HomeMy WebLinkAboutFAI20-0001 Fire Annual Inspection 2020 Sprinkler Test Fail/( a-C3 C°c1 (Do , - L9c -- uSL Report of Inspection/Test Wilgus Fire Control, Inc Annual Sprinkler 1703 Sonoma St 06/17/2019 Redding, CA 96001 Property Owner/Agent Butte County Behavioral Butte County General Health Services Conducted by: Nathaniel Belmont 556 Cohasset Rd 2081 Second St Oroville, Ca Chico, Ca 95965 Inspection Ref: 200000006198 Dean Olson (530)538-7407 Print Date: 6/17/2019 Signatures Inspector-Printed Inspector-Signature Date Completed I state that the information on this form is correct at the Nathaniel Belmont 6/17/19 time and place of my inspection,and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted. Sprink Spare heads? 2 riser,1 drain 75,55,75 45 sec alarm OS&Y at street Lock change,no key available Equipment Summary Site Inspected Unable to Serviced Failed Description Inspect Repaired Qty Qty % Qty % Qty % Qty Alarm Alarm Panel 2 1 1 100.0% 0 0.0% 0 0.0% 0 0.0% Alarm Battery Sealed Lead Acid 1 1 100.0% 0 0.0% 0 0.0% 0 0.0% Alarm CO Detector 4 4 100.0% 0 0.0% 0 0.0% 1 25.0% Alarm Indicating Device Strobe 6 6 100.0% 0 0.0% 0 0.0% 0 0.0% Horn/Strobe 5 5 100.0% 0, 0.0% 0 0.0% 0 0.0% Horn 3 3 100.0% 0 0.0% 0 0.0% 0 0.0% Alarm Initiating Device Smoke Detector-PE 11 11 100.0% 0 0.0% - 0 0.0% 1 9.1% Manual Pull Station 3 3 100.0% 0 0.0% 0 0.0% 0 0.0% Valve Tamper Switch 1 1 100.0% 0 0.0% 0 0.0% 0 0.0% Water Flow Switch 1 1 100.0% 0 0.0% 0 0.0% 0 0.0% Alarm Panel Information Panel Manufacturer Model Serial No. Location Silent Knight Overcurrent Protect Type Overcurrent Size(Amps) Primary Supply Disconnect Location/Panel#/Breaker# RECEIVED BUTTE COUNTY Print Date: 6/17/2019 DEC 19 2019 Page 1 of 4 Copyright 2002-2018 Life Safety Inspector,OnSite Software BEHAVIORAL HEALTH,ASD Report of Inspection/Test Wilgus Fire Control, Inc Annual Sprinkler 06/17/2019 Property: Butte County Behavioral Health Owner: Butte County General Services Inspection Ref: 200000006198 Battery Test E o 2 o o § a� as '5 .r co '5 Q a Manufacturer y as .0 N 'N a) rn an m m co c Location Type o m a a> Y o co co o al v 0 0 5 _ 3 Model f6Q o c a, `o 0U > J 2 cu 0 -02 0 y U U U j fa cv as Q cc a* U aU Is FACP 2 Sealed Lead Acid Apex 1280 06/19 Ok Ok Ok 27 13 8 13 8 Ok System Function Summary& Test Function Description Test Result Alarm Functions Alarm Bells/Horns/Strobes Evacuation Alarm functions including Bells/Horns/Strobes actuate properly Pass Alarm Panel Supervisory Functions Panel AC Power Loss Loss of AC power to the alarm panel is detected by the alarm system. Pass Panel Sec Power Loss Loss of Secondary power to the alarm panel is detected by the alarm system. Pass Open Alarm Circuits Electrical opens in initiating and indicating circuits are detected. Pass Short Alarm Circuits Electrical shorts in initiating and indicating circuits are detected. Pass Ground Faults Detected Ground faults in alarm circuits are detected Pass Panel Inspection (Alarm Panel 2) Yes System was in operation upon arrival? Yes Panel and surrounding equipment,conduit and wiring well secured and in good condition Yes Are all lamps and displays operating correctly? Yes Primary power supply operates properly under full load? Yes Surge/Transient suppressors visually inspected? Yes Have all fuses been checked for rating and supervision? Yes Are drawings and wiring diagrams available at the Yes Are operating instructions posted or available at the panel? panel? Yes Are zones labeled and identified? Alarm Device List — c CO CO O_ c F.U O N Device Type Zone/Address Location/Description Manufacturer Modelco c 0 tP F_ U a Activity center System Sensor i4 Ok Main House East Hall Ok Main House West Hall#1 Ok Main Hall West Hall#2 Ok Smoke Detector-PE Mechanical Room System Sensor 2WB Ok Ok Smoke Detector-PE Activity center System Sensor i4 Ok Ok Smoke Detector-PE Main House East Hall System Sensor Ok Ok Smoke Detector-PE Main House Office System Sensor Ok Ok Smoke Detector-PE Main House West Hall#1 System Sensor Ok X Smoke Detector-PE Main House West Hall#2 System Sensor Ok Ok Print Date: 6/17/2019 Page 2 of 4 Copyright 2002-2018 Life Safety Inspector,OnSite Software F.() 1 ZU—cx)0/ r)06- Zbo ()3 Report of Inspection/Test Wilgus Fire Control, Inc Annual Sprinkler 06/17/2019 Property: Butte County Behavioral Health Owner: Butte County General Services Inspection Ref: 200000006198 Alarm Device List O Device Type Zone/Address Location/Description Manufacturer Model >, c .0 U u_ Smoke Detector-PE Rose Room System Sensor Ok Ok Smoke Detector-PE Sunflower Room System Sensor Ok Ok Smoke Detector-PE Clover Room System Sensor Ok Ok Smoke Detector-PE Lilac Room System Sensor Ok Ok Smoke Detector-PE Orchid Room System Sensor Ok Ok Manual Pull Station Garden Entry Silent Knight Ok Ok Manual Pull Station Activity Center Entry Silent Knight Ok Ok Manual Pull Station Main House Entry Silent Knight Ok Ok Water Flow Switch Ok Ok Valve Tamper Switch Ok Ok Horn/Strobe Activity Center Ok Ok Horn/Strobe Main House Living Room Ok Ok Horn/Strobe Main House West Hall Ok Ok Horn/Strobe Ok Ok Horn/Strobe Ok Ok Horn Exterior Front Ok Ok Horn Exterior East Ok Ok Horn Ok Ok Strobe Activity Center Ok Ok Strobe Activity Center Restroom Ok Ok Strobe Main House East Restroom Ok Ok Strobe Main House Kitchen Ok Ok Strobe Main House Men's Restroom Ok Ok Strobe Main House Women's Restroom Ok Ok Alarm Device Number of Items: 34 S Repaired,Replaced and Tested Ok 0 0 Detail Summary X Number of Items Requiring Service 0 1 Ok-Item passed NI Number of Items NOT Inspected 0 0 Print Date: 6/17/2019 Page 3 of 4 Copyright 2002-2018 Life Safety Inspector,OnSite Software Report of Inspection/Test Wilgus Fire Control, Inc Annual Sprinkler 06/17/2019 Property: Butte County Behavioral Health Owner: Butte County General Services Inspection Ref: 200000006198 Deficiency / Recommendations Summary These items were deficient and do not meet the requirements of the applicable code at the time of the inspection. Items marked Recommendation are not required by the applicable code but are opportunities to improve the Life Safety of the property. Signatures Inspection ivauian:. I state that the information on this form is correct at the time and place of my inspection, Belmont and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted. Sprink Spare heads? 2 riser,1 drain 75,55,75 45 sec alarm OS&Y at street Lock change,no key available Device Inspection/Test Main House West Hall#1 Main House West Hall#1 CO Detector Main House West Hall#1 Pass Test? Smoke Detector Inspection/Test Main House West Hall#1 Main House West Hall#1 System Sensor Initiating Device Smoke Detector-PE Main House West Hall#1 Alarm Test? Print Date: 6/17/2019 Page 4 of 4 Copyright 2002-2018 Life Safety Inspector,OnSite Software