HomeMy WebLinkAboutFAI20-0001 Fire Annual Inspection 2020 Sprinkler Test Fail/( a-C3 C°c1
(Do , - L9c -- uSL
Report of Inspection/Test Wilgus Fire Control, Inc
Annual Sprinkler 1703 Sonoma St
06/17/2019 Redding, CA 96001
Property Owner/Agent
Butte County Behavioral Butte County General
Health Services
Conducted by: Nathaniel Belmont
556 Cohasset Rd 2081 Second St Oroville, Ca
Chico, Ca 95965
Inspection Ref: 200000006198
Dean Olson
(530)538-7407 Print Date: 6/17/2019
Signatures
Inspector-Printed Inspector-Signature Date Completed I state that the information on this form is correct at the
Nathaniel Belmont 6/17/19 time and place of my inspection,and all equipment
tested at this time was left in operational condition
upon completion of this inspection except as noted.
Sprink
Spare heads?
2 riser,1 drain
75,55,75
45 sec alarm
OS&Y at street
Lock change,no key available
Equipment Summary
Site Inspected Unable to Serviced Failed
Description Inspect Repaired
Qty Qty % Qty % Qty % Qty
Alarm Alarm Panel 2
1 1 100.0% 0 0.0% 0 0.0% 0 0.0%
Alarm Battery
Sealed Lead Acid 1 1 100.0% 0 0.0% 0 0.0% 0 0.0%
Alarm CO Detector
4 4 100.0% 0 0.0% 0 0.0% 1 25.0%
Alarm Indicating Device
Strobe 6 6 100.0% 0 0.0% 0 0.0% 0 0.0%
Horn/Strobe 5 5 100.0% 0, 0.0% 0 0.0% 0 0.0%
Horn 3 3 100.0% 0 0.0% 0 0.0% 0 0.0%
Alarm Initiating Device
Smoke Detector-PE 11 11 100.0% 0 0.0% - 0 0.0% 1 9.1%
Manual Pull Station 3 3 100.0% 0 0.0% 0 0.0% 0 0.0%
Valve Tamper Switch 1 1 100.0% 0 0.0% 0 0.0% 0 0.0%
Water Flow Switch 1 1 100.0% 0 0.0% 0 0.0% 0 0.0%
Alarm Panel Information
Panel Manufacturer Model Serial No. Location
Silent Knight
Overcurrent Protect Type Overcurrent Size(Amps) Primary Supply Disconnect Location/Panel#/Breaker#
RECEIVED BUTTE COUNTY
Print Date: 6/17/2019 DEC 19 2019 Page 1 of 4
Copyright 2002-2018 Life Safety Inspector,OnSite Software
BEHAVIORAL HEALTH,ASD
Report of Inspection/Test Wilgus Fire Control, Inc
Annual Sprinkler
06/17/2019
Property: Butte County Behavioral Health
Owner: Butte County General Services Inspection Ref: 200000006198
Battery Test
E o 2 o o § a� as '5 .r co '5 Q a
Manufacturer y as .0 N 'N a) rn an m m co c
Location Type o m a a> Y o co co o al v 0 0 5 _
3 Model f6Q o c a, `o 0U > J 2 cu
0 -02
0 y U U U j fa cv as Q
cc a* U aU Is
FACP 2 Sealed Lead Acid Apex 1280 06/19 Ok Ok Ok 27 13 8 13 8 Ok
System Function Summary& Test
Function Description Test Result
Alarm Functions
Alarm Bells/Horns/Strobes Evacuation Alarm functions including Bells/Horns/Strobes actuate properly Pass
Alarm Panel Supervisory Functions
Panel AC Power Loss Loss of AC power to the alarm panel is detected by the alarm system. Pass
Panel Sec Power Loss Loss of Secondary power to the alarm panel is detected by the alarm system. Pass
Open Alarm Circuits Electrical opens in initiating and indicating circuits are detected. Pass
Short Alarm Circuits Electrical shorts in initiating and indicating circuits are detected. Pass
Ground Faults Detected Ground faults in alarm circuits are detected Pass
Panel Inspection (Alarm Panel 2)
Yes System was in operation upon arrival? Yes Panel and surrounding equipment,conduit and wiring
well secured and in good condition
Yes Are all lamps and displays operating correctly? Yes Primary power supply operates properly under full
load?
Yes Surge/Transient suppressors visually inspected? Yes Have all fuses been checked for rating and
supervision?
Yes Are drawings and wiring diagrams available at the Yes Are operating instructions posted or available at the
panel? panel?
Yes Are zones labeled and identified?
Alarm Device List
— c CO
CO O_ c
F.U O N
Device Type Zone/Address Location/Description Manufacturer Modelco c 0 tP F_
U a
Activity center System Sensor i4 Ok
Main House East Hall Ok
Main House West Hall#1 Ok
Main Hall West Hall#2 Ok
Smoke Detector-PE Mechanical Room System Sensor 2WB Ok Ok
Smoke Detector-PE Activity center System Sensor i4 Ok Ok
Smoke Detector-PE Main House East Hall System Sensor Ok Ok
Smoke Detector-PE Main House Office System Sensor Ok Ok
Smoke Detector-PE Main House West Hall#1 System Sensor Ok X
Smoke Detector-PE Main House West Hall#2 System Sensor Ok Ok
Print Date: 6/17/2019 Page 2 of 4
Copyright 2002-2018 Life Safety Inspector,OnSite Software
F.() 1 ZU—cx)0/
r)06- Zbo ()3
Report of Inspection/Test Wilgus Fire Control, Inc
Annual Sprinkler
06/17/2019
Property: Butte County Behavioral Health
Owner: Butte County General Services Inspection Ref: 200000006198
Alarm Device List
O
Device Type Zone/Address Location/Description Manufacturer Model >, c .0
U u_
Smoke Detector-PE Rose Room System Sensor Ok Ok
Smoke Detector-PE Sunflower Room System Sensor Ok Ok
Smoke Detector-PE Clover Room System Sensor Ok Ok
Smoke Detector-PE Lilac Room System Sensor Ok Ok
Smoke Detector-PE Orchid Room System Sensor Ok Ok
Manual Pull Station Garden Entry Silent Knight Ok Ok
Manual Pull Station Activity Center Entry Silent Knight Ok Ok
Manual Pull Station Main House Entry Silent Knight Ok Ok
Water Flow Switch Ok Ok
Valve Tamper Switch Ok Ok
Horn/Strobe Activity Center Ok Ok
Horn/Strobe Main House Living Room Ok Ok
Horn/Strobe Main House West Hall Ok Ok
Horn/Strobe Ok Ok
Horn/Strobe Ok Ok
Horn Exterior Front Ok Ok
Horn Exterior East Ok Ok
Horn Ok Ok
Strobe Activity Center Ok Ok
Strobe Activity Center Restroom Ok Ok
Strobe Main House East Restroom Ok Ok
Strobe Main House Kitchen Ok Ok
Strobe Main House Men's Restroom Ok Ok
Strobe Main House Women's Restroom Ok Ok
Alarm Device Number of Items: 34 S Repaired,Replaced and Tested Ok 0 0
Detail Summary X Number of Items Requiring Service 0 1
Ok-Item passed NI Number of Items NOT Inspected 0 0
Print Date: 6/17/2019 Page 3 of 4
Copyright 2002-2018 Life Safety Inspector,OnSite Software
Report of Inspection/Test Wilgus Fire Control, Inc
Annual Sprinkler
06/17/2019
Property: Butte County Behavioral Health
Owner: Butte County General Services Inspection Ref: 200000006198
Deficiency / Recommendations Summary
These items were deficient and do not meet the requirements of the applicable code at the time of the inspection. Items marked
Recommendation are not required by the applicable code but are opportunities to improve the Life Safety of the property.
Signatures
Inspection
ivauian:. I state that the information on this form is correct at the time and place of my inspection,
Belmont and all equipment tested at this time was left in operational condition upon completion of
this inspection except as noted.
Sprink
Spare heads?
2 riser,1 drain
75,55,75
45 sec alarm
OS&Y at street
Lock change,no key available
Device Inspection/Test Main House West Hall#1 Main House West Hall#1
CO Detector Main House West Hall#1
Pass Test?
Smoke Detector Inspection/Test Main House West Hall#1 Main House West Hall#1
System Sensor Initiating Device Smoke Detector-PE Main House West Hall#1
Alarm Test?
Print Date: 6/17/2019 Page 4 of 4