ALARM & DETECTION EQUIPMENT TEST REPORT
Type of Inspection:ANNUAL Date: 2/26/20
Customer DURHAM USD
Site: DURHAM HIGH SCHOOL
Street: 9455 PUTNEY DRIVE Contact: Eric
City/State: DURHAM, CA Phone#: 530-519-4604
Fax#:
1. Before Test Notify Proper Authorities: Name Phone #
A. Owner or Owner's Rep Eric 530-519-4604
B. Fire Department DISPATCH 530-538-6460
C. Central Station NA
D. Central Station Acct# NA
2. Control Panel Status Yes No Note#
A. Is the system monitored by Central Station? ( X
On Test Time: 3:30 Return to Service Time: 8:00
B. Is the Power Light on? X !
C. Does the Panel indicate Normal conditions? X 1
D. Are all indicating Lamp Bulbs in Operator order? X I
E. Does the Trouble Light operate? X
F. Does the Silence Switch Operate? X
G. Battery A.H. 18 Date Batteries Installed: 1/19
H- Does the Panel have Non-Operational Zones? x
I. Does the Panel have Battery Backup? X
J. Do the batteries indicate they are Properly Charged? X 1
Condition of Batteries: Good Note#
Battery Voltage with AC Power: 27.86 Battery Voltage without AC Power: 27.50
K. List any trouble conditions on panel before test: Note#
Note#
Comments: Note#
Note#
3. FACP Manufacturer: SIMPLEX Model# 4020 System Type: ADDRESSAB
Location of Annunciators: MAIN OFFICE
Location of Primary Power Source:COMP LAB Panel# 1 B Breaker 17
Comments: Note#
Note#
FCPS: Manufacturer: SIMPLEX Model# 4009 Panel/Breaker# Location: NURSES OFFI(
Battery Voltage with A/C Power: 28.07 w/o A/C Power 27.65 Date: 1/19
FCPS: Manufacturer: SIMPLEX Model# 4009 Panel/Breaker# Location: NURSES OFFI(
Battery Voltage with A/C Power: 27.99 w/o A/C Power 27.67 Date: 12/19/18
FCPS: Manufacturer: SIMPLEX Model# 4009 PaneliBreaker# Location: POTTERY
Battery Voltage with A/C Power: 27.70 w/o A/C Power P7 57 Date: 10/18
Owner/Rep: Phone#:
Date:
Inspector: Mat Machado Phone#: 530-362-2609 Date:2/26/20
,1(!1!7.rh/1
ALARM AND DETECTION REPORT Page 2 of 6
Property Site: DURHAM HIGH SCHOOL
Operational
#Tested
This
Equipment Total# Report Yes N/A Note#
4. Remote Annunciators 1 1 X
5. Zones
6. Manual Stations (Pull)
Hardwire
Addressable 43 43 X
7. Detectors
Photoelectric 13 13 X
Ionization
Heats/Fixed or R of R
Flame
Duct(See#15) 7 7 X
8. Horn/Strobe 22 22 X
Strobe Only 8 8 X
Bell
Speakers I
Horn I 7 7 X
9. I
10. Automatic Door Release I
11. Water Flow switches I 2 2 1
Did W/F Ring Outside Bell? I
Did W/F Activate Alarm Panel?
12. Tamper Switches I
13. PIV I
OS & Y
14.
15. Did test of Duct Detectors shut down air handling units? X
16. Did the Monitoring Center(Fire Dept, Central Station, Lease Line) receive signal? X I
17. Is system reset for normal conditions? X
18. Is system restored to operational service? X
19. Have Proper Authorities (see#1) been notified system is back in service? X
List Proper Authorities:Cal Fire
20. Indicate %of equipment tested this report 25% 50% 75% 00%
21. Indicate %of equipment tested YTD 25% 50% 75% ✓ 00%
Comments for any"no" answers or explanations (Note#):
See Discrepancy Report
9/9k/911 (f\��
ALARM AND DETECTION REPORT Page 3 of 6
Property Site: DURHAM HIGH SCHOOL
DEVICE �10Of�c DEVICE
C
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
PDD HVAC UNIT ON BAND ROOM ROOF NORTH X 1 64
PDD HVAC UNIT ON BAND ROOM ROOF SOUTH X 1 65
PDD HVAC UNIT ON SHOP ROOF X 1 66
PDD HVAC UNIT 1 GYM ROOF X 1 67
PDD HVAC UNIT 2 GYM ROOF X 1 68
PDD HVAC UNIT 3 GYM ROOF X 1 69
PDD HVAC UNIT 4 GYM ROOF X 1 70
PS GYM EAST EXIT X 1 1
PS GYM SOUTH WEST X 2 1 2
PS GYM NORTH WEST X 1 3
PS BOYS LOCKER X 1 16
PS GIRLS LOCKER X 1 5
PS WRESTLING ROOM (WEIGHT) X 1 6
PS CAFE SOUTH WEST X 1 7
PS CAFE SOUTH EAST X 1 8
PS CAFE EAST X 1 4
PS KITCHEN NORTH X 1 10
PS MUSIC ROOM SOUTH X 1 13
PS MUSIC ROOM WEST X 1 14
PS BAND ROOM WEST X 1 15
PS BAND ROOM EAST X 2 1 9
PS ROOM 103 X 1 17
PS ROOM 104 X 1 19
PS ROOM 105 X 1 /20
fA\ )</
ALARM AND DETECTION REPORT DURHAM HIGH SCHOOL Page 4 of 6
DEVICE zone or DEVICE
SLC
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL #
PS ROOM 106 X 1 21
PS ROOM 107 X 1 22
PS ROOM 108 X 1 23
PS ADMIN EAST X 1 24
PS ROOM 102 X 1 27
PS ROOM 101 X 1 30 I
PS ADMIN WEST X 1 32 I
PS MAIN OFFICE X 1 12 I
PS ROOM 201 NORTH X 1 34
PS ROOM 202 X 1 35
PS ROOM 203 X 1 36
PS ROOM 204 X 1 37
PS ROOM 201 SOUTH X 1 38
PS ROOM 202 south X 1 39
PS PORT 61 X 1 41
PS PORT 60 X 1 42
PS AG SHOP NORTH WEST X 1 43
PS AG SHOP NORTH X 1 44
PS ROOM 25 X 1 46
PS AG SHOP SOUTH X 3 1 47
PS AG ROOM X 1 48
PS ARTS & CRAFTS FOYER X 1 49
PS ART ROOM X 1 50
PS AUTO SHOP X 1 59
PS PORT 62 X 1 62
PS PORT 63 X 1 63
1
1
nincrnn ( \ 1
ALARM AND DETECTION REPORT DURHAM HIGH SCHOOL Page 5 of 6
Zone or DEVICE
DEVICE SLC
TYPE DEVICE LOCATION PASS FAIL NOTE# CHANNEL
PSD LIBRARY X 1 25 I
PSD LIBRARY X 1 26
PSD ROOM 102 X 1 28
PSD ROOM 101 X 1 29 I
PSD MEDIA CENTER X 1 31
PSD KILN ROOM X 1 51
PSD SD1 CLASSROOM MEZZ WEST(AG MEZZ) X 1 52
PSD SD2 CLASSROOM MEZZ WEST(AG MEZZ) X 1 53
PSD SD3 CLASSROOM MEZZ WEST(AG MEZZ) X 1 54
PSD SD1 CLASSROOM MEZZ EAST(AG MEZZ) X 1 55
PSD SD2 CLASSROOM MF77 EAST(AG MF77) X 1 56
PSD ROOM 103 X 1 18
PSD NURSES OFFICE X 1 61
WF CAFETERIA JANITORS OFFICE(BOYS LOCKER) 1 1 11
WF SCIENCE WING (ROOM DIS 14) 1 1 57 I
,_,,,Pl lr fl ■ III i
ALARM AND DETECTION REPORT DURHAM HIGH SCHOOL Page 6 of
Zone or DEVICE
DEVICE CHANNEL ;
TYPE DEVICE LOCATION PASS FAIL NOTE #
I
1
! I
I
1
I I
I I I
I I
I I
1 1
LEGEND
PSG-Photoelectric Smoke Detector BD-Beam Detector Horn V-Visual
SD--Ionization Smoke Detector PS-Pell Station WPH-Weather Proof Horn TS--Tamper Switch
PDD-Photo Duct Smoke Detector RR-Rate of Rise Heat Detector C-Chime WT -Water Flow Switch
IDD-Ion Duct Smoke Detector HT -Fired Temp Heat Detector CV-Chime Visual DH-Door Holder
DHS-Door Holder- &SmokeDetector FD-FlameDetector S--Speaker OE -Outside Stem &VokeTamper Valve
tilt) —Siena{ Starifn Sm* . —RQI AV--Ali P V—Pnct Inti -At:Or Valve
Cur- Elevator Curtains FRD - Fire Rolldown Door SDC Smoke Detector& Door Holder Combo
CO - Carbon Monoxide Detector - - --
NOTE # COMMENT
See Discrepancy Report
9/9A/9n OcWAPL