• SYSTEM RECORD OF INSPECTION AND TESTING
This form is to be completed by the system inspection and testing contractor at the time of a system test.
It shall be permitted to modify this form as needed to provide a more complete and/or clear record.
Insert N/A In all unused lines.
Attach additional sheets,data, or calculations as necessary to provide a complete record.
Inspection/Test Start Date/Time:7-7-2020 1115 Inspection/Test Completion Date/Time: 7-7-2020 1215
Supplemental Form(s)Attached: (yes/no)
1. PROPERTY INFORMATION
Name ofproperty: Mooretown Rancheria-Gym
Address: 2 Alvera Drive
Description ofproperty:
Name of property representative: Ronald
Address:
Phone:530-680-3163 Fax: E-mail:
2. TESTING AND MONITORING INFORMATION
Testing organization: Eagle Security Systems a vyanet operating group company
Address: 3268 Esplanade; Chico, CA 95973
Phone:530-345-6395 Fax: E-mail:
Monitoring organization: TMS-Total monitoring services
Address:
phone:888-610-4377 Fax: E-mail:
Account number:221-1453 Phone line 1:530-533-4292 Phone line 2: 530-533-4293
Means oftransmission: POTS
Entity to which alarms are retransmitted: Phone:
3. DOCUMENTATION
Onsite location of the required record documents and site-specific software:
4. DESCRIPTION OF SYSTEM OR SERVICE
4.1 Control Unit
Manufacturer:Bosch Model number:7024
4.2 Software Firmware
Firmware revision number:
4.3 System Power
4.3.1 Primary(Main)Power
Nominal voltage: 120 Amps: 20 Location: Electrical Room/A
Overcurrent protection type: Breaker Amps: 20 Disconnecting means location: #26
m 2012 National Fire Protection Association NFPA72(p.1 of 4)
FIGURE 7.8.2(g) System Record of Inspection and Testing.(SIG-TMS)
0 2013 Edition
DOCUMENTATION 72-49
SYSTEM RECORD OF INSPECTION AND TESTING (continued)
4. DESCRIPTION OF SYSTEM OR SERVICE(continued)
4.3.2 Secondary Power
Type:Battery Location: Panel
' Battery type(if applicable): SLA 12v 8AH (2)
i Calculated capacity of batteries to drive the system:
In standby mode(hours): In alarm mode(minutes):
5. NOTIFICATIONS MADE PRIOR TO TESTING
Monitoring organization Contact:TMS-Total monitoring services Time: 1115
Building management Contact:On-Site Time: 1115
Building occupants Contact:On-Site Time: 1115
Authority having jurisdiction Contact: Time:
Other,if required Contact: Time:
6. TESTING RESULTS
6.1 Control Unit and Related Equipment
Visual Functional
Description Inspec 'on Tes Comments
Control unit
Lamps/LEDs/LCDs
Fuses /
Trouble signals y
Disconnect switches ❑ ❑ N/A
Ground-fault monitoring 0 o' N/A
Supervision/ �V
Local annunciator
Remote annunciators
Remote power panels ❑ ❑ N/A
❑ ❑
6.2 Secondary Power
Visual Functional
Description Inspec ion Tes Comments
Battery condition
Load voltage
11 Y1
Discharge test / E
Charger test
Remote panel batteries ❑ ❑ N/A
m 2012 National Fire Protection Association NFPA 72(p.2 of 4)
FIGURE 7.8.2(g) Continued
2013 Edition i;.7
72-50 NATIONALFIREALARM AND SIGNALING CODE
it
SYSTEM RECORD OF INSPECTION AND TESTING (continued)
6. TESTING RESULTS (continued)
6.3 Alarm and Supervisory Alarm Initiating Device
Attach supplementary device test sheets for all initiating devices.
6.4 Notification Appliances
Attach supplementary appliance test sheets for all notification appliances.
6.5 Interface Equipment
Attach supplementary interface component test sheets for all interface components.
Circuit Interface/Signaling Line Circuit Interface/Fire Alarm Control Interface
6.6 Supervising Station Monitoring
Description Ye No Time Comments
Alarm signal 0 1133
Alarm restoration Y 0 1133
Trouble signal )1.1i 0 1123
Trouble restoration 0 1133
Supervisory signal 0 0
I .
Supervisory restoration 0 0
6.7 Public Emergency Alarm Reporting System
Description Yes No Time Comments
Alarm signal 0 • 0
Alarm restoration 0 0
Trouble signal 0 0
Trouble restoration 0 0
Supervisory signal 0 0
Supervisory restoration 0 • 0
C 2012 National Fire Protection Association NFPA 72(p.3 of 4)
FIGURE 7.8.2(g) Continued
W2013 Edition
DOCUMENTATION 72-51
SYSTEM RECORD OF INSPECTION AND TESTING (continued)
7. NOTIFICATIONS THAT TESTING IS COMPLETE
Monitoring organization Contact: TMS-Total monitoring services Time: 1215
Buildingmanagement Contact: On-Site Time: 1215
Buildingoccupants Contact: On-Site Time: 1215
Authority havingjurisdiction Contact: Time: •
i Other,ifrequired Contact: Time:
8. SYSTEM RESTORED TO NORMAL OPERATION
Date:7-7-2020 Time: 1215
9. CERTIFICATION
This system as specified .erein has been inspected and tested according to NFPA 72,2013 edition,Chapter 14.
1 Ale
Signed _.dw'r �"� Printed name: Connor Dalton Date: 7-7-2020
Organization: _ _ Title: Technician Phone: 530-345-6395
Qualifications(refer to 10.5.3): NICET 1-152852
10. DEFECTS OR MALFUNCTIONS NOT CORRECTED AT CONCLUSION OF SYSTEM INSPECTION,
TESTING, OR MAINTENANCE
10.1 Acceptance by Owner or Owner's Representative:
The and ned acceptedo9the t t report for the system as specifiedpherein:rQ
Signed1�/t�M ) Printed name: (L.CN>41[J� a1�� Date: 7-7-2020
Organization:AO0i-CtewiaIl0.r9G YI`title: _"1-- Phone: t7 -9/0$5°-÷
ID 2012 National Fire Protection Association NFPA 72(p.4 of 4)
FIGURE 7.8.2(g) Continued
2013 Edition I gel
72-52 NATIONALFIREALARMANDSIGNALINGCODE
NOTIFICATION APPLIANCE
SUPPLEMENTARY RECORD OF INSPECTION AND TESTING
This form is a supplement to the System Record of Inspection and Testing.
It includes a notification appliance test record. •
This form is to be completed by the system inspection and testing contractor at the time of the inspection and/or test.
It shall be permitted to modify this form as needed to provide a more complete and/or clear record.
Insert N/A in all unused lines.
Inspection/Test Start Date/Time:7-7-2020 1115 Inspection/Test Completion Date/Time:
• 7-7-2020 1215 Number of Supplemental Pages Attached:
1. PROPERTY INFORMATION
Name ofproperty: Mooretown Rancheria-Gym
Address: 2 Alvera Drive, Oroville, CA 95966
2. NOTIFICATION APPLIANCE TEST RESULTS
Appliance Type Location/Identifier Test Results
Bell Riser Exterior Pass
Horn Strobe Lobby
Horn Strobe Gym
Horn Strobe Gym
Horn Strobe Gym
Horn Strobe Gym
Strobe Mens Restroom
Strobe Womens Restroom
C 2012 National Fire Protection Association NFPA 72(p.1 of 2)
FIGURE7.8.2(h)Notif icati on Appliance Supplementary Record of Inspection and Testing.(SIG-TMS)
0 2013 Edition
72-54 NATIONALFI REALARM AND SIGNALING CODE
INITIATING DEVICE
SUPPLEMENTARY RECORD OF INSPECTION AND TESTING
This form is a supplement to the System Record of Inspection and Testing.
It includes an initiating device test record.
This form is to be completed by the system inspection and testing contractor at the time of the inspection and/or test.
It shall be permitted to modify this form as needed to provide a more complete and/or clear record.
Insert N/A in all unused lines.
Inspection/Test Start Date/Time:7-7- 1115 InspectionfTest Completion Date/Time:
7-7-2020 1215 Number of Supplemental Pages Attached:
1. PROPERTY INFORMATION
Name ofproperty: Mooretown Rancheria-Gym
Address: 2 Alvera Drive, Oroville, CA 95966
2. INITIATING DEVICE TEST RESULTS
Device Type AddressLocat on i Test Results
es
SD 1 FACU
WF 3 SW Office Closet ITV 5 Secs-Pass
Pull 4 Lobby
Pull 4 Gym East Wall
Pull 4 Gym Stage North
Pull 4 Gym Stage South
Pull 4 Gym Front
m 2012 National Fire Protection Association NFPA 72(p.1 of 2)
FIGURE7.8.2(i)InitiatingDeviceSupplementaryRecordoflnspectionandTesting.(SIG-TMS)
•
2013 Edition •