HomeMy WebLinkAbout031-040-028 CF Archive (2)LACc9 •� �— ,v 2008 Butte County Fire Alarm/Sprinkler Testing Juvenile Hall Report Tested: Fire sprinkler system Fire alarm system including • 6 Pull Stations • 10 Horn/Strobes • 30 Strobes • 36 Fire Dampers • 182 Heat Detectors • 254 Smoke Detectors � 12 Monitoring Tamper/Supervisory Devices During the test 8 Duct detectors were discovered, that have never been tested, or included in the contract. The fire sprinkler pump needs some service. One heat detector was found missing/never installed One smoke detector was un -testable because of location above HVAC ducting. 4 L*C' CzUA-t F--Vtr,. Rot -5Q' Inspection, Testing and Maintenance of Fire Alarm Systems Fire Control,Wilgus Inc. FIRE ALARM DIVISION 1703 Sonoma St Redding, Ca 96001 (530)241-2465 (800)776-3046 Ca. License #462979 C-16, C-10 UL # S24291 Building Name: Address: q City: Postal Code: C� ilk C- qS Date of Service S '7/D6 Time p f1 Z� V Annual Insp do Initial Inspection Last Service Date U 1 1:1 Single Stage Two Stage ite Monitoring? ❑ yes ®no ❑ Manufacturer: • Model # 9�00 ti c Phone: Contact Person: z L Fax: Owner: Phone: Fax: Phone: Central Station: _ "Yes"- Acceptable "No"- Unacceptable (Explain No answers in comments Yes No Summa ® The Fire alarm system is now fully functional without deficiencies. ❑ The Fire alarm system has deficiencies noted on the a es attached. ® ❑ The Fire Alarm System is tested in accordance with NFPA 72 1�c1 �1 Seauence of Operation confirmed and tested. Technicians After -test Checklist Reconnect time limit cutouts? Reconnect ancilln functions? Reconnect ancillary functions off site connections)? Reconnect signal ower? Advise fire department the testin is completed? Ensure that the alarm s stem is functional? Comments Yne a. % z - 4%,ro- 0-A &-r-Lk X 0 -- I state that the information on this form is correct at the time and place of my inspection, and that all equipment was tested in conformance with applicable codes and the Manufacturers requirements and "-OiMe wq*left in operational condition upon completion of this inspection except as noted in comments. 5 0 Ll 30 ,. ,. T&Gician Signature Dae Time I Owner or Authorized Agent 1 of 4 Inspection, Testing and Maintenance of Fire Alarm Systems Date 5 .1 IC) $ Building Name 0-k Yes - Tested correctly "X" No - Did not test correctly (Explain NO answers in comments) SNA" Not applicable Control Unit Tests Annunciator Inspection & Tests Power on visual indicator? Power on indicator? Common visual trouble signal? Individual alarm and supervisory zone indication? Common audible trouble signal? Individual alarm and supervisory zone indication labels? Trouble signal silence switch? Common trouble signal? Main Power supply failure trouble signal? Visual indicator test - Lamp test? Ground fault tested on positive and negative trouble signal Input wiring from control unit is supervised? Alert signal operation? Alarm signal silence visual indicator? Alarm signal operation? Switches for ancillary function operate as intended? Automatic transfer from Alert signal to Alarm signal? Other ancillary function visual indicators? Acknowledge switch operation? Manual activation of alarm signal and indication? Alarm signal silence inhibit? Power Supply Inspection Alarm signal silence operation? Fused with mfgs marked rating of the system? Alarm signal silence visual indication? Adequate to meet the requirements of the system? Alarm signal when silenced automatically reinstate on Remote Trouble Unit Tests and Inspection subsequent alarm? IA"t wiring from control unit is supervised? Alarm signal silence automatic cut-out timer? Visu ouble signal? Input circuit alarm and supervisory operation including _ Audible ble signal? visual indicator? Audible trou signal silence? Input circuit trouble operation? Battery Tests and Inspection Output circuit alarm operation? Battery type Output circuit trouble operation? Battery Voltage Visual indicator test (lamp test)? AC power on Is. Vdc V11 4 Coded signal sequence operate not less than the required AC power on 12 Vdc number of times and the correct alarm signal thereafter. Coded signal sequences are not interrupted by subsequent alarms? Input circuit to output circuit operation including ancilliary device, for correct matrix operation Reset operation? Main power to emergency power supply transfer? tilh Data communications link (DCL) supervision & operation �J p Control unit interconnection to monitoring Station? Control Unit Inspection Input circuit designations, correctly identified in relation to connected field devices Output circuit designations correctly identified in relation to connected field devices. Designations for common control functions & indicators Cabinet, plugin components and modules securely in place Plugin cables securely in place Record date, revision and version of Firmware & software Date: Rev: Ver: Cleanliness? Fuses in accordance with MFGs specification Control Unit lock Termination points from wiring to field devices secure Battery Amp Hours: AC power on a.D, 5 Ah AC power on Ah Inspected for physical damage? Terminal cleaned and lubricated? Terminals clamped tightly? Val_ Correct Electrolyte level? A Specific gravity within mfg specifications? Electrolyte leaks? Adequately ventilated? Within manufacturer's rated life date code? Disconnection causes trouble signal? Generator Power Supply A,Qv,ides power to AC circuit serving the fire alarm? Trou condition at the em gen shall result in an audible common ftkle signal and a visual indication at the required annunc or? 2 of 4 tr Date 5/7/0 Inspection, Testing and Maintenance of Fire Alarm Systems Name 114"Yes - Tested correctly 11X11 No - Did not test correctly (Explain NO answers in comments) "NA" Not applicable Field Devices Field Devices continued Each device is free of damage, foreign substance & Water Flow Detection devices flow mechanically supported independent of wiring? a) tested by appropriate water means Each device tested while connected to control unit? b) time delay recorded Manual Pull stations tested? Two stage pullstations tested and functions confirmed? L _.� Supervisory Devices Shut-off valves tested and result in trouble signal? Heat detectors tested Low pressure supervisory device inspected and tested? Smoke detectors Low water supervisor test? Inspected for cleanliness? Sensitivity tested? tJ A Low temperature supervisor device tested Each power loss (eg fire pump and air compressor) tested? Systems Tested for Operation? Other Fixed Type Extinguishing -- — Remote indicator units inspected and tested? Verify operation of the output contacts initiates the Status change confirmation inspection and tested? specified function at the FA control unit. Air Duct smoke detectors tested? Supervisory Devices Other Types p Beam type smoke detectors for actuation & sensitivity? �-- Inspected and tested as per manufacturer requirements? a Flame detectors inspected and tested? Combination detectors inspected and tested? Signal Appliances Shall be inspected and tested for operability -- �— detectors — other s inspected & tested Automatic de type pe Proper installation and tightness, tampering & obstruction? a) initiation b) deteZt<is oriented so as to detect hazard? 1314 Intelligibility of voice messages? Audibility of alert, alarm and voice messages/ c) sensivity ted? Visual signal appliance inspected and tested? Combination devices tested? Sequential Display Inspection and Testing Individual alarm, supervisory and trouble inputs are clearly indicated and separately designated? Individual alarm and supervisory input designation labels are properly identified? Alarm input overrides supervisory and trouble input? Supervisory input overrides trouble input? Display can be manually advanced? First alarm is clearly identified each time it is displayed Alarm and supervisory input can be retrieved until system is reset? Printer Testing Operde-tion as intended? Zone o h alarm initiating device is correctly printed? Rated voltage ' sent? Printers located in Proprietary Control Centers N" and acknowledgements are automatically printed? Time to is recorded by the printer? Each event is rded as they occur? System records sta anges with loss of data? Paper advances automati ch that print record is visible? Printer operates under loss of main powers 1 ? Printer is monitored for "low paper" and "paper o 91 9 Voice Communication Inspection/Tests ower on indicator? C on visual trouble signal? Co on audible trouble signal? r Trou a signal silence switch? All cal voice paging including visual indicator? output c alts for selective voice paging and visual. Output c' its for selective voice paging trouble/visual Microphon including press to talk switch? Operation o VC systems does interfere with initial inhibit time o lert and alarm signal. All call voice p ing operates on emergency power? Upon failure of a amplifier, system automatically transfers to bac ku amplifier. Circuits for emerge cy telephone call in operation including audible an visual indication Circuits for emergenc telephone for operation, including two way voice comm 'cation? Circuits for emergency t ephones trouble and visual ops. Emergency telephone ve communication? Emergency telephone ope le or in -use tone at handset. Emergency telephone call-in amp? Emergency telephone call-in a dible signal? All telephone zone select switch s individually tested? Individual telephone zone select ' dicators? Operating instruction clearly vis Lockable release mechanism is i Ancillary Device Testing Circuit Circuit Circuit 3 of 4 Inspection, Testing and Maintenance of Fire Alarm Systems FD'ate s) ? ) o 3 Building Name 9, A F-- ra tI &NV U - S t 1 %j P W ,1 e 4 " k k Device Testing — Legend and Notes Device Description T e Model No. M HT Manual Pull station Rq% t• %G • 112L Heat detector non restorable(Note 9 RHT Heat detector, Restorable(Note 9 aftF• s S Smoke detector(Note 1, 2 & 9 RI Remote indicator unit DS Duct smoke detector(Note 1, 3 & 9 PS Photo electric smoke detector = S 355 SFD Supporting Feld device monitor FS Sprinkler flow switch ffote 4 SS Sprinkler supervisory device Note LA -- Low air PS — Pressure switch EM Fault isolation module B Bell H Horn V Visual si al appliance -%Q t HS Born/Strobe SP Cone type speaker HSP Horn type speaker AD Ancillary device(Note 8 ET Emergency Telephone --- Other supervisory devices Notes 6 & --- other type of detector Note 1. Smoke detector sensitivity measurement and cleaning date should be recorded in the remarks column. Note 2. Status change, including time delay, should be recorded in the remarks column. Note 3. Duct smoke detector pressure differential should be confirmed and recorded in the remarks column. Note 4. Time delay setting of water flow switch should be recorded in the remarks column. Note 5. Sprinkler supervisory switches cause trouble condition to be annunciated but not an alarm condition. Note 6. Upper and lower pressure setting of supervisory devices should be recorded in the remarks column. Note 7. Low temperature setting should be recorded in the remarks column. Note 8. Identify the specific ancillary devices in the remarks column. Note 9. Identify date fire detector was changed. Caution: The tests reported on this form do not include the actual operational test of ancillary devices. 4 of 4 VA Butte County Juvenile Hall Fire Alarm Test 5R/2008 Devices Tested •lypeDescription Alarm/Device Notification Booster Panels Alarm Zone Time of Test Device Address ACTIVE SUPERVISORY Address Batte Volts Batte Amps__ Pass YIN 1M049 1M138 13 8.3 Y lectrica I Room 13 5.83 Y JB Pod 13 7 Y PIV TAMPER 13 7 Y D Pod 13 0.64 n 1 M 153 0 0 nmwmwwwwsmm n :/F Pod 13 .�•6 Y Z000 13 7 Y Devices Tested •lypeDescription Alarm/Device Alarm Zone Time of Test Device Address ACTIVE SUPERVISORY SPRINKLER TAMPER Z000 1M049 1M138 ACTIVE SUPERVISORY ACTIVE SUPERVISORY JOCKEY PUMP PUMP OPR ALARM Z000 Z000 10*38A 050708 1 M 151 ACTIVE SUPERVISORY JCKY FLOW SWITCH Z000 10*39A 050708 1 M048 ACTIVE SUPERVISORY PIV TAMPER Z008 11 *02A 050708 1 M003 ACTIVE SUPERVISORY PHASE FAILURE FP Z000 10*45A 050708 1 M 153 ACTIVE TAMPER TWIN GATE VALVE TMPR Z000 11 *04A 050708 1 M002 ACTIVE TAMPER TWIN GATE VALVE TMPR Z000 11 *05A 050708 1 M002 ACTIVE TAMPER TWIN GATE VALVE TMPR Z000 11 *06A 050708 1 M002 ACTIVE TAMPER TWIN GATE VALVE TMPR Z000 11 *06A 050708 1 M002 ALARM: HEAT DETECT E/F TOILET LET STAF F 119 Z001 09*01 A 050908 1 D 129 . ALARM: HEA T DETECT Z001 01 *43P 050908 1 M090 . • T DETECT ALARM. HEA Z001 01 *46P 050908 1 M090 ALARM: HE. AT DETECT 2001 01 *49P 050908 1 M090 • T DETECT ALARM. HEA Z001 01 *52P 050908 1 M090 • T DETECT ALARM. HEA Z001 01 *55P 050908 1 M090 • T DETECT ALARM. HEA Z001 0.1 *55P 050908 1 M090 • DETECT ALARM. HEAT Z001 01 *56P 050908 1M090 • DETECT ALARM. HEAT F102 CLASSROOM Z000 10*47A 050908 1M104 • - DETECT ALARM. HEAT E102 CLASSROOM Z000 09*37A 050908 1M144 • T DETECT ALARM. HEA E102 CLASSROOM Z000 09*41 A 050908 1 M 144 • HEAT DETECT ALARM. KITCHEN J155 Z001 09*41A 050808 2DO34 ALARM: HE. AT DETECT A101 HIGH CLNG HEATS Z000 10*48A 050808 2M115 • T DETECT ALARM. HEA B POD HIGH CEILING Z000 11 *27A 050808 2M158 ALARM: HE. AT DETECT STAFF TOILET/SH J142 Z001 12*47P 050708 1 DO16 • AT DETECT ALARM. HE TOILET -EXAM MED J136 Z001 12*42P 050708 1 D036 ALARM. HEA T DETECT ADMIN BATH ROOM 113 Z000 12*OOP 050708 1 D060 ALARM: HEAT DETECT PUBLIC BATHROOM 103 Z001 12*07P 050708 1 D063 • EAT DETECT ALARM. H TOILET LET INTAKE J 109 Z001 12*24P 050708 1 D087 ALARM: H EAT DETECT F JANITORS CL. F 117 Z001 09*48A 050908 1 D 130 ALARM: HEAT DETECT E JANITORS CL. E117 Z001 08*54A 050908 1 D131 ALARM: HEAT DETECT LAUNDRY J141 Z001 12*44P 050708 1 D 133 ALARM: HEAT DETECT J144 STAFF LOCKERS Z000 10*51 A 050708 1 M010 ALARM: HEAT DETECT J144 STAFF LOCKERS Z000 10*52A 050708 1M010 ALARM: HEAT DETECT J144 STAFF LOCKERS Z000 10*53A 050708 1 M010 ALARM: HEAT DETECT J131 SALLYPORT Z000 08*11 A 050908 1 MO15 ALARM HEAT DETECT J130 MAIN CORRIDOR Z000 03*15P 050808 1MO18 • EAT DETECT ALARM. H J 130 MAIN CORRIDOR DOR Z000 03*18P 050808 1 MO18 ALARM: H. EAT DETECT J130 MAIN CORRIDOR Z000 03*21 P 050808 1 M018 ALARM: HEAT DETECT J130 MAIN CORRIDOR Z000 03*21 P 050808 1 MO18 ALARM: HEAT DETECT J141 LAUNDRY Z000 11*06A 050908 1MO19 ALARM: HEAT DETECT J141 LAUNDRY z000 11*08A 050908 1MO19 ALARM: HEAT DETECT J140 BREAK ROOM z000 11*03A 050908 1M022 ALARM: HEAT DETECT J140 BREAK ROOM z000 11 *09A 050908 1 M022 ALARM: HEAT DETECT F101 LOW CEILING z000 10*50A 050908 1 M032 ALARM: HEAT DETECT F101 LOW CEILING z000 10*50A 050908 1 M032 ALARM: HEAT DETECT F101 LOW CEILING z000 10*51A 050908 1 M032 ALARM: HEAT DETECT E POD HEATS ABOVE z000 11 *25A 050908 1 M035 ALARM: HEAT DETECT E POD HEATS ABOVE z000 11 *26A 050908 1 M035 ALARM: HEAT DETECT E POD HEATS ABOVE z000 11 *29A 050908 1 M035 ALARM: HEAT DETECT E POD HEATS ABOVE z000 11 *30A 050908 1M035 ALARM: HEAT DETECT J132 NURSES FILES FS z001 11 *12A 050908 1 M040 ALARM: HEAT DETECT J132 NURSES FILES FS z001 11 *13A 050908 1 M040 ALARM: HEAT DETECT J132 NURSES FILES FS z001 11 *15A 050908 1 M040 ALARM: HEAT DETECT J132 NURSES FILES FS z001 11*19A 050908 1M040 ALARM: HEAT DETECT J132 NURSES FILES FS z001 11 *19A 050908 1 M040 ALARM: HEAT DETECT E101 HIGH CEILING z000 08*36A 050908 1 M046 ALARM: HEAT DETECT E101 HIGH CEILING z000 08*38A 050908 1 M046 ALARM: HEAT DETECT E101 HIGH CEILING z000 08*40A 050908 1 M046 ALARM: HEAT DETECT E101 HIGH CEILING z000 08*43A 050908 1 M046 ALARM: HEAT DETECT E101 HIGH CEILING z000 08*45A 050908 1 M046 ALARM: HEAT DETECT J107 CLOTHING z000 01 *12P 050908 1 M047 ALARM: HEAT DETECT J107 CLOTHING z000 01*13P 050908 1M047 ALARM: HEAT DETECT J107 CLOTHING z000 01 *14P 050908 1 M047 ALARM: HEAT DETECT J107 CLOTHING z000 12*22P 050708 1 M047 ALARM: HEAT DETECT J105 J106 HOLDING z000 01*06P 050908 1M051 ALARM: HEAT DETECT J105 J106 HOLDING z000 01 *06P 050908 1 M051 ALARM: HEAT DETECT J105 J106 HOLDING z000 01*07P 050908 1M051 ALARM: HEAT DETECT J105 J106 HOLDING z000 01*08P 050908 1M051 ALARM: HEAT DETECT J105 J106 HOLDING z000 01 *08P 050908 1 M051 ALARM: HEAT DETECT J105 J106 HOLDING z000 01 *09P 050908 1 M051 ALARM: HEAT DETECT J105 J106 HOLDING z000 01*09P 050908 1M051 ALARM: HEAT DETECT J105 J106 HOLDING z000 01 *10P 050908 1 M051 ALARM: HEAT DETECT J105 J106 HOLDING z000 12*15P 050708 1M051 ALARM: HEAT DETECT J101 SALLYPORT z000 01 *17P 050908 1 M054 ALARM: HEAT DETECT F101 HIGH CEILING z000 09*09A 050908 1 M056 ALARM: HEAT DETECT F101 HIGH CEILING z000 09*13A 050908 1 M056 ALARM: HEAT DETECT F101 HIGH CEILING z000 09*23A 050908 1 M056 ALARM: HEAT DETECT F101 HIGH CEILING z000 09*24A 050908 1 M056 ALARM: HEAT DETECT J144 STAFF LOCKERS z000 08*13A 050908 1 M058 ALARM: HEAT DETECT J144 STAFF LOCKERS z000 08*13A 050908 1M058 ALARM: HEAT DETECT J144 STAFF LOCKERS z000 08*15A 050908 1 M058 ALARM: HEAT DETECT J144 STAFF LOCKERS z000 08*16A 050908 1 M058 ALARM: HEAT DETECT J123 VISITATION SALY z000 02*06P 050908 1M060 ALARM: HEAT DETECT J123 VISITATION SALY z000 02*07P 050908 1 M060 ALARM: HEAT DETECT z001 01 *43P 050908 1 M090 ALARM: HEAT DETECT z001 01 *44P 050908 1 M090 ALARM: HEAT DETECT z001 01 *45P 050908 1 M090 ALARM: HEAT DETECT z001 01 *45P 050908 1 M090 ALARM: HEAT DETECT z001 01 *57P 050908 1 M090 ALARM: HEAT DETECT z001 01 *58P 050908 1 M090 ALARM: HEAT DETECT z001 01 *59P 050908 1 M090 ALARM: HEAT DETECT z001 02*01 P 050908 1 M090 ALARM: HEAT DETECT z001 02*02P 050908 1 M090 ALARM: HEAT DETECT z001 02*02P 050908 1 M090 ALARM: HEAT DETECT z001 02*03P 050908 1 Mo90 ALARM: HEAT DETECT z001 02*03P 050908 1 M090 ALARM: HEAT DETECT J121 STORAGE z000 02*09P 050908 1 MO92 ALARM: HEAT DETECT J121 STORAGE z000 02*12P 050908 1 M092 LARM: HEAT DETECT J121 STORAGE z000 02*12P 050908 1 M092 LARM: HEAT DETECT J116 VISITING z000 02*08P 050908 1 MO97 LARM: HEAT DETECT J116 VISITING z000 02*09P 050908 1 M097 LARM: HEAT DETECT J116 VISITING z000 02*10P 050908 1 M097 LARM: HEAT DETECT J116 VISITING z000 02*10P 050908 1 M097 LARM: HEAT DETECT J116 VISITING z000 02*11 P 050908 1 M097 LARM: HEAT DETECT J180 CORRIDOR z000 02*47P 050808 1 M 103 LARM: HEAT DETECT J180 CORRIDOR z000 02*48P 050808 1 M103 LARM: HEAT DETECT J180 CORRIDOR z000 02*51 P 050808 1 M103 LARM: HEAT DETECT J180 CORRIDOR z000 02*54P 050808 1M103 ALARM: HEAT DETECT J180 CORRIDOR z000 02*56P 050808 1M103 ALARM: HEAT DETECT J180 CORRIDOR z000 02*58P 050808 1 M 103 ALARM: HEAT DETECT F102 CLASSROOM z000 10*48A 050908 1 M104 ALARM: HEAT DETECT F102 CLASSROOM z000 10*54A 050908 1M104 ALARM: HEAT DETECT F102 CLASSROOM z000 10*55A 050908 1M104 ALARM: HEAT DETECT E101 LOW CEILING z000 08*54A 050908 1 M147 ALARM: HEAT DETECT E101 LOW CEILING z000 08*56A 050908 1 M147 ALARM: HEAT DETECT E101 LOW CEILING z000 08*58A 050908 1 M147 ALARM: HEAT DETECT B JANITORS CL. B117 z001 10*10A 050808 2DO08 ALARM: HEAT DETECT AIB TOILET STAF A119 z001 10*09A 050808 2DO09 ALARM: HEAT DETECT A JANITORS CL. A117 zo01 10*08A 050808 2DO10 ALARM: HEAT DETECT TOILET KITCHEN J158 z001 09*42A 050808 2DO35 ALARM: HEAT DETECT KIT. SALLYPORT J153 z001 09*45A 050808 2DO40 ALARM: HEAT DETECT C JANITORS CL. C117 z001 02*34P 050808 2DO88 ALARM: HEAT DETECT CID TOILET STAF Cl 19 zoo 1 01 *56P 050808 2 DO89 ALARM: HEAT DETECT D JANITORS CL. D117 z001 01 *56P 050808 2DO90 ALARM: HEAT DETECT A102 CLASSROOM z000 11 *11 A 050808 2MO24 ALARM: HEAT DETECT A102 CLASSROOM z000 11 *14A 050808 2MO24 ALARM: HEAT DETECT A102 CLASSROOM z000 11 *15A 050808 2MO24 ALARM: HEAT DETECT A102 CLASSROOM z000 11 *18A 050808 2MO24 ALARM: HEAT DETECT A101 LWR. CEILING z000 11*04A 050808 2MO27 ALARM: HEAT DETECT A101 LWR. CEILING z000 11*05A 050808 2MO27 ALARM: HEAT DETECT BELOW KITCHEN z001 09*39A 050808 2MO31 ALARM: HEAT DETECT BELOW KITCHEN z001 09*40A 050808 2MO31 ALARM: HEAT DETECT BELOW KITCHEN z001 09*40A 050808 2MO31 ALARM: HEAT DETECT ABOVE KITCHEN z000 11 *34A 050908 2MO32 ALARM: HEAT DETECT ABOVE KITCHEN z000 11 *34A 050908 2MO32 ALARM: HEAT DETECT ABOVE KITCHEN z000 11 *35A 050908 2MO32 ALARM: HEAT DETECT ABOVE KITCHEN z000 11 *36A 050908 2MO32 ALARM: HEAT DETECT ABOVE KITCHEN z000 11 *50A 050908 2MO32 ALARM: HEAT DETECT ABOVE KITCHEN z000 11*51A 050908 2MO32 ALARM: HEAT DETECT ABOVE KITCHEN z000 11 *51A 050908 2MO32 ALARM: HEAT DETECT ABOVE KITCHEN z000 11 *52A 050908 2MO32 ALARM: HEAT DETECT ABOVE KITCHEN z000 11 *55A 050908 2MO32 ALARM: HEAT DETECT ABOVE KITCHEN z000 11 *55A 050908 2MO32 ALARM: HEAT DETECT OFFICE KITCHEN z000 11 *43A 050908 2MO33 ALARM: HEAT DETECT OFFICE KITCHEN z000 11 *44A 050908 2MO33 ALARM: HEAT DETECT J160 STORAGE RM z000 11*36A 050908 2MO42 ALARM: HEAT DETECT J160 STORAGE RM z000 11*41A 050908 2MO42 ALARM: HEAT DETECT J160 STORAGE RM z000 11*45A 050908 2MO42 ALARM: HEAT DETECT B102 HEATS ABOVE z000 11*56A 050808 2MO54 ALARM: HEAT DETECT B102 HEATS ABOVE z000 11 *58A 050808 2MO54 ALARM: HEAT DETECT B102 HEATS ABOVE z000 11 *59A 050808 2MO54 ALARM: HEAT DETECT B102 HEATS ABOVE z000 12*01 P 050808 2MO54 ALARM: HEAT DETECT B102 HEATS ABOVE z000 12*01 P 050808 2MO54 ALARM: HEAT DETECT B101 LOW CEILING HEAT z000 01 *23P 050808 2MO56 ALARM: HEAT DETECT B101 LOW CEILING HEAT z000 01 *24P 050808 2MO56 ALARM: HEAT DETECT C101 LOW CEILING z000 02*38P 050808 2MO61 ALARM: HEAT DETECT C101 LOW CEILING z000 02*39P 050808 2MO61 ALARM: HEAT DETECT C101 LOW CEILING z000 02*40P 050808 2MO61 ALARM: HEAT DETECT C102 CLASSROOM z000 08*26A 050908 2MO64 ALARM: HEAT DETECT C102 CLASSROOM z000 08*26A 050908 2MO64 ALARM: HEAT DETECT C102 CLASSROOM z000 08*27A 050908 2MO64 ALARM: HEAT DETECT C102 CLASSROOM z000 08*29A 050908 2MO64 ALARM: HEAT DETECT J170 CORRIDOR z000 03*06P 050808 2MO65 ALARM: HEAT DETECT J170 CORRIDOR z000 03*08P 050808 2MO65 ALARM: HEAT DETECT J171 SALLYPORT z000 03*12P 050808 2MO69 ALARM: HEAT DETECT D102 CLASSROOM z000 01*57P 050808 2M103 ALARM: HEAT DETECT D102 CLASSROOM z000 01*58P 050808 2M103 ALARM: HEAT DETECT D102 CLASSROOM z000 01*59P 050808 2M103 ALARM: HEAT DETECT D102 CLASSROOM z000 02*OOP 050808 2M103 ALARM: HEAT DETECT D101 HEATS ABOVE z000 01 *32P 050808 2M1 14 ALARM: HEAT DETECT D101 HEATS ABOVE z000 01*38P 050808 2M114 ALARM: HEAT DETECT Dl 01 H EATS ABOVE z000 01 *42 P 050808 2M1 14 ALARM: HEAT DETECT D101 HEATS ABOVE z000 01*44P 050808 2M114 ALARM: HEAT DETECT D101 HEATS ABOVE z000 01*47P 050808 2M114 ALARM: HEAT DETECT D101 HEATS ABOVE z000 01*50P 050808 2M114 ALARM: HEAT DETECT A101 HIGH CLNG HEATS z000 10*37A 050808 2M115 ALARM: HEAT DETECT A101 HIGH CLNG HEATS z000 10*40A 050808 2M115 ALARM: HEAT- DETECT A101 HIGH CLNG HEATS z000 10*42A 050808 2M115 ALARM: HEAT DETECT A101 HIGH CLNG HEATS z000 10*47A 050808 2M115 ALARM: HEAT DETECT A101 HIGH CLNG HEATS z000 10*51A 050808 2M115 ALARM: HEAT DETECT C101 HIGH CEILING z000 02*19P 050808 2M147 ALARM: HEAT DETECT C101 HIGH CEILING z000 02*27P 050808 2M147 ALARM: HEAT DETECT C101 HIGH CEILING z000 02*29P 050808 2M147 ALARM: HEAT DETECT C101 HIGH CEILING z000 02*32P 050808 2M147 ALARM: HEAT DETECT B POD HIGH CEILING z000 11*32A 050808 2M158 ALARM: HEAT DETECT B POD HIGH CEILING z000 11*40A 050808 2M158 ALARM: HEAT DETECT B POD HIGH CEILING z000 11*45A 050808 2M158 ALARM: HEAT DETECT B POD HIGH CEILING z000 11*46A 050808 2M158 ALARM: MONITOR D101 LOW CEILING z000 01*52P 050808 2M106 ALARM: MONITOR D101 LOW CEILING z000 01 *54P 050808 2M106 ALARM: MONITOR D101 LOW CEILING z000 01 *55P 050808 2M106 ALARM: PULL STATION J131 SALLYPORT z000 12*49P 050708 1 MO13 ALARM: PULL STATION J131 SALLYPORT z000 12*49P 050708 1 MO13 ALARM: PULL STATION 104 HALL ADMINISTRAT z001 12*06P 050708 1 M070 ALARM: PULL STATION El 18 STAFF STATION z000 08*44A 050908 1 M124 ALARM: PULL STATION Al 18 STAFF STATION z000 10*1OA 050808 2MO13 ALARM: PULL STATION J151 RECEIVING SALLY z000 09*45A 050808 2MO41 ALARM: PULL STATION J 171 SALLY PORT z000 09*56A 050808 2MO72 ALARM: PULL STATION C118 STAFF STATION z000 01 *31 P 050808 2MO93 ALARM: PULL STATION J181 SALLYPORT z000 09*53A 050808 2M113 ALARM: SMOKE(PHOTO) WEST CORRIDOR 5 J130 z001 09*51A 050808 1 DO17 ALARM: SMOKE(PHOTO) WEST CORRIDOR 2 J130 z001 09*50A 050808 1 D020 ALARM: SMOKE(PHOTO) WEST CORRIDOR 3 J130 zo01 09*50A 050808 1 D032 ALARM: SMOKE(PHOTO) SKYLIGHT E-POD E201 z001 08*55A 050908 1 D044 ALARM: SMOKE(PHOTO) MECHANICAL RM. F203 z001 09*58A 050908 1 D062 ALARM: SMOKE(PHOTO) E/F ELECT. RM. F114 z001 09*05A 050908 1D123 ALARM: SMOKE(PHOTO) E/F STORAGE El 14 zo01 09*03A 050908 1 D134 ALARM: SMOKE(PHOTO) E CLASS RM STR E103 zool 09*32A 050908 1 D143 ALARM: SMOKE(PHOTO) CLASSROOM E-POD E102 zo01 09*31A 050908 1 D145 ALARM: SMOKE(PHOTO) E/F 2ND STR. W E216 z001 09*16A 050908 1D153 ALARM: SMOKE(PHOTO) A LOW CEIL. S A101 z001 10*07A 050808 2DO26 ALARM: SMOKE(PHOTO) ROOF DR./STR. E J 152 z001 09*47A 050808 2DO38 ALARM: SMOKE(PHOTO) D-12 SLEEP UNIT D208 z001 01 *38P 050808 2DO65 ALARM: SMOKE(PHOTO) NORTH CORI DOR 1 J170 z001 09*54A 050808 2DO67 LARM: SMOKE(PHOTO) ELECTRICAL RM.W J148 2001 10*56A 050708 1 D007 LARM: SMOKE(PHOTO) ELECTRICAL RM.M J148 2001 10*54A 050708 1 D008 LARM: SMOKE(PHOTO) ELECTRICAL RM.E J148 2001 10"55A 050708 1D009 LARM: SMOKE(PHOTO) STAFF LOCKER RM J144 2001 12"48P 050708 1D011 LARM: SMOKE(PHOTO) STAFF CHANGING J143 2001 12'48P 050708 1D012 LARM: SMOKE(PHOTO) SALLYPORT-STAFF J131 2001 12*48P 050708 1D014 LARM: SMOKE(PHOTO) PROPERTY RM.W J102 2001 12"13P 050708 1D015 LARM: SMOKE(PHOTO) PROPERTY RM.M J102 2001 12"13P 050708 1D018 LARM: SMOKE(PHOTO) PROPERTY RM.E J102 2001 12*12P 050708 1D019 �LARM: SMOKE(PHOTO) BREAK RM. J140 2001 12*43P 050708 1D021 ALARM: SMOKE(PHOTO) E HIGH CEIL. S E201 2001 08"35A 050908 1 D022 ALARM: SMOKE(PHOTO) F HIGH CEIL. N F201 2001 09"06A 050908 1 D023 ALARM: SMOKE(PHOTO) F HIGH CEIL. W F201 2001 09*10A050908 1D024 ALARM: SMOKE(PHOTO) F HIGH CEIL. S F201 2001 09"`15A 050908 1D025 ALARM: SMOKE(PHOTO) EDUCAT. STR. E J139 2001 12''45P 050708 1 D026 ALARM: SMOKE(PHOTO) EpUCAT. STR. W J139 2001 12*46P 050708 1D027 ALARM: SMOKE(PHOTO) TELEPHONE RM. J149 2001 12"01 P 050708 1 D031 ALARM: SMOKE(PHOTO) EXAM RM WAITING J138 2001 12*41 P 050708 1 D033 ALARM: SMOKE(PHOTO) EXAM RM. MED. J137 2001 12"40P 050708 1D034 ALARM: SMOKE(PHOTO) E-16 SLEEP UNIT E211 2001 08"48A 050908 1 D035 ALARM: SMOKE(PHOTO) SOILED UTILITY J135 2000 12*39P 050708 1 D038 ALARM: SMOKE(PHOTO) NURSES FILES J132 2001 12*38P 050708 1D039 ALARM: SMOKE(PHOTO) E-15 SLEEP UNIT E210 2001 08''49A 050908 1 D040 ALARM: SMOKE(PHOTO) CLEAN UTILITY J134 2001 12*39P 050708 1D041 ALARM: SMOKE(PHOTO) E HIGH CEIL. Id E201 2001 08*34A 050908 1 D043 ALARM: SMOKE(PHOTO) E HIGH CEIL. E E201 2001 08"`35A 050908 1 D045 ALARM: SMOKE(PHOTO) WEST CORRIDOR 2 J130 2001 09*50A 050808 1D046 ALARM: SMOKE(PHOTO) E-14 SLEEP UNIT E209 2001 08*49A 050908 1 D047 ALARM: SMOKE(PHOTO) CLOTHING INTAKE J107 2001 12*25P 050708 1 D048 ALARM: SMOKE(PHOTO) HOLDING RM. J106 2001 12"`20P 050708 1D049 ALARM: SMOKE(PHOTO) HOLDING RM. J106 2001 12*22P 050708 1D049 ALARM: SMOKE(PHOTO) HOLDING CELL J105 2001 12"`19P 050708 1 D050 ALARM: SMOKE(PHOTO) SALLYPORT-CAR J101 2001 11"59A 050708 1D052 ALARM: SMOKE(PHOTO) F HIGH CEIL. E F201 2001 09"`25A050908 1D053 ALARM: SMOKE(PHOTO) CORRIDOR ADMIN 112 2001 11*59A 050708 1 D055 ALARM: SMOKE(PHOTO) SKYLIGHT F-POD F201 2001 09*27A 050908 1 D057 ALARM: SMOKE(PHOTO) HOLDING WEST #2 J112 2001 12"11 P 050708 1 D058 ALARM: SMOKE(PHOTO) HOLDING EAST #1 J111 2001 12*11 P 050708 1 D059 ALARM: SMOKE(PHOTO) MECHANICAL RM. F203 2001 09*58A 050908 1 D062 ALARM: SMOKE(PHOTO) F-16 SLEEP UNIT F204 2001 09*57A 050908 1 D064 ALARM: SMOKE(PHOTO) SALLYPORT VISIT J123 2001 12*08P 050708 1 D065 ALARM: SMOKE(PHOTO) F-15 SLEEP UNIT F205 2001 09*57A 050908 1 D066 ALARM: SMOKE(PHOTO) E HIGH CEIL. W E201 2001 08"`35A 050908 1 D067 ALARM: SMOKE(PHOTO) LOBBY N 100 2001 12*07P 050708 1 D068 ALARM: SMOKE(PHOTO) HALL-FRONT ADMIN 104 2001 12"03P 050708 1D069 ALARM: SMOKE(PHOTO) ELECTRICAL ADMIN 115 2001 12"09P 050708 1 D071 ALARM: SMOKE(PHOTO) CLERICAL N 108 2001 12"01 P 050708 1 D072 ALARM: SMOKE(PHOTO) CLERICALS 108 2001 12*01 P 050708 1 D073 ALARM: SMOKE(PHOTO) SUPERVISOR NORTH 111 2001 12"03P 050708 1 D074 ALARM: SMOKE(PHOTO) SUPERVISOR SOUTH 110 2001 12'02P 050708 1 D075 ALARM: SMOKE(PHOTO) SUPERINTENDANT 109 2001 12*02P 050708 1D076 ALARM: SMOKE(PHOTO) BREAK RM.ADMIN 107 2001 12"03P 050708 1D077 ALARM: SMOKE(PHOTO) CONFERENCE ADMIN 106 2001 12*05P 050708 1D078 ALARM: SMOKE(PHOTO) RECEPTION ADMIN 105 2001 12*05P 050708 1D079 ALARM: SMOKE(PHOTO) LOBBY S 100 2001 12*06P 050708 1 D081 ALARM: SMOKE(PHOTO) RECORDS ADMIN 116 2001 12*05P 050708 1D082 ALARM: SMOKE(PHOTO) NO-CONTACT V. S J125 2001 12*28P 050708 1D083 ALARM: SMOKE(PHOTO) NO-CONTACT V. N J116 2001 12"27P 050708 1D084 ALARM: SMOKE(PHOTO) INTEVIEW INTAKE J110 2001 12*21 P 050708 1 D086 ALARM: SMOKE(PHOTO) INTAKE W J104 2001 12*14P 050708 1 D090 ALARM: SMOKE(PHOTO) INTAKE W J104 2001 12*20P 050708 1 D090 ALARM: SMOKE(PHOTO) WEST CORRIDOR 1 J 130 2001 09*52A 050808 1 D091 ALARM: SMOKE(PHOTO) VISITING OBSERV.J122 2001 12*29P 050708 1 D093 ALARM: SMOKE(PHOTO) VISIT UTIL STR J121 2001 12*31 P 050708 1 D094 ALARM: SMOKE(PHOTO) VISIT.CONTACT S J120- 2001 12*29P 050708 1 D095 ALARM: SMOKE(PHOTO) VISIT.CONTACT N J120 2001 12*28P 050708 1 D096 ALARM: SMOKE(PHOTO) C.C. BATHROOM J118 2001 12*33P 050708 1 D098 ALARM: SMOKE(PHOTO) CENTRAL CONTROL J117 2001 12*33P 050708 1 D099 ALARM: SMOKE(PHOTO) EAST CORRIDOR 2 J180 2001 09*52A 050808 1 D100 ALARM: SMOKE(PHOTO) EAST CORRIDOR 1 J180 2001 09*57A 050808 1 D101 ALARM: SMOKE(PHOTO) EAST SALLYPORT J 181 2001 09*53A 050808 1 D 102 ALARM: SMOKE(PHOTO) EAST SALLYPORT J 181 2001 09*55A 050808 113102 ALARM: SMOKE(PHOTO) E-10 SLEEP UNIT E205 2001 08*52A 050908 113103 ALARM: SMOKE(PHOTO) E-11 S. U. DAL. E206 2001 08*51 A 050908 1 D104 ALARM: SMOKE(PHOTO) CLASSROOM F-POD F102 2001 10*47A 050908 1D105 ALARM: SMOKE(PHOTO) F LOW CEIL. N F101 2001 09*50A 050908 113106 ALARM: SMOKE(PHOTO) F LOW CEIL. S F101 2001 09*49A 050908 113107 ALARM: SMOKE(PHOTO) E-12 S.U. DBL. E207 2001 08*50A 050908 1 D108 ALARM: SMOKE(PHOTO) EAST CORRIDOR 3 J180 2001 09*52A 050808 11)109 ALARM: SMOKE(PHOTO) EAST CORRIDOR 4 J180 2001 09*52A 050808 11)110 ALARM: SMOKE(PHOTO) EAST CORRIDOR 5 J180 2001 09*53A 050808 1 D111 ALARM: SMOKE(PHOTO) E-13 SLEEP UNIT E208 2001 08*50A 050908 1 D113 ALARM: SMOKE(PHOTO) CLASS STR. F J103 2001 10*46A 050908 1 D114 ALARM: SMOKE(PHOTO) F-08 SLEEP UNIT F104 2001 09*53A 050908 11)115 ALARM: SMOKE(PHOTO) F-07 SLEEP UNIT F105 2001 09*52A 050908 1 D116 ALARM: SMOKE(PHOTO) F-06 S.U.DBL/HC F106 2001 09*52A 050908 11)117 ALARM: SMOKE(PHOTO) F-05 S.U. DBL. F107 2001 09*52A 050908 1 D118 ALARM: SMOKE(PHOTO) F-04 SLEEP UNIT F108 2001 09*52A 050908 1D`119 ALARM: SMOKE(PHOTO) F-03 SLEEP UNIT F109 2001 09*51A 050908 11)120 ALARM: SMOKE(PHOTO) F-02 SLEEP UNIT F110 2001 09*51A 050908 1 D121 ALARM: SMOKE(PHOTO) F-01 SLEEP UNIT F111 2001 09*51A 050908 11)122 ALARM: SMOKE(PHOTO) C.C. SALLYPORT J115 2001 12*26P 050708 1D124 ALARM: SMOKE(PHOTO) E/F SALLYPORT E115 2001 09*04A 050908 1 D127 ALARM: SMOKE(PHOTO) F INTERVEW RM F116 2001 09*49A 050908 11)128 ALARM: SMOKE(PHOTO) E/F STAFF AREA E118 2001 09*01A 050908 113132 ALARM: SMOKE(PHOTO) E-08 SLEEP UNIT E111 2001 08*45A 050908 1D135 ALARM: SMOKE(PHOTO) E-07 SLEEP UNIT E110 2001 08*45A 050908 1 D136 ALARM: SMOKE(PHOTO) E-06 SLEEP UNIT E109 2001 08*46A 050908 11)137 ALARM: SMOKE(PHOTO) E-05 SLEEP UNIT E108 2001 08*46A 050908 1D138 ALARM: SMOKE(PHOTO) E-04 S.U. DBL. E107 2001 08*47A 050908 11)139 ALARM: SMOKE(PHOTO) E-03 S.U.DBL/HC E106 2001 08*47A 050908 1 D140 ALARM: SMOKE(PHOTO) E-02 SLEEP UNIT E105 2001 08*47A 050908 113141 ALARM: SMOKE(PHOTO) E-01 SLEEP UNIT E104 2001 08*48A 050908 1 D142 ALARM: SMOKE(PHOTO) E-09 SLEEP UNIT E204 2001 08*53A 050908 1 D144 ALARM: SMOKE(PHOTO) E LOW CEIL. N E101 2001 08*34A 050908 1 D146 ALARM: SMOKE(PHOTO) E LOW CEIL. S E101 2001 08*34A 050908 1 D147 ALARM: SMOKE(PHOTO) E INTERVIEW RM E116 2001 08*37A 050908 113149 ALARM: SMOKE(PHOTO) E/F LOW VOLTAGE E215 2001 09*17A 050908 113150 ALARM: SMOKE(PHOTO) E/F 2ND FL.PASS E214 2001 09*18A 050908 1 D151 ALARM: SMOKE(PHOTO) E/F 2ND STR. E E216 2001 09*18A 050908 11)152 ALARM: SMOKE(PHOTO) F-09 SLEEP UNIT F211 2001 09*54A 050908 11)154 ALARM: SMOKE(PHOTO) F-10 SLEEP UNIT F210 2001 09*55A 050908 113155 ALARM: SMOKE(PHOTO) F-11 SLEEP UNIT F209 2001 09*55A 050908 113156 ALARM: SMOKE(PHOTO) F-12 SLEEP UNIT F208 2001 09*56A 050908 113157 ALARM: SMOKE(PHOTO) F-13 S.U. DBL. E207 2001 09*55A 050908 11)158 ALARM: SMOKE(PHOTO) F-14 S.U. DBL. F206 2001 09*56A 050908 11)159 LARM: SMOKE(PHOTO) A/6 STORAGE 6114 2001 10*31A 050808 2D003 LARM: SMOKE(PHOTO) A/B ELECTRICAL A114 2001 10*25A 050808 2D004 LARM: SMOKE(PHOTO) A INTERVIEW RM A116 2001 10"11A 050808 2D006 LARM: SMOKE(PHOTO) B INTERVIEW RM 6116 2001 11*23A 050808 2D007 LARM: SMOKE(PHOTO) AIB STAFF ROOM A118 2001 10*10A 050808 2D011 LARM: SMOKE(PHOTO) SKYLIGHT D-POD D201 2001 01*34P 050808 2D012 LARM: SMOKE(PHOTO) A-08 SLEEP UNIT A111 2001 10"12A 050808 2D014 LARM: SMOKE(PHOTO) A-07 SLEEP UNIT A110 2001 10*13A 050808 2D015 LARM: SMOKE(PHOTO) A-06 SLEEP UNIT A109 2001 10"13A 050808 2D016 LARM: SMOKE(PHOTO) A-05 SLEEP UNIT A108 2001 10'`14A 050808 2D017 LARM: SMOKE(PHOTO) A-04 S.U. DBL A107 2001 10*16A 050808 2D018 LARM: SMOKE(PHOTO) A-03 S.U.DBUHC A106 2001 10"15A 050808 2D019 ALARM: SMOKE(PHOTO) A-02 SLEEP UNIT A105 2001 10*14A 050808 2D020 ALARM: SMOKE(PHOTO) A-01 SLEEP UNIT A104 2001 10*15A 050808 2D021 ALARM: SMOKE(PHOTO) A CLASS RM STR A103 2001 10"08A 050808 2D022 ALARM: SMOKE(PHOTO) CLASSROOM A-POD A102 2001 10*09A 050808 2D025 ALARM: SMOKE(PHOTO) D HIGH CEIL. N D201 2001 01'36P 050808 2D031 ALARM: SMOKE(PHOTO) D HIGH CEIL. E D201 2001 01"30P 050808 2D032 ALARM: SMOKE(PHOTO) KITHEN OFFICE J161 2001 09*44A 050808 2D033 ALARM: SMOKE(PHOTO) KITCHEN STR. N J160 2001 09*42A 050808 2D037 ALARM: SMOKE(PHOTO) ROOF DR./STR. W J152 2001 09'`46A 050808 2D039 ALARM: SMOKE(PHOTO) D HIGH CEIL. S D201 2001 01*49P 050808 2D042 ALARM: SMOKE(PHOTO) KITCHEN STR. S J160 2001 09"`44A 050808 2D043 ALARM: SMOKE(PHOTO) B-01 SLEEP UNIT 6111 2001 11"24A 050808 2D044 ALARM: SMOKE(PHOTO) B-02 SLEEP UNIT 6110 2001 11*24A 050808 2D045 ALARM: SMOKE(PHOTO) B-03 SLEEP UNIT 8109 2001 11"25A 050808 2D046 ALARM: SMOKE(PHOTO) B-04 SLEEP UNIT 6108 2001 11 *25A 050808 2D047 ALARM: SMOKE(PHOTO) B-05 S.U. DBL 6107 2001 11*25A 050808 2D048 ALARM: SMOKE(PHOTO) B-05 S.U. DBL 6107 2001 11'`27A 050808 2D048 ALARM: SMOKE(PHOTO) B-06 S.U.DBUHC 6106 2001 11"'26A 050808 2D049 ALARM: SMOKE(PHOTO) B-07 SLEEP UNIT 6105 2001 11 *26A 050808 2D050 ALARM: SMOKE(PHOTO) B-08 SLEEP UNIT 6104 2001 11*26A 050808 2D051 ALARM: SMOKE(PHOTO) CLASS STR. B 6103 2001 11 *53A 050808 2D052 ALARM: SMOKE(PHOTO) CLASSROOM B-POD 8102 2001 11*47A 050808 2D053 ALARM: SMOKE(PHOTO) BLOW CEIL. N 6101 2001 11*48A 050808 2D055 ALARM: SMOKE(PHOTO) . BLOW CEIL. S 6101 2001 11*47A 050808 2D057 ALARM: SMOKE(PHOTO) D-09 SLEEP UNIT D211 2001 01"36P 050808 2D059 ALARM: SMOKE(PHOTO) CLOW CEIL. S C101 2001 02*14P 050808 2D060 ALARM: SMOKE(PHOTO) D-10 SLEEP UNIT D210 2001 01"37P 050808 2D061 ALARM: SMOKE(PHOTO) CLOW CEIL. N C101 2001 02*24P 050808 2D062 ALARM: SMOKE(PHOTO) CLASSROOM C-POD C102 2001 08*24A 050908 2D063 ALARM: SMOKE(PHOTO) D-11 SLEEP UNIT D209 2001 01 "37P 050808 2D064 ALARM: SMOKE(PHOTO) D-12 SLEEP UNIT D208 2001 01*39P 050808 2D065 ALARM: SMOKE(PHOTO) NORTH CORIDOR 1 J170 2001 09*57A 050808 2D067 ALARM: SMOKE(PHOTO) CLASS RM.STR. C C103 2001 08"24A 050908 2D068 ALARM: SMOKE(PHOTO) D-14 S.U. DBL D206 2001 01*39P 050808 2D069 ALARM: SMOKE(PHOTO) D-15 SLEEP UNIT D205 2001 01"39P 050808 2D071 ALARM: SMOKE(PHOTO) C-01 SLEEP UNIT C104 2001 02*22P 050808 2D072 ALARM: SMOKE(PHOTO) C-02 SLEEP UNIT C105 2001 02*20P 050808 2D073 ALARM: SMOKE(PHOTO) C-03 S.U.DBL/HC C106 2001 02*19P 050808 2D074 ALARM: SMOKE(PHOTO) C-04 S.U. DBL C107 2001 02"19P 050808 2D075 ALARM: SMOKE(PHOTO) C-05 SLEEP UNIT C108 2001 02'`19P 050808 2D076 ALARM: SMOKE(PHOTO) C-06 SLEEP UNIT C109 2001 02"18P 050808 2D077 ALARM: SMOKE(PHOTO) C-07 SLEEP UNIT C110 2001 02'18P 050808 2D078 ALARM: SMOKE(PHOTO) C-08 SLEEP UNIT C111 2001 02`18P 050808 2D079 ALARM: SMOKE(PHOTO) D-16 SLEEP UNIT D204 2001 01*40P 050808 2D080 ALARM: SMOKE(PHOTO) C/D 2ND MECH RM D203 2001 01*41P 050808 2D081 ALARM: SMOKE(PHOTO) C/D ELECT. RM. C114 2001 02*13P 050808 2D083 ALARM: SMOKE(PHOTO) C/D STORAGE D114 2001 01"32P 050808 2D084 ALARM: SMOKE(PHOTO) D INTERVIEW RM. D116 2001 01*31P 050808 2D086 ALARM: SMOKE(PHOTO) D INTERVIEW RM. D116 2001 01*36P 050808 2D086 ALARM: SMOKE(PHOTO) C INTERVIEW RM. C116 2001 02'12P 050808 2D087 ALARM: SMOKE(PHOTO) C/D STAFF AREA C118 2001 01"`31P 050808 2D091 ALARM: SMOKE(PHOTO) D HIGH CEIL. W D201 2001 01'`41 P 050808 2D092 ALARM: SMOKE(PHOTO) D-01 SLEEP UNIT D111 2001 01"33P 050808 2D094 ALARM: SMOKE(PHOTO) D-02 SLEEP UNIT D110 2001 01*34P 050808 2D095 ALARM: SMOKE(PHOTO) D-03 SLEEP UNIT D109 2001 01*34P 050808 2D096 ALARM: SMOKE(PHOTO) D-04 SLEEP UNIT D108 2001 01"34P 050808 2D097 ALARM: SMOKE(PHOTO) D-05 S.U. DBL. D107 2001 01"34P 050808 2D098 ALARM: SMOKE(PHOTO) D-07 SLEEP UNIT D105 2001 01*35P 050808 2D100 ALARM: SMOKE(PHOTO) D-08 SLEEP UNIT D104 2001 01*37P 050808 2D101 ALARM: SMOKE(PHOTO) D CLASS RM STR D103 2001 01*43P 050808 2D102 ALARM: SMOKE(PHOTO) CLASSROOM D -POD D102 2001 01*45P 050808 2D104 ALARM: SMOKE(PHOTO) D LOW CEIL. S D101 2001 01*30P 050808 213107 ALARM: SMOKE(PHOTO) SKYLIGHT C -POD C201 2001 02*24P 050808 2D108 ALARM: SMOKE(PHOTO) SKYLIGHT C -POD C201 2001 02'''25P 050808 2D108 ALARM: SMOKE(PHOTO) C HIGH CEIL. N C201 2001 02*24P 050808 2D109 ALARM: SMOKE(PHOTO) A/B LOW VOLTAGE A215 2001 10"23A 050808 2D110 ALARM: SMOKE(PHOTO) A/B 2ND FL.PASS A214 2000 10*24A 050808 21)111 ALARM: SMOKE(PHOTO) A/B 2ND STR. E A216 2001 10*25A 050808 2D112 ALARM: SMOKE(PHOTO) A/B 2ND STR. W A216 2001 10"24A 050808 2D113 ALARM: SMOKE(PHOTO) A HIGH CEIL. E A201 2001 10"45A 050808 2D114 ALARM: SMOKE(PHOTO) SKYLIGHT A -POD A201 2001 10*44A 050808 213115 ALARM: SMOKE(PHOTO) A HIGH CEIL. S A201 2001 10"`39A 050808 2D116 ALARM: SMOKE(PHOTO) A HIGH CEIL. W A201 2001 10*35A 050808 2D117 ALARM: SMOKE(PHOTO) A-16 SLEEP UNIT A211 2001 10*17A 050808 213118 ALARM: SMOKE(PHOTO) A-15 SLEEP UNIT A210 2001 10*21A 050808 2D119 ALARM: SMOKE(PHOTO) A-14 SLEEP UNIT A209 2001 10'"`21A 050808 2D120 ALARM: SMOKE(PHOTO) A-13 SLEEP UNIT A208 2001 10"21A 050808 2D121 ALARM: SMOKE(PHOTO) A-12 S.U. DBL. A207 2001 10*20A 050808 2D122 ALARM: SMOKE(PHOTO) A-11 S.U. DBL. A206 2001 10"20A 050808 2D123 ALARM: SMOKE(PHOTO) A-10 SLEEP UNIT A205 2001 10*20A 050808 2D124 ALARM: SMOKE(PHOTO) A-09 SLEEP UNIT A204 2001 10"19A 050808 2D125 ALARM: SMOKE(PHOTO) A HIGH CEIL. N A201 2001 10*41A 050808 2D127 ALARM: SMOKE(PHOTO) B HIGH CEIL. W 6201 2001 11*42A050808 213128 ALARM: SMOKE(PHOTO) B HIGH CEIL. S 8201 2001 11*38A 050808 2D129 ALARM: SMOKE(PHOTO) B HIGH CEIL. E 6201 2001 11"`23A 050808 2D130 ALARM: SMOKE(PHOTO) SKYLIGHTS -POD 6201 2001 11"35A050808 2D131 ALARM: SMOKE(PHOTO) B-09 SLEEP UNIT 8211 2001 11*30A 050808 2D132 ALARM: SMOKE(PHOTO) 6-10 SLEEP UNIT 6210 2001 11*31A 050808 2D133 ALARM: SMOKE(PHOTO) B-11 SLEEP UNIT 6209 2001 11*30A 050808 2D134 ALARM: SMOKE(PHOTO) B-12 SLEEP UNIT 8208 2001 11*31A 050808 2D135 ALARM: SMOKE(PHOTO) B-13 S.U. DBL. 8207 2001 11*32A 050808 2D136 ALARM: SMOKE(PHOTO) B-14 S.U. DBL. 6206 2001 11*33A 050808 2D137 ALARM: SMOKE(PHOTO) B-15 SLEEP UNIT 6205 2001 11`'33A 050808 213138 ALARM: SMOKE(PHOTO) B-16 SLEEP UNIT 8204 2001 11=34A 050808 2D139 ALARM: SMOKE(PHOTO) B HIGH CEIL. N 6201 2001 11*30A050808 2D141 ALARM: SMOKE(PHOTO) C/D LOW VOLT RM C216 2001 02"31P 050808 2D142 ALARM: SMOKE(PHOTO) C/D 2ND FL.PASS C214 2001 02*30P 050808 2D143 ALARM: SMOKE(PHOTO) C/D 2ND STR. W C215 2001 02*31 P 050808 2D144 ALARM: SMOKE(PHOTO) C/D 2ND STR. E C215 2001 02"34P 050808 2D145 ALARM: SMOKE(PHOTO) C HIGH CEIL. E C201 2001 02*06P 050808 213146 ALARM: SMOKE(PHOTO) SALLYPORT NORTH J171 2001 09*54A 050808 213147 ALARM: SMOKE(PHOTO) C HIGH CEIL. S C201 2001 02""23P 050808 2D148 ALARM: SMOKE(PHOTO) C HIGH CEIL. W C201 2001 02*23P 050808 2D149 ALARM: SMOKE(PHOTO) C-16 SLEEP UNIT C211 2001 02'25P 050808 213150 LARM: SMOKE(PHOTO) C-15 SLEEP UNIT C210 2001 02*25P 050808 2D151 LARM: SMOKE(PHOTO) C-14 SLEEP UNIT C209 2001 02*25P 050808 2D152 LARM: SMOKE(PHOTO) C-13 SLEEP UNIT C208 2001 02*26P 050808 2D153 LARM: SMOKE(PHOTO) C-12 S.U. DBL. C207 2001 02*27P 050808 2D154 LARM: SMOKE(PHOTO) C-11 S. U. DBL. C206 2001 02*27P 050808 2D155 ,LARM: SMOKE(PHOTO) C-10 SLEEP UNIT C205 2001 02*28P 050808 2D156 ,LARM: SMOKE(PHOTO) C-09 SLEEP UNIT C204 2001 02*28P 050808 2D157 ,LARM: SMOKE(PHOTO) C MECHANICAL RM C203 2001 02*29P 050808 21)158 ,LARM: WATERFLOW MAIN BUILDING 2000 10*42A 050708 1 MO'12 ROUBL MONITOR E F POD BOOSTER TRBL OPEN 09*1 OA 050908 1 M136 25-78 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS Inspection, Testing, and Maintenance Cover Sheet NEPA 25 as amended by CCR, Title 19 Property Information: NIA, FAIL* ___. M0J��� Name. �t � Occupancy/Use: /Use: 7 panc Y hof CAi� o Address: r' Construction Type: C• % «.�i. X ❑ Standpipe and Hose Systems 6 Cit : %-.'r . t �` a Y No. Stories: ,,.�,..,, �4E Mp ZIP: a 59 V; Year Constructed: 7 Contact: y( Telephone: [A Fire Pump 8 Contractor Information: ,_,1_.._ Number of System Risers Name: Wilgus Fire Control, Inc. O Water Storage Tank Copy sent to: Address: 1703 Sonoma St 1( ❑ Owner Date City: Rem ❑Water Spray System ❑ Fire AHJ Date State: California ❑ Contractor Date Telephone: (530)241-2465 ❑Foam Water Sprinkler System NOTES: � 1 ) For specific inspection, testing, and CA License# 462979 C-16 C-10 C-7 maintenance requirements and information, see NFPA 25, 2002 Edition as amended by Job # California Code of Regulations, Title 19, §901 Performed b : � Perf to §90fi. Y .�1w+Q�� (Print) 2) Inspection Item y performed y the s rna be b Owner in accordance with California Code of Note: Contractor information may be pre-printed Regulations Title 19 904.1 a Forms included with this report NFPA 25 Chapter Number of Forms NIA, FAIL* PASS ;q Automatic Sprinkler System 5 � X ❑ Standpipe and Hose Systems 6 ❑ Private Water Supply System 7 y( [A Fire Pump 8 O Water Storage Tank 9 1( ❑Water Spray System 10 ❑Foam Water Sprinkler System 11 � *See "Deficiencies and Comments" section at end of each respective form. State Fire Marshal AES 1 March 21, 2006 e ANNEX B 25-79 Inspection, Testing, and Maintenance Fire Sprinkler System Page 1 of 4 NFPA 25, Cha ter 5 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance:System Riser ID: f fell WL -0 I Property Information: Type of System: oF CA��� Name: Wet Pipe D D Pie `a a L11 _ Dry p Address. t D Preaction �► ,,� 0 Deluge`. Baa City: Main Drain Test Results: Abbreviation Key: I = Inspection Initial Static Pressure: 110 (psi) T = Test M = Maintenance Residual Pressure: S�S (psi) A-0 = After Operation t MI = Per Manufacturer's Instructions 1 i) Restored Static Pressure:(Ps Item Activity =Freque=ncyDescription NFPA 25 Reference Fail NIA Pass 1.1 1 Daily Preaction/Deluge Valves — Enclosure 12.4.3.1 Week) temperature 1.2 1 Daily Dry Pipe Valves — Enclosure 12.4.4.1.1 Week) temperature 1.3 I Quarter! y Gauges (Dry, Preaction, Deluge 5.2.4.2 Systems) 5.2.4.3 1.4 I Quarterly Control Valves 12.3.2.1 1.5 I Quarterly Alarm Devices 5.2.6 1.6 ! Quarterly Gauges (Wet Pipe Systems) 5.2.4.1 1.7 ! Quarterly Hydraulic nameplate 5.2.7 1.8 I Quarterly Pipe and Fittings 5.2.2' 1.9 I Quarterly Sprinklers 5.2.1 'X 1.10 1 Quarterly Spare Sprinklers 5.2.1.3 1.11 I Quarterly Fire Department Connections 12.7.1 1.12 I Quarterly Alarm Valves — Exterior Inspection 12.4.1.1 X 1.13 I Quarter) Quarterly Preaction/D6uge Valves --Exterior 12.4.3.1.6 X Ins ection 1.14 I Quarterly Pressure Reducing Valves 12.5.1.1 1.15 I Quarterly Dry Pipe Valves — Exterior Inspection 12.4.4.1.4 ` 1.16 I Quarterly Backflow Preventers 12.6.1 1.17 I Annually Buildings 5.2.5 State Fire Marshal AES 2 March 21, 2006 25-80 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PR0TFC`.TT0N �V4TF.MR Inspection, Testing, and Maintenance Fire Sprinkler System Page 2 of 4 NEPA 25, Chapter 5 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: _ System Riser ID: i Property Information: NEPA 25 Reference Fail Type of System: oT CA Name: CK Wet Pipe Address: ❑ Dry Pipe � Hangers ❑Preaction 9 ❑ Deluge ARE N1 City:c 1.19 Item Activity Frequency Description NEPA 25 Reference Fail N/A Pass 1.18 1 Annually Hangers 5.2.3 1.19 1 Annually Seismic Braces 5.2.3 1.20 1 5 Years Hangers (Accessible concealed spaces) 5.2.3.3 1.21 1 5 Years Seismic Braces (Accessible concealed spaces) 5.2.3.3 X 1.22 1 5 Years Pipe and Fittings (Accessible concealed spaces) 5.2.2.3 1.23 1 5 Years Sprinklers (Accessible concealed spaces) 5.2.1.1.4 1.24 1 5 Years Alarm Valves — Interior Inspection 12.4.1.2 1.25 1 5 Years Alarm Valves - Strainers, filters, orifices 12.4.1.2 1.26 1 5 Years Check Valves — Interior Inspection 12.4.2.1 •y� 1.27 I 5 Years PreactioniDeluge Valves — Interior Ins cfion 12.4.3.1.7 1.28 1 5 Years Preaction/Deluge Valves - Strainers, filters orifices 12.4.3.1.8 1.29 1 5 Years Dry Pipe Valves — Interior Inspecfion 12.4.4.1.5 1.30 1 5 Years Dry Pipe Valves - Strainers, filters, orifices 12.4.4.1.6 2.1 T Annually Alarm Devices (90 Sec) 5.3.3 12.2.7 X 2.2 T Annually Main Drain Test (Enter data on Page 1) 12.2.6 12.2.6.1 12.3.3.4 2.3 T Annually Antifreeze Test 5.3.4 2.4 T Annually Control Valve - Position -12.3.3.1 2.5 T Annually Control Valve — Operation 12.3.3.1 2.6 T Annually Supervisory 12.3.3.5 2.7 T Annually Preaction Valve — Priming Water 12.4.3.2.1 .� 2.8 T Annually Preaction Valve — Low Air Pressure Alarm 12.4.3.2.10 2.9 T Annually Preaction Valve — Full Flow Trip Test 12.4.3.2.2 State Fire Marshal AES 2 . March 21, 2006 ANNEX B 25-81 Inspection, Testing, and Maintenance Fire Sprinkler System Page 3 of 4 NFPA 25, Cha ter 5 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: 5/7108 System Riser ID: Property Information: System: ca��� Fail Type of tioF Name: 4' ®Wet Pipe ,��� � T ❑ Dry Pipe Address: ❑ Preaction ❑ Deluge E MP► City: Dtoo--Ae- ..� 9 s3k 5 2.11 em E ActivityFrequency q y Description NFPA 25 Reference Fail NIA Pass 2.10 T Annually Dry Pipe Valve — Priming Water 12.4.4.2.1 2.11 T Annually Dry Pipe Valve — Low Air Pressure Alarm 12.4.4.2.6 2.12 T Annually Dry Pipe Valve — Quick -Opening Device 12.4.4.2.4 �. 2.13 T Annually Dry Pipe Valve — Trip Test 12.4.4.2.2 2.14 T Annually Backflow Preventer Assemblies 12.6.2 2.15 T 3 Years Dry Pipe Valve — Full Flow Trip Test 12.4.4.2.2.2 2.16 T 5 Years Gauges 5.3.2 2.17 T 5 Years Pressure Reducing Valve 12.5.1.2 2.18 T 5 Years Fire Department Connection Backflush 12.7.4 2.19 T 5 Years Sprinklers — Extra High Temperature 5.3.1.1.1.3 .� 2.20 T 5 Years Sprinklers — Corrosive environment or corrosive water .... 5112 3 � 2.21 T 10 Years Sprinklers - Dry 5.3.1.1.1.5 2.22 T 20 Years Sprinklers - Fast Response 5.3.1.1.1.2 2.23 T 50 Years Sprinklers 5.3.1.1.1 2.24 T 75 Years Sprinklers 75 years in service 5.3.1.1.1.4 2.25 T Sprinklers manufactured prior to 1920 — Re ace 5.3.1.1.1.1 3.1 M Annually Control Valves 12.3.4 �( 3.2 M Annually Preaction/Deluge Valves 12.4.3.3.2 3.3 M Annually Dry Pipe Valves/Quick-Opening Devices 12.4.4.3.2 3.4 M Annually Dry Pipe Valve — Low Point Drains 12.4.4.3.3 3.5 M 5 Years Obstruction Investigation Chapter 13 State Fire Marshal AES 2 March 21, 2006 2582 INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS Inspection, Testing, and Maintenance Fire Sprinkler System Page 4 of 4 NEPA 25, Chapter 5 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: 5/7/019 System Riser ID: Property Information: Name: �- Type of System: torr CAI c % Wet Pipe � - Address.. 1 .. � ❑Dry Pipe � ❑ Preac ion t y ❑ Deluge � Ma City: Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the Item number of the Activity listed above: ❑ See Continuation Page(s) (Indite ;n, fj r ontinuation pages) PASS ❑ FAI L 71,9 signature Date State Fire Marshal AES 2 March 21, 2006 2S -RR TN.9PFC_TT0N_ TESTING_ AND MARqTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS Inspection, Testing, and Maintenance Fire Pumps Page 1 of 8 NEPA 25, Chapter 8 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: i P, Pump ID: . _ ' ..011 '�'� ` • Property Information: Serial Number: raw-:' Y • 1 Name. O, ` ' �1 j l Key: ' Abbreviation i � Address: --�,.�-' I = Inspection T = Test Shaft Orientation: M = Maintenance A-0 = After Operation City: MI = Per Manufacturer's Instructions State Fire Marshal AES 5 March 21, 2006 Annual Fire Pump Test Results Type of Driver: Date of Pump Test: 5 Number of pumps at this location: III Electric If multiple pumps: ❑ Diesel Shaft Orientation: ❑ Series arrangement ❑ Gasoline ❑ Horizontal ❑ Parallel arrangement ❑ Steam 11 Vertical NOTE: Submit a separate form for each pump ❑ Gas Nameplate Data Test Results Shutoff psi p Flow C9P m ) Net Pump RPM Pressure (psi) Volts Amps Pressure 100% Rated Capacity OLOO gPm 100% Rated psi Pressure( 150% Rated �� gpm Capacity 65% Rated psi Pressure Rated RPM ()o rpm Type of Test: 04 Discharge to Atmosphere ❑ Recirculation Controller: Test Equipment QQ Flow Meter 1 Size: �`� y Manufacturer: ❑ Play pipe (1-118 ) ❑ Play pipe (1-3/4") Serial Number: (o PO DS $ ❑ Diffuser/ Size: State Fire Marshal AES 5 March 21, 2006 ANNEX B 25-R9 Inspection, Testing, and Maintenance Fire Pumps NFPA 25, Chapter 8 as amended by CCR, Title 19 Page 2 of 8 Date of Inspection, Testing, Maintenance: Pump ID: Description p Property rtYInformation' Name: � Serial Number: ,-'rA� Pass _ I Address: Abbreviation Key: -•,,� --� _-' ' I = Inspection T =Test louvers M = Maintenance City: `Q"' '' �''S�'S� A-0 = After Operation - MI = Per Manufacturer's Instructions FIRE PUMP INSPECTIONS Item Activity Frequency q y Description p NEPA 25 Reference Fail NIA Pass 1.1 I Weekly Pump House heating and ventilating 8.2.2( 1} louvers x 1.2 I Weekly Circulation Relief Valve 12.5.6.1 1.3 I Weekly Pressure Relief Valve 12.5.6.2 X 1.4 I Quarterly Control Valves 12.3.2.1 Fire Pump System: 8.2.2(2) 1.5 ! Weekly a• Pump Suction, discharge, and .. 822 2 a ()() b ass valves are open. �{ 1.6 1 Weekly b. Piping is free of leaks. 8.2.2(2)(b) 1.7 1 Weekly C. Suction pressure gauge reading is 8.2.2(2 } (c} normal X' 1.8 1 Weekly d. System line pressure gauge 8.2.2 2 d ()( } readingis normal 1.9 1 Weekly e. Suction reservoir is full. 8.2.2(2)(e) 1.10 1 Weekly f. Wet pit suction screens are 8.2.2 2 ()(� unobstructed and in lace. Electrical System Conditions: 8.2.2(3) 1.14 f Weekly a. Controller pilot fight is illuminated. 8.2.2(3)(a) 1.12 l Weekly b. Transfer switch normal pilot light is 8..2.2 3 ()�} illuminated. 1.13 1 Weekly c. Isolating switch is closed — standby 8.2.2(3)(c) (emergency) source. d. Reverse phase alarm pilot light is 1.14 1 Weekly off or normal phase rotation pilot light 8.2.2(3)(d) is on. 1.15 1 Weekly Oil level in vertical motor sight glass is 8.2.2 3 (}(e } normal. Diesel Engine System Conditions: 8.2.2(4) 1.16 1 Weekly a. Fuel tank is iwo-thirds full. 8.2.2(4)(a) State Fire Marshal AES 5 March 21, 2006 25.90 INSPECTION. TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS Inspection, Testing, and Maintenance Fire Pumps Page 3 of 8 NEPA 25, Chapter 8 as amended by CCR, Tine 19 Date of Inspection, Testing, Maintenance: r Pump ID: 11? a �YInformation: Serial Number:Pro �' s ''• Name: ' �.3!'77� fait Abbreviation Key. Address: I = Ins eclion R �E 1 T = Test b Controller selector switch is in M = Maintenance A-0 = After Operation City: Qi b%# ,fle MI = Per Manufacturer's Instructions Item . Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.17 1 Weekly b Controller selector switch is in 8'2'2 (4)(b) i x auto" position. 1.18 ! Week! y c. Batteries (2) voltage readings are 8.2.2(4)(c) normal 1.19 I Weeklyd. Batteries (2) charging current 8.2.2(4)(d) • readings are normal 1.20 I Weeklye. Batteries (2) pilot lights are on or 8.2.2(4)(e) battery failure 2 Ii hts are off. 1.21 I Weekly f. All alarm pilot lights are off. 8.2.2(4)(f) 1.22 1 Weekly9- Engine running time meter is 8.2.2(4)(g) reading. 1.23 1 Weeklyh. Oil level in right angle gear drive is 8.2.2(4)(h) normal. 1.24 I Weekly i. Crankcase oil level is normal. 8.2.2(4)(1) 1.25 l Weekly j. Cooling water level is normal. 8.2.2(4)0) 1.26 1 Weeklyk. Electrolyte level in batteries is 8.2.2(4)(k) normal. 1.27 1 Weekly 1. battery terminals are free from .. $22(4)(1) � corrosion. 1.28 1 Weekly m. Water jacket heater is operating. 8.2.2(4)(m) Steam System Conditions: 8.2.2(5) 1.29 ! Weekly Steam pressure gauge reading is 8.2.2 5 () normal. Pump System: Table 8.5.3(A) 1.30 l A-0 Wet pit suction screens Table Table 5 Electrical System: Table 8.5.3(C) 1.31 t Annually Inspect emergency manual starling Table means 8.5.3 C 4 Diesel Engine System: Table 8.5.3(D) 1.32 I Weekly Fuel: Tank Level. e Table 1 a State Fire Marshal AES 5 March 21, 2006 ANNEX B 25..91 Inspection, Testing, and Maintenance Fire Pumps Page 4 of 8 NFPA 25, Chapter 8 as amended by CCR, Title 19 Date of inspection, Testing, Maintenance: Pump ID: Description NFPA 25 Reference Property Information: Serial Number: --/"• �,:i •;'y� Name:� 117 7.2 Address: �- � u � � Abbreviation Key:,. • ' `- r 1 . =- '� � Inspec�on' ` Fuel: Tank Float Switch T - Test M = Maintenance City: ' r- A-0 = After Operation MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.33 1 Weekly Fuel: Tank Float Switch Table 8.5.3(D)(1)(b) 1.34 1 Weekly Fuel: Solenoid valve operation Table 8.5.3(D)(1)(c 1.35 1 Weekly Fuel: Flexible hoses and connectors Table 8.5.3(D)(1)(g) 1.36 1 Weekly Lubrication System: Oil level. Table 8.5.3(D)(2)(a) 1.37 1 Weekly Cooling System: Level Table 8.5.3(D)(3)(a) 1.38 1 Weekly Cooling System: Adequate cooling water Table to heat exchanger. 8.5.3(D) 3 d 1.39 1 Weekly Cooling System: Water pumps. Table 8.5.3(D)(3)( 1.40 1 Weekly Cooling System: Condition of flexible Table hoses and connections. 8.5.3(D)(3)(g 1.41 1 Weekly Cooling System: Jacket water heater Table 8.5.3(D)(3)(h) X 1.42 1 Weekly Battery System: Electrolyte level. Table 8.5.3(D)(5)(a) is 1.43 1 Weekly Exhaust System: Leakage Table 8.5.3(D)(4)(a) 1.44 1 Weeldy Electrical System: General inspection Table 8.5.3(D)(6)(a) 1.45 1 Monthly Battery System: Charger and charge rage. Table 8.5.3(D)(5)(e) 1.46 1 Monthly Battery System: Equalize charge. Table 8.5.3(D)(5)(f) 1.47 1 Monthly Electrical System: Circuit breakers or Table fuses. 8.5.3(D)(6)(f) 1.48 1 Quarterly Lubrication System: Crankcase breather Table 8.5.3(D)(2)(e) 1.49 1 Quarterly Exhaust System: Insulation and fire Table hazards. 8.5.3(D)(4)(c) 1.50 1 Quarterly Battery System: Terminals dean and tight. Table 8.5.3(D)(5)(b) ` 1.51 1 Quarterly Electrical System: Wire chafing where Table ' subject to moving. 8.5.3(D)(6)(c) Cooling System: Antifreeze protection Table 1.52 1 Semiannually level 8.5.3(D)(3)(b) State Fire Marshal AES 5 March 21, 2006 25-92 INSPECTION. TESTING. AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS Item Inspection, Testing, and Maintenance Fine Pumps NFPA 25, Chapter 8 as amended by CCR, Title 19 Page 5 of 8 Date of Inspection, Testing, Maintenance: 7 p Pump ID: Fail • Property Informa'�on. Pass Serial Number: l�y� }, r' ; •ice .J L Name: Exhaust System: Flexible exhaust section. I8.5.3(D)(4)(f)_ oa- ' Add ess: � r Abbreviation Key: I = Inspection IV Annually Fuel: Tank vents and overflow piping is unobstructed. T =Test ..� M = Maintenance I Annually Fuel: Piping. A-0 = After Operation City; •, = SGj� MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Reference Fail N/A Pass 1.53 I Semiannually Exhaust System: Flexible exhaust section. I8.5.3(D)(4)(f)_ Table 1.54 I Annually Fuel: Tank vents and overflow piping is unobstructed. Table 8.5.3 D 1 h 1.55 I Annually Fuel: Piping. Table 8.5.3 D 1 i `( 1.56 I Annually Cooling System: Inspect ductwork Table 6.5.3 D 3 i 1.57 I Annually Exhaust System: Hangers and supports. Table 8.5.3 D 4 e % FIRE PUMP TESTS 2.1 T Weekly Pump Operation — No Flow condition 8.3.1 2.2 T Monthly Engine Generator Sets NFPA 110 7( 2.3 T Annually Control Valve —Position 12.3.3.1 X 2.4 T Annually Control Valve —Operation 12.3.3.1 2.5 T Annually Supervisory 12.3.3.5 x 2.6 T Annually Pump Operation —Flow condition 8.3.3.1 2.7 T 5 Year Pressure Reducing Valve 12.5.1.2 X 2.8 T Automatic Transfer Switches NFPA 110 Pump System: Table 8.5.3(A) 2.9 T Annually y Pump System: Check Pump shaft end la . Table 8.5.3(A)(2) 2.10 T Annually Pump System: Check accuracy of pressure gauges and sensors. Table 8.5.3 A 3 2.11 T Annually Pump System Check pump coupling alignment. Table 8.5.3 A 4 x 2.12 T Annually Pressure Relief Valve 12.5.6.2.2 y( 2.13 T Annually Circulation Relief Valve 12.5.6.1.2 � State Fire Marshal AES 5 March 21, 2006 ANNEX B 25-93 Inspection, Testing, and Maintenance Fire Pumps Page 6 of 8 N F PA 25, Chapter 8 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: S -7 Pump ID: -, Property Information: Name: Serial Number:,t:,�. '.JI 7 7� Fail Abbreviation Key:;-. Address:`' �. � t �....... _-x- l=Inspection T = Test '= - M = Maintenance A-0 = After Operation City: ' �� �� C1 MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail N/A Pass Reference Electrical System: Table 8.5.3(C) 2.14 T Monthly Electrical System: Exercise isolating Table switch and circuit breaker. 8.5.3 C 1 2.15 T Semiannually Electrical System: Operate manual Table starting means (electrical). 8.5.3 C 3 2.16 T AnnuallyElectrical System: Trip circuit breaker Table if mechanism provided). 8.5.3(C)(2) X Electrical System: Operate emergency Table 2.17 T Annually manual starting means (without 8,5.3 C 4 ()() power). Diesel Engine System: Table 8.5.3(D) 2.18 T Monthly Battery System: Specific Gravity or Table state of charge 8.5.3 D 5 d 2.19 T Semiannually Electrical System: Operation of Table safeties and alarms. 8.5.3 D 6 d 2.20 T AnnuallyExhaust System: Excessive back Table pressure 8.5.3 D 4 d Fire Pump Maintenance (NFPA 25:8.5.1) 3.1 M Annually Control valves 12.3.4 Pump System: Table 8.5.3(A) 3.2 M Annually Lubricate pump bearings Table e 't ) 2C Mechanical Transmission: Table 8.5.3(B) 3.3 M Annually Lubricate Coupling Table 8.5.3 B 1 X 3.4 M Annually Lubricate right-angle gear drive Table 8.5.3 B 2 Electrical System: Table 8.5.3(C) 3.5 M Annually Tighten electrical connections Table 8.5.3 C 5 3.6 M AnnuallyLubricate mechanical moving parts Table (excluding starters and relays) i.5.3 C 6 State Fire Marshal AES 5 March 21, 2006 25-94 INSPECTION. TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS Inspection, Testing, and Maintenance Fire Pumps Page 7 of 8 NFPA 25, Chapter 8 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: Z Pump 1D: 1 �`, "�."� -��-��� 6f- CAf"q Property Information. Serial Number: Name: , z ..SaO-77 a i Pass Abbreviation Key: I=Inspection�,�, -` Address: ,r Annually Calibrate pressure switch settings. T =Test =` M = Maintenance A-0 = After Operation City: MI = Per Manufacturer's Instructions Item Activity ' ' Frequency q y Description P NFPA 25 Reference Fail N/A Pass 3.7 M Annually Calibrate pressure switch settings. Table 8.5.3(C)(7) Table 3.8 M Annual{ Y Grease motor bearings g 8.5.3 C 8 Diesel Engine System: Table 8.5.3{D} Table Table 3.9 M Weekly Fuel: Water n system. i 1 � Fuel: Strainer, filter, or dirt leg, or Table 3.1 o M Quarterly combination thereof. 8.5.3 D 1 d Fuel: Water or foreign material in Table 3.'t 1 M p►nnuaH y tank. 8.5.3 D 1 a �C Table8.5.3 3.12 M Annually Cooling System: Antifreeze g Ys D 3 c Table _ Lubrication System. 8.5.3 D 2 Table TablD 3.13 M Weekly Lube oil heater 2 d Table8.5.3 3.14 M Quarterly Crankcase breather C D 2 e 3.15 M Annually/5o Hours Oil chan9e Table 8.5.3 D 2 b 3.16 M Annually/50 Ho urs De•l Filter(s) s Table 8.5.3(D)(2)_(c) Table 'n System: Coote g8.5.3 D 3 Table Table 3.17 M Quarterly Water Strainer 3 ' 3.18 M Semiannually ' Antifreeze protection level. P Table 8.5.3 D a b e Table 3.19 M Annually Rod out heat exchanger. 3 e Table 3.20 M Annually Clean louvers. 8.5.3 D 3 i Table System: Exhaust S y 8.5.3 D 4 Table 3.21 M Weekly Drain condensate trap. 8.5.3 D 4 b • State Fire Marshal AES 5 March 21, 2006 25-95 Inspection, Testing, and Maintenance Fire Pumps Page 8 of 8 NFPA 25, Chapter 8 as amended by CCR, Title 19 Date of Inspection, Testing, Maintenance: S Pump ID: Property rtyInformation: 4, Serial Number: �- Name: f Slo17 7 a, . t Address.I ti Abbreviation Key.•. I =Inspection `JAli (XVexW ZStt. 6A w" t� �A T = Test - - M = Maintenance A-0 = After Operation City: ra ,;A MI = Per Manufacturer's Instructions Item Activity Frequency Description NFPA 25 Fail NIA Pass (XVexW ZStt. 6A w" t� �A Reference See Continuation Page(s) (Indicate the,. mbe f nti uation pages) C7 PASS FA# L - - -- a Signature D6te Battery System: 3.22 M Monthly Remove corrosion, case exterior clean Table and dry. 8.5.3D5c Electrical System: Table 8.5.3 D 6 3.23 M Semiannually Boxes, panels, and cabinets. Table , %t 8.5.3 D 6 e 3.24 M Annually Tighten control and power wiring Table connections. 8.5.3 D 6 b 3.25 M Biannually Circuit breakers and fuses Table 8.5.3 D 6 Item Deficiencies and Comments: Deficiencies and Comments Item number must correspond to the item number of the Activity listed above: A;-A-"kC-a'-nC-J=-A1 0001�O4� �� D ("SS - S (XVexW ZStt. 6A w" t� �A See Continuation Page(s) (Indicate the,. mbe f nti uation pages) C7 PASS FA# L - - -- a Signature D6te State Fire Marshal AES 5 March 21, 2006 .ANNEXB 25-95 Inspection, Testing, and Maintenance Fire Pumps NFPA 25, Chapter 8 as amended by CCRI Title 19 Date of Inspee ion, Testing, Maintenance: 5 /710 s Property Information: Name: Address: City: 9 Z�19 f Pump ID: I Serial Number. 0 ).,,- S 1z, 17 7 J., Page 8 of 8 ` P Abbreviation Key: �-• ; _ .-. I = Inspection V NriA T = Test M = Maintenance A -Q = After Operation MI = Per Manufacturer's Instructions. State Fire Marshal AES 5 March 21, 2006 Description ' Battery System: Remove corrosion, case exterior clean and dry. Electrical system: Boxes, panels, and cabinets. NEPA 25 Fail NIA PassReference Item Acfivity Frequency 3.2 2 M Monthly Table 8.5.3 D 5 c Table 8.5.3 D 6 Table Table 6 e •x• 3.23 M Semiannually Annually 3.24 M Tighten control and power wiring connections_ Table 8.5.3 D 6 b 3,25 M Biannually Circuit breakers and fuses e Table D 6 ) State Fire Marshal AES 5 March 21, 2006