HomeMy WebLinkAboutCSA 128 CF Fire Well and Pump Testing 2019 6301 Bearden Lane
Power Services Inc. Modesto, CA 95357
209.527.2908/800.808.9283
209.527.2921 fax
www.powerhydrodynamics.com
Monday, August 5, 2019
Dave Woods
Hereford Sub Division
20 Red Fox Ct.
Chico, CA 95973
Dear Dave Woods:
Enclosed are the results of your pump test. The results are based on conditions during
the time of the test. If these conditions vary from the normal operation of your pump, the
results shown may not describe the pump's normal performance.
Some of the factors, which influence pump performance, are:
- Changes in discharge pressures
- Changes in water table level and well yield
- Pump wear
- Proper pump design for application
We offer the following services to help our customers save time and money. Pump
testing, irrigation system analysis, irrigation water management, and electric rate
management. Visit our website at www.powerhydrodynamics.com for more information or
to use our water cost calculator.
Please feel free to call 209-527-2908 if you have questions about this test or on the other
services that Power Services has to offer.
Regards,
William Thomas Power, Ill
Enclosures
6301 Bearden Lane
Power Services Inc. Modesto, CA 95357
209.527.2908/800.808.9283
209.527.2921 fax
www.powerhydrodynamics.com
CONFIDENTIAL/PROPRIETARY INFORMATION
Dave Woods Monday, August 5, 2019
Hereford Sub Division
20 Red Fox Ct.
Chico, CA 95973
SUBJECT: PUMPING COST ANALYSIS
HP: 20.00 Plant: Hereford Fire Pump
PUMP TEST REFERENCE NUMBER: PT-23095
PUMP TEST RUN: Run 1 Nearest Hydrant
The following Pumping Cost Analysis is presented as an aid to your cost accounting. This analysis is an
estimate prepared from operating criteria supplied from the pump test performed Jul 31st 2019 and
information provided by you during the pump test.
It is recommended and assumed that:
1. Overall plant efficiency can be improved to: 60%
2. Water requirements will be the same as for the past year.
3. All operating conditions (annual hours of operation, discharge head, and water
pumping level)will remain the same as they were at the time of the pump test.
EXISTING PLANT IMPROVED PLANT SAVINGS
EFFICIENCY EFFICIENCY
kWh/AF 263.7 216.9 46.8
Estimated Total kWh 23,791 19,570 4,221
Average Cost per kWh $0.24 $0.24
Average Cost per hour $5.66 $4.76 $0.9
Cost Per Acre Ft. $62.72 $51.59 $11.13
Estimated Acre Ft. Per Year 90.23 90.23
Run Hours 1,000.00 1,000.00
Overall Plant Efficiency 49.4% 60%
Estimated Total Annual Cost $5,658.85 $4,654.89 $1,003.96
It is sincerely hoped that this information will prove helpful to you, and that your concerns over maintaining
optimum pumping efficiency will be continued.
If you have any questions, please contact Bill Power at(209) 527-2908.
Regards,
William Thomas Power, III
Enclosures
6301 Bearden Lane
Power Services Inc. Modesto, CA 95357
209.527.2908/800.808.9283
209.527.2921 fax
Report ID: PT-23095 www.powerhydrodynamics.com
Agricultural and Domestic Pump Test Report
Hereford Sub Division - Hereford Fire Pump - Run 1 Nearest Hydrant
Latitude: 39.81323W Longitude: -121.90109N Elevation: 190 ft
Test Date: Jul 31st 2019 Tester: Bill Power Nameplate HP: 20.00 hp
Customer Information Power Company Data Equipment Data
Hereford Sub Division PG&E Motor Make: Franklin
20 Red Fox Ct. Meter#: 1006873268 Volts/Amps: 460V/26.9A
Chico, CA 95973 Rate Schedule: Al Serial#:
Average Cost: $0.24 Pump Make: No Name Plate
Contact: Dave Woods Pump Type: Submersible
Cell: 530-230-7825
Drive Type: Electric Motor
Gearhead Make:
Hydraulic Data Flow Data
Standing Water Level (SWL): 51.50 ft Run Number: 1 of 2
Recovered Water Level (RWL): 52.00 ft Measured Flow: 490 gpm
Pumping Water Level (PWL): 81.00 ft Customer Flow: 0 gpm
Drawdown: 29.5 ft Flow Velocity: 4.52 ft/sec
Discharge Pressure: 20.00 lb/sqft Acre Feet per 24 Hr: 2.17
Discharge Level: 46.2 ft Cubic Feet Per Second (CFS): 1.09 ft
Total Lift: 127.2 ft Discharge Pressure: 20 psi
Well Yield: 16.61 gpm/ft
Water Source: Well
Power Data
Horsepower Input to Motor: 31.89 hp Percent of Rated Motor Load: 131%
Brake Horsepower: 26.15 hp Kilowatt Hours per Acre Foot: 263.68
Kilowatt Input to Motor: 23.79 kW Cost to Pump an Acre Foot: $62.72
Energy Cost: $5.66/hr Overall Plant Efficiency: 49.36%
Name Plate RPM: 3450 rpm Water Horsepower: 15.74 hp
Run Hours: 1000
Remarks
All results are based on conditions during the time of the test. If these conditions vary from the normal operation of
your pump,the results shown may not describe the pump's normal performance.
Motor loading may be excessive. Suggest contacting your pump serviceman.
Overall efficiency of this plant is considered to be fair assuming this run represents plant's normal operating condition.
Recovered water level based on 5 minutes recovery,well could still be recovering.
Pump started for test, pumping water level could still be drawing down.
This pump has an adequate test section.
This pump did not have a flow meter.
HPI measured with direct read KWI.
Cost Analysis page is based on 1000 run time hours.Your savings may differ based on pumps actual usage.
6301 Bearden Lane
Power Services Inc. Modesto, CA 95357
209.527.2908/800.808.9283
209.527.2921 fax
www.powerhydrodynamics.com
CONFIDENTIAL/PROPRIETARY INFORMATION
Dave Woods Monday, August 5, 2019
Hereford Sub Division
20 Red Fox Ct.
Chico, CA 95973
SUBJECT: PUMPING COST ANALYSIS
HP: 20.00 Plant: Hereford Fire Pump
PUMP TEST REFERENCE NUMBER: PT-23095
PUMP TEST RUN: Run 2 Farthest Hydrant
The following Pumping Cost Analysis is presented as an aid to your cost accounting. This analysis is an
estimate prepared from operating criteria supplied from the pump test performed Jul 31st 2019 and
information provided by you during the pump test.
It is recommended and assumed that:
1. Overall plant efficiency can be improved to: 60%
2. Water requirements will be the same as for the past year.
3. All operating conditions (annual hours of operation, discharge head, and water
pumping level)will remain the same as they were at the time of the pump test.
EXISTING PLANT IMPROVED PLANT SAVINGS
EFFICIENCY EFFICIENCY
kWh/AF 298.2 228.4 69.9
Estimated Total kWh 22,901 17,537 5,364
Average Cost per kWh $0.24 $0.24
Average Cost per hour $5.45 $4.76 $0.69
Cost Per Acre Ft. $70.94 $54.33 $16.62
Estimated Acre Ft. Per Year 76.78 76.78
Run Hours 1,000.00 1,000.00
Overall Plant Efficiency 45.9% 60%
Estimated Total Annual Cost $5,447.14 $4,171.31 $1,275.84
It is sincerely hoped that this information will prove helpful to you, and that your concerns over maintaining
optimum pumping efficiency will be continued.
If you have any questions, please contact Bill Power at(209) 527-2908.
Regards,
William Thomas Power, III
Enclosures
6301 Bearden Lane
Power Services Inc. Modesto, CA 95357
209.527.2908/800.808.9283
209.527.2921 fax
Report ID: PT-23095 www.powerhydrodynamics.com
Agricultural and Domestic Pump Test Report
Hereford Sub Division - Hereford Fire Pump - Run 2 Farthest Hydrant
Latitude: 39.81323W Longitude: -121.90109N Elevation: 190 ft
Test Date: Jul 31st 2019 Tester: Bill Power Nameplate HP: 20.00 hp
Customer Information Power Company Data Equipment Data
Hereford Sub Division PG&E Motor Make: Franklin
20 Red Fox Ct. Meter#: 1006873268 Volts/Amps: 460V/26.9A
Chico, CA 95973 Rate Schedule: Al Serial#:
Average Cost: $0.24 Pump Make: No Name Plate
Contact: Dave Woods Pump Type: Submersible
Cell: 530-230-7825
Drive Type: Electric Motor
Gearhead Make:
Hydraulic Data Flow Data
Standing Water Level (SWL): 51.50 ft Run Number: 2 of 2
Recovered Water Level (RWL): 52.00 ft Measured Flow: 417 gpm
Pumping Water Level (PWL): 78.50 ft Customer Flow: 0 gpm
Drawdown: 27 ft Flow Velocity: 3.85 ft/sec
Discharge Pressure: 24.00 lb/sqft Acre Feet per 24 Hr: 1.85
Discharge Level: 55.44 ft Cubic Feet Per Second (CFS): 0.93 ft
Total Lift: 133.94 ft Discharge Pressure: 24 psi
Well Yield: 15.44 gpm/ft
Water Source: Well
Power Data
Horsepower Input to Motor: 30.7 hp Percent of Rated Motor Load: 126%
Brake Horsepower: 25.17 hp Kilowatt Hours per Acre Foot: 298.25
Kilowatt Input to Motor: 22.9 kW Cost to Pump an Acre Foot: $70.94
Energy Cost: $5.45/hr Overall Plant Efficiency: 45.95%
Name Plate RPM: 3450 rpm Water Horsepower: 14.1 hp
Run Hours: 1000
Remarks
All results are based on conditions during the time of the test. If these conditions vary from the normal operation of
your pump,the results shown may not describe the pump's normal performance.
Motor loading may be excessive. Suggest contacting your pump serviceman.
Overall efficiency of this plant is considered to be low assuming this run represents plant's normal operating condition.
Recovered water level based on 5 minutes recovery,well could still be recovering.
Pump started for test, pumping water level could still be drawing down.
This pump has an adequate test section.
This pump did not have a flow meter.
HPI measured with direct read KWI.
Cost Analysis page is based on 1000 run time hours.Your savings may differ based on pumps actual usage.
6301 Bearden Lane
Power Services Inc. Modesto, CA 95357
209.527.2908/800.808.9283
209.527.2921 fax
www.powerhydrodynamics.com
DAVE WOODS
HEREFORD SUB DIVISION
20 RED FOX CT.
CHICO, CA 95973
Pump Name: HEREFORD FIRE PUMP Pump Location:
Latitude: 39.81323W Longitude: -121.90109N Elevation: 190 ft
HYDRAULIC TEST RESULTS PT-23095 Test Date: Jul 31st 2019
Tester: Bill Power Utility: PG&E Meter kh: 21.60
Meter#: 1006873268 Rate Sched: Al Meter Const: 1
Annual Run Hrs: 1000 Avg Cost kWh: $0.23786
Equipment
Motor Make: Franklin Serial:
Volts: 460 Amps: 26.9 Horsepower: 20.00
Gearhead Make: NameplateRPM: 3450 Drive Type: Electric Motor
Pump Make: No Name Plate Pump Type: Submersible
Water Source: Well
Results Test 1 Test 2
Discharge Pressure, PSI 20.00 24.00
Standing Water Level, Feet 51.50 51.50
Drawdown, Feet 29.5 27
Discharge Head, Feet 46.2 55.44
Pumping Water Level, Feet 81.00 78.50
Total Measured Head, Feet 127.2 133.94
Measured GPM 490.00 417.00
Well Yield, GPM/ft Drawdown 16.6 15.4
Acre Feet Pumped in 24 Hours 2.168 1.845
kW Input to Motor 23.79 22.9
HP Input to Motor 31.89 30.697
Motor Load % 130.7 125.9
kWh per Acre Foot 264 298
Overall Plant Efficiency (%) 49.4 45.9
Energy Cost per Hour 5.66 5.45
Water Horsepower, hp 15.74 14.1
Flow Velocity, ft/sec 4.52 3.85
6301 Bearden Lane
Power Services, Inc. Modesto, CA 95357
209.527.2908
Fax 209.527.2921
800.808.9283
August 5, 2019
Hereford Sub Division
Dave Woods
20 Red Fox Ct.
Chico, CA 95973
This letter is to confirm the information we gathered during the Pump Test that was performed
on July 31, 2019 for the Fire Hydrants located on Red Fox Ct. in Chico, CA.
On this day we measured a sustained flow of 490 GPM at 20 PSI for 60 minutes on the
nearest hydrant and a flow of 417 GPM at 24 PSI for 30 minutes on the farthest hydrant.
We used equipment that is accurate +/- .02% for flow measurement and +/- .005% for
pressure measurement. The methodology used to test this pump was that of the California
Association of Pump Test Professionals and is recognized to be accurate by the U.S.
Department of Energy, the Hydraulic Institute, the California Energy Commission, Pacific Gas
and Electric, Southern California Edison and the California Public Utilities Commission.
This information should fulfill the requirements imposed upon you by the inspecting Fire
District. Should the Fire Marshall from your District have further questions, please have them
contact me directly in my office (209) 527-2908 or (800) 808-9283.
Regards,
\--.).'iP-- ---EZ,-\_,si. ai----}t-,--
William Thomas Power III
Power Services, Inc. for
Hereford Sub Division
Pra��er Services, Inc_ Flow Tests
July 31 , 2019
Test Location Run Measured
Red Fox Ct. Chico # GPM
Nearest Hydrant 1 490
Farthest Hydrant 2 417
Test conducted by: Bill Power
The flow test was performed on 7/31/19