HomeMy WebLinkAboutFAI CF Fire Pump Report CSA 158 12_2019Durham -i'. PUMP PUMP CHECK REPORT
2313 Durham -Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#158 Ishi Valley
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/12/19
Motor Mfg: Franklin HP: 25
Meter #: 1006908237
RPM 3450 Volts 240 Phase 3
Rated Amps: 75
TM 80E—]Yes F]No Serial #
PG &E Acct. # Other:
Panel Mfg: Furnas NEMA Size:
3
Type: ❑ X/L ❑ PAN Other:
Discharge Mfg: Steel 6" Serial#:
Non -Running Checks: Pump Model Manufacturer
na FILubricant Levels - Service and Change if Necessary
na Oiler Unit and/or Packing
❑ Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: 11W/I Acceptable Limits
Unacceptable
❑ Fuses - Replace if Necessary FIReplaced
Size: TR90R
Perform General Clean -Up of Electrical Panel and Motor
Running Checks: Motor winding resistance:
Excessive or Unusual Noise 1-10k
Excessive or Unusual Vibration F]Ok
Control Devices: ❑X H.O.A. ❑X Start Switch
Time Clock
Frost Start Time Delay
Other: Pressure Switch
Amperage: Expected: 65
Actual: L1: 68 L2: 75.1 L3:
61.2 Average: 68.1
Overload Underload
Even Load
Bowl Adjustment: N/A Yes No
Comments:
Slightly overloaded with uneven load but within service factor
Gate is falling apart, needs to be repaired or replaced.
GPS: 39048'32.57"N 121053'38.30"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
SAPump Dept. Files\PUMP TESTS & INSPECTIONS\Cal Fire CSA's\158 Ishi Valley\158 Reports
Durham til'. Pump
2313 Durham -Dayton Hwy.
Durham, CA 95938 530.891.4821
CSA#158 Ishi Valley
CUSTOMER NAME: Butte County Fire Dept.
PUMP CHECK REPORT
DATE: 12/12/19
Motor Mfg: Franklin HP: 1
Meter #: 1006908237
RPM 3450 Volts 240 Phase 1
Rated Amps: 9.8
TM 80E—]Yes F—,]No Serial #
PG &E Acct. # Other:
Panel Mfg: Franklin control box NEMA Size:
Type: F—]X/L F—] P/W Date code
Discharge Mfg: 1 1/4 Serial#:
Non -Running Checks: Tank Model WX-302 Manufacturer Well -X -Trot
na FILubricant Levels - Service and Change if Necessary
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: DWI Acceptable Limits
Unacceptable
F]Fuses - Replace if Necessary ❑ Replaced
Size: N/A
Perform General Clean -Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: Less than 1 Meg Q's to ground
Excessive or Unusual Noise ❑ Ok
Excessive or Unusual Vibration F]Ok
Control Devices: ❑ H.O.A. Start Switch
Time Clock
Frost Start Time Delay
Other: Pres. Sw. 30-50
Amperage: Expected:
Actual: Red: 0.8 Yellow: 11.6 Black:
10.3 Average: 7.567
Overload Underload
FlEven Load
Bowl Adjustment: N/A Yes F—] No
Comments:
GPS: 39°48'32.57"N 121°53'38.30"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
SAPump Dept. Files\PUMP TESTS & INSPECTIONS\Cal Fire CSA's\158 Ishi Valley\158 Reports