HomeMy WebLinkAboutFAI CF Fire Pump Report CSA 137 12_2019Durham`, . Pump
2313 Durham -Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#137 Durham
CUSTOMER NAME: Butte County Fire Dept.
PUMP CHECK REPORT
Industrial Partners
DATE. 12/12/19
Motor Mfg: US motors HP: 100
Meter #: 1005520819
RPM 1775 Volts 460 Phase 3
Rated Amps: 120
TM 80E—]Yes F—]No Serial#
T07TO59ROOSR-12
PG &E Acct. # Other:
Panel Mfg: Delta NEMA Size:
3
Type: ❑ X/L P/VV Other:
Pump Mfg: Serial#:
Non -Running Checks: Pump Model Manufacturer
❑ Lubricant Levels - Service and Change if Necessary
Oiler Unit and/or Packing
❑ Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: F]W/I Acceptable Limits
Unacceptable
❑ Fuses - Replace if Necessary FIReplaced
Size: 150A MCP
❑ Perform General Clean -Up of Electrical Panel and Motor
Running Checks: Motor winding resistance:
Excessive or Unusual Noise 1-10k
Excessive or Unusual Vibration F]Ok
Control Devices: 1-1 H.O.A. Start Switch
Time Clock
Frost Start Time Delay
Other: Pressure Switch
Amperage: Expected: 120.5
Actual: L1: 115 L2: 112.8 L3:
126.7 Average: 118.2
Overload Underload
Even Load
Bowl Adjustment: Yes ❑X No
Comments:
Slightly uneven load, similar to previous inspection.
GPS: 39038'41.08"N 121°43'18.99"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS & INSPECTIONS\Cal Fire CSA's\137 Durham Dayton Ind Partn\137 Reports
Durhami : Pump
2313 Durham -Dayton Hwy.
Durham, CA 95938 530.891.4821
PUMP CHECK REPORT
CSA #137 Durham Dayton Industrial Partners
CUSTOMER NAME: Butte County fire Dept
DATE: 12/12/19
Motor Mfg: Franklin HP: 3 Meter #:
RPM 3450 Volts 460 Phase 3
Rated Amps: 4.8
TM 80E—] Yes F—]No Serial #
PG &E Acct. # Other:
Panel Mfg: IEC NEMA Size: ?
Type: ❑ X/L F] P/W Other:
Pump Mfg: SUB Serial#:
Non -Running Checks: Pump Model Manufacturer
na FILubricant Levels - Service and Change if Necessary Discharge
na Oiler Unit and/or Packing
❑ Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: F]W/I Acceptable Limits
Unacceptable
❑ Fuses - Replace if Necessary FIReplaced Size:
TSR10R
❑ Perform General Clean -Up of Electrical Panel and Motor
Running Checks: Motor winding resistance:
Q's to ground
Excessive or Unusual Noise F]Ok/see comments Pressure tank:
OK
Excessive or Unusual Vibration 1-1Ok/see comments Tank condition:
good
Control Devices: ❑ H.O.A. Start Switch
Time Clock
Frost Start Time Delay Other:
Amperage: Expected: 4.8 Pressure setting:
Actual: L1: 6 L2: 4.8 L3: 4.5
Average: 5.1
Overload Underload
Even Load
Bowl Adjustment: N/A FYes FINo
Comments:
GPS:
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
SAPump Dept. Files\PUMP TESTS & INSPECTIONS\Cal Fire CSA's\137 Durham Dayton Ind Partn\137 Reports