 8.5.3(D)
2.18
T
Monthly
Battery System: Specific Gravity or
Table
state of charge
8.5.3 D 5 d
2.19
T
Semiannually
Electrical System: Operation of
Table
safeties and alarms.
8.5.3 D 6 d
2.20
T
AnnuallyExhaust
System: Excessive back
Table
pressure
8.5.3 D 4 d
Fire Pump Maintenance (NFPA 25:8.5.1)
3.1
M
Annually
Control valves
12.3.4
Pump System:
Table 8.5.3(A)
3.2
M
Annually
Lubricate pump bearings
Table
e
't )
2C
Mechanical Transmission:
Table 8.5.3(B)
3.3
M
Annually
Lubricate Coupling
Table
8.5.3 B 1
X
3.4
M
Annually
Lubricate right-angle gear drive
Table
8.5.3 B 2
Electrical System:
Table 8.5.3(C)
3.5
M
Annually
Tighten electrical connections
Table
8.5.3 C 5
3.6
M
AnnuallyLubricate
mechanical moving parts
Table
(excluding starters and relays)
i.5.3 C 6
State Fire Marshal AES 5 March 21, 2006
25-94 INSPECTION. TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
Inspection, Testing, and Maintenance Fire Pumps Page 7 of 8
NFPA 25, Chapter 8 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: Z
Pump 1D: 1 �`,
"�."� -��-���
6f- CAf"q
Property Information.
Serial Number:
Name: , z
..SaO-77 a i
Pass
Abbreviation Key:
I=Inspection�,�, -`
Address: ,r
Annually
Calibrate pressure switch settings.
T =Test =`
M = Maintenance
A-0 = After Operation
City:
MI = Per Manufacturer's Instructions
Item
Activity
' '
Frequency
q y
Description
P
NFPA 25
Reference
Fail
N/A
Pass
3.7
M
Annually
Calibrate pressure switch settings.
Table
8.5.3(C)(7)
Table
3.8
M
Annual{ Y
Grease motor bearings
g
8.5.3 C 8
Diesel Engine System:
Table 8.5.3{D}
Table
Table
3.9
M
Weekly
Fuel: Water n system.
i
1
�
Fuel: Strainer, filter, or dirt leg, or
Table
3.1 o
M
Quarterly
combination thereof.
8.5.3 D 1 d
Fuel: Water or foreign material in
Table
3.'t 1
M
p►nnuaH y
tank.
8.5.3 D 1 a
�C
Table8.5.3
3.12
M
Annually
Cooling System: Antifreeze
g Ys
D 3 c
Table
_
Lubrication System.
8.5.3 D 2
Table
TablD
3.13
M
Weekly
Lube oil heater
2 d
Table8.5.3
3.14
M
Quarterly
Crankcase breather
C
D 2 e
3.15
M
Annually/5o
Hours
Oil chan9e
Table
8.5.3 D 2 b
3.16
M
Annually/50
Ho urs
De•l Filter(s) s
Table
8.5.3(D)(2)_(c)
Table
'n System:
Coote g8.5.3
D 3
Table
Table
3.17
M
Quarterly
Water Strainer
3 '
3.18
M
Semiannually
'
Antifreeze protection level.
P
Table
8.5.3 D a b
e
Table
3.19
M
Annually
Rod out heat exchanger.
3 e
Table
3.20
M
Annually
Clean louvers.
8.5.3 D 3 i
Table
System:
Exhaust S y
8.5.3 D 4
Table
3.21
M
Weekly
Drain condensate trap.
8.5.3 D 4 b
•
State Fire Marshal AES 5
March 21, 2006
25-95
Inspection, Testing, and Maintenance Fire Pumps Page 8 of 8
NFPA 25, Chapter 8 as amended by CCR, Title 19
Date of Inspection, Testing, Maintenance: S
Pump ID:
Property rtyInformation:
4,
Serial Number: �-
Name:
f
Slo17 7 a,
. t
Address.I ti
Abbreviation Key.•.
I =Inspection `JAli
(XVexW ZStt. 6A w" t� �A
T = Test
- -
M = Maintenance
A-0 = After Operation
City: ra ,;A
MI = Per Manufacturer's Instructions
Item
Activity
Frequency
Description
NFPA 25
Fail
NIA
Pass
(XVexW ZStt. 6A w" t� �A
Reference
See Continuation Page(s) (Indicate the,. mbe f nti uation pages)
C7 PASS
FA# L - - -- a
Signature D6te
Battery System:
3.22
M
Monthly
Remove corrosion, case exterior clean
Table
and dry.
8.5.3D5c
Electrical System:
Table
8.5.3 D 6
3.23
M
Semiannually
Boxes, panels, and cabinets.
Table
,
%t
8.5.3 D 6 e
3.24
M
Annually
Tighten control and power wiring
Table
connections.
8.5.3 D 6 b
3.25
M
Biannually
Circuit breakers and fuses
Table
8.5.3 D 6
Item
Deficiencies and Comments:
Deficiencies and Comments Item number must correspond to the item number
of the Activity listed above:
A;-A-"kC-a'-nC-J=-A1
0001�O4� �� D ("SS - S
(XVexW ZStt. 6A w" t� �A
See Continuation Page(s) (Indicate the,. mbe f nti uation pages)
C7 PASS
FA# L - - -- a
Signature D6te
State Fire Marshal AES 5 March 21, 2006
.ANNEXB 25-95
Inspection, Testing, and Maintenance Fire Pumps
NFPA 25, Chapter 8 as amended by CCRI Title 19
Date of Inspee ion, Testing, Maintenance: 5
/710 s
Property Information:
Name:
Address:
City: 9 Z�19
f
Pump ID: I
Serial Number.
0 ).,,- S 1z, 17 7 J.,
Page 8 of 8
` P
Abbreviation Key: �-• ; _ .-.
I = Inspection V NriA
T = Test
M = Maintenance
A -Q = After Operation
MI = Per Manufacturer's Instructions.
State Fire Marshal AES 5
March 21, 2006
Description
'
Battery System:
Remove corrosion, case exterior clean
and dry.
Electrical system:
Boxes, panels, and cabinets.
NEPA 25
Fail
NIA
PassReference
Item
Acfivity
Frequency
3.2 2
M
Monthly
Table
8.5.3 D 5 c
Table
8.5.3 D 6
Table
Table
6 e
•x•
3.23
M
Semiannually
Annually
3.24
M
Tighten control and power wiring
connections_
Table
8.5.3 D 6 b
3,25
M
Biannually
Circuit breakers and fuses
e
Table
D 6 )
State Fire Marshal AES 5
March 21, 2006