HomeMy WebLinkAboutCF Fire Pump Report CSA 183 12_2019 Durham . Pump PUMP CHECK REPORT 2313 Durham-Dayton Hwy. Durham, CA 95938 530.891.4821 CSA#183 - Rare Earth Subdivision CUSTOMER NAME: Butte County Fire Dept. DATE: 12/13/2019 Motor Mfg: Franklin HP: 1.5 Meter#: RPM 3450 Volts 240 Phase 1 Rated Amps: 11.5 MAX TM 80 Yes No Serial# PG &E Acct. # Other: Panel Mfg: NEMA Size: Type: X X/L P/W Other: Pump Mfg: ?Sub Serial#: Non-Running Checks: Pump Model Manufacturer na Lubricant Levels-Service and Change if Necessary Discharge CAST 11/4 na Oiler Unit and/or Packing Electrical Leads & Connections - Repair and Tighten as Necessary Incoming Idle Voltage: W/I Acceptable Limits Unacceptable Fuses - Replace if Necessary Replaced Size: 20 AMP BREAKER Perform General Clean-Up of Electrical Panel and Motor Running Checks: Motor winding resistance: O s to ground Excessive or Unusual Noise Ok/see comments Pressure tank: PC-266 TANK Excessive or Unusual Vibration Ok/see comments Tank condition: (Control Devices: H.O.A. Start Switch Time Clock Frost Start nTime Delay Other: PRESS. SWITCH Amperage: Expected: 11.5 Pressure setting: 40-60 Actual: Y 11.8 B 12.7 R 1.5 Average: 8.667 Overload Underload Even Load Bowl Adiustment: N/A Yes No Comments: Gate broken GPS: The above readings reflect the site and pump conditions at the time of inspection. This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system. S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\183 Rare Earth Subd\183 Reports Durham iik Pump PUMP CHECK REPORT 2313 Durham-Dayton Hwy. Durham, CA 95938 530.891.4821 CSA#183 - Rare Earth Subdivision CUSTOMER NAME: Butte County Fire Dept. DATE: 12/13/2019 Motor Mfg: Franklin HP: 60 Meter#: 1005378640 RPM ? Volts 480 Phase 3 Rated Amps: ? TM 80 Yes No Serial# PG &E Acct. # Other: Panel Mfg: SIEMANS NEMA Size: 3.5 Type: X X/L P/W Other: Pump Mfg: ? Sub Serial#: Non-Running Checks: Pump Model Manufacturer na Lubricant Levels -Service and Change if Necessary Discharge 6" Fab na Oiler Unit and/or Packing Electrical Leads & Connections - Repair and Tighten as Necessary Incoming Idle Voltage: nW/I Acceptable Limits Unacceptable Fuses - Replace if Necessary Replaced Size: FLSR 200 ID Perform General Clean-Up of Electrical Panel and Motor Running Checks: Motor winding resistance: O's to ground Excessive or Unusual Noise Ok/see comments Pressure tank: Excessive or Unusual Vibration Ok/see comments Tank condition: Control Devices: H.O.A. Start Switch Time Clock 1-7 Frost Start (Time Delay Other: Amperage: Expected: 80.5 Pressure setting: Press Sw 50-70 Actual: L1 66.4 L2 65 L3 64.2 Average: 65.2 Overload Underload Even Load Bowl Adiustment: N/A Yes No Comments: Slightly high incoming voltage. 491V,492V, 490V GPS: The above readings reflect the site and pump conditions at the time of inspection. This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system. S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\183 Rare Earth Subd\183 Reports