FIRE SAFETY CORRECTION NOTICE
FILE NUMBER PAGE OF PAGE
FAI15-0052 1 12
NAME HOURS MINUTES
Butte Community College
ADDRESS
3536 Butte Campus Drive, Oroville, CA 95965, (530) 895-2511
THE CALIFORNIA HEALTH AND SAFETY CODE AND THE STATE FIRE MARSHAL'S
REGULATIONS REQUIRE THE FOLLOWING FIRE SAFETY DEFICIENCIES BE CORRECTED:
Project Information
A required Fire Life and Safety inspection pursuant to Health and Safety Code § 13146.3 was conducted at
the above facility from July 28, 2020 to August 2, 2020. Due to the size of the campus and duration of
inspection I was unaccompanied, however contact was made prior to inspection with Mark Allen, Facilities,
530-624-4199.
Inspection
The inspection consisted of the entire campus including; Public Safety Training Grounds (PSTG), Welding
Manufacturing (WM), Facilities Planning Management (FPM), Recycling Center, Physical Education (GYM),
Mens Locker Room (MLR), Womens Locker Rooms (WLR), Field House (KAP), Arts (ARTS), Student Health
Clinic (SHC), Swing Space A (SSA), Swing Space C (SSC), Swing Space F (SSF), Swing Space G (SSG),
Regional Testing Center (RTC), Business Education (BE), Student Administration Services (SAS), Campus
Center (CC), Allied Health/Public Service Center (AHPS), Library (LB), Media Center (MC), Learning
Resource Center (LRC), Life Science (LS), Automotive Technology (AT), Physical Science (PS), Ag Storage,
Mechanized Ag (MA), Ag Repair Shop, Horticulture Storage, Green Houses, Environmental Horticulture (EH),
and Child Development Center (CDC). During the inspection the following deficiencies were noted.
Deficiencies
WM at Exterior Gas Storage Area
Extension cord use. Remove cord or provide permanent wiring. CFC 605.5
WM 128
Remove items blocking electrical panels and maintain access. CFC 605.5
`1
F1
I
WM North Welding Shop between Booth 30 and 31
Open electrical junction box, provide cover plate. CFC 605.6
�a ,-
WM Exterior Breezeway at Panel HPZ
Remove items blocking electrical panels and maintain access. CFC 605.5
' 3 pi;ro',00
}
N.
ill
41... ,
cow
WM Various locations,Oily Rag Bins
Empty oily rag containers daily. CCR,T19, Div. 1, §3.19 (2) (c)
,:rr
iirr
ler
ark
WM Exterior FDC
FDC is missing caps. Provide caps as noted in Voltage Specialist's discrepancy report from 6-9-20.
FPM at Pete Huru's Office
Exit sign is non operative. Repair or replace sign. CFC 1104.5
Gym 118
Extension cord use. Remove cord or provide permanent wiring. CFC 605.5
400
Gym 122
Electrical Panel 1LA, missing blank cover plate, provide cover plate. CFC 605.6
.r
EngJ
1E1 e
Gym Fire Sprinkler System
Replace automatic fire sprinkler system inspector test valve as noted in Voltage Specialist's
discrepancy report from 6-9-20.
MLR 102
Fire Extinguisher is mounted too high.Top of extinguisher cannot be above 5'from floor.
iIt
1 —
IlMI
MLR 102
Ladders are blocking fire extinguisher access, remove ladders. CFC 906.6
i In I,
.1 ti, \Ili i
1
4'lit
- . , 1 4. 'r.„t---,. .
lifi OSI
MLR at MLR 107
Exit sign is damaged. Repair or replace sign. CFC 1104.5
w.
alli
v-
1 1
WLR South Wall at Restroom
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
WLR at WLR 115
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
WLR at WLR 117
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
KAPC 203
Exit Sign and Emergency Lighting are non-operational. Repair or replace lighting. CFC 1008 and
1104.5
KAPC 204
Exit Sign and Emergency Lighting are non-operational. Repair or replace lighting. CFC 1008 and
1104.5
KAPC 209
Exit Sign and Emergency Lighting are non-operational. Repair or replace lighting. CFC 1008 and
1104.5
KAPC 214
Exit Sign and Emergency Lighting are non-operational. Repair or replace lighting. CFC 1008 and
1104.5
KAPC 215
Exit Sign and Emergency Lighting are non-operational. Repair or replace lighting. CFC 1008 and
1104.5
KAPC 216
Exit Sign and Emergency Lighting are non-operational. Repair or replace lighting. CFC 1008 and
1104.5
ARTS 166
At door 166-1, adjust door so that it opens smoothly,and does not contact floor. CFC 1031.2
KAPC Exterior FDC
Remove one of the FDC connectors and provide FDC caps as noted in Voltage Specialist's
discrepancy report from 6-9-20.
ARTS 205
Extension cord use. Remove extension cord or provide permanent wiring. CFC 605.5
SSA 102
Exit door at northeast corner, adjust door so that it opens smoothly. CFC 1031.2
A*
K
'
hr
SAS 152
Items blocking fire extinguisher access, remove items, maintain access. CFC 906.6
Vey 1
CC at Cafeteria Check Stand
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
CC 212.1
Fire Extinguisher not mounted. Mount Fire Extinguisher. CFC 906.7
CC, Bookstore, Store room
Extension cord use. Remove extension cord or provide permanent wiring. CFC 605.5 and 605.9.1
_�
1 ��
Or I
1 .111
! _II ii
III 11 l �`r '
it
illF, 5,
CC, Book Store, Beverage Display at West Register
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
CC, Bookstore, East Register
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
CC, Bookstore, North Wall
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
CC 108.1
Extension cord use. Remove extension cord or provide permanent wiring. CFC 605.5 and 605.9.1
CC, First Floor,West side at Stair and Water Fountain
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
CC, Bookstore/Lounge Area,South side
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
CC, Bookstore
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
CC, Bookstore, First Floor at East side
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
LB 103
Missing ceiling tile. Replace tile. CFC 703.1
e
LB 207 Custodian Room
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
LB 210
Extension cord use. Remove extension cord or provide permanent wiring. CFC 605.5
0Y r.
Elia**
\-,
LB 221
Fire Extinguisher not mounted. Mount Fire Extinguisher. CFC 906.7
LB 308
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
LB
Replace missing sprinkler escutcheons in 3rd floor gender RR, 2nd floor AC room, Room 216, and
in Room 104 as noted in Voltage Specialist's discrepancy report from 6-9-20.
TE 105 A/B Hall
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
Missing ceiling tile. Replace tile. CFC 703.1
a� t
S
AHPS 166 at South Door
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
AHPS 227
Hole in ceiling. Repair hole. CFC 703.1
BE 107
Exit Sign and Emergency Lighting are non-operational. Repair or replace lighting. CFC 1008 and
1104.5
BE 115
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
BE 115
Replace ceiling tile, open electrical junction box, provide coverplate. CFC 703.1 and 605.6
11111
BE 129
Fire Extinguisher is mounted too high.Top of extinguisher cannot be above 5'from floor. CCR,
T19, Div. 1, §567.4
BE 136
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
Emergency Exit is blocked. Remove obstructions.
40. ad
CDC Lady Bugs Room
Remove Fabric covering at ceiling or provide documentation that fabric meets CFC Chapter 8
and CCR T19. Div.1 requirements or has been treated with a fire retardant coating. CFC 803.4
CDC Catepillar Room
Remove Fabric covering at ceiling or provide documentation that fabric meets CFC Chapter 8
and CCR T19. Div.1 requirements or has been treated with a fire retardant coating. CFC 803.4
.411`.
�I A
A �.
CDC Butterflies Room
Remove Fabric covering at ceiling or provide documentation that fabric meets CFC Chapter 8
and CCR T19. Div.1 requirements or has been treated with a fire retardant coating. CFC 803.4
` -4010-
CDC
`CDC Bumblebee Room
Remove Fabric covering at ceiling or provide documentation that fabric meets CFC Chapter 8
and CCR T19. Div.1 requirements or has been treated with a fire retardant coating. CFC 803.4
LRC First Floor West Entry
Open electrical junction box, provide cover plate. CFC 605.6
LS 105
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
LS Lab Area Across from 123 A
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
LS 111
Emergency Lighting is non-operational. Repair or replace lighting. CFC 1008 and 1104.5
Items Discussed/Requested
After the inspection, discussed with Mark Allen general fire safety practices and procedures.
Forwarded a copy of the report on 8-15-20 via email to Mark Allen.
ISSUED BY(DEPUTY FIRE MARSHAL) RECEIVED BY DATE
Mark Allen
Christopher Boyd Email: allenmar@butte.edu 8-15-2020
Please provide the following;
Fire Extinguisher-Monthly Inspection Logs for 2020, Annual maintenance report
Automatic Fire Sprinkler Systems-Annual testing, inspection and maintenance reports
Alternative Automatic Extinguishing Systems-Testing, inspection and maintenance reports for CC
Kitchen (ANSUL) and TE and AHPS South (FM 200).
Fire Alarm Systems-Annual testing, inspection and maintenance reports for all buildings.
Overhead Fire Doors and Curtains- Provide documentation of annual testing and maintenance.These
operational tests can be performed by Butte College Maintenance personnel.