FIRE SAFETY CORRECTION NOTICE
FILE NUMBER PAGE OF PAGE
FAI15-0052 1
NAME HOURS MINUTES
Butte Community College
ADDRESS
3536 Butte Campus Drive, Oroville, CA 95965, (530) 895-2511
THE CALIFORNIA HEALTH AND SAFETY CODE AND THE STATE FIRE MARSHAL'S
REGULATIONS REQUIRE THE FOLLOWING FIRE SAFETY DEFICIENCIES BE CORRECTED:
Project Information
A required Fire Life and Safety inspection pursuant to Health and Safety Code § 13146.3 was conducted at
the above facility from September 3, 2019 to September 5, 2019. Due to the size of the campus and duration
of inspection I was unaccompanied, however contact was made prior to inspection with Mark Allen,
Maintenance Lead, 530-624-4199.
Inspection
The inspection consisted of the entire campus including; Public Safety Training Grounds (PSTG), Facilities
Planning Management (FPM), Recycling Center, Physical Education (GYM), Mens Locker Room (MLR),
Womens Locker Rooms (WLR), Arts (ARTS), Student Health Clinic (SHC), Swing Space A (SSA), Swing
Space C (SSC), Swing Space F (SSF), Swing Space G (SSG), Regional Testing Center (RTC), Business
Education (BE), Student Administration Services (SAS), Campus Center (CC), Allied Health/Public Service
Center (AHPS), Library (LB), Media Center (MC), Learning Resource Center (LRC), Life Science (LS),
Automotive Technology (AT), Physical Science (PS), Welding Manufacturing (WM), Ag Storage, Mechanized
Ag (MA), Ag Repair Shop, Horticulture Storage, Green Houses, and Environmental Horticulture (EH). The
Child Development Center was previously inspected. During the inspection the following deficiencies were
noted.
Deficiencies
PSTC- Fire Grounds Training Building
Remove items blocking Air Compressor Electrical Disconnect LDPG#6, CFC 605.3
Remove storage (tires)from Fire Sprinkler Riser Room, CFC 315.3.3, 509.2
PSTC- Fire Grounds Training Building cont.
Fire Alarm Report from 12-28-2018 by Voltage Specialist states that white board is covering
annunciator. Was white board removed or annunciator relocated?
Fire Damper Inspection Report from 11/13/2016 by Voltage Specialist states multiple dampers
failed to close due to a bad actuator. Have repairs been made?
Gym 123
Label Fire Department Connection. A metal sign with letters no less 2" high, and a contrasting
background. Sign should read "FDC" and denote the building the connection serves. CFC 912.5
MLR 114
LPG container stored inside office. Remove container. CFC 6103.2.1
ARTS Building
Label Fire Department Connection. A metal sign with letters no less 2" high, and a contrasting
background. Sign should read "FDC" and denote the building the connection serves. CFC 912.5.
Remove blue tape on sprinkler head escutcheons at northeast exterior corner of building
adjacent to ARTS 138.
Fire Damper Inspection Report from 12/22/2016 by Voltage Specialist states; FSD 87 key is
broken off in switch. Switch need replaced; FSD 78 is STUCK CLOSED, FSD 41 switch did not close
damper, FSD 4 switch had no light and did not close damper; next to FSD87 there is an unused
damper test switch. Have repairs been made?
ARTS 105
Perform general housekeeping, correct storage, CCR T19, Div.1 §3.08
ARTS 162 AN Loft
Remove items blocking Handicapped Elevator, CFC 1003.6, 1031.2
ARTS 166
At door 166-1, adjust door so that it opens smoothly, and does not contact floor. CFC 1031.2
ARTS 165 Hall
Remove rolling chair and riser racks from egress corridor. CFC 1031 and CCR T19, Div.1 §3.11
Remove recycling can from under fire door. CFC 703.2
ARTS 105
Perform general housekeeping, correct storage. CCR T19, Div.1 §3.08
ARTS 252
Reinstall electrical panel cover on panel H2A. CFC 605.6
Regional Test Center(RTC)
South Door, Emergency Exit Sign non-operational, CFC 1008& 1104.5
RTC Room 103, Hall, Emergency Exit Light non-operational, CFC 1008 & 1104.5
SAS
Label Fire Department Connection. A metal sign with letters no less 2" high, and a contrasting
background. Sign should read "FDC" and denote the building the connection serves. CFC 912.5
CC
Fire Alarm Report from 12/28/2018 by Voltage Specialist states battery was not dated. Has
battery been replaced?
Remove items blocking electrical panel access, CFC 605.3
H
Remove trashcan from blocking Fire Extinguisher cabinet, second floor dining area
i Y'I k: .III
l
LI B
Fire Damper Inspection Report from 11/18/2016 by Voltage Specialist states multiple dampers
failed to close due to a bad actuator. Have repairs been made?
MC
Label Fire Department Connection.A metal sign with letters no less 2" high, and a contrasting
background. Sign should read "FDC" and denote the building the connection serves. CFC 912.5
AH PS
Label Fire Department Connection.A metal sign with letters no less 2" high, and a contrasting
background. Sign should read "FDC" and denote the building the connection serves. CFC 912.5
APHS 003
Secure gas cylinder. CFC 5303.5.3
AHPS 129
Fire Sprinkler Riser is blocked. CFC 315.3.3, 509.2
AHPS 173
Clean Agent System, provide semi-annual testing and maintenance report, CCR T19 Div. 1 § 904
AHPS North
Fire Alarm Report from 1/13/2019 by Voltage Specialist states system duct detector failed to
trigger alarm? Has detector been replaced?
Fire Damper Inspection Report from 12/22/2016 by Voltage Specialist states several dampers
failed. No note/correction page attached to report. Have repairs been made?
BE
Fire Alarm Report from 12/26/2018 by Voltage Specialist states system HVAC does not have
duct detection device? Has detection been installed?Additionally, southwest pull station was
noted as sticking. Has device been repaired or replaced?
TE
Provide current copy of annual testing and maintenance for FM 200 Extinguishing System, last
was 3-28-2018.
CDC
Fire Alarm Report from 12/28/2018 by Voltage Specialist states battery was not dated. Has
battery been replaced?
LS
Fire Damper Inspection Report from 11/02/2016 by Voltage Specialist states several dampers
failed to close when Fire Alarm was activated. Have repairs been made?
LRC
Fire Damper Inspection Report from 12/02/2016 by Voltage Specialist states damper 12-6 failed
to close, and had a bad actuator. Have repairs been made?
WM
Label Fire Department Connection.A metal sign with letters no less 2" high, and a contrasting
background. Sign should read "FDC" and denote the building the connection serves. CFC 912.5
Southeast corner, lower WM outside storage, remove items blocking Alarm Pull Station, CFC
1003.6, 1031.2
/�jr
t.,
MI •
WM BC403 Gas Cylinder Storage
Secure gas cylinders. (Not to chain link fencing). CFC 5303.5.3
y4. '/ �E/P.1 ii'' P, `�f
rot,
,;-,
f.,r,i.e.),A), _.,..1.4 , -; f
r-:.v'-1.4e,,,- '.. ''',":",/,'/V.:,::, 1 ,0 1 i „I
,_. _, .„,, ,,,., ,,,,,,. ., , .1 , i,,, I,' ''"'+-
/ t,^ ' J
p i.d �,. m. = yam_
►ltIrA►„ t . rti
MA Repair Shop
Remove yellow extension cord to fridge, replace with permanent wiring, CFC 605.5
FPM
Fire Alarm Report from 1/13/2019 by Voltage Specialist states system duct detector failed to
trigger alarm? Has detector been replaced?
Fire Damper Inspection Report from 12/03/2016 by Voltage Specialist states several dampers
held open by wire. Have fusible links been replaced?
Items Discussed/Requested
After the inspection, discussed with Mark Allen general fire safety practices and procedures.
Forwarded a copy of the report on 9-12-19 via email to Mark Allen and Kim Jones.
ISSUED BY(DEPUTY FIRE MARSHAL) RECEIVED BY DATE
Mark Allen
Christopher Boyd Email: allenmar@butte.edu 9-12-2019
Please provide the following;
Fire Extinguisher-Monthly Inspection Logs for 2019
Alternative Automatic Extinguishing Systems-Testing and maintenance reports for CC Kitchen (ANSUL)
and TE and AHPS South (FM 200).
Fire Alarm Systems-Annual testing and maintenance reports for SAS,TE, LRC as they were not included
in reports provided.
Fire Dampers-Annual testing and maintenance reports for AHPS South as they were not included in
reports provided.
Overhead Fire Doors and Curtains- Provide documentation of annual testing and maintenance.These
operational tests can be performed by Butte College Maintenance personnel.