Loading...
HomeMy WebLinkAboutCF Fire Pump Report CSA 176 12_2019 Durham ;h . Pump PUMP CHECK REPORT 2313 Durham-Dayton Hwy. Durham, CA 95938 530.891.4821 CSA#176 - Pheasant Landing Ph. 3 CUSTOMER NAME: Butte County Fire Dept. DATE: 12/13/2019 Motor Mfg: Franklin HP: 1.5 Meter#: RPM 3450 Volts 460 Phase 3 Rated Amps: 2.5 TM 80 Yes No Serial# PG &E Acct. # Other: Panel Mfg: NEMA Size: Type: X X/L P/W Other: Pump Mfg: Serial#: Non-Running Checks: Pump Model Type na Lubricant Levels - Service and Change if Necessary na Oiler Unit and/or Packing Electrical Leads & Connections- Repair and Tighten as Necessary Incoming Idle Voltage: W/I Acceptable Limits Unacceptable Fuses- Replace if Necessary Replaced Size: CMR-6 Perform General Clean-Up of Electrical Panel and Motor Running Checks: Motor winding resistance: O's to ground Excessive or Unusual Noise Ok/see comments Pressure tank: AP-80 Excessive or Unusual Vibration Ok/see comments Tank condition: ok Control Devices: H.O.A. Start Switch nTime Clock nFrost Start nTime Delay Other: PRESS. SWITCH Amperage: Expected: 2.5 Pressure setting: Actual: R 2.5 Y 3.2 B 3.2 Average: 2.967 Overload Underload Even Load Bowl Adjustment: N/A Yes No Comments: GPS: 39°48' 49.58"N 121° 47' 40.91"W The above readings reflect the site and pump conditions at the time of inspection. This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system. S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\176 Pheasant Landing 3\176 Reports Durham '. Pump PUMP CHECK REPORT 2313 Durham-Dayton Hwy. Durham, CA 95938 530.891.4821 CSA#176 -Pheasant Landing Ph. 3 CUSTOMER NAME: Butte County Fire Dept. DATE: 12/13/2019 Motor Mfg: Franklin HP: 15 Meter#: 1006782900 RPM Volts 460 Phase 3 Rated Amps: 37.5 TM 80 Yes No Serial# PG &E Acct. # Other: Pump Date Code: 07/01 Panel Mfg: Myers NEMA Size: Type: X/L P/W Other: Pump Mfg: Serial#: Non-Running Checks: Pump Model Manufacturer na , Lubricant Levels - Service and Change if Necessary Discharge na Oiler Unit and/or Packing Electrical Leads & Connections- Repair and Tighten as Necessary Incoming Idle Voltage: W/I Acceptable Limits nUnacceptable Fuses - Replace if Necessary Replaced Size: 60 Amp Perform General Clean-Up of Electrical Panel and Motor Running Checks: Motor winding resistance: O's to ground Excessive or Unusual Noise Ok/see comments Pressure tank: Bad Excessive or Unusual Vibration Ok/see comments Tank condition: Control Devices: H.O.A. Start Switch Time Clock Frost Start Time Delay Other: Amperage: Expected: 37.5 Pressure setting: Actual: Li 37 L2 34.8 L3 36 Average: 35.93 Overload Underload Even Load Bowl Adjustment: N/A Yes No Comments: Incoming voltage is 490V,492V&490V Pressure tank is water logged and needs to be replaced, pressure gauge broken GPS: 39° 48'49.58"N 121° 47'40.91"W The above readings reflect the site and pump conditions at the time of inspection. This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system. S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\176 Pheasant Landing 3\176 Reports