PUMP CHECK REPORT
CSA#169 Pheasant Landin
CUSTOMER NAME: Butte County Fire Dept.
DATE: 12/12/19
Motor Mfg: Newman HP: 40 Meter #: 1005576060
RPM 1770 Volts 460 Phase 3 Rated Amps: 59
TM 80Eā]Yes Fā]No Serial # 326TPH/DD27K2PM
PG &E Acct. # Other:
Panel Mfg: Cuttler Hammer NEMA Size: 21/2
Type: āX/L F] P/W Other:
Pump Mfg: Peerless 6" Serial#:
Non -Running Checks: Pump Model Manufacturer Newman
Lubricant Levels - Service and Change if Necessary
Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: F]W/I Acceptable Limits Unacceptable
F]Fuses - Replace if Necessary FIReplaced Size: 100A MCP
Perform General Clean -Up of Electrical Panel and Motor
Running Checks: Motor winding resistance:
Excessive or Unusual Noise F]Ok/see comments Pressure tank: n/a
Excessive or Unusual Vibration F]Ok/see comments Tank condition: n/a
Control Devices: ā H.O.A. Start Switch Time Clock
Frost Start Time Delay Other:
Amperage: Expected: 59 Pressure setting: PRESS SWITCH
Actual: R 47.3 Y 47.7 B 415.3 Average: 170.1
Overload Underload FlEven Load
Bowl Adiustment: N/A F]Yes E]No
Comments:
NO JOCKY PUMP
No Backspin protection, needs to be addressed
Idle voltage is a little high at around 495V. System holding 40 psi pressure.
Gate is broken.
GPS: 39°47'57.43"N 121'53'5.30"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.