HomeMy WebLinkAbout065-510-007 ehdr19-01025 b19-3132 water sample (1)October 7, 2019 Lab ID : CH 1975001
Gary Hubbard Customer : 7-13092
Quality Control - Organic
Constituent
Method
Date/ID
Type
Units
Cone.
QC Data
DQO
Note
Organic
CA ELAP Certification No. 1563
1,2 -Dichlorobenzene -d4
524.2
10/03/19:211478VRG
Blank
ug/L
10.00
101%
70-130
MS
ug/L
10.00
106%
70-130
(SP 1912899-001)
MSD
ug/L
10.00
105%
70-130
MSRPD
ug/L
10.00
0.9%
<20
524.2
10/03/19:215518VRG
CCV
ug/L
10.00
99.7%
70-130
Bromofluorobenzene
524.2
10/03/19:211478VRG
Blank
ug/L
10.00
89.3%
70-130
MS
ug/L
10.00
102%
70-130
(SP 1912899-001)
MSD
ug/L
10.00
101%
70-130
MSRPD
ug/L
10.00
1.3%
<30
Bromofluorobenzene (BFB)
524.2
10/03/19:215518VRG
CCV
ug/L
10.00
98.2%
70-130
Benzene
524.2
10/03/19:211478VRG
Blank
ug/L
ND
<0.5
MS
ug/L
10.00
68.8%
12-158
(SP 1912899-001)
MSD
ug/L
10.00
90.7%
12-158
MSRPD
ug/L
10.00
27.5%
<36
524.2
10/03/19:215518VRG
CCV
ug/L
1 10.00
1 106%
1 70-130
Definition
CCV : Continuing Calibration Verification - Analyzed to verify the instrument calibration is within criteria.
Blank : Method Blank - Prepared to verify that the preparation process is not contributing contamination to the samples.
Matrix Spikes - A random sample is spiked with a known amount of analyte. The recoveries are an indication of how that sample
MS
matrix affects analyte recovery.
: Matrix Spike Duplicate of MS/MSD pair - A random sample duplicate is spiked with a known amount of analyte. The recoveries
MSD
are an indication of how that sample matrix affects analyte recovery.
: MS/MSD Relative Percent Difference (RPD) - The MS relative percent difference is an indication of precision for the preparation
MSRPD
and analysis.
ND : Non -detect - Result was below the DQO listed for the analyte.
DQO : Data Quality Objective - This is the criteria against which the quality control data is compared.
Corporate Offices & Laboratory Office & Laboratory Office & Laboratory
563 E. Lindo Avenue 3442 Empresa Drive, Suite D
Chico, CA 95926 San Luis Obispo, CA 93401
TEL: (530)343-5818 TEL: (805)783-2940
FAX: (530)343-3807 FAX: (805)783-2912
CA ELAP Certification No. 2670 CA ELAP Certification No. 2775
Office & Laboratory
853 Corporation Street
2500 Stagecoach Road
Santa Paula, CA 93060
Stockton, CA 95215
TEL: (805)392-2000
TEL: (209)942-0182
Env FAX: (805)525-4172 / Ag FAX: (805)392-2063 FAX: (209)942-0423
CA ELAP Certification No. 1573
CA ELAP Certification No. 1563
Page 4 of 4
Office & Laboratory
9415 W. Goshen Avenue
Visalia, CA 93291
TEL: (559)734-9473
FAX: (559)734-8435