HomeMy WebLinkAboutCF Fire Pump Report CSA 169 12_2019 DurhamW. Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#169 Pheasant Landing
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/12/19
Motor Mfg: Newman HP: 40 Meter#: 1005576060
RPM 1770 Volts 460 Phase 3 Rated Amps: 59
TM 80 Yes No Serial# 326TPH/DD27K2PM
PG &E Acct. # Other:
Panel Mfg: Cuttler Hammer NEMA Size: 21/2
Type:n X/L n P/W Other:
Pump Mfg: Peerless 6" Serial#:
Non-Runninq Checks: Pump Model Manufacturer Newman
Lubricant Levels- Service and Change if Necessary
Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/l Acceptable Limits Unacceptable
Fuses - Replace if Necessary Replaced Size: 100A MCP
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance:
Excessive or Unusual Noise Ok/see comments Pressure tank: n/a
Excessive or Unusual Vibration Ok/see comments Tank condition: n/a
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other:
Amperage: Expected: 59 Pressure setting: PRESS SWITCH
Actual: R 47.3 Y 47.7 B 415.3 Average: 170.1
Overload Underload Even Load
Bowl Adjustment: N/A Yes No
Comments:
NO JOCKY PUMP
No Backspin protection, needs to be addressed
Idle voltage is a little high at around 495V. System holding 40 psi pressure.
Gate is broken.
GPS: 39°47'57.43"N 121°53'5.30"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\169 Pheasant Landing\169 Reports