HomeMy WebLinkAboutCF Fire Pump Report CSA 158 12_2019 Durham : Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#158 Ishi Valley
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/12/19
Motor Mfg: Franklin HP: 25 Meter#: 1006908237
RPM 3450 Volts 240 Phase 3 Rated Amps: 75
TM 80 Yes No Serial#
PG &E Acct. # Other:
Panel Mfg: Furnas NEMA Size: 3
Type: X/L P/W Other:
Discharge Mfg: Steel 6" Serial#:
Non-Running Checks: Pump Model Manufacturer
na Lubricant Levels -Service and Change if Necessary
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses- Replace if Necessary Replaced Size: TR9OR
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance:
Excessive or Unusual Noise Ok
Excessive or Unusual Vibration Ok
Control Devices: X H.O.A. X Start Switch (Time Clock
Frost Start Time Delay Other: Pressure Switch
Amperage: Expected: 65
Actual: L1: 68 L2: 75.1 L3: 61.2 Average: 68.1
Overload Underload Even Load
Bowl Adjustment: N/A Yes No
Comments:
Slightly overloaded with uneven load but within service factor
Gate is falling apart, needs to be repaired or replaced.
GPS: 39°48'32.57"N 121°53'38.30"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.
S:\Pump Dept. Files\PUMP TESTS&INSPECTIONS\Cal Fire CSA's\158 Ishi Valley\158 Reports
Durham; '. Pump PUMP CHECK REPORT
2313 Durham-Dayton Hwy.
Durham, CA 95938 530.891.4821 CSA#158 Ishi Valley
CUSTOMER NAME: Butte County Fire Dept. DATE: 12/12/19
Motor Mfg: Franklin HP: 1 Meter#: 1006908237
RPM 3450 Volts 240 Phase 1 Rated Amps: 9.8
TM 80 Yes No Serial#
PG &E Acct. # Other:
Panel Mfg: Franklin control box NEMA Size:
Type: X/L P/W Date code
Discharge Mfg: 1 1/4 Serial#:
Non-Running Checks: Tank Model WX-302 Manufacturer Well-X-Trol
na Lubricant Levels - Service and Change if Necessary
na Oiler Unit and/or Packing
Electrical Leads & Connections - Repair and Tighten as Necessary
Incoming Idle Voltage: W/I Acceptable Limits Unacceptable
Fuses- Replace if Necessary Replaced Size: N/A
Perform General Clean-Up of Electrical Panel and Motor
Running Checks: Motor winding resistance: Less than 1 Meg O's to ground
Excessive or Unusual Noise Ok
Excessive or Unusual Vibration Ok
Control Devices: H.O.A. Start Switch Time Clock
Frost Start Time Delay Other: Pres. Sw. 30-50
Amperage: Expected:
Actual: Red: 0.8 Yellow: 11.6 Black: 10.3 Average: 7.567
Overload Underload Even Load
Bowl Adiustment: N/A Yes No
Comments:
GPS: 39°48'32.57"N 121°53'38.30"W
The above readings reflect the site and pump conditions at the time of inspection.
This report does not guarantee the continuation of these conditions, nor warranty any part of the existing system.