HomeMy WebLinkAboutCF Fire Pump Report CSA 176 12_2019 Durham ;h . Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#176 - Pheasant Landing Ph. 3
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/13/2019
Motor Mfg: Franklin HP: 1.5 Meter#:
RPM 3450 Volts 460 Phase 3 Rated Amps: 2.5
TM 80 Yes No Serial#
PG &E Acct. # Other:
Panel Mfg: NEMA Size:
Type: X X/L P/W Other:
Pump Mfg: Serial#:
Non-Running Checks: Pump Model Type
na Lubricant Levels - Service and Change if Necessary
na Oiler Unit and/or Packing
Electrical Leads & Connections- Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses- Replace if Necessary Replaced Size: CMR-6
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: O's to ground
Excessive or Unusual Noise Ok/see comments Pressure tank: AP-80
Excessive or Unusual Vibration Ok/see comments Tank condition: ok
Control Devices: H.O.A. Start Switch nTime Clock
nFrost Start nTime Delay Other: PRESS. SWITCH
Amperage: Expected: 2.5 Pressure setting:
Actual: R 2.5 Y 3.2 B 3.2 Average: 2.967
Overload Underload Even Load
Bowl Adjustment: N/A Yes No
Comments:
GPS: 39°48' 49.58"N 121° 47' 40.91"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\176 Pheasant Landing 3\176 Reports
Durham '. Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#176 -Pheasant Landing Ph. 3
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/13/2019
Motor Mfg: Franklin HP: 15 Meter#: 1006782900
RPM Volts 460 Phase 3 Rated Amps: 37.5
TM 80 Yes No Serial#
PG &E Acct. # Other: Pump Date Code: 07/01
Panel Mfg: Myers NEMA Size:
Type: X/L P/W Other:
Pump Mfg: Serial#:
Non-Running Checks: Pump Model Manufacturer
na , Lubricant Levels - Service and Change if Necessary Discharge
na Oiler Unit and/or Packing
Electrical Leads & Connections- Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits nUnacceptable
Fuses - Replace if Necessary Replaced Size: 60 Amp
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: O's to ground
Excessive or Unusual Noise Ok/see comments Pressure tank: Bad
Excessive or Unusual Vibration Ok/see comments Tank condition:
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other:
Amperage: Expected: 37.5 Pressure setting:
Actual: Li 37 L2 34.8 L3 36 Average: 35.93
Overload Underload Even Load
Bowl Adjustment: N/A Yes No
Comments:
Incoming voltage is 490V,492V&490V
Pressure tank is water logged and needs to be replaced, pressure gauge broken
GPS: 39° 48'49.58"N 121° 47'40.91"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\176 Pheasant Landing 3\176 Reports