HomeMy WebLinkAbout040-180-062_10_29_85-3_6_01.3Page 1 of 1 la Fowler, Steve From: BTU Durham Stn Sent: Tuesday, December 19, 2000 1:51 PM To: Orthel, Bill Cc: BTU Durham Stn; Fowler, Steve Subject: Fire alarm test, Durham school district Chief: Did the alarm test for the school district today and found the following problems: High school: Need to repair alarm box # 104, unable to pull handle down to trip the box Repair horn in Auto shop. Strobes activate, but no horn upon tripping of the box Intermediate school: No problems noted. Elementary school: Portable # 29, No horn upon activation. Portable # 31, Remove rakes in front of pull station. Portable # 32, Drapes, computer table hiding pull station. Main building, strobe lights inoperable in main hallways. Also, per Captain Fowler, I showed grounds maintence how to mark out restricted area in front of and around FDC connection on North side of gym. I found the maintence staff to be very helpful while doing the above inspections. #1,Qu,ve any questions just ask. COds.,.Haile Capin St�,45 2/19/01 Page 1 of 1 Fowler, Steve From: BTU Durham Stn Sent: Monday, December 18, 2000 8:57 PM To: Fowler, Steve; BTU Durham Stn Subject: DUSD warehouse Steve, We took a quick look at the pesticide room again and found it padlocked. At least 30 gallons of pesticide/herbicide including Direx 80 DE, Trimec, Balan 2.5G (100# + powder), SurPlan and Phostoxin (6 canisters.) Also explosive 1.4 stored in room, a gas used to kill gopher/rodents. No one hour fire construction, no ventilation. Mr.. York very defensive. MSDS binder there, didn't check for every substance listed but had at least 20 MSDSs. The electrical room still not locked, he states very little electricity in the room now, all the hazard signs were needed before electrical system was overhauled. Asked him to lock the room and he stated "Didn't have time for it today would do it tomorrow, besides kids are gone for two weeks for winter break" Definite attitude. Issued facility inspection form stating it must be locked in 7 days. Will reinspect next Monday. Will ask my partner Chris to test the fire alarms tomorrow if he has time. Shannon Garrett Butte County Fire Durham Station 45 12/19/00 December 15, 2000 DURHAM UNIFIED SCHu0L DISTRICT Penny Chennell, Ed.D., District Superintendent P.O. Box 300 Durham, California 95938 Telephone (530) 895-4675 Facsimile (530) 895-4692 http://www.bcoe.butte.kl2.ca.us/durham/ BOARD of TRUSTEES: Linda Boles Michael McDonald Bill Orthel Tom Simmons Donna Killoran Steven J. Fowler, Life Safety Officer Butte County Fire Department 176 Nelson Avenue OrVVille, CA 95965-3495 Dear Officer Fowler: Thank you for your recent visits to our campus and the help you and Bill Orthel have provided in bringing our fire apparatus access, hydrant clearance and vehicle movement and parking into compliance. The following is a report on the current status as well as projected timelines for completion of each of the numbered items denoted in your letter of November 30, 2000: 1. we are in the process of designing a sign with your recommended language as well as similar language necessary to comply .with the. Am e 'cans with Disabilities Act. This should be installed by February 28, 2001. �o 2. A minimum 10' red curb has been painted on both sides of each fire hydrant and some have been stenciled with "No Parking, Fire Lane". The signage and balance of the stenciling will be completed by January 31, 2001.&)Z>,- 3. Signs as requested have been installed and Dave York will contact the Station 45 to determine where the yellow lines should be. The painting will be completed by January 31. 4. We are in the process of determining how to best address the deletion of the existing fire lanes not designated as such and will either repaint them as passenger loading zones or have all paint removed entirely. This should be completed by February 28. 0-y�. 5. This item is nearly done and should be complete by February 28. ,6%v 6. This is completed. 7. Dave York will be contacting you to clarify how best to address this issue and we should be able to complete it by February 28. DURHAM ELEMENTARY SCHOOL DURHAM INTERMEDIATE SCHOOL DURHAM HIGH SCHOOL ELIZABETH T. CAPEN STEPHEN J. PILUSO PAUL ARNOLD PRINCIPAL PRINCIPAL PRINCIPAL Telephone (530) 895-4695 Telephone (530) 895-4690 Telephone (530) 895-4680 Facsimile (530) 895-4665 Facsimile (530) 895-4305 Facsimile (530) 895-4688 MISSION HIGH SCHOOL STEPHEN J. PILUSO PRINCIPAL Telephone (530) 895-4690 Steven J. Fowler, Life Safety Officer December 15, 2000 Page Two This should be completed by February 28. 9. Dave has measured the gate at 12.5 feet. We plan to have a pedestrian gate installed to the north of the existing gate by February 28 and the existing gate will then remain locked in the normal manner. eirlz-� 10. Signs have been installed on two of the five gates and the balance should be done by February 28. 11. As this involves moving an existing handicap accessible space, this item will be included as part of the striping to be done by a professional contractor in the summe of 2001. 12.-14. 14 C_ We will include these in the plans for the future installation of any additional portables classrooms on our campus. Although we are working to complete each of these items as soon as possible, the da es noted above are based on weather permitting for items involving painting. Again, thank you for your guidance and cooperation in addressing these issues. Our office will be closed from December 20, 2000, through January 2, 2000, but please feel free to leave me a message at 895- 4675, extension 222 and 1 will return your call. S' cerelkerrson Z'a y Business Manager cc: Bill Orthel, November 30, 2000 Dr. Penny Chennell, Superintendent Durham Unified School District Putney Drive, Durham, CA 95938 Dear Dr. Chennell, I was recently appointed Butte County Fire Department's Life Safety Officer (Fire Marshal). My duties include conducting Title 19 Panic and Life Safety Inspections that were previously the responsibility of the California State Fire Marshal Fire Captain Ted Crawford passed to me the job he had been doing to determine better fire apparatus access, fire hydrant clearance, and staff and visitor vehicle movement and parking within the District's boundaries. I have attached a list and a map that show where fire lanes shall be designated; where fire lanes may be deleted, where gates should be placed or widened; and, where building egress shall be marked and maintained. Each item has a corresponding number on the campus map. Items numbered 1 through 11 must be completed by December 28, 2000; items 12, 13 and 14 are to be discussed and negotiated prior to the addition of any new portables or new construction. Once you have had time to review this list I would like to schedule a meeting with you and your staff to assist with the implementation of each of the items. Sincerely, William R. Sager Fire Chief By: Steven J. Fowler Life Safety Officer Cc: B. Orthel G. Morris Chrono November 223, 2000 Dr. Penny Schanell Durham Unified School District P.Q. Boas 300 Durham, CA 95938 Dear Dr. S Subject: Durham Elementary School CSFM #0007-000-555-9 An inspection of the referenced facility was recently conducted in accordance with Section 13108C of the California Health and Safety Cootie. The purpose was to determine compliance with the minimum fire and life safety standards required by Titles 19 and 24 of the California Code of Regulations. The attached report is to advise you of the actions that are required to correct the noted deficiencies. This facility needs to be brought into compliance within 14 days. If we can be of further assistance, or you desire additional information or clarification, please contact me at the Durham Fire Station, (530) 891-2788. Sincerely, Shannon M. Garrett Fire Apparatus Engineer Butte County Fire Department s Cr R C TENANCE 1. i't cords not to replace permanent wiring. 1998 CEC 400-8(1),1998 CFC Sec. 8506.1 Pe ANhard-wired receptacles required to eliminate multiple power strips. Power strips cannot be combined. Office bus scheduling area. t344ach clearance required around all electrical panels. 1998 CEC 110-16a AWA=Wical panels in bus maintenance building. 3. Alt panels and breakers are marked. 1998 CEC 110-17c Mark all breakers at control panel. 4. Combustible waste containers larger than 40 gallons must be made of metal or have a maximum heat release rate as allowed the Fire Code. 1998 CFC Sec. 1103.2.1.4 plastic waste containers larger than 40 gallons must be replaced with metal containers. ka ATHLETIC DEPARTMENT 0 1. Remove combustible storage from heater, mechanical, electrical room. 1998 Title 19 Sec. 3.19f Remove combustible storage in electrical building next to football tower. ", Extinguishers shall be serviced annually and shall have a current service tag attached: 1998 Title 19 Sec. 3.29 Obtain an annual service for the fire extinguisher in the baseball tower. CkI De 0 e 9Publicof Works 0 o u n t o f B u t t e 0 0 0 0 i County, Center Drive J. Michael Crump, Director Orovillt�, CA 93965-339 A oV N (530)338-7/6,41 L. ,o w�¢�5 Warner C. Phillips, Assistant Director (FAX) 538-7/683 November 21, 2000 Mrs. Penny Chennell. Superintendent Durham Unified School District P.D. Box 300 Durham, CA 95935 Re: Traffic/Circulation — Durham Schools Dear Penny: I want to thank you for inviting me to meet with you on October 27, 2000, to discuss the traffic and circulation issues in and around the Durham Schools. I would like to provide volt with the following summary of my comments and ideas we discussed. C� Midwav -- The County' has designed and budgeted for the coi1sr-LICtion of a left torn pocket on the Midway at the entrance to the Midway baseball fields. This project is planned for construction during the summer of 2001. When complete. this intersection will provide safe ingress/egress from this area. Durham Dayton Highway — The existing unimproved access to the Durham Dayton Highway located behind the football/baseball fields will need improvements before it should be used on a regular basis for school ingress/egress. The posted speed limit along this section o Durham Davion Highway is 25 mph. A dedicated left turn pocket is probably not warranted at this location. A standard County road approach (attached) WDWN need to be constructed prior to this access being open on an ongoing basis to school rraffic. The standard road approach would require the removal of some landscaping, fronting the yards of the adjacent homes. The school district should also consider paving the access road to minimize dost that will affect the neighbors. An additional concern the school district should consider before inoving too far forward on this access option is the impact of more vehicles traveling past the baseball fields and spectator stands, which are located in the area_ Putney Drive -- As we all know, Putney Drive, as well as the internal school roads in this area. are veru congested dciring the periods before and after school. 11�Iy experience when dropping nay son off at school is that it can often times take me 5-7 minutes to be able to turn left onto Durham Dayton Highway from Putney DrI'Ve. While this delay and congestion is often frustrating, I have not observed any ny significant traffic safety issues. The congestion requires all vehicles to drive slowly in this area. which provides the driver every opportunity to observe and avoid interactions with pedestrians and other vehicles. The CHP has also been veru active in their enforcement of the 25 mph speed limit when children are resent in the scat p pool zone along Durham Darton Highway. Emergency access to the schools during the periods of heavy congestion is a concern that should be addressed. I recommend that the school district meet with the area's emergency response agencies and develop a plan on how they would access the Ppy P school grounds during an emergency. I would be more than ha to be art ofthis meeting. Cl Potential new driveway access from elementary school parking lot: I would suggest that the school district not consider developing a new driveway access from the elementary school parking area onto Durham Dayton Highway. I believe this new access route would create additional conflicts between vehicles and school children. This new rote would be viewed by many vehicles from both the hi rh Schoul tand middle school as a short cut or reliever from the Putney Drive congestion. Also, vehicles using this proposed driveway and turning left onto Durham Dayton Highway Y g y would only add to the traffic going east on Durham Hayton Highway past Putney Drive, which would result in more delay on Putney Drive. Again I wish to thank you for allowing me to review and comment on the school district's traffic and circcilation issues. 1 would be happy to continue to work with you and your Board on this issue. Sincerely. Mike Crump Director of Public Works MCIj m Attachment .. W. -W ON ouvoNvis ALNnoo NOi103NN00 CVOUol` enci k, smaom onand dO 1N31N1ki'bd3CJ 0313103dS SV HIM CV08 M7 {1d018AMMS N011 MUINI) 11 04, IN3M3Avd J0 3003 - r -_ - -�- - , -ti a3ainoHs � .s G BUTTE COUNTY-FIRE-BEPAikTiM£NT/CM FIRE TITLE 19/24 INSPECTION NO. '1 2 3 FACILITY INSPECTION REINSPECT: y/YES NO Facility Occupancy Address Inspector Ph ar f3& Station Contact Station Phone AV -1-t -.1,m a Compliance: Yea No a 0 Not applicable - NIA ACCESS — All Inspections ELECTRICAL —All inspections Address Offlnod M and visible from road OAP Co. Cone 32-M Access to public stroot or 2D R. wide lone frlsa.0s) Getes wide enough to 8*9 lire eppW0111 a (r1a3.1et Fire protection equipment vis�laiblo (ri" m PORTABLE FIRE EXTINGUISHERS — All {tsspsctiotls Extingutetxers have current annual service tag (r1s srs. m) Maximum travel 75 ft. (rig -ser) Provide clear access to fire 04in9uiaher (Treses 2) Extinguishers mounted on *vW in cabinet, visible and signed massa a) EXITS — All Inspections Exits not obstructed (r," 11) Exit signs in piece (CDC 1003 2 9 tt), :.1 Doors without key or special kvtorrledge (CFC 1207 3) Rooms with Occupant Load of 50 Persons or More Exit MuminNon and signs in place (COC 1003 28.2) Modmum occupancy sign in piece Cr1s3 301 Two exit doorsfpanic hardware swing in direction of trawl tele 2so1 a 2) HOUSEKEEPING; —All Inspections No waste or ruhbish accumulation malts or outside T1a.3.14) Reduce storage to at least below cel npl sprinWsts 010 3.1 h Remove oombrn. slaps hom Mater. mesh., clad. room (T1a�.1eq Provide approved metal Winer for * rag storage (r.,aa.lsy Flommoble k lukle stared property (T-1"131 Extension cords do not replace permanent Wiring (CECAM-6 1)) Extension cords do not pass through doorsANaHs (cec.-daps (2.3)) 3D inch clearance around all electrical ponds mE(r11a16A) A!I panels and breakers are marked iCEC- 110-11 C) Repair holes in fire -resistive Construction crc (300.21.22) Mulb-plug power strips have circuit breaker (CES: 400.13) FIRE PROTECTION EQUIPMENT — Ali inspections Hood system servicedltagged every 6 mo. by cart. tech. (r19-eoa) Cken fritters. hood. and duct area over cooking appliances (crc 1006 2 t tlliai Wn extfnguishinQ Systems (rill -3 74) Provide spare sprinkler heeds (6 min.) andfor sprinkler wrench (Theca s) Replace damaged, corroded, or painted sprinkler heeds (rr9•ew s) Identity sprinkler valves and secure in open position (rv;Lw4.$) Replace missing caps on fire department connection (TiQ.ea 3) Provide Syr. certification test for sprinkler/standpipe (T 10404) MECHANICAL EQUIPMENT — All Inspections Vents and otwnneys — No obvious N L%Kds (cmcch 8) SMOKE DETECTORS — Day Care Sr. Res., Hospitsts, Apts. Property installed and tested (T19 719 Tse) SCHOOLS, JAILS AND HOSPITALS Docorationsandcurtains fie retwdent (Tis -3 08) IPG tanks fenced with iod0d 9310% ("" 2Z FiRE DRILLS — School and Day Caro Willa 19-3.131 AA systems oppablSRaaked to office Held monthly (elementary *&mus) Held semi-wwwally thigh schools) Evacuation pians posted in dt rooms Emergency prooeduras posted in office Teachers take roll books The above deficiejacies ust be corrected within days. Inspection Date: 1 BUTTE COUNTY 1~IRE DEPARTMENT/CDF FIRE TITLE 19/24 FACILITY INSPECTION INSPECTICN NO (D 2 3 RE11ivSPE--T. YES }( NO Facility J r�' h0 'Occupancy (1'c6,14 l�,a� Address�P�f �r - DUrhra �,� Inspector �>I /2z Phone uyS'r- Al &7S Station Contact Station Phone Compliance: Yes ACCESS — All inspections AddrQss eorrecttposted and visible from road (ao4e co code 12-9) Access to public street or 20 ft. wide lane (719.3 05) Gates wide enough to admit fire apparatus Ttg-d 161 fire protect;on equipment visible/accessible ;7196.3141 PORTABLE FIRE EXTINGUISHERS •- All Inspections Extinguishers have current annual service tag cr19-sus 1A1 Maximum travel 75 ft. IT -9-567) Provide clear access to fire extinguisher ;719-5e3 -2} No s 0 Not applicable - N/A Extinguishers mounted on wall/or in cabinet. visible and signed r719.563 A) EXITS -- All Inspections Exits nct obstructed 1719-3111 Jtf S y X: SM 14— tsJ q Exit signs in place (CBC r003 :: s 1; pac Doors operate without key or special knowledge (CFC 12077 3) Rooms with Occupant Load of 50 Persons or More Exit illumination and signs in place tcsc 1oo3 2 a �) Maximum occupancy sign in place (T19.3 31711 Two exit doors/pantc hardware swing in direction of travel ;crc 2so1 s _) HOUSEKEEPING -- All Inspections No waste or rubbish accumulation inside or outside T19-31 41 Reduce storage to at least below ceiling/ sprinklers {T1S3 1a} Remove combus. storage from heater, meth., elect. room rr19.3 IM Provide approved metal container for oily rag storage (r-19.3 190 Flammable liquids stored property (T-179-3 t5) Corrections and Comments ELECTRICAL -- All inspections Extension cords do not replace permanent wiring CFGa04Arr1 Extension cords .10 not pass througn doors/walls CEC -*C a n 3)) 30 incn clearance arouna all elecmcai panels =•O.!eA) All panes orearcers Ire marked .. . Repair holes .n tire-esist,ve construction - -,,. _,. Multi -Plug power strips rave circuit breai(er c=_ ,� -To.t-1 FIRE PROTECTION EQUIPMENT — All Inspections 'food system seraceattagged avery 5 mo by cert tech '-19.904) Clean filters hood. ana duct area over cooking appiiances (CrC '006 2 8) Maintain extrnguishnu systems .!-L---v Prov de spare sprinkler heads 176 min i and/or sprnkler wrench (7.19-s04 5) Reptace damaged, corroded. cr painted sprinkler heads T19 -90a 5) Identify sprinkler valves and secure in open position ,r9 Vna s Replace missing caps on fire department connection r, 9-9o4 3) provide Syr. certification test for sprinklerlstandpipe Ti 9-9o4) MECHANICAL EQUIPMENT -- All Inspections Vents and chimneys -- No obvious hazzards (cv1C-:7h 9) SMOKE DETECTCRS -- Day Care Sr. Res., Hospitals, Apts. —Property installed and tested -L-as -54? SCHOOLS, JAILS AND HOSPITALS Decorations and curtains fire retardant (T19-5 C87 _PG tanks fenced with locked gates ,x196.3 r) FIRE DRILLS -- School and Day Care (Title 193.13) All systems operablelhooiced to office Held monthly (elementary schools Held semi-annually (high schools) Evacuation plans posted in ail rooms Emergency procedures posted in office Teachers take roil books r a -a fep- -t-e3 1-n SS r P4 -,c 11 / of XLr -r C2 SIV P P 4J -41 -to ' aCCe SS � +v JP0 e- 61 e 5 - The above deficiencies must be c rrected within days. Inspection Date: OwnerNanager AP k BUTTE COUNTY FIRE DEPARTMENT/CDF FIRE TITLE 19/24 INSPECTION NO. (D 2 3 FACILITY INSPECTION REINSPECT: ? � YES � i NO Facility. Wfhn M Occupancy ST_�_nn 'i'T Address Pu- NJf0_u Dr• _ Inspector j p,.-* Phone Station --3 Contact Q Station Phone -..I.-- . �_ —,if ACCESS -All inspections Address correct/posted and visible from road (aura co. cod* 32-9) Access to public street or �0 ft. wide lane 719.3.05) Gates wide enough to admit fir apparatus (rise ra) Fire protection equipment visible/accessible (r193.14) PORTABLE FIRE EXTINGUISHERS - All Inspections Extinguishers have current annual service tag (r19.575.1A) 11W - v Not appucaote = NIA Maximum travel 75 ft. (r19S87) Provide clear access to fire extinguisher (r19.5e3 2) Extinguishers mounded on wall/or in cabinet, visible and signed (r%.,w.e) EXITS — All Inspections Exits not obstructed (r19-3.11) Exit signs in place (cat 1003.2.9.1) Doors operate without key or special knowledge (cFc 1207.3) Rooms with Occupant Load of 50 Persons or More Exit illumination and signs in place (CBC 1003.2.8.2) Maximum occupancy sign in place (x193.30) Two exit doors/panic hardware swing in direction of travel (cFc 2soi a.z) r HOUSEKEEPING - All Inspections No waste or rubbish accumulation inside or outside T19-3 i4) Reduce storage to at least below ceiling/ sprinklers (T193 141 Remove combus. storage from heater, meth., oW. room.-er'i'93.1" Provide approved metal container for oily rag storage (T•193.19c) Flammable liquids stored property (r-1&3 tis) Corrections and omments du v- ► bJ q ELECTRICAL -All inspections Extension cords do not replace permanent wiring (cEc-aaa-alp) Extension cords Qo not pass through doorsAvalls (cec_4w a (2.3)) 30 inch clearagye around all electrical panels (cEG11a1aA) ___All panels and bre01k &are marked (CE 10-17 c) Repair holes in fire -resistive construction cEc (300.21.22) Mufti -plug power strips have circuit breaker (cec 40o-13) FiRE PROTECTION EQUIPMENT —All Inspections Hood system serviced1lagged every 6 mo. by cert. tech. (nq-w4) Clean fitters, hood, and duct area over cooking appliances (cFc 1o09.2.6) Maintain extinguishing systems (r19•.3.24) Provide spare sprinkler heads (6 min.) and/or sprinkler wrench (r19-904.5) Replace damaged, corroded, or painted sprinkler heads (T1a9oa.5) Identify sprinkler valves and secure in open position (r19-904.$) Replace missing caps on fire department connection (rig -904.3) Provide 5 -yr. certification test for sprinkler/standpipe (T19.90 t) MECHANICAL EQUIPMENT — All Inspections Vents and chimneys — No obvious hazards (cenach a) SMOKE DETECTORS — Day Care Sr. Res., Hospitals, Apt*. Properly installed and tested (rig -749.:54) SCHOOLS, JAILS AND HOSPITALS Decorations and curtains fire retardant (n9.3.08) LPG tanks fenced with locked gates (x19-322) FiRE DRILLS - School and Day Care (Title 183.13) All systems operableJhooked to office Held monthly (elementary schools) Held semi-annually (high schools) Evacuation plans posted in all rooms Emergency procedures posted in office Teachers take roll books The above deficiencies must be corrected withinrY. days. Inspection Date: Owner/Manager & LA. AP # uthor: BILL ORTHEL at BUTTU ate:- 8'/24/98 12:17 PM riority: Normal 0: KAREN PITTMAN at BUTTE—RU C: TED CRAWFORD at BUTTE RU j e ct : MEMO ---------------------------------- Message Contents ------------------------------------ KAREN, COULD YOU PLEASE HAVE SOMEONE PUT THIS ON COUNTY LETTER HEAD. THANKS! BILL TO: BARRY MORRELL,SUPERINTENDENT DURHAM UNIFIED SCHOOL DISTRICT PUTNEY DR, DURHAM, CA . 9 5 9 3 8 FROM: BILL ORTHEL,BATTALION CHIEF CDF/ BUTTE COUNTY FIRE SUBJECT: WATER SUPPLY AND ACCESS,DURHAM SCHOOLS I HAVE MET SEVERAL TIMES WITH JIM JOHANSEN AND ARCHITECT MATT MCKISSON REGARDING FIRE HYDRANTS AND THE PLUMBING HARDSHIP GRANT. THERE WERE TO BE THREE NEW HYDRANTS AND SOME UPGRADES OF EXISTING HYDRANTS. THE THREE NEW HYDRANT LOCATIONS AS AGREED UPON WERE #1,NEAR THE CONTINUATION SCHOOL,#2,NEAR SOUTH WEST CORNER OF HIGH SCOOL PARKING LOT AND #3,NORTH EAST OF THE BUS BARNS NEAR THE POOL. SEVERAL OTHER PROSPECTIVE SITES WERE STUBBED OUT AND THE #4 ALTERNATE SITE WAS NEAR GOODSPEED AND THE SCOOL ENTRANCE.PRIORITY WAS GIVEN TO THOSE LOCATIONS NEAR NEW AND PROSPECTIVE PORTABLE SITES. I WAS LATER ADVISED THAT THE #2 SITE WAS NOT FEASIBLE.A LOCATION MIDWAY ON THE SOUTH END OF THE HIGH SCHOOL PARKING LOT WAS PROPOSED BY JIM JOHANSEN. THIS WAS AGREEABLE TO ME. LAST WEEK I NOTICED HYDRANT LOCATIONS #1,3 AND 4 WERE INSTALLED. I'M NOW BEING ADVISED THAT THE ARCHITECT WANTS A HYDRANT NEAR SITE #2 BUT IT WILL COST MORE MONEY. I HAVE ADVISED THAT THE ALTERNATE SITE #2 IS ACCEPTABLE TO ME AND THAT A SITE ON THE WEST SIDE OF THE ELEMENTARY SCHOOL WOULD BE A GOOD FUTURE LOCATION. I'M CONCERNED WHY HYDRANT SITE #4 WAS INSTALLED INSTEAD OF ALTERNATE SITE#2 OR SOME OTHER SITE NEAR THE WEST END OF THE ELEMENTARY SCHOOL. I'M AVAILABLE TO CONSIDER ANY ALTERNATIVES. PLEASE CONTACT ME AT 895-6567. BILL ORTHEL BATTALION CHIEF Author: BILL ORTHEL at BUTRU Date. 6/24/98 12:23 PM Priority: Normal CC: BTU ECC at BUTTE—RU TO: BTU - DURHAM STN 45 (A.5) at BUTTE—RU • BTU - JARBO GAP STN ( 5 ) at BUTTE RU J: BTU - RICHVALE STN 71 (A8) at BUTTE RU TO: BTU REL B3 S1 at BUTTE—RU TO: DAN COSTELLO at BUTTE—RU TO: DAVE RICHARDSON at BUTTE—RU TO: CHRIS STARNES at BUTTE—RU TO: BTU - NORD STN 41 (A2) at BUTTE—RU TO: BTU - NORTH CHICO STN 42 (A3) at BUTTE—RU ITO: BTU - SOUTH CHICO STN 44 (A4) at BUTTE—RU TO: BTU REL B4 S1 at BUTTE—RU TO: BTU REL B4 V1 at BUTTE—RU 0: STEVE IVERSON at BUTTE—RU O: DAVE MINTON at BUTTE—RU 0: BILL REDDING at BUTTE—RU O: DALE WAUGH at BUTTE—RU C: HENRI BRACHAIS at BUTTE—RU C: JOHN HAWKINS at BUTTE—RU C: BILL HOLMES at BUTTE—RU C: BILL SAGER at BUTTE RU C: GEORGE MORRIS at BUTTE RU C: TED CRAWFORD at BUTTE RU C: Joe Campbell at BUTTE RU ubject: DURHAM SCH DIST WATER SUPPLY ------------------------------------ Message Contents DUE TO CONTAMINATION PROBLEMS,THE SCHOOL IS STILL ON THEIR PUMP SYSTEM. 2113 UNDER A STATE HARDSHIP PLUMBING GRANT DUSD HAS UPGRADED THEIR WATER SYSTEM INCLUDING RAISING A COUPLE OF EXISTING HYDRANTS AND ADDING NEW STEAMER HYDRANTS AT THE NORTH END OF GOODSPEED,WEST S I DE, AGAI ST THE POOL FENCE, EAST SIDE OF DISTRICT OFFICE PARKING LOT,NORTH OF BUS BARN AND ONE ON THE NORTH SIDE OF THE GATE BETWEEN THE OLD GYM AND THE REC DISTRICT PROPERTY. THERE IS SUPPOSE TO BE ONE PUT IN ON THE SOUTH SIDE OF THE HS PARKING LOT ON THE NORTH SIDE OF THE ELEMENTARY SCHOOL.THERE WERE ALSO A NUMBER OF STUBS PUT INTO THE SYSTEM FOR FUTURE HYDRANTS. ALSO THE TWO PORTABLES ON THE NW CORNER OF THE DURHAM REC DIST PROPERTY IS THE LOCATION OF THE NEW MISSION HS(ALTERNATIVE ED.) THE NEW BASE BALL FIELDS ARE IN SERVICE NORTH EAST OF THE HS. THEY CAN BE ACCESSED OFF THE MIDWAY OR THE NORTH SIDE OF THE HS GYM. PS THANKS TO TED CRAWFORD FOR HIS PLANNING ASSISTANCE. 2113 TO: CHIEF ORTHEL FROM: SHANNON GARRETT DATE: 8/17/98 SUBJECT: DURHAM SCHOOL DISTRICT WATER SUPPLY CHIEF ORTHEL; I WAS NOT ABLE TO MEET WITH DAVE YORK TODAY, HE WAS IN SACRAMENTO ON BUSINESS. I DID MEET WITH MATT MCKISSON AND HE TOOK ME ON A TOUR OF THE COMPOUND. I LEARNED THE FOLLOWING FACTS ABOUT THE WATER SUPPLY: 1. ALL DOMESTIC WATER INTO THE CAMPUS IS PROVIDED BY DURHAM IRRIGATION DISTRICT. 2. ALL STEAMER HYDRANTS ARE FED BY DURHAM IRRIGATION DISTRIC`1', THEY ARE NOT LONGER TIED INTO THE SCHOOL IRRIGATION SYSTEM. 3. ALL WARFHEADS (2 1/2ARE FED BY THE SCHOOL IRRIGATIGA. SYSTEM ONLY, NO TIE TO DURHAM IRRIGATION DISTRICT. 4. THE PUMP THAT FEEDS THE SCHOOL IRRIGATION SYSTEM IS ON THE DECLINE, AND THEY HOPE TO HAVE A NEW ONE BUILT IN THE NEXT FEW YEARS. 5. THE WELL THAT FEEDS THE SCHOOL IRRIGATION SYSTEM CURRENTLY IS CHLORINATED TO MEET POTABILITY STANDARDS. THEY WILL PROBABLY ABANDON THE CHLORINATION WITHIN THE NEXT SIX MONTHS, MAKING THAT WATER NON -POTABLE. 6. THE SCHOOL WOULD BE HAPPY TO ADD A 4 1/2" FDC AT THE PUMP HOUSE OFF OF AN EXISTING 6" PIPE THAT HAS A GATE VALVE. WE JUST NEED TO SUPPLY THEM WITH THE FDC. 7. MATT WOULD LIKE TO SEE A FIRE DEPT. ACCESS GATE INSTALLED OFF OF DURHAM DAYTON, ON THE WEST SIDE OF THE ELEMENTARY SCHOOL. THIS WOULD PROVIDE BETTER ACCESS TO THE PORTABLE CLASSROOMS ON THE NORTHWEST SIDE OF THE ELEM. SCHOOL. 8. IF HE CAN ARRANGE FOR THE ABOVE MENTIONED GATE HE WOULD LIKE TO INSTALL A STEAMER HYDRANT BETWEEN THE TIMBER JUNGLE GYM AND THE PORTABLE CLASSROOMS. 9. A CHECK VALVE WAS INSTALLED TODAY TO COMPLETELY SEPARATE THE SCHOOL IRRIGATION WATER FROM DURHAM IRRIGATION DISTRICT WATER. THIS ADDITION NOW MAKES THE KEY AT STA 45 OBSOLETE. WE CAN NO LONGER AUGMENT THE TOWN SUPPLY WITH SCHOOL IRRIGATION WATER OR VICE VERSA. 10.WE TOURED THE HIGH SCHOOL GYM. THE ONLY SPRINKLERED AREAS ARE ABOVE AND BELOW THE STAGE. THEY ALSO RECENTLY REDISCOVERED A FEW HIDDEN STORAGE SPACES LIKE MEZZANINES ABOVE THE LOCKER ROOMS, THE STAGE AND THE KITCHEN. THEY ALL SEEM TO BE CONNECTED BUT IT WOULD BE HARD FOR A PERSON TO TRAVEL BETWEEN THEM. (EASY FOR A FIRE j THE SPACE ABOVE THE LOCKER ROOMS IS ACCESSIBLE FROM EACH LOCKER ROOM. THE SPACE BY THE STAGE IS ACCESSIBLE BY A SMALL DOOR ON THE WEST WALL. THE KITCHEN SPACE IS ACCESSIBLE IN THE KITCHEN HALLWAY. AS YOU CAN SEE WE LEARNED A LOT FROM MATT, HE WAS VERY HELPFUL. WOULD YOU LIKE ME TO TRACK DOWN A 4 1/2' FDC FOR THE PUMP HOUSE? I WILL BE MAKING THE NECESSARY CHANGES TO THE HYDRANT RECORDS ASAP AND PUTTING DOWN THE BLUE DOTS ON FRIDAY. IQ &R C/) m M;u 0 0 M > icl) NJ 1 0 . ................................ Ul tit w� . \(/) 0;u m . ......... . . .. . . N) -A X '7 > OP -No (0 17) Eml 11 R33) . . . . ................................................ .... 0 0 0 co 0 0 c c ............. . A� Fcn cn IM INS �H AM 0 4109 Zeering Rd., Denair, CA 95316 800-222-7099 209-632-7571 AXIOM FAX 209-632-4711 SITE REVIEW for GonVault Flammable Liquid Storage Vaulted Tank Cor Vault is very concerned that all tank sites be reviewed by the Local Fire Marshal. To prevent confusion created by this con- cer and for your convenience this form can be used. It does not replace a permit, but will satisfy our requirements at Con- a' It. Please fill it out, have it signed by your local Fire Marshal, and return the original to us. The second copy is for the Fire Ma shal, and the third copy is for your records. Fill d out by /Applicant Fire )istrict Add ess Phone # APPROVED y State, Zip r nRE AND PANIC ONLY Fire Marshal 1 144.1n+ -hI in Ia-m— - I I Date Fire arshal's Signatur I [p STATS F ®i: + r l y QU9$ ons Regarding This Form To ConVeult SEEGER'S PRINTING /209 687-2 760 /203fPM ate Suhmitted weer ddress_�0- ity, State, Zip nz,Z hone Nurnber� g,S 15��8� ennission is hereby granted to above applicant to install fuel tanks on premises I cated at _-�u�,�ss, �ck ,,y ounty of _ eZ:T , Ca. as described below. Check applicable liquid - Waste Oil Gas Diesel Tank Size/d� L, Type Liquid X1 TankSize 4�2 .17-D O Type Liquid X Tank Size Type Liquid Tank Size Type Liquid Dealer, Contractor's or Installer's name and address: 110/yo A plicant's Signature Fire )istrict Add ess Phone # APPROVED y State, Zip r nRE AND PANIC ONLY Fire Marshal 1 144.1n+ -hI in Ia-m— - I I Date Fire arshal's Signatur I [p STATS F ®i: + r l y QU9$ ons Regarding This Form To ConVeult SEEGER'S PRINTING /209 687-2 760 /203fPM Aloakk •,ol%� 7 -� j 0 o o �Nld� dotes FA� p lks, AVaZJ 17 I r, r { � f 7. 1 f{ li! It Q z 41-'- IL L p EHI ���RTL:PA�Dl I�.C�HC EM�E7�FILLCD EEL POSTS. . THE CONCRETE PAD IS A REQUIREMENT OF CONVAUL'1 -WHILE THE POSTS ARE A RECOMM ENDA T I OST . IF POSTS ARE USED, TH EN THE POST (S) ON THE " TANK ACCESS" SIDE SHOULD BE CONSTRUCTED TO ALLOW REMOVAL FOR INSTALLATION] OR INSTALLED AFTER THE TANK HAS BEEN SET. THE CORNER POSTS SHOULD ALLOW 1116" CLEARANCE FROM THE SIDE FROM THE SIDE OR 6'2" FROM THE END. THE "SUPPORTS" OF THE TANK ARE 6" WIDE AND ARE SET IN 1$" FROM TE;E ENDS OF THE TANK. 1000 GALLON STORAGE VAULT I - 6" �•._ PLAN SECTION THE GASBOY PUMP IS I/4 HP AND REQUIRES 115 VOLT. 4AMP POWER. CONDUIT MAYBE ,BROUGHT UP. THROUGH THE CONCRETE SLAB AT THE PI -PAP SND INSURING THAT 1T WILL NOT BE I UNDERNEATH THE TANK. 1200FOOTING dW `* •'_ ' 6" 0 STEEL POSTS WITH CONCRETE . j • • POURED SOLID .•. TYPICAL • • REMOVABLE w --+.-__._--+ r_._._..._ ��..._._.....- -_--- �._�•� STEEL POSTS . -• .. SAS /V EC,FSSA RY ' �• • .. 6 THICK CONCRETE _..__--s-------.i--- - . .. SLAB WITH #3 at ----.—♦-------*----_--.I.._ I - 6" �•._ PLAN SECTION THE GASBOY PUMP IS I/4 HP AND REQUIRES 115 VOLT. 4AMP POWER. CONDUIT MAYBE ,BROUGHT UP. THROUGH THE CONCRETE SLAB AT THE PI -PAP SND INSURING THAT 1T WILL NOT BE I UNDERNEATH THE TANK. DURHAM UNIFIED SChOOL DISTRICT DONALD C. McNELIS, District Superintendent P.O. BOX 300 • DURHAM, CALIFORNIA • 95938 • (916) 895-4675 BOARD OF TRUSTEES Richard L. Anderson • Ruby O. Kimmelshue • Arthur L. Moore • Myles L. Pustejovsky• M. Anthony Soares November 13, 1990 b1r. Jack Krisn State F i ars}aall State of California #4 Williamsburg Lane Chico, CA 95926 Re: Above -Ground Fuel and Gas Tanks Dear Mr. Krisp: In reference to our conversation, please find enclosed a diagram showing the proposed location for two above -ground fuel and gas tanks. As per your advise, the District will be using the ConVault tanks with the attached pumping systems. The existing pumps will be eliminated. I have also enclosed a diagram showing the construction of the concrete pads that will be used. With your written approval for this location, we will be able to proceed with this project. Thank you, in advance, for your assistance. Sincerely, G Randy Silverman Transportation Foreman RS: lav DURHAM DURHAM ELEMENTARY SCHOOL INTERMEDIATE SCHOOL NOEL J. BUEHLER STEPHEN J. PILUSO PRINCIPAL PRINCIPAL Phone 895-4695 Phone 895-4690 P.O. Box 700 P.O. Box 310 DURHAM HIGH SCHOOL WILLIAM M. JENSEN PRINCIPAL Phone 895-4680 P.O. Box 600 ST&Tc" OF CALIFORNIA—STATE AND CONSUMER SERVICES AGENCY GEORGE DEUKMEJIAN, Governor OFFICE OF THE STATE FIRE MARSHAL .•..••��:�.: NORTHERN REGIONAL DIVISION C3 0 3 FLORIN ROAD, SUITE 400 A9TSS 466- 325 �� A-CRAMENTO, CA 95823 TDD (916) 427-4186 `•�•••• April 11, 1990 Donald C. McNelis, Superintendent Durham Unified School District P. O. Box 300 Durham, CA 95938 Dear Mr. McNelis: DURHAM HIGH SCHOOL/DURHAM INTERMEDIATE SCHOOL CSFM File #52-04-21-0045-000-035-1 Thank you for your response to our letter of corrections dated February 15, 1990. In regards to the required sprinkler system for the Intermediate School Gymnasium, an alternate means of protection can be granted under the following conditions: 1 1. The gym capacity is posted and strictly maintained at no more than 299 occupants. 2. All exit doors are kept clear of any obstructions, including tables and chairs set-up to collect tickets at the entrance. 3. A schedule of events, such as plays, dances, and games, will be forwarded monthly to the State Fire Marshal., 4 Williamsburg Lane, Suite 3, Chico, CA 95926. Random checks of these conditions will be conducted periodically by Deputy Slaughter. To validate this alternate means of protection, please confirm in writing your agreement to adhere to these conditions. Thank you for your cooperation and assistance in our mutual efforts to provide a fire safe environment for your students and staff. If you have any further questions, please contact Deputy Rodney Slaughter at (916) 895-4312. Sincerely, IL EDWAR F. SEITS Division Chief EFS: RS: al SENTINEL FIRE (&76) 4.55-5630 EQUIPMENT COMPANY r From the desk of JOIIIY IYEILL iAj o d � d � �.t ��vu���,p �v `-,eta 2�-� " -1 , 7Dezi4 4s\� �C,f,c-sem n d ka s. l �C 5702 BROADWAY, SACRAMENTO, CALIFORNIA 95820 AUTOMATIC FI.i: SPRINKLER SYSTEM INS _XTION REPORT State Lie. #A-0067 E-4 J �t SENTINEL FIRE (916) 455-5630 EQUIPMENT COMPANY 5702 BROADWAY, SACRAMENTO, CALIFORNIA 95820 Customer's Order Number Date I -k) 1917 U Name -Do yAQ Nh. 15c- 1 T L VV Ph... q )R --g q -f-4 Location�`� O Billing MAINTENANCE REQUIREMENTS: AUTOMATIC FIRE SPRINKLERS .5 STATE FIRE MARSHAL TITLE 19 (P. Ilio) (register 83. No 33-8-13-83) COMPONENT rr)RRF(7fVE ACTIONS W, REMARKS: 51t-�/L S_C -S, � 1-10 t4 (, STS► C� V ►v✓J*-V21%rA CGS' S PRI NKLERS ❑ I Leaking corroded or painted. ❑ I. Replace. ❑ 2 Flow obstructed. ❑ 2. Correct. ❑ 3. Installed in correct position ❑ 3. Correct.`'"9 (upright or pendant). ❑ 4. Extra sprinklers and wrench ❑ 4. Provide. not available. ❑ S. Extra sprinklers not the same ❑ 5. Provide. orifice size or temperature rating as in system. GRAVITY TANK, SUCTION TANK & RESERVOIR SUPPLY ❑ I Vessel damaged. ❑ I. Repair. ❑ 2. Water level inadequate. ❑ 2. Fill. Repair. PRESSURE TANK SUPPLY ❑ I Tank damages. ❑ I. Repair. -Nik 2 Water level too high or too low. ❑ 2. Fill or drain. Repair. 3 Air pressure level low. ❑ 3. Fill. Repair. Ll 4 Valves closed. ❑ 4. Open. hers Serviced Checked man License# '�() JA� M" I L., rple,�_--F Q 3' 2aztw p;�na8c C) ' G'nv6a entieE2- ❑ gavziu A42tPl� -"- O 'r AMPO boe"I Av�,U cc bu s a- ill" r�.. :9 is 0m too Om- p T tfb*a' is t: 3 9�'• � t 7 hat s t�f �; lu rgcdt+ots 1 L!!i ' r<r iu Akzlcw� fiyucc ztsc pc fsujbo* L1460 L4 i k +uaati�eice not t pc P vws p ,Axl k K[c►� vuq Map •• ❑ +t`;�ttrkagC' , N {f1, tem " _ tR.:egal.ert fioa�ttou 3+• -Cawxc" Q 3' 2aztw p;�na8c C) ' G'nv6a entieE2- ❑ gavziu A42tPl� -"- O 'r AMPO boe"I Av�,U cc bu s a- ill" AUTOMATIC F`�`=SPRINKLERSYSTEMIN°'=CTIONREPORT s.ta�c.«a�6, EA P SENTINEL FIRE (976) 455-5630 EQUIPMENT COMPANY 5702 BROADWAY, SACRAMENTO, CALIFORNIA 95820 Customees Order Number Name I,h'lo Location Y'- 10 N��f 40300 Billing Address 330 MA14TENANCE REQUIREMENTS: AUTOMATIC FIRE SPRINKLERS § 90 t.5 STATE FIRE MARSHAL TITLE 19 (p. 1; ) (register 83. No 33-8-13-83) COMPONENT HECK POINTS CORRECTIVE ACTIONS FIR DEPARTMENT CONNECTION BACKFLOWED ❑ I. Inlet caps missing. ❑ 1. Inspect interior. Repla e. ❑ Couplings damaged. ❑ 2. Repair or replace. ❑ 3 Couplings do not rotate smoothly,❑ 3. Lubricate. ❑ 4 Gaskets missing or deteriorated. ❑ 4. Replace. ❑ 5 Clapper valves do not close ❑ 5. Repair. completely. 1:16 Visable or exterior obstructions. ❑ 6. Remove. 7 Not identified. ❑ 7. Replace, repair or install sign. CUN ROL VALVES ❑ 1. Valves leak. ❑ 1. Repair. o ❑ 2 Valves not secured in open ❑ 2. Open, secure. position. . ❑ 3. Visible or exterior obstructions. [13. Remove. RISE ❑ 1 Leaks. ❑ 1. Repair. ❑2 Visible or exterior obstructions. C32. Remove. ❑ 34 Bracing damaged. ❑ 3. Repair. GUA ES ❑ 1 Guages damaged. ❑ 1. Repair or replace. E:1 2.; Gu age valves turned off. ❑ 2. Turn on. ❑ 3.' System pressure. ❑ 3. Record. �. ❑ 4. upply pressure. ❑ 4. Record. SPRI KLERS ❑ 1. aking corroded or painted. ❑ 1. Replace. ❑ 2. ow obstructed. ❑ 2. Correct. ❑ 3. nstalled in correct position ❑ 3. Correct. (upright or pendant). ❑ 4. tra sprinklers and wrench ❑ 4. Provide. of available. ❑ 5. tra sprinklers not the same ❑ 5. Provide. rifice size or temperature rating in system. GRAV TANK, SUCTION TANK & RESERVOIR SUPPLY ❑ 1. essel damaged. ❑ 1. Repair. ❑ 2.., ater level inadequate. ❑ 2. Fill. Repair. PRES URE TANK SUPPLY ❑ 1. Tank damages. ❑ 1. Repair. �2. ater level too high or too low. ❑ 2. Fill or drain. Repair. 3.'r pressure level low. C] 3. Fill. Repair. v4. V Ives closed. ❑ 4. Open. Extinguishers Serviced Checked. Due Servicembn License# 19,30 REMARKS: ��fL- S"�---- I 9r 4'-lJ�ans ave lou"00" look k/)v y_ CdMAj* .wJ slet2 TIWPw- X* 1 _, •�Z - I � •r yae , 4 '- - - la. to aye Vim n- r fur I NOW `l ICU, ira` � } �� r'�' b� ipin�q • S}C�F —Ll 6w 3vQ .40 .aaoi lady► its alt ewl S;Q'40 1�4mlul tjilfNij� to aryllautitt 1�?Q' ,`. �; .F [�j _�iu7aytq•�rsstb�7_ E.GI `l�� \ �� : (;��. � ��- J"' ('�. - .1 ... � I - blt�s�.a❑ - .9?tr?Y.r1q'�(lr�glD`L, i+Q -' _ _ • ice. .-`.� IiVI'11���;j�. Yotis:.E G3 naFtiao9wa tri tiaisanl, .s} . Q tfzttaww bass ;islsfo=tsyix _ p std�etsys fog t t' �•a�v,2 �Q asnae sdt,wa: antes a!-+ix'r a C] Oe»r�tsalgat�s�cr��� . R snaiz4� nr iz . YT 440 u2 !!� •boll i Jn ;y� t .iria•tb ro Itit .S p. +�►A#.rn,t�ot� ista'! S r ae" a z Don McNeel is , District Superintendent December 11, 1989 Durham Unified School District Inspection date: October 10, 1989 WING 100 1. All hold -open devices shall be removed from corridor classroom doors, (24 CCR 2-3305(h)] he louvered doors to the restrooms , storage closet, and custodial closet shall be replaced with labeled 20 -minute fire - rated assemblies; or, the louvers removed and the openings filled with gypsum wallboard and sealed on both sides with heavy -gauge sheet steel. [24 CCR 2-3305(h)] The Dutch door to the Audio -Visual Room shall be replaced with a 20 -minute fire -rated assembly. [24 CCR 2-3304(c)] All storage and combustible items shall be removed from the ibrary exit corridor. [19 CCR 3.11] MULTIPURPOSE ROOM A five-year certification shall be provided for•the sprinkler system. [19 CCR 904] ART, ROOD AND AGRICIILTURAL SHOP Doors between each Shop Classroom Loft area shall be maintained self-closing. [24 CCR 2-3305] now Don McNeelis, Distric Superintendant Durham Unified School Distric P.O. Box 300 Durham, Ca. 95938 DURHAM HIGH SCHOOL SFM FILE #52-04-21-0008-000-035-1 Dear Mr. McNeelis, 10 October 89 A follow-up inspection was conducted at the above facility to determine com- pliance with applicable sections of Titles 19 and 24 of the California Code of Regulations. The following deficiencies were noted and shall be corrected ; Wing 100 a) Remove all hold -open devices from the classroom doors which exit into the corridor (T-24 CCR 2-3305 (h)). b) Louvered doors used in exit corridor (boys and girls restrooms, storage closet, and custodial closet) shall be sealed with 5/8" type X gypsum wallboard and finished with sheetmetal.(T-24 CCR 2-3304(c)). c) The dutchydoor to the Audio -Visual room shall be replaced with a 20 minute solid core door (T-24 CCR 2-3304(c)). d) Remove all storage and combustible items from the library exit corridor (T-19 CCR 3.11). Multi-purpose Room a) Provide a five year certification on the sprinkler system located in the multipurpose room (T-19 CCR 904) ART, Wood, and Agricultural Shop a) Doors between each shop classroom` loft`' area shall be maintained self-closing (T-24 CCR 2-3305). I urge you to correct these deficiencies as soon as possible. If you have any_ questions, please contact Rodney Slaughter at, (916) 895-4312. Sincerely Dan Najera I— Mb,. office of the State Fire Marshal Fire Safety Correction Notice r. File No. "- - — — - — Name: Address: The California Health and Safety Code and the deficiencies be corrected. State Fire Marshal's regulations require the following fire safety All— The above deficiencies are to be corrected within t days. When ALL deficiencies have been corrected, sign and return the certification on the opposite side of this form. If you have any questions,' contact the Office of the State" Fire Marshal at ISSUED BY (Deputy State Fire Marshall RECEIVED BY DATE N-I1 (Rev. 7/86) 66 96708 DISTRIBUTION: GREEN—Facility WHITE—Region YELLOW—Field *FIRE Office of the State Fire Marshal Fire Safety Correction Notice HAL File No: Name: Address: The California Health and Safety Code and the State Fire Marshal's regulations require the following fire safety deficiencies be corrected. The above deficiencies are to be corrected within days` When ALL deficiencies have been corrected, sign and return the certification on the, opposite side of this form. If you have any questions, contact the Office of the State Fire Marshal at ISSUED BY (Deputy State Fire Marshal RECEIVED BY DATE EN -11 (Rev. 7/86) 86 96708 DISTRIBUTION: GREEN—Facility WHITE—Region YELLOW—Field +.- Office of the State Fire Marshal Fire Safety Correction Notice File No:-------- Name: Address: *FIRE HAL The California Health'' and SafetyCode and the State Fire Marshal's regulations require the following fire safety :.Iden ' , __�"_""" The above' deficiencies are to be corrected within days. When ALL deficiencies have been corrected, sign and return the certification on; the opposite side of this form. If you have any questions, contact the Office; of the State Fire Marshal at ISSUED BY (Deputy State Fire Marshal) RECEIVED BY DATE EN -I1 (Rev. 7186) 86 96708 DISTRIBUTION: GREEN—Facility WHITE—Region YELLOW—Field la 0 .,,.,,,,v I � i •. � �'i! � .( ii i..., ivi 1 � �.4 �'t''� •. �q aw , i _ � ���j ..1� e�l'�•ri���_! Y 1 4r�'i��•,��••��������� �•t�i � tr of jfl�llltr ft L0 ta�s Gas T�REGISTERfD ISSUED BY of E`Date treated or APPLICATION s Coral of Chicago manufactured CONCERN No. 2001 S. Calumet Avenue owl }� t .�R>�♦? Chicago, IL 60616 4-23-86 El F -2Q6.15 This is to certify that the materials described on the reverse side hereof have been flame- retardant treated (or are inherently nonflammable). FOS._____ Durham High 9 4 5 5 Putney Dr . CITY Durham CA 95938 STATE ' Certification is hereby made that: (Check "a" or "b") (a) The articles described on the reverse side of this Certificate have been treated with a flame-retcrdant chemical approved and registered by the State Fire Marshal and that the application of said chemical was done in conformance with the laws of the State of California and the Rules and Regulations of ASPthe State Fire Marshal. �{ Name of chemical used ....................._---.---.--_...._.......___._........----.-.--..Chem. Reg. No .......................... Method of .®; application-------------- .--..--...................-_-----------------_.--.-...._._.-------------.-..-----------------------.-..- --- (b) The articles described on the reverse side hereof are made from a flame -resistant fabric or material lx:xl registered and approved by the State Fire Marshal for such use. Rim b is ILA, rn Trade name of flame -resistant fabric or material used__ Cx. Qa�..�'� F _. � �. Reg. No..F _.—.2 0 6 ..15 __.. Woo �- The Flame Retardant Process Used will Be Removed Washing tll not) zi Kathy Friend NMI, I e of A iico!• c t Fr , tio.^+ np ^� ���� ct�c.n Sucrrirtendent TdIe -��- ..... I ..� .. �:. �- . .� T .. �:.f 1...� �:.� 1.•.� ..t � �.� t.`.� !.'..� � _.� �.'..� �:j � �.. t � ..t �:.� �.:� t.•.� r:.t � •.� �.-.� �..� 1:..� t..� �...� �..i i...� �.. � �...t �..� �..t � .,� � ..� �, ,� � ..� t...� �.-.� � . � i. � �..� r: � � We hereby certify this to be a true copy of the original "CERTIFICATE OF FLAME RESISTANCE" issued to us, "original copy" of which has been filed with the California State Fire Marshal. VERTI-CAL DRAPERY C0,111=,... 709 DIXIEANNE AVE., SACRAMENTO, CA. 95815 CONTROL. NO. � .. ✓ -- -- CUSTOMER ORDER NO. --73 3-2 CUSTOMER INVOKE NO. ---1-39 YARDS OR QUANTITY --__.__ 35 yards COLOR Flax STYLE Stoplight �S_D_ 1.4 -30-86 VERTI C DRAPERY - FABRI%,�, HARDWARE & CUSTOM WORK `* E DRAPRY CO. FLAME PROOFING X HANDLE 709 DIXIEANN VE. • SACRAMENTO CALIF. 95815 PH NE 922-1793 OR 922-1889 NOV 13 '86 November 11, 1986 ,•- ..-.w.y.... r ~HjrC FIRE DEPT. Fc,. BC -1 STC, Chief Charles R. Lowden BC -2 FP8 Chico FD BC -3 DISP. 842 Salem St. BC -4 PCon Chico, 95926 noF BC -5 STA.1 ACM/PO STA. 2 CWS STA.3 BCFD STA, 4 Enclosed are District copies of Certificate of Flame Resistance. If any do not apply to your District, please return indicating where they should be sent . Any questions regarding this matter, please let us know. Sincerely, Carolyn uthmac er Accounting C H : a h Encl. a: • r r� 1. t• �� e� - - k �. f• kali li �-- /I - «. r 1 � • ! •� y S • - _ -. - �..•?r.. ••• ��a•`•.-11. .D�ti.... - O•w•.+�-sem.•• y1.K^:r,�t - , •1. •s.w. ..a•s...Isw•l�i�., .. .♦ . •rat y .�� ..•C •• r.• . r'• •, dKE STATE IRE MAR AL STATE ]FIRE MARSHAL I xAE SAFETY CORRECTION NOTIU.6 --t NAME OUrZ s&W-00i ADDRESS P.00 60?c 63 FILE NUMBER F FD� F�21 M oaRol [9 aoo 0 00 Ed In accordance with the minimum standards of Title 19, California Administrative Code, the following corrections are required: In. k- ig ik&ar A401c, 1fA1,QuA49-(F :Av-*r 64 WCsr- orzn�io e9he S7244,Z. .U0 l ttre.Pt A"110,01ACie, 0We64*-)q1 Se i F] Lt21-40YM tt.)ILL B&Z XIF016VE4 we uc U, d C 40'97q) s �€ G 908' W10 vac, u Lj 1 --Iput,c"a L, Aomt The above deficiencies are to be corrected within dans. Upon completion, please sign and return the certification on the opposite side of this form. If you have any questions, contact the State .Fire Marshal's Office at ( q1 6 ) 6!175'- `f 3 l 2 . ISSU14JD BY (DEPUTY STATE FIRE MARSHAL) RECEIVED BY DATE EN -11 ( EV. 7/81) YELLOW: REGION WHITE: FASILOTY GREEN: FEEL® 66701-355 3-84 12M TRIP OSP CERTIFICATION OF CORRECTIONS BY OWNER I certify that all item listed on the reverse of this form have been Corrected in accordance ,with the requirements of Title 19, California Administrative Code.. SIGNATURE . DATE (Fold on • this line) _ (Fold on this line) PLACE STAMP HERE STATE FM MARSHAL. Sacramento Region 4433 Florin .Road, Suite 409 Sacramento, CA 95823 -