HomeMy WebLinkAboutB19-3775 CF Fire Alarm Inspection SYSTEM RECORD OF COMPLETION
This form is to be completed by the system installation contractor at the time ofsystem acceptance and approval.
It shall be permitted to modifi,this form as needed to provide a more complete and/or clear record.
Insert N/A in all unused lines.
Attach additional sheets,data,or calculations as necessary to provide a complete record.
Form Completion Date: 4/30/2020 Supplemental Pages Attached: Yes
1. PROPERTY INFORMATION
Name of property: Helena Chemical
Address: 1566 Nelson Rd. Durham, CA. 95938
Description of property: Warehouse
Name of property representative: Helena Chemical
Address:
Phone: Fax: E-mail:
2. INSTALLATION, SERVICE,TESTING,AND MONITORING INFORMATION
Installation contractor: Foothill Fire Alarm &Security, Inc.
Address: 170 Erma Ct. Chico, CA. 95928
Phone: 530.826.3013 Fax: 530.893.3013 E-mail: alarms@ffprotection.com
Service organization: Foothill Fire Alarm&Security, Inc.
Address: 170 Erma Ct. Chico, CA. 95928
Phone: 530.826.3013 Fax: 530.893.3013 E-mail: alarms@ffprotection.com
Testing organization: Foothill Fire Alarm&Security, Inc.
Address: 170 Erma Ct. Chico, CA. 95928
Phone: 530.826.3013 Fax: 530.893.3013 E-mail: alarms@ffprotection.com
Effective date for test and inspection contract:
Monitoring organization: Foothill Fire Alarm &Security, Inc.
Address: 170 Erma Ct. Chico, CA. 95928
Phone: 530.826.3013 Fax: 530.893.3013 E-mail: alarms@ffprotection.com
Account number: Z570171 Phone line 1: 530.566.9853 Phone line 2: 530.566.9801
Means of transmission: POTS
Entity to which alarms are retransmitted: Butte County Cal Fire Phone: 530.538.7322
3. DOCUMENTATION
On-site location of the required record documents and site-specific software: FACP
4. DESCRIPTION OF SYSTEM OR SERVICE
This is a: ❑New system •Modification to existing system Permit number: B19-3775
NFPA 72 edition: 2016
4.1 Control Unit
Manufacturer: Silent Knight Model number: 5700
4.2 Software and Firmware
Firmware revision number: N/A
4.3 Alarm Verification a This system does not incorporate alarm verification.
Number of devices subject to alarm verification: Alarm verification set for seconds
Copyright m 2012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution.
SYSTEM RECORD OF COMPLETION (continued)
5. SYSTEM POWER
5.1 Control Unit
5.1.1 Primary Power
Input voltage of control panel: 120vac Control panel amps: 3
Overcurrent protection: Type: Circuit Breaker Amps: 20 .
Branch circuit disconnecting means location: Elec. Rm. Panel "LAA° Number: 22
5.1.2 Secondary Power
Type of secondary power: Batteries •
Location,if remote from the plant: FACP
Calculated capacity of secondary power to drive the system:
In standby mode(hours): 24 In alarm mode(minutes): 15
5.2 Control Unit
❑ This system does not have power extender panels
® Power extender panels are listed on supplementary sheet A
6. CIRCUITS AND PATHWAYS
Pathway Type I Dual Media Pathway I Separate Pathway i Class ! Survivability Level
Signaling Line I I X B 0 .
Device Power I I X I B I 0
Initiating Device I I X I B 0 .
Notification Appliance I i X I B I 0 •
Other(specify):
7. REMOTE ANNUNCIATORS •
Type I Location
NONE I •
I .
8. INITIATING DEVICES
Addressable or
Type Quantity I Conventional I Alarm or Supervisory Sensing Technology
Manual Pull Stations 12 Conventional with Module I A I N/A
Smoke Detectors 1 A I A Photoelectric
Duct Smoke Detectors 0 I
Heat Detectors 1 Conventional with Module I A Fixed/Rate of Rise
Gas Detectors 0 I I
Waterflow Switches 3 Conventional with Module I A I Flow
Tamper Switches 15 Conventional with Module I S I Switch
Copyright 0 2012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution.
SYSTEM RECORD OF COMPLETION (continued)
9. NOTIFICATION APPLIANCES
Type I Quantity I Description
Audible I I
Visible I 4 I Strobe
Combination Audible and Visible I 14 I Horn Strobe
10. SYSTEM CONTROL FUNCTIONS
Type I Quantity
Hold-Open Door Releasing Devices I N/A
HVAC Shutdown N/A
Fire/Smoke Dampers I N/A
Door Unlocking I N/A
Elevator Recall ! N/A
Elevator Shunt Trip N/A
11. INTERCONNECTED SYSTEMS
IN This system does not have interconnected systems.
❑ Interconnected systems are listed on supplementary sheet
12. CERTIFICATION AND APPROVALS
12.1 System Installation Contractor
This system as specified herein has been installed according to all NFPA standards cited herein.
�
Signed: 5 P0�/ Printed name: Shane DeValera Date: 4/30/2020
organization: Foothill Fire Protection Title: Manager Phone: 530.826.3013
12.2 System Operational Test
This system as specified herein has tested according to all NFPA standards cited herein.
Signed: c ,yy . Z7d/alg44., Printed name: Shane DeValera Date: 4/30/2020
Organization: Foothill Fire Protection Title: Manager Phone: 530.826.3013
12.3 Acceptance Test
Date and time of acceptance test: 4/30/2020 12:00//PM
Installing contractor representative: c/// ._/L� Z72YG
Testing contractor representative: c5'%2 t4. Z 4.1
Property representative: .,
AHJ representative: (/ J L I 30--24
Copyright B 2012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution.
NOTIFICATION APPLIANCE POWER PANEL
SUPPLEMENTARY RECORD OF COMPLETION
This form is a supplement to the System Record of Completion.It includes a list of types and locations
of notification appliance power extender panels.
This form is to be completed by the system installation contractor at the time of system acceptance and approval.
It shall be permitted to modify this form as needed to provide a more complete and/or clear record.
Insert N/A in all unused lines.
Form Completion Date: 4/30/2020 Number of Supplemental Pages Attached: 1
1. PROPERTY INFORMATION
Name of property: Helena Chemical
Address: 1566 Nelson Rd. Durham, CA. 95938
2. NOTIFICATION APPLIANCE POWER EXTENDER PANELS
Make and Model Location Area Served Power Source
PSN-106 AG Chem (North Whse) L1 } I
See Main System Record of Completion for additional information,certifications,and approvals.
Copyright 0 2012 National Fire Protection Association.This form may be copied for individual use other than for resale.It may not be copied for commercial sale or distribution.