Loading...
HomeMy WebLinkAboutFAI19-0036 CF Alarm Inspection ALARM AND DETECTION REPORT Page 1 of 4 Oyu—4 E0 — 0 G% 641 VOhTAGE\%PEcIAusTs 530-624-4514 C10/C18 License#880862 www.VoltageSpecialists.com Inspection # 1-123 • ALARM & DETECTION EQUIPMENT TEST REPORT Type of Inspection:ANNUAL Date: 2-28-20 Customer DURHAM USD Site: MISSION HILLS SCHOOL Street: 9455 PUTNEY DRIVE Contact: Eric City/State: DURHAM, CA Phone #: 530-519-4604 Fax#: 1. Before Test Notify Proper Authorities: Name Phone # A. Owner or Owner's Rep Eric 530-519-4604 B. Fire Department Cal Fire 530 891-2788 C. Central Station NA D. Central Station Acct# NA 2. Control Panel Status Yes No Note # A. Is the system monitored by Central Station? I X I On Test Time: 3:00 Return to Service Time: 5:00 B. Is the Power Light on? X C. Does the Panel indicate Normal conditions? X D. Are all indicating Lamp Bulbs in Operator order? X E. Does the Trouble Light operate? X F. Does the Silence Switch Operate? X G. Battery A.H.12 Date Batteries Installed: 1-3-19 H. Does the Panel have Non-Operational Zones? X I. Does the Panel have Battery Backup? X J. Do the batteries indicate they are Properly Charged? X Condition of Batteries: Good Note# Battery Voltage with AC Power: 27.95 Battery Voltage without AC Power: 27.58 K. List any trouble conditions on panel before test: Note# Note# Comments: Note# Note# 3. FACP Manufacturer: SILENT KNIGHT Model# 5820XL System Type: ADDRESSAB Location of Annunciators: NA Location of Primary Power Source:BEHIND PORT Panel# Breaker Comments: Note# Note# • FCPS: Manufacturer: Silent Kni ht Model# 5495 Panel/Breaker# g Location:P-5 Battery Voltage with A/C Power: 27.36 w/o A/C Power 27.17 Date: 1-3-19 FCPS: Manufacturer: Model# Panel/Breaker# Location: Battery Voltage with A/C Power: w/o A/C Power Date: FCPS: Manufacturer: Model# Panel/Breaker# Location: Battery Voltage with A/C Power: w/o A/C Power Date: Owner/Rep: Phone#: Date: Inspector: Mat Machado Phone#: 530-362-2609 Date:2-28-20 Owners Rep Sign: Date: Inspector Inspector Sign: ALARM AND DETECTION REPORT Page 2 of 4 Property Site: MISSION HILLS SCHOOL Operational #Tested This Equipment Total# Report Yes N/A Note# 4. Remote Annunciators 5. Zones 6. Manual Stations (Pull) Hardwire Addressable 6 6 X 7. Detectors Photoelectric 8 8 X Ionization Heats/Fixed or R of R 8 8 X Flame Duct(See#15) I 8. Horn/Strobe 7 7 X I Strobe Only 3 I 3 X Bell I Speakers Horn 4 I 4 X 9. I 10. Automatic Door Release X 11. Water Flow switches X Did W/F Ring Outside Bell? X Did W/F Activate Alarm Panel? X 12. Tamper Switches X 13. PIV X OS&Y X I14. 15. Did test of Duct Detectors shut down air handling units? X 16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line)receive signal? X 17. Is system reset for normal conditions? X I18. Is system restored to operational service? X I 19. Have Proper Authorities (see#1)been notified system is back in service? X List Proper Authorities:Cal Fire 20. Indicate%of equipment tested this report 25% 50% 75% ✓ 00% 21. Indicate%of equipment tested YTD 25% 50% 75% V 100% Comments for any"no"answers or explanations (Note#): 2-28-20 C6V5W— Owners Rep Sign: Date: Inspector Sign: ALARM AND DETECTION REPORT Page 3 of 4 Property Site: MISSION HILLS SCHOOL Zone or DEVICE SLc DEVICEu TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL HT GIRLS RR X 33 10 PS ROOM 1 X 33 3 PS Paradise Rm 1 X 33 20 PS Paradise Rm 2 X 33 21 PS Paradise Rm 3 X 33 22 PS Paradise Rm 4 X 33 23 PS Paradise Rm 5 X 33 24 PSD ROOM 1 X 33 1 PSD ROOM 1 X 33 4 PSD ROOM 2 X 33 6 PSD ROOM 2 X 33 7 PSD HANDICAP RR X 33 9 PSD Girls RR X 33 10 PSD BOYS RR X 33 11 PSD Paradise Rm 1 X 33 27 RR ROOM 1 AC X 33 2 RR ROOM 1 AC X 33 2 RR ROOM 2 AC X 33 5 RR ROOM 2 AC X 33 5 RR BOYS RR AC X 33 8 RR GIRLS RR AC X 33 8 RR HANDICAP RR AC X 33 8 RR RR PLUMBING CHASE X 33 8 Owners Rep Sign: Date: 2-28-20 Inspector Sign: 66 ALARM AND DETECTION REPORT MISSION HILLS SCHOOL Page 4 of 4 Zone or DEVICE DEVICE SLC TYPE DEVICE LOCATION PASS FAIL NOTE # CHANNEL I I LEGEND PSD—Photoelectric Smoke Detector BD —Beam Detector H —Horn V—Visual ISD —Ionization Smoke Detector PS—Pull Station WPH—Weather Proof Horn TS-•Tamper Switch PDD —Photo Duct Smoke Detector RR—Rate of Rise Heat Detector C—Chime WF --Water Flow Switch IDD —Ion Duct Smoke Detector HT —Fixed Temp Heat Detector (V —Chime Visual DH—Door Holder DHS--Door Holder & Smoke Detector Fr) —Flame Detector S---Speaker OSY —Outside Stern &Yoke Tamper Valve SSD —Signal Station Smoke.Detector R---Rpl I AV--Au dihle Visual PR/—Pnct Inrlirat_or Valve Cur - Elevator Curtains FRD - Fire Rolldown Door SDC Smoke Detector & Door Holder Combo CO - Carbon Monoxide Detector - • - NOTE # I COMMENT I I I I I I I I I I I I -1- - I I 2-28-20 66)75149 Owners Rep Sign: Date: Inspector Sign: