HomeMy WebLinkAbout040-180-062 CF Archive (2)Durham Unified School District Fire Inspection — 2000-2001 Page 1 of 6 Staff Timeline Responsible ,� for Correction °' 0 Inspection Exception and Future Compliance � Q Durham Elementary School Multi-purpose room: MOT ✓ Stage electrical circuit breakers not marked as to what they serve. [1998 CEC 110-17(c)] Identify individual circuits by labeling in breaker box. MOT ✓ Exit sign battery backup out of service. [1998 CBC 1003.2.8.2] Replace battery. MOT ✓ Metal table blocking exit and fire alarm pull station. [Title 19 CCR Section 3.11] Move table. Kitchen: MOT, ✓ Combustible materials too close to water heater. [Title 19 CCR Section 3.19 (f)] Debbie Move all combustible materials to a minimum of 36"from water heater (if heater is in a closet, remove all combustible materials from closet. MOT, ✓ Wire rack stored in front of electrical circuit panel. [1998 CEC 110-16(a)] Debbie Move rack to another location, 36" clearance required around panel. Library: MOT ✓ Hole in wall at "all call" receptacle in computer room. [1998 CEC Section 300-21,22] Repair hole with fire resistive materials. MOT ✓ Multi -plug power strips in computer room combined to reach wall plug receptacle. [1998 CEC Section 400- 8(1) Provide permanent wall plug. Exit Corridors: MOT, Liz ✓ Corridors used for storage (table, chairs, other classroom equipment). [Title 19 CCR Section 3.11 (a,b,c)] Consult with Butte County Fire Department Life Safety Officer on items to be removed. MOT ✓ No emergency exit lighting in corridors. [1998 CBC 1003.2.9.2] Install emergency exit lighting in corridors serving classrooms. Durham Unified School District Fire Inspection — 2000-2001 Page 2 o� 6 Staff Timeline Responsible ,..., for Correction Inspection Exception and Future Compliance 40 MOT, Liz ✓ Paper covering extinguisher cabinets, cabinets not marked conspicuously. [Title 19 CCR 563.8 (a,b)] Remove all paper covering fire extinguisher cabinets. Place "Fire Extinguisher" signs above cabinets mounted perpendicular to wall. Classrooms: MOT, Liz ✓ Teacher desks and/or chairs blocking exits to exterior. [Title 19 CCR Section 3.11] Move desks to facilitate clear exiting to exterior of building. MOT, Liz ✓ Microwave in classroom 6 covered with combustible materials; glue guns in room 32 used on combustible surface. [1998 CFC Section 1107] Remove combustible materials from microwave; use and store glue guns on fire resistive material. MOT ✓ Cable outlet in room 15 allows hole in wall. [1998 CEC 300-21,22] Repair holes in fire resistive construction. MOT, Liz ✓ Multi -plug power strips combined to lengthen and reach wall plugs in rooms 9, 11, 40. [1998 CEC 4008(1)] Provide permanent wiring to eliminate multiple "in-line "power strips. MOT, Liz ✓ Classroom 10 has non -surge protected power strip. [1998 CEC 400-13] Replace with circuit breaker protected strip. MOT ✓ Exit door in classroom 10 difficult to open. [1998 CFC Section 1207.3] Lubricate door or modify clearance between door and jamb to ease effort to open. MOT, Liz ✓ Fire alarm pull stations and indicator panel (classroom 38) not accessible or visible. [Title 19 Section 3.14] Remove obstructions blocking pull stations and indicator panels. Liz ✓ Combustible paper decorations and wall coverings (colored roll paper) shall not cover more than 10% of available wall surface in each classroom. Absolutely NO electrical devices (switches, plugs [duplex or fourplex receptacles], wiring raceways shall be covered. Flammable paper shall be kept at least 6 "away from all devices. [Title 19 Section 3.08] Main Office: MOT, Liz ✓ Multi -plug power strips combined in nurse's office. [1998 CEC 400-8(1)] Add permanent wall plug receptacle. MOT ✓ Wall open near speaker in nurse's office. [1998 CEC 300-21,22] Repair hole in fire resistive construction. Durham Unified School District Fire Inspection — 2000-2001 Page 3 of Staff Timeline Responsible r-, for Correction - Inspection Exception and Future 0 Compliance ►-� w Janitor's Room: MOT ✓ Combustibles blocking access to fire alarm panel. [ 1998 CEC 110-16-a] Minimum 36" clearance required aroundfire alarm panel. Durham Intermediate School District Office: MOT, ✓ Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), 1998 CFC Sec. 8506.1 Christy Permanent hard -wined receptacles required to eliminate power strips, reception area. Multiple power strips cannot be combined. MOT ✓ Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Mount telephone jack to wall to cover hole in fire resistive construction, main reception area. MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 All extinguishers must be signed; Board Room and psychologist office. MOT ✓ All panels and breakers are marked. 1998 CEC 110-17c Mark all breakers at control panel, exterior breaker box on NW corner. MOT ✓ Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Affix telephone jack to wall to repair hole in construction on East wall. Print Shop: MOT, ✓ Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), 1998 CFC Sec. 8506.1 Christy Permanent hard -wired receptacles required to eliminate power strips, desk area. Multiple power strips cannot be combined. MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 All extinguishers must be signed. MOT ✓ All panels and breakers are marked. 1998 CEC 110-17c Mark all breakers at control panel, paper storage room. MOT ✓ Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Repair hole in fire resistive construction by replacing broken cover on electrical outlet on west wall. Durham Unified School District Fire Inspection — 2000-2001 Page 4 0� Staff Timeline Responsible I ,� for Correction � 0 (D Inspection Exception and Future Compliance p � MOT ✓ Appliance cords and extension cords shall be kept in good condition with no splices. 1998 CFC Sec. 8504 Replace electrical cord on electric typewriter, front desk. District Warehouse: MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 All extinguishers must be mounted and signed. MOT, ✓ A clear width of 30 inches and minimum height of 72 inches shall be maintained from the face of electrical Helen panel boards to an aisle or corridor. 1998 CFC Sec. 8509.2 Remove stored materials from front of electrical panels; South entrance on West wall, and center wall East Side. MOT ✓ All panels and breakers are marked. 1998 CEC 110-17c Mark all breakers at control panel, breaker box on center wall. MOT ✓ Install ventilation system in pesticide/herbicide storage area. 1998 CFC 8003.1.4 Install ventilation fan and keep door locked when unoccupied. MOT ✓ Install extinguisher; paint room. 1997 CFC Standard 10-1 Mount 2A-10BC fire extinguisher near room exit. MOT ✓ Indoor storage of flammable and combustible liquids shall not exceed the exempted amounts in CFC table 7902.5-A (Attached) MOT ✓ Keep broiler room locked at all times when not occupied. MOT ✓ Electrical outlet needs cover plate. Cover electrical outlet at entrance to tool room. MOT ✓ All fuel storage must be in approved containers. 1998 CFC 7902.1.8.1.1 Mixed fuel in tool room needs to be stored in approved container. Main Office/Work Room: MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 All extinguishers must be signed in main office & work room. Durham Unified School District Fire Inspection — 2000-2001 Page 5 0i, Staff Timeline Responsible for Correction Inspection Exception and Future Compliance Library: MOT, Steve ✓ Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), 1998 CFC Sec. 8506.1 Permanent hard --wired receptacles required to eliminate power strips, computer lab, and front desk areas. Multiple power strips cannot be combined. MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 All extinguishers must be signed. Gym: MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 All extinguishers must be signed. MOT ✓ All panels and breakers are marked. 1998 CEC 110-17c Mark all breakers at control panel. Classrooms: MOT, Steve ✓ No fire hazard shall be permitted. 1998 Title 19 Sec. 3.14 Trim decorative paper away from electrical outlet one foot in all directions; classrooms 2, 8, 11, 13, 70 & GATE classroom. MOT, Steve ✓ Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), 1998 CFC Sec. 8506.1 Permanent hard -wired receptacles required to eliminate multiple power strips. Power strips cannot be combined: Classrooms 1, 2, 5, 8, 11 & 13. MOT, Steve ✓ 30 -inch clearance required around all electrical panels. 1998 CEC 110-16a Classroom 71. MOT, Steve ✓ Multi -plug power strips must have circuit breaker/fuse. 1998 CEC 400-13 Extension strip needs circuit breaker/fuse; classrooms 1, 2, 8, 10, 11 & 70. MOT ✓ Exit doors shall be operable from the inside without a key or any special knowledge or effort. 1998 CFC sec. 1207.3 Exit door sticking in classroom 10. MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 All extinguishers must be signed; classrooms 4, 5, 6, 7, 8, 9, 10, 11, & 13. E� Durham Unified School District Fire Inspection — 2000-2001 Page 6 0.. Staff Timeline Responsible 1 „� for Correction o elf -a Inspection Exception and Future (U � Compliance ti w MOT ✓ Extinguishers shall be conspicuously located where they will be readily accessible and immediately available in the event of a fire. They shall be located along normal paths of travel, including exits from an area. 1998 Title 19 Sec. 563.2. Relocate fire extinguisher at exit from classroom, classroom 9. MOT ✓ No fire hazard shall be permitted. 1998 Title 19 Sec. 3.14 Remove signs stating "Fire Door Do Not Obstruct "from doorway connecting classrooms 4 and 7. Door is not an exit. MOT, Steve ✓ Remove obstructions to eye wash station classroom 7. Durham High School Administration Building: MOT, Paul ✓ Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), 1998 CFC Sec. 8506.1 Permanent hard -wired receptacles required to eliminate power strips; reception area and J. Piacitelli office. Multiple power strips cannot be combined. MOT, Paul ✓ Multi -plug power strips must have circuit breaker/fuse. 1998 CEC 400-13 Extension strip needs circuit breaker/fuse; J. Piacitell i office. MOT ✓ Means of egress illumination shall be supplied with two sources of power where the means of egress system serves an occupant load of 100 or more. 1998 CBC 1003.2.9.2 Install required means of egress lighting to all designed exits; install exit signs Main Corridor. MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 Install protruding mounted extinguisher signs at extinguisher cabinets in Main Corridor. MOT ✓ Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Repair hole in wall, Athletic Director office, and men's restroom. Gym: MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 Install extinguisher signs at extinguisher cabinets; North wall & East wall. Durham Unified School District Fire Inspection — 2000-2001 Page 7 oi'13 Staff Timeline Responsible 1 "_4 for Correction 2 N Inspection Exception and Future Compliance p � w MOT, Paul ✓ Exits shall not be obstructed. 1998 Title 19 Sec. 3.11, 1998 CFC Sec. 1203 Do not store gym equipment in exit path, main entrance SE double doorway. MOT ✓ Exit doors shall be operable from the inside without a key or any special knowledge or effort. 1998 CFC sec. 1207.3 Center exit door sticking, NTS doorway. Stage: MOT ✓ Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Repair hole in wall, stage. MOT ✓ 30 -inch clearance required around all electrical panels. 1998 CEC 110-16a. All panels and breakers are marked. 1998 CEC 110-17c Individual circuit breakers must be marked at electrical panel, clearance must be maintained; dressing room. MOT ✓ No fire hazard shall be permitted. 1998 Title 19 Sec. 3.14 Remove paper from overhead spotlight. Cafeteria/Kitchen : MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 Mount extinguisher signs at all extinguishers, keep 30 " clearance. MOT, ✓ Multi -plug power strips must have circuit breaker/fuse. 1998 CEC 400-13 Vanessa Extension strip needs circuit breakerffuse; office, East wall. MOT ✓ Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Repair hole in wall, men's restroom. MOT ✓ Exits shall not be obstructed. 1998 Title 19 Sec. 3.11, 1998 CFC Sec. 1203 Clear exit path to doorway, North exit behind kitchen. MOT ✓ Install permanent hardwired switch to raise/lower security gate at kitchen entrance. Library: MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 Mount extinguisher signs at all extinguishers, keep 30" clearance. F_� Durham Unified School District Fire Inspection — 2000-2001 Page 8 0� Staff Timeline Responsible ,__4 for Correction Inspection Exception and Future Compliance p � w MOT, Paul ✓ Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), 1998 CFC Sec. 8506.1 Permanent hard -wired receptacles required to eliminate power strips, computer room. Multiple power strips cannot be combined. MOT, Paul ✓ Multi -plug power strips must have circuit breaker/fuse. 1998 CEC 400-13 Extension strip needs circuit breaker/fuse; computer room, librarian office. MOT ✓ Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Repair hole in wall, periodical room. MOT ✓ Exit illumination and signs in place. 1998 CBC 1003.2.9.2 Emergency lighting and exit signs are required at exits in rooms with occupant load of 50 persons or more, North exit corridor. MOT, Paul ✓ Exit stairways and corridors shall be kept clear of obstructions and storage. 1998 Title 19 Sec. 3.11 Remove all obstructions and stored items from the North exit corridors. Portable Classrooms: MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 Mount extinguisher signs at all extinguishers, keep 30" clearance; classrooms 60, 61, 62 & 63. 100 Building: MOT, Paul ✓ Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), 1998 CFC Sec. 8506.1 Permanent hard -wired receptacles required to eliminate power strips; computer lab. Multiple power strips cannot be combined, classroom 110. MOT, Paul ✓ Multi -plug power strips must have circuit breaker/fuse. 1998 CEC 400-13 Extension strip needs circuit breakerffuse; computer lab, librarian office. Classrooms 103, 105, 108, 109, & 110. MOT, Paul ✓ No fire hazard shall be permitted. 1998 Title 19 Sec. 3.14 Clear all decorative paperfrom electrical outlet one foot in all directions, classroom 107. MOT, Paul ✓ 30 -inch clearance required around all electrical panels. 1998 CEC 110-16a All panels and breakers are marked. 1998 CEC 110-17c Clear combustible material from under electrical panel classroom 104. Durham Unified School District Fire Inspection — 2000-2001 Page 9 o. 3 Staff Timeline Responsible r, for Correction Inspection Exception and Future aD 0 a4 � Compliance ti w 200 Building: MOT, Paul ✓ 30 -inch clearance required around all electrical panels. 1998 CEC 110-16a All panels and breakers are marked. 1998 CEC 110-17c Individual circuit breakers must be marked at electrical panel, clearance must be maintained; DIS 14, science store room. MOT ✓ Electrical panels that are accessible to children without adult supervision must be locked. MOT ✓ All standpipe and automatic fire protection systems must have back up wrenches and sprinkler heads available. MOT ✓ All standpipe and automatic fire protective systems must have clearance. MOT, Paul ✓ Obstructions to exits shall not be placed in the required width an exit; exits shall not be obstructed in any manner. 1998 Title 19 Sec. 3.11, 1998 CFC Sec. 1203 Exit doorway 204 must be cleared of obstructions and clearly marked "EXIT" on the interior. MOT, Paul ✓ Remove combustible storage from heater, mechanical, electrical room. 1998 Title 19 Sec. 3.19f No combustible storage in hot water heater closet. MOT, Paul ✓ No fire hazard shall be permitted. 1998 Title 19 Sec. 3.14 Remove combustible storage at least 36" around corrosive and flammable storage containers, science store room. MOT, Paul ✓ Remove combustible storage 24" from ceiling. MOT ✓ Repair hole in ceiling classroom 203. MOT ✓ Extension cords not to replace permanent wiring. 1998 CEC 400-8 (1), 1998 CFC Sec. 8506.1 Extension cords cannot be combined, classrooms 201, 202 & 203. MOT, Paul ✓ Appliance cords and extension cords shall be kept in good condition with no splices. 1998 CFC Sec. 8504 Appliance cords cannot have splices, classroom 203 stereo. MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 Mount extinguisher signs at all extinguishers, keep 30" clearance; classrooms 201, 202 & 203 Paul ✓ Poison cannot be store in glass containers in the sink; they must be stored in approved container. 400 Building: Durham Unified School District Fire Inspection — 2000-2001 Page 10 o.L Staff Timeline Responsible for Correction Inspection Exception and Future Compliance p ti 0 � w MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 Install extinguisher signs at extinguisher. MOT ✓ No fire hazard shall be permitted. 1998 Title 19 Sec. 3.14 Install cover to attic access in mezzanine. MOT, Paul ✓ Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), 1998 CFC Sec. 8506.1 Multiple power strips cannot be combined, computer closet. MOT, Paul ✓ Exits shall not be obstructed. 1998 Title 19 Sec. 3.11, 1998 CFC Sec. 1203 Relocate metal table away from exit at south door. MOT ✓ Secure mezzanine wooden rail to the wall. 500 Building: MOT, Paul ✓ All combustible waste material and rubbish shall be stored in approved containers. 1998 T19 3.19b No fire hazard shall be permitted. 1998 Title 19 Sec. 3.14 Clean accumulated sawdust from sawdust collection system daily or install larger storage capacity. MOT ✓ All waste containers must be metal with attached metal lid and emptied daily, woodworking areas. Large metal dumpster with metal lid between Ag and Auto shop could ease waste problems. MOT ✓ Extinguishers mounted on wall/or in cabinet, visible and signed. 1998 Title 19 563.8 Extinguishers need sign. MOT, Paul ✓ Obstructions to exits shall not be placed in the required width an exit; exits shall not be obstructed in any manner. 1998 Title 19 Sec. 3.119 CFC Sec. 1203 Move refrigerator on East wall so it does not block exit path to the doorway. MOT ✓ Fusible link on roll up door separating classrooms must be replaced every 6 months. MOT ✓ No fire hazard shall be permitted. 1998 Title 19 Sec. 3.14 Replace all missing ceiling tiles in wood shop and arts/crafts classroom. MOT, Paul ✓ Remove obstructions to eye wash station in arts/crafts closet. MOT ✓ Secure mezzanine wooden rail to the wall. Arts/crafts classroom and wood shop. Durham Unified School District Fire Inspection — 2000-200 Page 11 0,. Staff Timeline Responsible for Correction °' 0 Inspection Exception and Future 0 to 0 Compliance ti MOT, Paul ✓ No fire hazard shall be permitted. 1998 Title 19 Sec. 3.14 Remove combustible storage from electrical panel in West room connecting arts and wood shop. MOT ✓ Recommend installation of larger smoke removal system above arc -welding area to keep toxic smoke from entering GATE classroom. MOT ✓ Install protective covers over lights, kiln room. MOT, Paul ✓ Appliance cords and extension cords shall be kept in good condition with no splices. 1998 CFC Sec. 8504 Appliance cords cannot have splices, electric fan secured to mezzanine rail in arts/crafts. Auto Shop: MOT, Paul No fire hazard shall be permitted. 1998 Title 19 Sec. 3.14 ✓ Repair hole in ceiling, North storeroom. ✓ Clear combustible storage under canopy/awning outside Auto Shop. ✓ Replace ceiling panel in classroom. ✓ Install protective covers over lights, North storeroom. MOT ✓ 30 -inch clearance required around all electrical panels. 1998 CEC 110-16a. All panels and breakers are marked. 1998 CEC 110-17c Individual circuit breakers must be marked at electrical panel, clearance must be maintained. MOT ✓ Extinguishers shall be visible and accessible at all times. 1998 Title 19 Sec. 3.29 Lower extinguisher mounted in classroom to at least five feet. MOT ✓ Replace electrical junction box on classroom light switch, knockouts must be intact. MOT, Paul ✓ Secure tool cage in open position with lock during school hours. All Schools — Fire Alarms Durham High School: MOT ✓ Repair alarm pull station #104, unable to pull handle down to trip box. Repair horn in auto shop, strobes activate, but horn does not. Durham Intermediate School: N/A No problems noted. Durham Unified School District Fire Inspection — 2000-2001 Page 12 0l Staff Timeline Responsible for Correction and Future Compliance p I o ,--4 � Inspection Exception Durham Elementary School: MOT ✓ Portable ##29: No horn activation. ✓ Portable #31: Remove rakes blocking pull station. ✓ Portable #32: Drapes and computer table blocking pull station. ✓ Main building: Strobe lights inoperable in main hallways. April 4, 2001 Captain Steven J. Fowler Butte County Fire 176 Nelson Avenue Oroville, CA 95965 DURHAM UNIFIED SChOOL DISTRICT Penny Chennell, Ed.D., District Superintendent P.O. Box 300 Durham, California 95938 Telephone -(530) 895-4675 Facsimile (530) 895-4692 http://www.bcoe.butte.kl2.ca.us/durhai-n/ BOARD of TRUSTEES: Linda Boles Michael McDonald Bill Orthel Tom Simmons Donna Killoran Re: Your letter of March 6, 2001 Dear Steve: Thank you for your office's recent inspection of our facilities, your letter of March 6 and our subsequent meeting to discuss your report. We have reviewed your report and assigned staff members and a timeline for correction to each exception noted. A copy of those assignments are enclosed for your review. We have begun work on a number of items and intend to have each completed by the date noted on the attached report. Please note that the designated in the "future" column are largely items requiring additional permanent electrical wall plugs at our elementary school. These will be added as part of the modernization of that site which could begin as early as the summer of 2002. Once you have had an opportunity to review the enclosed, please contact me if you have any concerns or questions. Sincerely, CC�IhritsrjyT.A�. atterson Business Manager Enclosures cc(w/encl): Dave York DURHAM ELEMENTARY SCHOOL DURHAM INTERMEDIATE SCHOOL DURHAM HIGH SCHOOL ELIZABETH T. CAPEN STEPHEN J. PILUSO PAUL ARNOLD PRINCIPAL PRINCIPAL PRINCIPAL Telephone (530) 895-4695 Telephone (530) 895-4690 Telephone (530) 895-4680 Facsimile (530) 895-4665 Facsimile (530) 895-4305 Facsimile (530) 895-4688 MISSION HIGH SCHOOL STEPHEN J. PiLUSO PRINCIPAL Telephone (530) 895-4690 S FD VOLUNTEER F RECOMPANIES BANGOR BIGGS BUTTE CREEK CANYON BUTTE MEADOWS CHEROKEE CLIPPER MILLS COHASSET DeSABLA DURHAM FEATHER FALLS FOREST RANCH rnLnEN 1:1ZA WEq GREATER GRIDLEY KELLY RIDGE MAGALIA NORTH CHICO PALERMO PENTZ VALLEY PIONEER RICHVALE ROBINSON MILL STIRLING CITY TH ERMALITO B FD FULL-TIME FIRE STATIONS BANGOR BIGGS DURHAM GRIDLEY KELLY RIDGE ORD NORTH CHICO OROVILLE PALERMO RICHVALE SOUTH CHICO UPPER RIDGE C F FIRE STATIONS BUTTE MEADOWS COHASS ET FEATHER FALLS FOREST RANCH HARTS MILL JARBO GAP OROVILLE HO PARADISE ROBINSON MILL STIRLING CITY BUTTE FIRE CENTER MAGALIA R FORESTATION N RSERY DAVIS MAGALIA AIR ATTACK BASE CHICO FIRE LOOKOUTS BALD MOUNTAIN BLOOMER HILL PLATTE MOUNTAIN SAWMILL PEAK SUNSET HILL A SO PROUDLY SERVING CITY OF BIGGS CITY OF GRIDLEY LAND OF NATURAL WEALTH AND BcAU IY BUTTE COUNTY FIRE DEPARTMENT CALIFORNIA DEPARTMENT OF FORESTRY AND FIRE PROTECTION "Sixty-seven fears of Cooperative Emergency Services” ` 176 NELSON AVENUE • OROVILLE, CALIFORNIA 95965-3495 TELEPHONE: (530) 538-7111 FAX: (530) 538-7401 v March b, 2001 �/�'!�I Dr. Penny Chennell, Superintendent r Durham Unified School District P.O. Box 300 Durham, CA 95938 Ref: Durham Unified School District Dear Penny, An inspection of the referenced facility was recently conducted in accordance with Section 13145 of the California Health and Safety Code. The purpose was to determine compliance with the minimum fire and life safety standards required by Titles 19 and 24 of the California Code of Regulations. The attached report is to advise you of the actions that are required to correct noted deficiencies. To insure this facility is brought into compliance within a reasonable time, please submit your plan for accomplishing these corrections, to this office, within' -3 0 days from receipt of this notice. If you have alreadycorrected these deficiencies, please advise us so we can make an appointment for a re -inspection and update our files. If I can be of further assistance, or you desire additional information or clarification, please contact me at the CDF Fire/Butte County Fire Department Fire Prevention Bureau headquarters, (5 3 0) 538-3859. Sincerelv, William R. Sager Fire Chief BvSteven J. Fowler Life Safety Officer 2 Durham Elementary School Multi-purpose room: Stage electrical circuit breakers not marked as to what they serve. 1998 CEC 110-17(c) Identify individual circuits by labeling in breaker box. Exit sign battery backup out of service. 1998 CBC 1003.2.8.2 Replace battery. Metal table blocking exit and fire alarm pull station. Title 19 CCR Section 3.11 Move table. Kitchen: Combustible materials too close to water heater. Title 19 CCR Section 3.19 (f) Move all combustible'materials to a minimum of 36" from water heater (if heater is in a closet, remove all combustible materials from closet.) Wire rack stored in front of electrical circuit panel. 1998 CEC 110-16(a) Move rack to another location, 36" clearance required around panel. Libr • Hole in wall at "all call" receptacle in computer room. 1998 CEC Section 300-21,22 Repair hole with fire resistive materials. Multi -plug power strips in computer room combined to reach wall plug receptacle. 1998 CEC Section 400- 8(1) Provide permanent wall plug. Exit Corridors: Corridors used for storage (table, chairs, and other classroom equipment). Title 19 CCR Section 3.11 (a,b, c) Consult with Butte County Fire Department Life Safety Officer on items to be removed. No emergency exit lighting in corridors. 1998 CBC 1003.2.9.2 Install emergency exit lighting in corridors serving classrooms. Paper covering extinguisher cabinets, cabinets not marked conspicuously. Title 19 CCR 563.8 (a,b) Remove all paper covering fire extinguisher cabinets. Place "Fire Extinguisher" signs above cabinets mounted perpendicular to wall. Classrooms Teacher desks and/or chairs blocking exits to exterior. Title 19 CCR Section 3.11 Move furniture to facilitate clear exiting to exterior of building. Microwave in classroom 6 covered with combustible materials; glue guns in room 32 used on combustible surface. 1998 CFC Section 1107 Remove combustible materials from microwave; use and store glue guns on fire resistive material. Cable outlet in room 15 allows hole in wall. 1998 CEC 300-21,22 Repair holes in fire resistive construction. A Multi -plug power strips combined to lengthen and reach wall plugs in rooms %11, 40. 1998 CEC 4008(1) Provide permanent wiring to eliminate multiple "in-line" power strips. Classroom 10 has non -surge protected power strip. 1998 CEC 400-13 Replace with circuit breaker protected strip. Exit door in classroom 10 difficult to open. 1998 CFC Section 1207.3 Lubricate door or modify clearance between door and jamb to ease effort to open. Fire alarm pull stations and indicator panel (classroom 38) not accessible or visible. Title 19 Section 3.14 Remove obstructions blocking pull stations and indicator panels. Combustible paper decorations and wall coverings (colored roll paper) shall not cover more than 10% of available wail surface in each classroom. Absolutely NO electrical devices (switches, plugs [duplex or four -plea receptacles], or wiring raceways shall be covered e paper shall be kept at least 6 CC away from all devices. Title 19 Section 3.08 Main Office: Multi -plug power strips combined in nurse's office. 1998 CEC 400-8(1) Add permanent wall plug receptacle. Wall open near speaker in nurse's office. 1998 CEC 300-21,22 Repair hole in fire resistive construction. Janitor's Room: Combustibles blocking access to fire alarm panel. 1998 CEC 110-16-a Minimum 36" clearance required around fire alarm panel. Durham Intermediate School District Office Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), 1998 CFC Sec. 8506.1 Permanent hard -wired receptacles required to eliminate power strips, reception area. Multiple power strips cannot be combined. Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Mount telephone jack to wall to cover hole in fire resistive construction, main reception area. Extinguishers mounted on wall/or in cabinet, visible and signed, Title 19 563.8 All extinguishers must be signed in Board Room and psychologist office. All panels and breakers are marked 1998 CEC 110-17c Mark all breakers at control panel, exterior breaker bog on NW corner. Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Affix telephone jack to wall to repair hole in construction on east wall. 4 Print Shop Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), 1998 CFC Sec. 8506.1 Permanent hard -wired receptacles required to eliminate power strips, desk area. Multiple power strips canunot be combined. Extinguishers mounted on wall/or in cabinet, visible and/or signed. Title 19 563.8 All extinguishers must be signed if not visible from across room. All panels and breakers are marked. 1998 CEC 110-17c Mark all breakers at control panel, paper storage room. Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Repair hole in fire resistive construction by replacing broken cover on electrical outlet on west wan. Appliance cords and extension cords shall be kept in good condition with no splices. 1998 CFC Sec. 8504 Replace electrical cord on electric typewriter, front desk. District Warehouse Extinguishers mounted on wall/or in cabinet, visible and signed Title 19 563.8 All extinguishers must be mounted and signed. A clear width of 30 inches and iu* height of 72 inches shall be maintained from the face of electrical panel boards to an aisle or corridor. 1998 CFC Sec. 8509.2 Remove stored materials from front of electrical panels; south entrance on west wall, and center wall eastside. All panels and breakers are marked. 1998 CEC 110-17c Mark an breakers at control panel, breaker box on center wall Install ventilation system in pesticide/herbicide storage room. 1998 CFC 8003.1.4 Install ventilation fan and keep door locked when unoccupied. Install extinguisher in paint storage room. 1997 CFC Standard 10-1 Mount 2A-IOBC fire extinguisher near room exit. Indoor storage of flammable and combustible liquids shall not exceed the exempted amounts in CFC table 7902.5-A (attached.) Keep "broiler room" locked at all times when not occupied. Electrical outlet needs cover plate. Cover electrical outlet at entrance to tool room. All fuel storage must be in approved containers. 1998 CFC 7902.1.8.1.1 Mixed fuel in tool room needs to be stored in approved container. Main Office/Work Room Extinguishers mounted on wall/or in cabinet, visible and/or signed. Title 19 563.8 All extinguishers must be signed in main office & work room. 5 Library Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), 1998 CFC Sec. 8506.1 Permanent hard -wired receptacles required to eliminate power strips, computer lab, and front desk areas. Multiple power strips cannot be combined. Extinguishers mounted on wall/or in cabinet, visible and signed Title 19 563.8 All extinguishers must be signed. Gvm Extinguishers mounted on wall/or in cabinet, visible and signed Title 19 563.8 All extinguishers must be signed. All panels and breakers are marked. 1998 CEC 110-17c Mark all breakers at control panel. Classrooms No fire hazard shall be permitted. Title 19 Sec. 3.14 Trim decorative papers away from electrical outlet 611in all directions in classrooms 2, 8, 11, 13,70 & GATE classroom. Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), 1998 CFC Sec. 8506.1 Permanent hard -wired receptacles required to eliminate multiple power strips. Power strips cannot be combined: classrooms 1, 2, 5, 8,11 & 13. Thirty -(30) inch clearance required around front of all electrical panels. 1998 CEC 110-16a Classroom 71. Multi -plug power strips must have circuit breaker/fuse. 1998 CEC 400-13 Classrooms 1, 2, 8,10,11 & 70. Exit doors shall be operable from the inside without a key or any special knowledge or effort. 1998 CFC 1207.3 Exit door sticking in classroom 10. Extinguishers mounted on wallfor in cabinet, visible and signed. Title 19 563.8 All extinguishers must be signed: classrooms 4, 5, 6, 71t 8199 10, 11 9 & 13. Extinguishers shall be conspicuously located where they will be readily accessible and immediately available in the event of a fire. They shall be located along normal paths of travel, including exits from an area. Title 19 Sec. 563.2. Relocate fire extinguisher at exit from classroom 9. No fire hazard shall be permitted Title 19 Sec. 3.14 Remove signs stating "Fire Door Do Not Obstruct" from doorway connecting classrooms 4 and 7. Door is not an exit. Remove obstructions to eve wash station classroom 7. 6 Durham High School Administration Building Extension cords not to replace permanent wiring. 1998 CEC 400-8(1)1 1998 CFC Sec. 8506.1 Permanent hard -wired receptacles required to eliminate power strips; reception area and J. Piacitelli office. Multiple power strips cannot be combined. Multi -plug power strips must have circuit breaker/fuse. 1998 CEC 400-13 Extension strip needs circuit breaker/fuse in J. Piacitelli office. Means of egress illation shall be supplied with two sources of power where the means of egress system serves an occupant load of 100.or more. 1998 CBC 1003.2.9.2 Install required means of egress lighting to all designed exits; install exit signs main corridor. Extinguishers mounted on wall/or in cabinet, visible and signed. Title 19 563.8 Install protruding wall -mounted extinguisher signs at extinguisher cabinets in main corridor. Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Repair hole in wall, Athletic Director office, and men's restroom. Extinguishers mounted on wall/or in cabinet, visible and signed Title 19 563.8 Install extinguisher signs at extinguisher cabinets --north wall and east wall. Exits shall not be obstructed. Title 19 Sec. 3.11, 1998 CFC Sec. 1203 Do not store gym equipment in exit path, main entrance SE double doorway. Exit doors shall be operable from the inside without a key or any special knowledge or effort. 1998 CFC Sec. 1207.3 Center exit door sticking, NW doorway. Stage Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Repair hole in wall, stage. 30 -inch clearance required around all electrical panels. 1998 CEC 110-16a. All panels and breakers are marked 1998 CEC 110-17c Individual circuit breakers must be marked at electrical panel, clearance must be maintained in dressing room. No fire hazard shall be permitted. Title 19 Sec. 3.14 Remove paper from overhead spotlight. Cafeteria/Kitchen Extinguishers mounted on wall/or in cabinet, visible and signed Title 19 563.8 Mount extinguisher signs at all extinguishers, keep 30" clearance. Multi -plug power strips must have circuit breaker/fuse. 1998 CEC 400-13 Extension strip needs circuit breaker/fuse in office and on east wall. h Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Repair hole in wall, men's restroom. Exits shall not be obstructed. Title 19 Sec. 3.11, 1998 CFC Sec. 1203 Clear exit path to doorway, north exit behind kitchen. Install permanent hardwired switch to raise/lower security gate at kitchen entrance. Libr Extinguishers mounted on wall/or in cabinet, visible and signed. Title 19 563. 8 Mount extinguisher signs at all extinguishers, keep 30" clearance. Extension cords not to replace permanent wiring. 1998 CEC 400-8(1)3, 1998 CFC Sec. 8506.1 Permanent hard -wired receptacles required to eliminate power strips, computer room. Multiple power strips cannot be combined. Multi -plug power strips must have circuit breaker/fuse. 1998 CEC 400-13 Extension strip needs circuit breaker/fuse: computer room, librarian office. Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Repair hole in wall, periodical room. Exit illumination and signs in place. 1998 CBC 1003.2.9.2 Emergency lighting and exit signs are required at exits in rooms with occupant load of 50 persons or more, north exit corridor. Exit stairways and corridors shall be kept clear of obstructions and storage. Title 19 Sec. 3.11 Remove all obstructions and stored items from the north exit corridors. Portable Classrooms Extinguishers mounted on wall/or in cabinet, visible and signed Title 19 563.8 Mount extinguisher signs at all extinguishers, keep 30" clearance: classrooms 60, 61, 62 & 63. 100 Building Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), 1998 CFC Sec. 8506.1 Permanent hard -wired receptacles required to eliminate power strips in computer lab. Multiple power strips cannot be combined, classroom 110. Multi -plug power strips must have circuit breaker/fuse. 1998 CEC 400-13 Extension strip needs circuit breaker/fuse: computer lab, librarian office, and classrooms 1039105,10891099 & 110. No fire hazard shall be permitted. Title 19 Sec. 3.14 Clear all decorative paper from electrical outlet 6" in all directions: classroom 107. 30 -inch clearance required around all electrical panels. 1998 CEC 110-16a All panels and breakers are marked. 1998 CEC 110-17c Clear combustible material from under electrical panel: classroom 104. 200 Building 30 -inch clearance required around all electrical panels. 1998 CEC 110-16a All panels and breakers are marked 1998 CEC 110-17c Individual circuit breakers must be marked at electrical panel, clearance must be maintained: DIS 14, science storage room. Electrical panels that are accessible to children without adult supervision must be locked. All standpipe and automatic fire protection systems must have back up wrenches and sprinkler heads available. All standpipe and automatic fire protective systems must have 36"') clearance. Obstructions to exits shall not be placed in the required width an exit; exits shall not be obstructed in any manner. Title 19 Sec. 3.117 1998 CFC Sec. 1203 Exit doorway 204 must be cleared of obstructions and clearly marked "EXIT" on the interior. Remove combustible storage from heater, mechanical, electrical room. Title 19 Sec. 3.19f No combustible storage in hot water heater closet. No fire hazard shall be permitted. Title 19 Sec. 3.14 Remove combustible storage at least 36" around corrosive and flammable storage containers, science storage room. Remove combustible storage 24" from ceiling. Repair hole in ceiling classroom 203. Extension cords not to replace permanent wiring. 1998 CEC 400-8 (1)7 1998 CFC Sec. 8506.1 Extension cords cannot be combined: classrooms 201, 202 & 203. Appliance cords and extension cords shall be kept in good condition with no splices. 1998 CFC Sec. 8504 Appliance cords cannot have splices: classroom 203 stereo. Extinguishers mounted on wall/or in cabinet, visible and signed. Title 19 563.8 Mount extinguisher signs at all extinguishers, keep 30" clearance: classrooms 201, 202 & 203. Poisons in science (ex -photo -lab) storage room cannot be store in glass containers in the sink; they must be stored in approved container and separated from other chemicals. 400 Building Extinguishers mounted on wall/or in cabinet, visible and signed Title 19 563.8 Install extinguisher signs at extinguisher. No fire hazard shall be permitted. Title 19 Sec. 3.14 Install cover to attic access in mezzanine. Extension cords not to replace permanent wiring. 1998 CEC 400-8(1)1, 1998 CFC Sec. 8506.1 Multiple power strips cannot be combined: computer closet Exits shall not be obstructed. Title 19 Sec. 3.11, 1998 CFC Sec. 1203 Relocate metal table away from exit at south door. Secure mezzanine wooden rail to the wall. 9 500 Builain All combustible waste material and rubbish shall be stored in approved containers. T19 3.19b No fire hazard shall be permitted. Title 19 Sec. 3.14 Clean accumulated sawdust from sawdust collection system daily or install larger storage capacity. All waste containers must be metal with attached metal lid and emptied daily, woodworking areas. Large metal dumpster with metal lid between Ag and Auto shop could ease waste problems. Extinguishers mounted on wall/or in cabinet, visible and signed Title 19 563.8 Extinguishers need sign. Obstructions to exits shall not be placed in the required width an exit; exits shall not be obstructed in any manner. Title 19 Sec. 3. 11, CFC Sec. 1203 Move refrigerator on east wall so it does not block exit path to the doorway. Fusible W k on roll up door separating classrooms must be replaced every 6 months. No fire hazard shall be permitted. Title 19 Sec. 3.14 Replace all missing ceiling tiles in wood shop and arts/crafts classroom. Remove obstructions to eye wash station in arts/crafts closet. Secure mezzanine wooden rail to the wall. Arts/crafts classroom and wood shop. No fire hazard shall be permitted. Title 19 Sec. 3.14 Remove combustible storage.from electrical panel in west room connecting arts and wood shop. Recommend installation of larger smoke removal system above arc -welding area to keep toxic smoke from entering GATE classroom. Install protective covers over lights, kiln room. Appliance cords and extension cords shall be kept in good condition with no splices. 1998 CFC Sec. 8504 Appliance cords cannot have splices, electric fan secured to mezzanine rail in arts/crafts. Exit signs shall be provided where two or more exits are required from a room or area, at stair enclosure doors, or where necessary to clearly indicate direction of egress. CFC Sec. 1212.2 CBC Sec. 10 13. 1 Mark exit door that leads to the exterior on south side of Arts/Crafts classroom. Auto Shop No fire hazard shall be permitted. Title 19 Sec. 3.14 Repair hole in ceiling, north storeroom. Clear combustible storage under canopy/awning outside Auto Shop. Replace ceiling panel in classroom. Install protective covers over lights, north storeroom. 30 -inch clearance required around all electrical panels. 1998 CEC 110-16a. All panels and breakers are marked.. 1998 CEC 110-17c Individual circuit breakers must be marked at electrical panel, clearance must be maintained. ZV Extingmhers shall be visible and accessible at all times. Title 19 Sec. 3.29 Lower extinguisher mounted in classroom to at least five feet. Replace electrical junction box on classroom light switch, knockouts must be intact. CEC 110-12 (a) Secure tool cage in open position with lock during school hours. II a All Schools -- Fire Alarms High School: High Repair alarm pull station # 104, unable to pull handle down to trip box. Repair horn in auto shop, strobes activate, but horn does not. Intermediate School: No problems noted. Elementary School: Portable #29 — No horn activation Portable #31— Remove rakes blocking pull station Portable #32 -- Drapes and computer table blocking pull station. Main building — Strobe lights inoperable in main hallways BC VOLUNTEER FIR COMPANIES NGOR IGGS TTE CREEK CANYON TTE MEADOWS HEROKEE LIPPER MILLS HASSET SABLA URHAM F THER FALLS F REST RANCH L D EN FEATH`R. EATER GRIDLEY LLY RIDGE AGALIA N RTH CHICO P LERMO P NTZ VALLEY P ONEER R CHVALE R BINSON MILL S IRLING CITY BCF FULL-TIME FIRE STATIONS B NGOR B GGS D RHAM G IIDLEY LLY RIDGE RD A DRTH CHICO O OVILLE P LER MO R CHVALE SOUTH CHICO U PER RIDGE CDF FIRE STATIONS B JTTE MEADOWS C HASS ET FEATHER FALLS FOREST RANCH HARTS MILL J RBO GAP O 1OVILLE HCS PARADISE ROBINSON MILL S IRLING CITY BUTTE FIRE CENTER GALIA REFORESTATION NU R ERY D VIS GALLA AIR ATTACK BASE C Ico FIRE LOOKOUTS BALD MOUNTAIN BI.00MER HILL PIATTE MOUNTAIN S WMILL PEAK SIJNSET HILL ALSO PROUDLY SERVING CITY OF BIGGS C6 OF GRIDLEY Dr. Penny rhemell District Superintendent Durham Unified School District P.O. Box 300 Durham, CA 95938 Dear Penny: K, it �nsinf LAND OF NATURAL \/VEALTH AND BEAU BUTTE COUNTY FIRE DEPARTMENT CALIFORNIA DEPARTMENT OF FORESTRY AND FIRE PROTECTION "Sixty-seven Years of Cooperative Emergency Services " 176 NELSON AVENUE • OROVILLE, CALIFORNIA 95965-3495 TELEPHONE: (530) 538-7111 FAX: (530) 538-7401 February 6, 2001 In response to your letter of January 30 I have deleted the parking spaces allotted on the west side of the high school gym. The fire lane that extends along the entire west side now intersects with the line that parallels the rear of the gym. (See attached drawing.) In regards to Mr. Wells' complaint I decline to change my original requirements for the following reasons: 1. Mr. Wells' vehicle would block safe and unhampered access to a public way from any of the exit doors along the north side of the gym in the event of an incident where fire engines. fire hose, ambulances. lav enforcement vehicles or personal vehicles may block the required fire apparatus roadway. 2. Parking in the "plane" of the designated fire lane sets the stage for others to do the same --the tendency of the public being "I'll only be a minute" or "if lie can, why can't IT If we can be of further assistance, or you desire additional information or clarification. please contact Fire Captain Steve Fowler at (534) 538-7888. Cc: Chrono � Bill Orthel Dave York BCFD Station 45 file Sincerelv. William R. Sager Fire Chief Bv: Steven J. Fo r Life Safety macer Durham Elementary School CSFM #0007-000-555-9 AULT WURPOSE ROOM Al[ panels and breakers are marked. 1998 CEC 110-17c Individual circuit breakers must be marked at stage electrical panel Exit illumination and signs in place. 1998 CBC 1003.2.8.2 Backup exit illumination must be in good working order. Exits and fire alarm pull stations shall not obstructed 1998 Title 19 Sec. Relocate metal table away from exit and fire alarm pull station. 3.11, 1998 CFC Sec. 1203 • Remove combustible storage from heater, mechanical, electrical room. 1998 Title 19 Sec. 3.19f No combustible storage in hot water heater closet. . 30 -inch clearance required around all electrical panels. 1998 CEC 110-16a Remove wire rack stored in front of circuit breaker in Baker room. RARY Exit illumination and signs in place. 1998 CBC 1003.2.9.2 Emergency lighting is required at exits in rooms with occupant load of 50 persons or more. Repair holes in fire resistive construction. 1998 CEC 300-21, 22 Repair hole in wall at all call receptacle, computer room. Extension cords not to replace permanent wiring. 1998 CEC 400-8(1),1998 CFC Sec. 8506.1 Permanent hard -wired receptacles required to eliminate power strips, computer room. Multiple power strips cannot be combined CORRIDORS Exit stairways and corridors shall be kept clear of obstructions and storage. 1998 Title 19 Sec. 3.11 Remove all obstructions and stored items from the North &South exit corridors. Means of egress illumination shall be supplied with two sources of power where the means of egress system serves an occupant load of 100 or more. 1998 CBC 1003.2.9.2 Install required means of egress lighting to all designed exits. Extinguishers mounted on walUor in cabinet, visible and signed 1998 Title 19 563.8 Remove paper display from exterior of extinguisher cabinet, South corridor. Install protruding mounted extinguisher signs at extinguisher cabinets, North &South corridors. ASSROOMS Obstructions to exits shall not bep laced in the required width an exit; exits shall not be obstructed in any manner. 1998 Title 19 Sec. 3.11, 1998 CFC Sec. 1203 Classrooms cannot have teacher desks or chairs blocking the required exit to the open yard area, at any time. Combustibles must be kept at a distance from heating appliances as indicated on the appliance listing. 1998 CFC Sec. 1107.1, 1998 CFC Sec. 1109.2 Microwave in classroom 6 must have clearance. Glue guns in classroom 32 must be stored on fire resistive surface. 3. Repair holes in fire resistive construction. 1998 CEC 300-219 22 Cover cable outlet in classroom 15. 4. Extension cords not to replace permanent wiring. 1998 CEC 400-8(1),1998 CFC Sec. 8506.1 Multiple power strips/extension cords cannot be combined; classrooms 9, 11, 40. 5. Mul -plug power strips must have circuit breakepfuse. 1998 CEC 400-13 Extension strip needs circuit breaker/fuse; classroom 10. 6. Exit doors shall be oP erable from the inside without a key or any special knowledge or effort. 1998 CFC sec. 1207.3 Exit door sticking; classroom 10. 7. No fire hazard shall be permitted. 1998 Title 19 Sec. 3.14 Keep fire alarm pull box clearly visible and accessible; Learning Center. Keep fire alarm indicator clearly visible, classroom 38. ka Durham Elementary School CSFM #0007-000-555-9 LM N oFNCE . Extension cords not to replace permanent wiring. 1998 CEC 400-8(1), CFC Sec. 8506.1 Multiple power strips/extension cords cannot be combined; nurses office. • Repair holes in fire re"ve construction. 1998 CEC 300-219 22 Cover opening in wall near the speaker; nurses office. ANITOR CLOSET 30 -inch clearance required around all electrical panels. 1998 CEC 110-16a Remove accumulated combustibles around fire alarm control panel. 4 Af To /1t css,v.) Alir. cf- Ee-tgt6u (PtfS.K c t.mac_ S r AIS +AJO G, Z . Apo",t10 tP,e�C.c�rn� `` S� Pis ro ,���•�G La ; a/� T-'� Ajv /PAW�14 /-J %) -I— (Ole" . 3 lq-d o "Ad ��,,,.� '-ne t p,Es l4No S14.)s 1 rJ �"A)T OA -I-6V- Q . Soti. 4�0 CA bIC7 GYeM S. W,*f- "F,).o tom" gym tf n/T 2g S %/ fit/ ��7✓ /CTS ��d+n%� d� �Cf'�17 T- T XW Varma t'CeA�Z-- ✓E l ,f C714 AAO J'& �A,)4 . 1p� /Ylf}-��cJ-r�-,^l i�- % �2.� L�4-�'✓� �uG tf �.�n Sc,FoP /� rMoP ��. �'3.4� C� -sT- /-5— FEVT- (1)tDE . 4V January 30, 2001 176 Nelson Avenue Oroville, California 95965 Dear Steve: DURHAM UNIFIED SChj0L DISTRICT Penny Chennell, Ed.D., District Superintendent P.O. Box 300 Durham, California 95938 Telephone (530) 895-4675 Facsimile (530) 895-4692 http://www.bcoe.butte.kl2.ca.us/durhanV BOARD of TRUSTEES: Linda Boles Michael McDonald Bill Orthel Tom Simmons Donna Killoran During your recent DUSD fire and safety inspections, one recommendation involved marking a fire land at Durham High School on the Werth side of the m'?it1YUTpnBP roOIT'a and gy Tlr-slUm. building. The specific mandate was as follows: • Run a line the entire length of the building from corner to corner (beginning at the kitchen freezer area and continuing to the corner of the boys' locker room) • Put in parking areas on the west side of the boys' locker room from the north corner up to the designated fire lane. It has come to my attention that this requirement would negatively affect one of our high school teachers, W. Bill Wells, who currently parks his vehicle on the north side of the gymnasium behind the locker room area. To accommodate his parking needs, I ask that you consider the following proposals: Leave the last section of wall on the north side of the building (the boys' locker room) for one parking space that Mr. Wells can use during the school day. This space does not block the entry to any door and affords visiblity for the vehicle. It allows Mr. Wells to access his vehicle for an emergency. In addition, he can haul equipment to and from the fields throughout the school day. Leaving one designated space known to staff and students and a clearly marked fire lane line should not encourage people to park next to the building. Parking spaces at the west side of the locker room (behind the boys' locker room) will bloc visibility at the turn and leave cars out of view and unprotected all day. (O I appreciate you responding to this request at your earliest convenience.��� Sincerely, Penny C�, Ed. D. Superintendent DURHAM ELEMENTARY SCHOOL DURHAM INTERMEDIATE SCHOOL DURHAM HIGH SCHOOL ELIZABETH T. CAPEN STEPHEN J. PILUSO PAUL ARNOLD PRINCIPAL PRINCIPAL PRINCIPAL Telephone (530) 895-4695 Telephone (530) 895-4690 Telephone (530) 895-4680 Facsimile (530) 895-4665 Facsimile (530) 895-4305 Facsimile (530) 895-4688 MISSION HIGH SCHOOL STEPHEN J. PILUSO PRINCIPAL Telephone (530) 895-4690 9'-8" from building to new o dire Lane (second / ' concrete expansion cut north of building.") i DURHAM HIGH GYM MINIMUM 20' FD ACCESS REQUIRED W z g 3: W W Z NEW FIRE LANE 4" wide RED stripe with WHITE "FIRE LANE - NO PARKING" PAINTED IN CENTER OF STRIPE OR IN RED ABOVE STRIPE. (Typ.) i TITLE: FIRE LANE REQUIREMENTS--NIVi PARKING LOT nURHAM HIGH SCHOOL Rte./• '+ '��,�•���'��. .-..:tib ./.' / �.) / Iy�J • /.: Ar Or BC D VOLUNTEER FI COMPANIES ANGOR IGGS UTTE CREEK CANYON UTTE MEADOWS HEROKEE UPPER MILLS OHASSET eSABLA URHAM FATHER FALLS OREST RANCH OLDEN FEATHER GREATER GRIDLEY KELLY RIDGE MAGALIA NORTH CHICO PALERMO PENTZ VALLEY PIONEER RICHVALE ROBINSON MILL STIRLING CITY THERMAUTO BC FD FULL-TIME FIRE STATIONS BANGOR BIGGS DURHAM GRIDLEY ELLY RIDGE CORD NORTH CHICO OROVILLE PALERMO RICHVALE SOUTH CHICO UPPER RIDGE C F FIRE STATIONS BUTTE MEADOWS COHASS ET FEATHER FALLS FOREST RANCH HARTS MILL JARBO GAP OROVILLE HO PARADISE ROBINSON MILL STIRLING CITY B JTTE FIRE CENTER MAGALIA R EFORESTATION N RSERY DAVIS MAGALIA A R ATTACK BASE CHICO F1 RE LOOKOUTS BALD MOUNTAIN BLOOMER HILL PLATTE MOUNTAIN SAWMILL PEAK SUNSET HILL SO PROUDLY SERVING CITY OF BIGGS CITY OF GRIDLEY Christy Patterson, Business.Manager Durham Unified school- District P.O. Box 300 Durham, CA 95938 Dear Christy, Ma �uite Count LAND OF NATURAL WEALTH AND BEAUTY BUTTE COUNTY FIRE DEPARTMENT CALIFORNIA DEPARTMENT OF FORESTRY AND FIRE PROTECTION "Sixty-seven Years of Cooperative Emergency Services" 176 NELSON AVENUE • OROVILLE, CALIFORNIA 95965-3495 TELEPHONE: (530) 538-7111 FAX: (530) 538-7401 January 2, 2Q01 I have reviewed your letter of December 15, 2000 and agree to your projected timelines, except for item number 11. I will review the need to move the existing handicap parking space with Mr. York. 'The exiting from the Durham Intermediate Gym was one of our primary concerns whin the access issues were first brought to my attention. I have attached a drawing of the fire lane requirements for the northwest parking lot behind the gym. Placing the fire lane in the location shown allows the minimum 20' fire apparatus access lane required. It also allows clear passage for any person exiting any north - facing door to the "public way." Thank you for your rapid response to all of the issues. It has been -.nd I'm sure will. continue to be a great working relationship. Sincerely, William R. Sager Fire Chief By: Stev n J. wler Life ety Officer CC: W. OFtlel BCFD Sta. 45 Chrono 1, / W z g W LL W z MINIMUM 20' FD ACCESS REQUIRED W z g W W U- R. W z 9'-8" from building to new 0 Fire Lane (second "concrete expansion cut / north of building.") DURHAM HIGH GYM PARI )ACE NEW FIRE LANE - 4" wide RED stripe with WHITE "FIRE LANE - NO PARKING" PAINTED IN CENTER OF STRIPE OR IN RED ABOVE STRIPE. TITLE: FIRE LANE REQUIREMENTS --NW PARKING LOT DURHAM HIGH SCHOOL C a b December 28, 2000 Dr. Penny Schanell, Superintendent Durham Unified School District P.O. Box 300 Durham, CA 95938 Ref: Durham Elementary School and all schools fire alarms Dear Penny, An inspection of the referenced facility was recently conducted in accordance with Section 13145 of the California Health and Safety Code. The purpose was to determine compliance with the minimum fire and life safety standards required by Titles 19 and 24 of the California Code of Regulations. The attached report is to advise you of the actions that are required to correct noted deficiencies. To insure this facility is brought into compliance within a reasonable time, please submit your plan for accomplishing these corrections, to this office, within 30 days from receipt of this notice. If you have already corrected these deficiencies, please advise us so we can make an appointment for a reinspection and update our files. If I can be of further assistance, or you desire additional information or clarification, please contact me at the CDF Fire/Butte County Fire Department Fire Prevention Bureau headquarters, (530) 538-7888. Sincerely, William R. Sager Fire Chief By: Steven J. Fowler Life Safety Officer Durham Elementary School and all schools' fire alarms systems Nov. 22, 2000 Multi-purpose ,room: 1. Stage electrical circuits not marked as to what they serve. [1998 CEC 110-17(c)] Identify individual circuits by labeling in breaker box. 2. Exit sign battery backup out of service. [ 1998 CBC 1003.2.8.2] Replace battery. 3. Metal table blocking exit and fire alarm pull station. [Title 19 CCR Section 3.11] Move table. Kitchen• 1. Combustible materials too close to water heater. [Title 19 CCR Section 3.19 (f)] Move all combustible materials to a minimum of 36" from water heater (if heater is in a closet, remove all combustible materials from closet. 2. Wire rack stored in front of electrical circuit panel. [1998 CEC 110-16(a)] Move rack to another location, 36" clearance required around panel. Library: 1. Hole in wall at "all call" receptacle in computer room. [1998 CEC Section 300-21,22] Repair bole with fire resistive materials. 2. Multi -plug power strips in computer room combined to reach wall plug receptacle. [1998 CEC Section 400-8(1) Provide Permanent wall plug. Exit Corridors: 1. Corridors used for storage (table, chairs, other classroom equipment). [Title 19 CCR Section 3.11 (a,b,c)] Consult with Butte County Fire Department Life Safety Officer on items to be removed. 2. No emerggncy exit lighting in corridors. [1998 CBC 1003.2.9.2] Install emergency exit lighting in corridors serving classrooms. 3. Paper covering extinguisher cabinets, cabinets not marked conspicuously. [Title 19 CCR 563.8 (a,b)] Remove all paper covering.fire.ex#inguisher cabinets. Place "Fire Extinguisher" signs above. cabinets mounted perpendicular to wall. ® I e Classrooms 1. Teacher disks and/or chairs blocking exits to exterior. [Title 19 CCR Section 3.11] Move desks to facilitate clear exiting to exterior of building. 2. Microwave in classroom 6 covered with combustible materials; glue guns in room 32 used on combustible surface. 11998 CFC Section 1107] Remove combustible materials from microwave; use and store glue guns on fire resistive material. 3. Cable outlet in room 15 allows hole in wall. [ 1998 CEC 300-21,22] Repair holes in fire resistive construction. 4. Multi -plug power strips combined to lengthen and reach wall plugs in rooms 9, 11, 40. [1998 CEC 4008(1)] Provide permanent wiring to eliminate multiple "in-line" power strips. 5. Classroom 10 has non -surge protected power strip. [1998 CEC 400-13] Replace with circuit breaker protected strip. 6. Exit door 'in classroom 10 difficult to open. [1998 CFC Section 12073] Lubricate door or modify clearance between door and jamb to ease effort to open. 7. Fire alarm pull stations and indicator panel (classroom 38) not accessible or visible. [Title 19 Section 3.14] Remove obstructions blocking pull stations and indicator panels. Main Office: 1. Multi -plug power strips combined in nurse's office. [ 1998 CEC 400-8(1)] Add permanent wall plug receptacle. 2. Wall open near speaker in nurse's office. [ 1998 CEC 300-21,22] Repair hole in fire resistive construction. 1. Combustibles blocking access to fire- alarm panel. [ 1998 CEC 110-16-a] Minimum 36" clearance required around fire alarm panel.